HomeMy WebLinkAbout2012 RESULTSAppendix VI (Copies of Monitoring System Certification form and UST Monitoring Plot Plan available at http: //www.waterboards.ca.gov.) MONITORING SYSTEM CERTIFICATION For Use By All Jurisdictions Within the State of California Authority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner /operator. The owner /operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date. A. General Information Facility Name: ARCO AMPM 01960 Bldg. No.; Site Address: 1701 Brundage Ln. City: Bakersfield Zip: Facility Contact Person: Ron Rogers Contact Phone No.: (-) Make /Model of Monitoring System: Veeder Root TLS 350 Date of Testing /Servicing: 5 / 23 / 2012 B. Inventory of Equipment Tested /Certified Check the appropriate boxes to indicatespecific equipment ins ected /serviced: Tank ID: T1: 87 Tank ID: T2: 87 X In -Tank Gauging Probe. Model: Veeder Root 846390 X In -Tank Gauging Probe. Model: Veeder Root 846390 X Annular Space or Vault Sensor. Model: Veeder Root 794390 X Annular Space or Vault Sensor. Model: Veeder Root 794390 X Piping Sump / Trench Sensor(s). Model: Veeder Root 794380 X Piping Sump / Trench Sensor(s). Model: Veeder Root 794380 X Fill Sump Sensor(s). Model: Veeder Root 794380 X Fill Sump Sensor(s). Model: Veeder Root 794380 X Mechanical Line Leak Detector. Model: VMI LD 2000 X Mechanical Line Leak Detector. Model: VMI LD 2000 Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model: X Tank Overfill / High -Level Sensor. Model: VR Overfill Alarm X Tank Overfill / High -Level Sensor. Model: VR Overfill Alarm Others eci equipment t e and model in Section E on Pa e 2). Other (specify equipment type and model in Section E on Page 2). Tank ID: T3:87 Tank ID: T4:91 X In -Tank Gauging Probe. Model: Veeder Root 846390 X In -Tank Gauging Probe. Model: Veeder Root 846390 X Annular Space or Vault Sensor. Model: Veeder Root 794390 X Annular Space or Vault Sensor. Model: Veeder Root 794390 X Piping Sump / Trench Sensor(s). Model: Veeder Root 794380 X Piping Sump / Trench Sensor(s). Model: Veeder Root 794380 X Fill Sump Sensor(s). Model: Veeder Root 794380 X Fill Sump Sensor(s). Model: Veeder Root 794380 X Mechanical Line Leak Detector. Model: VMI LD 2000 X Mechanical Line Leak Detector. Model: VMI LD 2000 Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model: X Tank Overfill / High -Level Sensor. Model: VR Overfill Alarm X Tank Overfill / High -Level Sensor. Model: VR Overfill Alarm Others eci a ui ment tXee and model in Section E on Pa e 2 . Other (specify equipment type and model in Section E on Page 2). Dispenser ID: 1 -2 Dispenser ID: 3-4 X Dispenser Containment Sensor(s). Model: Veeder Root 794380 X Dispenser Containment Sensor(s). Model: Veeder Root 794380 X Shear Valve(s). X Shear Valve(s). Dispenser Containment Floats and Chains . Dispenser Containment Floats and Chain(s). Dispenser ID: 5 -6 Dispenser ID: 7 -8 X Dispenser Containment Sensor(s). Model: Veeder Root 794380 X Dispenser Containment Sensor(s). Model: Veeder Root 794380 X Shear Valve(s). X Shear Valve(s). Dispenser Containment Floats and Chain(s). Dispenser Containment Floats and Chain(s). Dispenser ID: 9 -10 Dispenser ID: 11 -12 X Dispenser Containment Sensor(s). Model: Veeder Root 794380 X Dispenser Containment Sensor(s). Model: Veeder Root 794380 X Shear Valve(s). X Shear Valve(s). Dispenser Containment Floats and Chains Dispenser Containment Floats and Chain(s). 'If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility. C. Certification - I certify that the equipment identified in this document was inspected /serviced in accordance with the manufacturers' guidelines. Attached to this Certification is information (e.g. manufacturers' checklists) necessary to verify that this information is correct and a Plot Plan showing the layout of monitoring equipment For any equipment capable of generating such reports, I have also attached a copy of the report; (check all that apply): System set -up " Alarm history report Technician Name (print): Stewart Bradly Signature: Certification No.: 8141938 -UT License. No.: 481053 Testing Company Name: Kern County Construction, Inc Phone No.:( 661 ) 634 -9950 Testing Company Address: PO Box 6096, Bakersfield, CA 93386 Date of Testing /Servicing: 5 / 23 / 2012 Monitoring System Certification Page 1 of 4 12107 2/21/07 � �G ,��. ll/� lam` �� � i `l \ �' D. Results of Testing /Servicing Software Version Installed: Complete the following checklist: X Yes No* Is the audible alarm operational? X Yes No* Is the visual alarm operational? X Yes No* Were all sensors visually inspected, functionally tested, and confirmed operational? X Yes No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not interfere with their proper operation? Yes :i No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) operational? X N/A X Yes No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment monitoring system N/A detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate positive shut -down? (Check all that apply) X Sump/Trench Sensors; Dispenser Containment Sensors. Did you confirm positive shut -down due to leaks and sensor failure /disconnection? X Yes; .: No. X Yes L No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no mechanical overfill prevention N/A valve is installed), is the overfill warning alarm visible and audible at the tank fill point(s) and operating properly? If so, at what percent of tank capacity does the alarm trigger? 90 % Yes* X No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E, below. X Yes* No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) o Product; :' Water. If es, describe causes in Section E, below. X Yes No* Was monitoring system set -up reviewed to ensure proper settings? Attach set up reports, if applicable iEl� X Yes ❑ No* Is all monitoring equipment operational per manufacturer's specifications? * In Section E below, describe how and when these deficiencies were or will be corrected. Comments: Monitoring System Certification Page 2 of 4 12/07 2/21/07 F. In -Tank Gauging / SIR Equipment: XCheck this box if tank gauging is used only for inventory control. "'. Check this box if no tank gauging or SIR equipment is installed. This section must be completed if in -tank gauging equipment is used to perform leak detection monitoring. Complete the following checklist: Yes No* Has all input wiring been inspected for proper entry and termination, including testing for ground faults? Yes No* Were all tank gauging probes visually inspected for damage and residue buildup? Yes No* Was accuracy of system product level readings tested? Yes No* Was accuracy of system water level readings tested? Yes No* Were all probes reinstalled properly? Yes No* Were all items on the equipment manufacturer's maintenance checklist completed? * In the Section H, below, describe how and when these deficiencies were or will be corrected. G. Line Leak Detectors (LLD): I, Check this box if LLDs are not installed. Complete the following checklist: X Yes No* For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance? (Check all N/A that apply) Simulated leak rate: X 3 g.p.h.; '10.1 g.p.h ; -, 0.2 g.p.h. X Yes _. No* Were all LLDs confirmed operational and accurate within regulatory requirements? X Yes : ; No* Was the testing apparatus properly calibrated? X Yes i7 No* For mechanical LLDs, does the LLD restrict product flow if it detects a leak? N/A Yes E No* For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak? X N/A Yes Li No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or X N/A disconnected? Yes No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or X N/A fails a test? Yes _ No* For electronic LLDs, have all accessible wiring connections been visually inspected? X N/A X Yes :; No* Were all items on the equipment manufacturer's maintenance checklist completed? * In the Section H, below, describe how and when these deficiencies were or will be corrected. H. Comments: Monitoring System Certification Page 3 of 4 12/07 2/21/07 Monitoring System Certification }�, f UST Monitoring Site Plan Site Address: 1701 /����� *'K 1� 4le• _Ba-ka''Srtt161 LA / 1 ::::::......... r:z-Ci r ..... . ................... ........................ ........................ � ............. .................. ...................... ............................... ...................... ............................... ............................. I....................... ...................... ............................... ...................... ............................... Date map was drawn: Instructions If you already have a diagram that shows all required information, you may include it, rather than this page, with your Monitoring System Certification. On your site plan, show the general layout of tanks and piping. Clearly identify locations of the following equipment, if installed: monitoring system control panels; sensors monitoring tank annular spaces, sumps, dispenser pans, spill containers, or other secondary containment areas; mechanical or electronic line leak detectors; and in -tank liquid level probes (if used for leak detection). In the space provided, note the date this Site Plan was prepared. Monitoring System Certification Page 4 of 4 12/07 4 2/21/07 SWRCB, January 2006 Spill Bucket Testing Report Form This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printouts from tests (if applicable), should be provided to the facility owner /operator for submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: Arco AMPM 01960 Date of Testing: 5 -23 -12 Facility Address: 1701 Brundage Ln., Bakersfield, CA Facility Contact: Ron Rogers Phone: Date Local Agency Was Notified of Testing : 5 -14 -12 Name of Local Agency Inspector (if present during testing): Esther Durran 2. TESTING CONTRACTOR INFORMATION Company Name: Kern County Construction, Inc. PO Box 6096, Bakersfield, CA 93386 Technician Conducting Test: Stewart Bradly Credentials: X CSLB Contractor X ICC Service Tech. ❑ SWRCB Tank Tester ❑ Other (Spec) License Number(s): 481053 8141938 -UT 3. SPILL BUCKET TESTING INFORMATION Test Method Used: XHydrostatic ❑ Vacuum ❑ Other Test Equipment Used: Visual Equipment Resolution: 0.0" Identify Spill Bucket (By Tank Number, Stored Product, etc. 1 T1:87 2 T2:87 3 T3:87 4 T4:91 Bucket Installation Type: ❑ Direct Bury X Contained in Sump ❑ Direct Bury X Contained in Sump ❑ Direct Bury X Contained in Sump ❑ Direct Bury ❑ Contained in Sum Bucket Diameter: I 11" 1 1" 11" 11" Bucket Depth: 1 15" 15" 14" 15" Wait time between applying vacuum /water and start of test: 15 Min. 15 Min. 15 Min. 15 Min. Test Start Time (Ti): 9:45 9:45 9:45 9:45 initial Reading (Ri): 8.25" 7.75" 8.00' 8.00" Test End Time (TF): 10:45 10:45 10:45 10:45 Final Reading (RI.): 8.25" 7.75" 8.00" 8.00" Test Duration (TF — Tj): 1 Hr. 1 Hr. I Hr. 1 Hr. Change in Reading (RF - Ri): 0.0" 0.0" 0.0" 0.0" Pass /Fail Threshold or Criteria: 0.0" 0.0" 0.0" 0.0" Test Result. X Pass ❑ Fail I X Pass ❑ Fail X Pass ❑ Fail I X Pass ❑ Fail Comments — (include information on repairs made prior to testing, and recommended follow -up for failed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information container/ in this report is true, accurate, and in full compliance with legal requirements. Technician's Signature: Date: /Z 7 State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements may be more stringent. iJ•(STEI•'1 SETUP 11AY ?U1 7'59 AM ti;1`STEf 9 UNITS U.S. S''i'STEM LANGUAGE ENGL I SH SYSTEM DATE: TIME FORI,lAT 1,1014 DD YYYY HH :l °lf °I : SS xM ARI ,0 am'- p i t 1 9 - 0 1701 Btur-ldaye Lane Bal,:ersf i el d CA 93304 SHIFT I' I P•IE i DISABLED SHIFT TIME 2 DISABLED SHIFT TIME 3 DISABLED SHIFT TIME lE 4 DISABLED SHIFT BIR PRINTOUTS DISABLED DAILY BIR PRINTOUTS D I SABLED TICKETED DELIVERY DISABLED TANK PER TST NEEDED WRN DISABLED TANK ANN TST NEEDED WRN DISABLED LINE RE- EPJABLE METHOD PANS LINE TEST LINE PER TST NEEDED WRN DISABLED LINE ANN TST NEEDED WRN DISABLED PRINT TC: VOLUMES ENABLED TEMP COMPENSATION VALUE (DEC, F ): 66.0 STICK HEIGHT OFFSET DISABLED ULLAGE: 90% H- PROTOCOL DATA FORI "IAT HE I G' HT DISABLED PRECISION TEST DURATI(ni HOURS: 72 DISABLED DAYLIGHT SAV I NC: T I I'lE ENABLED DISABLED START LATE AUTO SENSOR FUEL ALARM 1 "lAR WEEK '_2 SUN START T I IlE AUTO SENSOR WATER ALARM ?:U0 AM DISABLED END DATE AUTO SENSOR OUT ALARM NOV WEEK I SUN END TIME 2 :00 AM RE- DIRECT L: =AL PRINTOUT DISABLED EURO PROTC_(='`)L PIEFI,: S CUSTOM ALARMS DISABLED SERVICE NOTICE RECEIVER SETUP: DISABLED D 8 : VEEDER ROOT (FI 11S ) ISO 3166 COUNTRY r'2 CODE: R0VR TYPE: COMPUTER PORT NO: 3 RETRY NO: 5 HASSI DENS ITY RETRY DELAY: 5 DISABLED CONFIRMATION REPORT: OFF AUTO DELIVERY DID COI°MUNICATION5 SETUP DISABLED SYSTEI °1 SECUk I T'':' AUTO EXTERNAL I NPUT �N CODE : 006000 DISABLED PORT SETT I NGS : AUTO EXTERNAL INPUT OFF MAINTENANCE HISTORY DISABLED DISABLED AUTO SENSOR FUEL ALARM BAUD RATE 9600 DISABLED PARITY NONE AUTO SENSOR WATER ALARM TANK CHART SECURITY DISABLED DISABLED AUTO SENSOR OUT ALARM RS- 2'32 SECURITY DISABLED CUSTOM ALARMS DISABLED SERVICE NOTICE RECEIVER SETUP: DISABLED D 8 : VEEDER ROOT (FI 11S ) ISO 3166 COUNTRY r'2 CODE: R0VR TYPE: COMPUTER PORT NO: 3 RETRY NO: 5 HASSI DENS ITY RETRY DELAY: 5 DISABLED CONFIRMATION REPORT: OFF AUTO DIAL TIME SETUP: COI°MUNICATION5 SETUP - - _ - - - - - - - - D 8:VEEDER ROOT (FMS) DIAL ON DATE PORT SETT I NGS : OCT G.- 2009 DIAL TIME : 7:53 AH (:O1" 11 °1 BOARD 1 (RS -232) RECEIVER REPORTS: BAUD RATE 9600 PARITY NONE STOP BIT 2 STOP DATA LENGTH: 7 DATA RS- 2'32 SECURITY CODE : DISABLED COMM BOARD : 2 (ED 11-1 ) RS -232 SECURITY CODE : DISABLED COMM BOARD 3 (S -SAT BAUD RATE 9600 PARITY fJOh1E STOP BIT I STOP RS- '2:x' END OF 1°IESSAGE DATA LENGTH: 8 DATA DISABLED RS -232 SECURITY AUTO DIAL ALARM SETUP CODE : DISABLED DTR NORMAL STATE: HIGH D 6 : VEEDER ROOT (F[,12;) AUTO TRAf•JSP'l I T SETTINGS: I N- TAIV }: ALARMS AUTO LEAK ALARM LIMIT ALL:HIGH WATER ALARM DISABLED ALL:SUDDEN LOSS ALARI'l AUTO HIGH WATER L I f ^I I T ALL : PRA }BE OUT DISABLED ALL :HIGH WATER WARNING AUTO OVERFILL LIMIT ALL:MAX PRODUCT ALARM DISABLED ALL:GROSS TEST FAIL AUTO LOW PRODUCT ALL :PERIODIi - TEST FAIL DISABLED ALL:ANNUAL TEST FAIL AUTO THEFT 1-11,11T ALL : NO C SLD IDLE TIME DISABLED ALL:CSLD INCR RATE WARN AUTO DEL I VER'I' START DISABLED SIPHON N1AN I FOLDED TANKS ISD HOSE ALARMS T#: 02.03 LIQUID SENSOR F;LI °15 ALL : GROSS COLLECT 'T WARN LINE MAN I FOLDED TANl'S ALL:FUEL ALARfl ALL:GROSS COLLECT FAIL Tit: NONE HLL:SENSOR OUT ALARM ALL : DEGRD COLLECT WARN ALL:SHORT ALARM ALL:DEGRD COLLECT FAIL ALL : WATER ALARM ALL : FLOW COLLECT WARN LEAK 1 "1I.I4 PERIODIC: 25% ALL:WATER OUT ALARM ALL:FLOW COLLECT FAIL 2421 ALL:HIGH LIQUID ALARM ALL:AIRFLOW MTR SETUP ALL:LOW LIQUID ALARM LEAK MIN ANNUAL 50% ALL :LIQUID WARNING VAPOR FLW MTR ALMS 4842 ALL:CHK VAPOR FLOW MTR Comm SIDE DIM ALl l ALL : D 1 BAWLED 011"I ALHRt l PMC ALARMS PERIODIC TEST TYPE ALL : COI "11'IUPJ 1 CAT I Ol,J ALARM VP RUNTIME FAULT STANDARD ALL: TRANSACT ION ALARM VP EMISSIONS WARN VF EMISSIONS FAIL ANNUAL TEST FAIL kECC PC 1 L I AT I Uh AL" VP PRESSURE WAR N ALARM D 1'SABLEU ALL:PROD THRESHOLD ALM VP PRESSURE FAIL ALL:CLOSE SHIFT WARNING VP DUTY CYCLE WARN PERIODIC TEST FAIL ALL:CLOSE DAILY WARNING VP DUTY CYCLE FAIL ALARM DISABLED PRESSURE LINE LEAK. PMC SETUP FAIL GROSS TEST FAIL ALL:GROSS LINE FAIL ALARM DISABLED ALL:ANNUAL LINE FAIL ANN TEST AVERAGING: OFF ALL : PLLD OPEN ALARM PER TEST AVERAGING: OFF ALL: UNKNOWN ALARM ALL:PLLD SHUTDOWN ALARM TANK: TEST NOTIFY: OFF ALL:UNKNOWN ALARM ALL: UNKNOWN ALARM TNK TST SIPHON BREAK:OFF ALL:PERIODIC LINE FAIL ALL:LOW PRESSURE ALARM DELIVERY DELAY 1 MIN ALL: UNKNOWN ALARM PUMP THRESHOLD : 10.00% ALL:CONT HANDLE ALM IN -TANK: SETUP ALL : LN EQUIP FAULT ALM - _ - - - - - - - - - - SMARTSENSOR ALARMS T 1:UNLEADED R ALL :SETUP DATA WARNING PRODUCT CODE 1 AL1-:COMf°1UNICATION ALARM THERMAL COEFF :.000700 ALL : SENSOR FAULT ALARM TANK DIAMETER 9'1. 00 ALL:FUEL WARNING TANK PROFILE 20 PTS ALL:FUEL ALARM FULL VOL 9684 ALL:WATER WARNING 87.4 IIVCH VOL 9624 ALL:WATER ALARM ALL:HIGH LIQUID WARIIIING 82.8 1NCH VOL 78.2 INCH VOL 9380 9020 T '= :UNLEADED R ALL:HIGH LIQUID ALARM 73.6 INCH VOL 8580 PRODUCT CODE 1 ALL:LOW LIQUID WARNING 69.0 INCH VOL 8079 THERMAL COEFF :.000700 ALL:LOW LIQUID ALARM 64.4 IIVCH VOL 7529 TANK DIAMETER 9".00 ALL:TEMPERATURE WARNING J9.8 1NCH VOL 6957 TANK PROFILE 20�PTS ALL:RELA'a' ACTIVE 55.':' 1NCH VOL 6942 FULL VOL 9684 ALL:IIJSTALL ALARM 50.6 INCH VOL 5707 87.4 INCH VOL 9624 ALL:SENSOR FAULT WARN 46.0 INCH VOL 5061 82.8 1NCH VOL 9380 ALL:VACUUM WARNING 41.4 INCH VOL 4413 78.2 IIVCH VOL : 9020 ALL: 110 VACUUM ALARM 36.8 I NGH VOL 3787 73.6 IIVCH VOL 8580 32.2 INCH VOL 3157 69.0 INCH VOL : 8079 ISD SITE ALARMS 27.6 INCH VOL 2550 64.4 IIVCH VOL 7529 ISD STAGE I WARN 23.0 INCH VOL 1973 59.8 INCH VOL : 6957 ISD GROSS PRES WARN 18.4 I NCH VOL 1937 55.2 INCH VOL 6342 1 SD GROSS PRES FAIL 13.8 INCH VOL 966 50.6 INCH VOL 5707 ISD DEGRD PRES WARN 9.2 INCH VOL 648 46.0 INCH VOL : 5061 ISD DEGRD PRES FAIL 4.6 INCH VOL 217 41.4 I NGH VOL 4413 METER DATA NO 36.8 INCH VOL 3787 ISD VAPOR LEAK: WARN 32.2 INCH VOL 3157 ISD VAPOR LEAK FAIL 27.6 IIVCH VOL 2550 ISD VP PRES WARN FLOAT SIZE: 2.0 IN. 23.0 INCH VOL 1973 ISD VP PRES FAIL 18.4 INCH VOL 1437 ISD VP STATUS WARN I ;JATER WARNING 0.8 13.8 IIVCH VOL 966 ISD VP STATUS FAIL HIGH WATER LIf "MIT: 1.0 9.2 INCH VOL 548 MISSING RELAY SETUP 4.6 INCH VOL 217 MISSING HOSE SETUP MAX OR LABEL VOL: 9684 METER DATA NO MISSING TANK SETUP OVERFILL LIMIT 90 MISS VAPOR FLOW MTR 8715 - MISS VAPOR PRES SEN HIGH PRODUCT 95; FLOAT SIZE: 2,.0 IN. MISSING VP INPUT 5199 ISD SETUP WARN DELIVERY LIMIT 10% WATER WARNING 0.8 ISD SETUP FAIL 966 HIGH WATER LIMIT: 1.0 ISD SENSOR OUT WARN ISD SENSOR OUT FAIL LOW PRODUCT 550 1'lA, , OR LABEL VOL: 9684 PC -ISD FAILURE LEAK: ALARM LIMIT: 15 OVERFILL LIMIT 715 SUDDEN LOSS L I 191 T : 40 895% TANI.' TILT 0.00 HIGH PRODUCT 999 PROBE OFFSET 0.00 DELIVERY LIMIT yly9 l U% uC0 LOW PRODUCT 550 LEAK ALARM 1-1111T: 15 SUDDEN LOS'S LIMIT. 40 TAM; TILT 0.50 PROBE OFFSET 0.00 SIPHON MhN I FOLDED TANKS TO: 01.03 LINE MANIFOLDED TANKS T13: NONE LEAF; MIN PERIODIC?: 25 %6 421 LEAF; MIN ANNUAL 50% 4842 PERIODIC TEST TYPE STANDARD ANNUAL TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED GROSS TEST FAIL ALARM DISABLED ANN TEST AVERAGING: OFF PER TEST AVERAGING: OFF TANK TEEN NOTIFY: OFF TNK TST SIPHON BREAK:OFF DEL I VERY DELAY l III I N PUMP THRESHOLD 10.00% T 3 : UPILEHDED R PRODUCT COME 1 THERMAL COEFF :.000700 TANK. DIAMETER 92.00 TANK PROFILE 20 PTS SULLEN LOSS LIMIT: FULL VOL : 9684 87.4 INCH VOL 9624 82.8 INCH VOL 9380 76.2 INCH VOL 9020 73.6 INCH VOL 8580 69.0 I NC: H 'VOL 8079 64.4 INCH VOL 7529 59.8 INCH VOL 6957 55.2 INCH VOL 6342 50.6 INCH VOL 5707 46.0 INCH VOL : 5061 41.4 INCH VOL 4413 36.8 INCH VOL : 3767 32.2 INCH VOL 3157 27.6 INCH VOL 2550 23.0 INCH VOL 1973 18.4 INCH VOL 1437 13.8 INCH VOL 966 9.2 INCH VOL 548 4.6 INCH VOL 217 METER DATA VOL NO FLOAT SIZE: 2'.0 IN. WATER WARNING 0.8 HIGH WATER LIMIT: 1.0 MAX OR LABEL VOL: 9684 OVERFILL LIMIT 90% 8715 HIGH PRODUCT 957 9199 DEL I VERY L I I °1 I T 10% 968 LOW PRODUCT 550 LEAF: ALARM LIMIT: 15 SULLEN LOSS LIMIT: 40 TANK TILT 1.10 PROBE OFFSET 0.00 SIPHON MANIFOLDED TANKS Tit: 01.02 LINE MANIFOLDED TANKS TO: NONE LEAK MIN PERIODIC:: 5% 2421 LEAK MIN AllNUAL : 50 4642 PERIODIC TEST TYPE STANDARD ANNUAL TEST FAIL ALARM DISABLED PERIODIC' TEST FAIL ALARM DISABLED GROSS TEST FAIL ALARM DISABLED ANN TEST AVERAGING: OFF PER TEST AVERAGING: OFF TANK TEST NOTIFY: OFF TNK TST SIPHON BREHK:OFF DELIVERY DELAY 1 I °11 IV PUMP THRESHOLD : 10.00% T 4 : UL PREMIUM PRODUCT CODE 3 THERMAL COEFF :.000700 TANK DIAMETER 92.00 TANK PROFILE 20 PTS FULL VOL : 9684 87.4 INCH VOL 9624 82.8 INCH VOL 9380 78.2 INCH VOL 9020 73.6 INCH VOL 8580 69.0 INCH VOL : 8079 64.4 INCH VOL 7529 59.8 INCH VOL : 6957 55.2 INCH VOL 6342 50.6 I NCH VOL 5707 46.0 INCH VOL 5061 41.4 INCH VOL 4410 36.8 INCH VOL 3787 32.2 INCH VOL 3157 27.6 INCH VOL 2550 23.0 INCH VOL : 1973 18.4 INCH VOL 1437 13.8 INCH VOL : 966 9.2 INCH VOL 548 4.6 INCH VOL 217 METER DATA NO FLOAT SIZE: 2.0 IN. WATER WARNING 0.8 HIGH WATER LIMIT: 1.0 [lAX OR LABEL VOL: 9684 OVERFILL LIMIT 900 8715 HIGH PRODUCT 95% 9199 DEL I VERY L I I°1 I T 10% 968 LOW PRODUCT 550 LEAF: ALARM LIMIT: 15 SUDDEN LOSS LIMIT: 40 TANK TILT 3.00 PROBE OFFSET 0.00 SIPHON MANIFOLDED TANKS T#: NONE LINE MANIFOLDED TANKS TO: NONE LEAK MIN PERIODIC: 25% 2421 LEAK MIN ANNUAL : 50% 4842 PERIODIC TEST TYPE STANDARD ANNUAL TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED GROSS TEST FAIL ALARM DISABLED ANN TEST AVERAGING: OFF PER TEST AVERAGING: OFF TANK TEST NOTIFY: OFF TNK TST SIPHON BREAK:OFF DELIVERY DELA �` 1 I °1 111 Pump THRESHOLD : 10.00% LEAK TEST METHi1Lj TEST oi,l D—TE . ALL TANK JUN b. 2008 START T I I °1E : DISABLED TEST RATE :0.20 GAL!HR DURATION HOURS TST EARLY STOP:DISAHLED LEAK TEST REPORT FORMAT NORMAL LINE LEAK LOCKOUT fUT SETUP LOOKOUT SCHEDULE DAILY START TIME: DISABLED STOP TIME : DISABLED LIQUID SENSOR SETUP L 1 :87 NORTH STF' SUMP TRI - STATE (SINGLE FLOAT) CATEGORY' : STP SUMP L 2 :91 ANNULAR TRI -STATE (SINGLE FLOAT) CATEGORY : ANNULAR SPACE L 3 :91 FILL SUMP TRI - STATE (SINGLE FLOAT) CATEGORY : PIPING SUMP L 4 :91 U14L STP SUMP TRI -STATE (SINGLE FLOAT) CATEGORY : STP SUMP L 5 :DISP.1 UDC TRI -STATE (SINGLE FLOAT) CATEGORY : DISPENSER PAN L E:DISP.3 -4 UDC TRI -STATE (SINGLE FLOAT) CATEGORY : DISPENSER PAN L 7 :DISP.5 -6 UDC TRI -STATE (SINGLE FLOAT) CATEGORY : DISPENSER PAN L B :DISF'.7 -8 UDC TRI -STATE (S1f,1GLE FLOAT) CATEGORY : DISPENSER PAN L 9:87 SOUTH ANNULAR TRI -STATE (SINGLE FLOAT) CATEGORY : ANNULAR SPACE L10:87 SOUTH FILL SUMP TRI -STATE (SINGLE FLOAT) CATEGORY : PIPING SUMP 1-11:87 SOUTH STP SUMP TRI -STATE (SINGLE FLOAT) CATEGORY : STP SUMP L12:87 CENTER ANNULAR TRI -STATE (SINGLE FLOAT) CATEGORY : ANNULAR SPACE L13 :87 CENTER FILL SUMP TRI -STATE (SINGLE FLOAT) CATEGORY : PIPING SUMP L14:87 )-ENTER STP SUMP TRI -STATE (SINGLE FLOAT) CATEGORY : STP SUMP L15:67 NORTH ANNULAR TRI-STATE (SINGLE FLOAT) CATEGORY : ANNULAR SPACE L16:87 NORTH FILL SUMP TRI -STATE (SINGLE FLOAT) CATEGORY : PIPING SUMP L17:DISP.9 -10 UDC TRI -STATE (SINGLE FLOAT) CATEGORY : DISPENSER PAN L18:DISP.11 -12 UDC TRI -STATE (SINGLE FLOAT) CATEGORY : DISPENSER PAN OUTPUT RELAY SETUP R 1:UNLEADED SHUTDOWN TYPE: STANDARD NORMALLY CLOSED TANK #: 1 IN -TANK ALARMS T I:HIGH WATER ALARM T 2 :HIGH WATER ALARM. T 3:HIGH WATER ALARM LIQUID SENSOR ALMS ALL:FUEL ALARM ALL :SENSOR OUT ALARM ALL :SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL R 2:PREMIUM SHUTDOWN TYPE: STANDARD NORMALLY CLOSED TANK 0: 4 IN-TANK ALARMS T 4 :HIGH WATER ALHRfl LIQUID SENSOR ALMS ALL-FUEL ALARM ALL:SENSOR OUT ALARM ALL:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL-DEGRD COLLECT FAIL R 3:OVERFILL ALARM TYPE' STANDARD NORMALLY OPEN TANK 0: NONE I N -TANK ALARMS ALL:OVERFILL ALARM ALL :HIGH PRODUCT ALARM ALL:MAX PRODUCT ALARM ALARM H I 2,,T0R`i' REPORT DELIVERY NEEDED MAY 23. 20 12 9 Al"I PRODUCT ALARM '23, '2012 9:57 AM A. LOW TE1•P WARN ING tljA , ) 23. 2012 9:59 AM riAY 23. 201'2 9 :57 Alli ALARM HI,,3ToR',,' REPORT I : UNLEADED R HIGH PRODUCT ALARM j,,J A Y 23, '2012 9,57 Al"I PROBE OUT 10:0'2 At"] I,IA` , ' -723, 2`012 9:58 AM t'i A Y 23, 2012' 9:56 hill DELIVERY NEEDED MAY 23. 20 12 9 Al"I PRODUCT ALARM '23, '2012 9:57 AM A. LOW TE1•P WARN ING tljA , ) 23. 2012 9:59 AM riAY 23. 201'2 9 :57 Alli ALARM HI,,3ToR',,' REPORT I N -Th NK HI-HRIll T 2:UNLEHDED R HIGH PRODUCT HbARtvl mAY 23, 2101'2 10:0'2 At"] PROBE OUT R 11AY 23, 20 12' 10:0'2 AM I-lAY 23.. 21012 10:01 AM LOW TEMP WAR1,111,4G REPORT rlAY 23.. 2012 10:01 AM ALARM REPORT ---- I N -'fr,l, [41*' h'LARl'l - - - -- T 3:UNLEADED R 10:09 AM HIGH PRODUCT ALARM FUEL ALAR11 MA's' 23.- 2012" 10:04 Atli PROBE OUT MA' , ) '�'3, "01" 10.05 Al"I mAy 23, -201-2, 10:04 AM LOW TEMP Wr`iRNING MAY 23.. 2012 10:04 AM ALAR11 REPORT Il'-J-TANK ALARM - - - -- T 4:UL PREl"IfUl"I HIGH PRODUCT ALARM MAY 23, 2012 10:08 AM PROBE OUT SENSOR ,_, SOR OUT ALARM MAY 23, '2012 10:09 AM MAY 23, �27012 10:06 Alll DELI VERY NEEDED MAY 23. 2012 10:07 Hill LOW TEf"IF, LdARl,-JIhJG 11AY 2:3. 2012 10:10 Am ALARM HI;ST= '.,R'Z REPORT ----- SENSOR REPORT L 1:87 NORTH STP SUMP STP SUMP SUMP FUEL-ALARI-1 FUEL ALARM JvlAY 9-3, 20 MAY '23. 2012 q:126 All SENSOR ,_, SOR OUT ALARM All 11AY 23, 201,21 9:16 Atli FUEL '-' 1L"Rl"l FUEL ALAR11 - MAY 23. 8: 36 AM ALrlRfll HISTI'_)R"i" REPORT ----- SENSOR ALARM - - - -- L 2:91 ANNULAR ANNULAR SPACE SENSOR OUT ALARM MAY 23, 22012 9:16 AM FUEL ALARM MAY '23, 2'012 8:48 AM SEN,Sc')R OUT 6L"`R[l1 APR 24, 21012 9:2722 AM ALARM HISTOR',` REPORT ----- SENSOR ALARM - - - -- L 3:91 FILL SUMP PIPING SU11P SENSOR OUT ALARM MAY 23. 201271 9:16 r,11l1 FUEL ALARM VIAY 23, 22012 8.46 Atli SENSOR OUT ALARM APR 2'4 - '20 12 9 AM ALARM HIS TORY REP%'_)RT ----- SENSOR ALhRl"l L UDC DISPENSER PAN FUEL ALARM 9:23 M I-JAY _23, 2012 - - SENSOR OUT HLARI'l 11AV 23, 2012 9:16 AM FUEL ALARM J.JAY ''23, 2012 8:34 AM ALARl"l HIS TORT REPORT ----- SENSOR i�Li:&`l - - - -- L 6:DI SF' .3-4 UDC DISPENSER PAN FUEL ALARM jj(AY 23, 20122 9:222 AM SENSOR OUT ALARM j.jAy -,3, 2012 9:16 Al"I FUEL ALARM 2:3, 2-1012 8:33 AM ALHpj.j H I STORY REPORT ----- SENSOR ALARM L 4:91 UNL STP SUMP STP SUMP FUEL ALARM JvlAY 9-3, 20 FUEL ALARM SENSOR OUT ALARM I"IAY 23, '20122 All SENSOR OUT ALARI`l 23, 2012 Al"I FUEL ALAR11 8: 35 AM IvJAY ALARM HIS TORY REP%'_)RT ----- SENSOR ALhRl"l L UDC DISPENSER PAN FUEL ALARM 9:23 M I-JAY _23, 2012 - - SENSOR OUT HLARI'l 11AV 23, 2012 9:16 AM FUEL ALARM J.JAY ''23, 2012 8:34 AM ALARl"l HIS TORT REPORT ----- SENSOR i�Li:&`l - - - -- L 6:DI SF' .3-4 UDC DISPENSER PAN FUEL ALARM jj(AY 23, 20122 9:222 AM SENSOR OUT ALARM j.jAy -,3, 2012 9:16 Al"I FUEL ALARM 2:3, 2-1012 8:33 AM ALHpj.j H I STORY REPORT ALARM - - - -- L 7:DISP.5-6 UDC DISpElq,-,ER PAN FUEL ALARM JvlAY 9-3, 20 9-23 Al"I SENSOR OUT ALARM IllAY 23, 30J." 9:16 AM FUEL ALARM MAY 23. -,o - 8::34 AM ALARM H I3T"__)'?V REPORT ----- SENSOR ALARM - - - -- L B:DISP-7-8 UDC D I s PE14SER PAN FUEL ALARM 11AY 23, 201-- 9:24 All] SENSOR ENSOR OUT ALARM IllAy 223, 201' 9:16 All' FUEL ALARM (41 ALARM HISTOR"i- REPORT ALhRil HISTOR"Z REPORT ----- SENSOR " ILARM ----- L 9 :87 SOUTH ANNULAR ANNULAR SPACE SENSOR OUT AD'"Rt'l 1"WZ 213, 22012 9:16 All FUEL ALARl"I MA`il 23. 2012 8: 521 AM SENSOR OUT HL--l(l APR 24.. 2012- '6:22 i!4-1 REPORT HLARI-1 H123TOR'i" REPORT SENSOR Al-HRI-1 ----- L I I : 67 SOUTH STF SUMP STP BUIll? FUEL ALARM MA14" 23, 20122 9:27 AM SENSOR OUT "''l-r"IRM MA`,` 23. 2012 9:16 AM FUEL ALARI-1 MAY 23, '2012 8:37 All ALr`lRfl REPORT ----- SENSOR hbHRll ----- CENTER ANNULAR ANNULAR SPACE SENSOR OUT MLARr,i 111AY 23, -201 . 2 5:16 AM FUEL hLr"lRl-1 MAY 23, 2012 8:51 Atl .SEN,S-OR OUT APR '24.. '201-7, q:22 All ALARI-1 REPORT SENSOR HLAR11 L13:87 CE1,4TER FILL L10:07 S-oUTH FILL SUMP PIPING sul-W SENSOR OUT ALARM OUT ALARM 23, 2012 9:16 AM FUEL f:il-HRM All MAY '23, 21012 8:39 All SENSOR OUT hLARl"l , APR 24.- 2012 9:12 HM HLARI-1 H123TOR'i" REPORT SENSOR Al-HRI-1 ----- L I I : 67 SOUTH STF SUMP STP BUIll? FUEL ALARM MA14" 23, 20122 9:27 AM SENSOR OUT "''l-r"IRM MA`,` 23. 2012 9:16 AM FUEL ALARI-1 MAY 23, '2012 8:37 All ALr`lRfl REPORT ----- SENSOR hbHRll ----- CENTER ANNULAR ANNULAR SPACE SENSOR OUT MLARr,i 111AY 23, -201 . 2 5:16 AM FUEL hLr"lRl-1 MAY 23, 2012 8:51 Atl .SEN,S-OR OUT APR '24.. '201-7, q:22 All ALARI-1 REPORT SENSOR HLAR11 L13:87 CE1,4TER FILL SUMP PIPING SUMP SENSOR OUT ALARM SENSOR OUT HL(-iRM MAY 2-13, 201-2 9:16 All FUEL ALAR11 11AY 23-- 2012' I-11AY 1-13, 201121 8: 41 AM SENSOR OUT ALARM APR '24, 2012 All SENSOR ALARM L14:87 CENTER STP SUMP S c TP SUMP FUEL ALARM MAY 23, 20122 9:26 AM SENSOR OUT HL(-iRM MAY 23, 2012 9 :16 i4l FUEL ALARM 11AY 23-- 2012' 8:36 AM HLARtl HlSTOR`Z REPORT ----- SENSOR ALHRPl - - - -- L15:87 NORTH ANNULAR ANNULAR SPACE SENSOR OUT HLHRtll tl,lAy 213- 2012 9:16 hNj FUEL ALARM MAY 23- 2012 e:50 AM SENSOR OUT ALARM APR 24, 2012 9 : 222 Aj°j AI-r"IRI'l HISTORY REPUmi ----- I .M,2OR ALARM - - - -- L16:87 NORTH FILL SUMP P I P I NG SUMP SENSOR OUT ALARfl MAY 23.- 2FJ12 9:16 AM FUEL AL"Rll HAY 23, 2012 8:42 AM SENSOR OUT ALARM APR 24, 21012 9:21121 AM ALARM HISTCR•i" REPORT SENSOR ri L17:DISP.9-10 UDC DISPENSER PAN FUEL ALARM 1-1Ay 223, 20121 9.21 AM SENSOR OUT f:il-HRI'll MAY 23, 20122 9:16 AM FUEL ALARM 11AY 223.- '--'0 1 .22 33 AM F U Nsop 6L p,., 'D I /V3 FUEL tIP6N b1no 2J.. 2012 9: SEIV'so' OUT 2o tlf4v -,au'r , 1�4L,�ptj till E 141 012 9:16 FUL qpI 2,3 2012 8:32 Qhj