HomeMy WebLinkAbout2011 FMCMONITORING SYSTEM CERTIFICATION For Use By All Jurisdictions Within the State of California Authority Cited.- Chapter 6 7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner /operator. The owner /operator must submit a copy of this form to the local agency regulating UST systems within 30 days of this date. A. General Information Facility Name: Mt. Vernon & Columbus Arco AM /PM Bldg. No.: Site Address: 2698 Mt. Vernon Avenue City: Bakersfield Zip: 93306 Facility Contact Person: Monty Hawatmeh Contact Phone No.: 661 - 703 -7273 Make/Model of Monitoring System: Veeder -Root TLS -350 B. Inventoryy of Equipment Tested /Certified Check the appropriate boxes to indicate specific equipment Inspected/serviced: Date of Testing/Servicing: 09/6/2011 Tank ID: 20000 gal. Regular Tank ID: 12000 gal. Super [x] In -Tank Gauging Probe. Model: 847390- 107 [x] In -Tank Gauging Probe. Model: 847390 -107 [x] Annular Space or Vault Probe. Model: 794390 -409 L] Annular Space or Vault Sensor. Model: 794390.409 [x] Piping Sump / Trench Sensor(s). Model: 794380- 208 [x] Piping Sump / Trench Sensor(s). Model: 794380 -208 [x] Fill Sump Sensor(s) Model: 794380 -208 L] Fill Sump Sensor(s). Model: 794380 -208 ❑ Mechanical Line Leak Detector. Model: ❑ Mechanical Line Leak Detector. Model: [X] Electronic Line Leak Detector. Model: Red Jacket Lx] Electronic Line Leak Detector. Model: Red Jacket [x] Tank Overfill / High Level Sensor. Model: 847390 -107 U Tank Overfill / High Leval Sensor. Model: 847390 -107 ❑ Other (specify equip. type and model in Sec. E on Pg. 2) ❑ Other (specify equip. type and model in Sec. E on Pg. 2) Tank ID: Tank ID: ❑ In -Tank Gauging Probe. Model: ❑ In -Tank Gauging Probe. Model: ❑ Annular Space or Vault Sensor. Model: ❑ Annular Space or Vault Sensor. Model: ❑ Piping Sump / Trench Sensor(s). Model: ❑ Piping Sump / Trench Sensor(s). Model: ❑ Fill Sump Sensors(s). Model: ❑ Fill Sump Sensor(s). Model: [_J Mechanical Line Leak Decector. Model: ❑ Mechanical Line Leak Detector. Model: ❑ Electronic Line Leak Detector. Model: ❑ Electronic Line Leak Detector. Model: ❑ Tank Overfill / High Level Sensor. Model: ❑ Tank Overfill / High Level Sensor. Model: ❑ Other (specify equip. type and model in Sec. E on Pg. 2) ❑ Other (specify equip. typs and model in Sec. E on Pg. 2) Dispenser ID: 1 & 2 Dispenser ID: _3 & 4 ❑c Dispenser Containment Sensor(s). Model: 794380 -208 L] Dispenser Containment Sensor(s). Model: 794380 -208 [7 Shear Valve(s). L] Shear Valve(s). ❑ Dispenser Containment Float(s) and Chain(s). ❑ Dispenser Containment Float(s) and Chain(s) Dispenser ID: 5 & 6 Dispenser ID: 7 & 8 [x] Dispenser Containment Sensor(s). Model: 794380 -208 [x] Dispenser Containment Sensor(s). Model: 794380 -208 [x] Shear Valve(s). U Shear Valve(s). ❑ Dispenser Containment Float(s) and Chains(s). ❑ Dispenser Containment Float(s) and Chain(s). Dispenser ID: Dispenser ID: ❑ Dispenser Containment Sensor(s). Model: ❑ Dispenser Containment Sensor(s). Model: ❑ Shear Valve(s). ❑ Shear Valve(s). ❑ Dispenser Containment Float(s) and Chain(s) ❑ Dispenser Containment Float(s) and Chain(s). *If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility. C. Certification - I certify that the equipment identified in this document was inspected /services in accordance with the manufacturers' guidlines. Attached to this Certification is information (e.g. manufacturers' checklist) necessary to varify that this information is correct and a plot plan showing the layout of monitoring equipment. For equipment capable of generating such reports, I have attached a copy of the report; (check all that apply) ❑x S et -up [x] Alar hist Technician Name (print): Bryan A Self Signature: Certification No: B37501 License No: 804904 Testing Company Name: Confidence UST Services, Inc. Phone No: 800- 339 -9930 Site Address: 2698 Mt. Vernon Avenue, Bakersfield, CA 93306 Date of Testing/Servicing: 091612011 D. Results of Testing /Servicing Software Version Installed: 328.03 Complete the following checklist: [x] Yes ❑ No* Is the audible alarm operational? x Yes No* Is e Visua a arm operational? x Yes No* Were all sensors visually inspected, functionally tested, and confinned operational? Yes ❑ No* Were all sensors installed at the lowest point of secondary containment and positioned so that other _jj equipment will not interfere with their proper operation? Yes No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) Hx N/A operational? x Yes ❑ No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary ❑ N/A containment monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initate positive shut - down? N Sump/Trench Sensors [x] Dispenser Containment Sensors Did you confirm positive shut -down due to leaks and sensor failure /disconnected? [x] Yes; ❑ No; [x] Yes ❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no L] N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visual and audible at the tank fill point(s) and operating properly? If so, at what percent of tank capasity does the alarm trigger? 90 % ❑ Yes* U No Was any momtonng equipment replaced? If Yes, identify specific sensors, probes, or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E, below. ❑ Yes* ❑ No Was liquid found inside any secondary containment systems designed as dry systems? ❑ Product; ❑ Water. If yes, describe causes in Section E, below. TxTYes No* I Was monitoring system set -up reviewed to ensure proper settings? Attach set -up reports, if applicable. Lxj yes No* I Is all monitoring equipment operational per manufacturer's specifications? * In Section E below, discribe how and when these deficiencies were or will be corrected. E. Comments: F. In -Tank Guaging / SIR Equipment: [X] Check this box if tank guaging is used only for inventory control. ❑ Check this box if tank guaging or SIR equipment is installed. This section must be completed if in -tank guaging equipment is used to perform leak detection monitoring. Complete the following checklist: U Yes ❑ No* Has all input wiring been inspected for proper enter and termination,including testing for ground faults? x Yes No* Were all tank guaging probes visually inspected for damage and residue buildup? x T Yes No* Was accuracy of system product level readings tested? x Yes No* Was accuracy of system water level readings tested? x Yes No* Were all probes reinstalled properly? [�j Yes ❑ No* 1 Were all items on the equipment manufacturer's maintenance checklist completed? * In the Section H, below, describe how and when these deficiencies were or will be corrected. G. Line Leak Detectors (LLD): ❑ Check this box if LLD's are not.installed. Complete the following checklist: [xj Yes ❑ No* For equip. start-up or annual equipment certification, was a leak simulated to varify LLD performance? (Check all that apply) Simulated leak rate: [X]3 g.p.h.: ❑0.1 g.p.h.; ❑0.2 g.p.h.; x Yes No* Were all LLD's confirmed operational and accurate within regulatory requirments? x Yes No Was the testing apparatus properly ca i rate ? ❑ Yes No For mac amca LLD's, does the LLD restrict product ow i it detects a leak? gesN/A [x] Yo* For electronic LLD's, does the turbine automatically shut off if the LLD detects a leak? ❑ N/A Fx] Yes No* For electronic LLD's, does the turbine automatically shut off if any portion of the monitoring system is ❑ N/A disabled or disconnected? [xj Yes No* For electronic LLD's, does the turbine automatically shut off if any portion of the monitoring system ❑ N/A malfunction or fails a test? rx� Yes No* For electronic LLD's, have all accessible wiring connections been visually inspected? ❑ N/A x Yes No I Were all items on the equipment manufacturer's maintenance checklist completed? * In the section H, below, describe how and when these deficiencies were or will be corrected. H. Comments: AP( > am. Pm 82703 2698 IIT Ver-nom Ava dshersfIeId CA 93306 SEP G. 2011 8:48 AM SYSTEI °f B:Tr%i I'LIti REPORT ALL FUNC7'It)NS NORHAL 1 NVEhrrOF-1 REPORT T 1 : UNI- F;=,DErJ R VOLUME = 14735 GALS ULLAGE = 4968 CALS 90% ULLAGE- 2997 GALS TG VOLUME - 14523 GALS HEIGHT - 81.47 INCHES WATER VOL - 0 1jhl -S WATER e u.(10 INCHES TEMP = 80.6 DEG F 'T 2 : UL PRE111 Uhl VOLUME _ 3267 ;ALS ULLAGE 8582 C4 0 1L5 90A ULLAf;E= 7397 ,� TC VOLUME z 3213 rALS HE I I.',HT = 58.06 1 NCH! WATER VOL 0 GALS WATER = i i. 00 INCHES TEMP = 93.'> DEC F 'r } 1, x r. END � A r SIFTWARG P.EVI-00N LEVEL VERSION 328.03 SOFTI =1raREa �s4t,3Fe- I rJCr -J:� CREATED - 08.06.06.17.21 S- MODULES 330160 -004 -a SYSTEM FEnTURE.S: PERIODIC I N- TANK TE: n 's ANNUAL 1 N -TAPQ; TESTS ISD SYSTEM SETUP SEP -6. 2011 8:48" All;- SYSTEM UNIT'S U.S. SYSTEM LANGUAGE EIVGL I SH SYSTEM DATE. °TIME FORMAT MON DD rA'Y HH:MM:SS ::M I ARCO amOarn 82703 2698 NIT Varnon Ave � BakersrIe_Id ! CA 93306 r SHIFT TIME 1 6:00 AM SHIFT TIME 2 D I S§(BLED SHIFT TIME 3 DI LEl? SHIFT TIME 4 DISABLED TANK PER TST I•EDr WRN DISABLED TANK ANN T3T' "NEEDED WRN DISABLED, LINE RE- 1ENABLE METHOD PASS L I �E TEST LINE PEI TST NEEDED WRN D I SABLIW LINE ANN TST NEEDED WRN DISABLED PRINT TG VOLUMES ENABLED TEMP COMPENSATION VALUE 63EG F 1: 60.0 ST I CK SHE I CHT OFFSET DISABLED ULLAGE: 90% H- PROTOCOL DATA F0041AT HEIGHT DAYLIGHT SAVING TIME `ENABLED START DATE MAR WEEK 2 SUN START TIME 2:00 AM END DATE NOV WEEK I SUN END TIME 2:00 AM RE- DIRECT LOCAL PR 114TOUT DISABLED EURO PROTOCOL PREFIX S SYSTEM SECURITY CODE : 000000 MAINTENANCE HISTORY DISABLED TANK CHART SECURITY DISABLED r'US'rOM ALARMS DISABLED SERVICE NOTICE DISABLED MASS/DENS ITY DISABLED �::OhihlUh! i Cr;'1' l Of•IS 5GT11P - - - - - _ - - - - - - REC:E I VEP SETUP: 1 N -TmN)t 8ETUF - - - - - _ - _ - - - - PORT :SETT I NGS : NONE T 1 : UIILEHDED R PRODUCT CODE I COMM BOARD 1 < EG t IN ) THERMAL COEFF :.000700 PS -232 SECURITY TANK DIAMETER 117.75 COLE : D1SHNLED TANK PROFILE 20 PTS FULL VOL : 19703 COMM BOARD 2 (S-SAT ? 1 1 1 .9 1 NCH VOL 19389 BAUD RATE 96[i0 106.0 I NCH VOL 18791 PARITY NONE 100.1 1NCH VOL : 18010 STOP BIT I STOP 94.2 1 NCH VOL 17091 DATA LENCTFI : 8 DH Cis 88.3 1 NCH VOL 16062 RS -232 SECURITY AUTO DIAL TIME SETUP: 82.4 1N(;H VOL : 14923 CODE : DISABLED 76.5 INCH VOL 13739 DTP. NOPJ IAL STATE: H I l3H NONE 70.6 1 NC :H VOL 12507 64.8 1NCH VOL 11269 COMM BOAp.D : 3 R2 _.,3 58.9 1NGH VOL : 9961 BAUD RATE 53.0 INCH VOL 8678 PAR ! ODD DD 47.1 1NCH VOL 7409 TOP BATA BET : 1 41.2 1NCH VOL 6170 DATA LENGTH: 7 DATA DATA 35.3 INCH VOL 4977 RS -232 SECURITY 29.4 INCH VOL 382'4 COLE DISABLED 23.5 1W;H VOL .2780 17.7 INCH VOL 1878 11.8 ll,rH VOL 1049 AUTO TP.ANSM l T SETT 1►JC;S : 5.9 I NCH VOL 400 AUTO LEEK ALARM L 1111 T DISABLED FLOAT SIZE: a . 0 t IV . AUTO Hit' H WATER LIMIT DISABLED RS -232 END OF MES'S;Hr;E WATER WARMINIis 2.0 AUTO OVERFILL LIMIT DISABLED HIGH WATER LIMIT: 1.0 D I SABLED AUTO LOW PRODUCT HUTO DIAL a►LHR19 SETUP - - - - - - - - - - - - NIA ( OR LABEL VOL: 703 19703 DISABLED OVERFILL LIMIT AUTO THEFT LIMIT 17732 D E SABLED HIGH PRODUCT 9521 AUTO DEL]VE>;Y START 18718 1) 1SABLED DELIVERY LIMIT I5» AUTO DELIVER"` END 2955 DISABLED AUTO EXTERNAL INPUT ON LOW PRODUCT 1000 DISABLED LEAK ALAP.I1 LIMIT: 99 AUTO EYTERIVNL 114PUT OFF SUDDEN LOSS LIMIT: 99 DISABLED TANK TILT 1.00 AUTO SEN5t3R FUEL ALt0?1 °1 PROBE OFFSET -1.00 DISABLED AUTO SENSOR WATER ALKR19 DISABLED ri�rIV SIPHON IFULDCG 'Cr;N1;S AUTO SENSOR OUT ALtiRIH TO: NONE DISABLED LINE I°IAN I FOLDED T a : NONE LEAK MIN PER I vD I,; : 29% 5713 LEAAK Nl IN ANNUmL 29% 5713 PERIODIC TEST TYPE STANDARD HNNUAL TEST FHI L ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED GROSS TEST FAIL ALAF11 D E SHBLED ANN TEST AVERAGING: OFF PER TEST AVERNcING: OFF TANS; TEST ilJOT l FV : OFF TNK TST SIPHON 8REHI•::OFF DELIVERY DELAY 5 I'1 I N PUMP THRESHOLD 10.00'1 T 2 : UL PP.EM I Uhl LEAK TEST METHOD OUTPUT RELA',' SUrLIP PRODLN::T C:ODE 3 - - - - - - - - - - - - - - - - - - - - - - - - THERMAL COEFF :.000700 TEST ON DATE : ALL TANK TANK DIAMETER 117.75 JUN 6. 2008 R 1:87 STP TANY. PROFILE 20 PTS START TIME : 1) 1SABLED TYPE: FULL VOL 11849 TEST RATE :0.20 GAL /HR STANDARD 111.9 114CH VOL 11676 DURATION 2 HOURS " NORMALLY CLOSED 106.0 INCH VOL 11334 100.1 INCH VOL 10963 TST EARLY STOP:DISHBLED TANK P: 1 94.2 INCH :H VOL 10334 88.3 INCH VOL 9717 LEAF: TEST REPORT FORMAT 82.4 INCH VOL 9027 NORMAL LIQUID SEr18Ok ALMS- 76.5 INCH VOL 8307 L I :FUEL ALARM 70.6 1NC:H VOL 7554 L 5: FUEL ALARM 6:1.8 INCH VOL 6795 L 6:FUEL ALARM 58.9 INCH VOL 5992 L 7:FUEL ALARM 53.0 1N:H VOL 5204 L 8: FUEL ALARM 47.1 INCH VOL 4426 L I:SEIVSOP. OUT ALARM 41.2 WH VOL 3652 L 5:SENSOR OUT ALARM 35.3 1NCH VOL : 2941 L 6:SENSOR OUT ALARM 29.4 INCH VOL 2243 L 7:SENS0R OUT ALARM 23.5 1 NCH VOL 1616 L 8:SENSOR OUT ALr -;Rhl 17.7 INCH VOL 1 079 1 1 .8 I NCH VOL 594 L I OU I D SENSOR t;ETU• ISD SITE ALHRPIS 5.9 1NCH VOL 221 - - - - - - - - - - - - ISD GROSS PRES FAIL. ISD DEGRD PRES FAIL L 1:87 STP VAPOR LEAK FAIL FLOAT SIZE: 4.0 IN. TRI -STATE iSI1W;LE FLOAT) _ISD ISD VP PRES FAIL i'A'fE,';ORY . STP SUMP wATEP. WARNING 2.0 ISD HOSE ALARMS HIGH WATER LIMIT: 1.0 ALL:GROSS COLLECT FAIL L 2:87 ANNULAR ALL:DEGRD COLLE�:T FAIL MAX OR LABEL VOL: 1.1849 TRI -STATE ( S I PIOLE FLOAT) ALL : FLOW COLLE(,'T FAIL OVERFILL LIMIT 901: CATEGORY : ANNULAR S> 4(:E 10664 R 2:9) STP HIGH PRODUCT 9511. TYPE: 11256 STANDARD DELIVERY LIMIT 15%: L 3:91 STP NORMALLY CLOSED 1777 TR I -STATE (S I PA':LE: FLOAT CwrEWRY : STP F;UMP TANK P: 2 LOW PROUCT 500 LEAK ALARM LIMIT: 99 SUDDEN LOESS LIMIT: 99 L 4:91 ANNUL14P. LIQUID SENSOR HLI•iS TANK TILT 0.00 TRI -STATE c31NGLE FLOAT) L 3:FUEL mUiRM PROBE OFFSET 0.00 CATEGORY : AtlNUU;R SPA<:E L 5:FUEL AU-;RM L 6:FUEL ALARM L 7:FUEL ALARM S1 PHO14 MAN I FOLDED TANlrS L 8: FUEL ALARM TO: NONE L 5 : D 1 SP 1-2 L 3: SENSOR OUT AI..AR11 L114E MAN1FOLDEEl TN'.l -STATE (S1IVC;LIE FLOAT) L S:SENSOR OUT AI.ARL1 Td: N014E CATEGORY : DISP13N6 :ER PAN L 6 :SENSOR OUT ALARM L 7:SENSOR OUT ALARM L B:SEN50R OUT ALARM LEAK M I r4 PER I OC, I C• P 9 %: 3436 L 6:DISF' 3 -4 ISD SITE ALARMS TRI -STATE <SINGLE FLOAT) ISD CROSS PRES FAIL. LEAs: M I N ANNUAL 29 %: CATEGORY : D I SPENSCR PAN ISD DEGRD PRES FAIL 3436 ISD VAPOR LEHIi FAIL ISD VP PRES FAIL PER1OD1L' TEST TYPE L 7:DISP 5 -6 ISD HOSE ALARI.6 STANDARD TRI -STATE (S 1 r1r,LE FLOW') ALL :GROSS COLLECT FA I L s`ATEi.ORY : DISPENSER PHN ALL : DEGRD COLLECT FAIL ANNUAL TEST FAIL ALL : FLOW C.0LLEC -1' FA 1 L ALARM DISABLED PERIODIC TEST FAIL. L 8:DISP 7 -8 ALARM DISABLED TRI- STATE- (SINGLE FLOAT) CATEGORY : D I :SPENSER PAN GRO SS TEST FAIL ALARM DISABLE( ANN TEST AVERAGING: OFF L 9:87 FILL PER TEST AVERACt l NG : OFF TF.1 -STATE ( S I NC;LE FLOAT) CATEGORY . PIPING ,Ur1P TANK TEST' 01' 1 F:' : x1 OFF TNK TST SIPHON BREAI`.:OFF LI O: 91 FILL TRI -STATE LSINGLE FLOAT) DELIVERY DW41,1 5 MIN CATEGORY : P I F' I NG SL1hiP PUMP THRESHOiXi 10.00-. R C OVEFFILL HLNRM TYPE: STANDARD NORMALLY OPEN TANK: 9: NONE 1 N -TAN): ALARMS ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM ALL:MAX PRODO -7 ALARM SMARTSENSOR SETUP s I: D I SP I-'-, F'S CATEGORY VAPOR PP.ESSUPE s '3:DISF' 1 -2 FM CATEGORY H 1 R FLOW METER s :L�ISF' 3 -4 FM C'A1')O(>P.`,' H I R FLOW METER s 4:GI8P 5 -6 FM t ATEGOR`f r; I P. F1.041 DIETER s 5:1)1SP 7 -8 FM C:rATEC,0P HIP PLOW METER EVR ISD SETUP DiR, TYPE: VACUUM W� 31ST VACUUM ASSIST TYPE HEAL' VAC. NOZZLE AWL RANGE MAX: 1.15 MIN: 0.95 VAPOR PROC.ESSON TYPE NONE ANALYSIS TIMES TIME: 10:00 AM DELHI' MINUTES: 1 ACCEPT HIGH ORVR : ID DISABLED NUM LABEL BLEND3 1 - 25507 I SI) HONE TABLE 2 21006 1D FT' FL HL HA RR 01 01 01 02 01 UU 02 02 02 02. 01 UU 03 03 03 02 04 UU 04 04 04 02 04' UU 05 05 05 02 02 UU 06 06 06 02 02 UU 07 07 07 02 03 IJU 08 08 08 02 03 UU ISD AIRFLOW METER MAP ID SERIAL NUM LABEL BLEND3 1 - 25507 -- -- - DISP 1 -2 F 2 21006 D1SP 5-6 F 9 2$432 [lisp 7 -8 F 4 25061 DISP 3 -4 F ISD FUEL GRADE HONE MAR' I 2 3 4 FP HHH MHH MHH MHH AA 01 501 901~301 U U 1 02 502 902 30? U U 1 03 503 303 903 U U 4 04 504 904 304 U IJ 4 05 505 905 305 U U 2 06 506 906 306 U U 2 07 507 907 307 U U 3 08 508 908 308 U U 3 LABEL TABLE 1: UNASSIGNED 2: BLEND3 3: REGULAR 4: MID GRADE 5: PREMIUM 6: GOLD 7: BRONZE 8: SILVER. 9: BLEND 10: BLEND4 PPIC SETUP Pm' VERSION: 01.01 VAPOR PROCESSOR TYPE NONE PROCESSOR G'ONTROL LEVEL: NONE ALHRN HISTORY REPORT - - - -- ENSTEII ALARM - - - -- PAPER OUT AUG 17, 2011 10:03 AM PRINTER ERROR AUG 17. 2011 10:03 HM A k w r- s END r- r. r i ALARM H l l�r L <iR'; REPORT - --- IN-TANK HLr1PM - T 1 : UNLEADED R SETUP I-ATr; WHP111IrU', JUN 6. 2008 8:05 (41 HIGH WATER ALARM 1*14Y 13. 1200'j 8:46 AM OVEPr I L-L ALHRI'l HAR 15. 2011 1 :2'5 PM LOW W)DUCT ALARM FEB 12. 2010 4:40 PM HUG I, 2009 2 :23 PM MA'`i 13. 2009 8:48 AIM H 1 GH FP.;rLii li :T HLAK''M MAP, 15. 2011 1:28 Pll JUN 30. 2009 9 :40 All JUN 6. 2008 8:05 All INVALID FUEL LEVEL FEB 12- 213111 5:03 P11 AUG 1, 2009 2:56 PM MAY 5. 2009 9:32 PM PROSE OUT AUr, '23, 2010 9:38 AM AUG 23. 2010 9:36 Ahi DELIVER;' NEEDED JUL 1- 201 1 7:38 P11 SEP 317. 2010 10:29 PM AUG 23 • 2010 9 : 36 All ALARM H I ST,01R" REPORT - - -- IN-TANK HLArP1 - T 2:1JL PREMIUM SETUP DATH WAR141140 JUN 6, 2008 8:05 AM LOW PRODUCT ALARM AUG 23, 2010 9::35 Hrl MAY 13, 2009 F1 :48 Af °I APR 27. 2009 5:16 11;1 HIGH PRODUCT ALARM JUN 30. 2009 9:41 Hrl JUN 6. 2008 8:05 AM INVALID FUEL LEVEL AUG 23, 2010 9:39 mm PROBE OUT AUG 23� 2010 9:33 Hr1 AUG 23. 2010 9:35 0.0 HIGH WATER IJARNINV JUN 6. 2009 11146 HM DELIVERY NEEDED .JUL 31. 2011 9:11 PM JUN 2. 2011 8:00 Pm MAY 10, 2011 5:02 F•1.1 LOW TEMP WAP.IV I PIG AUG 23. 2010 9:39 All . k END ,. : n 'r. - r;LARM H 15TrjR';' - - - -- SENSOR hLHF,f-I - L 1 :87 sip STP SUMP SENSOR OUT A1-HFil AUG 2'3. 2010 10:07 HM FUEL ALARM HuG 23. 2010 10:06 r;M FUEL ALARM AUG 23. 2010 9:521 HM ri X - - = END x , - - F1 ALARM HISTORY REPORT - - - -- SENSOR HL+iRI•'I - - -- L 2:87 ANNULAR ANNULAP SPACE FUEL (ALARM AUG 23. 2010 12:14 PM FUEL ALARM AUG 23. 2010 12:13 PM FUEL HLARl,i AUG 23, 2010 12:1,2 Prl A n x x A END x � , '- ALARM HISTORY N'.L"• PORT - - - -- SENOR ALARM - L 3:91 STP STP SUMP FUEL ALARM AUG 23, 2010 :09 PM FUEL ALARM Alper 23, 2010 10:06 rill FUEL ALARM AUG 2'3. 2010 9:4.1 All A 1 ri A ': END r t is . R ALARM HISTORY REPORT r;LARM HISTORY REPORT ALARM H 1:3TOR'r REPORT - - -- SENSOR ALARM - - -- L 4:91 A NNUL.FiR ANNULHR SPr• CE FUEL ALARM AUG' 23, 2010 12:02 P11 FUEL ALARM AUG 23. 21310 12,01 PM FUEL ALARM AW 23. 2010 11:59 AM A t- rt, EIV[J 4% t r- ALARM HISTORY kI F'(*:T - - -- SEr6*oP - -- L 5:1)ISP 1 -2 D I SPENS'ER Pr:h1 FUEL ALARM AUG 23. 2110 1 :28 PITT FUEL ALARM AUG 23. 2010 10:16 AM FUEL ALARM :AUG 23. 2010 10:06 mi'l - - - -- SEN..;Ok ALARM - - - -- L 6:111ISP 3 -4 DISPENSER PAN FUEL ALARM AUG 23. 2010 10: 06 AM FUEL. ALARM HLP3 23. 2010 9:54 AM FUEL ALAPJ9 JUN 30. 2009 9:37 AM s n +; s r END :0' A ALARM HISTORY REPORT - -- -- SENSOR ALARM. -- -, L 7:DISP 5 -6 DISPENSER PAN FUEL ALARM AUG 23. 2010 10:06 AN FUEL ALARM AUG 23. 2010 9:54 All FUEL ALARM JUN 30, 2009 9:38 rill ., x R ENE, ► A A + END k r A Z - - - -- SENSOR ALARM - - - -- L B:UISP 7 -8 DISPENSER PAN FUEL ALARM AUG 23. 2010 10:06 AM FUEL ALARM AUG 23, 2010 9:55 W FUEL ALARM JUN 30. 2005 9:37 HN r 1 R . ENP % m -, t ALARM HI::Ti>PY REI,,wr - - - -- SENSOR al-ARM - - - -- 1. 9:87 FILL PIPING SUMP SETUP DATA WARN I Nr; MAR 24. 2011 9:06 AM SETUP DATA WiYW I Nr; MAR 23. 2011 3:31 FM FUEL ALARM MAR ". 2011 :J: 15 PM .,.r.END R �� ALARM H I STOR•'r REPOIOT --- 1_10:91 FILL P I I• I W, SUMP FUEL. ALARM AUG 23. 2010 9:56 iim FUEL ALARM JUN 3U • 2009 5.44 riM FUEL +iLARH JUN 30. 2005 x:'23 a1r9 X...'• END A., t ft - - - -- SDCOR #ALARM - - - -- L 1 :87 STP STP SUMP FUEL. HLAPM SEP 6. 2•U 1 1 9: 17 AN - --- SENSOR, rit.s-01 - - --- L 3:91 STP STP SUMP FUEL ALARM SEP 6. 2u11 9:17 Hti - - - -- SLNSOR ViLAkil - - -- L 5:DISP 1 -2 U' I SPEN DER PAN FUEL HLARr1 SEP 6. 2011 9:20 k1l -•- - 2EIVGOR - -- I_ o:GI:P 3 -4 Ul5PEN-'EP. PAN FUEL ALARM SEP 6. 22011 9:21 HI "I -- - -- SENSO){ Hl.r {kI7 - - - -- 1 [. 1:U1:9P 7 -8 DISPEKSER PAN FUEL i LAK1.1 SEP 6. :,oil 9 : 2,4 #41 SEPISOR ;IL.iRM L 7:DISP 5 -e DISPENSER PApi FUEL ALARM SEP 6. 2011 9:24 KPI - - --- SEWSOP. ALARM - - -- 1,10:91 FILL P 1 P I PIG SUPIP FUEL ALARM SEP 6. 2011 9:25 kM - - -- SENSOR wL.HRM - - - -- L. 9:87 FILL P 1 P I NG SU1P FUEL mLARM SEP 6. 2011 9:25 41 AK*O am,r -qn V703 2698 MT Varncn Kva S ®I =er 3f fi e l d 04 93306 SEP E . 201 1 9: 27 ;-ir'1 S.'sTEM :TATIJ'3 P.EPowr ALL FUNCTIONS PK)Ri`IAL - - - -- SENSOR ALARM - - -- 1. 2:87 ANNUL4., ANNULAR SPACE FUEL ALAP11 SEP 6. 2011 9:29 41 - - - -- SENSOR 14.HRM -- L 2:87 ANNULAR NNNULAR SPi•CE FUEL AUiRM SEP 6. 2011 9:29 9 W1 AK'0 aimpin 8'2703 ARCO Wl.,pm 82,703" 2698 MT Vor-r.osi Ave :2698 PIT Vernon Ave Balror5f i el d Bab Q"3f iv I d 0A 93306 C'A 9=6 SEP 6. 201 1 9:30 iM SEP 6. 2011 9:35 Art SYPITEH ST�MG REI,(.,P'f SYSTEM ST�j`1'1_1:� REPOPT - - - - - - - - - - - L 2:FUEL ALARM - - - - - - - - - - - - L 4: FUEL mLi-iRM SENSOR mlmP(,] SENSOR ALARN L 4'91 ANNULAR L 2:87 AlqlqUbAR ANNULmP SPw E e4 1 ('10LAP SPAt-E FUEL ALARM FUEL ALAPM SEP •, 2011 9:36 W SEP 6. 2011 9:31 Am ARCO arow pm 82703 SENSOR ALAR1,1 2698 MI, Vel-non Ave L 4:1?1 ANNULAR Bale;-r sf i E? I d ANNULAR SPACE CA 93306 FUEL ALAPH SEP 6, 2011 9:34 H11 SER 6. 2011 9:39 HM SENSOIR L 4:91 ANNUL�P ANNULHIR SPACE FUEL HIJ-01 SEP 6. 21011 9:34 AM slp.3,Tul RL:Powv - - - - - - - - - - - - ALL FUtc-rIONS NORMAL AW_;HIVE kii-ir, S c hVE SETUP DhTm: s*rt4RT T I mE: SEP 6. 2011 9:48;3) 41 ARCHIVE UTILiTV SAVE SETUP rtP,Th: END TIME: SEP 6. 2,Oil 9:50:30 OM B'sqES : 1502 ----- SENSOR t4LmRH L 5:1)ISP 1-2 DISPENSEP PAN FUEL ALARM SEP, iL. 2011 -9:53 SENSOR ALARM L 1:87 STP STP SUMP FUEL ALARM SEP 6. 2011 9:53 "1 - - - -- SEWSOP AI-4a Vl 1, 9:87 FILL PINNG SUMP C-EIIISOR OUT HLfAR111 SEP 6. 2011 95:3 W -- -- S'Eur-X)P 1.10:91 FILL Pi PING SUMP SE11:3OR OUT ALARM I-')'EF 6. 201 1 9:53 #41'1 SEI't';op AIj.-,K11 L G:DISP 7-8 DISPENSER PAN FUEL ALARPI ,'E� .D - 6. 2CI 1 1 9:54 ikl-1 SENSOR i4ljiRll L 1,:67 HNNUUIR i-01NULHR SPAf;F FUEL ALAPH S. E P 6. '21:111 9:54 AM SEM�OR ALARM L -1:91 ANNULHR ANNULAR SPACE FUEL ALARM SEP 6. 2011 9:54 r:dl ALARM L STP IM SUMP SE14SOR OUT ALARM SEP 6. 2011 9:54 AN ARCO an. pin 82703 2698 MT VQrnoro Fives sal. Ql,sf I e I d CA 93306 SEP 6. 2011 9:54 A11 SYSTEM MORT - - - - - - - - - - - - ALL FUN OTI GPI NORMAL SEtqSOR ALARM L G*ISP 3-4 DISPENSER NAN FUEL ALARM SEP 6. 201I 9:57 All rl HR'Q0 am, pno G!"103 2698 MT Ve•nor, Ave Besl,er st I * I d CA 9:J306 SEP 6. 2011 9:57 AN civalis w-Wr - - - - - - - - - - - - L 6: FUEL t4IHp%m SWRCB, January 2006 Spill Bucket Testing Report Form This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printouts from tests (if applicable), should be provided to the facility owner /operator for submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: Mt Vernon & Columbus Arco AM /PM Date of Testing: 9/6/2011 Facility Address: 2698 Mt. Vernon Avenue Bakersfield, CA 93306 Facility Contact: Monty Hawatmeh I Phone: 661 - 703 -7273 Date Local Agency Was Notified of Testing: Ester Duran Name of Local Agency Inspector (f present during testing): 8/23/2011 2. TESTING CONTRACTOR INFORMATION Company Name: Confidence UST Services, Inc. Technician Conducting Test: Bryan A Self Credentials: Z CSLB Contractor X ICC Service Tech. X SWRCB Tank Tester ❑ Other (Spec) License Number(s): CSLB# 804904 ICC# 8022804 -UT Tank Tester 11 -1756 3. SPILL BUCKET TESTING INFORMATION Test Method Used: El Hydrostatic ❑ Vacuum ❑ Other Test Equipment Used: Lake Test Equipment Resolution: 0.0625" Identify Spill Bucket (By Tank Number, Stored Product, etc. 1 Regular 2 Super 3 4 Bucket Installation Type: ❑ Direct Bury X Contained in Sump ❑ Direct Bury X Contained in Sump ❑ Direct Bury ❑ Contained in Sump ❑ Direct Bury ❑ Contained in Sum Bucket Diameter: 12.00" 12.00" Bucket Depth: 13.50" 13.75" Wait time between applying vacuum /water and start of test: 5 Min 5 Min Test Start Time (Ti): 9:00 am 9:00 am Initial Reading (Rj): 9.75" 10.00" Test End Time (TF): 10:00 am 10:00 am Final Reading (RF): 9.75" 10.00" Test Duration (TF — Ti): 1 Hour 1 Hour Change in Reading (RF - Rj): 0.00" 0.00" Pass /Fail Threshold or Criteria: 0.0625" 0.0625" Test Result: X Pass ❑ Fail X Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail Comments — (include information on repairs made prior to testing, and recommended follow -up for failed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements. Technician's Signature:, !4�:! Date: 09/6/2011 State laws and regulations do not cufntly require testing to be performed by a qualified contractor. However, local requirements may be more stringent.