Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25, Chapter 5 as amended by CCR, Title 19
Date Of Inspection, Testing, Maintenance:
Property Information:
Name: Buck Owens Building
Address: 3223 Sillect Avenue
City:
Bakersfield
09/29/2012
System Riser ID:
Type Of System:
Wet Pipe
Dry Pipe
❑ Preaction
❑ Deluge
7267
Main Drain Test Results:
Abbreviation Key:
Initial Static Pressure: 85 (psi)
I = Inspection
T = Test
Residual Pressure: 40 (psi)
M = Maintenance
A -0 = After Operation
Restored Static Pressure: 70 (psi)
MI = Per Manufacturers Instructions
Item
Activity
Frequency
Description
NFPA 25
Fail
N/A
Pass
Reference
1.1
1
Daily
Preaction /Deluge Valves - Enclosure
12.4.3.1
X
Weekly
temperature
1.2
1
Daily
Dry Pipe Valves - Enclosure temperature
12.4.4.1.1
X
Weekly
1.3
1
Quarterly
Gauges - (Dry, Preaction, Deluge Systems)
5'2'4'2
5.2.4.3
X
1.4
1
Quarterly
Control Valves
12.3.2.1
X
1.5
1
Quarterly
Alarm Devices
5.2.6
X
1.6
1
Quarterly
Gauges (Wet Pipe Systems)
5.2.4.1
X
1.7
1
Quarterly
Hydraulic nameplate
5.2.7
X
1,8
I
Quarterly
Pipe and Fittings
5.2.2
X
1,9
1
Quarterly
Sprinklers
5.2.1
X
1.10
1
Quarterly
Spare Sprinklers
5.2.1.3
X
1.11
I
Quarterly
Fire Department Connections
12.7.1
X
1.12
1
Quarterly
Alarm Valves - Exterior Inspection
12.4.1.1
X
1.13
1
Quarterly
Preaction /Deluge Valves - Exterior Inspection
12.4.3.1.6
X
1.14
1
Quarterly
Pressure Reducing Valves
12.5.1.1
X
1.15
1
Quarterly
Dry Pipe Valves- Exterior Inspection
12.4.4.1.4
X
1.16
1
Quarterly
Backflow Preventers
12.6.1
X
1.17
1
Annual
Buildings
5.2.5
X
State Fire Marshal AES 2
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717
June 17, 2008
Page 1 of 5
ANNEX B
Item
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25, Chapter 5 as amended by CCR, Title 19
Frequency
Date Of Inspection, Testing, Maintenance:
09/29/2012
System Riser ID: 7267
N/A
Property Information:
1.18
Type Of System:
Annually
Name: Buck Owens Building
5.2.3
❑X Wet Pipe
��pF Cq�O
X
1.19
1
P 9
�
Address: 3223 Sillect Avenue
5.2.3
Dry Pipe
2
h a
X
1.20
❑ Preaction
5 Years
Hangers (Accessible concealed spaces)
5.2.3.3
��
1.21
Deluge
_
M
City: Bakersfield
5.2.3.3
RE
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
1.18
1
Annually
Hangers
5.2.3
X
1.19
1
Annually
Seismic Braces
5.2.3
X
1.20
1
5 Years
Hangers (Accessible concealed spaces)
5.2.3.3
X
1.21
I
5 Years
Seismic Braces (Accessible concealed
spaces)
5.2.3.3
X
1.22
1
5 Years
Pipe and Fittings (Accessible concealed
spaces)
5.2.2.3
X
1.23
l
5 Years
Sprinklers (Accessible concealed spaces)
5.2.1.1.4
X
1.24
I
5 Years
Alarm Valves - Interior Inspection
12.4.1.2
X
1.25
1
5 Years
Alarm Valves - Strainers, filters, orifices
12.4.1.2
X
1.26
1
5 Years
Check Valves - Interior Inspection
12.4.2.1
X
1.27
I
5 Years
Preaction /Deluge Valves - Interior Inspection
12.4.3.1.7
X
1.28
I
5 Years
Preaction/Deluge Valves - Strainers, filters,
orifices
12.4.3.1.8
X
1.29
1
5 Years
Dry Pipe Valves - Interior Inspection
12.4.4.1.5
X
1.30
1
5 Years
Dry Pipe Valves - Strainers, filters, orifices
12.4.4.1.6
X
2.1
T
Annually
Alarm Devices (90 Sec)
5.3.3
12.2.7
X
2.2
T
Annually
Main Drain Test (Enter data on Page 1)
12.2.6
12.2.6.1
12.3.3.4
X
2.3
T
Annually
Antifreeze Test
5.3.4
X
2.4
T
Annually
Control Valve - Position
12.3.3.1
X
2.5
T
Annually
Control Valve - Operation
12.3.3.1
X
2.6
T
Annually
Supervisory
12.3.3.5
X
2.7
T
Annually
Preaction Valve - Priming Water
12.4.3.2.1
X
2.8
T
Annually
Preaction Valve - Low Air Pressure Alarm
12.4.3.2.10
X
2.9
T
Annually
I Preaction Valve - Full Flow Trip Test
12.4.3.2.2
X
State Fire Marshal AES 2
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717
June 17, 2008
Page 2 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25, Chapter 5 as amended by CCR, Title 19
Date Of Inspection, Testing, Maintenance: 09/29/2012
System Riser ID: 7267
Property Information:
Type Of System:
F CA C
Name: Buck Owens Building
Wet Pipe
❑x
Address: 3223 Sillect Avenue
ca
Dry Pipe q
El Preaction �i►
9��P
Deluge qE M
City: Bakersfield
NFPA 25
Item
Activity
Frequency
Description
Reference
Fail
N/A
Pass
2.10
T
Annually
Dry Pipe Valve - Priming Water
12.4.4.2.1
X
2.11
T
Annually
Dry Pipe Valve - Low Air Pressure Alarm
12.4.4.2.6
X
2.12
T
Annually
Dry Pipe Valve - Quick- Opening Device
12.4.4.2.4
X
2.13
T
Annually
Dry Pipe Valve - Trip Test
12.4.4.2.2
X
2.14
T
Annually
Backflow Preventor Assemblies
12.6.2
X
2.15
T
3 Years
Dry Pipe Valve - Full Flow Trip Test
12.4.4.2.2.2
X
2.16
T
5 Years
Gauges
5.3.2
X
2.17
T
5 Years
Pressure Reducing Valve
12.5.1.2
X
2.18
T
5 Years
Fire Department Connection Backflush
12.7.4
X
2.19
T
5 Years
Sprinklers - Extra High Temperature
5.3.1.1.1.3
X
2.20
T
5 Years
Sprinklers - Corrosive environment or
5.3.1.1.2
X
corrosive water
2.21
T
10 Years
Sprinklers - Dry
5.3.1.1.1.5
X
2.22
T
20 Years
Sprinklers - Fast Response
5.3.1.1.1.2
X
2.23
T
50 Years
Sprinklers
5.3.1.1.1
X
2.24
T
75 Years
Sprinklers 75 years in service
5.3.1.1.1.4
X
2.25
T
Sprinklers manufactured prior to 1920 -
5.3.1.1.1.1
X
Replace
3.1
M
Annually
Control Valves
12.3.4
X
3.2
M
Annually
Preaction /Deluge Valves
12.4.3.3.2
X
3.3
M
Annually
Dry Pipe Valves /Quick- Opening Devices
12.4.4.3.2
X
3.4
M
Annually
Dry Pipe Valve - Low Point Drains
12.4.4.3.3
X
3.5
M
5 Years
Obstruction Investigation
Chapter 13
X
State Fire Marshal AES 2
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717
June 17, 2008
Page 3 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25, Chapter 5 as amended by CCR, Title 19
Date Of Inspection, Testing, Maintenance: 09/29/2012
Property Information:
Name: Buck Owens Building
Address: 3223 Sillect Avenue
City: Bakersfield
System Riser ID: 7267
Type Of System:
F CAC�,�`O
❑X Wet Pipe Q ,Q
❑ Dry Pipe q
❑ Preaction �► ,,
P
E] Deluge �E tA
Item
Deficiencies and Comments:
Deficiencies and Comments Item number must correspond to to the Item number
of the activity listed above:
❑ See Continuation Page(s) (Indicate the number of continuation pages)
❑ PASS /I k i 1
❑ FAIL / l v ` ` J 08/29/2012
Signature Date
State Fire Marshal AES 2
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717
March 21, 2006
Page 4 of 5
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 5 of 5