HomeMy WebLinkAbout2011 RESULTS{25.5 MONITORING SYSTEM CERTIFICATION For Use By All Jurisdictions Within the State of California Authority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prreoared for each monitoring system control panel by the technician who performs the work A copy of this form must be provided to the tank system owner /operator. The owner /operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date_ A. General Information Facility Name: LUCKY 7 FOOD STORE Site Address: 2501 WHITE LN. City: BAKERSFIELD Bldg. No.: _ Zip: 93304 Facility Contact Person: MANJIT SINGH Contact Phone No.: ( ) Make/Model of Monitoring System: TLS -350 INSP. - ERNIE MADINA Date of Testing/Servicing: 1111412011 B. Inventory of Equipment Teste&Certified Check the aourotirlate boxes to indicate specific eauiriment insaected/serviced: Tank ID: REGULAR 87 Tank ID: MID GRADE 89 Z In -Tank Gauging Probe. Model: MAG ® In -Tank Gauging Probe. Model: MACS ® Annular Space or Vault Sensor. Model: 409 ® Annular Space or Vault Sensor. Model: 409 Z Piping Sump / Trench Sensor(s). Model: 208 ® Piping Sump / Trench Sensor(s). Model: 208 ❑ Fill Sump Sensor(s). Model: ❑ Fill Sump Sensor(s). Model: ® Mechanical Line Leak Detector. Model: FX1V Z Mechanical Line Leak Detector, Model: FE -PETRO ❑ Electronic Line Leak Detector. Model: ❑ Electronic Line Leak Detector. Model: ❑ Tank Overfill / High -Level Sensor. Model: ❑ Tank Overfill / High -Level Sensor. Model: ❑ Other (specify equipment type and model in Section E on Page 2). ❑ Other (specify equipment type and model in Section E on Page 2). Tank ID: PREMIUM 91 Tank ID: ® In -Tank Gauging Probe. Model: MACS ❑ In -Tank Gauging Probe. Model: ® Annular Space or Vault Sensor. Model: 409 ❑ Annular Space or Vault Sensor. Model: Z Piping Sump /Trench Sensor(s), Model: 208 ❑ Piping Sump / Trench Sensor(s). Model: ❑ Fill Sump Sensor(s). Model: ❑ Fill Sump Sensor(s). Model: ® Mechanical Line Leak Detector. Model: FX1V ❑ Mechanical Line Leak Detector. Model: ❑ Electronic Line Leak Detector. Model: ❑ Electronic Line Leak Detector. Model: ❑ Tank Overfill / High - Level Sensor. Model: ❑ Tank Overfill / High -Level Sensor. Model: ❑ Other (specify equipment type and model in Section E on Page 2). ❑ Other (specify equipment type and model in Section E on Page 2). Dispenser ID: 112 Dispenser ID: 314 Z Dispenser Containment Sensor(s). Model: 406 ® Dispenser Containment Sensor(s). Model: 406 ® Shear Valve(s). Z Shear Valve(s). ❑ Dispenser Containment Float(s) and Chain(s). ❑ Dispenser Containment Float(s) and Chain(s). Dispenser ID: Dispenser ID: ❑ Dispenser Containment Sensor(s). Model: ❑ Dispenser Containment Sensor(s). Model: ❑ Shear Valve(s). ❑ Shear Valve(s). ❑ Dispenser Containment Float(s) and Chain(s). ❑ Dispenser Containment Float(s) and Chain(s). Dispenser ID: Dispenser ID: ❑ Dispenser Containment Sensor(s). Model: ❑ Dispenser Containment Sensor(s). Model: ❑ Shear Valve(s). ❑ Shear Valve(s). ❑ Dispenser Containment Float(s) and Chain(s). ❑ Dispenser Containment Float(s) and Chain(s). *If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility. C. Certification - I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers' guidelines. Attached to this Certification is information (e g. manufacturers' checklists) necessary to verify that this information is correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also attached a copy of the report; (check all that apply): ® System set -ap Alarm history report Technician Name (print): RYAN MASON Signature: Certification No.: A273671 ICC# 8029371 -UT License. No.: 611 809850 Testing Company Name: RICH ENVIRONMENTAL Phone o.: (661) 326 -8402 Testing Company Address: 5643 BROOKS CT. BAKERSFIELD, CA 93308 Date of Testing/Servicing: 11/14/2011 Page 1 of 5 UN -036 — U4 www.unidocs.org Rev. 01/17/08 , Monitoring System Certification A Results of Testing/Servicing Software Version Installed: 323.03 Complete the following checklist: ® Yes ❑ No* Is the audible alarm operational? ® Yes ❑ No* Is the visual alarm operational? ® Yes ❑ No* Were all sensors visually inspected, functionally tested, and confirmed operational? ® Yes ❑ No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not interfere with their proper operation? ❑ Yes ❑ No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem) ® N/A operational? ® Yes ❑ No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment ❑ N/A monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate positive shut -down? (Check all that apply) ® Sump/Trench Sensors; ❑ Dispenser Containment Sensors. Did you confirm positive shut -down due to leaks and sensor failure/disconnection? ® Yes; ❑ No. ❑ Yes ❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no ® N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank fill point(s) and operating properly? If so, at what percent of tank capacity does the alarm trigger? % ❑ Yes* ® No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E, below. ❑ Yes* ® No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) ❑ Product; ❑ Water. If yes, describe causes in Section E, below. ® Yes ❑ No* Was monitoring system set -up reviewed to ensure proper settings? Attach set up reports, if applicable ® Yes ❑ No* 1 Is all monitoring equipment operational per manufacturer's specifications? * In Section E below, describe how and when these deficiencies were or will be corrected. E. Comments: Page 2 of 5 UN -036 —2/4 www.unidocs org Rev. 01/17/08 Monitoring System Certification F. In -Tank Gauging / SIR Equipment: ® Check this box if tank gauging is used only for inventory control. ❑ Check this box if no tank gauging or SIR equipment is installed. This section must be completed if in -tank gauging equipment is used to perform leak detection monitoring. Complete the following checklist: • Yes ❑ No* Has all input wiring been inspected for proper entry and termination, including testing for ground faults? • Yes ❑ No* Were all tank gauging probes visually inspected for damage and residue buildup? • Yes ❑ No* Was accuracy of system product level readings tested? • Yes ❑ No* Was accuracy of system water level readings tested? • Yes ❑ No* Were all probes reinstalled properly? • Yes ❑ No* Were all items on the equipment manufacturer's maintenance checklist completed? * In Section H, below, describe how and when these deficiencies were or will be corrected. G. Line Leak Detectors (LLD): Cmmnlete the fallnwino checkiistr ❑ Check this box if LLDs are not installed. ® Yes ❑ No* For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance? ❑ N/A (Check all that apply) Simulated leak rate: ® 3 g.p.h.; [10.1 g.p.h ; ❑ 0.2 g.p.h. • Yes ❑ No* Were all LLDs confirmed operational and accurate within regulatory requirements? • Yes ❑ No* Was the testing apparatus properly calibrated? • Yes ❑ No* For mechanical LLDs, does the LLD restrict product flow if it detects a leak? ❑ N/A ❑ Yes ❑ No* For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak? ® N/A • Yes ❑ No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled ® N/A or disconnected? • Yes ❑ No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions ® N/A or fails a test? • Yes ❑ No* For electronic LLDs, have all accessible wiring connections been visually inspected? ® N • Yes ❑ No* Were all items on the equipment manufacturer's maintenance checklist completed? * In Section H, below, describe how and when these deficiencies were or will be corrected. H. Comments: UN -036 — 3/4 Page 3 of 5 www.unidocs.org Rev. 01/17/08 Monitoring System Certification UST Monitoring Site Plan Site Address: 2501 WHITE LN. BAKERSFIELD, CA. 93304 .... .. .. .. .. •. _ . .0 .y+yT ......... . .. . . . .. ..... . . ... .. . ..... . ...... .................. ....... .............. . (i- +�A4,. Sc�Swt+tiP Q .......... .......... . . . •~6- rt1Di�L,f i�Q . . . . . . . . . 4-0006M �VlC . . ... .. . . .. . . . . . . . .. . .. .. : ...... �� ................. .. - ... .............. 1........ 1,® �D .......... .... ........ ............... ...... ,�-.� ............... ................I......... . ............ .... .......... ........................... a L:. ............ ............... . ............ .:.:........ ......................... : :. :.. ............ .. ....... ...................::.:: .. -: - -. :: :: : : : ........................... : : :: :...... rJ:.:.: :: ............ .............. 1. ............ .... I ...... .. .........................., .......................... Date map was drawn: 11/2512009. Instruetions )f you already Crave a Wagrram that shows all required infarmation, you may include it, rather than this page, with your Monitoring System Costificatiom On your site plan, show the general layout of tanks and piping. Clearly identify locations of the following equipment, if installtxL moniloring system control panels; sensors monitoring tank annular spaces, sumps, dispenser pans, spill containers, or other secondary corrtaiumeirt areas; mechanical or electronic line leak detectors; and in -tack liquid level probes (if used for leak detection). In the space provided, note the Jade Lhi9 Site Plan was prepared. UN4% -as Page 5 of 5 www.anidomorg Rev. 01/17/08- 4QU9 SWRCB, January 2006 Spill Bucket Testing Report Form This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printouts from tests (if applicable), should be provided to the facility owner /operator for submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: LUCKY 7 FOOD STORE I Date of Testing: 11/14/11 Facility Address: 2501 WHITE LN, BAKERSFIELD, CA. 93304 Facility Contact: MANJIT SINGH Phone: Date Local Agency Was Notified of Testing: Name of Local Agency Inspector (if present during testing): ERNE MADINA 2. TESTING CONTRACTOR INFORMATION Company Name: RICH ENVIRONMENTAL Technician Conducting Test: RYAN MASON Credentials: ❑ CSLB Contractor X ]CC Service Tech. ❑ SWRCB Tank Tester ❑ Other (Spec) License Number(s): 8029371 -UT 3. SPILL BUCKET TESTING INFORMATION Test Method Used: X Hydrostatic ❑ Vacuum ❑ Other Test Equipment Used: VISUAL Equipment Resolution: 0 Identify Spill Bucket (By Tank Number, Stored Product, eta 2 1 REGULAR 87 -FILL 2 PREMHUM 91- FILL 3 MID-89 FILL 4 Bucket Installation Type: X Direct Bury ❑ Contained in Sump X Direct Bury ❑ Contained in Sump X Direct Bury ❑ Contained in Sump ❑ Direct Bury ❑ Contained in Sum Bucket Diameter: 12" 12" 12" Bucket Depth: 14" 14" 14" Wait time between applying vacuum/water and start of test: 30 MIN 30 MIN 30 MIN Test Start Time (TO: 09:30 09:30 09:30 Initial Reading (Rj): 12" 12" 12" Test End Time (TF): 10:30 10:30 10:30 Final Reading (RF): 12" 12" 12" Test Duration (Ty— TO: 1 -HOUR 1 -HOUR 1 -HOUR Change in Reading (RF - R,): 0 0 0 Pass/Fad Threshold or Criteria: +/-0.00 +/-0.00 +/-0.00 Test Result: X Pass ❑ Fail X Pass ❑ Fail X Pass ❑ Fail ❑ Pass ❑ Fail Comments — (include information on repairs made prior to testing, and recommended follow -up for failed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all lite information contained in this report is true, accurate, and in full compliance with legal requirements. Technician's Date: 11/14/11 State laws and regulations do noycurrently require testing to be performed by a qualified contractor. However, local requirements may be more stringent. RICH ENVIRONMENTAL 3305 BRITTAN ST. BAKERSFIELD, CA. 93308 OFFICE (661)326 -8402 FAX (661)326 -8934 PRODUCT LINE LEAK DETECTOR TEST WORK SHEET WIN: FACILITY NAME: LUCKY 7 FOOD STORE FACILITY ADDRESS: 2501 WHITE LANE, BAKERSFIELD PRODUCT LINE TYPE: PRESSURE q4Z19 Aj V PRODUCT LEAK DETECTOR TYPE TEST TRIP PASS BELOW P.S.I. OR SERIAL NUMBER 3 G.P.H. FAIL UNL -87 L/D TYPE: FX1V YES 11 P.S.I. PASS SERIAL # 6251 NE9"9 L/D TYPE: FE -PETRO YES 10 P.S.I. PASS SERIAL # UNREADABLE PREM -91 L/D TYPE : FX1 V YES 10 P.S.I. PASS SERIAL # 9787 LID TYPE: PASS YES SERIAL # FAIL i CERTIFY THE ABOVE TESTS WERE CONDUCTED ON THIS DATE ACCORDING TO RED JACKET PUMPS FIELD TEST APPARATUS TESTING PROCEDURE AND LIMITATIONS. THE MECHANICAL LEAK DETECTOR TEST PASS / FAIL IS DETERMINED BY USING A LOW FLOW THRESHOLD TRIP RATE OF 3 GALLONS PER HOUR OR LESS AT 10 P.S.I. I ACKNOWLEDGE THAT ALL DATA COLLECTED IS TRUE AND CORRECT TO THE BEST OF MY KNOWLEDGE. TECHNICIAN: RYAN MASON SIGNATURE: DATE: 11/14/11 '9--o SYSTEM SETUP DEC 14. 2011 4 :17 PM SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH MMOONTDD YYYTYY'HH:�MM:SS )d, LUCKY 7 2501 WHITE N BAAKERSFIELDLCA 93304 661 - 397 -3722 SHIFT TIME 1 DISABLED SHIFT TIME 2 DISABLED SHIFT TIME 3 DISABLED SHIFT TIME 4 ; DISABLED TANK PER TST NEEDED WRN DISABLED TANK ANN TST NEEDED WRN DISABLED PASS RE-ENABLE EST' METHOD LINE PER TST NEEDED WRN DISABLED LINE ANN TST NEEDED WRN DISABLED PRINT TC VOLUMES ENABLED TEMP COMPENSATION VALUE (DEG F ): 60.0 STICK HEIGHT OFFSET DISABLED DAYLIGHT SAVING TIME DISABLED SYSTEM SECURITY CODE : 000000 CUSTOM ALARM LABELS DISABLED IN -TANK SETUP T I:UNLEADED 87 PRODUCT CODE COMMUNICATIONS SETUP SOFTWARE REVISION LEVEL - - - - - _ - - - - - - VERSION 323.03 : 96.00 TANK PROFILE 1 PT CREATED - 03.08306.06.10 PORT SETTINGS: NO SOFTWARE MODULE NONE FOUND SYSTEM FEATURES: PERIODIC IN -TANK TESTS ANNUAL IN -TANK TESTS RS -232 END OF MESSAGE DISABLED SYSTEM SETUP DEC 14. 2011 4 :17 PM SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH MMOONTDD YYYTYY'HH:�MM:SS )d, LUCKY 7 2501 WHITE N BAAKERSFIELDLCA 93304 661 - 397 -3722 SHIFT TIME 1 DISABLED SHIFT TIME 2 DISABLED SHIFT TIME 3 DISABLED SHIFT TIME 4 ; DISABLED TANK PER TST NEEDED WRN DISABLED TANK ANN TST NEEDED WRN DISABLED PASS RE-ENABLE EST' METHOD LINE PER TST NEEDED WRN DISABLED LINE ANN TST NEEDED WRN DISABLED PRINT TC VOLUMES ENABLED TEMP COMPENSATION VALUE (DEG F ): 60.0 STICK HEIGHT OFFSET DISABLED DAYLIGHT SAVING TIME DISABLED SYSTEM SECURITY CODE : 000000 CUSTOM ALARM LABELS DISABLED IN -TANK SETUP T I:UNLEADED 87 PRODUCT CODE I 1 THERMAL COEFF :.000070 TANK DIAMETER : 96.00 TANK PROFILE 1 PT FULL VOL 10000 FLOAT SIZE: 4.0 IN. WATER WARNING 2.0 HIGH WATER LIMIT: 3.0 MAX OR LABEL VOL: 10000 OVERFILL LIMIT 909 9000 HIGH PRODUCT 95°r. DELIVERY LIMIT 95� 1000 LOW PRODUCT 500 LEAK ALARM LIMIT: 99 SUDDEN LOSS LIMIT: 99 TANK TILT 4.00 PROBE OFFSET -1.00 SIPHON MANIFOLDED TANKS T #: NONE LINE MANIFOLDED TANKS T#: NONE LEAK MIN PERIODIC: 0% • D LEAK MIN ANNUAL 0% Q PERIODIC TEST TYPE STANDARD ANNUAL TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED GROSS TEST FAIL ALARM DISABLED ANN TEST AVERAGING: OFF PER TEST AVERAGING: OFF TANK TEST NOTIFY: OFF T 2 :SUPER 91 PRODUCT CODE 2 THERMAL COEFF :.000070 TANK DIAMETER 96.00 TANK PROFILE 1 PT FULL VOL 10000 FLOAT SIZE: WATER WARNING HIGH WATER LIMIT: MAX OR LABEL VOL: OVERFILL LIMIT HIGH PRODUCT DELIVERY LIMIT 4.0 IN. 2.0 3.0 LOW PRODUCT LEAK ALARM LIMIT: SUDDEN LOSS LIMIT: TANK TILT PROBE OFFSET 10000 9000 95% 9500 100/0 1000 500 99 99 3.10 0.00 SIPHON MANIFOLDED TANKS T#t NONE LINE MANIFOLDED TANKS T#: NONE LEAK MIN PERIODIC: cm 0 LEAK MIN ANNUAL 0/1, 0 PERIODIC TEST TYPE STANDARD ANNUAL TEST FAIL ALARM DISABLE[ PERIODIC TEST FAIL ALARM DISABLEI GROSS TEST FAIL ALARM DISABLE, ANN TEST AVERAGING: OF PER TEST AVERAGING: OF TANK TEST NOTIFY: OF TNK TST SIPHON BREAK:OF DELIVERY DELAY 15 MI PUMP THRESHOLD 10.0( SIPHON MANIFOLDED TANKS ALARM HISTORY REPORT T#: NONE L 6:89- ANNULAR LINE MANIFOLDED TANKS TRI -STATE (SINGLE FLOAT) - -- -- SYSTEM ALARM TO: NONE CATEGORY : ANNULAR SPACE PAPER OUT OCT 30. 201I 6:34 PM PRINTER ERROR LEAK MIN PERIODIC: 00% OCT 30. 2011 6:34 PM 0 BATTERY IS OFF LEAK MIN ANNUAL 0 JAN 1. 1996 8:00 0% JAN 0 PERIODIC TEST TYPE STANDARD LIQUID SENSOR SETUP qLt24 ` T3:SPECIAL89 OUTPUT RELAY SETUP - - - - - - - - - - - - * * * END R 1:87 SHUTOFF PRODUCT CODE 3 L RECONCILIATION SETUF THERMAL COEFF :.000070 ALARM DISABLED 1:87 STP - - _ - _ _ TANK DIAMETER 96.00 LE _ _ _ TANK PROFILE I PT CATEGORY :(SIN FLOAT) FULL VOL 10000 AUTOMATIC DAILY CLOS R 2:91 SHUTOFF DELIVERY DELAY 15 MIN L 2:89 -STP TIME: 2:00 AM FLOAT SIZE: 4.0 IN. TRI -STATE (SINGLE FLOAT) PERIODIC RECONCILIAT CATEGORY : STP SUMP MODE: WATER WARNING 2.0 MON' HIGH WATER LIMIT: 3.0 COMPENSATION L 3'91 -STP STANDARD. MAX OR LABEL VOL: 10000 TRI -STATE (SINGLE FLOAT) OVERFILL LIMIT .: 901/0 CATEGORY : STP SUMP BUS SLOT FUEL 9000 METER HIGH PRODUCT 959 TANK MAP EMPTY - 9500 L 4:87- ANNULAR DELIVERY LIMIT loo TRI -STATE (SINGLE FLOAT) 1000 CATEGORY : ANNULAR SPACE LOW PRODUCT 500 LEAK ALARM LIMIT: 99 SUDDEN LOSS LIMIT: 99 L 5:91 - ANNULAR TANK TILT 4.00 TRI-STATE (SINGLE FLOAT) PROBE OFFSET 0.00 CATEGORY : ANNULAR SPACE SIPHON MANIFOLDED TANKS ALARM HISTORY REPORT T#: NONE L 6:89- ANNULAR LINE MANIFOLDED TANKS TRI -STATE (SINGLE FLOAT) - -- -- SYSTEM ALARM TO: NONE CATEGORY : ANNULAR SPACE PAPER OUT OCT 30. 201I 6:34 PM PRINTER ERROR LEAK MIN PERIODIC: 00% OCT 30. 2011 6:34 PM 0 BATTERY IS OFF LEAK MIN ANNUAL 0 JAN 1. 1996 8:00 0% JAN 0 PERIODIC TEST TYPE STANDARD ANNUAL TEST FAIL ALARM DISABLED OUTPUT RELAY SETUP PERIODIC TEST FAIL ALARM DISABLED * * * END R 1:87 SHUTOFF TYPE: GROSS TEST FAIL STANDARD ALARM DISABLED NORMALLY CLOSED ANN TEST AVERAGING: OFF PER TEST AVERAGING: OFF LIQUID SE _ SOR ALMS TANK TEST NOTIFY: OFF �:SHONSOROUTT ALARM TNK TST SIPHON BREAK:OFF R 2:91 SHUTOFF DELIVERY DELAY 15 MIN TYPE: PUMP THRESHOLD 10.00% STANDARD NORMALLY CLOSED LEAK TEST METHOD TEST ON DATE : ALL TANK JAN 1. 1996 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS •.•n... r•nrn �. n•rnn • n r annr ti> LIQUID SENSOR ALMS ALL :FUEL ALARM ALL:SENSOR OUT ALARM ALL:SHORT ALARM R 3:89 SHUTOFF TYPE: STANDARD NORMALLY CLOSED LIQUID SENSOR ALMS ALL:FUEL ALARM ALL:SENSOR OUT ALARM ALL:SHORT ALARM DELIVERY NEEDED SEP 2, 2011 5:43 PM AUG 4, 2011 10:18 AM MAY 25, 2011 4:20 PM xXXxX END X*xxs %-" L-L-t ALARM HISTORY REPORT ALARM HISTORY REPORT ALARM HISTORY REPORT - - -- IN-TAW ALARM - - - -- -- SENSOR ALARM - - - -- IN -TANK ALARM - - - -- L 2:89 -STP T 1:UNLEADED 87 STP SUMP T 3:SPECIAL 69 ENSO4,OUT ALARM ALARM ALARM HISTORY REPORT 30 AM OCT 29, 2011 9:13 PM OCT 11. 2011 9:28 AM INVALID FUEL LEVEL NOV 6. 2011 8:42 AM FUEL ALARM MAY 26. 2011 7:19 PM OCT 17, 2011 8:27 AM NOV 14. 2011 9:22 AM SEP 7, 2011 9:39 AM SENSOR OUT ALARM HIGH PRODUCT ALARM STP SUMP SETUP DATA WARNING OCT 29. 2011 9:14 PM PROBE OUT MAR 31. 2011 2:20 PM DEC 6. 2008 5:39 AM NOV 25. 2009 10:19 AM MAR 2. 2008 4:14 AM FUEL ALARM INVALID FUEL LEVEL DELIVERY NEEDED SEP 2. 2011 10 :20 PM DEC 13, 2011 7:14 AM AUG 4, 2011 4:51 PM DEC 3. 2011 5:14 PM MAY 19. 2011 4:08 PM NOV 4, 2011 3:07 PM PROBE OUT * * * END NOV 25, 2009 10:19 AM END DELIVERY NEEDED SEP 2, 2011 5:43 PM AUG 4, 2011 10:18 AM MAY 25, 2011 4:20 PM xXXxX END X*xxs ALARM HISTORY REPORT - - - -- SENSOR ALARM - - - -- L 3:91 -STP STP SUMP * END * SENSOR OUT ALARM NOV 14, 2011 9:30 AM ALARM HISTORY REPORT FUEL ALARM NOV 14, 2011 9:21 AM -- - -- SENSOR ALARM - - - -- L 1:87 STP SENSOR OUT ALARM STP SUMP NOV 23. 2010 9 :41 AM SENSOR OUT ALARM NOV 14. 2011 9:30 AM FUEL ALARM ALARM HISTORY REPORT NOV 14, 2011 9:21 AM - - -- IN -TANK ALARM - - - -- SENSOR OUT ALARM NOV 23. 2010 9:41 AM T 2:SUPER 91 INVALID FUEL LEVEL * * * END NOV 28, 2011 7:02 PM OCT 19, 2011 3:21 PM JUL 14. 2011 8:31 PM PROBE OUT NOV 25, 2009 10:19 AM * * END DELIVERY NEEDED DEC 12. 2011 3:46 PM NOV 24, 2011 8:22 AM OCT 13, 2011 6:33 AM ALARM HISTORY REPORT - - - -- SENSOR ALARM - - -- L 4:87- ANNULAR ANNULAR SPACE SENSOR OUT ALARM NOV 14. 2011 9:30 AM FUEL ALARM NOV 14. 2011 9:24 AM SENSOR OUT ALARM ;� * * X END X x x NOV 23. 2010 9:41 AM qL W ALARM HISTORY REPORT ----- SENSOR ALARM - -�_ L 5:91-ANNULAR ANNULAR SPACE SENSOR OUT ALARM NOV 14. 2011 9:30 AM FUEL. ALARM NOV 14, 2011 9:23 AM SENSOR-OUT ALARM NOV 23. 2010 9:41 AM x w x N X END A x X K x ALARM HISTORY REPORT ----- SENSOR ALARM L 6169 - ANNULAR ANNULAR SPACE SENSOR OUT ALARM NOV 14. 2011 9:30 AM FUEL ALARM NOV 14. 2011 9:22 AM SENSOR OUT ALARI NOV 23. 2019 9:41 AM X*0( *X END xxxwx L-mlq ? MONITOR CERT. FAILURE REPORT SITE NAME : LUCKY 7 FOOD STORE DATE: 11/14/11 THE FOLLOWING COMPONENTS WERE REPLACED/R.EPAARED r COMPLETE TESTING. (f REPAIRS: NONE LABOR: NONE PARTS INTALLED : NONE NAME : TITLE: SIGNATURE: THE ABOVE NAMED PERSON TAKES FULL RESPONSIBILITY OF NOTIFYING THE APPROPRIATE PARTY TO HAVE CORRECTIVE ACTION TAKEN TO REPAIR THE ABOVE LISTED PROBLEMS AND NOTIFYING RICH ENVIRONMANTAL FOR ANY NEEDED RETESTING. THIS ALSO RELEASES RICH ENVIRONMENTAL OF ANY FINES OR PENALTIES OCCURING FROM NON - COMPLIANCE. A COPY OF THIS DOCUMENT HAS BEEN LEFT ON -SITE FOR YOUR CONVIENENCE.