HomeMy WebLinkAboutSB989 2013SWRCB, January 2002 Page __ of __ Secondary Containment Testing Report Form This form is intended for use by contractors pe1jorming periodic testing of UST secondary containment systems. Use the appropriate pages of this form to report results for all components tested. The completedform, written test procedures, and printouts from tests (if applicable), should be provided to the facility owner/operator for submittal to the local regulat01y agency. 1. FACILITY INFORMATION Facility Name: Metro Mart I Date ofTesting: 8/30/13 Facility Address: 4600 Stine Rd. Bakersfield, Ca. 93312 Facility Contact: Mike I Phone: 661-83 1-0836 Date Local Agency Was Notified ofTesting: 8/27113 Name of Local Agency Inspector (if present during testing): N/A 2. TESTING CONTRACTOR INFORMATION Company Name: Confidence UST Services Technician Conducting Test: Frank Landa Credentials: x CSLB Licensed Contractor o SWRCB Licensed Tank Tester License Type: CSLB I License Number:804904 ICC# 8180171/8018524 Manufacturer Training Manufacturer Component(s) Date Training Expires UST 11122/2013 lnstallaton/Retrofit UST Service ICC 1-28-2015 technician Star. Smith. Fibercast Fiber Glass Systems N.A. 3. SUMMARY OF TEST RESULTS t-Not Repairs 1 Not Repairs Component Pass Fail Component Pass Fail Tested Made Tested Made DSL Annular X [] , UDC# 1-2 X u 0 l 87# 1 Annular X ~ n n UDC # 3-4 X u "' 87#2 Annular X [J [) 0 UDC #5-6 X 0 0 0 91 Annular X 0 n UDC# 7-8 X 0 0 0 DSL Secondary X 0 n X UDC # 9-10 X 0 0 0 87# 1 Secondary X 0 n 0 DSL Fill Bucket X [) [J 0 87#2 Secondary X 0 n X 87 #1 Fill Bucket X n n 0 91 Secondary X 0 0 0 87 # 1 Vapor Bucket X 1 0 0 DSL STP 0 X 0 0 87 # 2 Fill Bucket X 0 0 0 87#1 STP X n ~ 0 87 # 2 Vapor Bucket X 0 0 :::J ..... 87#2 STP X n 0 0 91 Fill Bucket X 0 0 0 91 STP X .J2_ n ~ 91 Vapor Bucket X 0 0 0 _, If hydrostatic testing was performed, describe what was done with the water after completion of tests: Water was gut back into test trailer and waste drum RESPONSIBLE FOR CONDUCTING THIS TESTING To the best of my knowled~:=nent are accurate and in full compliance with legal requirements Technician's Signature: ._.. Date: 8/30/13 SWRCB, January 2002 Page __ of __ 4. TANK ANNULAR TESTING Test Method Developed By: D Tank Manufacturer x Industry Standard D Professional Engineer D Other (Specify) Test Method Used: D Pressure x Vacuum D Hydrostatic D Other (Specify) Test Equipment Used: Calibrated Gages Equipment Resolution:0.0625" Tank #DSL Tank #87#1 Tank#87#2 Tank #91 Is Tank Exempt From Testing?1 DYes X No DYes X No DYes X No DYes X No Tank Capacity: Unknown Unknown Unknown Unknown Tank Material: Steel Steel Steel Steel Tank Manufacturer: Unknown Unknown Unknown Unknown Product Stored: DSL Regular Regular Premium Wait time between applying pressure/vacuum/water and 5 Min. 5 Min. 5 Min. 5Min. starting test: Test Start Time: 8:30am 8:30am 8:30am 8:30am Initial Reading (R1): IOHG IOHG IOHG IOHG Test End Time: 9:30am 9:30am 9:30am 9:30am Final Reading (Rr): IOHG IOHG IOHG 10 HG Test Duration: I Hour I Hour I Hour I Hour Change in Reading (RF-Rr): 0.00" 0.00" 0.00" 0.00" Pass/Fail Threshold or Criteria: 0.00" 0.00" 0.00" 0.00" Test Result: X Pass DFail X Pass 0 Fail X Pass DFail X Pass DFail Was sensor removed for testing? DYes DNo DNA DYes DNo DNA DYes DNo DNA DYes DNo DNA Was sensor properly replaced and DYes DNo DNA DYes DNo DNA DYes DNo DNA DYes DNo DNA verified functional after testing? Comments -(include information on repairs made prior to testing, and recommended.follow-upfor.failed tests) 1 Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary containment, such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment testing. {California Code of Regulations, Title 23, Section 2637(a)(6)} ! i SWRCB, January 2002 Page_ of_ 5. SECONDARY PIPE TESTING Test Method Developed By: 0 Piping Manufacturer x Industry Standard 0 Professional Engineer 0 Other (SpecifY) Test Method Used: x Pressure 0 Vacuum 0 Hydrostatic 0 Other (.SpecifY) Test Equipment Used: Calibrated Gages Equipment Resolution:0.0625" Piping Run # DSL Piping Run# 87 #1 Piping Run #87 #2 Piping Run #91 Piping Material: Fiberglass Fiberglass Fiberglass Fiberglass Piping Manufacturer: Smith Smith Smith Smith Piping Diameter: 3" 3" 3" 3" Length of Piping Run: 80' 100' 100' 100' Product Stored: DSL Regular Regular Premium Method and location of Boot in STP Boot in STP Boot in STP Boot in STP piping-mn isolation: Wait time between applying pressure/vacuum/water and 5 Min. 5 Min. 5 Min. 5 Min. starting test: Test Start Time: 9:00am 9:00am 9:00am 9:00am Initial Reading (R1): 5 PSI 5 PSI 5 PSI 5 PSI Test End Time: 10:00 am 10:00 am IO:OO am 10:00 am Final Reading (RF): 5 PSI 5 PSI 5 PSI 5 PSI Test Duration: I Hour I Hour I Hour I Hour Change in Reading (RF-R1): 0.00" 0.00" 0.00" 0.00" Pass/Fail Threshold or 0.00" 0.00" 0.00" 0.00" Criteria: Test Result: X Pass 0 Fail X Pass 0 Fail X Pass OFail X Pass 0 Fail Comments -(include information on repairs made prior to testing, and recommended.follow-up .for.failed tests) Replaced (1) 3.5x 2.4 a test boot in DSL STP, and in 87#2 STP SWRCB, January 2002 Page __ of_ 6. PIPING SUMP TESTING Test Method Developed By: D Sump Manufacturer x Industry Standard D Professional Engineer D Other (Spec[fy) Test Method Used: D Pressure D Vacuum x Hydrostatic D Other (SpecifY) Test Equipment Used: Ts-sts Equipment Resolution: Sump #DSL Sump #87 #I Sump #87#2 Sump #91 Sump Diameter: 40" 36" 36" 36" Sump Depth: 60" 60" 60" 60" Sump Material: Fiberglass Fiberglass Fiberglass Fiberglass Height from Tank Top to Top of 18" Highest Piping Penetration: 16" 16" 16" Height from Tank Top to Lowest 24" Electrical Penetration: 20" 20" 20" Condition of sump prior to testing: Clean Clean Clean Clean Portion of Sump Tested 1 20" 18" 18" 18" Does turbine shut down when sump sensor detects liquid (both DYes DNo XNA DYes DNoXNA DYes DNoXNA DYes DNo XNA product and water)?• Turbine shutdown response time NA NA NA NA Is system programmed for fail-safe shutdown?· DYes DNo XNA DYes DNoXNA DYes DNoXNA DYes DNo XNA Was fail-safe verified to be DYes DNo XNA DYes DNoX NA DYes DNoXNA DYes ONo XNA operational?• Wait time between applying pressure/vacuum/water and starting SMin. 5 Min. SMin. SMin. test: Test Start Time: Initial Reading (R1): ~--...... '"""II. I Test End Time: ~ee1N l,;ON "'~~Trtl -,VI~ -Final Reading (RF): Resl Jlts -r<esu tS Test Duration: Change in Reading (RF-R!): Pass/Fail Threshold or Criteria: Test Result: D Pass X Fail X Pass D Fail X Pass DFail X Pass DFail Was sensor removed for testing? X Yes DNo DNA X Yes DNo DNA X Yes DNo DNA X Yes DNo DNA Was sensor properly replaced and X Yes DNo DNA X Yes DNo DNA XYes DNo DNA X Yes DNo DNA verified functional after testing? Comments -(include information on repairs made prior to testing, and recommended.follow-up.for.failed tests) DSL STP fails. possible problem with tank_c_Ql_l_ar 1 If the entire depth of the sump is not tested, specify how much was tested. If the answer to~ of the questions indicated with an asterisk(*) is "NO" or "NA", the entire sump must be tested. (See SWRCB LG-160) I SWRCB, January 2002 Page __ of __ '· \,Jl,..I.J.L:J.I..'--.L'.I..U.I...&;J..l"V~•' '-'...._,.L.,...._.L-.........._,. ... ,. • ...,.~,.,...._ ,.....,...,._ .a ~- Test Method Developed By: D UDC Manufacturer x Industry Standard D Professional Engineer D Other (SpecifY) Test Method Used: D Pressure D Vacuum x Hydrostatic D Other (SpecifY) Test Equipment Used: Ts-sts Equipment Resolution: UDC # 1-2 UDC # 3-4 UDC#S-6 UDC # 7-8 UDC Manufacturer: Bravo Bravo Bravo Bravo UDC Material: Fiberglass Fiberglass Fiberglass Fiberglass UDC Depth: 37" 37" 37" 37" Height from UDC Bottom to Top 18" 18" 18" 18" of Highest Piping Penetration: Height from UDC Bottom to 0" 0" 0" 0" Lowest Electrical Penetration: Condition ofUDC prior to Clean Clean Clean Clean testing: Portion of UDC Tested 20" 20" 20" 20 Does turbine shut down when UDC sensor detects liquid (both product and water)?* DYes DNo X NA DYes DNoXNA DYes DNo XNA DYes DNo XNA Turbine shutdown response time NA NA NA NA Is system programmed for fail- safe shutdown?* DYes DNo XNA DYes DNoX NA DYes DNo XNA DYes DNo XNA Was fail-safe verified to be DYes DNo XNA DYes DNoXNA DYes DNo XNA DYes DNo XNA operational?• Wait time between applying 5 Min 5 Min 5 Min. 5 Min. pressure/vacuum/water and starting test """ -.... --•• -Test Stmt Time: ~ """" I ~I lr'r"\t\1 -.;;;Jt:t: •• , vUf~ Initial Reading (R1): -~""' II~ 1-'-'· .. R~c:.r •ltc:: Test End Time: KeSl lltS -- Final Reading (RF): Test Duration: Change in Reading (RF-R1): Pass/Fail Threshold or Criteria: Test Result: X Pass DFail X Pass OFail X Pass D Fail X Pass D Fail I Was sensor removed for testing? X Yes DNo DNA X Yes DNo DNA XYes DNo DNA X Yes DNo DNA I Was sensor properly replaced and XYes DNo DNA X Yes DNo DNA X Yes DNo DNA X Yes DNo DNA I verified functional after testing? Comments -(include information on repairs made prior to testing, and recommended.follow-upforfailed tests) 1 If the entire depth of the UDC is not tested, specify how much was tested. If the answer to~ of the questions indicated with an asterisk(*) is "NO" or "NA", the entire UDC must be tested. (See SWRCB LG-160) SWRCB, January 2002 Page __ of __ '· Ul"'UIJI'.-UIOI ..1!.11..,0.1!11.'-'-'-'l" .. '"'~ .,J.T.A...&:./.1, • ....,..., '-' A.AJ ..... ••~,- Test Method Developed By: J UDC Manufacturer x Industry Standard 'l Professional Engineer Other (Specify) Test Method Used: Pressure D Vacuum x llydrostatic Other (Specify) Test Equipment Used: Ts-sts Equipment Resolution: UDC # 9-10 UOC# UDC# UDC# UDC Manufacturer: Bravo UDC Material: Fiberglass UDC Depth: 37'' Height from UDC Bottom to Top 18" of Highest Piping Penetration: Height from UDC Bottom to 0" Lowest Electrical Penetration: Condition of UDC prior to Clean testing: Portion of UDC Tested 20" Does turbine shut down when UDC sensor detects liquid (both product and water)?• n Yes DNo XNA DYes DNo NA DYes ONo Dl\:A []Yes D No DNA Turbine shutdown response time NA Is system programmed for fail- safe shutdown?· • Yes No XNA C.. Yes uNo NA DYes LJNo DNA DYes nNo [ NA Was fail-safe verified to be ..... Yes No X NA ._,Yes :J No NA DYes "No NA [.,Yes L'No rNA operational?• Wait time between applying 5 Min pressure/vacuum/water and starting test Test Start Time: ~--I ·'"" ... Initial Reading (R1): """" I 'lv\JI~ Test End Time: RP-~ ultc:: Final Reading (RF): Test Duration: Change in Reading (RF-R1): Pass/Fail Threshold or Criteria: Test Result: X Pass D Fail D Pass DFail D Pass D Fail D Pass D Fail Was sensor removed for testing? X Yes No DNA Yes DNo DNA DYes ONo r'JNA [)Yes CJNo DNA Was sensor properly replaced and X Yes 0 No DNA Yes DNo DNA DYes DNo nNA 0 Yes nNo DNA verified functional after testing? !.... Comments-(include information on repairs made prior to testing, and recommended.follow-up[or.fai/ed test~) 1 If the entire depth of the UDC is not tested, specify how much was tested. If the answer to .!illY of the questions indicated with an asterisk(*) is "NO" or "NA'', the entire UDC must be tested. (See SWRCB LG-160) SWRCB, January 2002 Page_ of_ 9. SPILL/OVERFILL CONTAINMENT BOXES Facility is Not Equipped With Spill/Overfill Containment Boxes 0 Spill/Overfill Containment Boxes are Present, but were Not Tested 0 Test Method Developed By: 0 Spill Bucket Manufacturer x Industry Standard 0 Professional Engineer 0 Other (Specify) Test Method Used: 0 Pressure OVacuum x Hydrostatic 0 Other (SpecifY) Test Equipment Used: Ts-sts Equipment Resolution: Spill Box # DSL Fill Spill Box# 87 #1 Fill Spill Box # 87 #1 Spill Box # 87 #2 Fill i Vapor Bucket Diameter: 12" 12" 12" 12" Bucket Depth: 13" 13" 13" 13" Wait time between applying pressure/vacuum/water and 5 Min 5 Min 5 Min 5 Min starting test: Test Start Time: Initial Reading (R1): Test End Time: SP-P-INC ~ON ::>ee lNl ~ON Final Reading (Rr): Do~•• If~ Re~u It~ I Test Duration: --·-'"'""' ' ' Change in Reading (Rr-R1): Pass/Fail Threshold or Criteria: Test Result: X Pass 0 Fail X Pass 0 Fail X Pass OFail X Pass OFail Comments -(include information on repairs made prior to testing, and recommendedfollow-up.for failed tests) Installed new fill ca]2S_Qn_a1Lbuckets. SWRCB, January 2002 Page_ of_ 9. SPILL/OVERFILL CONTAINMENT BOXES Facility is Not Equipped With Spill/Overfill Containment Boxes 0 Spill/Overfill Containment Boxes are Present, but were Not Tested 0 Test Method Developed By: 0 Spill Bucket Manufacturer x Industry Standard 0 Professional Engineer 0 Other (SpecifY) Test Method Used: 0 Pressure 0 Vacuum x Hydrostatic 0 Other (SpecifY) Test Equipment Used: Ts-sts Equipment Resolution: Spill Box # 87#2 Spill Box #91 Fill Spill Box #91 Vapor Spill Box# Vapor Bucket Diameter: 12" 12" 12" Bucket Depth: 13" 13" 13" Wait time between applying pressure/vacuum/water and 5 Min. 5 Min. 5 Min. starting test: Test Start Time: Initial Reading (R1): ~--INrnt..• I Test End Time: -·-... D~""· .14.- Final Reading (RF): 1'-C~UIL~ I I I Test Duration: Change in Reading (RF-R1): Pass/Fail Threshold or Criteria: Test Result: X Pass OFail X Pass 0 Fail X Pass OFail 0 Pass OFail Comments -(include information on repairs made prior to testing, and recommended.follow-up.forfailed tests) ~f\D~+. ()0 ('~ \UST; \l' +· ~'~tuc"f\0 "SUlLO WITH CONFIDENCE" Lic.970703 ~fiDE"+, ()0 ~ ~USTcl "'I,CES•~ "COMPLIANCE WITH CONFIDENCE" Lie. 804904 Toll Free #: 1-800-339-9930 Job Order /Invoice #: 3\3l/ I ~p~e1f3 lime I To Whom I ~;;;;jb l Site Name: \'J\,Q.-~ S §4\/\ ld\.. J Name: Confidence UST Street: L.U,Q_ 00 _ -$ k N__ e.G_ Ll City: \3 ~ ~f',-t\C/state: (Af.} Zip: 'f3:?{)tC( Street: 16250 Meacham Road City: Bakersfield, CA 93314 Terms: Store No: ...... / Description of work performed: k.S f'.' {)$._ ~{S C-:j ~ 1' ""'-~ I+ !IJ J4f\ILCL lcrvs-Pc...-5S {t..f\ A. t ( .<\or /)/1 dut "--Pt..s5 €1!L ~\( tlir s~A,~ ~ ....,.. --"' -f;:k Q441.,s il.A..c,.VL \1\.t\ ~o( f< lxxJ.it'tLJ a~ $"5 {j_]_ -D" -"""-9> 11£1 ~ 7'* z CHil-d 9J s .w -o~ s-s -~&·&"5 /VLO ,tl~ ,.... (') ~, ....... '\)<;L S±I:L F4r\s-Re~~&s 7\Jeeoed TRAVEL and LABOR Start OTTotal Travel ;c;() Labor Travel Date I Technician(s) Name I I Start t End I Total I I OT Start I OTEnd I OTTotal Travel --Labor --Travel Date I Technician(s) Name I . I Start I End I Total I l OT Start I OTEnd I OTTotal Travel -- Labor --Travel SUPPLIES -MATERIALS-RENTALS Check One USTPa~ Site Parts COMMENTS Store Employee Print Name: TeChnician Print Name: Date I TeChnician Signature: Date SITE -CANARY ,, It r• 91FILL ii:ST STA:mo 9:51 Al1 TEST STARiEO Ce/30/2013 6EG Ill LEVEL 3.11986 l'l EtlD r:HE 10:07 AM EI.O DAiE 08/30/2013 Et.O LEVEL 3. 4975 :u .. E ~I\ ThRESH~L) 0. 002 itl TEST RESLl T PASSEO 87WILL \9\ TEST S1 ARiEO ~:51 AH TF.Sl STA~TEQ 03/30/2013 BE1J1'I LEVEL 3. 106? IN END T:HE 10:07 •V1 E';J OATE 08/30/20'3 Er.:: LEVEL 3. 10E~ ltl LEAK T~RESHOLD C.002 IN TEST RESULT PASSED DSLSTP lEST SiP~TEO 9:)1 ~~ TESi STARTED 08/30/2013 !:EGW LEVEL 1, !3120 ltl p,; Tltl 10:07 PH [113 DATE Oc/30/2013 EID LEVEL 1. 9083 PI LEAk THRESHDLQ 0, C02 Ill TEST RESUL-FAILED 91FILL ~ TESI STARTED 10:11 4H ~ -~sT ST~~TE~ Ob/30/2013 BEGltl LEVEL 3,11977 HI E~ID TIME 10:26 1\!1 EtD OATE 08/30/2013 EtD LEVEL 3,11975 IN LEAK -HRESH(lD 0, 002 HI -Es,. fiESlLT i>I\SSEO 9 i'JI\P TEST STARTED 11:22 AH TEST STARTED 08/30/2013 BFGlN LEVEL 6. 6110 lU Etll 7IHE 11:37 A"' END GATE 08/30/2013 E~D LE1JEL 6. 5109 ltl LEAK THRFSHOLO 0.002 IN TEST RESULT PASSED 871VfiP TEST STARTED 11:22 AM TEST STARTED 08/30/2013 BEGIIJ E\JEL 6. 8757 It• EtiU -It£ 11:31 AH E~D OATE 08/30/2013 END LEVEL 6. 8762 Hl LEAK THRES~OLD 0,002 IN TEST ReSULT PASStO 911JAil TEST STAR-ED 11 :Jli AM TEST STARTED 08/30/2013 BEGIN LEVEL 6, 5938 ltl f:M) T:ME 11:19 AH EI.S DATE 05/30/2013 E';[) LEVEL 6. S33e :" EAK THREShOLD O.OC2 iN TEST RESULT P~SSEO 13SS'id :.: <!X 't ~11 {l(J[lL 'I tt')(JCCr .. ~ ~(:9: ;.! ,~p·, ,~ ' . "' r'l •• ''10• .1'.' C/:1, 1 ,rSll-.S3! f -:l1$3lj.;. :·!T lWl G'li !.ll~ 1~::; ~~I! G'l~ 11':l1 ·n•F:J "! .. :•!." !S3! .iiS L2 r,'-'q "' iJ 111 ~ i ,:;~ 1" ::.·11 S f!QQO l ,\•rl l~jlj, C1SS1J·• 1 l:lSJ.• lql '.l (.C' . , 1 J •S]jH! ~1-:' . t.l C>t( 'l H\:;-; C'd L i:(lrt;t·: 3.\11 f''l• h\.4 c;:1 :r::l r· J -' . ' .. h. 'J,iJ' ·.:: .... ~ ... ' (J •I J-:!~'-'-S :. J'lJ_ :,'J l. 'h '!Jl ~>:11 c: .SJl i.':> l" 'J3SS-:: L lS?~ 1 ~ JL ·o1 ~· •• ·\ J : .. s~c~ li'-" ',l ··~lt '! "~.•;1 Cl3 :..r~w:;.·•· ~lllC 0.1 :w a?:r ~,;!! Cll~ ',! h • • 1·1:~ ~.l:;~'l : ..... , ... '· ... . , ...... ·' l ' ~ 1 .... "" r t ..... , ; 1 .. . v. '"~::~~--~ ']~ iUJt; (rC:II lS ·: !S.:-. t1 _, OSLHLL fJSI ~ lL~ [5 '"ilf,"t,; ,~.,: : 'IM Tt::::• 'ifll!'!t.-:~. t'tr. jt," -:,:,' :/N:··t .. • f ~ I /'J' i Tb 5TAf<E: .:nr:no;~ &~~.>.'! ~E·I~; c;. '· )"i.; 1': t.H•'r: LE~E, ~. ~SS.:. :r: !:tiD ·;111: 1~:2o ;;~, t.'l!i TIME iO:Cfl 1':-\ P!~ 0.<\•E f•·J3~12·,·3 P!L DATE J:.t?.f:/2013 t.·O L~VEL 'di!h1l'! E.·:r; LEvE~ 5. ';~5& 1:; =~·-q~;-=?~r .. .. ~·\~ l• • ' I.. ... E ;·... T .,;cs .... j~,.J •• CC2 i', Ti ST -:E5Lt 7 FI15Sf(; TtST ~tSUtl ff.SSEl! 871F!Ll I 871F ttl fEST S1ARIED 12:0/J PH TESi STARTEr; 11:u6 A:1 TEST STARTED 08/30/2013 if. TEST STARTED 08/30/2013 BEGit, EVU 5. 6505 Jt, RF.GIN LEvEL 5. 6509 ill EIID liME 12:19 PH FNO T !ME 12:01 PM END DATE 08/30/2013 UIO DATE 08/30/20:3 END LEVEL 5. 6560 ltl Etf.l LEVEL 5, 6515 IU lEAK TIIRESHDLD 0. 002 HI LEA~ THRES~.OLC 0, 002 liJ lEST RESULT PASSED llS' RES:..tl PASSED 872STP 872Slf' TEST STARTE[J 12:0a PM '"ESl ST t<RTED 1l: 116 AM TEST STARTED 08/30/2013 TEST STARTED 00/30/2013 BEGIN U:VEL 3. 39115 w BEG l.'i LEVEl s. 3946 Ill EliO TIME 12:19 PM EIID liME 12:01 PM END DATE 08/30/2013 F.IIO OATE 08/30/2013 Et:O LEVEL 3. 39111 IN EI:D LEVEL 3. 3907 ;t; LEAK THRESHOLD 0, 002 ;r: LE,w: iH.qESHOLO 0. 002 ;t; TEST liESULl P~SSEO lEST litSULT FASSEO ,. II t J lA I" ~-~ .• l I. i ~lC~fl Mil>=~ il500 Sl !NF RO E'll~tEULO fA J33Gb OP/30/2013 11:35 tiM S'IHP d:AK itST RE'Of<. LDCJ-2 TES: ~TI\R-:::0 ll:?i liN TEST ST1,~-~;; 86/30/2013 BEG!:I LE'JEt fJ, 6ll71 HI EID T I Me 11 : 35 A~ E' ;::J DATE Oo/3C/20 l:l E'.O I fi!EL ~. 6f:7a JfJ ~ ~~~K THiESHO_[! 0. Q1)2 1 '. TEST RESULT P~)SFu UOC5-5 TEST ST!\RlW P:.n AM TEST Sif1'iTED o;/3mO 13 BEGHJ LEVFL 1. 3(Jb7 :·~ Er:o mE 11:52 AM U.O 9AT[ 08/30/2013 E'm ... EVEL 1. 3076 Hl Lt~K TH' ES110~u 0. C02 lrt TfSf RESL .. T PF1SSED 17 I '(, I I \ ., t ' M~TRO f1AR d600 sm:E kD UA~EEFIELL (A 833~9 08/30/2013 i1:52 AN S:.JHP LEAK 1 eST f!EPU~f LDCl-2 -~sr S'ARTED 11:37 Ar TEST S"'ARTEC (i.=f'K/2013 EEGW ~EVEI d. 61175 W Er .D T I ~E 1 1 :52 AM Er(l DATE Ot/30/2013 HD LEVEL 11. 5a711 I'l LEA'< THRESHCLu C. 002 : ~~ iEST RESULT PASS:O UOC3-a TES Sli\RiElJ -EST $111F:H:O BEGJ:J LEVEL E:~D TIME . 2:~0 ~~t1 . ,'.i'"i0/2013 J. :;1)5t, Ill '2:35 f'~l E~m G? i[ 08/30/2013 PlO LEVEL 5, J0£:2 IN I EAK THRESHOLL 0. 002 IIi :EST RESULT PASSED UlJCJ-6 TFS" SiAf<TFlJ 12:20 P~\ TES" Si~RTED u'J3,•?0'~ 2.EGW LEVEL 1. aor.:u it: E'JO TIME i?.:35 P'\ c:u n41E a.:-/J0/2013 E'f[J LEVEL 1. ,C,i)f;.., ItJ t tAil THRESHC~O D. 001 IIJ n:s ~ RESU • .T PftSSED ll. li1 li1 II ,. M~ r~o t'ti~ 1 aiiOO ST WE kD SAKEEF !Elv CA 'J33('l OJ/30/?013 1:11 rH St~'11-' l hiK 1FT ~.[ ··G!il UCJC?-8 ':::::r sTARTEu :.!:::b Hl -EST SW:TED k/30i20:3 :lEG:l~ LE\'EL tl,liQ32 jt; Er:u TIPE 1: ll Ft: E::O CGiF OK/30/2013 E:;[; LEIJEL a. d~l31 1.'1 L~AK i11RESrOLJ :l. 90? l 'J TEST RESLL i F•t,SSF!J uur.n 10 IES STARTED 12:56 fM TEST STA"Tto 8EG!I! LEVEL EI,O i!HE EI;[J DATE F:;[) LE•JEL Oc/30t2?1J 11,5627 HI 1:11 r'l •x.I:.0/20'3 a. s.s3a w LEt7ol' rHRFSHO~L C. OC•2 :I; TtST RES~ki PASSED MEii::O MAF:· d600 S T HJE RO P,A~EEC![LD (A 83309 06/30/20i3 i :2.:. fN S~':t' ~Fi>~ TtSl Hf.:-QR; J!JCI ~ TfSi STAP.•EfJ EST s-~no 8EG It; LEI.EL END TIME FNO DATE t:tjfJ LEVEL l FA'< THRESHOd; TEST RESULT i: i3 ~t' ):./3': 12·~ 13 u.a'm I': 1:.!c; F-'1 08/30/2013 11. n83n IN C'. C02 l'l f'ASSED UOC810 TEST STARTED 1:;~ ~M TES' SlflfHED 03/30/2013 BEGW LEVEL 4, 5533 Ill EIJO TIME 1:26 PM Et;[J DATE 08/30i2013 E~IO LEVEL a, SW U! EAfl T!iREShOl D 0. 002 I 'I ~EST RtSLti PASSED