Loading...
HomeMy WebLinkAbout2012 SB989 RESULTSMay 18, 2012 SB989 3 -YEAR POST REPAIR COMPLIANCE TEST Inspector Esther Duran Bakersfield Fire Department 2101 H Street Bakersfield, CA 93301 SUBJECT: SB 989 COMPLIANCE TESTING AT COSTCO FUELING STATION — 3800 ROSEDALE HWY, BAKERSFIELD, CA 93308 — FACILITY NO. 688 To Whom It May Concern: Below please find the secondary containment testing results for the above - referenced site. These results are being sent to you per the requirement of SB 989. Initial testing was performed by Wayne Perry, Inc. on 2/16/2012 with some components failing. Permitted secondary containment repairs were made pursuant to Permit #12- 10000180. Post Repair testing and inspection were conducted on 5/16/2012 and witnessed by Inspector Esther Duran with passing results. Please see attached report for further details. CONTRACTOR: Wayne Perry, Inc. License No: 300345 Technician: Austen Downey — ICC #8018653 If you have any questions regarding the attached results, please contact the undersigned at (714) 826 -0352. Sincerely, Wayne Perry, Inc. aviary young Mary Young Program Manger Attachments — SB 989 Testing Results Cc: Dennis Bock — Costco Costco #688 8281 Commonwealth Avenue Buena Park, California 90621 Phone (714) 826 -0352 1 Fax (714) 523 -9735 Pagel of 4 Secondary Containment Testing Report Form This form is intended for use by contractors performing periodic testing of UST secondary containment systems. Use the appropriate pages of this form to report results for all components tested. The completed form, written test procedures, and printouts fi-om tests (f applicable), should be provided to the facilityowner /operator for submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: COSTCO #688 1 Date of Testing: 5%16/2012 Facility Address: 3800 ROSEDALE HWY, BAKERSFIELD, CA 93308 Facility Contact: Phone: Date Local Agency Was Notified of Testing: 5/10/2012 Name of Local Agency Inspector (f present during testing): Esther Duran 2. TESTING CONTRACTOR INFORMATION Company Name: Wayne Perry, Incorporated Technician Conducting Test: Austen Downey ICC #8018563 Credentials: X CSLB Licensed Contractor SWRCB Licensed Tank Tester License Type: A, HAZ, C21, C10, B, C61, D40 License Number: 300345 Manufacturer Training Manufacturer Component(s) Date Training Expires Furnished on request 3. SUMMARY OF TEST RESULTS Two (2) 55- gallon drums were left on site CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING To the best of my knowledge, the facts stated in this document are accurate and in full compliance with legal requirements Technician's Signature: Date:_5 /16/2012 Component AIIx STP Sump 1 011-01 L■J ►� WWE M ' ►_� w= M0 000M WE M M0 WW=M oWoo■ MW M r_■ wm 0000 �000 0000 0000 °v; �or■�■� �oo u ..= - ._.._.... - -- W_w_m _m•_ _ Two (2) 55- gallon drums were left on site CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING To the best of my knowledge, the facts stated in this document are accurate and in full compliance with legal requirements Technician's Signature: Date:_5 /16/2012 Page 2 of 4 1. SECONDARY PIl'E TESTING Test Method Developed By: ❑ Piping Manufacturer ® Industry Standard ❑ Professional Engineer Other (Specify) Test Method Used: ® Pressure ❑ Vacuum ❑ Hydrostatic ❑ Other (Spec) Test Equipment Used: See attached testing procedures Equipment Resolution: Piping Run # 91 Piping Run # Vent/Va or Piping Material: Plastic Fiberglass Piping Manufacturer: Environ Smith Piping Diameter: 2" 4" over 3" Length of Piping Run: Product Stored: Premium Vapors Method and location of piping-run isolation: Test boot in sump Test boot in sump Wait time between applying pressure /vacuum/water and starting test: 30 minutes 30 minutes Test Start Time: 11:10am 11:10am Initial Reading (R,): 5.5 psi 5 psi Test End Time: 12:10pm 12:10pm Final Reading (RF): 5.5 psi 5 psi Test Duration: 1 hour 1 hour Change in Reading (RF -R,): 0 0 Pass/Fail Threshold or Criteria: 0.00 0.00 0.00 0.00 Test Result:. Z Pas S El Fait' ®::Pass. Fail,: ". ❑_i Pass :; . ❑Fail, " •'❑ Pass. ❑ .Fail..:: Comments — (include information on repairs made prior to testing, and recommended follow -up for failed tests) Repairs made pursuant to Bakersfield Fire Permit #12- 10000180 — Post repair testing witnessed by Inspector Esther Page 3 of 4 2. PIPING SUMP TESTING Test Method Developed By: ❑ Sump Manufacturer ® Industry Standard ❑ Professional Engineer ❑ Other (Sped&) Test Method Used: ❑ Pressure ❑ Vacuum ® Hydrostatic ❑ Other (Specify) Test Equipment Used: See attached testing procedures Equipment Resolution: Sump # 87 Aux Sump # 87 Aux Sump # 91 Sump # 91 Sump Diameter: 48" 48" 48" 48" Sump Depth: 62" 62" 62" 62" Sump Material & Manufacturer: Fiberglass Fiberglass Fiberglass Fiberglass Height from Tank Top to Top of Highest Piping Penetration: 2619 2699 22" 2219 Height from Tank Top to Lowest Electrical Penetration: 24" 24" 20" 20" Condition of sump prior to testing: Fair Fair Fair Fair Portion of Sum Tested' Sump e Above highest -. penetration Above highest penetration Above highest penetration Above highest penetration Does turbine shut down when sump sensor detects liquid (both product and water)? ❑Yes El No ® NA ❑Yes [] No ® NA ❑Yes [:j No ® NA ❑Yes ❑ No ® NA Turbine shutdown response time Is system programmed for fail -safe ❑ Yes ❑ No ®NA El Yes El No ® NA El Yes E] No NA Yes No ®NA ❑ El Was fail -safe verified to be operational?* F-1 Yes ❑ No ®NA ❑ Yes ❑ No ® NA ❑ Yes ❑ No NA ❑Yes ❑ No ®NA Wait time between applying pressure /vacuum/water and starting test: 30 minutes 30 minutes 30 minutes 30 minutes Test Start Time: 11:16am 11:32am 11:16am 11:32am Initial Reading (RI): 0.2481 0.2483 3.2732 3.2732 Test End Time: 11:31am 11:47am 11:31am 11:47am Final Reading (RF): 0.24835 0.24821 3.2732 3.27317 Test Duration: 15 min 15 min 15 min 15 min Change in Reading (RF -R,): 0.00025 0.00009 0 0.00003 Pass/Fail Threshold or Criteria: 0.002 0.002 0.002 0.002 Test Result: Z. Pass ❑ Fail ®Pass:. ❑;Fail N Pass.; Fa><1 ` Pass: `.:Fail.:.] Was sensor removed for testing? ® Yes ❑ No ❑ NA ®Yes ❑ No ❑ NA ®Yes [_1 No ❑ NA ® Yes ❑ No ❑ NA Was sensor properly replaced and verified functional after testing? ®Yes E] No El NA ®Yes El No El NA Eyes E] No ❑ NA ®Yes E] No El NA Comments — (include information on repairs made prior to testing, and recommended follow -up for failed tests) Repairs made pursuant to Bakersfield Fire Permit #12- 10000180 — Post repair testing witnessed by Inspector Esther Duran i If the entire depth of the sump is not tested, specify how much was tested. If the answer to anv of the questions indicated with an asterisk(*) is "NO" or "NA ", the entire sump must be tested. (See SWRCB LG -160) Page 4 of 4 7. UNDER- DISPENSER CONTAINMENT (UDQ TESTING Test Method Developed By: ❑ UDC Manufacturer ® Industry Standard ❑ Professional Engineer ❑ Other (Specify) Test Method Used: ❑ Pressure ❑ Vacuum ® Hydrostatic ❑ Other (Spec) Test Equipment Used: See attached testing procedures. Equipment Resolution: Ftix .a UDC # 7/8 UDC # 7/8 UDC Manufacturer: Environ Environ UDC Material: Plastic Plastic UDC Depth: 30" 30" Height from UDC Bottom to Top of Highest Piping Penetration: 8" 8" Height from UDC Bottom to Lowest Electrical Penetration: 6" 6" Condition of UDC prior to _ testing: Fair Fair Portion of UDC Tested Above highest penetration Above highest pene tration Above highest penetration Above highest penetration Does turbine shut down when UDC sensor detects liquid (both product and water)?* ❑ Yes ❑ No ® NA ❑Yes ❑ No ® NA ❑ Yes ❑ No ® NA ❑ Yes ❑ No ® NA Turbine shutdown response time Is system programmed for fail - safe shutdown ?" ❑ Z' ❑ No ®NA ❑Yes ❑ No ®NA ❑Yes ❑ No [D NA El Yes ❑ No ®NA Was fail -safe verified to be o erationalf ❑ Yes ❑ No ® NA ❑Yes ❑ No ® NA ❑ Yes ❑ No ® NA ❑ Yes ❑ No ® NA. Wait time between applying pressure /vacuum/water and starting test 30 minutes 30 minutes 30 minutes 30 minutes Test Start Time: 11:20am 11:38am Initial Reading (R1): 2.1025 2.1026 Test End Time: 11:35am 11:53am Final Readin (RF): 2.1025 2.1026 Test Duration: 15 min 15 min Change in Reading (RF -R1): 0 0 Pass/Fail Threshold or Criteria: 0.002 0.002 0.002 0.002 Test Result: :. Pass ❑Fail ®..:Pass :. Fail ❑! Pass ..; ; Fail ❑ Eass: ;Fail Was sensor removed for testing? ®Yes ❑No ❑ NA ®Yes [—]No ❑NA ®Yes ❑No ❑ NA ®Yes ❑No ❑ NA Was sensor properly replaced and verified functional after testing? ®Yes ❑No ❑ NA ®Yes ❑No ❑NA ®Yes ❑No ❑ NA ®Yes [—]No ❑ NA CommentS — (include information on repairs made prior to testing, and recommended follow -up for failed tests) Repairs made pursuant to Bakersfield Fire Permit #12- 10000180 — Post repair testing witnessed by Inspector Esther Duran 1 If the entire depth of the UDC is not tested, specify how much was tested. If the answer to any of the questions indicated with an asterisk(*) is "NO" or "NA ", the entire UDC must be tested. (See SWRCB LG -160) p p�. Al ELDS NYAf no ItA t Test al S Ac" i, T U AS Test Site t ius'�,; Status r'4. e Pas's/FaiI.j'.-,:' Restart ° --7Ar b, 6 rl tostco 6800 Rosedale hwy AM f 3w. N Saving ... :h ­ti . . . . . . . PASS a Bakersfield, CA 93308-XXXX C . . . . . . . . ff! Wed, May 16, 2012 11:31 AM . . . . . . . . . . �0.00025 R -,Prod U: dt = ix . . . . . . . . . . . M jj 85 aux M 'Type, Tank Sump Turbine AS 0 2'48'3 EM Wed, May 16, 2012 11:16 AM f 3w. N Nest End Time1 T a t-V 0'.'2482 p ff! Wed, May 16, 2012 11:31 AM 15 ,,ITest.passed 0.0020 .0.'2479 '05/' 1,1 21�'-.-00';AM' 1'1--2'4':'00'AM -U '27--00� 11:'31 12-,'-1:; -"05116/20 -;05Aff 6� j,,,-i05116/201 06 xJ �34 =UE EM M MM NO M M ME ME M IMMIMMOMM WOMOMM SO ME WMINUMIZION MZ MMIMMUMMUM MMMMINOW . ME ii among w =1 ON ■ P.'Eoiim.-Imnp!!N M P-MMINUMM MMM on M M ME ■MMMMMMMM IM MOM 0 ■mom 0 now Is Epp mmm mm .mg-mgammonno mmm ==a ImnommmaxwoMMOMM ......... -mon NI■■■NOMPM p MUMMIMM 0 mm; M limmeloPE2ggm MMM MMMM M MOMM MONSOON I ME w M mom MMIM IIM ME =mom M IM■E ME M M '20 ME ISIMMOMMOMMERM MOM'S rM ME on M ME w== ■MMMMIMNMMM ME OWWWW MINE OMEN M ME MEM MMOMM 0 0 ====�Mm■n 122201im.1 M wMizzwMEMMMM ■02221MRO ■ ■ mmm� 1,1 21�'-.-00';AM' 1'1--2'4':'00'AM -U '27--00� 11:'31 12-,'-1:; -"05116/20 -;05Aff 6� j,,,-i05116/201 06 xJ �34 Fky�' �G� ..X n's ;�: .:'.3 ..... � f..IC9e +�:e:. u.� ,.�.i..+� ....a14: ... �A..��.- .'S..T... .- ..aa... n_ i� � "i!c, '.4 -. \.L 3I - __+4e...M ��:W.. �S. . t+•�.`.fs � Test Site x - - :Status PasslFail 7Restartbort Costco 3800 Rosedale hwy Saving... .: ; a Bakersfield, CA 93308 .Change., Return,. lq -XXXX s 0.00003 j Product d t �c� .r9 r�,� n�1r`% �e 3 '`� e' ,ri 6+K s� .' ���`a��F � C'1 a7 � q § s f �' - eti 'w q ,T e Ell -. s 2�aa f `5 === �G�—=— Tank Sump Turbine C= E• �CC EE=-- �-- °— L■ °C— J= EEEC= O==CC= —_ -M C EMOMEMS -_ - -- - -- MIMM .. ......... ..... ....__.. ..._...... �. __. .. __ _. �...... __. _.. ... _... _ • 1 �_�_ - === �G�—=— C= E• �CC EE=-- �-- °— L■ °C— J= EEEC= O==CC= —_ -M C EMOMEMS -_ - -- - -- MIMM .. ......... ..... ....__.. ..._...... �. __. .. __ _. �...... __. _.. ... _... _ • 1 �_�_ ==--= - - -� _- -- -E -- MOMEM E� =_ --- --- - ------ S a Saving... "I . c.fi-S - Change u r, r o 00.000 E-Nr4, ig M&N AIX", ji�l ',-v ku-- TS I Costco 3800 R osedale hwy Bakersfield, CA .93308-XXXX 1 'P ro a U Ctr 4-�11 ud , 7Y , _ T y�e, Dispenser 7 8 -T, 2 ME 4. 'Wed, May 16, 2012 11:38 AM I- Wed may 16, 2012 11:53 AM it qq 15 0.0020 f es es Test passed I 6 mfnb n -T- �N N j 21026': -4 - - - - - - - - - H `� xV I �, 2 f625-I -, j 1 16 AM