MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State of California
Authority Cited., Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of
Regulations
This form must be used to document testing and servicing of monitoring equipment A separate certification or report must be prepared for
each monitoring system control panel by the technktian who performs the work. A copy of this torn must be provided to the tank system
owner/operator. The owner /operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date.
A. General Information
Facility Name: Bakemfleld City Com Yard Bldg. No.:
Site Address: 4101 Tmxtun Ave. City: Bakersfield Zip:
Facility Contact Person:
Contact Phone No.:
Make/Madel of Monitodng System Veeder -Root TLS -350 Date of Testing /Servicing: _j21 15 f2010
B. Inventory of Equipment Tested/Certified
Check the appropriate boxes to Indicatespecific equipment Insl acted /serviced:
Tank ID: 87 UL
Tank to:
❑ In -Tank Gauging Probe.
Model: 848390
❑ In -Tank Gauging Probe.
Model:
❑ Annular Space or Vault Sensor.
Model: _ 794390409
0 Annular Space or Vault Sensor.
Model:
❑ Piping Sump / Trench Sensor(s).
Model: 794380-208
0 Piping Sump / Trench Sensor(s).
Model:
0 FIII Sump Sensor(s).
Model:
0 Fill Sump Sensor(s).
Model:
❑ Mechanical Una Leak Detector.
Model: FXV
0 Mechanical Line Leak Detector.
Model:
0 Electronic Una Leak Detector.
Model:
❑ Electronic tine Leak Detector.
Model:
0 Tank Overfill / High -Level Sensor.
Model:
❑ Tank Overfill / High -Level Sensor.
Model:
0 Other (specify equipment type and model In Section E on Pane 2).
0 Other (specify equipment type and model In Section E on Page 2).
Tank ID: 91 UL
Tank ID:
0 In -Tank Gauging Probe.
Model: 848390
❑ In -Tank Gauging Probe.
Model:
❑ Annular Space or Vault Sensor.
Model: 794390409
❑ Annular Space or Vault Sensor.
Model:
❑ Piping Sump/ Trench Sensor(s).
Model: 794380.208
D Piping Sump / Trench Sensor(s).
Model:
❑ Fill Sump Sensor(s).
Model:
0 Fill Sump Sensor(s).
Model:
0 Mechanical Une Leak Detector.
Model: FXV
❑ Mechanical Line Leek Detector.
Model:
❑ Electronic Line Leak Detector.
Model:
0 Electronic Line Leak Detector.
Model:
0 Tank Overfill / High -Level Sensor.
Model:
0 Tank Overfill / High -Level Sensor.
Model:
❑ Other (specily equipment typo and model M Section E on Pane 2).
❑ Other s equipment type and model In Section E on P290 2).
DlapenserlD: 1 -2
Dispenser ID:
0 Dispenser Containment Sensor(e).
Model: 847990-001
0 Dispenser Containment Sensor(s).
Model:
❑ Shear Valve(s).
❑ Sheer Valve(a).
0 Dispenser Containment Float(s) and Chain(s).
❑ Dispenser Containment Floats and
Chain e .
Dispenser ID: 7-8
Dispenser ID:
❑ Dispenser Containment Sensor(s).
Model: 847990.001
❑ Dispenser Containment Sensor(s).
Model:
❑ Shear Volve(s).
❑ Shear Valve(s).
0 Dis sneer Containment Float a and Chain(s).
11 Dls sec Containment Floa a and
Chain e .
Dispenser ID:
Dispenser to:
❑ Dispenser Containment Sensor(s).
Model:
0 Dispenser Containment Sensor(s).
Model:
0 ShearValve(s).
❑ ShearValve(s).
❑ Dia near Containment Front a and Chain a
❑ Dis sneer Containrrrent Floe s end Chain e .
'If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser of the facility.
C. Certification - I certtfy that the equipment Identifled in this document was Inspected/serviced In accordance with the manufacturers'
guidelines. Attached to this Certification Is Information (e.g. manufacturers' checklists) necessary to verity that this Information is correct
and a Plot Plan showing the layout of monitoring equipment For any equipment capable of generating such reports, I have also attached a
copy of the report; (checkoff that apply): X System set -up X Alarm history report
Technician Name (print): Bruce W. Hinslev Signature:
Certification No.: A25212 License. No.: 92173M
Testing Company Name: Cal - Valley Eouipment Phone No.:(881) 327 -9341
Testing Company Address: 3500 Gilmore Ave. Bakersfield. Co. 93308 Date of Testing/Servicing: 12 / 15 / 2010
Monitoring System Certification Page 1 of 4
12/07
2/21/07
D. Results of Test]ng/Servlcing
Software Version Installed: 123.02
Comolete the followlno checklist:
X Yes
❑ No'
Is the audible alarm operational?
X Yes
❑ No'
Is the visual alarm operational?
X Yes
❑ No'
Were all sensors visually Inspected, functionally tested, and confirmed operational?
X Yes
❑ No'
Were all sensors Installed at lowest point of secondary containment and positioned so that other equipment will not interfere with their
proper o ration?
❑ Yes
❑ No'
If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) operational?
X N/A
Yes
X No'
For pressurized piping systems, does the turbine automatically, shut down if the piping secondary containment monitoring system
❑ NIA
detects a leek falls to operate, or Is electrically disconnected? If yes: which sensors initiate positive shut-down? (Check all that apply)
X Sump/Trench Sensors; Dispenser Containment Sensors. Did you confirm positive shut -down due to leaks Ia sensor
failureldisconnection? XYes• ❑ No.
❑ Yes
❑ No'
For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e, no mechanical overfill prevention
X N/A
valve Is Installed), Is the overfill warning alarm visible and audible at the tank fill point(s) and operating properly? If so, at what percent
of tank capacity does the alarm tri er? %
❑ Yes'
X No
Was any monitoring equipment replaced? If yea, Identify specific sensors, probes, or other equipment replaced and list the
manufacturer name and model for all replacement parts in Section E below.
❑ Yes'
X No
Was liquid found inside any secondary containment systems designed as dry systems? (Check a// that apply) ❑ Product; ❑ Water. If
es, describe causes in Section E below.
X Yea
❑ No'
Was monitoring system set-up reviewed to ensure proper settings? Attach set up reports, if applicable
X Yea
❑ No'
Is all monitoring equipment operational per manufacturers specifications?
• In Section E below, describe how and when these deficiencies were or will be corrected.
Comments:
Performed Product line testing.
Monitoring System Certification Page 2 of 4 12107
2/21/07
F. In -Tank Gauging / SIR Equipment: X Check this box if tank gauging is used only for inventory control.
❑ Check this box if no tank gauging or SIR equipment is Installed.
This section must be completed If In -tank gauging equipment is used to perform leak detection monitoring.
Loom fete me
r000wm cnecmim:
❑ No'
Yes
❑ No'
Has all Input wiring been inspected for proper entry and termination, Including testing for ground faults?
Yes
❑ No'
Were all tank gauging probes visually inspected for damage and residue buildup?
Yes
❑ No'
Was accuracy of system product level readings tested?
Yes
D No'
Was accuracy of system water level readings tested?
Yee
Cl No'
Were all probes reinstalled properly?
Yes
❑ No'
Were all items on the equipment manufacturer's maintenance checklist completed?
In the aecuon n, oelow, as cnae now ana wren mesa aenciencles were or Win ae corrected.
II G. Line Leak Detectors (LLD): ❑ Check this box If LLDs are not Installed.
1 !`w.....In�n 11,e lnll.�wlnn whn..Lllu�•
•
Yes
❑ No'
For equipment start-up or annual equipment certification, was a leak simulated to verity LLD performance? (Check all
❑ WA
that apply) Simulated leak rate: X 3 g.p.h.; 0 0.1 g.p.h ; ❑ 02 g.p.h.
•
Yes
❑ No'
Were an LLDs confirmed operational and accurate within regulatory requirements?
•
Yes
❑ No'
Was the testing apparatus properly calibrated?
•
Yes
❑ No*
For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
❑ WA
❑
Yes
0 No'
For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak?
X WA
❑
Yes
❑ No'
For electronic LLDS, does the turbine automatically shut off if any portlon of the monitoring system is disabled or
X WA
disconnected?
❑
Yes
0 No'
For electronic LLDs, does the turbine automatically shut off if any portion of tt7e monitoring system malfunctions or
X WA
fails a test?
❑
Yes
❑ No'
For electronic LLDs, have all accessible wiring connections been visually Inspected?
X WA
X
Yes
❑ No'
Were all items on the equipment manufacturer's maintenance checklist completed?
In the Section H, below, describe how and when these deficiencies were or will be corrected.
H. Comments:
Monitoring System Certification Page 3 of 4 12107
3 2/21/07
Monitoring System Certification
UST Monitoring Site Plan
She Address: _ 4101 Truxtun Ave. Bakersfield. Ca.
Date map was drawn: _j2_1 ;_/2010 .
Instructions
If you already have a diagram that shows all required information, you may include it, rather than thla page, with your Monitoring System
Certification. On your site plan, show the general layout of tanks and piping. Clearly Identify locations of the following equipment, it installed:
monitoring system control panels; sensors monitoring tank annular spaces, sumps, dispenser pans, spill containers, or other secondary
containment areas; mechanical or electronic line leak detectors; and in -tank liquid level probes (if used for leak detection). In the space
provided, note the date this Site Plan was prepared.
Monitoring System Certification Page 4 of 4 12107
4 2/21/07
CAL- VALLEY EQUIPMENT
3500 Gilmore Avenue
AES PLT -100R Bakersfield, CA 93308
Ph#661- 327 -9341
Fax#661- 325 -2529
NAME:
Bakersfield City Corp. Yard
LINE #1:
Diesel
TECHNICIAN:
Bruce W. Hinsle
ADDRESS:
4101 Truxtun Ave.
LINE #2:
87 UL
LICENSE #:
90 -1069
CITY/ ST.:
Bakersfield, Ca.
LINE #3:
-0.021
TEST DATE:
12/15/2010
-HE CONVERSION CONSTANT IS FOUND BY: (60 MIN /HR) / (37901MIL/GAL) = 0.0158311 (MIN/HOUR (GAL/MIN)
Wide the volume differential by the test time (15 minutes) and multiply by 0. 0158311, which will convert the volume differential from milliliters per
ninute to gallons per hour. The conversion constant causes the millimeters and minutes to cancel out
PRODUCT
TIME.
PSI
START VOL
ml
END VOL
ml
TEST VOL
DIFF. ml
GPH GAIN/LOSS (ml)
PASS
FAIL
Diesel
10:10
50
222
201
21
-0.021
X
°
10:25
50
201
181
21
-0.020
x
COMMENTS:
PRODUCT
TIME
PSI
START VOL
ml
END VOL
(mo
TEST VOL
DIFF. ml
GPH GAIN/LOSS (ml)
PASS
FAIL
87 UL
11:40
50
200
177
23
-0.023
x
°
11:55
50
177
155
22
-0.022
x
COMMENTS:
PRODUCT
TIME
PSI
START VOL
ml
END VOL
ml
TEST VOL
DIFF. ml
GPH GAIN/LOSS (ml)
PASS
FAIL
COMMENTS:
I declare under penalty of perjury that I am a licensed tank tester in the State of California and I X
that the information in this report is true and correct to the best of my knowledge. w
CVE
Cal- Valley Equipment
3500 Gilmore Ave.
Bakersfield CA 93308
661 - 327 -9341 FAX# 661 -325 -2529
VAPORLESS MAr1UFACrURING, INC.
LDT -890 Leak Detector Temt Record
Contractor. Cal-Valley Equipment
Customer: Bakersfield City Corp Yard
Date: 12/15/2010
Location: 4101 Ttvxtun Ave.
Bakersfield, Ca.
Product: Diesel
Technician: Bruce W. Hinsle
I Manufacturer: F E Petro I Model No.: I
Serial No.:
Leak Detector identification
Manufacturer: Red'acket
Description:
Dia
Piston-type: PLD
Tamper -proof seal installed:
Other Style Leak Detector:
Notes:
Leak Detector in Submersible Pumn Test at Dianenser
Operating Pump Pressure (psi): 28
(para. 15
Gallons per hour rate: 3.0
.22
Line pressure with pump shut off (psi): 20
23
Bleed -back Test with pump off (ml): 60
(para. 26
Step-through Step-through time to full flow (secs): 3
(para. 30
Leak detector stays in leak search position (Yes/No): Yes
42
Leak Detector Test
Pass / Fail Notes:
Pass _
*Complete thermal expansion test before failing leak detector
CVE
Cal- Valley Equipment
3500 Gilmore Ave.
Bakersfield CA 93308
661 - 327 -9341 FAX# 661 - 325 -2529
VAPORLESS MANUFACTURING, INC.
LDT -890 Leak Detector Test Record
Contractor: Cal-Valley Equipment
Customer: Bakersfield City Corp Yard .
Date: 12/15/2010
Location: 4101 Truxtun Ave.
Bakersfield Ca.
Product: 87 UL
Technician: Bruce W. Hinsle
Submersible Pumn Identification
E Petro
Serial No.: I Notes: I
Leak Detector Identification
Manufacturer: Red'acket
Description:
Diaphragm-type:
Piston-type: PLD
Tamper -proof seal installed:
Other Style Leak Detector:
Notes:
Leak Detector in Submersible Pump Test at Dispenser
Operating Pressure (psi): 28
ara 15
Gallons per hour rate: 3.0
22
Line pressure with pump shut off (psi): 25
23
Bleed -back Test with pump off (ml): 55
26
St through time to full flow (secs): 3
30
Leak detector stays in leak search position (Yes/No): Yes
42
Leak Detector Test
Pass / Fail
Notes:
Pass
*Complete Thermal expansion test before failing leak detector
«.. �,.
_ ....- _.. -__---- - _... -----------
. . - - .. - ......_
x x x x END x ** x
VERSIOtV 123.02
ALARM HISTORY REPORT
SOFTWARE# 346123 -100 —C
CREATED — 02.11.25.15.17
- - -- IN —TANK ALARM - - - --
NO SOFTWARE MODULE
T 21DIESEL —NO.2
SYSTEM FEATURES:
PERIODIC IN —TANK TESTS
y
ANNUAL IN —TANK TESTS
DELIVERY NEEDED
3
DEC 14, 2010 2:43 PM
DEC 3, 2010 1:01 PM
NOV 23, 2010 6:32 AM
r
I
ALARM HISTORY REPORT
II
-- i
I�lI -- SENSOR ALARM --- --
d.
L 3:DIESEL STP
d
ddd STP SUMP
A FUEL ALARM
ALARM HISTORY REPORT
`
DEC 15, 2010 i0:00 AM
l
-- SYSTEM ALARM - - - --
'•"FUEL ALARM
DEC 18, 2009 9:37 AM
R PAPER OUT
NOV 19, 2010 8:00 AM
x x x x x END x * x x *
-FUEL ALARM
PR [ tVTER ERROR
NOV 19, 2010 8:00 AM
1; DEC 18, 2009 6:24 AM
. BATTERY IS OFF
JAN 1, 1996 8:00 AM I
i
ALARM HISTORY REPORT
x x x x x END x x x x x
- - - -- SENSOR ALARM - - - --
x x* x x END x x x x x
L 1:UNLEADED STP
STP SUMP
I.
FUEL ALARM
DEC 15, 2010 10:00 AM
FUEL ALARM
I
li !l
DEC 16, 2009 9:37 AM
FUEL ALARM
DEC 18, 2009 8:19 AM
ALARM HISTORY REPORT
— SENSOR ALARM - --
C ALARM HISTORY REPORT
4:DIESEL ANNULAR
`
fL
ANNULAR SPACE
- - -- IN —TANK ALARM - -- --
FUEL ALARM
I� DEC 15, 2010 10:07 AM
T 1:UNLEADED
t' j
I FUEL ALARM
HIGH WATER ALARM
DEC 18. 2009 9:37 AM
AUG 24, 2005 11:54 AM
fxxxxENDxxxxx
FUEL ALARM
OVERFILL ALARM
DEC 18, 2009 8:28 AM
JAN 5, 2004 8:14 AM
NOV 7, 2003 11 :42 AM
HIGH PRODUCT ALARM
JAN S. 2004 8:14 AM
NOV 7, 2003 11:39 AM i
PRO13E OUT
DEC 22, 2003 11:18 AM
HIGH WATER WARNING
ALARM HISTORY REPORT
x x x x x END x x x x x
j AUG 24, 2005 11:54 AM
�
----- SENSOR ALARM -- - --
4,. -
L 2:UNLEADED ANNULAR
DELIVERY NEEDED
ANNULAR SPACE
DEC 9, 2010 6:24 AM
FUEL ALARM
NOV 24, 2010 9:40 AM
DEC 15, 2010 10:05 AM
NOV 10, 2010 2:01 PM
FUEL ALARM
DEC 18, 2009 9:38 AM
FUEL ALARM
DEC 18. 2009 8 :22 AM
. ..
PERIODIC TEST TYPE
STANDARD
ANNUAL TEST FAIL
i ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
I GROSS TEST FAIL
fff ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
I
DELIVERY DELAY 3 MIN
PUMP THRESHOLD 10.00X
LEAK TEST METHOD
TEST ON DATE : ALL TANK
JAN 1, 1996
START TIME : DISABLED
TEST RATE :0.20 GAL/HR
DURATION 2 HOURS
TST EARLY STOP:DISAELED
LEAK TEST REPORT FORMAT
NORMAL
. l t
1
OUTPUT RELAY SETUP
f R !:UNLEADED —STP
TYPE:
STANDARD
NORMALLY CLOSED
IN —TANK ALARMS
T !:HIGH WATER ALARM
T !:LOW PRODUCT ALARM
LIQUID SENSOR ALMS
1 L !:FUEL ALARM
L !:SENSOR OUT ALARM
L 2:SENSOR OUT ALARM
L !:SHORT ALARM
L 2:SHORT ALARM
R 2.:DIESEL STP
TYPE:
STANDARD
1ORMALLY CLOSED
IN —TANK ALARMS
T 2.:HIGH WATER ALARM
T 2:LOW PRODUCT ALARM
LIQUID SENSOR ALMS
L 3 :FUEL ALARM
L 3:SENSOR OUT ALARM
L 4:SENSOR OUT ALARM
L 3:214ORT ALARM
L 4:SHORT ALARM
R 3:REMOTE BEACON
TYPE:
STANDARD
NORMALLY CLOSED
IN —TANK ALARMS
ALL:LOW PRODUCT ALARM
LIQUID SENSOR ALMS
ALL:FUEL ALARM
ALL:SENSOR OUT ALARM
ALL:SHORT ALARM
LIQUID SENSOR SETUP
L 1 :UNLEADED STP
TRI —STATE (SINGLE FLOAT)
CATEGORY : STP SUMP
L 2:UNLPADED ANNULAR
TRI —STATE (SINGLE FLOAT)
CATEGORY : ANNULAR SPACE RECONCILIATION SETUP
I L 3:DIESEL
PERIODIC TEST TYPE
AUTOMATIC DAILY CLOSING
TRI —STATE
QUICK
:' TINE: 2:00 AM
ANNUAL TEST FAIL
STP SUMP
ALARM DISABLED
j
PERIODIC TEST FAIL
_
ALARM DISABLED
L 4:DIES£L
GROSS TEST FAIL
TRI —STATE
ALARM DISABLED
TEMP COMPENSATION
STANDARD
ANN TEST AVERAGING:
OFF
;.
PER TEST AVERAGING:
OFF
TANK TEST NOTIFY:
OFF .:
c BUS SLOT FUEL METER TANK
TNK TST SIPHON SREAK:OFF .f
1s
.DELIVERY DELAY
3 MIN
i
PUMP THRESHOLD 10.00%
J
1
T 2:DIESEL —NO.2
PRODUCT CODE
2
THERMAL COEFF :.000470
TANK DIAMETER 119.36
TANK PROFILE
4 PTS
FULL VOL
14783
89.5 INCH VOL
12023
59.7 INCH VOL
7400 ,
29.8 INCH VOL
2750
FLOAT SIZE: 4.0
IN. {
WATER WARNING
2.0
HIGH WATER LIMIT:
4.0
MAX OR LABEL VOL:
14783 '
OVERFILL LIMIT
990Ac
14635
HIGH PRODUCT
98K JI
II
14487 ;
DELIVERY LIMIT
40%
pt
5913
s
LOW PRODUCT
300 `I
LEAK ALARM LIMIT:
99 d
SUDDEN LOSS LIMIT:
99 ;
TANK TILT —
0.25 .!
PROBE OFFSET
0.00
SIPHON MANIFOLDED TANKS
TO: NONE
LINE MANIFOLDED TANKS
TO: NONE
LEAK MIN PERIODIC:
0)t
LEAK MIN ANNUAL :
ox }:
0
PERIODIC TEST TYPE
STANDARD
ANNUAL TEST FAIL
i ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
I GROSS TEST FAIL
fff ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
I
DELIVERY DELAY 3 MIN
PUMP THRESHOLD 10.00X
LEAK TEST METHOD
TEST ON DATE : ALL TANK
JAN 1, 1996
START TIME : DISABLED
TEST RATE :0.20 GAL/HR
DURATION 2 HOURS
TST EARLY STOP:DISAELED
LEAK TEST REPORT FORMAT
NORMAL
. l t
1
OUTPUT RELAY SETUP
f R !:UNLEADED —STP
TYPE:
STANDARD
NORMALLY CLOSED
IN —TANK ALARMS
T !:HIGH WATER ALARM
T !:LOW PRODUCT ALARM
LIQUID SENSOR ALMS
1 L !:FUEL ALARM
L !:SENSOR OUT ALARM
L 2:SENSOR OUT ALARM
L !:SHORT ALARM
L 2:SHORT ALARM
R 2.:DIESEL STP
TYPE:
STANDARD
1ORMALLY CLOSED
IN —TANK ALARMS
T 2.:HIGH WATER ALARM
T 2:LOW PRODUCT ALARM
LIQUID SENSOR ALMS
L 3 :FUEL ALARM
L 3:SENSOR OUT ALARM
L 4:SENSOR OUT ALARM
L 3:214ORT ALARM
L 4:SHORT ALARM
R 3:REMOTE BEACON
TYPE:
STANDARD
NORMALLY CLOSED
IN —TANK ALARMS
ALL:LOW PRODUCT ALARM
LIQUID SENSOR ALMS
ALL:FUEL ALARM
ALL:SENSOR OUT ALARM
ALL:SHORT ALARM
LIQUID SENSOR SETUP
L 1 :UNLEADED STP
TRI —STATE (SINGLE FLOAT)
CATEGORY : STP SUMP
L 2:UNLPADED ANNULAR
TRI —STATE (SINGLE FLOAT)
CATEGORY : ANNULAR SPACE RECONCILIATION SETUP
I L 3:DIESEL
STP
AUTOMATIC DAILY CLOSING
TRI —STATE
(SINGLE FLOAT)
:' TINE: 2:00 AM
CATEGORY
STP SUMP
1
PERIODIC RECONCILIATION
MODE: MONTHLY .
L 4:DIES£L
ANNULAR
TRI —STATE
(SINGLE FLOAT)
TEMP COMPENSATION
STANDARD
CATEGORY
ANNULAR SPACE.{
c BUS SLOT FUEL METER TANK
i
;Y. — — — — — — — — — — — —
TANK MAP EMPTY
,
1
k
SYSTEM SETUP
DEC 15. 2010 12:41 PM
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH :MM:SS xM
CITY CORP. YARD
4101 TRUXTON AVE.
SAKERSERFID CA.93309
661- 326 -3795
SHIFT TIME I DISABLED
SHIFT TIME 2 : DISABLED
SHIFT TIME 3 DISABLED
SHIFT TIME 4 DISABLED
TANK PER TST NEEDED WRN
DISABLED
TANK ANN TST NEEDED WRN
DISABLED
LINE RE- ENABLE METHOD
PASS LINE TEST
LINE PER TST NEEDED WRN
DISABLED
LINE ANN TST NEEDED URN
DISABLED
PRINT TC VOLUMES
ENABLED
TEMP COMPENSATION
VALUE (DEC F ): 60.0
STICK HEIGHT OFFSET
DISABLED
DAYLIGHT SAVING TIME
i
ENABLED
START DATE
APR WEEK 1 SUN
�1
START TIME
+I
2:00 AM
i
END DATE
OCT WEEK 6 SUN
END TIME
2:00 AM
¢
(.i
CUSTOM ALARM LABELS
DISABLED
COMMUNICATIONS SETUP
PORT SETTINGS:
NONE FOUND.:-
.
RS -232 END OF MESSAGE
DISABLED
1N -TANK SETUP
T 1:UNLEADED
PRODUCT CODE 1
THERMAL COEFF :.000700
TANK DIAMETER 119.38
TANK PROFILE 4 PTS
FULL VOL 14783
89.5 INCH VOL 12023
59.7 INCH VOL 7400
29.8 INCH VOL 2750
FLOAT SIZE: 4.0 IN, j
WATER WARNING 2.0
HIGH WATER LIMIT: 4.0
MAX OR LABEL VOL: 14783
OVERFILL LIMIT 99%
14635
HIGH PRODUCT 9B%
14487
DELIVERY LIMIT 40%
5913..
LOW PRODUCT 300 :