HomeMy WebLinkAboutHP GO GO-3301 Wible Line testCONFIDENCE UST SERVICES, INC.
417 Montclair Street. Bakersfield, CA 93309 800-339-9930 or 661-631-3870
:FINAL TEST RESULTS :
ALERT 1000 I ALERT 1050 I TEI LT-3
CUSTOMER ADDRESS: WORK ORDER:31685
TEST DATE : 12/10/2013
SITE ADDRESS:
HP GoGo
3301 Wibl e Road
Baker sfield , CA 93309
SITE CONTACT :!:lo
TECHNICIAN: Doug You ong
HE' GoGo
3 301 liiible Road
Bake r s field, CA 93309
PHONE NUMBER:661 -835-80 44
PHONE NUMBER :B00-339-9930 LICENSE :901076
WATER IN BACKFILL: N/A DATE & TIME OF LAST FUEL DELIVERY:N/A
TANK INFORMATION :
(WET T ED)
PRODUCT TYPE:
TOTAL GALLONS:
PRODUCT LEVEL :
PERCENT FULL:
TEST METHOD:
WATER IN TANK:
TANK MATERIAL:
P.S.I.@ BOTTOM:
TEST DURATION:
FINAL LEAK RATE :
TEST RESULT:
TANK INFORMATION
(ULLAGE) U/F ONLY
ULLAGE GALLONS:
START PRESSURE:
END PRESSURE :
TEST RESULT:
PRODUCT LINES :
LINE TYPE :
START TIME:
END TIME:
TEST PRESSURE :
FINAL LEAK RATE:
TEST RESULT:
MECHANICAL
LEAK DETECTORS:
MODEL:
SERIAL NUMBER:
CHECK VALVE PSI:
BLEED OFF ml:
LEAK RATE TESTED:
TEST RESULT:
TANK 1
Regular #1
ALERT 1050X
TEI LT-3
Pressure
9 :20 am
9:35 am
50 psi
-0.001 gph
PASS
Red Jacket FXT
TANK 2 TANK 3 TANK 4
Regular #2 Premium
ALERT 1050X ALERT 1050X ALERT 1050X
TEI LT-3 TEI LT-3 TEI LT-3
This Produc t Line Pressure
IS Manifolded To 9:40 am
Regular #1 and 9:55 am
Shares a Common 50 psi
Product Line -0.000 GPH
PASS PASS
Red Jacket FXT Red Jacket FXT Red Jacket FXT
A) These systems and methods meet or exceed the criteria in USEPA 40CFR parts 280, NFPA 329-87 and all applicable state codes.
B) Any il e isted above may requi re further action, chec k with all regul atory agenci es.
Date: Manufacture~na1~iification No :
Ale~l : 200404 TEI : LT -3,099 12--It/ -lr3