HomeMy WebLinkAboutFMC 2013els 1~ environmental services, inc. 25971 Towne Centre Drive, Foothill Ranch, CA 92610 Tel: (949) 460-5200 Fax: (949) 460-5210 Date: To: From: Sent Via: Re: 12/16/2013 Ernie Medina Bakersfield Fire Dept. 1500 Truxtun Ave Bakersfield, CA 93301 Billy Moothart Email Monitoring System Cert Foods Co # 384 2501 Haley St. Bakersfield, CA 93305 TRANSMITTAL The following test report(s) are included: Monitoring System Cert Comments: Please do not hesitate to call me at (949) 460-5200 if you have any questions or concerns regarding this work. 936527 Appendix VI (Copies of Monitoring System Certification form and UST Monitoring Plot Plan available at http://www.waterboards.ca.gov.) MONITORING SYSTEM CERTIFICATION For Use By All Jurisdictions Within the State of California Authority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner/operator. The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date. A. General Information Facility Name: Foods Co # 384 Bldg. No.: ______ _ Site Address: 2501 Haley St. City: Bakersfield Zip: 93305 Facility Contact Person: _________________ Contact Phone No.: { (661) 813_-_2_05_2 _______ _ Make/Model of Monitoring System: -'-T-'-'L-=-S--'-3'--'5-'-0 ____________ _ Date of Testing/Servicing: __ 1_2_/51_2_0_1_3 __ _ B. Inventory of Equipment TestecVCertified Ch k h . b . d" T ec t e appropnate oxes to 1n 1cate spec1 1c equ1pment ms ~ecte dl d serv1ce : Tank ID: Unleaded Tank 10· Premium ~ In-Tank Gauging Probe. Model: 846390-110 ~ . Model: 8216390-110 ~ In-Tank Gauging Probe. ~ Annular Space or Vault Sensor. Model: 794380-303 ~ Annular Space or Vault Sensor. Model: Soli! w1th D1esel ~ Piping Sump I Trench Sensor(s). Model: 794380-323/304 ~ Piping Sump I Trench Sensor(s). Model: 7921380-32373021 ?_ Fill Sump Sensor(s). Model: 794380-323/304 ~ Fill Sump Sensor(s). Model: 794380-3237304 --. Mechanical Line Leak Detector. Model: --. Mechanical Line Leak Detector. Model: ~ Electronic Line Leak Detector. Model: PLLD ~ Electronic Line Leak Detector. Model: PLLD ?_ Tank Overiill I High-Level Sensor. Model: 846390-110 ?_ Tank Overiill/ High-Level Sensor. Model: 846390-110 ~ Other (specify equipment type and model in Section E on Page 2). ~ Other (specify equipment type and model in Section E on Page 2). ~nk ID: U1ese1 I!lnk ID: ~ In-Tank Gauging Probe. Model: 846390-110 ~ In-Tank Gauging Probe. Model: Annular Space or Vault Sensor. Model: 794380-303 ~ Annular Space or Vault Sensor. Model: Piping Sump I Trench Sensor(s). Model: 794380-3237304 ~ Piping Sump I Trench Sensor(s). Model: ~ Fill Sump Sensor(s). Model: 794380-323/304 ~ Fill Sump Sensor(s). Model: ~ Mechanical Line Leak Detector. Model: ~ Mechanical Line Leak Detector. Model: ~ Electronic Line Leak Detector. Model: PLLD ~ Electronic Line Leak Detector. Model: ~ Tank Overiill I High-Level Sensor. Model: 846390-110 ~ Tank Overiill I High-Level Sensor. Model: ~ Other (specify equipment type and model in Section E on Page 2). ~ Other (specify equipment type and model in Section E on Page 2). Dispenser ID: 1 I 2 ~"'"""'"' 314 ~ Dispenser Containment Sensor(s). Model: 794380-323/304 Dispenser Containment Sensor(s). Model: 794380-323/304 Shear Valve(s). Shear Valve(s). Dispenser Containment Float(s) and Chain(s). Dispenser Containment Roat(s) and Chain(s). Dispenser ID: 5 I 6 Dispenser ID: 7 I 8 ~ Dispenser Containment Sensor(s). Model: 794380-323/304 ~ Dispenser Containment Sensor(s). Model: 794380-323/304 Shear Valve(s). Shear Valve(s). Dispenser Containment Roat(s) and Chain(s). Dispenser Containment Roat(s) and Chain(s). Dispenser 1 D: 9 I 1 0 DispenseriD: 11/12-13/14 ~ Dispenser Containment Sensor(s). Model: 794380-3237304 ~ Dispenser Containment Sensor(s). Model: 794380-323/304 Shear Valve(s). Shear Valve(s). Dispenser Containment Float(s) and Chain(s Dispenser Containment Roat(s) and Chain(s). . .. .. If the facility conta1ns more tanks or dispensers, copy this form. Include 1nformat1on for every tank and dispenser at the facility . C. Certification -I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers' guidelines. Attached to this Certification is information (e.g. manufacturers' checklists) necessary to verify that this information is correct and a Plot Plan showing the layout of monitor.JrljJ equipment. For any equipment capable of generatin. g sue. h reports, I have also attached a copy of the report; (check a// that apply): ~System set-up ~Alarm history report ./ : rl ~· J'YL '-,-/ Technician Name (print): Sheer Signature: d'fn · • l Certification No.: 837955 License. No.: 808313 / Testing Company Name: Belshire Environmental Services, Inc. Phone No.:~)_4_6_0-_5_2_00 ________ _ Testing company Address: 25971 Towne Centre Dr., Foothill Ranch, CA 92610 Date of Testing/Servicing: 12/5/2013 Monitoring System Certification Page 1 of4 12/07 D. Results of Testing/Servicing Software Version Installed: 330.01 ~~~~~~~~~~~~~~~--- c omp1ete t h f II h kl" e o owmg_c ec IS!: li']Yes 0 No* Is the audible alarm operational? li']Yes 0 No* Is the visual alarm operational? I [Yes ~No* Were all sensors visually inspected, functionally tested, and confim1ed operational? li']Yes D No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not interfere wah their proper operation? bl]Yes D No* If alam1s are relayed to a remote monitoring station, is all communications equipment (e.g. modem) operational? NIA li']Yes B No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment monitoring system N/A ~eels a leak, fails to operat~or is electrically disconnected? If yes: which sensors initiate positive shut-down? {Check all that apply) Sump/Trench Sens~ ~ispenser Containment Sensors. Did you confirm positive shut-down due to leaks .5!lli! sensor failure/disconnection? '1/ es; No. li']Yes B No* For tank systems that utilize the monit01ing system as the primary tank overfill warning device (i.e. no mechanical overfill prevention N/A valve is installed), is the overfill warning alarm visible and audible at the tank fill point(s) and operating properly? If so, at what percent of tank capac tty does the alam1 triQQer? 90 % UYes* ~No Was any monttoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E, below. UYes* bl) No Was liquid found inside any secondary containment systems designed as dry systems? {Check all that apply)UProduct; UWater. If yes, describe causes in Section E, below. bl]Yes L J No* Was monitoring system set-up reviewed to ensure proper settings? Attach set up reports, if applicable fV']Yes f l No* Is all monitoring equipment operational per manufacturer's specifications? .. *In Section E below, descnbe how and when these def1c1enc1es were or Will be corrected. E. Comments: Vent box 794380-323/304 S 11 in no vac alarm S13 did not go into high liquid alarm Monitoring System Certification Page 2 of4 12/07 F. In-Tank Gauging I SIR Equipment: ~ Check this box if tank gauging is used only for inventory control. D Check this box if no tank gauging or SIR equipment is installed. This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring. Complete the following checklist· DYes 0 No* Has all input wiring been inspected for proper entry and termination, including testing for ground faults? DYes 0 No* Were all tank gauging probes visually inspected for damage and residue buildup? DYes 0 No* Was accuracy of system product level readings tested? DYes 0 No* Was accuracy of system water level readings tested? DYes 0 No* Were all probes reinstalled properly? DYes 0 No* Were all items on the equipment manufacturer's maintenance checklist completed? .. *In the Sect1on H, below, descnbe how and when these defiCiencies were or Will be corrected. G. Line Leak Detectors (LLD): D Check this box if LLDs are not installed. Complete the following checklist: ~Yes 8 No* For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance? (Check all N/A that apply) Simulated leak rate: ~3 g.p.h.; Do.1 g.p.h; D 0.2 g.p.h. bl] Yes i J No* Were all LLDs confirmed operational and accurate within regulatory requirements? ~Yes 0 No* Was the testing apparatus properly calibrated? U Yes kJ No* For mechanical LLDs, does the LLD restrict product flow if it detects a leak? N/A bl] Yes tj No* For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak? N/A ~Yes 8 No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or NIA disconnected? ~Yes 8 No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or N/A fails a test? ~Yes 8 No* For electronic LLDs, have all accessible wiring connections been visually inspected? N/A ~ Yes UNo* Were all items on the equipment manufacturer's maintenance checklist completed? . . * In the Section H, below, descnbe how and when these def1c1enc1es were or will be corrected . H. Comments: Monitoring System Certification Page 3 of4 12/07 environmental services, inc. <!tiU/'1 lowm~ Centre Drive. fCo1Jlhili Rwu.:h, CA U2610 Leak Detector Test Form """ Location Name: Foods Co# 384 Date: 12/5/2013 ~~~-~.~ .. ~. --~. ~·~· ~ ... ~-~~~.~~-··~.~. ~.~~.~ .. ~"~" ~ .. ·~~· ·-~· -.~. ~ .. ~~"-~- Address: 2501 Haley St. Agency: Bakersfield Fire Dept City, State Bakersfield, CA Inspector: Line Number: 1 2 3 4 Product: Unleaded Premium Diesel Manufacturer: Veeder Root Veeder Root Veeder Root Model#: PLLD PLLD PLLD Full Operating Pressure (psi): 32 31 32 Line Bleed Back (ml): 120 100 110 Trip Time (sec): N/A N/A N/A Metering Pressure (psi): N/A N/A N/A "" FIE Holding Pressure (psi) N/A N/A N/A "" Test Leak Rate (gph) 3.0 3.0 3.0 Pass/Fall Pass Pass Pass Comments: Technician Name Technician Signature SWRCB, January 2006 Spill Bucket Testing Report Form This form is intended for use by contractors performing annual testing of UST spill containment stmctures. The completed form and printouts from tests (if applicable), should be provided to the facility owner/operator for submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: Foods Co# 384 J Date of Testing: 12/5/2013 Facility Address: 2501 Haley St. Facility Contact: I Phone: 6618732052 Date Local Agency Was Notified of Testing: 10/15/2013 Name of Local Agency Inspector (if present during testing): 2. TESTING CONTRACTOR INFORMATION Company Name: Belshire Environmental Services, Inc. Technician Conducting Test: Jerry Sheer Credentials 1: ~ CSLB Contractor DICC Service Tech. 0 SWRCB Tank Tester OOther (Specify) License Number(s): 808313 3. SPILL BUCKET TESTING INFORMATION Test Method Used: ~Hydrostatic 0Vacuum D Other Test Equipment Used: Visual Equipment Resolution: Identify Spill Bucket (By Tank 1 91 F 2 91 v 3 Diesel F 4 Number, Stored Product, etc.) Bucket Installation Type: Contained in Sump Contained in Sump Contained in Sump Bucket Diameter: 12" 12" 12" Bucket Depth: 12" 12" 12" Wait time between applying 10 min 10 min 10 min vacuum/water and start of test: Test Start Time (T1): 09:00am 09:00am 09:00am Initial Reading (R1): 11 11 11 Test End Time (T p): 10:00 am 10:00 am 10:00 am Final Reading (Rp): 11 11 11 Test Duration (Tp-T1): 60 60 0 Change in Reading (RF-R1): 0.0000 0.0000 0.0000 Pass/Fail Threshold or Criteria: No Visual Loss No Visual Loss No Visual Loss No Visual Loss Test Result: ~Pass D Fail ~Pass DFail ~Pass DFail DPass D Fail Comments -(include infonnation on repairs made prior to testing, and recommended follow-up for failed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the infonnation contained in this report is true, accurate, and in full compliance with legal requirements. ;/ t'~ l (/;rJ-ilv'--tlt-Date: 12/5/2013 1 State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements may be more stringent. SWRCB, January 2006 Spill Bucket Testing Report Form This form is illtended for use by contractors pe1jorming annual testing of UST spill containment structures. The completed form and printouts from tests (if applicable), should be provided to the facility owner/operator for submittal to the local regulatOI)' agency. 1. FACILITY INFORMATION Facility Name: Foods Co# 384 / Date of Testing: 12/5/2013 Facility Address: 2501 Haley St. Facility Contact: I Phone: 6618732052 Date Local Agency Was Notified of Testing: 10/15/2013 Name of Local Agency Inspector (if present during testing): 2. TESTING CONTRACTOR INFORMATION Company Name: Belshire Environmental Services, Inc. Technician Conducting Test: Jerry Sheer Credentials 1: ~ CSLB Contractor OICC Service Tech. 0 SWRCB Tank Tester OOther (Specify) License Number(s): 808313 3. SPILL BUCKET TESTING INFORMATION Test Method Used: ~Hydrostatic OVacuum 0 Other Test Equipment Used: Visual Equipment Resolution: Identify Spill Bucket (By Tank 1 87 MF1 2 87 MV 1 3 87 MF2 4 87 MV2 Number, Stored Product, etc.) Bucket Installation Type: Contained in Sump Contained in Sump Contained in Sump Contained in Sump Bucket Diameter: 12" 12" 12" 12" Bucket Depth: 12" 12" 12" 12" Wait time between applying 10 min 10 min 10 min 10 min vacuum/water and start of test: Test Start Time (T1): 09:00am 09:00am 09:00am 09:00am Initial Reading (R1): 11 11 11 11 Test End Time (T p): 10:00 am 10:00 am 10:00 am 10:00 am Final Reading (Rp): 11 11 11 11 Test Duration (TF-T1): 60 60 60 60 01ange in Reading (RF-R1): 0.0000 0.0000 0.0000 0.0000 Pass/Fail Threshold or No Visual Loss No Visual Loss No Visual Loss No Visual Loss Criteria: Test Result: ~Pass 0 Fail ~Pass 0Fail ~Pass OF ail ~Pass 0 Fail Comments -(include infonnation on repairs made prior to testing, and recommended follow-up for failed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the infonnation contained in this report is true, accurate, and in full compliance with legal requirements. / ' ti ,-IJ\\ !~ IIJt)· 'lu'-1 ~,(-Technician's Signature:. _ f/.---------~.7~----~~------------------ / Date: 12/5/2013 1 State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements may be more stringent. Monitoring System Certification Form: Addendum for Vacuum/Pressure Interstitial Sensors LG 163-l, Enc. II I. Results of Vacuum/Pressure Monitoring Equipment Testing This page should be used to document testing and servicing of vacuum and pressure interstitial sensors. A copy of this form must be included with the Monitoring System Certification Form, which must be provided to the tank system owner/operator. The owner/operator must submit a copy of the Monitoring System Certification Form to the local agency regulating UST systems within 30 days of test date. Sensor ID 89 Component(s) Monitored by this Sensor: 87 Product ---------------------------------------------------11 Sensor Functionality Test Result: [K] Pass; D Fail Interstitial Communication Test Result: [K] Pass; D Fail 810 Interstitial Communication Test Result: [ill Pass; D Fail Component(s) Monitored by this Sensor: 87-91 ----~--------------------------------------------_,1 Sensor Functionality Test Result: [ill Pass; D Fail 811 Interstitial Communication Test Result: D Pass; lli] Fail Component(s) Monitored by this Sensor: 87 Ventr . --------------------------------------------------~ Sensor Test Result: [ill Pass; D Fail. Interstitial Communication Test Result: [K] Pass; D Fail 812 Component(s) Monitored by this Sensor: 91 Product --------------------------------------------------~ Sensor Functionali Test Result: [K] Pass; D Fail Interstitial Communication Test Result: [ill Pass; D Fail 813 Component(s) Monitored by this Sensor: 91 Vent --------------------------------------------------~ Sensor Functionali Test Result: D Pass; [X] Fail Component(s) Monitored by this Sensor: Diesel Product --------------------------------------------------~ Sensor Functional Test Result: [ill Pass; D Fail Interstitial Communication Test Result: [ill Pass; D Fail 814 Interstitial Communication Test Result: IX] Pass; D Fail 817 Component(s) Monitored by this Sensor: Diesel Vent ---------------------------------------------------i Sensor Functionality Test Result: IX] Pass; D Fail Component(s) Monitored by this Sensor: ---------------------------------------------------1 Sensor Functionality Test Result: D Pass; D Fail Interstitial Communication Test Result: D Pass; D Fail Component(s) Monitored by this Sensor: ---------------------------------------------------1 Sensor Functionality Test Result: D Pass; D Fail Interstitial Communication Test Result: D Pass; D Fail Component(s) Monitored by this Sensor: ---------------------------------------------------1 Sensor Functional Test Result: D Pass; D Fail Interstitial Communication Test Result: D Pass; D Fail How was interstitial communication verified? [X] Leak Introduced at Far End of Interstitial D Visual Vacuum was restored to operating levels in all interstitial spaces: DYes [XI No (If no, describe in Sec. J, below) J. Comments: 811 in no vac alarm 813 No High liquid alarm BUSINESS NAME: FOODSCO FUEL CENTER #384 SITE ADDRESS: 2501 HALEY STREET MAP DATE: 3/22/13 10,000 DIESEL 8,000 PREMIUM 1-w w 0:: lii > w ...J < X 0 N I SURVEYED BY: FB Driveway I CITY: BAKERSFIELD I DRAWN BY: GK ----~ ..... ~ I • HEIGHT STREET I ZIP: 93305 I FACILITY ID#: PARKING LOT , 0 0 c (/) n 0 !!I 0 ;:o m **NOTE: ALL PIPING LOCATIONS ARE ESTIMATED & SCALING IS APPROXIMATE** ~ CARBON ~ CANNISTER -U DISPENSER VENT RISER VENT BOX PRODUCT PIPING VAPOR RETURN/ VENT LINE • A F T MONITORING PANEL ANNULAR SENSOR FILL SUMP SENSOR TURBINE SUMP SENSOR VEEDER ROOT L LINE LEAK VEEDER ROOT TLS-350R DETECTOR PLLD (8484) VEEDER ROOT' VEEDER ROOT 794380-303 u UDC SENSOR 794380-323 (SUMP) 794380-304 (INTERSTITIAL) VEEDER ROOT VENT BOX VEEDER ROOT 794380-323 (SUMP) v SENSOR 794380-323 (SUMP) 794380-304 (INTERSTITIAL) 794380-304 (INTERSTITIAL) VEEDER ROOT ALL SENSORS SET FOR POSITIVE 794380-323 (SUMP) SHUTDOWN. 794380-304 (INTERSTITIAL) Be 1 shire TLS Po 11 er DO command set ver 5. 7 Started at 12/5/2013 3:28:26 PM I10200 DEC 5, 2013 3:27 PM FOODS CO • 3 84 2505 HALEY BAKERSFIELD CA, 661-873-9343 SYSTEM CONFIGURATION SL~T 2 ~ ~ 7 8 16 11 12 13 14 15 16 BOARD TYPE 4 PROBE / G.T. PLLD SENSOR BD INTERSTITIAL BD INTERSTITIAL BD INTERSTITIAL BD 8SMARTSENSOR BD 7SMARTSENSOR BD 8SMARTSENSOR BD ~~~go pij~~R Bg~RD UNUSED UNUSED UNUSED UNUSED UNUSED UNUSED COMM 1 ELEC DISP INT, CO~IM 2 SERIAL SAT BD COMM 3 UNUSED COMM 4 UNUSED COMM 5 RS485 SERIAL BD COMM 6 RS232 SERIAL BD I20600 DEC 5, 2013 3: 27 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 TANK ALARM HISTORY TANK 1 UN1 OVERFILL ALARM LOW PRODUCT ALARM SUDDEN LOSS ALARM HIGH PRODUCT ALARM INVALID FUEL LEVEL PROBE OUT DELIVERY NEEDED LOW TEMP WARNING TANK PR1 OVERFILL ALARM LOW PRODUCT ALARM SUDDEN LOSS ALARM HIGH PRODUCT ALARM INVALID FUEL LEVEL PROBE OUT HIGH WATER WARNING DELIVERY NEEDED LOW TEMP WARNING TANK 3 DIESEL OVERFILL ALARM LOW PRODUCT ALARM SUDDEN LOSS ALARM HIGH PRODUCT ALARM INVALID FUEL LEVEL PROBE OUT DELIVERY NEEDED MAX PRODUCT ALARM LOW TEMP WARNING !30200 DEC 5, 2013 3:27 PM FOODS CO. 384 POWI~4g~lESET 3919 202970 203082 203127 39544 514845 9949365 9928 102072 9852763 mm~ 9823814 9765830 9mm 9786178 9767641 9753587 68839 15029 DEC 5 , 2013 10: 44 AM NOV 12, 2013 11:39 AM OCT 31, 2013 1:57 AM DEC 15, 2010 3:26 PM DEC 5 , 2013 10: 39 AM g~§ g: ~m 1U~ :: DEC 6 2011 11:46 AM ~5t 28: ~8H 1U8 ~ DEC 15, 2010 2: 55 PM DEC 5, 2013 10:47 AM DEC 5, 2013 10:39 AM DEC 6, 2012 2:49 PM ~~r 2/i' ~8B U8 :~ APR 23: 2013 7:02 PM DEC DEC DEC DEC DEC DEC ~: ~8H 1~:~6 ~ 6, 201111:53 AM ~: ~m 1u~ ~ 6, 2011 11:29 AM 2:35 PM 3:26 PM DEC 6 2012 2:35 PM m 2~: ~8i6 l:U~ ~ DEC 6, 2011 11:29 AM m ~: DEC 15, g~§ ~: DEC 6, DEC 27, DEC 5, OCT 17, JUL 14, 2013 10:35 AM 2011 11; 31 AM 2010 2:55 PM 2013 10:37 AM 2013 10: 34 AM 2012 2:41 PM 2010 1:01 PM 2013 10: 34 AM 2013 4:47 PM 2013 9:40 PM DEC DEC DEC ~: ~8H 1~:H ~ 6, 2011 11:31 AM DEC DEC g~§ 1~: ~m 1U~ ~ NOV12,2013 8:33AM DEC 6, 2012 2:19 PM DEC 29, 2010 12:43 PM DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC DEC 2~: 1~: 2011 11:58 AM 2010 1:31 PM 2013 10:32 AM 2012 2:25 PM 2010 2:55 PM ~: ~8H i8:H ~ 6, 2012 2:25PM ~: ~8B iU~ ~ 6, 2012 2:26 PM DEC 27, 2010 1:31 PM DEC 27, 2010 1:33 PM CURRENT 163590 3930 201773 201888 201819 39448 510153 39514 9936 101934 8459622 8456970 8457956 8453682 8446209 8440533 101216 487065 8452740 84um Page 1 2505 HALEY BAKERSFIELD CA, 661-873-9343 LIQUID ALARM HISTORY REPORT !30700 DEC 5, 2013 3:27 PM I31600 DEC 5 , 2013 3: 2 7 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 SMART SENSOR ALARM HISTORY REPORT LOW LIQUID ALARM SENSOR OUT ALARM FUEL ALARM LOW LIQUID ALARM SENSOR OUT ALARM FUEL ALARM LOW LIQUID ALARM SENSOR OUT ALARM FUEL ALARM LO\~ LIQUID ALARM SENSOR OUT ALARM FUEL ALARM LOW LIQUID ALARM FUEL ALARM SENSOR OUT ALARM LOW LIQUID ALARM SENSOR OUT ALARM FUEL ALARM LOW LIQUID ALARM FUEL ALARM SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM FUEL ALARM SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM SENSOR OUT ALARM FUEL ALARM FUEL ALARM SENSOR OUT ALARM HIGH LIQUID ALARM LOW LIQUID ALARM SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM SENSOR OUT ALARM FUEL ALARM FUEL ALARM SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM SENSOR OUT ALARM FUEL ALARM FUEL ALARM SENSOR OUT ALARM ~ij~H L\:~S~BD At~~~M SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM SENSOR OUT ALARM FUEL ALARM FUEL ALARM SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM SENSOR OUT ALARM FUEL ALARM FUEL ALARM SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM SENSOR OUT ALARM FUEL ALARM FUEL ALARM COMMUNICATION ALARM COMMUNICATION ALARM COMMUNICATION ALARM COMMUNICATION ALARM COMMUNICATION ALARM COMMUNICATION ALARM COMMUNICATION ALARM COMMUNICATION ALARM NO VACUUM ALARM HIGH LIQUID ALARM NO VACUUM ALARM HIGH LIQUID ALARM NO VACUUM ALARM NO VACUUM ALARM HIGH LIQUID ALARM HIGH LIQUID ALARM NO VACUUM ALARM ~6GMIJS~I~L~~~RM NO VACUUM ALARM DEC 5 , 2013 10: 03 AM NO VACUUM ALARM DEC 5, 2013 9:58AM NO VACUUM ALARM 14 DEC 6, 2012 10:53 AM HIGH LIQUID ALARM DIESEL PRODUCT m ~: ~m 18:8~ AM NO VACUUM ALARM AM HIGH LIQUID ALARM DEC 6, 2012 11:05 AM HIGH LIQUID ALARM 15 PMC CANISTER 8:48 AM SENSOR FAULT ALARM JAN 24, 2013 MAR 17, 2012 9:07 AM SENSOR FAULT ALARM JAN 23, 2012 6:09 16 ATM P 17 DIESEL VENT DEC ~: ~8H 18:8~ DEC 6, 2012 11:05 DEC I32300 DEC 5' 2013 3:27 PM I34200 DEC 5' 2013 3:27 PM I34700 DEC 5, 2013 3:27 PM I34C00 DEC 5' 2013 3:27 PM I20700 DEC 5' 2013 3:27 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 TANK LEAK TEST HISTORY T 1:UN1 LAST GROSS TEST PASSED: NO TEST PASSED LAST ANNUAL TEST PASSED: NO TEST PASSED FULLEST ANNUAL TEST PASS NO TEST PASSED LAST PERIODIC TEST PASS: NO TEST PASSED FULLEST PERIODIC TEST PASSED EACH MONTH: TEST START TIME TANK LEAK TEST HISTORY T 2: PR1 LAST GROSS TEST PASSED: NO TEST PASSED LAST ANNUAL TEST PASSED: NO TEST PASSED FULLEST ANNUAL TEST PASS NO TEST PASSED LAST PERIODIC TEST PASS: NO TEST PASSED FULLEST PERIODIC TEST PASSED EACH MONTH: TEST START TIME TANK LEAK TEST HISTORY T 3 :DIESEL LAST GROSS TEST PASSED: NO TEST PASSED LAST ANNUAL TEST PASSED: NO TEST PASSED FULLEST ANNUAL TEST PASS NO TEST PASSED LAST PERIODIC TEST PASS: NO TEST PASSED FULLEST PERIODIC TEST PASSED EACH MONTH: TEST START TIME I31200 DEC 5, 2013 3:27 PM I38200 DEC 5, 2013 3:27 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 PM SENSOR FAULT ALARM AM NO VACUUM ALARM AM HIGH LIQUID ALARM AM HIGH LIQUID ALARM HOURS VOLUME % VOLUME HOURS VOLUME % VOLUME HOURS VOLUME % VOLUME PRESSURE LINE LEAK ALARM HISTORY REPORT Q 1:87 UNLEADED DEC 5, 2013 10:52 AM DEC 5, 2013 10: 20 AM DEC 5, 2013 9:56AM GROSS LINE FAIL PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM TEST TYPE TEST TYPE TEST TYPE Page 2 DEC ~: 2013 9 55 AM DEC 2013 9 52 AM DEC ~: 2013 9 49 AM DEC 2013 9 49 AM DEC ~: 2013 9:48AM DEC 2013 9:45 AM DEC 5' 2013 9:45 AM Q 2:91 UNLEADED DEC 5, 2013 10: 54 AM DEC 5, 2013 10:54 AM DEC 5, 2013 10:20 AM DEC 5, 2013 10:02 AM DEC 5, 2013 9: 56 AM DEC 5' 2013 9:49 AM DEC 5' 2013 9:49 AM DEC ~: 2013 9:48 AM DEC 2013 9:45 AM DEC 5' 2013 9:45 AM Q 3: DIESEL DEC 5' 2013 10:43 AM DEC 5' 2013 10:43 AM DEC ~: 2013 10:32 AM DEC 2013 10: 20 AM DEC 5' 2013 10: 06 AM DEC ~: 2013 9:49 AM DEC 2013 9:49AM DEC 5' 2013 9:48 AM DEC 5' 2013 9:45 AM DEC 5' 2013 9:45 AM I38700 DEC 5' 2013 3:27 PM I40200 DEC 5' 2013 3:27 PM FOODS CO . 3 84 2505 HALEY BAKERSFIELD CA. 661-873-9343 INPUT LOCATION 1 EMERGENCY SHUT OFF PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM GROSS LINE FAIL PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM GROSS LINE FAIL PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM ~~~ 2~: ~8H llH ~ AUG22,2013 9:50AM EXTERN INPUT ALARM EXTERN INPUT ALARM EXTERN INPUT ALARM m 2~: ~8H 1U~ ~ AUG 22, 2013 9:50 AM I20300 DEC 5, 2013 3: 2 7 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 TANK 1 UN1 TEST STATUS: OFF LEAK DATA NOT AVAILABLE ON THIS TANK TANK 2 PR1 TEST STATUS: OFF LEAK OATA NOT AVAILABLE ON THIS TANK TANK 3 DIESEL TEST STATUS: OFF LEAK DATA NOT AVAILABLE ON THIS TANK I25100 DEC 5, 2013 3: 27 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 CSLD TEST RESULTS TANK PRODUCT 200 FOODS CO . 3 84 2505 HALEY BAKERSFIELD CA. 661-873-9343 DEC 5' 2013 3:27 TANK PRODUCT 1 UN1 2 PR1 3 DIESEL 210 FOODS CO • 3 84 2505 HALEY BAKERSFIELD CA. 661-873-9343 TANK 1 UN1 PM TEST STATUS: OFF RESULT GALLONS 12642 3514 1971 LEAK DATA NOT AVAILABLE ON THIS TANK TANK 2 PR1 TEST STATUS: OFF LEAK DATA NOT AVAILABLE ON THIS TANK TANK 3 DIESEL TEST STATUS: OFF LEAK DATA NOT AVAILABLE ON THIS TANK I21300 DEC 5, 2013 3:27 PM FOODS CO. 384 EXTERN INPUT NORMAL EXTERN INPUT NORMAL EXTERN INPUT NORMAL INCHES 71.84 53.86 30.40 WATER DEG F 0.0 64.2 0.0 68.7 0.0 72.7 ULLAGE 7140 4387 8449 2505 HALEY BAKERSFIELD CA. 661-873-9343 DELIVERY REPORT T 1:UN1 INCREASE DATE I TIME HEIGHT 103,09END: DEC 5, 2013 10:51 AM 72 •3~TART: DEC 5, 2013 10:43 AM AMOUNT: END: DEC 81.99 START: DEC 44.82 AMOUNT: END: DEC 84.85 START: DEC 47.59 AMOUNT: END: DEC 84.66 4, 2013 5:57PM 4, 2013 5:38 PM 3, 2013 2:07PM 3, 2013 1:46 PM 2, 2013 2: 44 PM 42 • 95TART: DEC 2, 2013 2:23 PM AMOUNT: 94.89 END: DEC 1, 2013 1:24 AM 51.6lTART: DEC 1, 2013 1:04AM AMOUNT: 83 .57 END: NOV 30, 2013 2:42AM 55 .1~TART: NOV 30, 2013 2:24 AM AMOUNT: 91.58 END: NOV 29, 2013 2:46 AM 53 • 6~TART: NOV 29, 2013 2:16 AM AMOUNT: 95 .61 END: NOV 27, 2013 4:37 PM 57 •2~TART: NOV 27, 2013 4:16PM AMOUNT: BB.OB END: NOV 27, 2013 12:24 AM 46 •2~TART: NOV 26, 2013 11:50 PM AMOUNT: 73 .97 END: NOV 26, 2013 11:16 AM 46 .5~TART: NOV 26, 2013 10:54 AM AMOUNT: T 2:PR1 INCREASE DATE I TIME HEIGHT 104• 97END: DEC 5, 2013 10:44 AM ZO. 5lTART: DEC 5, 2013 10:34 AM AMOUNT: END: DEC 56.33 START: DEC 44.32 AMOUNT: 4, 2013 6:03 P~l 4, 2013 5:53PM 55 .49 END: DEC 3, 2013 2:11PM 43 • 3~TART: DEC 3, 2013 2:02 PM AMOUNT: 76 .76 END: NOV 30, 2013 2:36AM 42 • B~TART: NOV 30, 2013 2:22 AM AMOUNT: 52.53 END: NOV 29, 2013 2:21AM 40 • 3~TART: NOV 29, 2013 2:12 AM AMOUNT: 50.BB END: NOV 27, 2013 4:27 PM 38 .5~TART: NOV 27, 2013 4:18PM AMOUNT: 52 •50 END: NOV 26, 2013 11:29 AM 40.Z~TART: NOV 26, 2013 11:17 AM AMOUNT: END: NOV 24, 2013 12:04 AM GALLONS TC GALLONS WATER TEMP DEG F 18375 12758 5617 14734 6781 7953 15294 7372 7922 15258 6378 8880 17114 8240 8874 15046 9016 6030 16543 8694 7849 17233 9476 7757 15907 7082 8825 13092 7156 5936 18386 0.85 12775 0.00 5611 14698 0.00 6751 0.00 7947 15234 0. 00 7337 0.00 7897 15195 0.00 6345 0.00 8850 17043 0.00 8201 0.00 8842 14977 0.00 8972 0.00 6005 16471 0.00 8652 0.00 7819 17173 0.00 9455 0.00 7718 15884 0.00 7062 0.00 8822 13062 0. 00 7135 0.00 5927 59.11 58.14 63.44 66.31 65.52 66.59 65.82 67.19 65.87 66.84 66.43 66.97 66.16 66.68 64.93 63.12 62.04 63.98 63.25 64.11 GALLONS TC GALLONS WATER TEMP DEG F 7409 929 7367 0.00 923 0.00 6480 6444 3723 2716 1007 3651 2637 1014 5425 2594 2831 3401 2390 1011 3262 2251 1011 3399 2387 1012 4184 3702 0.00 2697 0.00 1005 3625 0.00 2616 0.00 1009 5403 0.00 2573 0.00 2830 3375 0.00 2371 0.00 1004 3240 0.00 2234 0.00 1006 3379 0.00 2369 0.00 1010 4162 0. 00 67.94 68.37 67.85 70.10 70.11 71.08 65.82 71.08 70.53 71.34 69.74 70.53 67.98 70.72 67.30 Page 3 61.79 39 • 9~TART: NOV 23, 2013 11:54 PM AMOUNT: 48 •07 END: NOV 23, 2013 4:08 AM 35 •6lTART: NOV 23, 2013 3:58AM AMOUNT: 48 •40 END: NOV 21, 2013 10:19 PM 35 •9~TART: NOV 21, 2013 10:09 PM AMOUNT: T 3:DIESEL ~~i~~~SE DATE I TIME 103. 63END: DEC 5, 2013 10:37 AM START: DEC 5, 2013 10:28 AM 9.08 AMOUNT: 41•83 END: NOV 26, 2013 11:23 AM 27 •3~TART: NOV 26, 2013 11:13 AM AMOUNT: 40 .31 END: NOV 16, 2013 3:12 AM 25 .5FART: NOV 16, 2013 3:03AM AMOUNT: 57 •90 END: OCT 20, 2013 5:27PM 49 • 3~TART: OCT 20, 2013 5:17 PM AMOUNT: 61.93 END: OCT 9, 2013 7:36 PM 49 .1~TART: OCT 9, 2013 7:25 PM AMOUNT: 50 •74 END: OCT 8, 2013 12:27 PM 5o.o5TART: OCT 8, 2013 12:18 PM AMOUNT: 52 •60 END: OCT 5, 2013 6:30PM 43 • B~TART: OCT 5, 2013 6:20 PM AMOUNT: 48•69 END: SEP 30, 2013 2:14 AM 39 .S~TART: SEP 30, 2013 1:59AM AMOUNT: 46 .00 END: SEP 23, 2013 11:23 PM 3o.z5TART: SEP 23, 2013 11:13 PM AMOUNT: 39 . 7 4 END: SEP 16, 2013 2: 44 AM 35 .0~TART: SEP 16, 2013 2:36 AM AMOUNT: I31800 DEC 5, 2013 3:27 PM !37400 DEC 5 , 2013 3: 2 7 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA, 661-873-9343 PRESSURE LINE LEAK TEST HISTORY 2364 1820 3027 2017 1010 3054 2348 0.00 1814 3009 0.00 2001 0.00 1008 3033 0.00 2043 2026 0. 00 1011 1007 GALLONS TC GALLONS WATER 9756 9704 0.00 300 298 0.00 9456 9406 3176 1678 1498 3008 1515 1493 5046 4033 1013 5526 4013 1513 4198 4111 87 4417 3406 1011 3959 2955 1004 3648 1952 1696 2945 2441 504 3155 0.00 1668 0.00 1487 2986 0.00 1504 0.00 1482 4996 0.00 3994 0.00 1002 5469 0.00 3969 0.00 1500 4152 0.00 4067 0.00 85 4369 0.00 3371 0.00 998 3921 0.00 2924 0.00 997 3607 0.00 1930 0. 00 1677 2911 0.00 2415 0.00 496 Q 1:87 UNLEADED LAST 3.0 PASS: DEC 5, 2013 1:47 PM FIRST 0 .10 PASS EACH MONTH: FIRST 0. 20 PASS EACH MONTH: Q 2:91 UNLEADED LAST 3 . 0 PASS: FIRST 0 .10 PASS EACH MONTH: FIRST 0. 20 PASS EACH MONTH: Q 3 :DIESEL LAST 3.0 PASS: DEC 5, 2013 11:01 AM DEC 5, 2013 11:02 AM 69.43 68.08 70.86 69.75 71.66 TEMP DEG F 71.60 72.74 74.30 73.11 75.77 76.81 81.51 81.24 82.83 84.01 84.04 83.96 83.85 82.73 80.95 83.39 84.64 84.59 85.19 83.35 FIRST 0 .10 PASS EACH MONTH: FIRST 0. 20 PASS EACH MONTH: I38400 DEC 5, 2013 3: 2 7 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 PRESSURE LINE LEAK TEST HISTORY Q 1: 8 7 UNLEADED LAST 3.0 PASS: FIRST 0 .10 PASS EACH MONTH: Q 2:91 UNLEADED LAST 3 . 0 PASS: FIRST 0 .10 PASS EACH MONTH: Q 3 :DIESEL LAST 3.0 PASS: FIRST 0 .10 PASS EACH MONTH: !38900 DEC 5, 2013 3:27 PM Il1100 DEC 5, 2013 3: 2 7 PM FOODS CO • 3 84 2505 HALEY BAKERSFIELD CA. 661-873-9343 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION TIME Q 3 OTHER 11:02AM Q 3 OTHER 11:02AM Q 2 OTHER ll:OlAM ~l~O£I~ER ~1~o8illER ~o~s~illER ~oMA~ER Q 1 OTHER 10: 52AM T 1 TANK 10:49AM T 1 TANK 10:47AM T 1 TANK 10:47AM T 1 TANK 10:44AM T 1 TANK 10:44AM ~0~4~,illER Q 3 OTHER 10:43AM T 1 TANK 10:42AM T 1 TANK 10:39AM T 1 TANK 10: 39AM T 2 TANK 10: 38AM T 2 TANK 10:37AM T 2 TANK 10:37AM T 2 TANK 10: 36AM T 2 TANK 10: 35AM T 2 TANK 10:34AM ~oM,illER T 3 TANK 10: 32AM T 3 TANK 10:32AM Q 3 OTHER 10:32AM T 3 TANK 10: 32AM T 3 TANK 10:31AM DIESEL DIESEL 91 UNLEADED 91 UNLEADED 87 UNLEADED 91 UNLEADED 91 UNLEADED 87 UNLEADED UNl UN1 UNl UNl UNl DIESEL DIESEL UNl UN1 UNl PRl PRl PRl PRl PRl PRl DIESEL DIESEL DIESEL DIESEL DIESEL DIESEL DEC 5, 2013 1:47 PM DEC 5, 2013 11:01 AM DEC 5, 2013 11:02 AM ALARM TYPE STATE PLLD SHUTDOWN ALARM CLEAR DATE 12-05-13 12-05-13 GROSS LINE FAIL CLEAR PLLD SHUTDOWN ALARM CLEAR 12-05-13 GROSS LINE FAIL CLEAR 12-05-13 GROSS LINE FAIL CLEAR 12-05-13 PLLD SHUTDOWN ALARM ALARM 12-05-13 GROSS LINE FAIL ALARM 12-05-13 GROSS LINE FAIL ALARM 12-05-13 PROBE OUT CLEAR 12-05-13 OVERFILL ALARM CLEAR 12-05-13 PROBE OUT ALARM 12-05-13 OVERFILL ALARM ALARM 12-05-13 SUDDEN LOSS ALARM CLEAR 12-05-13 PLLD SHUTDOWN ALARM ALARM 12-05-13 GROSS LINE FAIL ALARM 12-05-13 PROBE OUT CLEAR 12-05-13 PROBE OUT ALARM 12-05-13 SUDDEN LOSS ALARM ALARM 12-05-13 PROBE OUT CLEAR 12-05-13 OVERFILL ALARM CLEAR 12-05-13 PROBE OUT ALARM 12-05-13 OVERFILL ALARM ALARM 12-05-13 PROBE OUT CLEAR 12-05-13 PROBE OUT ALARM 12-05-13 PLLD SHUTDOWN ALARM CLEAR 12-05-13 LOW PRODUCT ALARM CLEAR 12-05-13 LOW PRODUCT ALARM ALARM 12-05-13 PLLD SHUTDOWN ALARM ALARM 12-05-13 PROBE OUT CLEAR 12-05-13 OVERFILL ALARM CLEAR 12-05-13 Page 4 T 3 TANK 10:3WI DIESEL PROBE OUT ALARM 12-05-13 T 3 TANK 10:30AM DIESEL OVERFILL ALARM ALARM 12-05-13 T 3 TANK 10:29AM DIESEL PROBE OUT CLEAR 12-05-13 T 3 TANK 10: 28AM DIESEL PROBE OUT ALARM 12-05-13 I 1 INPUT 10:24AM EMERGENCY SHUT OFF EXTERN INPUT ALARM CLEAR 12-05-13 I 1 INPUT 10:22AM EMERGENCY SHUT OFF EXTERN INPUT ALARM ALARM 12-05-13 Q 2 OTHER 10: 22AM L16 PIPE 10:22AM Ll5 PIPE 10:22AM 91 UNLEADED 91 FILL BRINE 91 FILL Ll4 STP SUMP 91 TURBINE BRINE 10:21AM L13 STP SUMP 91 TURBINE 10:2WI Ll2 ANNULAR 87 ANNULAR 10:21AM ~0~2~ER L11 PIPE 10: 21AM LlO PIPE 10:21AM 87 UNLEADED 87 FILL BRINE 87 FILL L 9 STP SUMP 87 TURBINE BRINE 10:21AM ~0~2~ER L23 PIPE 10:21AM L22 PIPE 10:21AM DIESEL VENT SUMP BRINE VENT SUMP L21 PIPE DIESEL FILL BRINE 10:21AM I11200 DEC 5, 2013 3:27 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION TIME T 1 TANK UNl 10:51AM T 1 TANK UNl 10:49AI>I T 2 TANK 10:41AM T 2 TANK 10:38AM T 2 TANK 10:35AM T 2 TANK 10: 35AI>I T 2 TANK 10:35AM T 2 TANK 10:34AM T 3 TANK 10:32AM T 3 TANK 10:32AM T 3 TANK 10:32AM T 3 TANK 10:32AM T 3 TANK 10:29AM T 3 TANK 10:28AM SYSTEM 8: SOAM SYSTEM 8:50AM SYSTEM 8:50AM SYSTEM 8: SOAM SYSTEM 8:48AM SYSTEM 8:48AM SYSTEM 8:47AM SYSTEM 8:47AM OTHER 10: 53AM OTHER 8:01AM SYSTEM 10:43AM SYSTEM 10:43AM PR1 PR1 PRl PR1 PR1 PRl DIESEL DIESEL DIESEL DIESEL DIESEL DIESEL PLLD SHUTDOWN ALARM CLEAR 12-05-13 SENSOR OUT ALARM CLEAR 12-05-13 SENSOR OUT ALARM CLEAR 12-05-13 SENSOR OUT ALARM CLEAR 12-05-13 SENSOR OUT ALARM CLEAR 12-05-13 SENSOR OUT ALARM CLEAR 12-05-13 PLLD SHUTDOWN ALARM CLEAR 12-05-13 SENSOR OUT ALARM CLEAR 12-05-13 SENSOR OUT ALARM CLEAR 12-05-13 SENSOR OUT ALARM CLEAR PLLD SHUTDOWN ALARM CLEAR 12-05-13 12-05-13 SENSOR OUT ALARM SENSOR OUT ALARM SENSOR OUT ALARM ALARM TYPE LOW TEMP WARNING LOW TEMP WARNING CLEAR 12-05-13 CLEAR 12-05-13 CLEAR 12-05-13 STATE DATE CLEAR 12-05-13 ALARM 12-05-13 LOW TEMP WARNING CLEAR 12-05-13 LOW TEMP WARNING ALARM 12-05-13 DELIVERY NEEDED CLEAR 12-05-13 INVALID FUEL LEVEL CLEAR 12-05-13 INVALID FUEL LEVEL ALARM 12-05-13 DELIVERY NEEDED ALARM 12-05-13 DELIVERY NEEDED CLEAR 12-05-13 DELIVERY NEEDED ALARM 12-05-13 INVALID FUEL LEVEL CLEAR 12-05-13 INVALID FUEL LEVEL ALARM 12-05-13 DELIVERY NEEDED CLEAR 12-05-13 DELIVERY NEEDED ALARM 12-05-13 PRINTER ERROR CLEAR 12-05-13 PAPER OUT CLEAR 12-05-13 PRINTER ERROR ALARM 12-05-13 PAPER OUT ALARM 12-05-13 PRINTER ERROR CLEAR 12-05-13 PAPER OUT CLEAR 12-05-13 PAPER OUT ALARM 12-05-13 PRINTER ERROR ALARM 12-05-13 ISO VAPOR LEAK WARN CLEAR 11-12-13 ISO VAPOR LEAK WARN ALARM 11-10-13 PRINTER ERROR CLEAR 10-30-13 PAPER OUT CLEAR 10-30-13 SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:40AM SYSTEM 10:40AM SYSTEM 10:40AM SYSTEM 10:40AM SYSTEM 10:40AM SYSTEM 10:40AM SYSTEM 10:40AM SYSTEM 10:40AM SYSTEM 10:37AM SYSTEM 10:37AM SYSTEM 10:37AM SYSTEM 10:37AM Il1400 DEC 5, 2013 3: 2 7 PM FOODS CO . 3 84 2505 HALEY BAKERSFIELD CA. 661-873-9343 CLEARED ALARMS REPORT ID CATEGORY DESCRIPTION TIME £17o2r~ER DIESEL £17 o~.lJ1ER DIESEL £1~0~r~ER 91 UNLEADED £1~0~ER 91 UNLEADED £1fo8.lJ1ER 87 UNLEADED T 1 TANK 10:49AM T 1 TANK 10:47AM T 1 TANK 10:44AM T 1 TANK 10:42AM T 2 TANK 10:38AM T 2 TANK 10:37AM T 2 TANK 10:35AM £o73~.lJ1ER UN1 UN1 UN1 UN1 PR1 PR1 PR1 DIESEL PRINTER ERROR ALARM 10-30-13 PAPER OUT ALARM 10-30-13 PRINTER ERROR CLEAR 10-30-13 PAPER OUT CLEAR 10-30-13 PRINTER ERROR ALARM 10-30-13 PAPER OUT ALARM 10-30-13 PRINTER ERROR CLEAR 10-30-13 PAPER OUT CLEAR 10-30-13 PRINTER ERROR ALARM 10-30-13 PAPER OUT ALARM 10-30-13 PRINTER ERROR CLEAR 10-30-13 PAPER OUT CLEAR 10-30-13 PRINTER ERROR ALARM 10-30-13 PAPER OUT ALARM 10-30-13 PRINTER ERROR CLEAR 10-30-13 PAPER OUT CLEAR 10-30-13 PRINTER ERROR ALARM 10-30-13 PAPER OUT ALARM 10-30-13 PRINTER ERROR CLEAR 10-30-13 PAPER OUT CLEAR 10-30-13 PRINTER ERROR ALARM 10-30-13 PAPER OUT ALARM 10-30-13 PRINTER ERROR CLEAR 10-30-13 PAPER OUT CLEAR 10-30-13 ALARM TYPE STATE PLLD SHUTDOWN ALARM CLEAR DATE 12-05-13 12-05-13 GROSS LINE FAIL CLEAR PLLD SHUTDOWN ALARM CLEAR 12-05-13 GROSS LINE FAIL CLEAR 12-05-13 GROSS LINE FAIL CLEAR 12-05-13 PROBE OUT CLEAR 12-05-13 OVERFILL ALARM CLEAR 12-05-13 SUDDEN LOSS ALARM CLEAR 12-05-13 PROBE OUT CLEAR 12-05-13 PROBE OUT CLEAR 12-05-13 OVERFILL ALARM CLEAR 12-05-13 PROBE OUT CLEAR 12-05-13 PLLD SHUTDOWN ALARM CLEAR 12-05-13 T 3 TANK 10:32AM DIESEL LOW PRODUCT ALARM CLEAR 12-05-13 T 3 TANK 10:32AM T 3 TANK 10:31AM T 3 TANK 10:29AM I 1 INPUT 10:24AM £o~2~.lJ1ER Ll6 PIPE 10:22AM Ll5 PIPE 10:22AM DIESEL PROBE OUT CLEAR 12-05-13 DIESEL OVERFILL ALARM CLEAR 12-05-13 DIESEL PROBE OUT CLEAR 12-05-13 EMERGENCY SHUT OFF EXTERN INPUT ALARM CLEAR 12-05-13 91 UNLEADED PLLD SHUTDOWN ALARM CLEAR 12-05-13 91 FILL BRINE SENSOR OUT ALARM CLEAR 12-05-13 91 FILL SENSOR OUT ALARM CLEAR 12-05-13 Page 5 Idt2ru SUMP 91 TURBINE BRINE Id72ru SUMP 91 TURBINE L12 ANNULAR 87 ANNULAR 10:21AM £of2~ER Lll PIPE 10:21AM LlO PIPE 10:21AM 87 UNLEADED 87 FILL BRINE 87 FILL L 9 STP SUMP 87 TURBINE BRINE 10:21AM £o7z£.lJ1ER L23 PIPE 10:21AM L22 PIPE 10:21AM L21 PIPE 10:21.AM T 1 TANK 10:51AM T 2 TANK 10:41AM T 2 TANK 10: 35AM T 2 TANK 10: 35AM T 3 TANK 10: 32AM T 3 TANK 10:32AI>I T 3 TANK 10: 29AM SYSTEM 8:50AM SYSTEM 8:50AM SYSTEM 8:48AM SYSTEM 8:48AM OTHER 10:53AM SYSTEM 10:43AM SYSTEM 10:43AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:40AM SYSTEM 10:40AM SYSTEM 10:40AM SYSTEM 10:40AM SYSTEM 10:37AM SYSTEM 10: 37AM 9999FF1B DIESEL VENT SUMP BRINE VENT SUMP DIESEL FILL BRINE UN1 PR1 PR1 PR1 DIESEL DIESEL DIESEL SENSOR OUT ALARM CLEAR 12-05-13 SENSOR OUT ALARM CLEAR 12-05-13 SENSOR OUT ALARM CLEAR 12-05-13 PLLD SHUTDOWN ALARM CLEAR 12-05-13 SENSOR OUT ALARM CLEAR 12-05-13 SENSOR OUT ALARM CLEAR 12-05-13 SENSOR OUT ALARM CLEAR 12-05-13 PLLD SHUTDOWN ALARM CLEAR 12-05-13 SENSOR OUT ALARM CLEAR 12-05-13 SENSOR OUT ALARM CLEAR 12-05-13 SENSOR OUT ALARM CLEAR 12-05-13 LOW THIP WARNING CLEAR 12-05-13 LOW TEMP WARNING CLEAR 12-05-13 DELIVERY NEEDED CLEAR 12-05-13 INVALID FUEL LEVEL CLEAR 12-05-13 DELIVERY NEEDED CLEAR 12-05-13 INVALID FUEL LEVEL CLEAR 12-05-13 DELIVERY NEEDED CLEAR 12-05-13 PRINTER ERROR CLEAR 12-05-13 PAPER OUT CLEAR 12-05-13 PRINTER ERROR CLEAR 12-05-13 PAPER OUT CLEAR 12-05-13 ISO VAPOR LEAK WARN CLEAR 11-12-13 PRINTER ERROR CLEAR 10-30-13 PAPER OUT CLEAR 10-30-13 PRINTER ERROR CLEAR 10-30-13 PAPER OUT CLEAR 10-30-13 PRINTER ERROR CLEAR 10-30-13 PAPER OUT CLEAR 10-30-13 PRINTER ERROR CLEAR 10-30-13 PAPER OUT CLEAR 10-30-13 PRINTER ERROR CLEAR 10-30-13 PAPER OUT CLEAR 10-30-13 PRINTER ERROR CLEAR 10-30-13 PAPER OUT CLEAR 10-30-13 PRINTER ERROR CLEAR 10-30-13 PAPER OUT CLEAR 10-30-13 ~~H~~~ep~LS Paller SYSTEM_SETUP command set ver 5. 7 Started at 12/5/2013 I10200 DEC 5, 2013 3:22 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 SYSTEM CONFIGURATION SLOT 1 2 BOARD TYPE ~ 5 6 7 ~ 10 11 12 13 4 PROBE / G.T. PLLD SENSOR BD INTERSTITIAL BD INTERSTITIAL BD INTERSTITIAL BD 8SMARTSENSOR BD 7SMARTSENSOR BD 8SMARTSENSOR BD COMBO I/O BOARD PLLD POWER BD UNUSED UNUSED UNUSED H UNUSED UNUSED 16 UNUSED COMM 1 ELEC DISP INT. COMM 2 SERIAL SAT BD COMM 3 UNUSED COMM 4 UNUSED COMM 5 RS485 SERIAL BD COMM 6 RS232 SERIAL BD I10100 DEC 5, 2013 3:22 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 SYSTEM STATUS REPORT s11: NO VACUUM ALARM I11100 DEC 5, 2013 3: 22 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION TIME Q 3 OTHER 11:02AM Q 3 OTHER 11:02AM Q 2 OTHER 11:01AM Q 2 OTHER ll:OlAM ~1~08ll1ER ~o~5~lljER ~o~5~lljER ~o\~lljER T 1 TANK 10:49AM T 1 TANK 10:47AM T 1 TANK 10: 47AM T 1 TANK 10:44AM T 1 TANK 10:44AM ~0~ 4~lljER ~0~4~lljER T 1 TANK 10:42AM T 1 TANK 10:39AM T 1 TANK 10:39AM T 2 TANK 10:38AM T 2 TANK 10:37AM T 2 TANK 10: 37AM T 2 TANK 10: 36AM T 2 TANK 10: 35AM T 2 TANK 10: 34AM ~oMI~ER T 3 TANK 10:32AM T 3 TANK 10:32AM ~oMTilER T 3 TANK 10:32AM Iohi%jK T 3 TANK 10:31AM T 3 TANK 10:30AM T 3 TANK 10:29AM T 3 TANK 10:28AM I 1 INPUT 10: 24AM I 1 INPUT 10: 22AM ~o~2~TI1ER L16 PIPE 10:22AM L15 PIPE 10:22AM \:liM~ SUMP L13 STP SUMP DIESEL DIESEL 91 UNLEADED 91 UNLEADED 87 UNLEADED 91 UNLEADED 91 UNLEADED 87 UNLEADED UN1 UN1 UN1 UN1 UN1 DIESEL DIESEL UN1 UN1 UN1 PR1 PR1 PR1 PR1 PR1 PR1 DIESEL DIESEL DIESEL DIESEL DIESEL DIESEL DIESEL DIESEL DIESEL DIESEL EMERGENCY SHUT OFF EMERGENCY SHUT OFF 91 UNLEADED 91 FILL BRINE 91 FILL 91 TURBINE BRINE 91 TURBINE POWER ON RESET 164807 3919 202970 203082 203127 39544 514845 9949365 9928 102072 9852763 9870287 9798228 9823814 9765830 9798012 101521 9786178 9767641 9753587 68839 15029 ALARM TYPE CURRENT 16§H8 201773 201888 201819 39448 8;mu m~m 8446209 8440533 101216 487065 ~~um STATE PLLD SHUTDOWN ALARM CLEAR GROSS LINE FAIL CLEAR PLLD SHUTDOWN ALARM CLEAR GROSS LINE FAIL CLEAR GROSS LINE FAIL CLEAR PLLD SHUTDOWN ALARM ALARM GROSS LINE FAIL GROSS LINE FAIL PROBE OUT OVERFILL ALARM PROBE OUT OVERFILL ALARM SUDDEN LOSS ALARM ALARM ALARM CLEAR CLEAR ALARM ALARM CLEAR PLLD SHUTDOWN ALARM ALARM GROSS LINE FAIL ALARM PROBE OUT CLEAR PROBE OUT ALARM SUDDEN LOSS ALARM ALARM PROBE OUT CLEAR OVERFILL ALARM CLEAR PROBE OUT ALARM OVERFILL ALARM ALARM PROBE OUT CLEAR PROBE OUT ALARM PLLD SHUTDOWN ALARM CLEAR LOW PRODUCT ALARM CLEAR LOW PRODUCT ALARM ALARM PLLD SHUTDOWN ALARM ALARM PROBE OUT CLEAR OVERFILL ALARM CLEAR PROBE OUT ALARM OVERFILL ALARM ALARM PROBE OUT CLEAR PROBE OUT ALARM EXTERN INPUT ALARM CLEAR EXTERN INPUT ALAR~I ALARM PLLD SHUTDOWN ALARM CLEAR SENSOR OUT ALARM CLEAR SENSOR OUT ALARM CLEAR SENSOR OUT ALARM CLEAR SENSOR OUT ALARM CLEAR DATE 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 Page 1 10:2W1 L12 ANNULAR 10: 21AM Q 1 OTHER 10:21AM L11 PIPE 10:2W1 L10 PIPE 10:21AM Io ~ 2ill suMP Q 3 OTHER 10:21AM L23 PIPE 10:21AM L22 PIPE 10:2W1 L21 PIPE 10:2W1 I11200 DEC 5, 2013 87 ANNULAR 87 UNLEADED 87 FILL BRINE 87 FILL 87 TURBINE BRINE DIESEL VENT SUMP BRINE VENT SUMP DIESEL FILL BRINE 3:22 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION TIME T 1 TANK UN1 10:51AM T 1 TANK UN1 10:49AM T 2 TANK PR1 10:41AM T 2 TANK PR1 10: 38AM T 2 TANK PR1 10: 35AM T 2 TANK PR1 10:35AM T 2 TANK PR1 10:35AM T 2 TANK PR1 10:34AM T 3 TANK DIESEL 10:32AM T 3 TANK DIESEL 10:32AM T 3 TANK DIESEL 10:32AM T 3 TANK DIESEL 10:32AM T 3 TANK DIESEL 10:29AM T 3 TANK DIESEL 10:28AM SYSTEM 8:50AM SYSTEM 8:50AM SYSTEM 8:50AM SYSTEM 8:50AM SYSTEM 8:48AM SYSTEM 8:48AM SYSTEM 8:47AM SYSTEM 8:47AM OTHER 10: 53AM OTHER 8:01AM SYSTEM 10:43AM SYSTEM 10:43AM SYSTEM 10:4W1 SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:4W1 SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:40AM SYSTEM 10:40AM SYSTEM 10:40AM SYSTEM 10:40AM SYSTEM 10:40AM SYSTEM 10:40AM SYSTEM 10:40AM SYSTEM 10:40AM SYSTE~I 10: 37AM SYSTEM 10:37AM SYSTEM 10: 37AM SYSTEM 10:37AM I11300 DEC 5, 2013 3:22 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 ACTIVE ALARMS REPORT ID CATEGORY DESCRIPTION s11 OTHER 87 VENT SENSOR OUT ALARM CLEAR PLLD SHUTDOWN ALARM CLEAR 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 SENSOR OUT ALARM SENSOR OUT ALARM SENSOR OUT ALARM CLEAR CLEAR CLEAR PLLD SHUTDOWN ALARM CLEAR SENSOR OUT ALARM CLEAR SENSOR OUT ALARM CLEAR SENSOR OUT ALARM CLEAR ALARM TYPE STATE DATE 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 LOW TEMP WARNING CLEAR LOW TEMP WARNING ALARM LOW TEMP WARNING CLEAR LOW TEMP WARNING ALARM DELIVERY NEEDED CLEAR INVALID FUEL LEVEL CLEAR INVALID FUEL LEVEL ALARM DELIVERY NEEDED ALARM DELIVERY NEEDED CLEAR DELIVERY NEEDED ALARM INVALID FUEL LEVEL CLEAR INVALID FUEL LEVEL ALARM DELIVERY NEEDED CLEAR DELIVERY NEEDED ALARM PRINTER ERROR CLEAR PAPER OUT CLEAR PRINTER ERROR ALARM PAPER OUT ALARM PRINTER ERROR CLEAR PAPER OUT PAPER OUT PRINTER ERROR ISO VAPOR LEAK WARN ISO VAPOR LEAK WARN PRINTER ERROR PAPER OUT PRINTER ERROR PAPER OUT PRINTER ERROR PAPER OUT PRINTER ERROR PAPER OUT PRINTER ERROR PAPER OUT PRINTER ERROR PAPER OUT PRINTER ERROR PAPER OUT PRINTER ERROR PAPER OUT PRINTER ERROR PAPER OUT PRINTER ERROR PAPER OUT PRINTER ERROR PAPER OUT PRINTER ERROR PAPER OUT PRINTER ERROR PAPER OUT ALARM TYPE NO VACUUM ALARM CLEAR 12-05-13 ALARM 12-05-13 ALARM 12-05-13 CLEAR 11-12-13 ALARM 11-10-13 CLEAR 10-30-13 CLEAR 10-30-13 ALARM 10-30-13 ALARM 10-30-13 CLEAR 10-30-13 CLEAR 10-30-13 ALARM 10-30-13 ALARM 10-30-13 CLEAR 10-30-13 CLEAR 10-30-13 ALARM 10-30-13 ALARM 10-30-13 CLEAR 10-30-13 CLEAR 10-30-13 ALARM 10-30-13 ALARM 10-30-13 CLEAR 10-30-13 CLEAR 10-30-13 ALARM 10-30-13 ALARM 10-30-13 CLEAR 10-30-13 CLEAR 10-30-13 ALARM 10-30-13 ALARM 10-30-13 CLEAR 10-30-13 CLEAR 10-30-13 DATE TIME 111400 DEC 5, 2013 3 : 22 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 CLEARED ALARMS REPORT ID CATEGORY DESCRIPTION TIME ~1 ~ o~..illER DIESEL ~1 ~ O~..illER DIESEL ~1~o~..illER 91 UNLEADED ~1~0mER 91 UNLEADED Q 1 OTHER 87 UNLEADED ll:OOAM T 1 TANK UN1 10:49AM T 1 TANK UN1 10:47AM T 1 TANK UN1 10:44AM T 1 TANK UN1 10:42AM T 2 TANK PR1 10: 38AM T 2 TANK PR1 10:37AM T 2 TANK PR1 10:3SAM Q 3 OTHER DIESEL 10:32AM T 3 TANK 10: 32AM T 3 TANK 10: 32AM T 3 TANK 10:31AM T 3 TANK 10:29AM DIESEL DIESEL DIESEL DIESEL I 1 INPUT 10:24AM ~oM..illER EMERGENCY SHUT OFF 91 UNLEADED Ll6 PIPE 10:22AM LlS PIPE 10:22AM L14 STP SUMP 10:21AM L13 STP SUMP 10: 21AM Ll2 ANNULAR 10:21AM ~0~2~..illER Lll PIPE 10:21AM L10 PIPE 10: 21AM L 9 STP SUMP 10:21AM Q 3 OTHER I0:21AM L23 PIPE 10:21AM L22 PIPE 10: 21AM L21 PIPE 10: 21AM T 1 TANK 10: SlAM T 2 TANK 10:41AM T 2 TANK 10:35AM T 2 TANK 10: 3SAM T 3 TANK 10:32AM T 3 TANK 10:32AM T 3 TANK 10:29AM SYSTEM 8: SOAM SYSTEM 8: SOAM SYSTEM 8:48AM SYSTEM 8:48AM OTHER 10: 53AM SYSTEM 10:43AM SYSTEM 10:43AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:40AM SYSTEM 10:40NI SYSTEM 10:40AM SYSTEM 10:40AM SYSTEM 10: 37AM SYSTEM 10:37AM IllSOO DEC 5, 2013 9999FF1B Il1A00 DEC 5, 2013 91 FILL BRINE 91 FILL 91 TURBINE BRINE 91 TURBINE 87 ANNULAR 87 UNLEADED 87 FILL BRINE 87 FILL 87 TURBINE BRINE DIESEL VENT SUMP BRINE VENT SUMP DIESEL FILL BRINE UN1 PR1 PR1 PR1 DIESEL DIESEL DIESEL 3:22 PM 3:22 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 SERVICE REPORT DATE/TIME LABEL ALARM TYPE STATE PLLD SHUTDOWN ALARM CLEAR GROSS LINE FAIL CLEAR PLLD SHUTDOWN ALARM CLEAR GROSS LINE FAIL GROSS LINE FAIL PROBE OUT OVERFILL ALARM SUDDEN LOSS ALARM PROBE OUT PROBE OUT OVERFILL ALARM PROBE OUT CLEAR CLEAR CLEAR CLEAR CLEAR CLEAR CLEAR CLEAR CLEAR PLLD SHUTDOWN ALARM CLEAR LOW PRODUCT ALARM CLEAR PROBE OUT CLEAR OVERFILL ALARM CLEAR PROBE OUT CLEAR EXTERN INPUT ALARM CLEAR PLLD SHUTDOWN ALARM CLEAR SENSOR OUT ALARM SENSOR OUT ALARM SENSOR OUT ALARM SENSOR OUT ALARM SENSOR OUT ALARM CLEAR CLEAR CLEAR CLEAR CLEAR PLLD SHUTDOWN ALARM CLEAR SENSOR OUT ALARM CLEAR SENSOR OUT ALARM CLEAR SENSOR OUT ALARM CLEAR PLLD SHUTDOWN ALARM CLEAR SENSOR OUT ALARM CLEAR SENSOR OUT ALARM CLEAR SENSOR OUT ALARM CLEAR LOW TEMP WARNING CLEAR LOW TEMP WARNING CLEAR DELIVERY NEEDED CLEAR INVALID FUEL LEVEL CLEAR DELIVERY NEEDED CLEAR INVALID FUEL LEVEL CLEAR DELIVERY NEEDED CLEAR PRINTER ERROR CLEAR PAPER OUT CLEAR PRINTER ERROR CLEAR PAPER OUT CLEAR ISD VAPOR LEAK WARN CLEAR PRINTER ERROR CLEAR PAPER OUT CLEAR PRINTER ERROR CLEAR PAPER OUT CLEAR PRINTER ERROR CLEAR PAPER OUT CLEAR PRINTER ERROR CLEAR PAPER OUT CLEAR PRINTER ERROR CLEAR PAPER OUT CLEAR PRINTER ERROR CLEAR PAPER OUT CLEAR PRINTER ERROR CLEAR PAPER OUT CLEAR ID LABEL DATE 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 12-05-13 11-12-13 10-30-13 10-30-13 10-30-13 10-30-13 10-30-13 10-30-13 10-30-13 10-30-13 10-30-13 10-30-13 10-30-13 10-30-13 10-30-13 10-30-13 Page 2 CODE NONE I11B00 DEC 5, 2013 3:22 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 SERVICE NOTICE SESSION REPORT START TIME 9999FF1B I20100 DEC 5, 2013 3:22 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA, 661-873-9343 IN-TANK INVENTORY TANK PRODUCT TEMP 1 UN1 64.15 2 PR1 68.67 3 DIESEL 72.67 I20200 DEC 5, 2013 3: 22 PM FOODS CO . 3 84 2505 HALEY BAKERSFIELD CA. 661-873-9343 DELIVERY REPORT T 1:UN1 END TIME VOLUME TC VOLUME 12668 12631 3516 3494 1971 1960 ULLAGE 7114 4385 8449 HEIGHT 71.96 53.89 30.40 WATER 0.00 0.00 0.00 INCREASE DATE / TIME GALLONS TC GALLONS WATER TEMP DEG F HEIGHT 103.09END: DEC 5, 2013 10:51 AM 72•3§TART: DEC 5, 2013 10:43 AM AMOUNT: END: DEC 81.99 START: DEC 44.82 AMOUNT: END: DEC 84.85 START: DEC 47.59 AMOUNT: END: DEC 84.66 START: DEC 42.90 AMOUNT: 4, 2013 4, 2013 3' 2013 3' 2013 2, 2013 2' 2013 94 •89 END: DEC 1, 2013 Sl.GlTART: DEC 1, 2013 AMOUNT: 83.57 END: NOV 30, 2013 SS.1~TART: NOV 30, 2013 AMOUNT: gl, SB END: NOV 29, 2013 53•6§TART: NOV 29, 2013 NIOUNT: gs. 61 END: NOV 27, 2013 57• 2rART: NOV 27, 2013 AMOUNT: 5:57 PM 5:38 PM 2:07 PM 1:46 PM 2:44 PM 2:23 PM 1:24 AM 1:04 AM 2:42 AM 2:24 AM 2:46 AM 2:16 AM 4:37 PM 4:16 PM 88 .08 END: NOV 27, 2013 12:24 AM 46 .2~TART: NOV 26, 2013 11:50 PM AMOUNT: 73•97 END: NOV 26, 2013 11:16 Nl 46 • s§TART: NOV 26, 2013 10:54 Nl AMOUNT: T 2: PR1 INCREASE DATE / TIME HEIGHT 104. glND: DEC 5, 2013 10:44 Nl 20.SlTART: DEC 5, 2013 10:34 AM AMOUNT: END: DEC 56.33 START: DEC 44.32 NIOUNT: END: DEC 55.49 START: DEC 43.36 AMOUNT: 4, 2013 4, 2013 3' 2013 3' 2013 76 . 76 END: NOV 30, 2013 42 .8~TART: NOV 30, 2013 AMOUNT: 52• 53 END: NOV 29, 2013 40 •3~TART: NOV 29, 2013 AMOUNT: END: NOV 27, 2013 6:03 PM 5:53 PM 2:11 PM 2:02 PM 2:36 AM 2:22 AM 2:21 AM 2:12 AM 4:27 PM 18375 12758 18386 0. 85 12775 0.00 5617 5611 14734 6781 7953 15294 7372 14698 0.00 6751 0.00 7947 15234 0. 00 7337 0.00 7922 7897 15258 6378 8880 17114 8240 15195 0. 00 6345 0.00 8850 17043 0. 00 8201 0.00 8874 8842 15046 9016 6030 16543 8694 14977 0.00 8972 0.00 6005 16471 0.00 8652 0.00 7849 7819 17233 17173 0. 00 9476 9455 0.00 7757 7718 15907 7082 15884 0. 00 7062 0.00 8825 8822 13092 7156 5936 13062 0.00 7135 0.00 5927 59.11 58.14 63.44 66.31 65.52 66.59 65.82 67.19 65.87 66.84 66.43 66.97 66.16 66.68 64.93 63.12 62.04 63.98 63.25 64.11 GALLONS TC GALLONS WATER TEMP DEG F 7409 929 7367 0.00 923 0.00 6480 6444 3723 2716 3702 0.00 2697 0.00 1007 1005 3651 2637 3625 0.00 2616 0.00 1014 1009 5425 2594 5403 0.00 2573 0.00 2831 2830 3401 2390 1011 3262 3375 0.00 2371 0.00 1004 3240 0.00 67.94 68.37 67.85 70.10 70.11 71.08 65.82 71.08 70.53 71.34 69.74 50.88 38. 5~TART: NOV 27, 2013 4:18 PM AMOUNT: 52 _50 END: NOV 26, 2013 11:29 AM 40_2~TART: NOV 26, 2013 11:17 AM AMOUNT: 61.79 END: NOV 24, 2013 12:04 AM 39• g§TART: NOV 23, 2013 11:54 PM AMOUNT: 48.0? END: NOV 23, 2013 4:08 AM 35 _6ITART: NOV 23, 2013 3:58AM AMOUNT: 48_40 END: NOV 21, 2013 10:19 PM 35_9~TART: NOV 21, 2013 10:09 PM AMOUNT: T 3 :DIESEL 2251 1011 3399 2387 1012 4184 2364 1820 3027 2017 1010 3054 2043 2234 0.00 1006 3379 0.00 2369 0.00 1010 4162 0.00 2348 0.00 1814 3009 0.00 2001 0.00 1008 3033 0.00 2026 0.00 1011 1007 70.53 67.98 70.72 67.30 69.43 68.08 70.86 69.75 71.66 INCREASE DATE / TIME GALLONS TC GALLONS WATER TEMP DEG F HEIGHT l03.63END: DEC 5, 2013 10:37 AM START: DEC 5, 2013 10:28 AM 9.08 AMOUNT: 41.83 END: NOV 26, 2013 11:23 AM 27_3~TART: NOV 26, 2013 11:13 AM AMOUNT: 40 _ 31 END: NOV 16, 2013 3:12 AM 25 _5~TART: NOV 16, 2013 3:03AM AMOUNT: 57_go END: OCT 20, 2013 5:27PM 49_3~TART: OCT 20, 2013 5:17 PM AMOUNT: 61.93 END: OCT 9, 2013 7:36 PM 49.l~TART: OCT 9, 2013 7:25PM AMOUNT: 50_74 END: OCT 8, 2013 12:27 PM 50. oSTART: OCT 8, 2013 12:18 PM AMOUNT: 52 _60 END: OCT 5, 2013 6:30 PM 43• 8~TART: OCT 5, 2013 6:20 PM AMOUNT: 48_69 END: SEP 30, 2013 2:14 AM 39 _8~TART: SEP 30, 2013 1:59AM AMOUNT: 46.00 END: SEP 23, 2013 11:23 PM 30_28TART: SEP 23, 2013 11:13 PM AMOUNT: 39_ 74 END: SEP 16, 2013 2:44 AM 35_0~TART: SEP 16, 2013 2:36 AM AMOUNT: I20300 DEC 5, 2013 3:22 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 TANK 1 UNl TEST STATUS: OFF LEAK DATA NOT AVAILABLE ON THIS TANK TANK 2 PRl TEST STATUS: OFF LEAK DATA NOT AVAILABLE ON THIS TANK TANK 3 DIESEL TEST STATUS: OFF LEAK DATA NOT AVAILABLE ON THIS TANK I20400 DEC 5, 2013 3:22 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 SHIFT REPORT SHIFT 1 TIME: 6:00 AM TANK PRODUCT 9756 300 9456 3176 1678 1498 3008 1515 1493 5046 4033 1013 5526 4013 1513 4198 4111 87 4417 3406 1011 3959 2955 1004 3648 1952 1696 2945 2441 504 9704 0.00 298 0.00 9406 3155 0.00 1668 0.00 1487 2986 0.00 1504 0.00 1482 4996 0.00 3994 0. 00 1002 5469 0.00 3969 0.00 1500 4152 0. 00 4067 0.00 85 4369 0.00 3371 0.00 998 3921 0.00 2924 0.00 997 3607 0.00 1930 0.00 1677 2911 0.00 2415 0.00 496 71.60 72.74 74.30 73.11 75.77 76.81 81.51 81.24 82.83 84.01 84.04 83.96 83.85 82.73 80.95 83.39 84.64 84.59 85.19 83.35 1 UNl VOLUME TC VOLUME ULLAGE HEIGHT WATER TEMP SHIFT 1 STARTING VALUES ENDING VALUES DELIVERY VALUE TOTALS 2 PRl SHIFT 1 STARTING VALUES ENDING VALUES DELIVERY VALUE TOTALS 11703 11657 8079 13174 13141 6608 7953 6482 VOLUME TC VOLUME ULLAGE 3298 3276 4603 3601 3580 4300 1007 704 ~u~ 8:88 ~u~ HEIGHT WATER TEMP 51.30 0.00 69.04 54.89 0. 00 67.89 Page 3 3 DIESEL SHIFT 1 STARTING VALUES ENDING VALUES DELIVERY VALUE TOTALS I20500 DEC 5 , 2013 3: 22 PM FOODS CO • 3 84 2505 HALEY BAKERSFIELD CA. 661-873-9343 TANK PRODUCT 1 UNl PRl DIESEL I20600 DEC 5, 2013 3:22 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 TANK ALARM HISTORY TANK 1 UNl OVERFILL ALARM LOW PRODUCT ALARM SUDDEN LOSS ALARM HIGH PRODUCT ALARM INVALID FUEL LEVEL PROBE OUT DELIVERY NEEDED LOW TEMP WARNING TANK 2 PRl OVERFILL ALARM LOW PRODUCT ALARM SUDDEN LOSS ALARM HIGH PRODUCT ALARM INVALID FUEL LEVEL PROBE OUT HIGH WATER WARNING DELIVERY NEEDED LOW TEMP WARNING TANK 3 DIESEL OVERFILL ALARM LOW PRODUCT ALARM SUDDEN LOSS ALARM HIGH PRODUCT ALARM INVALID FUEL LEVEL PROBE OUT DELIVERY NEEDED MAX PRODUCT ALARM LOW TEMP WARNING I20700 DEC 5, 2013 3:22 PM FOODS CO • 3 84 2505 HALEY BAKERSFIELD CA. 661-873-9343 TANK LEAK TEST HISTORY T l:UNl LAST GROSS TEST PASSED: VOLUME TC VOLUME ULLAGE HEIGHT WATER TEMP 8267 32.22 0.00 72.81 2153 2140 8436 30.52 0.00 72.59 1984 1972 0 169 STATUS NORMAL NORMAL NORMAL DEC 5, 2013 10:44 AM NOV 12, 2013 11:39 AM OCT 31, 2013 1:57 AM DEC 15, 8~§ ~: DEC 6, 2010 3:26 PM 2013 10:39 AM 2012 2:45 PM 2011 11:38 AM DEC 6 2011 11: 46 AM ~llt 28: ~8H 1H8 ~ DEC 15 , 2010 2: 55 PM DEC 5, 2013 10:47 AM DEC 5, 2013 10:39 AM DEC 6, 2012 2: 49 PM AUG 1, 2013 7:40 PM JUL 20, 2013 9:20 AM APR 23, 2013 7:02 PM DEC 5, 2013 10:49 AM 8~§ ~: ~m 1U~ ~ DEC DEC DEC ~: ~8H 1U~ ;;tl 6, 2011 11:29 AM DEC 6, 2012 2:35 PM DEC 15, 2010 3:26 PM DEC 6, 2012 2: 3 5 PM DEC 6, 2011 11:27 AM DEC 29, 2010 12:35 PM DEC 6, 2011 11:29 AM DEC 5, 2013 10:35 AM DEC 6, 2011 11:31 AM DEC 15, 2010 2: 55 PM DEC 5, 2013 10:37 AM DEC 5, 2013 10:34 AM DEC 6, 2012 2:41 PM DEC 27, 2010 1:01 PM DEC 5, 2013 10:34 AM OCT 17, 2013 4:47PM JUL 14, 2013 9:40 PM 8~§ ~: ~8H 1~:H ;;tl DEC 6, 2011 11:31 AM DEC DEC ~: ~m lu~ ~~ DEC 5, DEC 15, NOV 12, DEC 6, DEC 29, DEC 6, DEC 27, DEC 5, DEC 6, DEC 15, 2013 10:32 AM 2010 3:26 PM 2013 8:33 AM 2012 2:19 PM 2010 12:43 PM 2011 11:58 AM 2010 1:31 PM 2013 10:32 AM 2012 2:25 PM 2010 2:55 PM DEC DEC DEC ~: ~8B 1sm ~ 6, 2012 2:25 PM DEC DEC DEC ~: ~8B iU~ ~ 6, 2012 2:26 PM DEC 27, 2010 1:31PM DEC 27, 2010 1:33 PM NO TEST PASSED LAST ANNUAL TEST PASSED: NO TEST PASSED FULLEST ANNUAL TEST PASS NO TEST PASSED LAST PERIODIC TEST PASS: NO TEST PASSED FULLEST PERIODIC TEST PASSED EACH MONTH: TEST START TIME TANK LEAK TEST HISTORY T 2:PR1 LAST GROSS TEST PASSED: NO TEST PASSED LAST ANNUAL TEST PASSED: NO TEST PASSED FULLEST ANNUAL TEST PASS NO TEST PASSED LAST PERIODIC TEST PASS: NO TEST PASSED FULLEST PERIODIC TEST PASSED EACH MONTH: TEST START TIME TANK LEAK TEST HISTORY T 3: DIESEL LAST GROSS TEST PASSED: NO TEST PASSED LAST ANNUAL TEST PASSED: NO TEST PASSED FULLEST ANNUAL TEST PASS NO TEST PASSED LAST PERIODIC TEST PASS: NO TEST PASSED FULLEST PERIODIC TEST PASSED EACH MONTH: TEST START TIME I20800 DEC 5, 2013 3:22 PM HOURS HOURS HOURS PREVIOUS IN TANK LEAK TEST RESULTS TANK 1 TEST TYPE ANNUAL PERIODIC GROSS TANK 2 TEST TYPE ANNUAL UN1 START TIME NO TEST DATA AVAILABLE NO TEST DATA AVAILABLE NO TEST DATA AVAILABLE PR1 START TIME NO TEST DATA AVAILABLE PERIODIC NO TEST DATA AVAILABLE GROSS NO TEST DATA AVAILABLE DIESEL START TIME TANK 3 TEST TYPE ANNUAL PERIODIC GROSS NO TEST DATA AVAILABLE NO TEST DATA AVAILABLE NO TEST DATA AVAILABLE I20A00 DEC 5, 2013 3:23 PM FOODS CO • 3 84 2505 HALEY BAKERSFIELD CA. 661-873-9343 ADJUSTED DELIVERY REPORT MAG VOLUME % VOLUME TEST TYPE VOLUME % VOLUME TEST TYPE VOLUME % VOLUME TEST TYPE RESULT RATE HOURS VOLUME RESULT RATE HOURS VOLU~IE RESULT RATE HOURS VOLUME TANK 1 UN1 INCREASE DATE/TIME INCREASE INCREASE DELIVERY DELIVERY TANK 2 PR1 INCREASE DATE/TIME TANK 3 DIESEL INCREASE DATE/TIME I20B00 DEC 5, 2013 3:23 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 VOLUME TC VOLUME ADJUSTMENT VOLUME TC VOLUME MAG INCREASE INCREASE DELIVERY DELIVERY VOLUME TC VOLUME ADJUSTMENT VOLUME TC VOLUME MAG INCREASE INCREASE DELIVERY DELIVERY VOLUME TC VOLUME ADJUSTMENT VOLUME TC VOLUME BIR ADJUSTED DELIVERY REPORT Page 4 T 1:UN1 TC START END ADJ ADJ DELIVERY START DATE DELIVERY END DATE VOLUME VOLUME DELIV DEL IV T 2:PR1 START END ADJ ADJ TC DELIVERY START DATE DELIVERY END DATE VOLUME VOLUME DELIV DELIV T 3:DIESEL START END ADJ ADJ TC DELIVERY START DATE DELIVERY END DATE VOLUME VOLUME DELIV DELIV I20C00 DEC 5, 2013 3:23 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 LAST DELIVERY REPORT T 1:UN1 INCREASE DATE / TIME HEIGHT 103.09END: DEC 5, 2013 10:51 AM ?2.3§TART: DEC 5, 2013 10:43 AM AMOUNT: T 2:PR1 INCREASE DATE / TIME HEIGHT 104 • g/ND: DEC 5, 2013 10:44 AM 20.siTART: DEC 5, 2013 10:34 AM AMOUNT: T 3 :DIESEL INCREASE DATE / TIME HEIGHT 103,63END: DEC 5, 2013 10:37 AM START: DEC 5, 2013 10:28 AM 9.08 AMOUNT: I20D00 DEC 5, 2013 3:23 PM I21200 DEC 5, 2013 3:23 PM FOODS CO . 3 84 2505 HALEY BAKERSFIELD CA. 661-873-9343 TANK LEAK TEST HISTORY T 1: UN1 LAST GROSS TEST PASSED: NO TEST PASSED LAST ANNUAL TEST PASSED: NO TEST PASSED FULLEST ANNUAL TEST PASS NO TEST PASSED LAST PERIODIC TEST PASS: NO TEST PASSED FULLEST PERIODIC TEST PASSED EACH MONTH : TEST START TIME TANK LEAK TEST HISTORY T 2: PR1 LAST GROSS TEST PASSED: NO TEST PASSED LAST ANNUAL TEST PASSED: NO TEST PASSED FULLEST ANNUAL TEST PASS NO TEST PASSED LAST PERIODIC TEST PASS: NO TEST PASSED FULLEST PERIODIC TEST PASSED EACH MONTH: TEST START TIME TANK LEAK TEST HISTORY T 3 :DIESEL LAST GROSS TEST PASSED: NO TEST PASSED LAST ANNUAL TEST PASSED: NO TEST PASSED FULLEST ANNUAL TEST PASS NO TEST PASSED LAST PERIODIC TEST PASS: NO TEST PASSED HOURS HOURS GALLONS TC GALLONS WATER TEMP DEG F 18375 12758 18386 0.85 12775 0.00 5617 5611 59.11 58.14 GALLONS TC GALLONS WATER TEMP DEG F 7409 929 6480 7367 0.00 923 0.00 6444 67.94 68.37 GALLONS TC GALLONS WATER TEMP DEG F 9756 300 9456 9704 0.00 298 0.00 9406 VOLUME % VOLUME TEST TYPE VOLUME % VOLUME TEST TYPE 71.60 72.74 FULLEST PERIODIC TEST PASSED EACH MONTH: TEST START TIME HOURS VOLUME % VOLUME TEST TYPE I21400 DEC 5' 2013 3:23 PM I21500 DEC 5' 2013 3:23 PM I21600 DEC 5' 2013 3:23 PM I21700 DEC 5' 2013 3:23 PM TANK PROFILE TANK PRODUCT LABEL 1 UN1 2 PR1 3 DIESEL I21800 DEC 5' 2013 3:23 PM I21900 DEC 5' 2013 3:23 PM TANK CHART SECURITY DISABLED I21A00 DEC 5, 2013 3:23 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 IN-TANK INVENTORY PROFILE 4 PTS 4 PTS 4 PTS TANK PRODUCT VOLUME TC VOLUME 90% ULLAGE HEIGHT TEMP 1 64.16 2 68.67 3 UN1 PR1 DIESEL 12668 3516 1971 12631 3494 1960 72.67 I21B00 DEC 5' 2013 3:23 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 BIR ADJUSTED DELIVERY REPORT T 1:UN1 TC DELIVERY START DATE DELIVERY END DELIV T 2: PR1 TC DELIVERY START DATE DELIVERY END DEL IV T 3 :DIESEL TC DELIVERY START DATE DELIVERY END DELIV I25100 DEC 5, 2013 3:23 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA, 661-873-9343 CSLD TEST RESULTS TANK PRODUCT I28100 DEC 5' 2013 3:23 PM I28200 DEC 5' 2013 3:23 PM I30100 DEC 5' 2013 3:23 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 LIQUID STATUS REPORT SENSOR LOCATION 1 DISP 1-2 DUAL 2 DISP 3-4 DUAL 3 DISP 5-6 DUAL 4 DISP 7-8 DUAL 5 DISP 9-10 DUAL 6 DISP 11-12 DUAL 7 DISP 13-14 DUAL 8 87 TURBINE 9 87 TURBINE BRINE 10 87 FILL 11 87 FILL BRINE 12 f ANNULAR 13 1 TURBINE 14 91 TURBINE BRINE 15 91 FILL 16 91 FILL BRINE 17 91 DIESEL ANNULAR 18 DIESEL TURBINE 19 DIESEL TURBINE BRINE 20 DIESEL FILL 21 DIESEL FILL BRINE 22 VENT SUMP 23 VENT SUMP BRINE I30200 DEC 5, 2013 3: 23 PM RESULT STATUS SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR DATE DATE DATE NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL 5135 71.96 3594 53.89 7407 30.40 START END VOLUME VOLUME START END VOLUME VOLUME START END VOLUME VOLUME WATER 0.00 0. 00 0.00 ADJ DELIV ADJ DEL IV ADJ DELIV ADJ ADJ ADJ Page 5 FOODS CO. 384 2505 HALEY BAKERSFIELD CA, 661-873-9343 LIQUID ALARM HISTORY REPORT I30600 DEC 5' 2013 3:23 PM I30700 DEC 5' 2013 3:23 PM I31100 DEC 5' 2013 3:23 PM I31200 DEC 5' 2013 3:23 PM I31500 DEC 5' 2013 3:23 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 SMART SENSOR STATUS REPORT SENSOR LOCATION 1 DISP 1-2 VFM 2 DISP 3-4 VFM 3 DISP 5-6 VFM 4 DISP 7-8 VFM 5 DISP 9-10 VFM 6 DISP 11-12 VFM 7 DISP 13-14 VFM 8 DISP 13-14 PS 9 87 PRODUCT 10 87 91 VAPOR 11 87 VENT 12 91 PRODUCT 13 91 VENT 14 DIESEL PRODUCT 15 PMC CANISTER 16 ATM P 17 DIESEL VENT STATUS SENSOR LOW LIQUID ALARM SENSOR OUT ALARM FUEL ALARM LOW LIQUID ALARM SENSOR OUT ALARM FUEL ALARM LOW LIQUID ALARM SENSOR OUT ALARM FUEL ALARM LOW LIQUID ALARM SENSOR OUT ALARM FUEL ALARM LOW LIQUID ALARM FUEL ALARM SENSOR OUT ALARM LOW LIQUID ALARM SENSOR OUT ALARM FUEL ALARM LOW LIQUID ALARM FUEL ALARM SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM FUEL ALARM SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM SENSOR OUT ALARM FUEL ALARM FUEL ALARM SENSOR OUT ALARM ~6~H Li~3~5D At~~~M SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM SENSOR OUT ALARM FUEL ALARM FUEL ALARM SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM SENSOR OUT ALARM FUEL ALARM FUEL ALARM SENSOR OUT ALARM ~6~H Li~3~ji;D At~~~M SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM SENSOR OUT ALARM FUEL ALARM FUEL ALARM SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM SENSOR OUT ALARM FUEL ALARM FUEL ALARM SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM SENSOR OUT ALARM FUEL ALARM FUEL ALARM NORMAL SENSOR NORMAL SENSOR NORMAL SENSOR NORMAL SENSOR NORMAL SENSOR NORMAL SENSOR NORMAL SENSOR NORMAL SENSOR NORMAL SENSOR NORMAL NO VACUUM ALARM SENSOR NORMAL SENSOR NORMAL SENSOR NORMAL SENSOR NORMAL SENSOR NORMAL SENSOR NORMAL I31600 DEC 5' 2013 3:23 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA, 661-873-9343 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 DISP 1-2 VFM DEC 15, 2010 3:59 PM COMMUNICATION ALARM DISP 3-4 VFM DISP 5-6 VFM DEC 15, 2010 3:59 PM COMMUNICATION ALARM 4 DISP 7-8 VFM DEC 15, 2010 3:26 PM COMMUNICATION ALARM 5 DISP 9-10 VFM 8iVid~1BFM 3:26 PM COMMUNICATION ALARM 6 8iVi3-IS1BFM3' 26 PM COMMUNICATION ALARM 7 8iVi3-IS1~s 3' 26 PM COMMUNICATION ALARM DEC 6, 2011 10:34 AM COMMUNICATION ALARM DEC 15, 2010 3:26 PM COMMUNICATION ALARM 87 PRODUCT DEC 5, 2013 9:53 AM NO VACUUM ALARM DEC 5, 2013 9:52 AM HIGH LIQUID ALARM DEC 5, 2013 9:52 AM NO VACUUM ALARM 10 87 91 VAPOR DEC 5, 2013 9:56 AM HIGH LIQUID ALARM DEC 5, 2013 9:55 AM NO VACUUM ALARM DEC 5, 2013 9:55 AM NO VACUUM ALARM 11 87 VENT DEC 5, 2013 9:56 AM HIGH LIQUID ALARM DEC 5, 2013 9:55 AM HIGH LIQUID ALARM NOV 30, 2013 12:14 AM NO VACUUM ALARM 12 91 PRODUCT DEC 5, 2013 10:02 AM HIGH LIQUID ALARM DEC 5, 2013 10:02 AM NO VACUUM ALARM DEC 5, 2013 9:59 AM NO VACUUM ALARM 13 91 VENT DEC 5, 2013 10:03 AM NO VACUUM ALARM DEC 5, 2013 9:58 AM NO VACUUM ALARM 14 DEC 6, 2012 10:53 AM HIGH LIQUID ALARM DIESEL PRODUCT DEC 5, 2013 10:06 AM NO VACUUM ALARM DEC S, 2013 10:06 AM HIGH LIQUID ALARM DEC 6, 2012 11:05 AM HIGH LIQUID ALARM 15 PMC CANISTER JAN 24, 2013 8:48 AM SENSOR FAULT ALARM MAR 17, 2012 9:07 AM SENSOR FAULT ALARM JAN 23, 2012 6:09 PM SENSOR FAULT ALARM 16 ATM P 17 DIESEL VENT DEC ~: ~8H i8:8g AM NO VACUUM ALARM DEC AM HIGH LIQUID ALARM DEC 6, 2012 11: OS AM HIGH LIQUID ALARM 131700 DEC 5' 2013 3:23 PM 131800 DEC 5' 2013 3:23 PM I31900 DEC 5' 2013 3:23 PM 131AOO DEC 5' 2013 3:23 PM 132200 DEC 5' 2013 3:23 PM 132300 DEC 5' 2013 3:23 PM 133300 ~~RTSSE~n~ I~mLL\oG DATE SENSOR SERIAL NUMBER TYPE 10-12-15 15:27:48 9 10430074 VAC SENSOR 10-12-15 15:27: so 10 10430073 VAC SENSOR 10-12-15 15:27:52 11 10430072 VAC SENSOR 10-12-15 15:27:53 12 10430102 VAC SENSOR 10-12-15 15:27:56 13 10430101 VAC SENSOR 10-12-15 15:27:58 14 10430070 VAC SENSOR 10-12-15 15:28:01 16 6545 ATM P SENSOR 10-12-15 15:28:56 15 9190010 VAPOR VALVE 10-12-15 15 : 29: 02 2 41742 AIR FLOW METER 10-12-15 15:29:30 4 41748 AIR FLOW METER 10-12-15 15:32:11 6 52271 AIR FLOW METER 10-12-15 15:32:13 7 52274 AIR FLOW METER 10-12-15 15:33:20 8 10835 VAPOR PRESSURE 10-12-16 09:41:41 1 41743 AIR FLOW METER 10-12-16 09:41:59 3 52279 AIR FLOW METER 10-12-16 09:43:24 5 52276 AIR FLOW METER 10-12-16 10:01:52 17 10430068 VAC SENSOR 11-05-02 13:33:15 12 12831 VAC SENSOR 11-05-10 18:14:36 13 12365 VAC SENSOR 12-05-10 10:41:04 17 12160020 VAC SENSOR 12-05-17 13:27:44 17 14113 VAC SENSOR 12-05-17 13:54:42 17 12160020 VAC SENSOR 12-07-30 11:58:05 11 12220003 VAC SENSOR 13-05-24 09:03:34 9 10935 VAC SENSOR 134100 DEC 5' 2013 3:23 PM 134200 DEC 5' 2013 3:23 PM 134600 DEC 5' 2013 3:23 PM 134700 DEC 5' 2013 3:23 PM 134BOO DEC 5' 2013 3:23 PM 134C00 DEC 5' 2013 3:23 PM 135100 DEC 5' 2013 3:23 PM I35200 DEC 5' 2013 3:23 PM Page 6 135300 DEC 5, 2013 3:23 PM I37300 DEC 5 , 2013 3: 23 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 PRESSURE LINE LEAK TEST RESULTS Q 1:87 UNLEADED 3. 0 GAL/HR RESULTS: LAST TEST: DEC 5, 2013 1:47 PM PASS NUMBER OF TESTS PASSED PREY 24 HOURS : 115 SINCE MIDNIGHT : 53 0.10 GAL/HR RESULTS: NO 0.10 DATA AVAILABLE 0. 20 GAL/HR RESULTS: NO 0. 20 DATA AVAILABLE NO-VENT TEST ABORTS: 0 OUT OF 0 TEST Q 2:91 UNLEADED 3. 0 GAL/HR RESULTS: LAST TEST: DEC 5 , 2013 11: 01 AM PASS NUMBER OF TESTS PASSED PREY 24 HOURS : SINCE MIDNIGHT : 0.10 GAL/HR RESULTS: NO 0.10 DATA AVAILABLE 0. 20 GAL/HR RESULTS: NO 0. 20 DATA AVAILABLE NO-VENT TEST ABORTS: 0 OUT OF 0 TEST Q 3:DIESEL 3. 0 GAL/HR RESULTS: LAST TEST: DEC 5, 2013 11: 02 AM PASS NUMBER OF TESTS PASSED PREY 24 HOURS : SINCE MIDNIGHT : 0.10 GAL/HR RESULTS: NO 0.10 DATA AVAILABLE 0. 20 GAL/HR RESULTS: NO 0. 20 DATA AVAILABLE NO-VENT TEST ABORTS: 0 OUT OF 0 TEST 137400 DEC 5, 2013 3:23 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 PRESSURE LINE LEAK TEST HISTORY Q 1:87 UNLEADED LAST 3.0 PASS: DEC 5, 2013 1:47 PM FIRST 0.10 PASS EACH MONTH: FIRST 0. 20 PASS EACH MONTH: Q 2 : 91 UNLEADED LAST 3.0 PASS: DEC 5, 2013 11:01 AM FIRST 0.10 PASS EACH MONTH: FIRST 0.20 PASS EACH MONTH: Q 3:DIESEL LAST 3.0 PASS: DEC 5, 2013 11:02 AM FIRST 0.10 PASS EACH ~\ONTH: FIRST 0. 20 PASS EACH MONTH: I38100 DEC 5, 2013 3:23 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 PRESSURE LINE LEAK STATUS LINE HANDLE Q 1:87 UNLEADED ACTIVE ALARMS: Q 2:91 UNLEADED ACTIVE ALARMS: DISPENSING TEST STATUS ENABLED TEST COMPLETE ENABLED TEST COMPLETE PUMP OFF OFF OFF OFF Q 3 :DIESEL ACTIVE ALARMS: ENABLED TEST COMPLETE !38200 DEC 5 , 2013 3: 23 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 PRESSURE LINE LEAK ALARM HISTORY REPORT Q 1:87 UNLEADED DEC 5, 2013 DEC 5, 2013 DEC 5, 2013 DEC 5, 2013 DEC 5, 2013 DEC 5, 2013 DEC 5, 2013 DEC 5, 2013 DEC 5, 2013 DEC 5, 2013 Q 2:91 UNLEADED DEC 5, 2013 DEC 5, 2013 DEC 5, 2013 DEC 5, 2013 DEC 5, 2013 DEC 5, 2013 DEC 5, 2013 DEC 5, 2013 DEC 5, 2013 DEC 5, 2013 10:52 AM 10:20 AM 9:56 AM 9:55 AM 9:52 AM 9:49 AM 9:49 AM 9:48 AM 9:45 AM 9:45 AM 10:54 AM 10:54 AM 10:20 AM 10:02 AM 9:56 AM 9:49 AM 9:49 AM 9:48 AM 9:45 AM 9:45 AM Q 3 :DIESEL DEC 5, 2013 10:43 AM DEC 5, 2013 10:43 AM DEC 5, 2013 10:32 AM DEC 5 , 2013 10: 20 AM DEC 5, 2013 10:06 AM DEC 5, 2013 9:49 AM DEC 5, 2013 9:49 AM DEC 5, 2013 9:48 AM 8~§ ~: ~m u~ ~ !38300 DEC 5, 2013 3:23 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 GROSS LINE FAIL PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM GROSS LINE FAIL PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM GROSS LINE FAIL PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PRESSURE LINE LEAK TEST RESULTS Q 1:87 UNLEADED 3. 0 GAL/HR RESULTS: LAST TEST: DEC 5, 2013 1:47 PM PASS NUMBER OF TESTS PASSED PREY 24 HOURS : 115 SINCE MIDNIGHT : 53 0 .10 GAL/HR RESULTS: NO 0.10 DATA AVAILABLE Q 2:91 UNLEADED 3.0 GAL/HR RESULTS: LAST TEST: DEC 5, 2013 11:01 AM PASS NUMBER OF TESTS PASSED PREY 24 HOURS : 49 SINCE MIDNIGHT : 13 0.10 GAL/HR RESULTS: NO 0.10 DATA AVAILABLE Q 3: DIESEL 3. 0 GAL/HR RESULTS: LAST TEST: DEC 5 , 2013 11: 02 AM PASS NUMBER OF TESTS PASSED PREY 24 HOURS : SINCE MIDNIGHT : 0.10 GAL/HR RESULTS: NO 0.10 DATA AVAILABLE I38400 DEC 5, 2013 3:23 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 PRESSURE LINE LEAK TEST HISTORY Q 1:87 UNLEADED LAST 3.0 PASS: FIRST 0 .10 PASS EACH MONTH: Q 2:91 UNLEADED LAST 3.0 PASS: FIRST 0 .10 PASS EACH MONTH: Q 3: DIESEL LAST 3 . 0 PASS: FIRST 0 .10 PASS EACH MONTH: DEC 5, 2013 1:47 PM DEC 5, 2013 11:01 AM DEC 5, 2013 11:02 AM OFF OFF Page 7 I38600 DEC 5' 2013 3:23 PM I38700 DEC 5' 2013 3:23 PM I38800 DEC 5' 2013 3:23 PM !38900 DEC 5' 2013 3:23 PM !39100 DEC 5' 2013 3:23 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 TANKER LOAD REPORT T 1:UN1 NO START DATE/TIME VOLUME TEMP END DATE/TIME VOLUME NO DATA HISTORY T 2:PR1 NO START DATE/TIME VOLUME TEMP END DATE/TIME VOLUME NO DATA HISTORY T 3 :DIESEL NO START DATE/TIME VOLU~IE TEMP END DATE/TIME VOLUME NO DATA HISTORY !39200 DEC 5, 2013 3:23 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 TANKER LOAD REPORT T 1:UN1 NO DATE/TIME NO DATA HISTORY T 2:PR1 NO DATE/TIME NO DATA HISTORY T 3 :DIESEL NO DATE/TI~IE NO DATA HISTORY I40100 DEC 5, 2013 3:23 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 LOCATION EMERGENCY SHUT OFF I40200 DEC 5, 2013 3:23 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 I40300 LOCATION EMERGENCY SHUT OFF DEC 5, 2013 10:22 AM ~5~ ~~: ~8B 1U5 ~ m z~: ~8B 1U~ ~ AUG 22, 2013 9:50 AM DEC 5, 2013 3: 23 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 VOLUME TEMP TC VOLUME VOLUME TEMP TC VOLUME VOLUME TEMP TC VOLUME STATUS OFF EXTERN INPUT ALARM EXTERN INPUT ALARM EXTERN INPUT ALARM EXTERN INPUT NORMAL EXTERN INPUT NORMAL EXTERN INPUT NORMAL INPUT / GENERATOR ALARM HISTORY REPORT INPUT LOCATION 1 EMERGENCY SHUT OFF 9999FF1B I40600 m z~: ~8H iU~ ~ AUG 22, 2013 9:50AM DEC 5, 2013 10:24 AM SEP 29, 2013 5:29 AM AUG 22, 2013 9:50 Ml DEC 5, 2013 3:23 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 RELAY LOCATION I41100 DEC 5' 2013 3:23 PM I41200 DEC 5' 2013 3:23 PM I50100 DEC 5' 2013 3:23 PM SYSTEM DATE AND TIME STATUS EXTERN INPUT ALARM EXTERN INPUT ALARM EXTERN INPUT ALARM EXTERN INPUT NORMAL EXTERN INPUT NORMAL EXTERN INPUT NORMAL 1 OVERFILL TEMP TOTAL TEMP TOTAL TEMP TOTAL OPEN I50200 DEC 5' 2013 3:23 PM I50300 DEC 5' 2013 3:23 PM I50400 DEC 5' 2013 3:23 PM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED I50500 DEC 5, 2013 3:23 PM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS u.s. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH: MM: 55 XM I50600 DEC 5, 2013 3:23 PM PERIODIC TEST WARNINGS: DISABLED I50700 DEC 5, 2013 3:23 PM PERIODIC TEST WARNING: DAYS 25 I50800 DEC 5, 2013 3:23 PM PERIODIC TEST ALARM: DAYS = 30 I50900 DEC 5, 2013 3:23 PM ANNUAL TEST WARNINGS: DISABLED I50A00 DEC 5, 2013 3: 23 PM ANNUAL TEST WARNING: DAYS 355 I50B00 DEC 5, 2013 3:23 PM ANNUAL TEST ALARM: DAYS 365 I50c00 DEC 5, 2013 3: 23 PM REMOTE PRINTER DISABLED I50D00 DEC 5, 2013 3: 23 PM PRINT TC VOLU~IES ENABLED I50E00 DEC 5, 2013 3:23 PM TEMP COMPENSATION VALUE (DEG F): 60.0 I50F00 DEC 5, 2013 3:23 PM MON DO YYYY HH: MM: 55 xM I51100 DEC 5, 2013 3:23 PM SHIFT BIR PRINTOUTS DISABLED I51200 DEC 5 , 2013 3: 23 PM DAILY BIR PRINTOUTS DISABLED I51300 DEC 5' 2013 3:23 I51400 DEC 5' 2013 3:23 PM PM H-PROTOCOL DATA FORMAT HEIGHT I51500 DEC 5' 2013 3:23 PM I51600 DEC 5' 2013 3:23 PM RE-DIRECT LOCAL PRINTOUT DISABLED I51700 DEC 5, 2013 3:23 PM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS u.s. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DO YYYY HH:MM:SS xM Page 8 I51800 DEC 5, 2013 3:23 PM ALTERNATE LANGUAGE CODE PAGE CODE PAGE SELECTED: WINDOWS I51900 DEC 5' 2013 3:23 PM PRECISION TEST DURATION HOURS: 12 I51AOO DEC 5' 2013 3:23 PM DAYLIGHT SAVING TIME ENABLED OFF I51B00 DEC 5' 2013 3:23 PM DAYLIGHT SAVING TIME START DATE MAR WEEK SUN 2:00 END DATE NOV WEEK 1 SUN 2:00 I51C00 DEC 5' 2013 3:23 PM TICKETED DELIVERY DISABLED I51D00 DEC 5' 2013 3:23 PM I51E00 DEC 5' 2013 3:23 PM I52000 DEC 5' 2013 3:23 PM RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL 1 2 3 4 5 6 7 8 I52100 DEC 5' 2013 3:23 PM RECEIVER CONFIGURATION DIAL TYPE ON DATE ON DATE ON DATE ON DATE ON DATE ON DATE ON DATE ON DATE AM AM START TIME JAN 5, 2011 JAN 5, 2011 JAN 5, 2011 JAN 5, 2011 JAN 5, 2011 JAN 5, 2011 JAN 5, 2011 JAN 5, 2011 DEVICE 1 LABEL CONFIGURED OFF 2 3 4 5 6 7 8 I52200 DEC 5' 2013 3:23 PM RECEIVER LABEL DEVICE LABEL 1 2 3 4 5 6 7 8 I52300 DEC 5' 2013 3:23 PM RECEIVER TELEPHONE NUMBER RCVR LOCATION LABEL 1 2 3 ~ 7 8 I52400 DEC 5, 2013 3:23 PM OFF OFF OFF OFF OFF OFF OFF PHONE NUMBER RECEIVER DIALING DESTINATION TYPE RCVR LOCATION LABEL 1 2 ~ 5 6 7 8 I52500 DEC 5 , 2013 3: 23 PM FAX TYPE COMPUTER COMPUTER COMPUTER COMPUTER COMPUTER COMPUTER COMPUTER COMPUTER RECEIVER MODEM NUMBER TO DIAL RCVR LOCATION LABEL 1 2 ~ ! I52600 DEC 5 , 2013 3: 23 PM RECEIVER RETRY NUMBER LOCATION LABEL PORT NUMBER 1 1 1 t RETR~ NUMBER DISABLED DISABLED DISABLED DISABLED DISABLED DISABLED DISABLED DISABLED 2 3 3 3 4 3 5 3 6 3 7 3 8 3 I52700 DEC 5' 2013 3:23 PM RECEIVER RETRY DELAY TIME RCVR LOCATION LABEL RETRY DELAY 1 3 2 3 3 3 4 3 5 3 6 3 7 3 8 3 I52800 DEC 5, 2013 3:23 PM RECEIVER CONFIRMATION REPORT FLAG RCVR LOCATION LABEL 1 CONFIRMATION REPORT OFF 2 OFF 3 OFF 4 OFF 5 OFF 6 OFF 7 OFF 8 OFF I52900 DEC 5, 2013 3: 2 3 PM ALL PHONES I52A00 DEC 5, 2013 3:23 PM RECEIVER REPORT LIST RCVR LOCATION LABEL REPORT LIST I 52 BOO DEC 5, 2013 3:23 PM RECEIVER AUTO DIAL TYPE & START TIME RCVR 1 2 ~ ! I52C00 LOCATION LABEL DEC 5, 2013 3:23 PM RECEIVER SETUP REPORT D 1: -NO ALARM ASSIGNMENTS - D 2: -NO ALARM ASSIGNMENTS - D 3: -NO ALARM ASSIGNMENTS - D 4: -NO ALARM ASSIGNMENTS - D 5: -NO ALARM ASSIGNMENTS - D 6: -NO ALARM ASSIGNMENTS - D 7: -NO ALARM ASSIGNMENTS - D 8: -NO ALARM ASSIGNMENTS - I52D00 DEC 5, 2013 3:23 PM DIAL TYPE ON DATE ON DATE ON DATE ON DATE ON DATE ON DATE ON DATE ON DATE RECEIVER AUTODIAL ALARM STATUS RCVR STATUS 1 CLEAR 2 CLEAR 3 CLEAR 4 CLEAR 5 CLEAR 6 CLEAR 7 CLEAR 8 CLEAR I52E00 DEC 5, 2013 3:24 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 START TIME JAN 5, 2011 JAN 5, 2011 JAN 5, 2011 JAN 5, 2011 JAN 5, 2011 JAN 5, 2011 JAN 5, 2011 JAN 5, 2011 RECEIVER CLEARED ALARMS REPORT DELAY PERIOD RyVR 2 ~ 5 6 ~ I52F00 LOCATION LABEL DEC 5, 2013 3:24 PM RECEIVER ALARM STATUS D 1: SERVICE REPORT WARN ALARM CLEAR WARNING DELIVERY REPORT WRN NO DIAL TONE ALARM D 2: SERVICE REPORT WARN ALARM CLEAR WARNING DELIVERY REPORT WRN NO DIAL TONE ALARM CLEAR CLEAR CLEAR CLEAR CLEAR CLEAR CLEAR CLEAR DELAY PERIOD II j~ DISABLED DISABLED DISABLED DISABLED DISABLED DISABLED DISABLED DISABLED Page 9 D 3: SERVICE REPORT WARN ALARM CLEAR WARNING DELIVERY REPORT WRN NO DIAL TONE ALARM D 4: SERVICE REPORT WARN: ALARM CLEAR WARNING: DELIVERY REPORT WRN: NO DIAL TONE ALARM : D 5: SERVICE REPORT WARN: CLEAR CLEAR CLEAR CLEAR CLEAR CLEAR CLEAR CLEAR CLEAR ALARM CLEAR WARNING: CLEAR DELIVERY REPORT WRN: CLEAR NO DIAL TONE ALARM : CLEAR D 6: SERVICE REPORT WARN: CLEAR ALARM CLEAR WARNING: CLEAR DELIVERY REPORT WRN: CLEAR NO DIAL TONE ALARM : CLEAR D 7: SERVICE REPORT WARN: CLEAR ALARM CLEAR WARNING: CLEAR DELIVERY REPORT WRN: CLEAR NO DIAL TONE ALARM : CLEAR D 8: SERVICE REPORT WARN: CLEAR ALARM CLEAR WARNING: CLEAR DELIVERY REPORT WRN: CLEAR NO DIAL TONE ALARM : CLEAR I53000 DEC 5' 2013 3:24 PM I53100 DEC 5' 2013 3:24 PM RS-232 END OF MESSAGE DISABLED I53200 DEC 5' 2013 3:24 PM I53300 DEC 5' 2013 3:24 PM I53400 DEC 5' 2013 3:24 PM I53600 DEC 5' 2013 3:24 PM I53700 DEC 5' 2013 3:24 PM I53800 DEC 5' 2013 3:24 PM I54600 DEC 5' 2013 3:24 PM TANK PER TST NEEDED WRN: DISABLED I54700 DEC 5' 2013 3:24 PM TANK PER TST NEEDED WRN: DAYS I54800 DEC 5' 2013 3:24 PM TANK PER TST NEEDED ALM: DAYS I54900 DEC 5' 2013 3:24 PM TANK ANN TST NEEDED WRN: DISABLED I54A00 DEC 5, 2013 3:24 PM 25 30 TANK ANN TST NEEDED WRN: DAYS 355 I54B00 DEC 5, 2013 3:24 PM TANK ANN TST NEEDED ALM: DAYS 365 I54C00 DEC 5, 2013 3:24 PM I54DOO ~~6 3l662gMNT~~ 2~ob~: 9999FF1B I55300 DEC 5, 2013 3:24 PM LINE RE-ENABLE METHOD PASS LINE TEST I55400 DEC 5, 2013 3:24 PM I55500 DEC 5, 2013 3:24 PM I55600 DEC 5, 2013 3:24 PM LINE PER TST NEEDED WRN: DISABLED I55700 DEC 5, 2013 3:24 PM LINE PER TST NEEDED WRN: DAYS 25 I55800 DEC 5, 2013 3:24 PM LINE PER TST NEEDED ALM: DAYS 30 1 UN1 A 2 PR1 B 3 DIESEL c 4 4 I55900 DEC 5' 2013 3:24 PM I60400 DEC 5' 2013 3:24 PM LINE ANN TST NEEDED WRN: DISABLED TANK FULL VOLUME I55A00 TANK PRODUCT LABEL GALLONS DEC 5' 2013 3:24 PM 1 UN1 19782 2 PR1 7901 LINE ANN TST NEEDED WRN: DAYS 355 3 DIESEL 10420 4 0 I55B00 DEC 5' 2013 3:24 PM I60500 DEC 5' 2013 3:24 PM LINE ANN TST NEEDED AL~I: DAYS 365 TANK 4 POINT VOLUMES 9999FF1B TANK PRODUCT LABEL GALLONS I56000 1 UN1 19782 16033 9897 3741 DEC 5' 2013 3:24 PM 2 PR1 7901 6356 3964 1560 3 DIESEL 10420 8502 5200 1893 ~lASS/DENSITY 4 0 0 0 0 DISABLED I60600 DEC 5' 2013 3:24 PM I56400 DEC 5' 2013 3:24 PM TANK 20 POINT VOLUMES ULLAGE: 90% TANK PRODUCT LABEL GALLONS 1 UN1 19782 1603~ 0 0 0 0 0 I56500 0 0 9897 0 DEC 5' 2013 3:24 PM 0 0 0 3741 0 0 0 0 ~IAINTENANCE HISTORY PR1 7901 0 0 0 0 6356 0 0 DISABLED 0 0 3964 0 0 0 0 1560 0 0 0 0 I56600 DIESEL 10420 850~ 0 0 DEC 5' 2013 3:24 PM 0 0 0 0 0 5200 0 SERVICE NOTICE: DISABLED 0 0 0 1893 0 0 0 0 4 0 0 0 0 0 0 0 0 I56700 0 0 0 0 DEC 5' 2013 3:24 PM 0 0 0 0 0 0 0 0 I56800 DEC 5' 2013 3:24 PM I60700 DEC 5' 2013 3:24 PM I56900 TANK DIAMETER DEC 5' 2013 3:24 PM TANK PRODUCT LABEL INCHES 1 UN1 118.35 I56A00 2 PR1 118.35 DEC 5' 2013 3:24 PM 3 DIESEL 118.38 4 0.00 I5BC00 I60800 DEC 5' 2013 3:24 PM DEC 5' 2013 3:24 PM RECEIVER SETUP REPORT TANK TILT TANK PRODUCT LABEL INCHES D 1: 1 UN1 0.00 -NO ALARM ASSIGNMENTS -2 PR1 0.00 3 DIESEL 0.00 D 2: 4 0.00 -NO ALARM ASSIGNMENTS -I60900 D 3: DEC 5' 2013 3:24 PM -NO ALARM ASSIGNMENTS -TANK THER~IAL COEFFICIENT D 4: -NO ALARM ASSIGNMENTS -TANK PRODUCT LABEL 1 UN1 0.000700 D 5: 2 PR1 0.000700 -NO ALARM ASSIGNMENTS -3 DIESEL 0.000450 4 0.000000 D 6: -NO ALARM ASSIGNMENTS -I60A00 DEC 5' 2013 3:24 PM D 7: -NO ALARM ASSIGNMENTS -TANK FULL VOLUME D 8: TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UN1 -NO ALARM ASSIGNMENTS -4 PTS 19782 2 PR1 4 PTS 7901 3 DIESEL 4 PTS 10420 4 1 PT 0 I5BD00 DEC 5' 2013 3:24 PM I60B00 DEC 5' 2013 3:24 PM CUSTOM ALARM LABELS STICK HEIGHT OFFSET DISABLED ENABLE STATUS DISABLED I60COO I5BE00 DEC 5' 2013 3:24 PM DEC 5' 2013 3:24 PM TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES I5BF00 1 UN1 0.00 DEC 5' 2013 3:24 PM 2 PR1 0.00 3 DIESEL 0.00 4 0.00 I5E200 I60E00 DEC 5' 2013 3:24 PM DEC 5' 2013 3:24 PM I60100 DEC 5' 2013 3:24 PM I60F00 DEC 5' 2013 3:24 PM TANK CONFIGURATION PROBE OFFSET DEVICE LABEL CONFIGURED 1 UNl ON TANK PRODUCT LABEL INCHES 2 PR1 ON 1 UN1 0.00 3 DIESEL ON 2 PR1 0.00 4 OFF 3 DIESEL 0.00 4 0.00 I60200 DEC 5' 2013 3:24 PM I61000 DEC 5' 2013 3:24 PM TANK PRODUCT LABEL TANK DELIVERY DELAY TANK PRODUCT LABEL TANK PRODUCT LABEL 1 UN1 1 UN1 5 2 PR1 2 PR1 5 3 DIESEL 3 DIESEL 5 4 4 1 I60300 DEC 5' 2013 3:24 PM I61100 DEC 5' 2013 3:24 PM TANK PRODUCT CODE LEAK TEST METHOD ------ TANK PRODUCT LABEL TEST ON DATE : ALL TANK Page 10 JUL 23, 2010 START TIME : DISABLED TEST RATE :0, 20 GAL/HR DURATION : 2 HOURS TST EARLY STOP: DISABLED I61200 DEC 5, 2013 3:24 PM TANK MANIFOLDED PARTNERS TANK T~NKS 2 ~ I61300 PRODUCT LABEL UN1 PR1 DIESEL DEC 5, 2013 3:24 PM CSLD PROBABLITY OF DETECTION I61400 DEC 5, 2013 3:24 PM CSLD CLIMATE FACTOR I61500 DEC 5' 2013 3:24 PM TANK PRODUCT LABEL 1 UN1 2 PR1 3 DIESEL 4 I61600 DEC 5' 2013 3:24 PM TANK PRODUCT LABEL 1 UN1 2 PR1 3 DIESEL 4 I61800 DEC 5' 2013 3:24 PM I61900 DEC 5' 2013 3:24 PM I61A00 DEC 5' 2013 3:24 PM IN-TANK LEAK TEST EARLY TANK PRODUCT LABEL 1 UN1 2 PR1 3 DIESEL 4 I61B00 DEC 5' 2013 3:24 PM STOP SIPHON MANIFOLDED TANKS NONE NONE NONE NONE METER DATA NO NO NO NO CAL UPDATE IMMEDIATE IMMEDIATE IMMEDIATE IMMEDIATE TST EARLY STOP: DISABLED DISABLED DISABLED DISABLED LINE MANIFOLDED NONE NONE NONE NONE IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 DEC 5, 2013 3:24 PM CSLD REPORT ONLY I61D00 DEC 5, 2013 3: 24 PM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL TANKS 1 UN1 2 PR1 3 DIESEL 4 I61E00 DEC 5' 2013 3:24 PM I61F00 ~~~? 5, 2013 3:24 PM I62100 DEC 5' 2013 3:24 PM TANK LOW PRODUCT LIMIT TANK 1 2 3 4 I62200 PRODUCT LABEL UN1 PR1 DIESEL DEC 5, 2013 3:24 PM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL 1 UN1 2 PR1 3 DIESEL 4 I62300 DEC 5' 2013 3:24 PM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL 1 UN1 2 PR1 3 DIESEL 4 I62400 DEC 5' 2013 3:24 PM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL 1 UN1 2 PR1 3 DIESEL I62500 SIPHON MANIFOLDED TANKS LINE MANIFOLDED NONE NONE NONE NONE GALLONS 540 500 251 0 GALLONS 18793 7506 9899 0 GALLONS 17803 7110 9378 0 INCHES 3.0 3.0 3.0 NONE NONE NONE NONE Page 11 DEC 5' 2013 3:24 PM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL 1 UN1 2 PR1 3 DIESEL 4 I62600 DEC 5' 2013 3:24 PM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL 1 UN1 2 PR1 3 DIESEL 4 I62700 DEC 5' 2013 3:24 PM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL 1 UN1 2 PR1 3 DIESEL I62800 DEC 5' 2013 3:24 PM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL 1 UN1 2 PR1 3 DIESEL 4 I62900 DEC 5' 2013 3:24 PM TANK DELIVERY REQUIRED T~NK 2 3 4 I62A00 PRODUCT LABEL UN1 PR1 DIESEL DEC 5, 2013 3:24 PM LIMIT ANNUAL LEAK TEST MIN VOLU~IE TANK 1 i I62B00 PRODUCT LABEL UN1 PR1 DIESEL DEC 5, 2013 3:24 PM TANK LAST ANNUAL TEST TANK 1 2 3 4 I62C00 PRODUCT LABEL UN1 PR1 DIESEL DEC 5, 2013 3:24 PM TANK PERIODIC TEST TYPE TANK 1 2 ~ I62D00 PRODUCT LABEL UN1 PR1 DIESEL DEC 5, 2013 3:24 PM TANK LEAK TEST FAIL ALARMS 4 I62E00 PRODUCT LABEL UN1 PR1 DIESEL DEC 5, 2013 3:24 PM GALLONS 50 50 50 99 GALLONS 15 u INCHES 1.0 1.0 1.0 GALLONS 19782 7901 10428 GALLONS 2967 1185 1042 0 GALLONS 989 395 494 DATE ??? ~~~ 0 0, 8: 0, 8 0 0 PERIODIC TEST TYPE STANDARD STANDARD STANDARD STANDARD GROSS TEST FAIL PERIODIC TEST FAIL ANNUAL TEST FAIL GROSS TEST FAIL PERIODIC TEST FAIL ANNUAL TEST FAIL GROSS TEST FAIL PERIODIC TEST FAIL ANNUAL TEST FAIL GROSS TEST FAIL PERIODIC TEST FAIL ANNUAL TEST FAIL CAPO PROBE CONDUCTIVE BOOT FLAG TANK PRODUCT LABEL I62F00 DEC 5, 2013 3:24 PM MAG PROBE FLOAT SIZE TANK 1 2 3 I63000 PRODUCT LABEL UN1 PR1 DIESEL DEC 5, 2013 3:24 PM IN-TANK LEAK TEST NOTIFY I63100 PRODUCT LABEL UN1 PR1 DIESEL DEC 5, 2013 3:24 PM TANK LEAK TEST AVERAGING CAPO CONDUCTIVE BOOT: FLOAT SIZE: 3.0 IN. 3.0 IN. 3.0 IN. TANK TEST NOTIFY: OFF OFF OFF OFF ALARM DISABLED ALARM DISABLED ALARM DISABLED ALARM DISABLED ALARM DISABLED ALARM DISABLED ALARM DISABLED ALARM DISABLED ALARM DISABLED ALARM DISABLED ALARM DISABLED ALARM DISABLED TANK PRODUCT 1 UN1 2 PR1 3 DIESEL LABEL ANNUAL OFF OFF OFF PERIODIC OFF OFF OFF 4 I63200 DEC 5' 2013 3:24 PM TANK TEST SIPHON BREAK TANK PRODUCT LABEL 1 UN1 2 PR1 3 DIESEL 4 I63300 DEC 5, 2013 3:24 PM OFF SIPHON BREAK OFF OFF OFF OFF LEAK TEST REPORT FORMAT: NORMAL I63400 DEC 5, 2013 3:24 PM RECONCILIATION WARNING LIMIT TANK 1 2 3 4 I63500 PRODUCT LABEL UN1 PR1 DIESEL DEC 5, 2013 3:24 PM RECONCILIATION ALARM LIMIT T1NK 2 ~ I63600 PRODUCT LABEL UN1 PR1 DIESEL DEC 5, 2013 3:24 PM PERIODIC LEAK TEST MIN VOLUME TANK 1 2 3 4 I63900 PRODUCT LABEL UN1 PR1 DIESEL DEC 5, 2013 3:24 PM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 UN1 END FACTOR: NONE 2 PR1 END FACTOR: NONE 3 DIESEL END FACTOR: NONE 4 END FACTOR: NONE I63A00 DEC 5, 2013 3:24 PM GALLONS 0 8 GALLONS 989 395 494 0 OFF LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD PRODUCT LABEL UN1 PUMP THRESHOLD PR1 DIESEL I63B00 ¥~~K ~6 ~&i~T MiM~ AND VOLUMES I63C00 DEC 5, 2013 3:24 PM TANK 50 POINT FULL VOLUME TANK 1 2 3 4 I63D00 PRODUCT LABEL UN1 PR1 DIESEL DEC 5, 2013 3:24 PM 9999FF1B I68000 DEC 5, 2013 3:24 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 FUEL MANAGEMENT SETUP DELIVERY WARN DAYS: 0. 0 AUTO PRINT: DISABLED !8:88~ 10.00% GALLONS 0 0 0 0 FUEL MANAGEMENT AVERAGE SALES (GALLONS) UN1 ( TANK 1 ) SUN MON TUE WED THR FRI SAT 0 0 0 0 0 0 0 PR1 ( TANK 2 ) SUN MON TUE WED THR FRI SAT 0 0 0 0 0 0 0 DIESEL ( TANK 3 ) SUN MON TUE WED THR FRI SAT 0 0 0 0 0 0 0 I68100 DEC 5' 2013 3:24 PM Page 12 I68200 DEC 5' 2013 3:24 PM I68300 DEC 5' 2013 3:24 PM I70100 DEC 5' 2013 3:24 PM LIQUID CONFIGURATION DEVICE LABEL 1 DISP 1-2 DUAL 2 DISP 3-4 DUAL 3 DISP 5-6 DUAL 4 DISP 7-8 DUAL 5 DISP 9-10 DUAL 6 DISP 11-12 DUAL 7 DISP 13-14 DUAL 8 87 TURBINE 9 87 TURBINE BRINE 10 87 FILL 11 87 FILL BRINE 12 87 ANNULAR 13 91 TURBINE 14 91 TURBINE BRINE 15 91 FILL 16 91 FILL BRINE 17 91 DIESEL ANNULAR 18 DIESEL TURBINE 19 DIESEL TURBINE BRINE 20 DIESEL FILL 21 DIESEL FILL BRINE 22 VENT SUMP 23 VENT SUMP BRINE 24 I70200 DEC 5' 2013 3:24 PM LIQUID LABEL DEVICE LABEL 1 DISP 1-2 DUAL 2 DISP 3-4 DUAL 3 DISP 5-6 DUAL 4 DISP 7-8 DUAL 5 DISP 9-10 DUAL 6 DISP 11-12 DUAL 7 DISP 13-14 DUAL 8 87 TURBINE 9 87 TURBINE BRINE 10 87 FILL 11 87 FILL BRINE 12 87 ANNULAR 13 91 TURBINE 14 91 TURBINE BRINE 15 91 FILL 16 91 FILL BRINE 17 91 DIESEL ANNULAR 18 DIESEL TURBINE 19 DIESEL TURBINE BRINE 20 DIESEL FILL 21 DIESEL FILL BRINE 22 VENT SUMP 23 VENT SUMP BRINE 24 I70300 DEC 5, 2013 3:24 PM LIQUID TYPE SEN SO~ 2 3 4 5 6 7 18 11 12 13 14 15 16 17 18 19 20 21 22 23 24 I70400 LOCATION DISP 1-2 DUAL DISP 3-4 DUAL DISP 5-6 DUAL DISP 7-8 DUAL DISP 9-10 DUAL DISP 11-12 DUAL DISP 13-14 DUAL 87 TURBINE 87 TURBINE BRINE 87 FILL 87 FILL BRINE 87 ANNULAR 91 TURBINE 91 TURBINE BRINE 91 FILL 91 FILL BRINE 91 DIESEL ANNULAR DIESEL TURBINE DIESEL TURBINE BRINE DIESEL FILL DIESEL FILL BRINE VENT SUMP VENT SUMP BRINE DEC 5, 2013 3:24 PM LIQUID CATEGORY SEN SO~ 2 ~ J 11 12 13 14 15 16 H LOCATION DISP 1-2 DUAL DISP 3-4 DUAL DISP 5-6 DUAL DISP 7-8 DUAL DISP 9-10 DUAL DISP 11-12 DUAL DISP 13-14 DUAL 87 TURBINE 87 TURBINE BRINE 87 FILL 87 FILL BRINE 87 ANNULAR 91 TURBINE 91 TURBINE BRINE 91 FILL 91 FILL BRINE 91 DIESEL ANNULAR DIESEL TURBINE 19 DIESEL TURBINE BRINE 20 DIESEL FILL 21 DIESEL FILL BRINE 22 VENT SUMP H VENT SUMP BRINE I70600 DEC 5, 2013 3:24 PM !70700 DEC 5, 2013 3:24 PM CONFIGURED ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON OFF TYPE DW SUMP 2-1 DW SUMP 2-1 DW SUMP 2-1 DW SUMP 2-1 DW SUMP 2-1 DW SUMP 2-1 DW SUMP 2-1 TRI-STATE tSINGLE FLOAT~ TRI-STATE SINGLE FLOAT TRI-STATE SINGLE FLOAT TRI-STATE SINGLE FLOAT DUAL POINT HYDROSTATIC TRI-STATE tSINGLE FLOAT~ TRI-STATE SINGLE FLOAT TRI-STATE SINGLE FLOAT TRI-STATE SINGLE FLOAT DUAL POINT HYDROSTATIC TRI-STATE ~SINGLE FLOATl TRI-STATE SINGLE FLOAT TRI-STATE SINGLE FLOAT TRI-STATE SINGLE FLOAT TRI-STATE SINGLE FLOAT TRI-STATE SINGLE FLOAT TRI-STATE SINGLE FLOAT CATEGORY DISPENSER PAN DISPENSER PAN DISPENSER PAN DISPENSER PAN DISPENSER PAN DISPENSER PAN DISPENSER PAN STP SUMP STP SUMP PIPING SUMP PIPING SUMP ANNULAR SPACE STP SUMP STP SUMP PIPING SUMP PIPING SUMP ANNULAR SPACE STP SUMP STP SUMP PIPING SUMP PIPING SUMP PIPING SUMP PIPING SUMP OTHER SENSORS I70800 DEC 5' 2013 3:24 PM DEC 5' 2013 3:24 PM VACUUM SENSOR PUMP NUMBER I70900 DEVICE LABEL PUMP NUMBER DEC 5' 2013 3:24 PM 9 87 PRODUCT Q 1:87 UNLEADED 10 87 91 VAPOR Q 1: 8 7 UNLEADED 11 87 VENT Q 1:87 UNLEADED I71100 12 91 PRODUCT Q 2:91 UNLEADED DEC 5' 2013 3:24 PM 13 91 VENT Q 2:91 UNLEADED 14 DIESEL PRODUCT Q 3 :DIESEL 17 DIESEL VENT Q 3:DIESEL I71200 DEC 5' 2013 3:24 PM I72A00 DEC I71300 5' 2013 3:24 PM DEC 5' 2013 3:24 PM VACUUM SENSOR VOLUME DEVICE LABEL VOLUME I72100 9 87 PRODUCT 57. 5 GALLONS DEC 5' 2013 3:24 PM 10 87 91 VAPOR 69. 0 GALLONS 11 87 VENT 25 • 0 GALLONS SMART SENSOR CONFIGURATION 12 91 PRODUCT 57.5 GALLONS 13 91 VENT 25.0 GALLONS DEVICE LABEL CONFIGURED 14 DIESEL PRODUCT 46.0 GALLONS 1 DISP 1-2 VFM ON 17 DIESEL VENT 25.0 GALLONS 2 DISP 3-4 VFM ON 3 DISP 5-6 VFM ON 4 DISP 7-8 VFM ON I72BOO 5 DISP 9-10 VFM ON DEC 5' 2013 3:25 PM 6 DISP 11-12 VFM ON 7 DISP 13-14 VFM ON VACUUM SENSOR RELIEF VALVE PRESENT 8 DISP 13-14 PS ON 9 87 PRODUCT ON DEVICE LABEL RELIEF VALVE 10 87 91 VAPOR ON 9 87 PRODUCT NO 11 87 VENT ON 12 91 PRODUCT ON 10 87 91 VAPOR NO 13 91 VENT ON 11 87 VENT NO 14 DIESEL PRODUCT ON 12 91 PRODUCT NO 15 PMC CANISTER ON 13 91 VENT NO 16 ATM P ON 14 DIESEL PRODUCT NO 17 DIESEL VENT ON 17 DIESEL VENT NO 18 OFF 19 OFF 20 OFF 21 OFF I72C00 22 OFF DEC 5' 2013 3:25 PM 23 OFF 24 OFF VACUUM SENSOR RELIEF VALVE PRESSURE DEVICE LABEL RELIEF VALVE PRESSURE I72200 9 87 PRODUCT -9.0 PSI DEC 5' 2013 3:24 PM 10 87 91 VAPOR -9.0 PSI 11 87 VENT -9.0 PSI SMART SENSOR LABEL 12 91 PRODUCT -9.0 PSI 13 91 VENT -9.0 PSI DEVICE LABEL 14 DIESEL PRODUCT -9.0 PSI 1 DISP 1-2 VFM 17 DIESEL VENT -9.0 PSI 2 DISP 3-4 VFM 3 DISP 5-6 VFM 4 DISP 7-8 VFM I74100 5 DISP 9-10 VFM DEC 5' 2013 3:25 PM 6 DISP 11-12 VFM 7 DISP 13-14 VFM 8 DISP 13-14 PS I74200 9 87 PRODUCT DEC 5' 2013 3:25 PM 10 87 91 VAPOR 11 87 VENT 12 91 PRODUCT I74300 13 91 VENT DEC 5' 2013 3:25 PM 14 DIESEL PRODUCT 15 PMC CANISTER 16 ATM P I74400 17 DIESEL VENT DEC 5' 2013 3:25 PM 18 19 20 I74600 21 DEC 5' 2013 3:25 PM 22 23 24 I74700 DEC 5' 2013 3:25 PM I72300 DEC 5' 2013 3:24 PM I74800 DEC 5' 2013 3:25 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. I74900 661-873-9343 DEC 5' 2013 3:25 PM I74B00 SMARTSENSOR ASSIGNMENT DEC 5' 2013 3:25 PM DEVICE LABEL CATEGORY 01 DISP 1-2 VFM AIR FLOW METER 02 DISP 3-4 VFM AIR FLOW METER I74COO 03 DISP 5-6 VFM AIR FLOW METER DEC 5' 2013 3:25 PM 04 DISP 7-8 VFM AIR FLOW METER 05 DISP 9-10 VFM AIR FLOW METER 06 DISP 11-12 VFM AIR FLOW METER I74D00 07 DISP 13-14 VFM AIR FLOW METER DEC 5' 2013 3:25 PM 08 DISP 13-14 PS VAPOR PRESSURE 09 87 PRODUCT VAC SENSOR 10 87 91 VAPOR VAC SENSOR I74EOO 11 87 VENT VAC SENSOR DEC 5' 2013 3:25 PM 12 91 PRODUCT VAC SENSOR 13 91 VENT VAC SENSOR 14 DIESEL PRODUCT VAC SENSOR I75100 15 PMC CANISTER VAPOR VALVE DEC 5' 2013 3:25 PM 16 ATM P ATM P SENSOR 17 DIESEL VENT VAC SENSOR 18 UNKNOWN I75200 DEC 5' 2013 3:25 PM 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN I75300 22 UNKNOWN DEC 5' 2013 3:25 PM 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN I75400 26 UNKNOWN DEC 5' 2013 3:25 PM 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN I75500 30 UNKNOWN DEC 5' 2013 3:25 PM 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN I75600 34 UNKNOWN DEC 5' 2013 3:25 PM 35 UNKNOWN 36 UNKNOWN I75700 37 UNKNOWN DEC 5' 2013 3:25 PM 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN I75800 DEC 5' 2013 3:25 PM I72700 DEC 5' 2013 3:24 PM I75900 DEC 5' 2013 3:25 PM I72800 DEC 5' 2013 3:24 PM I75A00 DEC 5' 2013 3:25 PM I72900 LINE LEAK LOCKOUT SETUP Page 13 ------ LOCKOUT SCHEDULE DAILY START TIME: DISABLED STOP TIME : DISABLED I75B00 DEC 5' 2013 3:25 PM I75coo DEC 5' 2013 3:25 PM I75D00 DEC 5' 2013 3:25 PM I75E00 DEC 5' 2013 3:25 PM I75F00 DEC 5' 2013 3:25 PM I7A600 DEC 5' 2013 3:25 PM I7A700 DEC 5' 2013 3:25 PM I7A800 DEC 5' 2013 3:25 PM I7A900 DEC 5' 2013 3:25 PM 9999FF1B I7AC00 DEC 5' 2013 3:25 PM I7AD00 DEC 5' 2013 3:25 PM I7AE00 DEC 5' 2013 3:25 PM I7AF00 DEC 5' 2013 3:25 PM I7B100 ~G~LI~/; ~&HTI8~ 2 ~ PM METER -TANK MAP BUS SLOT FUEL_P METER TANK ------------------------------- TANK MAP EMPTY I7B200 DEC 5, 2013 3:25 PM METER CALIBRATION OFFSET: 0. 000% I7B400 DEC 5, 2013 3:25 P~f I7BC00 DEC 5, 2013 3:25PM I7BD00 DEC 5, 2013 3:25 PM PRESSURE LLD SETUP REPORT Q 1:87 UNLEADED IN-TANK ALARMS T 1: HIGH WATER ALARM T 1: LOW PRODUCT ALARM L[Q~~~U~tN~~R~LMS L 2: FUEL ALARM L 3: FUEL ALARM L 4: FUEL ALARM L 5: FUEL ALARM L 6: FUEL ALARM L 7: FUEL ALARM L 8: FUEL ALARM L 9: FUEL ALARM LlO: FUEL ALARM L22: FUEL ALARM L23: FUEL ALARM L 1: SENSOR OUT ALARM L 2: SENSOR OUT ALARM L 3: SENSOR OUT ALARM L 4: SENSOR OUT ALARM L 5: SENSOR OUT ALARM L 6: SENSOR OUT ALARM L ?:SENSOR OUT ALARM L 8: SENSOR OUT ALARM L 9: SENSOR OUT ALARM L10: SENSOR OUT ALARM Lll: SENSOR OUT ALARM L22: SENSOR OUT ALARM L23: SENSOR OUT ALARM L 1: SHORT ALARM L 2: SHORT ALARM L 3: SHORT ALARM L 4: SHORT ALARM L 5: SHORT ALARM L 6: SHORT ALARM L 7: SHORT ALARM L 8: SHORT ALARM L 9: SHORT ALARM LlO: SHORT ALARM Lll: SHORT ALARM Ll2: SHORT ALARM L22: SHORT ALARM L23: SHORT ALARM L12: HIGH LIQUID ALARM L 1: LOW LIQUID ALARM L 2: LOW LIQUID ALARM L 3: LOW LIQUID ALARM L 4: LOW LIQUID ALARM L 5: LOIY LIQUID ALARM L 6: LOIY LIQUID ALARM L 7: LOW LIQUID ALARM Lll: LOW LIQUID ALARM Ll2: LOW LIQUID ALARM Page 14 PRESSURE LINE LEAK Q 1: PLLD OPEN ALARM SMARTSENSOR ALARMS s10: FUEL ALARM s 9: HIGH LIQUID ALARM s10: HIGH LIQUID ALARM sll: HIGH LIQUID ALARM ISO SITE ALARMS ISO GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL: FLOW COLLECT FAIL Q 2: 91 UNLEADED IN-TANK ALARMS T 2: HIGH WATER ALARM T 2: LOW PRODUCT ALARM LIQUID SENSOR ALMS L 1: FUEL ALARM L 2: FUEL ALARM L 3: FUEL ALARM L 4: FUEL ALARM L 5: FUEL ALARM L 6: FUEL ALARM L 7: FUEL ALARM L13: FUEL ALARM L14: FUEL ALARM Ll5: FUEL ALARM L16: FUEL ALARM L17: FUEL ALARM L22: FUEL ALARM L23: FUEL ALARM L 1: SENSOR OUT ALARM L 2: SENSOR OUT ALARM L 3: SENSOR OUT ALARM L 4: SENSOR OUT ALARM L 5: SENSOR OUT ALARM L 6: SENSOR OUT ALARM L 7: SENSOR OUT ALARM Ll3: SENSOR OUT ALARM Ll4: SENSOR OUT ALARM L15 :SENSOR OUT ALARM Ll6: SENSOR OUT ALARM L17: SENSOR OUT ALARM L22: SENSOR OUT ALARM L23: SENSOR OUT ALARM L 1: SHORT ALARM L 2: SHORT ALARM L 3: SHORT ALARM L 4: SHORT ALARM L 5 : SHORT ALARM L 6: SHORT ALARM L 7: SHORT ALARM L13: SHORT ALARM L14: SHORT ALARM Ll5 :SHORT ALARM L16: SHORT ALARM L17: SHORT ALARM L22: SHORT ALARM L23: SHORT ALARM t1l':r6~\i~3~5D At~~~M L 2: LOIY LIQUID ALARM L 3: LOW LIQUID ALARM L 4: LOW LIQUID ALARM L 5: LOW LIQUID ALARM L 6: LOW LIQUID ALARM L 7: LOW LIQUID ALARM L17: LOW LIQUID ALARM PRESSURE LINE LEAK Q 2: PLLD OPEN ALARM SMARTSENSOR ALARMS s10: FUEL ALARM sl2: FUEL ALARM s13: FUEL ALARM s10: HIGH LIQUID ALARM s12: HIGH LIQUID ALARM s13: HIGH LIQUID ALARM ISO SITE ALARMS ISD GROSS PRES FAIL ISO DEGRD PRES FAIL ISO VAPOR LEAK FAIL ISD VP PRES FAIL ISO VP STATUS FAIL ISO HOSE ALARMS ALL: FLO\Y COLLECT FAIL Q 3 :DIESEL IN-TANK ALARMS T 3: HIGH WATER ALARM T 3: LOW PRODUCT ALARM L[Q~~~u~tN~~MLMS L 2: FUEL ALARM L 3: FUEL ALARM L 4: FUEL ALARM L17: FUEL ALARM L18 FUEL ALARM L19 FUEL ALARM L20 FUEL ALARM L21 FUEL ALARM L22 FUEL ALARM L23 FUEL ALARM L 1 SENSOR OUT ALARM L 2 SENSOR OUT ALARM L 3 SENSOR OUT ALARM L 4 SENSOR OUT ALARM Ll7 SENSOR OUT ALARM Ll8 SENSOR OUT ALARM Ll9 SENSOR OUT ALARM L20 SENSOR OUT ALARM L21 SENSOR OUT ALARM L22 SENSOR OUT ALARM L23 SENSOR OUT ALARM L 1 SHORT ALARM L 2 SHORT ALARM L 3 SHORT ALARM L 4 SHORT ALARM L17 SHORT ALARM L18 SHORT ALARM L19 SHORT ALARM L20 SHORT ALARM L21 SHORT ALARM L22 SHORT ALARM L23 SHORT ALARM t1i ~ij~H Li~3~5D At~~~M L 2 LOW LIQUID ALARM L 3 LOW LIQUID ALARM L 4 LOW LIQUID ALARM Ll7: LOW LIQUID ALARM PRESSURE LINE LEAK Q 3: PLLD OPEN ALARM SMARTSENSOR ALARMS s14: FUEL ALARM s17: FUEL ALARM s14: HIGH LIQUID ALARM s17: HIGH LIQUID ALARM I7BE00 DEC 5' 2013 3:25 PM I7C400 DEC 5' 2013 3:25 PM I7C500 DEC 5' 2013 3:25 PM I7C600 DEC 5' 2013 3:25 PM I7C700 DEC 5' 2013 3:25 PM I7C800 DEC 5' 2013 3:25 PM I7C900 DEC 5' 2013 3:25 PM I80100 DEC 5' 2013 3:25 PM EXTERNAL INPUT CONFIGURATION DEVICE LABEL 1 EMERGENCY SHUT OFF 2 I80200 DEC 5' 2013 3:25 PM EXTERNAL INPUT LABEL DEVICE LABEL 1 EMERGENCY SHUT OFF 2 I80300 DEC 5' 2013 3:25 PM EXTERNAL INPUT TYPE INPUT NAME 1 EMERGENCY SHUT OFF 2 I80400 DEC 5' 2013 3:25 PM I80600 DEC 5' 2013 3:25 PM RELAY CONFIGURATION DEVICE LABEL 1 OVERFILL 2 I80700 DEC 5' 2013 3:25 PM RELAY LABEL DEVICE LABEL 1 OVERFILL 2 I80800 DEC 5, 2013 3: 2 5 PM RELAY SETUP REPORT R 1: OVERFILL TYPE: STANDARD NORMALLY OPEN TANK #: NONE IN-TANK ALARMS ALL: OVERFILL ALARM ALL: HIGH PRODUCT ALARM R 2: TYPE: STANDARD NORMALLY OPEN TANK #: NONE -NO ALARM ASSIGNMENTS - I80900 DEC 5, 2013 3:26 PM RELAY ORIENTATION RELAY DESIGNATION 1 OVERFILL 2 I80A00 DEC 5, 2013 3:26 PM RELAY TYPE RELAY DESIGNATION 1 OVERFILL 2 I80B00 DEC 5, 2013 3:26 PM CONFIGURED ON OFF TYPE STANDARD STANDARD CONFIGURED ON OFF ORIENTATION NORMALLY OPEN NORMALLY OPEN TYPE STANDARD STANDARD ORIENTATION NORMALLY OPEN NORMALLY OPEN TANK# Page 15 RELAY TANK ASSIGNMENT RELAY DESIGNATION 1 OVERFILL 2 I80coo DEC 5' 2013 3:26 PM EXTERNAL INPUT TYPE INPUT NAME 1 EMERGENCY SHUT OFF 2 I85100 DEC 5' 2013 3:26 P~l RESTORE SETUP DATA: DISABLED I85200 DEC 5' 2013 3:26 PM SAVE SETUP DATA: DISABLED I85300 DEC 5' 2013 3:26 PM CLEAR SETUP DATA: DISABLED I88100 DEC 5' 2013 3:26 PM I88200 DEC 5' 2013 3:26 PM I88500 DEC 5' 2013 3:26 PM I88600 DEC 5' 2013 3:26 PM I88700 DEC 5' 2013 3:26 PM I88800 glj~M ~6A~g13 : 3:26 PM 1 ~EDIM CONNECTION NO E COMM BOARD 2 ~S-SAT ) CONNECTION NO E COMM BOARD 5 ~RS-485) CONNECTION NO E COMM BOARD 6 (RS-232) CONNECTION NONE I88900 DEC 5' 2013 3:26 PM I88DOO DEC 5' 2013 3:26 PM I89100 DEC 5' 2013 3:26 PM I8A200 DEC 5, 2013 3:26 PM FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343 SERVICE CODE LIST STANDARD LABEL CODE ~6mo~~~~~~st~~ 8i82 ~~n~~ll~E~c F~s~~D 818~ NO SOLUTION FOUND 0105 OTHER SOLUTION 0106 REPLACED KEYBOARD 0107 REPLACED DISPLAY 0108 SYSTEM UPGRADE 0109 CONDUCTED TRAINING 0110 OPERATOR ERROR 0111 INSTALLED PAPER 0201 REPLACED PRINTER 0202 NEW LINE SHARE DEY 0203 CLEARED PAPER JAM 0204 REMOVED TANK WATER 0301 PRECISION TANK TEST 0302 RECONNECTED PROBE 0303 REPLACED PROBE 0304 FIX STUCK FLOAT 0305 CLEANED PROBE 0306 CORRECT TANK CHART 0307 RESET ACCUCHART 0308 REPLACED SENSOR 0401 REWIRED SENSOR 0402 REMOVED FUEL 0403 REMOVED WATER 0404 ADJUSTED BRINE LVL 0405 REPAIRED PRIMARY LK 0406 REPAIRED SEC LK 0407 RECHARGED VACUUM 0408 REPLACED VAC TUBING 0409 ADDED COMM BOARD 0501 RESET MODEM 0502 RECONNECT PHONE LN 0503 NEW PHONE NUMBER 0504 NEW IP ADDRESS 0505 REPLACED COMM CABLE 0506 REPLACED DIM MODULE 0601 REPLACED DIM CABLE 0602 DIM MISAPPLICATION 0603 CAB RUN MODE 0604 REPAIRED LEAK 0701 REPAIRED STP CAP 0702 RESTORE STP POWER 0703 CLEAN FUNC ELEMENT 0704 DISBLE FUNC ELEMENT 0705 OUT OF FUEL 0706 REPL LLD TRANSDUCER 0707 REWIRED LLD 0708 REPLACED LLD MODULE 0709 REPLACED CHECK VLV 0710 REPLACE PRODUCT RL Y 0711 REPLACE DISP VALVE 0712 TANK NONE NONE TYPE STANDARD STANDARD ORIENTATION NORMALLY OPEN NORMALLY OPEN TANK# ELIM WPLLD NOISE 0713 INSTALL MECH LLD 0714 PERFORM LINE TEST 0715 REPLACED MLLD 0716 INSTALL NEW STP 0801 REPLACED UMP 0802 REPL FUNC ELEMENT 0803 REPL CHECK VALVE 0804 PMP NEW IP ADDRESS 0805 REPL CONTROL BOX 0806 REPLACED CAPACITOR 0807 REPLACED SEALS 0808 REPL VAR SPD CNTRL 0809 mcReeLbU~bNTROL 8~5~ REPL VLLD CHECK VLV 0902 VLLD SELF CHECK 0903 VLLD PUMP SELF TST 0904 VLLD OTHER ACTION 0905 CAL VAC ASSIST PUMP 1001 CONDUCTED A/L TEST 1002 BACK PRESSURE TEST 1003 2 IN DECAY TEST 1004 10 IN DECAY TEST 1005 REPAIRED CONT LEAK 1006 RPR VAC ASSIST PUMP 1007 REPL VAC ASSIST PMP 1008 ADJUSTED A/L 1009 SVC VAPOR PROCESSOR 1010 RPR SPILL BUCKET 1101 RPR DELIVERY CAP 1102 RPR VPR EXTR CAP 1103 RPR PROBE RISER CAP 1104 REPLACED FILTER 1201 REPL DISPENSER SW 1202 COLD BOOT SYSTEM 1203 REPAIRED DISPENSER 1204 RESET SHEAR VALVE 1205 REPL SHEAR VALVE 1206 REPAIRED PIPING 1207 REPAIRED BOOT 1208 CALIS LIQUID MTR 1209 REPL DISPENSER PRTR 1210 INSTALLED PAPER 1211 CLEARED PAPER JAM 1212 REPAIRED DOOR LOCK 1213 REPAIRED DOOR SW 1214 REPL HANGING HW 1301 REPLACED NOZZLE 1302 REPLACED BOOT 1303 REPLACED SPOUT 1304 REPL PRIMARY HOSE 1305 REPLACED BREAKAWAY 1306 REPAIRED BREAKAWAY 1307 REPLACED WHIP HOSE 1308 REPL HOSE EXTRACTOR 1309 REPL FLOIY LIMITER 1310 REPL NOZZLE COVER 1311 BAGGED OFF NOZZLE 1312 RETURNED NOZZLE 1313 REPROGRAMMED POS 1401 REPL POS SOFTWARE 1402 COLD BOOT SYSTEM 1403 REPLACED POS 1404 REWIRED POS 1405 RPR OUTSIDE LIGHTS 1501 REPAIRED SIGNAGE 1502 CLEANED STORM DRAIN 1503 SVC OIL WTR SEPRATR 1504 ANN OPERABILITY TST 1601 WEIGHT MEASURES TST 1602 6~~kAf~~Ee~~H TST 1~8~ ~~~LlE~8cKET TEST 1~8~ USER DEFINED LABEL CODE NONE I8A300 DEC 5, 2013 3:26 PM I8A400 DEC 5, 2013 3:26 PM I8BC00 DEC 5, 2013 3:26 PM RELAY SETUP REPORT R 1: OVERFILL TYPE: STANDARD NORMALLY OPEN TANK #: NONE IN-TANK ALARMS ALL: OVERFILL ALARM ALL: HIGH PRODUCT ALARM R 2: TYPE: STANDARD NORMALLY OPEN TANK #: NONE -NO ALARM ASSIGNMENTS - I8C100 DEC 5' 2013 3:26 PM I8C200 DEC 5' 2013 3:26 PM 9999FFlB9999FFlB I90100 DEC 5' 2013 3:26 PM I/O SYSTEM BOARD PASS I90200 DEC 5, 2013 3:26 PM SOFTWARE REVISION LEVEL VERSION 330.01 SOFTWARE# 346330-100-B CREATED -10.07.23.17 .25 S-MODULE# 330160-104-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS BIR ISD RAM PROM PASS PASS Page 16 I90300 DEC 5, 2013 3:26 PM PC DIAGNOSTIC DATA PERIPHERAL CONTROLLER PC SWARE# 330269-002-B CREATED -94.12.16.13.26 PC ROM CHECKSUM = PASSED PC RESET COUNTS = 91 PC COMM ERRORS = 63 MC CKSUM ERRS = 7 MC->PC COMMS =1158052404 MC<-PC COMMS =1158077687 I90500 DEC 5, 2013 3:26 PM SOFTWARE REVISION LEVEL VERSION 330. 01 SOFTWARE# 346330-100-B CREATED-10.07.23.17.25 S-~IODULE# 330160-104-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS BIR ISD 9999FFlB