HomeMy WebLinkAbout2011 RESULTSLk 31S
MONITORING SYSTEM CERTIFICATION.
For Use By All Jurisdictions Within the State of Cgli ,brnid
Authority Cited Chapter 6 7, Health and Safety Code; Chapter .16, lair ision 3;. Title 23, California Code of Rekulaticns
Thais form must be used to document testing and servicing of monitoring equipment. A separate certification or report must beoreoared :or gac11
monitoring tstem control Hanel by the technician who performs the work. A copy of this"'fortn mustbe.provided to the tank system ownerfopetator.
The owner /operator must submit a copy of this form to the local agency regulating USl systems Within, 30 days of test. date.
A. General Information
Facility Name: MOBIL STATION
Site Address: 13001 STOCKDALE AVENUE
Facility Contact Person: _
Make/Model of Monitoring System: TLS -350
B. Inventory of Equipment'. Tested /Certified
Check the appropriate boxes to indicate specific equipment inspected/serviced:
Bldg. No.:
City: BAKERSFIELD Zip: 93312
Contact,Phone -No.: ( )
Date of Testing/Servicing: 10/412011
Tank iD: 87 SYPHON
Tank iD: 87 MASTER'
®'In-Tank Gauging Probe.
Model: MAG -1
® In -Tank Gauging, Probe.
Model: MAG -1
®.Annular Space or Vault Sensor.
Model: 409
0 Annular-Space or Vault Sensor,
Model: 409
0 Piping Sump / Trench Sensor(s).
'Model: 208
® Piping Sump /Trench Sensor(s):
Model: 208
❑ Fill.Sump Sensor(s).
Model:
[] Fill Sump Sensor(s).
Modei.
® Mechanical Line Leah Detector.
Model RED JACKET
® Mechanical Linc.Leak Detector..
Model` RED JACKET
[Q Electronic Line Leak Detector,
Model:
❑ Electronic Line Leak Detector:
Model:
Tank .Overfill / High -Level Sensor.
Model: BALL FLOAT.
❑ yank Overfill-/ Nigh -Level Sensor:
Model:
❑ Other (Specify equipment n-pe and model in Section E on Page 2).
❑ Other (specify equipment type and model in Section E on 6ge 2).
,Tank..im DIESEL
Tank ED: 97.
Z'in =Tank Gauging Probe.
Model: MAG -1
M In -Tank Gauging Probe.
Model: MAG -1
S Annular Space or Vault Sensor.
Model: 409
® Annular Space or Vault Scnsor.
Model: 409.
2 Piping Sump / Trench Sensor(s).
Model: 208
® Piping Sumi5l 1 rench`Sensor(s).
Model: 208
❑ Fill Sump Sensor(s),
Model:
❑ Fill Sump Sen. s):
Model:
® Mechanical Line Leak Detector.
Model: RED JACKET
Mechanical Lim,LeA Detector:
Model: RED JACKET
❑ electronic Line ILA Detector.
Model:
❑ Electronic Line Le k- Detector.
Model:
® Tank Overfill i Fligh -Level Sensor,
Model: BALL FLOAT
® Tank'Overfill. /'High -Level Sensor;
Model: BALL:FLOAT
❑ Other (specify equipment type and
model in Section E on Page 2).
❑ Other f specifyequi equipment p t}pe :and "maxleLin Section E on rage 2).
Dispenser ID: 132
Dispenser ID 314
9 Dispenser Containment Sensor(s).
Model: 01
®Dispenser Containment. Sensor(s)...
Model: 01
® Shear Valve(s).
® Shear Valvefs).
tD'Uispenser Containment Float(s) a nd.Chain(s).
El Dispenser Containment ;Float(s) :and
Dispenser ID: -718
Chain(s).,
Dispenser ID: _516
® Dispenser Containment Scnsor(s).
Model: 01
® Dispenser Containment Sensor(s).
Model: 01
® Sheai Valve(s).
® Shear Valve(s).
❑ Dispenser Containment Fkmt(s) and
Chain(s).
❑ Dispenser Containment Float,(s) and
Chain(s).
Dispemer ID:
Dispenser ID:
Q 1)'aspenser Containment Sensor(s).
Model:
❑ Dispenser Containmeni.Sensor(s).
Model:
Shear Valvets).
❑ Shear Valve(s).
❑ Dispenser Containment Float(s) and Chain(s).
❑ Dispenser (outaidiTient Floats) and Chain(s)_
*If.the facility contains more tanks or dispensers, copy this form. Include information for evdiy tank and dispenser at the facility.
C. Certification - i certify that the equipment identified in this document was inspectedlserviced in accordance with the manufacturers'
guidelines. Attached to this Certification is information (e.g. manufacturers' checklists) necessary to verify that this information is
correct and a Plot Plan showing the: layout of monitoring a uipment. For any equipmenfcapable generating such reports, I have also
attached a copy of the report; (check all that apply): System set -up Alarm h' " rv' report
Technician Name (print): RICH PHILLIPS Signature:
Certification No.: A2908411036169-UT License. No. 11 D40. 809850-
Testing Company Name: RICH ENVIRONMENTAL `Phone No.c (661),392 -8687
Testing Company Address: 5643 BROOKS CT. BAKERSFIELD, CA 93308 Date of Testing Servicing: 10/412011
Page 1 of 5
CN -036— t/t www.unidoes.org. Rev. 01, /17M
• Monitoring System Certification
j D. ,Results of Testing /Servicing
Software Version Installed: 330.01
Complete the followine checklist:
46-151-, /
® Yes ❑ No',' Is the audible alarm operational?
®; Yes ❑ No* Is the visual alarm operational?
0 Yes ❑ No* Were all sensors visually inspected, functionally tested, and confirmed operational?
Yes ❑ No* Were all sensors installed..at lowest point of secondary containment:and positioned so that.other equipment will
not interfere'with''their proper operation?
❑ Yes ❑ No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem)
0 N/A operational?
23 Yes ❑ No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
❑ N/A monitoring system detects a leak, fails to operate, or is eiectncally:disconnected? If'yes: which sensors initiate
positive shut - down? (Check all that apply) ® Sumpi french. Sensors, ❑ Dispenser Containment Sensors.
Did you confirm positive shut -down due to leaks and sensor failure /disconnection? ® Yes: 0 No. li
® Yes
❑ No's
I For tank systems that utilize the monitoring system as the primary tank overfill warning device (Le., no
❑ N/A
( mechanical overfill 'prevention valve.is installed), is the overfill warning aiat7tl visible and audible at the tank
fill point(s) and operating properly? If so, at what percent of tank capacity does` the alarm trigger? %
❑ Yes*
®No
T�ist any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced
the manufacturer name and model for:ail replaceme3it parts:in Section E, below.
0 Yes*
® No
Was liquid found inside any secondary containment systems designed. as dry systems? (Check all that.apply)
❑ Product; ❑ Water. If yes, describe causes in Section.E; below.
(� Yes
❑ No*
Was monitoring system set -up reviewed,to ensure proper settings ? - Attach set-up,reports inapplicable
® Yes
❑ No*
is all monitoring equipment operational per manufacturer's specifications?
} In Section E_below, describe how and when these deficiencies were or will be corrected.
E. Comments:
Page 2 of $
LTM1i4136 — 2/4 www.unidoes.org Rey. 01 /17/08
Monitoring System Certification
F. In -Tank Garaging / SIR Equipment:
lV3't5Z— /
❑ Check this box 1f tank gauging is used`only for inventory control,
❑ Checicthis box'ifnoaank'gauging of SIR equipment is installed.
This section must be completed if in -tank gauging equipment is used to .perform leak. detection monitoring.
Complete the - following checklist-
0
Yes
❑ No*
Has all input wiring been inspected for proper entry and termination; including testing for D ound faults?
s?
Yes
0 No*
Were all tank gauging probes visually inspected for damage acid residue buildup?
Yes
❑ No*
Was accuracy of system product level readings.tested?
0 Yes
❑ No*
Was accuracy of system water level readings tested?
❑ Yes
❑ No*
Were all probes reinstalled properly?
❑ Yes
❑ No"
I Were all items on the equipment manufacturer's maintenance checklist completed?
" In Section % below, describe how and when these deficiencies were or will be corrected.
G. Line Leak (Detectors (LLD):
Complete the following checklist:
❑ Check ibis box if LLDs are not installed:
Z Yes
❑ No* '
For equipment start -up or annual equipment certification, was a leak simulated to: verify LL,D perforr ance? i
❑ 'N /A
(Check ail that apph) Cumulated leak rate: ®.3 g.p.h.; O.Q. I g.p.h ; 0.02 g.p.h.
Yes
❑ No*
Were all LLDs confirmed operational and accurate within regulatory requirements?
® Yes
❑ No*
Was the testing apparatus properly calibrated?
[3 Yes
❑ No*
For mechanical LLDs, does the -LLD restrict product flow if it detects a leak?:
❑ N/A
[] Yes-
❑ No*
For electronic LLDs, does. the turbine automatically shut off if the LLD detects a leak;'
® N/A
❑ Yes
❑ No*
For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled
® N/A
or disconnected?
❑ Yes
❑ NO
For electronic LLDs, does the turbine automatically shut off if.any portion of the manitonng system malfunctions
0 N/A
or fails a test? �
0 Yes
❑ No's
For electronic LUDs, have all accessible wiring connections been visually inspected ?`
,RI N/A
9 Yes
❑ No*
Were all items on the equipment manufacturer's maintenance.checklist completed?
* In Section H; below, describe how and when these deficiencies were or will -be corrected.
110. Comments:
Page 3 of 5
UN-036 — 3/4 www.unidomorg Rev. 01 /17108.
Monitoring System Certification Form: Addendum for Vacudm/iPressure Interstitial. Sensors
I. Results of Vacuum /Pressure Monitoring Equipment 'Testing
W 3ZSZ.. ei�
r
This page should be used to document testing and servicing of vacuum and pressure interstitial, sensors. A copy of
this form, must be included with the Monitoring System Certification Form, which must be provided to the tank
system owner /operator. The owner /operator must submit a copy of the Monitoring. System `Certification Form to the
local agency regulating UST systems within 30 days of test date.
Manufacturer: NONE Model:
System Type: ❑ Pressure; ® Vacuum
Sensor ID
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: ❑ Pass; ❑ Fail Interstitial'Communication°Test :Result: ❑ Pass; ❑ Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result; ❑ Pass; ❑ Fail Interstitial Communication Test Result: ❑ Pass; ❑ Fair
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: ❑ Pass; ❑ Fail Interstitial Communication Test Result: ❑ Pass; ❑ Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: ❑ Pass; ❑ Fail Interstitial �Communication Test Result: ❑ Pass; ❑ .Fail.
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: ❑ Pass; ❑ Fail Interstitial'Comniunication Test Result: ❑ Pass; Ej Fail .
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: ❑ Pass; ❑ Fail Interstitial Communication Test Result: ❑ Pass; ❑ . Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result ❑ Pass; ❑ Fail Interstitial'Communication Test Result:' ❑ Pass; ❑ Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: ❑ Pass; ❑ Fail Interstitial Communication 'Test Result: ❑ Pass-, ❑ Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: ❑ Pass; ❑ Fail Interstitial Communication Test Result: ❑ Pass; ❑ Fail
Components) Monitored by this Sensor:
Sensor Functionality Test Result: ❑ Pass; ❑ Fair Interstitial Communication Test Result;, ❑Pass;, ❑; Fail,
How was interstitial communication verified?
❑ Leak Introduced at Far End of Interstitial Space;' El Gauge; [] Visual Inspection; ❑ Other'(Describe in Sec., J, below)
Was vacuum /pressure restored to operating levels in all interstitial spaces? ❑ Yes ❑ No (If no, describe in Sec. J, below)
J. Comments: NONE OF THESE SENSORS ARE PRESENT AT THIS SITE.
Page 4 of 5
` If the sensor successfully detects a simulated vacuum /pressure leak' introduced in the interstitial space at the finthest point from the
sensor, vacuum/pressure has been demonstrated to be communicating throughout the interstice.
LIN -036A - 1/1 www.unidocs org Rev. 01/26/06
Monitoring System Certification
UST Monitoring Site Plan
Site Address: % 3 VO i r7-4(-
N3'tSZ
Date map was drawn: 10
Instructions
If you already have a diagram that shows all required information, you may include it, rather than this page, with your" Monitoring
System Certification. On your site plan, show the general layout of tanks and piping. Clearly identify locations of the following
equipment, if installed: monitoring system control panels; sensors monitoring tank annular spares,. sumps, dispenser pans, spill.
containers, or other secondary containment areas; mechanical or. electronic 'line..leak. detectors; and in -tank- liquid level probes (if used
for leak detection). In the space provided, note the date this Site Plan was prepared.
UN -036 = 4/4
Page 5 of 5
www:anidomorg
Rev. 01/17/09
1
SWRCB; January 2006
Spill Bucket Testing Report, Form
This form is intended for use by conrractors performing annual testing of UST spill containment structures. -The. completed form and.
printouts from, tests (if applicable), should be provided to the facility ownerloperator fur submittpl to the local reguluiofy. agency.
1. FACILITY INFORMATION
Facility Name: MOBIL STATION Date of T'esting`. 10/4/11
Facility, Address: 13001 STOCKDALE HWY, BAKERSFIELD
Facility Contact:
Phone: 4
bate Local Agency Was Notified of Testing: 8/18/,11
Name of Local. Agency Inspector (j present during testing):
2. TESTING CONTRACTOR INFORMATION
Company Name: RICH ENVIRONMENTAL
Technician Conducting Test: RICH PHILLIPS
Credentials': :'i CSLB Contractor X 1CC Service Tech, Q SWRCB Tank Tester 0 Other-(Specify _
License Number(s): 1035169 -UT
3. SPILL BUCKET TESTING.INFORMAATION
Test .Method Used: X Hydrostatic [I Vacuum ::i Other
Test Equipment Used: VISUAL
Equipment Resolution: 0.
Identify Spill Bucket (Av Tank
Number, Stored Product,
.491
I WESEL
287-S
3'87 -M
Bucket Instal iation Type:
Direct Bury
X Contained in Sump
❑ Direct Bury
X Contained in Sam p_.
0 Direct.Bury
X:Contained in Sump
❑Direct Bury
X Contained in Sump
`Bucket Diameter:
12"
12"
12"
12"
Bucket Depth
14"
14"
14"
14"
'Wait time between applying
vacuum/water and start of test:
30 MIN
30 MIN
30 MIN
30'M1N
Test =Start Time (T,):
9 :00
9:00
9:00
9 :00
Initial Reading (Rj):
14"
14"
14"
14"
Test End Time (Tr):
10:00
10:00
10:00
10:00
Final Reading (RF):
14"
14"
14"
14'
Test, Duration (TF — T;):
1 -HOUR
1 -HOUR
1 -HOUR
1 -HOUR
Change in Reading (R: - Ri):
.000
.000
000
.000
PassiFail Threshold or
Criteria:
a,.k,•,e.;...�,..•,,_.rr.
/-0.00
+/-0.00
•)
+/- 0:00
, y:. _
+/- 0.00 f
."° ?t'::;,i�lf.
Comments — (include information on repairs made-prior to- testing and recommended follow -up for failed'tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING T141S TESTING
I herehv certify that ali the information contaipof in this report is true, accurate,: and infull compliance with legal requirenteitts.
Technician's Signature:_ ^_ Date: _10,14/I'l
} State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
(Alb'iSZ/
RICH ENVIRONMENTAL
5643 BROODS CT. BAKFRSFIELD, CA. 93308
OFFICE (661)392 -8687 FAX {661)397 -0621
PRODUCT LINE LEAK DETECTOR TEST
WORK SHEET
FACILITY NAME: MOBIL STATION
FACILITY ADDRESS: 13001 STOCKDALE HWY, BAKERSFIELD
PRODUCT LINE TYPE: PRESSURE
PRODUCT � LEAK DETECTOR TYPE
TEST
TRIP
PASS
BELOW
P.M.
OR
SERIAL NUMBER
3 G.P.H.
FAIL
DIESEL
L/D TYPE: RED JACKET I
YES
11
PASS I
^ i
SERIAL #_ I
i
i
LID TYPE: RED JACKET
YES
11
PASS i
i
SERIAL # _
0
91
L/D TYPE. RED JACKET
I YES
10
PASS
f
i SERIAL # -
L/D TYPE.-
YES
PASS
SERIAL # -
T
n O
FA%L �
1. CERTIFY THE ABOVE TESTS WERE CONDUCTED ON THIS DATE ACCORDING TO RED
JACKET PI -IMPS FIELD TEST APPARATUS TESTING PROCEDURE AND LIMITATIONS.
THE MECHANICAL LEAK DETECTOR TEST PASS / FAIL. IS DETERMINED BY USING A
LOW FLOW THRESHOLD TRIP RATE OF 3 GALLONS PER HOUR-OR LESS AT 10 P.S'L I
ACKNOWLEDGE THAT ALL DATA COLLECTED IS TRUE AYD'CORRECT TO THE BEST
OF MY KNOWLEDGE.
TECHNICIAN: RICH PHILLIP
SIC NATURE: DATE: 10 /4 /11
SOFTWARE REVISION LEVEL
VERSION 330.01
SOFTWARE# 346330 -100 -B
CREATED - 10.07.23.17.25
S- MODULE# 330160 -004 -a
SYSTEM FEATURES:
PERIODIC IN -TANK TESTS
ANNUAL IN -TANK. TESTS
ISD
f
SYSTEM ^SETUP - - - - -
OCT 4. 2011 13:25 AM
SYSTEM UNITS
U.S..
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE /TIME FORMA'r
MON DD YYYY HH : fIM1: SS xM
MOBIL
1300,1 STOCKDALE HWY
BAKERSFIELD CA
SHIFT T I 1'1E 1 DISABLED
SHIFT TIME 2 DISABLED
SHIFT. TIME 3 DISABLED
SHIFT TIME 4 DISABLED
TANK PER TST NEEDED WRN
DISABLED
TANK ANN TST NEEDED WRN
DISABLED
LINE RE- ENABLE METHOD
PASS LINE TEST
LINE PER TST NEEDED WRN
DISABLED
LINE ANN TST NEEDED WRN
DISABLED
PRINT TC VOLUMES
ENABLED
TEMP COMPENSATION
VALUE (DEC F ): 60.0
STICK HEIGHT OFFSET
DISABLED
ULLAGE: 90%
H- PROTOCOL DATA FORMAT
HEIGHT
DAYLIGHT SAVING TIME
DISABLED
RE- DIRECT LOCAL PRINTOUT
DISABLED
EURO.PROTOCOL PREFIX
S
031., 1-1'I NGv UJ'il 1 3 "'
SIPHON MANIFOLDED TANKS
*,b4��
CODE : 000000
RS�2.32; SEC UR:ITY
LINE MANIFOLDED TANKS
MAINTENANCE HISTORY
T#: NOME
i
DISABLED
AUTO TRANSMIT SETTINGS:
LEAK MIN PERIODIC: 0�
i
RS-232 END OF MESSAGE
TANK CHART SECURITY
D'ISABLED
bISABI;ED
DISABLED
AUTO HIGH WATER LIMIT i
0
CUSTOM ALARMS
AUTO OVERFILL LIMIT
DISABLED
DISABLED
PERIODIC TEST TYPE
SERVICE NOTICE
STANDARD
DISABLED
DISABLED
AUTO THEFT LIMIT
ANNUAL TEST FAIL
ISO 3166 COUNTRY-
I`N -TANK SETUP
AUTO DELIVERY START
CODE:
- - - - - _ - -
- - -
AUTO DELIVERY END
T 1:.87 SIPHON
DISABLED
MASS:DENSITY
PROD C•ODE
1
DISABLED
.UCT'
THERMAL COEFF :.400740
AUTO EXTERNAL INPUT OFF
TANK DIAMETER
96,00
AUTO SENSOR.FIJEL ALARM
TANK PROFILE
I PT
FULL.VOL
10000
DISABLED
FLOAT SIZE: 4.0 IN.
AUTO SENSOR OUT ALARM
WATER WARNING
2.0
HIGH WATER LIMIT:
3.0
MAX' ;OR' LABEL VOL:
10000
OVERFILL 1.'IMIT
COMMUNICATIONS SETUP
9.000
- - - - - - - - - - - -
HIGH PRODUCT
5%
99
DELIVERY LIMIT
f PORT SETTINGS:
.
1000
COMM BOARD : 1 (EDIM )
LOW PRODUCT
1000
RS-232 SECURITY
LEAK ALARM LIMIT:
99
CODE : DISABLED
SUDDEN LOSS LIMIT:
99
TANK TILT
0,00
COMM BOARD 2 (RS -232)
PROBE OFFSET
0.00
BAUD RATE : 1200
PARITY ODD
STOP BIT : 1 STOP
SIPHON MANIFOLDED TANKS
DATA LENGTH, DATA
Tit: , 02
RS�2.32; SEC UR:ITY
LINE MANIFOLDED TANKS
CODE-: DISABLED
T#: NOME
i
AUTO TRANSMIT SETTINGS:
LEAK MIN PERIODIC: 0�
0
bISABI;ED
LEAK MIN ANNUAL
AUTO HIGH WATER LIMIT i
0
DISABLED
AUTO OVERFILL LIMIT
DISABLED
PERIODIC TEST TYPE
AUTO LOW PRODUCT
STANDARD
DISABLED
AUTO THEFT LIMIT
ANNUAL TEST FAIL
DISABLED
ALARM DISABLED
AUTO DELIVERY START
DISABLED
PERIODIC TEST FAIL .
AUTO DELIVERY END
ALARM DISABLED
DISABLED
AUTO EXTERNAL INPUT ON
GROSS: TEST FAIL
DISABLED
ALARM DISABLED
AUTO EXTERNAL INPUT OFF
DISABLED
ANN TEST AVERAGING: OFF
AUTO SENSOR.FIJEL ALARM
PER TEST AVERAGING: OFF
DISABLED
AUTO SENSOR WATER ALARM
TANK TEST NOTIFY: OFF
DISABLED
AUTO SENSOR OUT ALARM
TNK TST SIPHON 8REAK:OFF
DISABLED
DELIVERY DELAY 5 MIN
PUMP THRESHOLD. 10,00'-
43152_
T 4:1SUPEIR
PRODUCT CODE
4
T 3: D I EBEL
THERMAL COEFF :.o
obo
' 0
T 2:87 REC�
PRODUCT CODE 3
TANK D.IAHETtR
96.60
PRODUCT CODE
THERMAL COEFF :.000450
TANK PROFILE' F
'I PT
2
THERMAL COEFF 000700
TANK DIAMETER 96-00
FULL VOL :
1.0000
TANK-DIAMETER 96.00
TANK PROFILE I PT
TANY.PROFILE
FULL VOL 10000
I PT
FULL VOL 10000
FLOAT 8111I.£* 4.0
IN.
FLOAT SIZE: 4.0 IN•
WATER WARNING
2.0
FLOAT S 1 4.0 IN.
HIGH WATER LIMIT:
3.0
WATER WARNING 2.0
,WATER WARNING 2.0
HIGH WATER LIMIT: 3,0
MAX OR LABEL VOL:
1,0000
-"
HIGH WATER LIMIT: 3.0
OVERFILL LIMIT
95%
MAX OR LABEL VOL: 10000
9500
MAX OR LABEL VOL: loono
OVERFILL LIMIT 95%,
HIGH. PRODUCT
901
OVERFILL LIMIT 90%
9500
HIGH P 0%
PRODUCT 9
'DELIVERY LIMIT
9000
15%
HIGH PRODUCT 9000
9000
1500
95%
DELIVERY L 1111T 9500
DELIVERY LIMIT 15%.
15011
LOW PRODUCT.,
1000
10%
LEAK ALARM ,LIMIT;:
59
1000
LOW PRODUCT 1000
SUDDEN LOSS LIMIT.
99
LOW PRODUCT I li- 0 o
LEAK ALARM LIMIT: 99
TANK TILT
0.00
LEAK ALAR11 LIMIT: 99
SUDDEN LOSS LIMIT: 99
PROBE OFFSET,
0.00
SUDDEN, LOSS LIMIT 99
TANK TILT 0.00
-TANK TILT 0.00
PROBE OFFSET
PROBE OFFSET 0.00
SIPHON MANIFOLDED TANKS
0.00
TO' NONE
SIPHON IIAP41FOLDED TANX-S
LINE:MAN,IFOLDED TANKS
SIPHON MANIFOLDED TANKS
TO: NONE
TO: NONE
TO: 01
LINE MANIFOLDED TANKS
LINE MANIFOLDED TANKS
TO: NONE
T#: NONE
EAM I N PER I OD I C'
0%
LEAK MIN PERIODIC: 0%
EAK MIN PER I OD I C:
0
LEAK MIN ANNUAL
01%
0%
0
0
LEAK MIN ANNUAL 0*/*
XAX 111 N ANNUAL : 0%
0
PERIODIC TEST TYPE
0
STANDARD
PERIODIC TEST TYPE
'ERIODIC TEST TYPE
STANDARD
ANNUAL TEST FAIL.
ALARM DISABLED
STANDARD
ANNUAL TEST FAIL
,wNUAL TEST FAIL
ALARM DISABLED.
PERIODIC TEST FAIL
ALARM DISABLED
ALARM DISABLED
PERIODIC TEST FAIL
ERIODIC TEST FAIL
ALARM D I 3ABLED
GROSS 'TEST , FA I I,
ALARM DISABLED
ALARM DISABLED
I
GROSS TEST FAIL
I
ROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAG I'W-::
OFF
ALARI-1 DISABLED
PER TEST AVERAGING:
OFF'..
ANN TEST AVERAGING: OFF
IN TEST AVERAGING:
PER TEST AVERAGING: OFF
TANK TEST NOTIFY:
OFF
OFF
R TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK,TST SIPHON BREAK:OFF
. 4NK TEST NOTIFY' OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY
5 MIN
TST SIPHON BREAK:OFF
PUMP THRESHOLD
10.00%
DELIVERY, DELAx' 5 MIN
,LIVERY RELAY 5 M IN
PUMP THRESHOLD 10.00%
IMP THRESHOLD lfj.[)O%
LEAK TEST METHOD
.TEST ON DATE ALL TANK
JAN 29. 2009
START TIME : DISABLED
TEST RATE :0.20 GAL /HR
DURATION 2 HOURS
TST EARLY STOP, D I lsi)BLED
LEAK TEST REPORT FORMAT
NORMAL
i
LIQUID SENSOR SETUP
L 167 STP SIPHON
TRI -STATE (SINGLE FLOAT)
CATEGORY : STP SUMP
H
2:87 ANNULAR
TRI -STATE (SINGLE FLOAT)
,ATEGORY ANNULAR SPACE
3:87 STP
,RI-STATE '( SINGLE FLOAT)
TEGORY STP SUMP
k
4:87 ANNULAR SIPHON
' I- STATE (SINGLE FLOAT)
'ATEGORY : ANNULAR SPACE
5:DIESEL STP
RI--STATE (SINGLE FLOAT)
4;TRGORY : STP SUMP
'6:DikSEL ANfVULAR
RI -STATE (SINGLE FLOAT)
~TEGORY ANNULAR SPACE
7:91 STP
�I -STATE (SINGLE FLOAT)
TEGORY : STP SUMP
4
T
91 ANNULAR
-STATE (SINGLE FLOAT)
EGORY ANNULAR SPACE
OUTPUT RELAY SETUP:
R 1:87 SHUTDOWN'
TYPE,)
STANDARD
NORMALLY CLOSED
TANK #: 2
LIQUID SENSOR ALMS
L 1 :FUEL ALARM
L 3:FUEL ALARM
L I:SENSOR OUT ALARM
L 3 :SENSOR OUT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD . VP, PRES FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL :DEGRD COLLECT FAIL
ALL :FLOW COLLECT FAIL
R 2 :91 SHUTDOWN
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: 4
LIQUID SENSOR ALMS
L ?:FUEL ALARM
L 7:SENSOR OUT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
.ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT.FA1L
R 3 :DIESEL SHUTDOWN
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: NONE
LIQUID SENSOR ALMS
L 5:FUEL ALARM
L 5:SENSOR OUT ALARM
SMARTSENSOR SETUP
g I':'VAPOR PRESSURE
CATEGORY VAPOR PRESSURE
2::GARBON CAfVISTOR
CATEGORY VAPOR VALVE
s 3:DIS. 5 -6
CATEGORY AIR FLOW METER
CATEGORY AIR.FLOW.METER
7 -8
CATEGORY AIR FLOW METER
g 6 :DI5,. 1-2
CATEGORY AIR FLOW METER
s 8:
:ATM
CATEGORY ATM P SENSOR
EVR /ISD SIrTUP
EVR TYPE:: BALANCE
BALANCE NOZZLE TYPE
V8T
VEEDER ROOTSPOLISHER
ANALYS_12 TIMES
TIME! 10:•bOI AM.
ACGEPT..HIGH ORVR:
;DISABLED
w' I SD HOSE TABLE
ID' FP FL HL AA RR
01 01 01 02 04 02
-02 02 02 02 04 02
X03 03 03 02 02 02
04 04 04 02 02 02
05 05 05 02 01 02
`06 06 06 02 01 02
-07 07 07 02 03 02
08 09 08 02 03 0•?
�Y
'ISD AIRFLOW METER MAP
`*ID SERIAL NUM LABEL
1 3897fi� - - - -- DIS. -5 -6 --
2 36596 DIS.3 -4
3 389.82 DIS. 7 -8
4 38266 DIS. 1 -2
ISD FUEL GRADE HOSE MAP
1 2 3 4
FP MHH MHH 11HH MHH AA
r-----------------------
U1 101 901 201 U U 4
<02 102 902 202 U U 4
;03. 1.03 903 203 U U 2
X04 10:4 904 204 U U 2
05.105 905 205 3 U 1
06 .106 906 206 3 U 1
07 107 907 207 3 U 3
;08 208 908 108 3 U 3
LABEL TABLE
.�I UNASSIGNED
j2:. HLEND3
'x3: REGULAR
4: MID GRADE
`5: .PREMIUM
° 6 GOLD
7: BRONZE
8: SILVER
r -,9: BLEND2
1,O: HLEND4
t
WL SETUP
410 VERSION: 01.03
1APOR PROCESSOR TYPE
fEDER -ROOT POLISHER
ALARM HISTORY REPORT
----- SENSOR ALARM - -_
L 1 :87 STP SIPHON
STP SUMP
SENSOR OUT ALARM
OCT 4, 2011 9:38 AM
FUEL ALARM
OCT 4, 2011 1 9:15 All
FUEL AL14RPI
MAR 21.. 2011 6:36 PP9
ALARM HISTORY REPORT
SENSOR ALARM
L 2:87 ANNULAR
ANNULAR SPACE
SENSOR OUT ALARM
OCT 4, 2011 9:38 AM
FUEL ALARM
OCT 4, 2011 9:27 AM
ALARM HISTORY REPORT
- - - -- SENSOR ALARM - - - --
L 3:87 STP
STP SUMP
SENSOR OUT ALARM
OCT 4. 2011 9 :36 AM
FUEL ALARM
OCT 4, 2011 9:15 AM
FUEL ALARM
MAR 3, 2011 2:38 PM
ALARM HISTORY REPORT
SENSOR ALARM
L 4 :87 ANNULAR SIPHON
ANNULAR SPACE
SENSOR OUT ALARM
OCT 4. 2011 9:36 AM
FUEL ALARM
OCT 4, 2011 9:24 AM
ALARM HISTORY REPORT
- - - -- SENSOR ALARM
4 5 :DJESEL STP
STP SUMP
SENSOR O1JT ALARM
00T 4, 2011. 9:38 AM
FUEL. ALARM
- ° , 4, 2011 9:1-5 AM
ALARM HISTORY REPORT
- - - -- ,SENSOR ALARM -. - = -�
L 6.:DIESEL ANNULAR
ANNULAR -SPACE
SENSOR OUT ALARM
OCT- 4., 2011 9 :38 AM
FUEL ALARM
OCT 4. 2011 9:22 W
.ALARM HISTORY REPORT
�k3isz �,
- - - -- SENSOR. ALAR11 - - - --
L 7:91.OTP
STP :SUMP
SENSOR OUT ALARM
OCT' 4 , 2011 9': 38 AM
FUEL ALARM
OCT 4, 20111 9::16 AM
FUEL ALARM,
DEG '18, 2010 5 :07 PM
ALARM H I STOR'!. RET''ORT
------ SENSOR'ALARM
L B -::91 ANNULAR
ANNULAR SPACE.
SENSOR OUT .ALARM
OCT 4, 2011 9:38 AM
!:ILL AL'
IS1 -1
OCT 4, 2011 9 :18 AM
MONITOR CERT. FAILURE REPORT
SITE NAME: /y11> X31 L DATE: fl, --'�
ADDRESS: / 3 oo t rroc,k —p bt' Il wy TECHNICIAN:
CITY: IJA 66-a� i L SIGNATURE:
REPAIRS:
NONE
PARTS INSTALLED:
NONE
THE ABOVE NAMED PERSON TAKES ]FULL RESPONSIBILITY. OF NOTHrYING
THE APPROPRIATE PARTY TO HAVE CORRECTIVE ACTION TAKEN TO REPAIR
THE ABOVE LISTED PROBLEMS AND NOTH YING RICH ENVIRONMANTAL FOR
ANY NEEDED RETESTING. THIS ALSO RELEASE&RICH ENVIRONMENTAL OF
ANY FINES OR PENALTIES OCCURiNG FROM NON- COMPLIANCE.
A COPY OF THIS DOCUMENT HAS BEEN LEFT ON-SITE FOR -YOUR
CONVIENENCE.