HomeMy WebLinkAboutFMC 2013MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Wit/tin the State of Cal[fomia
Autltorizv Cited: Chapter 6. 7, Health and Sc!fety Code; Chapter 16, Division 3, Title 23, California Code q{Regulations
This form must be used to document testing and servicing of monitoring equipment. A separate eenification or report must be prepared for each
monitoring system control pan~l by the technician who perfonns the work. A copy of this form must be provided to the tank system
owner/operator. The owner/operator must submit a copy of this fonn to the local agency regulating tSr ~ystems within 30 days of test date.
A. General Information
Facility Name: Ramco Express Bldg. No.: -----
Site Address: 2222 F Street City: Bakersfield Zip: .;;...93,_3_0_1 __ _
Facility Contact Person: Rami Contact Phone No.: (661) 324-1758
Make/Model of Monitoring System: Veeder-Root TLS-350 Date ofTesting/Servicing: 12/19/2013
B. Inventory of Equipment Tested/Certified
'-'11'-'-" '-tl\.. fiJI loll V IIHI"-VV-'"-" IV ltiUt'-UI"' .;J "'-'-'"'-'-"'UI '"""''" , .. ,,. ''-'-''-''-"'''-' .. , ....... u.
Tank 10: 10,000 gal. Regualr Tank 10: 10,000 gal. Plus
181 In-Tank Gauging Probe. Model: 847390-107 1811n· rank Gauging Prolx:. Model: 847390-107
181 Annular Space or Vault Sensor. Model: 794390-409 181 Annular Space or Vauh Scrl'><lr. Model: 794390-409
181 Piping 'iump I n.>r!Ch Sensor(s). Model: 794380-208 181 Pipmg Sump/Trench Scn...or(s). Model: 794380-208
D Fill Sump ScrMr(s). Model: 0 Fill Sump Scnsor(s). Model:
0 Mechanic:1ll.inc l.eak Detector. Model: 0 Ml.-chanical Line Lc<tk Dcli .. 'Ctor. Model:
181 Electronic l..inc l.cak Detector. Model: PLLD 181 I'IL-ctronic Line Leak Detector. Model: PLLD
181 Tank Overfill/It igh-Level Scrt~r. Model: OPW-61-SO 181 Tank Overfill/ H igh-t..evcl Scm.or. Model: OPW-61-SO
0 Otherhpccify equipment type and model in Section con Page 2). 0 Other (specify equipml.'llttype and model in Section I' on Page 2).
Tank 10: 10,000 gal. Sueer Tank 10:
1811n-Tnnk Gaugmg Probe. Model: 847390-107 0 In-I ank Gauging Prolx:. \olodcl:
181 Annulnr Space or Vault Sensor. Model: 794390-409 0 Annular Space or Vault Sc~t,or. Model:
181 Piping Sump I Trench Scnsor(s). Model: 794380-208 0 Piping Sump/Trench Scnsor(s). Model:
0 Fill Sump Scnwr(s). Model: D Fill Sump Scnsor(s). Model:
0 Mechanical I inc l.cak Detector. Model: D Mechanical Line Leak Dctl.'Ctor. Model:
181 Electronic I inc I cak Detector. Model: PLLD 0 Hectmnic Line Leak Dcwctor. Model:
181lank Overfill lligh-l.cvel Sen..or \olodcl: OPW-61-SO 0 I ank 0\crfill/ High-t e\cl Scn .... or. Model: D Other ('(l(.'Ctfy equipment type and model in Section Eon Page 2). 0 Other (specifY equipment type and model in Section I on Page 2).
Dispenser 10: 1-2 Dispenser I D: 3 -4
D Dispenser Containment Sensor(s). Model: D Dispenser Containment Scnsor(s). Model:
181 Shear Valvl.'{s). 181 Shear Valvc(s).
181 Dispcn.<.,cr ( 'ontainment Float(s) and C'hain(s). 181 Dbpenscr Containment 1-loat(s) and Chain(s).
Dispenser 10: Dispenser I D:
D Dispenser Containment Sensor(s). Model: 0 Dis(l(.'IISCI' Containment Sc!lo,<lr(s). Model:
D Shear Valvc(s). D Shear Valvc(s).
D Dispenser Containment Float(s) and ('hain(s). D Dispenser Containment Float(s) and Chain(s).
Dispenser 10: Dispenser 10:
0 Dispcrt<;cr Containment Sensor(s). Model: 0 Dispenser C ontainrnent Scll~r(s). Model:
0 Shear Valvc(s). 0 Shear Valvc(s).
0 Dispenser C'ontauunent Float(s) and C'hanl(s). D Dr~(l(.'IISCI' Containment Float(s) and Chain(s).
•Jfthe facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification -I certify that the equipment identified in this document was inspected/serviced in accordance with the
manufacturers' guidelines. Attached to this Certification is information (e.g. manufacturers' checklists) necessary to verify that this
information is correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of generating such
reports, I have also attached a copy of the report; (clreck all tlrat app/J'}: [8] System set-up [8] Alarm ltistory report
Technician Name Krist~her Karns
Certification No.: B34106
Signature: ~4 '&.cA.,
License. No.: --'-80.:....4-=9-=0-=4 _____ _
Testing Company Name: Confidence UST Services, Inc. Phone No.: (800) 339-9930
Site Address: 2222 F Street, Bakersfield, CA 93301 Date ofTesting/Servicing: 12/19/2013
Page 1 of 3
Monitoring System Certification
D. Results of Testing/Servicing
Software Version Installed: 333.03 ~~~---------------------------
c he foll heckl·
[8l Yes 0 No* Is the audible alarm operational?
C8l Yes 0 No* Is the visual alarm operational?
[8l Yes 0 No* Were all sensors visually inspected, functionally tested, and confirmed operational?
C8l Yes 0 No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment
will not interfere with their proper operation?
0 Yes 0 No* If alarms arc relayed to a remote monitoring station, is all communications equipment (e.g., modem)
C8l N/A operational?
[8l Yes 0 No* For pressurized piping systems, docs the turbine automatically shut down if the piping secondary containment
0 N/A monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate
positive shut-down? (Check all that apply) [8l Sumpffrench Sensors; 0 Dispenser Containment Sensors.
Did you confirm positive shut-down due to leaks and sensor failure/disconnection? [8l Yes; 0 No.
0 Yes 0 No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no
C8l N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank
fill point(s) and operating properly? lf so, at what percent of tank capacity does the alarm trigger? -61%
0 Yes* C8l No Was any monitoring equipment replaced? If yes, identifY specific sensors, probes, or other equipment
replaced and list the manufacturer name and model for all replacement parts in Section E, below.
0 Yes* ~ No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that app~y)
0 Product; 0 Water. If yes, describe causes in Section E, below.
C8l Yes 0 No* Was monitoring system set-up reviewed to ensure proper settings? Attach set up reports, if applicable
0 Yes C8l No* Is all monitoring equipment operational per manufacturer's specifications?
*In Section E below, describe how and when these deficiencies were or will be corrected.
E. Comments: Q-3 Reg. PLLD failed to catch leak. It appears to have air in the line. The parts will be ordered to make
appropiate repairs.
91 OPW Direct Burial Spill Bucket failed and needs to be replaced.
Page 2 of 3
Monitoring System Certification
F. In-Tank Gauging I SIR Equipment: ~ Check this box if tank gauging is used only for inventory control.
0 Check this box if no tank gauging or SIR equipment is installed.
This section must be completed if in-tank gauging equipment is used to petfonn leak detection monitoring.
Complete the following checklist:
~Yes 0 No* Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
~Yes 0 No* Were all tank gauging probes visually inspected for damage and residue buildup?
~Yes 0 No* Was accuracy of system product level readings tested?
~Yes 0 No* Was accuracy of system water level readings tested?
~Yes 0 No* Were all probes reinstalled properly?
181 Yes 0 No* Were all items on the equipment manufacturer's maintenance checklist completed?
~'In the Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD): 0 Check this box ifLLDs are not installed.
Comolete the ft
~Yes 0 No* For equipment start-up or annual equipment certification, was a leak simulated to verifY LLD performance?
0 N/A (Check all that apply) Simulated leak rate: ~ 3 g.p.h.; 0 0.1 g.p.h ; 0 0.2 g.p.h.
0 Yes ~No* Were all LLDs confirmed operational and accurate within regulatory requirements?
~Yes 0 No* Was the testing apparatus properly calibrated?
0 Yes 0 No* For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
~ N/A
~Yes 0 No* For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak?
0 N/A
~Yes 0 No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled
0 N/A or disconnected?
~Yes 0 No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system
0 N/A malfimctions or fails a test?
~Yes 0 No* For electronic LLDs, have all accessible wiring connections been visually inspected?
0 N/A
~Yes 0 No* Were all items on the equipment manufacturer's maintenance checklist completed?
* In the Section H, below, describe how and when these deficiencies were or will be corrected.
H. Comments: Q-3 reg. PLLD fa1led to detect leak. It appears to have a1r m the I me. I he parts have been ordred
and we will rturn to make repa1rs and retest 87 Q-3 PLLD.
Page 3 of 3
I
Q I :PLlJS
0.20 GAL/HR RESULT:
DEC 19.2013 1:33AM PASS
Q 2:SUPER •
0.20 GAL/HR RESULT:
DEC 19.2013 I :34Pl1 PASS .·
I,
A : . :.~ ~
Q 3:REGULAR ·t• ~ ~ '
0.20 GAL/HR RESULT:
DEC 19.2013 1 ~£25At-J PASS
I I
PRESSURE LINE LEAK ALARM Q 2:SUPER
PLLD SHIJTDOWN ALARM
DEC 19. 2013 9:51 AM
----SENSOR. ALARM -----L 4:SUPER STP
STP SCR1P
FUEL ALARM
DEC 19. 2013 9:5t AN
!\ 1: ;~
. • ·I( . i
11" PRESSUR~·; !£~ AJ,Jir.tl ~3:REG . ~fl"' ~·-",~; PLLD SH ltl Rf1 ·
DEC 19. ~ 11tl ·:~ .P~ AH
\
./' J ,;P.
\ l'.\·' -----SEtSOR.A~RH -----L 6:REGULARJsrp· ..
STPSlJ1P
FUEL ALARM DEC 19, 2013 9:52 ~
PRESSURE LitlE LEAK ALARM
Q l :PLUS
PLLD SHIJTDOWII AUIRM DEC 19. 2013 9:52 AH
-----SENSOR ALARM __ _,...
L 2:PLUS STP
STP SU1P
FUEL ALARM
DEC 19. 2013 9:52 AH
RAHCO EXPRESS
2222 F STREET
BAKERSFIELD CA 93301
661-324-1758
DEC 19. 2013 9:54 AM
S\'STEJ1 STATUS REPORT
L 2: FUEL ALARM
L 4 :FUEL ALARM
L 6:FUEL ALARI'l
Q l :PLLD SHUTDOWN ALARM
Q 2:PLLD SHIJTDCWtl ALARM
Q 3:PLLD SHIJTDCWtl ALARM
ltNENTORY REPORT
T I :PLUS
VOLlJ1E • I 668 GALS
ULLAGE • 801 6 GALS
90Y. ULLAGE• 7047 GALS
TC VOLUME • 1660 GALS
HEIGHT • 20.31 HlCHES
WATER VOL • 0 GALS
WATER • 0.00 INCHES
TEMP • 66.4 DEC F
T 2:REGULAR
VOLll1E • 4725 GALS ULLAGE • 4959 GALS 90Y. ULLAGE• 3990 GALS
TC VOLUME • 4727 GALS
HEIGHT • 43.25 INCHES
WATER VOL • 0 G.ALS WATER ,. 0.00 ltiCHES
TEMP • 59.3 DEC F
T 3:SUPER VOLUHE .. 1384 GALS
ULLAGE .. 8300 GALS
90Y. ULLAGE• 7331 GALS
TC VOLlJ1E • 1375 GALS
HEIGHT • 17.80 ltiCHES WATER VOL • 13 GALS
WATER • 0. 77 ltiCHES
TEMP • 69.0 DEC F
X X X X X Et/0 X X X X X
SOFTWARE REVISION LEVEL
VERSION 333.03
SOFTWAREP 346333-100-D
CREATED-13.02.12.10.26
S-MODULEP 330160-064-o
~~O~~T~~~NK T£STS
ANNUAL I ti-TANX T£STS
ISD/APM
PLLD
0.10 AUTO
0.20 REPETITIV
WPLLD
0.10 AUTO
0.20 REPETITIV
S'ISTEM SETUP
DEC 19. 2013 9:5~ AM
SYSTEM UNITS u.s.
SYSTEM LAtiGUACE
EtiGLISH
SYSTEM DATE/TIME FORMAT NON DO 'l'{'('( tm:MM:SS l<M
RAHCO EXPRESS
2222 F STREET
BAKERSFIELD CA 93301
661-324-1758
SHIFT TIME I : DISABLED
SHIFT TIME 2 : DISABLED
SHIFT TIME 3 : DISABLED
SHIFT TIME 4 : DISABLED
TANK PER TST NEEDED WRU
DISABLED
TANK AtiN TST tiEEDED WRU
DISABLED
LINE RE-ENABLE METHOD
PASS LitlE TEST ---·-·
LitlE PER TST NEEDED WRN
DISABLED
LitlE ANN TST NEEDED WRII
DISABLED
PRJ NT TC VOLlJMES
ENABLED
TEMP COHPEt&-\l'IOtl
VALUE <DEG F >: 60.0
STICK HEIGHT OFFSET
DISABLED
ULLAGE: 9~:
H-PROTOCOL DATA FORMAT
HEIGHT
PRECISIOU TEST DURATION
HOURS: 12
0.20 GPH LINE TEST
AUTO-cONFIRM: EIIABLEO
0.10 GPH LUIE TEST
AUTO-cONF I RH: EliAS LED
PRINT PRECISIOII LitlE
TEST RESULTS: EtiABLEO
DAYLIGHT SAVING TIME
ENABLED
START DATE HAR WEEK 2 SUN
START TIME
2:00 AH
END DATE
NOV WEEK I SUtl
END TINE 2:00AM
R.E-DIRECT LOCAL PRWTOUT
DISABLED
EURO PROTOCOL PREFIX s
SYSTEM SECURITY CODE : 000000
HAiflfENANCE HISTORY
DISABLED
TANK CHART SECURITY
DISABLED
CUSTOM ALARHS
DISABLED
SERVICE IIOTICE
DISABLED
ISO 3166 courrrRY
CODE:
VAPOR MONITORING TYPE
CARB lSD
MASS/DENSITY
DISABLED
FISCAL HEIGHT SECURITY
DISABLED
INVENTORY ALARMS UNITS
COUFIG: STANDARD
MAX OR LABEL: VOLLt1E
HIGH PRODUCT: % MAX
OVERFILL : ~; MAX
DELIV NEEDED: ::.41AX
LOW PRODUCT : VOLLt1E
ALARM REDUCTION
ENABLED
CONMUIIICATIONS SETUP
PORT SETTH~:
COMM BOARD : l <RS-232> BAUD RATE : 9600
PARITY : ODD
STOP BIT : 1 STOP
DATA LENGTH: 7 DATA
RS-232 SECURITY
CODE : DISABLED
CONM BOARD : 2 <ED lt1 > RS-232 SECURITY
CODE : DISABLED
COMM BOARD : 3 <RS-232> BAUD RATE : 9600
PARITY : NONE
STOP BIT : I STOP DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
AUTO TRANSMIT SETTINGS:
AUTO LEAY. ALARM LIMIT
DISABLED
AUTO HIGH WATER LIMIT
DISABLED
AUTO OVERFILL LIMIT
DISABLED
AUTO LOW PROD~
DISABLED AUTO THEFT LIMIT
DISABLED
AUTO DELIVERY START
DISABLED
AUTO DELIVERY EIID
DISABLED
AUTO EXTERNAL I tiPUT ON
DISABLED AUTO EXTERNAL 1 NPUT OFF DISABLED
AUTO SENSOR FUEL ALARM
DISABLED
AUTO SENSOR WATER ALARM DISABLED AtrrO SENSOR OUT ALARM
DISABLED
RS-232 END OF MESSAGE
DISABLED
IN-TAIIK SETUP
T 1 :PLUS
PRODUCT CODE
THERMAL COEFF
TANK DIAMETER
TAtiK PROFILE FULL VOL
66.8 INCH VOL
44,5 INCH VOL
22.3 INCH VOL
1
.000700
89.00
4PTS 9684
7861 4904
1898
FLOAT SIZE: 4.0 Ill.
WATER HltUM~ : 0.200
WATER WARNIIIG : 2.0 HIGH WATER LIMIT! 3.0
WATER ALARM FILTER: LOW
MAX OR LABEL
VOLUME : 9684
HIGH PRODUCT Yo MAX : 95.0
<CALLOtiS> : 9200
OVERFILL LIMIT Y. MAX : 90.0
<GALLOIIS> : 8716
DELIVERY LIMIT :, MAX : 10.0
(CALLOIIS) : 968
LOW PROD~
VOLUME : 515
LEAK ALARM LIMIT: . 99
SUDDEN LOSS LIMIT! 50
TANK TILT : 3.02
PROBE OFFSET : o.oo
SIPHON MANIFOLDED TAN!~
Til! NONE
LINE MANIFOLDED TANKS TJI: NONE
LEAK Hill PERIODIC: I~
LEAK HI tl AtltWAL :
PERIODIC TEST TYPE
9Et3
lOY.
968
STAIIDARD
AtiNUAL TEST .FAIL
·•' AlARM ~ISABLED
P.ERIDDI~TEST·FAIL
ALARM DISABLED
CROSS TEST FAIL
ALARM DISABLED
Aim TEST AVERACitiG: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TllK TST SIPHON BREAK:OFF
DELIVERY DELAY : I HIN
PUMP THRESHOLD : IO.OW.
T 2:REGULAR
PRODUCT CODE
THERMAL COEFF
TANK DIAMETER TANK PROFILE FULL VOL
66.8 INCH VOL
44.5 INCH VOL
22. 3 ltlCH VOL
FLOAT SIZE:
WATER MINIMUM :
2 .000700
89.00
4PTS
9684
7861 4904
1898
4.0 IN.
0.200
WATER WARNUIG : 2.0 HIGH WATER LIMIT! 3.0
WATER ALARM FILTER: LOW
MAX OR LABEL
VOLUME : 9684
HIGH PRODUCT ~' MAX : 95.0
<CALLOtiS) : 9200
OVERFILL LIMIT ~MAX : 90.0
<GALLONS> : 8716
DELIVERY LIHlT Y. MAX : 10.0
<GALLONS> : 969
LOW-PRODUCT VOLU1E : 515
LEAK ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 50
TANK TILT : o.oo
PROBE OFFSET : o.oo
SIPHON MAtllFOLDED TANKS
Til: NONE
LitlE MANIFOLDED TANKS
Til! NOliE
LEAK Hill PERIODIC:
LEAK HI N AIIUUAL :
10:;
969
I 0};
968
PERIODIC TEST TYPE
STAilDARD
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLEO
CROSS TEST FAIL
ALARM DISABLED
AIIN TEST AVERAGitiG: OFF
PER TEST AVERACUlG: OFF
TANK TEST NOTIF"/: OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY : I MIN
PUMP THRESHOLD : 1 0. OOV.
T 3:SUPER PRODUCT CODE
THERt1AL COEFF
TANK DIAMETER
TANK PROFILE FULL VOL
66,8 l~H VOL
44.5111CH VOL
22.3 It.'CH VOL
FLOAT SIZE: WATER HlNINlJ1 :
3
,000700
89.00
4 PTS
9684
7861
4904 1696
4.0 HI.
0.200
WATER WARtliNG : 2,0 HIGH WATER LIMIT: 3.0
WATER ALARM FILTER: LOW
MAX OR LABEL
VOLUIIE : 9684
HIGH PRODUCT
!' HAX : 95.0
<GALLOIS) : 9200
OVERFILL LIMIT
Y. MAX : 90.0
<CALLOtlS> : 8716
DELIVERY LIMIT ~MAX : 10.0
<GALLONS> : 969
LOW PRODUCT
VOLUME : 515
LEAK ALARM LIMIT: 99 SUODEt~ LOSS LIMIT: 50
TAIIK TILT : 2.60
PROBE OFFSET : o.oo
SIPHON MANIFOLDED TANt'.S
Til: tiONE
LINE MANIFOLDED TAIIKS
Til: NONE
LEAK MIN PERIODIC:
LEAK MIN AlltiUAL :
10'4
969
IW.
968
PERIODIC TEST TYPE
STANDARD
AlltiUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
Atltl TEST AVERAGttiG: OFF PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TtiK TST SIPHON BREAK:OFF
DELIVERY DELAY : I MIN
PLV1P THRESHOLD : 10.00';
LEAK TEST METHOD
TEST ON DATE : ALL TANK
JUL 31. 2013
START TIME : 2:30 AM
TEST RATE !D.20 CAL/HR
DURATION : 2 HOURS ,
TST EARLY STOP!DISABLED
LEAK TEST REPORT FORMAT
ENHANCED
PRESSURE LitlE LEAK SETUP
Q 1 !PLUS
TVP:2.0 lfl STEEL LINE LENGTH: 125 FEET 0,20 GPH TEST: REPETITIV
0.10 GPH TEST: DISABLED
SHUTDOWN RATE: 3,0 GPH
LOW PRESSURE SHUTOFF:NO LOW PRESSURE : 0 PSI
T I:PLUS
DISPENSE MODE:
STANDARD SElSOR: HIGH PRESSURE
PRESSURE OFFSET: O,OPSI
MECHANICAL BLENDER: 110
Q 2:SUPER
TVJ>:2.0 IN STEEL
LINE LENGTH: 125 FEET
0.20 GPH TEST: REPETITIV
0, I 0 GPH TEST: A liTO
SHUTDOWN RATE: 3.0 GPH
LOW PRESSURE SHUTOFF:NO LOW PRESSURE : 0 PSI
T 3:SUPER
DISPENSE MODE:
STANDARD SENSOR: HIGH PRESSURE
PRESSURE OFFSET: O,OPSI
MECHANICAL BLENDER: llO
Q 3:REGULAR
TVP:2,0 IN STEEL
LitlE LENGTH: 125 FEET
0.20 GPH TEST: REPETITIV
0, I 0 GPH TEST: MAtiUAL
SHUTDOWtl RATE: 3, 0 GPH
LOW PRESSURE SHUTOFF:tiO
LOW PRESSURE : 0 PSI
T 2!REGULAR
DISPENSE MODE:
STANDARD SENSOR: HIGH PRESSURE
PRESSURE OFFSET: O,OPSI
MECHANICAL BLENDER: 110
LINE LEAK LOCKOUT SETUP
LOCKOUT SCHEDULE
DAILY
START TINE: DISABLED
STOP TIME : DISABLED
LIQUID SENSOR SETUP
L l !SUPER ANIIULAR
TRI-STATE <SINGLE FLOAT>
CATEGORY : AWWLAR SPACE
L 2:PLUS STP
TRI-STATE <SINGLE FLOAT>
CATEGORY : STP SUHP
L 3:REGULAR ANNULAR
TRI-STATE <SINGLE FLOAT>
CATEGORY : ANNULAR SPACE
L 4 :SUPER STP
TRI-STATE <SINGLE FLOAT>
CATEGORY : STP SUMP
L 5:PLUS AIIIIULAR
TRI-STATE <SINGLE FLOAT>
CATEGOR\' : AlliiULAR SPACE
L 6:REGULAR STP
TRI-STATE <SINGLE FLOAT>
CATEGORY : STP SUMP
PLLD LUIE DISABLE SETUP
Q I :PLUS
ltl-TANK ALARMS T I :HIGH WATER ALARM
T 1 :LOW PRODUCT ALARM
T 1 :PROBE Ol1T
LIQUID SENSOR ALMS L 2:FUEL ALARM
L 2 :SENSOR Ol1T ALARM
L 5:SENSOR Ol1T ALARM
L 2:SHORT ALARM
L 4:SHORT ALARM
lSD SITE ALARMS
lSD CROSS PRES FAIL
ISO OECRD PRES FAIL
lSD VAPOR LEAK FAIL lSD VP PRES FAIL
ISO VP STATUS FAIL
lSD SETUP FAIL
lSD SENSOR OUT FAIL
PC-ISO FAILURE
lSD HOSE Al.ARf'S
ALL!CROSS COLLECT FAIL
ALL:DEGRO COLLECT FAIL
ALL!FLOW COLLECT FAIL
Q 2:SUPER
IN-TANK ALARMS
T 3:HICH WATER ALARM T 3!LOW PRODUCT ALARM T 3!PROBE OUT
LIQUID SENSOR ALMS
L &~:FUEL ALARM
L I :SENSOR OUT ALARM
L 4 :SENSOR OUT ALARM
L I :SHORT ALARt1
lSD SITE ALARMS
lSD CROSS PRES FAIL
ISO DEGRO PRES FAIL
lSD VAPOR LEAK FAIL
lSD VP PRES FAIL
ISO VP STATUS FAIL
lSD SETUP FAIL
ISO SENSOR OUT FAIL
PC-lSD FAILURE
lSD HOSE ALARMS
ALL:CROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
Q 3:RECULAR
114-TAIIK ALARMS
T 2:HICH WATER ALARM
T 2!LOW PRODUCT ALARM
T 2!PROBE OUT
LIQUID SEilSOR ALMS
L 6:FUEL ALARM
L 3:SENSOR OUT ALARM
L 6!SENSOR OUT ALARM
lSD SITE ALARMS
ISO CROSS PRES FAIL
ISO DEGRD PRES FAIL
ISO VAPOR LEAK FAIL
ISO VP PRES FAIL
ISO VP STATUS FAIL
ISO SETUP FAIL
ISO SENSOR OUT FAIL
PC-lSD FAILURE
ISO HOSE ALARMS
ALL:CROSS COLLECT FAIL
ALL!DECRD COLLECT FAIL
ALL!FLOW COLLECT FAIL
.SHARTSEtiSOR SETUP ·------------
-~:F.l..QJ.L I:IE'IT..ER. 1-2 • CATEGORY AIR FL~-M~ER
~ 2:FLOW METTER 3-4
CATEGORY AIR FLOW METER
~ 3 :PRESSURE SEtlSOR
CATEGORY VAPOR PRESSURE
EVR/ISD SETUP
EVR TYPE: VACUUM ASSIST
VACUUM ASSIST TYPE
HEALY VAC
N02ZLE A/L RAtiGE
MAX: 1.15 MltH 0,95
VAPOR PROCESSOR TYPE
NONE
ANALYSIS TIMES
TIME! I :49 PM
DELAY MINllfES:
ACCEPT HIGH ORVR:
DISABLED
lSD HOSE TABLE
ID FP FL HL AA RR ------------------------01 33 01 02 01 00 02 34 02 02 01 00
03 35 03 02 02 00
04 00 04 02 02 00
ISO AIRFLOW METER MAP
ID SERIAL lll.t1 LABEL
I 20340
2 23389
FLOW METTE
FLOW METTE
ISO FUEL GRADE HOSE MAP
I 2 3 4
FP HHH HHH MHH MHH AA
00 204 004 104 u u 2
I 33 201 001 101 U U I
34 202 002 102 u u 1
35 203 003 103 u u 2
LABEL TABLE
1 UNASSIGNED
2 BLEND
3 REGULAR
4 MID GRADE 5 PREl1ILt1 6 COLO 7 BRONZE 8 SILVER
9 BLEND2 10 BLEND4
SOFTWARE REVISION LEVEL
VERSIOfl 333.03 SOFTWARE# 346333-100-D
CREATED-13.02.12.10.26
S-MODULE# 330160-064-a
S'ISTEl1 FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL I N-TAtiK TESTS
ISD/APM
PLLD
0.10 AUTO
0.20 REPETITIV
WPLLD
0.10 AUTO
0.20 REPETITIV
ALARM HISTORY REPORT
-----· SEt-ISOR ALARM -----
L I :SUPER AtHIULAR
ANNULAR SPACE
FUEL ALARM
AUG 23. 2013 9!41 AH
SENSOR OUT ALARM
AUG 23. 2013 9:25 AH
FUEL ALARM
AUG 23. 2013 9:20 AH
M M M M M END M M M M M
ALARM HISTORY REPORT
-----SENSOR ALARH -----L 2!PLUS STP
STP SUMP
FUEL ALARM DEC 19. 2013 9:52 AH
SENSOR OUT ALARM
! AUG 23. 2013 9:25 AH
I
FUEL ALARM AUG 23. 2013 9!14 AH
M M M M M END * ~ ~ * *
ALAJ(H HISTORY REPORT
-----SENSOR ALARM -----L 3:REGULAR AtltlULAR ANNULAR SPACE FUEL ALARM AUG 23. 2013 9:39 AM
SENSOR OUT ALARM AUG 23. 2013 9:25 AM
FUEL ALARM AUG 23. 2013 9!21 AH
M M M M )( END )( )( )( )( )(
ALARM HISTORY REPORT
-----SENSOR ALARM -----L 4 :SUPER STP STP SlklP FUEL ALARM DEC 19. 2013 9:51 AH
FUEL ALARM NOV 21. 2013 7:40PM
SENSOR OUT ALARM AUG 23. 2013 9!25 AH
---·-
M M M M M END M K M M M
ALARM HISTORY REPORT
---SENSOR ALARM ---L 5:PLUS ANNULAR AtlflULAR SPACE
FUEL ALARM AUG 23. 2013 10!04 AM
FUEL ALARM AUC 23. 2013 10!04 AM
FUEL ALARM AUC 23. 2013 9!38 AH
M M * M M EtiD M M * K K
ALARM HISTORY REPORT
----SEtSOR ALARM --L 6:REGULAR STP STP SIJ1P FUEL ALARM DEC 19. 2013 9:52 AM --"""'··--FUEL ALARM NOV 21. 2013 9:39PM
FUEL ALARM NOV 21. 2013 7!57 PM
M M M )( M END K M M )( )(
L
RAHCO EXPRESS 2222 F STREET BA~ERSFIELD CA 9~~01 661-324-1758
DEC 19. 2013 9:56AM
PRESSURE LitlE LEAK TEST HISTORY
Q I :PLUS
LAST 3.0 GAI../HR PASS: DEC 19. 2013 9:54 AH
FIRST 0.20 GAL/HR PASS EACH HOtlTH:
DEC 1. 2013 10!40 PM t~V J, 2013 12:23 AH OCT J, 2013 12!38 AH SEP J, 2013 11!04 PM
AUG 1. 2013 11!55 PM JUL 31. 2013 6:09PM
FIRST 0.10 GAI../HR PASS
EACH MONTH:
l( )( M )( )( EtlD )( )( )( )( )(
RAHCO EXPRESS 2222 F STREET BAKERSFIELD CA 93301 661-324-1759
DEC 19. 2013 9:56AM
PRESSURE LINE LEAK TEST HISTORY
Q 2:SUPER
LAST 3,0 GAI../HR PASS: DEC 19. 2013 8:55 AH
FIRST o.:m GAI../HR PASS
EACH HOtlTH:
DEC 1. 2013 12 08 AM NOV t. 2013 I 08 AM OCT 1. 2013 12 38 AH SEP 1. 2013 10 49 FN AUG 1. 2013 11 56 PH JUL 31. 2013 6 09 PH
FIRST 0.10 CAL/HR PASS EACH MONTH:
JUL 31. 2013 11!30 ~~
)( * )( M * EtiD M )( * * K
RAMCO EXPRESS 2222 F STREET BAKERSFIELD CA 9:1:101 661-324-1758
DEC 19. 2013 9:56AM
PRESSURE LlflE LEAK TEST HISTORY
Q 3:REGULAR
LAST 3.0 CAL/HR PASS: DEC 19. 2013 9:53AM
FIRST 0.20 GAL/HR PASS
EACH HONTH:
DEC 1. 2013 1 47 AM NOV 1. 2013 1 23 AM
OCT 1. 2013 3 3:1 AM
SEP 1. 2013 2 09 AM AUG 3. 2013 2 23 AM Jut 31. 2013 6 25 PH
FIRST 0.10 GAL/HR PASS EACH MONTH:
M M M M M E~D M M M M M
-----SENSOR ALARM -----L 5:PLUS AWIULAR
ANNULAR SPACE FUEL ALARM DEC 19. 2013 9:59AM
-----SEtSOR ALARM ----L 3:ijEGULAR ANNULAR ANNULAR SPACE-
FUEL ALARM • -.DEC 19. 2013 10:01 AH
~~:
-----SENSOR ALARM -----•
L 1 :SUPER AIINULAR
ANNULAR SPACE FUEL ALARM
DEC 19. 2013 10:03 AM
L
PRESSURE LINE u:AK ALARM
Q 1 :PLUS PLLO SHUTDOWN ALARM DEC 19. 2013 10:15 AH
-----SElSOR ALARM -----L 5:Pt.US ANIIULAR
ANNULAR SPACE
SENSOR OUT ALARH DEC 19. 2013 10:15 AM
PRESSURE LINE LEAK ALARM
Q 2:SUPER
PU.D SHUTDOWN ALARM DEC 19. 2013 10:15 AM
-----SEt:SOR ALARM -----L 1 :SUPER ANNULAR
ANNULAR SPACE
SElSOR OUT ALARM DEC 19. 2013 10:15 AM
PRESSURE LINE LEAK ALARH Q 3:REGULAR
PLLD SHUTDOWN ALARM DEC 19. 2013 10:15 AM
----SElSOR ALARM -----
L 6:REGU!.AR STP
STP Sli1P SEtlSOR OUT ALARH DEC 19. 2013 10!15 AM
-----SElSOR ALARM -----L 2:PLUS STP
STP SU'\P SENSOR OUT ALARM DEC 19. 2013 10:15 AM
-----SENSOR ALARM -----L 3:REGULAR ANNULAR ANNULAR SPACE SENSOR OUT ALARM DEC 19. 2013 10:15 AM
-----SENSOR ALARM -----
L 4:SUPER STP
STP SLtiP SENSOR OUT ALARM DEC 19. 2013 10:15 AM
RAHCO EXPRESS
2222 F STREET BAKERSFIELD CA 93301 661-324-1758
DEC 19. 2013 10:17 AM
SYSTEM STATUS REPORT
L 1 :SENSOR OUT ALARM
L 2 :SENSOR OUT ALARM
L 3:SENSOR OUT ALARM
L 4 :SENSOR OUT ALARM
t. S:SENSOR OUT ALARM
L 6:SEIISOR OUT ALARM
Q 1 :PLLD SHUTDOWN ALARM
Q 2:PLLD SHUTOOWt4 ALARM
Q 3:PLLD SHUTDOWN ALARM
PRESSURE LitlE LEAK ALARM
Q 1 !PLUS GROSS LitlE FAIL DEC 19. 2013 10:43 AM
PRESSURE LINE LEAY. ALARM
Q I :PLUS PLLD SHUTDOWN AI.ARH DEC 19. 2013 10:43 AM
PRESSURE LHIE LEAK AI.ARN Q 2:SUPER CROSS LINE FAIL DEC 19. 2013 10:47 AM
PRESSURE LINE LEAK ALARM
0 2:SUPER PLLD SHUTDOWN ALARM
DEC 19. 2013 10!47 PI-t
PRESSURE LitlE LEAK DJAG DEC 19. 2013 10:54 Al-1
Q 3:REGULAR
3, 0 TEST PASSES ------------PON PI P2
DEC 19. 2013 10:53 AH 29.8 21.5 19.7 DEC 19. 2013 10:51 AM 29.8 18.8 15.4 DEC 19. 2013 10:38 AH 29.8 17.9 14.0
DEC 19. 2013 10:23 AH 22.0 22.0 22.0 DEC 19. 2013 8:53AM 30.3 21.6 21.5
3.0 TEST FAILS ------------PON t~OV 8,
8.9 AUG 18. 30.5
PI P2 2013 I: 15 PM 9.-1 9.7 2013 10:11 AM 9.9 1.1
3.0 HI PRESSURE EVEilTS ------------PON PI P2
NO TEST DATA AVAILABLE d
PRESSURE LitlE LEAl: DIAG DEC 19. 2013 10:55 AM
Q I !PLUS
3,0 TEST PASSES
PON PI P2 DEC 19. 2013 10!37 AM 39.0 21.3 21.0 DEC 19. 201'3 10:32 AM 43.0 21.4 21.1
DEC 19. 2013 10:22 AH 20.9 21.1 21.1 DEC 19· 2013 8:54 AH 39.1 21.2 20.9 DEC 19. 2013 8:43 AH 39,0 21.1 20.8
3.0 TEST FAILS ------------POU PI f'2 DEC 19. 2013 10:43 AP-I 28.7 13.4 6.9
3.0 HI PRESSURE EVEtlTS ------------PON PI P2
NO TEST DATA AVAILABLE
PRESSURE LWE LEAl: DIAG DEC 19, 2013 10:55 AM
Q 2!SUPER
3.0 TEST PASSES
PON PI P2 DEC 19, 2013 10!37 AH 34.7 20.3 20.1 DEC 19. 2013 10!32 AH 36.1 20.4 20.1 DEC 19, 2013 10:22 AH 19.9 19.9 19.9 DEC 19. 2013 8:55 AH
38.7 20.3 20.1 DEC 19. 2013 8:44 AH 39.7 20.4 20.2
3.0 TEST FAILS
PON PI P2 DEC 19. 2013 10:47 AM 29.2 10.2 5.2
3.0 HI PRESSURE EVEtlTS ------------PON PI P2 NO TEST DATA AVAILABLE
PRESSURE I.WE LEAIC DIAG DEC 19. 2013 11:06 AH
Q 3:REGUUtR
3.0 TEST PASSES
POtl PI P2 DEC 19. 2013 11:05 AM 29.9 20.1 17.7 DEC 19. 2013 10:53 AH 29.8 21.5 19.7 DEC 19, 2013 10:51 AM 29.8 18.8 15.4 DEC 19. 2013 10:38 AH 29.8 17.9 14.0 DEC 19. 2013 10:23 AH 22.0 22.0 22.0
3.0 TEST FAILS
PON PI P2 NOV 8. 2013 1:15 PH 8,9 9.4 9.7 AUC 18. 2013 10:11 AM 30.5 9.9 1.1
3.0 HI PRESSURE EVEtlTS
PON PI P2
NO TEST DATA AVA I !.ABLE
RAHCO EXPRESS 2222 F STREET BAJ<ERSFIELD CA 93301 __
661-324-1758 -·--·-
DEC 19, 2013 II :45 AM
S'IST£11 STATUS REPORT
Q I :GROSS !.HIE FAIL
Q I :PLLD SHUTDOWN ALARM
Q 2:GROSS LINE FAIL
Q 2 :PLI.O SHUTDOIJil ALARM
RAMCO EXPRESS
2222 F STREET BAKERSFIELD CA 93301 661-324-1756
DEC 19. 2013 11:48 AH
SYSTEM STATUS REPORT
AlL FUNCTIOUS NORW\1.
RAMCO EXPRESS
2222 F STREET BAKERSFIELD CA 93301 661-324-1758
DEC 19. 2013 11!48 AH
SYSTEM STATU$ P.EF'ORT
ALL futlCTlONS tiORtii-\L
SWRCB, January 2006
Spill Bucket Testing Report Form
This form is intended for use by contractors pe1jonning annual testing of UST spill containment stmctllres. The completed fonn and
prinrows from tests(!( applicable), should be prOI'ided to thefacility ownedoperatorfor submittal to the local regulatOI)' agency.
1. FACILITY INFORMATION
Facility Name: Ramco Ex ress I Date ofTestins: 12/19/2013
Facility Address: 2222 F Street Bakersfield, CA 93301
Facility Contact: Rami I Phone: 818-339-7288
Date Local Agency Was Notified of Testing: 12/13/13
Name of Local Agency Inspector (if present during testing): Emie Medina
2. TESTING CONTRACTOR INFORMATION
Company Name: Confidence UST Services
Technician Conducting Test: Kristopher Kams
Credentials1: IRl CSLB Contractor IRl ICC Service Tech. IRI SWRCB Tank Tester 0 Other (Specify)
License Number(s): CSLB# 804904 ICC# 5264406-UT IT# 09-1743
-
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: Lake IRl Hydrostatic 0 Vacuum I l Other
Test Equipment Used: Lake Test Equipment Resolution: 0.0625"
Identify Spill Bucket (By Tank 1 Regular 2 Plus 3 Super 4
Number, Stored Product, etc.)
IRl Direct Bury IRl Direct Bury IRl Direct Bury 0 Direct Bury Bucket Installation Type: 0 Contained in Sump Contained in Sump ' Contained in Sump r Contained in Sump 1
Bucket Diameter: 12.00" 12.00" 12.00"
Bucket Depth: 11.25" 11.25'' 11.25"
Wait time between applying 5min. 5m in. 5rnin. vacuum/water and start of test:
Test Start Time {T1): 9:00am 9:00am 9:00am
Initial Reading {R1): I 0.00" 9. 75" 10.00"
Test End Time {TF): !O:OOam I O:OOam I O:OOam
Final Reading (~:): 10.00" 9.75" 4.00"
Test Duration (TF-T1): I Hour I Hour I !lour
Change in Reading (Rf-R1): 0.00" 0.00" 6.00"
Pass/Fail Threshold or 0.0625" 0.0625" 0.0625" Criteria:
Test Result: X Pass OFail X Pass 0 Fail 0 Pass X Fail 0 Pass OFail
Comments -(include i11(onnation on repairs made prior to testing, and recommendedfol!oll'-upforfailed tests)
91 OPW Direct Burial Spill Bucket failed and needs to be replaced.
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING TillS TESTING
I hereby certify that all the information con ained in_tl is report is true, accurate, and in full compliance with legal requirement.\:
Technician's Signature: Date: 12/19/2013
1 Stale laws and regulations do not currently require testing to be performed by a qualified contractor. However, local
requirements may be more stringent.
i
• Gl G •
·D. d,uns d!S ,;,tn~
0 Gl G 0 r/£
JeSU'di!l] dtun~ diS Jel!l!>lj
,~, 1: Q G
l{lO(o' Z/1 dwns dlS snld
J?suariSI()
QiOUWli ,.;g c fJS =!
~l\'=~
on.:=s
10H61fJ Pl''1im1ea J·:.!u;s 6Cr =t
:~Gtl) :J lZZZ ~~:v· s~z =£
ss~1Jq o;lJelj YliJ'.'•S 0' 3=('
1ou~d loqpcp<«A = r