HomeMy WebLinkAboutFMC 2013els 1~ environmental services, inc.
25971 Towne Centre Drive, Foothill Ranch, CA 92610
Tel: (949) 460-5200 Fax: (949) 460-5210
Date:
To:
From:
Sent Via:
Re:
12/16/2013
Ernie Medina
Bakersfield Fire Dept.
1500 Truxtun Ave
Bakersfield, CA 93301
Billy Moothart
Email
Monitoring System Cert
Foods Co # 384
2501 Haley St.
Bakersfield, CA 93305
TRANSMITTAL
The following test report(s) are included:
Monitoring System Cert
Comments:
Please do not hesitate to call me at (949) 460-5200 if you have any questions or concerns regarding this work.
936527
Appendix VI
(Copies of Monitoring System Certification form and UST Monitoring Plot Plan available at http://www.waterboards.ca.gov.)
MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State of California
Authority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of
Regulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for
each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system
owner/operator. The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date.
A. General Information
Facility Name: Foods Co # 384 Bldg. No.: ______ _
Site Address: 2501 Haley St. City: Bakersfield Zip: 93305
Facility Contact Person: _________________ Contact Phone No.: { (661) 813_-_2_05_2 _______ _
Make/Model of Monitoring System: -'-T-'-'L-=-S--'-3'--'5-'-0 ____________ _ Date of Testing/Servicing: __ 1_2_/51_2_0_1_3 __ _
B. Inventory of Equipment TestecVCertified
Ch k h . b . d" T ec t e appropnate oxes to 1n 1cate spec1 1c equ1pment ms ~ecte dl d serv1ce :
Tank ID: Unleaded Tank 10· Premium
~ In-Tank Gauging Probe. Model: 846390-110 ~ . Model: 8216390-110 ~ In-Tank Gauging Probe.
~ Annular Space or Vault Sensor. Model: 794380-303 ~ Annular Space or Vault Sensor. Model: Soli! w1th D1esel
~ Piping Sump I Trench Sensor(s). Model: 794380-323/304 ~ Piping Sump I Trench Sensor(s). Model: 7921380-32373021
?_ Fill Sump Sensor(s). Model: 794380-323/304 ~ Fill Sump Sensor(s). Model: 794380-3237304
--. Mechanical Line Leak Detector. Model: --. Mechanical Line Leak Detector. Model: ~ Electronic Line Leak Detector. Model: PLLD ~ Electronic Line Leak Detector. Model: PLLD
?_ Tank Overiill I High-Level Sensor. Model: 846390-110 ?_ Tank Overiill/ High-Level Sensor. Model: 846390-110
~ Other (specify equipment type and model in Section E on Page 2). ~ Other (specify equipment type and model in Section E on Page 2).
~nk ID: U1ese1 I!lnk ID: ~ In-Tank Gauging Probe. Model: 846390-110 ~ In-Tank Gauging Probe. Model:
Annular Space or Vault Sensor. Model: 794380-303 ~ Annular Space or Vault Sensor. Model:
Piping Sump I Trench Sensor(s). Model: 794380-3237304 ~ Piping Sump I Trench Sensor(s). Model: ~ Fill Sump Sensor(s). Model: 794380-323/304 ~ Fill Sump Sensor(s). Model:
~ Mechanical Line Leak Detector. Model: ~ Mechanical Line Leak Detector. Model: ~ Electronic Line Leak Detector. Model: PLLD ~ Electronic Line Leak Detector. Model: ~ Tank Overiill I High-Level Sensor. Model: 846390-110 ~ Tank Overiill I High-Level Sensor. Model:
~ Other (specify equipment type and model in Section E on Page 2). ~ Other (specify equipment type and model in Section E on Page 2).
Dispenser ID: 1 I 2 ~"'"""'"' 314 ~ Dispenser Containment Sensor(s). Model: 794380-323/304 Dispenser Containment Sensor(s). Model: 794380-323/304
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Roat(s) and Chain(s).
Dispenser ID: 5 I 6 Dispenser ID: 7 I 8
~ Dispenser Containment Sensor(s). Model: 794380-323/304 ~ Dispenser Containment Sensor(s). Model: 794380-323/304
Shear Valve(s). Shear Valve(s).
Dispenser Containment Roat(s) and Chain(s). Dispenser Containment Roat(s) and Chain(s).
Dispenser 1 D: 9 I 1 0 DispenseriD: 11/12-13/14
~ Dispenser Containment Sensor(s). Model: 794380-3237304 ~ Dispenser Containment Sensor(s). Model: 794380-323/304
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s Dispenser Containment Roat(s) and Chain(s). . .. .. If the facility conta1ns more tanks or dispensers, copy this form. Include 1nformat1on for every tank and dispenser at the facility .
C. Certification -I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers'
guidelines. Attached to this Certification is information (e.g. manufacturers' checklists) necessary to verify that this information is correct
and a Plot Plan showing the layout of monitor.JrljJ equipment. For any equipment capable of generatin. g sue. h reports, I have also attached a
copy of the report; (check a// that apply): ~System set-up ~Alarm history report ./ :
rl ~· J'YL '-,-/ Technician Name (print): Sheer Signature: d'fn · • l
Certification No.: 837955 License. No.: 808313 /
Testing Company Name: Belshire Environmental Services, Inc. Phone No.:~)_4_6_0-_5_2_00 ________ _
Testing company Address: 25971 Towne Centre Dr., Foothill Ranch, CA 92610 Date of Testing/Servicing: 12/5/2013
Monitoring System Certification Page 1 of4 12/07
D. Results of Testing/Servicing
Software Version Installed: 330.01 ~~~~~~~~~~~~~~~---
c omp1ete t h f II h kl" e o owmg_c ec IS!:
li']Yes 0 No* Is the audible alarm operational?
li']Yes 0 No* Is the visual alarm operational?
I [Yes ~No* Were all sensors visually inspected, functionally tested, and confim1ed operational?
li']Yes D No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not interfere wah their
proper operation?
bl]Yes D No* If alam1s are relayed to a remote monitoring station, is all communications equipment (e.g. modem) operational?
NIA
li']Yes B No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment monitoring system
N/A ~eels a leak, fails to operat~or is electrically disconnected? If yes: which sensors initiate positive shut-down? {Check all that apply)
Sump/Trench Sens~ ~ispenser Containment Sensors. Did you confirm positive shut-down due to leaks .5!lli! sensor
failure/disconnection? '1/ es; No.
li']Yes B No* For tank systems that utilize the monit01ing system as the primary tank overfill warning device (i.e. no mechanical overfill prevention
N/A valve is installed), is the overfill warning alarm visible and audible at the tank fill point(s) and operating properly? If so, at what percent
of tank capac tty does the alam1 triQQer? 90 %
UYes* ~No Was any monttoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the
manufacturer name and model for all replacement parts in Section E, below.
UYes* bl) No Was liquid found inside any secondary containment systems designed as dry systems? {Check all that apply)UProduct; UWater. If
yes, describe causes in Section E, below.
bl]Yes L J No* Was monitoring system set-up reviewed to ensure proper settings? Attach set up reports, if applicable
fV']Yes f l No* Is all monitoring equipment operational per manufacturer's specifications? .. *In Section E below, descnbe how and when these def1c1enc1es were or Will be corrected.
E. Comments:
Vent box 794380-323/304
S 11 in no vac alarm
S13 did not go into high liquid alarm
Monitoring System Certification Page 2 of4 12/07
F. In-Tank Gauging I SIR Equipment: ~ Check this box if tank gauging is used only for inventory control.
D Check this box if no tank gauging or SIR equipment is installed.
This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist·
DYes 0 No* Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
DYes 0 No* Were all tank gauging probes visually inspected for damage and residue buildup?
DYes 0 No* Was accuracy of system product level readings tested?
DYes 0 No* Was accuracy of system water level readings tested?
DYes 0 No* Were all probes reinstalled properly?
DYes 0 No* Were all items on the equipment manufacturer's maintenance checklist completed? .. *In the Sect1on H, below, descnbe how and when these defiCiencies were or Will be corrected.
G. Line Leak Detectors (LLD): D Check this box if LLDs are not installed.
Complete the following checklist:
~Yes 8 No* For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance? (Check all
N/A that apply) Simulated leak rate: ~3 g.p.h.; Do.1 g.p.h; D 0.2 g.p.h.
bl] Yes i J No* Were all LLDs confirmed operational and accurate within regulatory requirements?
~Yes 0 No* Was the testing apparatus properly calibrated?
U Yes kJ No* For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
N/A
bl] Yes tj No* For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak?
N/A
~Yes 8 No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or
NIA disconnected?
~Yes 8 No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or
N/A fails a test?
~Yes 8 No* For electronic LLDs, have all accessible wiring connections been visually inspected?
N/A
~ Yes UNo* Were all items on the equipment manufacturer's maintenance checklist completed? . . * In the Section H, below, descnbe how and when these def1c1enc1es were or will be corrected .
H. Comments:
Monitoring System Certification Page 3 of4 12/07
environmental services, inc.
<!tiU/'1 lowm~ Centre Drive. fCo1Jlhili Rwu.:h, CA U2610
Leak Detector Test Form
"""
Location Name: Foods Co# 384 Date: 12/5/2013
~~~-~.~ .. ~. --~. ~·~· ~ ... ~-~~~.~~-··~.~. ~.~~.~ .. ~"~" ~ .. ·~~· ·-~· -.~. ~ .. ~~"-~-
Address: 2501 Haley St. Agency: Bakersfield Fire Dept
City, State Bakersfield, CA Inspector:
Line Number: 1 2 3 4
Product: Unleaded Premium Diesel
Manufacturer: Veeder Root Veeder Root Veeder Root
Model#: PLLD PLLD PLLD
Full Operating Pressure (psi): 32 31 32
Line Bleed Back (ml): 120 100 110
Trip Time (sec): N/A N/A N/A
Metering Pressure (psi): N/A N/A N/A
""
FIE Holding Pressure (psi) N/A N/A N/A
""
Test Leak Rate (gph) 3.0 3.0 3.0
Pass/Fall Pass Pass Pass
Comments:
Technician Name
Technician Signature
SWRCB, January 2006
Spill Bucket Testing Report Form
This form is intended for use by contractors performing annual testing of UST spill containment stmctures. The completed form and
printouts from tests (if applicable), should be provided to the facility owner/operator for submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: Foods Co# 384 J Date of Testing: 12/5/2013
Facility Address: 2501 Haley St.
Facility Contact: I Phone: 6618732052
Date Local Agency Was Notified of Testing: 10/15/2013
Name of Local Agency Inspector (if present during testing):
2. TESTING CONTRACTOR INFORMATION
Company Name: Belshire Environmental Services, Inc.
Technician Conducting Test: Jerry Sheer
Credentials 1: ~ CSLB Contractor DICC Service Tech. 0 SWRCB Tank Tester OOther (Specify)
License Number(s): 808313
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: ~Hydrostatic 0Vacuum D Other
Test Equipment Used: Visual Equipment Resolution:
Identify Spill Bucket (By Tank 1 91 F 2 91 v 3 Diesel F 4
Number, Stored Product, etc.)
Bucket Installation Type: Contained in Sump Contained in Sump Contained in Sump
Bucket Diameter: 12" 12" 12"
Bucket Depth: 12" 12" 12"
Wait time between applying 10 min 10 min 10 min vacuum/water and start of test:
Test Start Time (T1): 09:00am 09:00am 09:00am
Initial Reading (R1): 11 11 11
Test End Time (T p): 10:00 am 10:00 am 10:00 am
Final Reading (Rp): 11 11 11
Test Duration (Tp-T1): 60 60 0
Change in Reading (RF-R1): 0.0000 0.0000 0.0000
Pass/Fail Threshold or
Criteria: No Visual Loss No Visual Loss No Visual Loss No Visual Loss
Test Result: ~Pass D Fail ~Pass DFail ~Pass DFail DPass D Fail
Comments -(include infonnation on repairs made prior to testing, and recommended follow-up for failed tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the infonnation contained in this report is true, accurate, and in full compliance with legal requirements.
;/ t'~ l (/;rJ-ilv'--tlt-Date: 12/5/2013
1 State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
SWRCB, January 2006
Spill Bucket Testing Report Form
This form is illtended for use by contractors pe1jorming annual testing of UST spill containment structures. The completed form and
printouts from tests (if applicable), should be provided to the facility owner/operator for submittal to the local regulatOI)' agency.
1. FACILITY INFORMATION
Facility Name: Foods Co# 384 / Date of Testing: 12/5/2013
Facility Address: 2501 Haley St.
Facility Contact: I Phone: 6618732052
Date Local Agency Was Notified of Testing: 10/15/2013
Name of Local Agency Inspector (if present during testing):
2. TESTING CONTRACTOR INFORMATION
Company Name: Belshire Environmental Services, Inc.
Technician Conducting Test: Jerry Sheer
Credentials 1: ~ CSLB Contractor OICC Service Tech. 0 SWRCB Tank Tester OOther (Specify)
License Number(s): 808313
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: ~Hydrostatic OVacuum 0 Other
Test Equipment Used: Visual Equipment Resolution:
Identify Spill Bucket (By Tank 1 87 MF1 2 87 MV 1 3 87 MF2 4 87 MV2 Number, Stored Product, etc.)
Bucket Installation Type: Contained in Sump Contained in Sump Contained in Sump Contained in Sump
Bucket Diameter: 12" 12" 12" 12"
Bucket Depth: 12" 12" 12" 12"
Wait time between applying 10 min 10 min 10 min 10 min vacuum/water and start of test:
Test Start Time (T1): 09:00am 09:00am 09:00am 09:00am
Initial Reading (R1): 11 11 11 11
Test End Time (T p): 10:00 am 10:00 am 10:00 am 10:00 am
Final Reading (Rp): 11 11 11 11
Test Duration (TF-T1): 60 60 60 60
01ange in Reading (RF-R1): 0.0000 0.0000 0.0000 0.0000
Pass/Fail Threshold or No Visual Loss No Visual Loss No Visual Loss No Visual Loss Criteria:
Test Result: ~Pass 0 Fail ~Pass 0Fail ~Pass OF ail ~Pass 0 Fail
Comments -(include infonnation on repairs made prior to testing, and recommended follow-up for failed tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the infonnation contained in this report is true, accurate, and in full compliance with legal requirements.
/ ' ti ,-IJ\\ !~ IIJt)· 'lu'-1 ~,(-Technician's Signature:. _ f/.---------~.7~----~~------------------
/
Date: 12/5/2013
1 State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
Monitoring System Certification Form: Addendum for Vacuum/Pressure Interstitial Sensors LG 163-l, Enc. II
I. Results of Vacuum/Pressure Monitoring Equipment Testing
This page should be used to document testing and servicing of vacuum and pressure interstitial sensors. A copy of
this form must be included with the Monitoring System Certification Form, which must be provided to the tank
system owner/operator. The owner/operator must submit a copy of the Monitoring System Certification Form to the
local agency regulating UST systems within 30 days of test date.
Sensor ID
89
Component(s) Monitored by this Sensor: 87 Product ---------------------------------------------------11
Sensor Functionality Test Result: [K] Pass; D Fail Interstitial Communication Test Result: [K] Pass; D Fail
810
Interstitial Communication Test Result: [ill Pass; D Fail
Component(s) Monitored by this Sensor: 87-91
----~--------------------------------------------_,1
Sensor Functionality Test Result: [ill Pass; D Fail
811
Interstitial Communication Test Result: D Pass; lli] Fail
Component(s) Monitored by this Sensor: 87 Ventr .
--------------------------------------------------~
Sensor Test Result: [ill Pass; D Fail.
Interstitial Communication Test Result: [K] Pass; D Fail 812
Component(s) Monitored by this Sensor: 91 Product
--------------------------------------------------~
Sensor Functionali Test Result: [K] Pass; D Fail
Interstitial Communication Test Result: [ill Pass; D Fail
813
Component(s) Monitored by this Sensor: 91 Vent
--------------------------------------------------~
Sensor Functionali Test Result: D Pass; [X] Fail
Component(s) Monitored by this Sensor: Diesel Product --------------------------------------------------~ Sensor Functional Test Result: [ill Pass; D Fail Interstitial Communication Test Result: [ill Pass; D Fail 814
Interstitial Communication Test Result: IX] Pass; D Fail 817
Component(s) Monitored by this Sensor: Diesel Vent ---------------------------------------------------i
Sensor Functionality Test Result: IX] Pass; D Fail
Component(s) Monitored by this Sensor: ---------------------------------------------------1
Sensor Functionality Test Result: D Pass; D Fail Interstitial Communication Test Result: D Pass; D Fail
Component(s) Monitored by this Sensor: ---------------------------------------------------1
Sensor Functionality Test Result: D Pass; D Fail Interstitial Communication Test Result: D Pass; D Fail
Component(s) Monitored by this Sensor: ---------------------------------------------------1
Sensor Functional Test Result: D Pass; D Fail Interstitial Communication Test Result: D Pass; D Fail
How was interstitial communication verified?
[X] Leak Introduced at Far End of Interstitial D Visual
Vacuum was restored to operating levels in all interstitial spaces: DYes [XI No (If no, describe in Sec. J, below)
J. Comments:
811 in no vac alarm
813 No High liquid alarm
BUSINESS NAME: FOODSCO FUEL CENTER #384
SITE ADDRESS: 2501 HALEY STREET
MAP DATE: 3/22/13
10,000
DIESEL
8,000
PREMIUM
1-w w 0:: lii
> w ...J < X
0
N
I SURVEYED BY: FB
Driveway
I CITY: BAKERSFIELD
I DRAWN BY: GK
----~ ..... ~
I
•
HEIGHT STREET
I ZIP: 93305
I FACILITY ID#:
PARKING LOT
,
0 0 c (/) n 0
!!I 0 ;:o m
**NOTE: ALL PIPING LOCATIONS ARE ESTIMATED & SCALING IS APPROXIMATE**
~ CARBON ~ CANNISTER -U DISPENSER
VENT RISER
VENT BOX
PRODUCT
PIPING
VAPOR
RETURN/
VENT LINE
•
A
F
T
MONITORING
PANEL
ANNULAR
SENSOR
FILL SUMP
SENSOR
TURBINE SUMP
SENSOR
VEEDER ROOT L LINE LEAK VEEDER ROOT
TLS-350R DETECTOR PLLD (8484)
VEEDER ROOT' VEEDER ROOT
794380-303 u UDC SENSOR 794380-323 (SUMP)
794380-304 (INTERSTITIAL)
VEEDER ROOT VENT BOX VEEDER ROOT
794380-323 (SUMP) v SENSOR 794380-323 (SUMP)
794380-304 (INTERSTITIAL) 794380-304 (INTERSTITIAL)
VEEDER ROOT ALL SENSORS SET FOR POSITIVE 794380-323 (SUMP) SHUTDOWN. 794380-304 (INTERSTITIAL)
Be 1 shire TLS Po 11 er DO command set ver 5. 7 Started at 12/5/2013 3:28:26 PM
I10200 DEC 5, 2013 3:27 PM
FOODS CO • 3 84 2505 HALEY BAKERSFIELD CA, 661-873-9343
SYSTEM CONFIGURATION
SL~T
2 ~ ~ 7 8
16 11 12 13 14 15 16
BOARD TYPE 4 PROBE / G.T. PLLD SENSOR BD INTERSTITIAL BD INTERSTITIAL BD INTERSTITIAL BD 8SMARTSENSOR BD 7SMARTSENSOR BD 8SMARTSENSOR BD ~~~go pij~~R Bg~RD
UNUSED UNUSED UNUSED UNUSED UNUSED UNUSED COMM 1 ELEC DISP INT, CO~IM 2 SERIAL SAT BD
COMM 3 UNUSED COMM 4 UNUSED COMM 5 RS485 SERIAL BD COMM 6 RS232 SERIAL BD
I20600 DEC 5, 2013 3: 27 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
TANK ALARM HISTORY
TANK 1 UN1
OVERFILL ALARM
LOW PRODUCT ALARM
SUDDEN LOSS ALARM
HIGH PRODUCT ALARM
INVALID FUEL LEVEL
PROBE OUT
DELIVERY NEEDED
LOW TEMP WARNING
TANK PR1
OVERFILL ALARM
LOW PRODUCT ALARM
SUDDEN LOSS ALARM
HIGH PRODUCT ALARM
INVALID FUEL LEVEL
PROBE OUT
HIGH WATER WARNING
DELIVERY NEEDED
LOW TEMP WARNING
TANK 3 DIESEL
OVERFILL ALARM
LOW PRODUCT ALARM
SUDDEN LOSS ALARM
HIGH PRODUCT ALARM
INVALID FUEL LEVEL
PROBE OUT
DELIVERY NEEDED
MAX PRODUCT ALARM
LOW TEMP WARNING
!30200
DEC 5, 2013 3:27 PM
FOODS CO. 384
POWI~4g~lESET
3919 202970 203082 203127 39544
514845
9949365 9928 102072 9852763 mm~ 9823814 9765830 9mm 9786178 9767641 9753587 68839 15029
DEC 5 , 2013 10: 44 AM NOV 12, 2013 11:39 AM OCT 31, 2013 1:57 AM
DEC 15, 2010 3:26 PM
DEC 5 , 2013 10: 39 AM g~§ g: ~m 1U~ ::
DEC 6 2011 11:46 AM ~5t 28: ~8H 1U8 ~
DEC 15, 2010 2: 55 PM
DEC 5, 2013 10:47 AM DEC 5, 2013 10:39 AM DEC 6, 2012 2:49 PM
~~r 2/i' ~8B U8 :~ APR 23: 2013 7:02 PM
DEC DEC DEC
DEC DEC DEC
~: ~8H 1~:~6 ~ 6, 201111:53 AM
~: ~m 1u~ ~
6, 2011 11:29 AM
2:35 PM 3:26 PM
DEC 6 2012 2:35 PM m 2~: ~8i6 l:U~ ~
DEC 6, 2011 11:29 AM
m ~: DEC 15,
g~§ ~:
DEC 6,
DEC 27,
DEC 5, OCT 17, JUL 14,
2013 10:35 AM 2011 11; 31 AM
2010 2:55 PM
2013 10:37 AM 2013 10: 34 AM 2012 2:41 PM
2010 1:01 PM
2013 10: 34 AM 2013 4:47 PM 2013 9:40 PM
DEC DEC DEC
~: ~8H 1~:H ~
6, 2011 11:31 AM
DEC DEC
g~§ 1~: ~m 1U~ ~
NOV12,2013 8:33AM DEC 6, 2012 2:19 PM DEC 29, 2010 12:43 PM
DEC
DEC
DEC DEC DEC
DEC DEC DEC
DEC DEC DEC
2~:
1~:
2011 11:58 AM 2010 1:31 PM
2013 10:32 AM 2012 2:25 PM 2010 2:55 PM
~: ~8H i8:H ~ 6, 2012 2:25PM
~: ~8B iU~ ~ 6, 2012 2:26 PM
DEC 27, 2010 1:31 PM
DEC 27, 2010 1:33 PM
CURRENT
163590 3930 201773 201888 201819
39448 510153 39514 9936 101934 8459622
8456970 8457956 8453682 8446209 8440533
101216 487065 8452740 84um
Page 1
2505 HALEY BAKERSFIELD CA, 661-873-9343
LIQUID ALARM HISTORY REPORT
!30700 DEC 5, 2013 3:27 PM
I31600 DEC 5 , 2013 3: 2 7 PM
FOODS CO. 384
2505 HALEY BAKERSFIELD CA. 661-873-9343
SMART SENSOR ALARM HISTORY REPORT
LOW LIQUID ALARM SENSOR OUT ALARM FUEL ALARM
LOW LIQUID ALARM SENSOR OUT ALARM FUEL ALARM
LOW LIQUID ALARM SENSOR OUT ALARM FUEL ALARM
LO\~ LIQUID ALARM SENSOR OUT ALARM FUEL ALARM
LOW LIQUID ALARM FUEL ALARM SENSOR OUT ALARM
LOW LIQUID ALARM SENSOR OUT ALARM FUEL ALARM
LOW LIQUID ALARM FUEL ALARM SENSOR OUT ALARM
SENSOR OUT ALARM FUEL ALARM
SENSOR OUT ALARM
SENSOR OUT ALARM FUEL ALARM FUEL ALARM
SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM
SENSOR OUT ALARM FUEL ALARM FUEL ALARM
SENSOR OUT ALARM HIGH LIQUID ALARM
LOW LIQUID ALARM
SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM
SENSOR OUT ALARM FUEL ALARM FUEL ALARM
SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM
SENSOR OUT ALARM
FUEL ALARM FUEL ALARM
SENSOR OUT ALARM ~ij~H L\:~S~BD At~~~M
SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM
SENSOR OUT ALARM
FUEL ALARM FUEL ALARM
SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM
SENSOR OUT ALARM FUEL ALARM FUEL ALARM
SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM
SENSOR OUT ALARM FUEL ALARM FUEL ALARM
COMMUNICATION ALARM
COMMUNICATION ALARM
COMMUNICATION ALARM
COMMUNICATION ALARM
COMMUNICATION ALARM
COMMUNICATION ALARM
COMMUNICATION ALARM COMMUNICATION ALARM
NO VACUUM ALARM HIGH LIQUID ALARM NO VACUUM ALARM
HIGH LIQUID ALARM NO VACUUM ALARM NO VACUUM ALARM
HIGH LIQUID ALARM HIGH LIQUID ALARM NO VACUUM ALARM
~6GMIJS~I~L~~~RM
NO VACUUM ALARM
DEC 5 , 2013 10: 03 AM NO VACUUM ALARM DEC 5, 2013 9:58AM NO VACUUM ALARM
14
DEC 6, 2012 10:53 AM HIGH LIQUID ALARM
DIESEL PRODUCT m ~: ~m 18:8~ AM NO VACUUM ALARM AM HIGH LIQUID ALARM DEC 6, 2012 11:05 AM HIGH LIQUID ALARM
15 PMC CANISTER
8:48 AM SENSOR FAULT ALARM JAN 24, 2013 MAR 17, 2012 9:07 AM SENSOR FAULT ALARM JAN 23, 2012 6:09 16 ATM P 17 DIESEL VENT
DEC ~: ~8H 18:8~ DEC 6, 2012 11:05 DEC
I32300 DEC 5' 2013 3:27 PM
I34200 DEC 5' 2013 3:27 PM
I34700 DEC 5, 2013 3:27 PM
I34C00 DEC 5' 2013 3:27 PM
I20700 DEC 5' 2013 3:27 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
TANK LEAK TEST HISTORY
T 1:UN1
LAST GROSS TEST PASSED:
NO TEST PASSED
LAST ANNUAL TEST PASSED:
NO TEST PASSED
FULLEST ANNUAL TEST PASS
NO TEST PASSED
LAST PERIODIC TEST PASS:
NO TEST PASSED
FULLEST PERIODIC TEST PASSED EACH MONTH:
TEST START TIME
TANK LEAK TEST HISTORY
T 2: PR1
LAST GROSS TEST PASSED:
NO TEST PASSED
LAST ANNUAL TEST PASSED:
NO TEST PASSED
FULLEST ANNUAL TEST PASS
NO TEST PASSED
LAST PERIODIC TEST PASS:
NO TEST PASSED
FULLEST PERIODIC TEST
PASSED EACH MONTH:
TEST START TIME
TANK LEAK TEST HISTORY
T 3 :DIESEL
LAST GROSS TEST PASSED:
NO TEST PASSED
LAST ANNUAL TEST PASSED:
NO TEST PASSED
FULLEST ANNUAL TEST PASS
NO TEST PASSED
LAST PERIODIC TEST PASS:
NO TEST PASSED
FULLEST PERIODIC TEST PASSED EACH MONTH:
TEST START TIME
I31200 DEC 5, 2013 3:27 PM
I38200 DEC 5, 2013 3:27 PM
FOODS CO. 384
2505 HALEY BAKERSFIELD CA. 661-873-9343
PM SENSOR FAULT ALARM
AM NO VACUUM ALARM AM HIGH LIQUID ALARM AM HIGH LIQUID ALARM
HOURS VOLUME % VOLUME
HOURS VOLUME % VOLUME
HOURS VOLUME % VOLUME
PRESSURE LINE LEAK ALARM HISTORY REPORT
Q 1:87 UNLEADED DEC 5, 2013 10:52 AM DEC 5, 2013 10: 20 AM DEC 5, 2013 9:56AM
GROSS LINE FAIL PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM
TEST TYPE
TEST TYPE
TEST TYPE
Page 2
DEC ~: 2013 9 55 AM DEC 2013 9 52 AM DEC ~: 2013 9 49 AM DEC 2013 9 49 AM
DEC ~: 2013 9:48AM DEC 2013 9:45 AM DEC 5' 2013 9:45 AM
Q 2:91 UNLEADED DEC 5, 2013 10: 54 AM DEC 5, 2013 10:54 AM DEC 5, 2013 10:20 AM DEC 5, 2013 10:02 AM DEC 5, 2013 9: 56 AM
DEC 5' 2013 9:49 AM DEC 5' 2013 9:49 AM DEC ~: 2013 9:48 AM DEC 2013 9:45 AM DEC 5' 2013 9:45 AM
Q 3: DIESEL DEC 5' 2013 10:43 AM DEC 5' 2013 10:43 AM DEC ~: 2013 10:32 AM DEC 2013 10: 20 AM DEC 5' 2013 10: 06 AM
DEC ~: 2013 9:49 AM DEC 2013 9:49AM DEC 5' 2013 9:48 AM DEC 5' 2013 9:45 AM DEC 5' 2013 9:45 AM
I38700 DEC 5' 2013 3:27 PM
I40200
DEC 5' 2013 3:27 PM
FOODS CO . 3 84
2505 HALEY
BAKERSFIELD CA. 661-873-9343
INPUT LOCATION
1 EMERGENCY SHUT OFF
PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM GROSS LINE FAIL
PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM GROSS LINE FAIL PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM
~~~ 2~: ~8H llH ~ AUG22,2013 9:50AM
EXTERN INPUT ALARM EXTERN INPUT ALARM EXTERN INPUT ALARM
m 2~: ~8H 1U~ ~ AUG 22, 2013 9:50 AM
I20300 DEC 5, 2013 3: 2 7 PM
FOODS CO. 384
2505 HALEY BAKERSFIELD CA. 661-873-9343
TANK 1 UN1 TEST STATUS: OFF
LEAK DATA NOT AVAILABLE ON THIS TANK
TANK 2 PR1
TEST STATUS: OFF LEAK OATA NOT AVAILABLE ON THIS TANK
TANK 3 DIESEL TEST STATUS: OFF LEAK DATA NOT AVAILABLE ON THIS TANK
I25100 DEC 5, 2013 3: 27 PM
FOODS CO. 384
2505 HALEY BAKERSFIELD CA. 661-873-9343
CSLD TEST RESULTS TANK PRODUCT
200 FOODS CO . 3 84 2505 HALEY BAKERSFIELD CA. 661-873-9343
DEC 5' 2013 3:27
TANK PRODUCT
1 UN1 2 PR1 3 DIESEL
210
FOODS CO • 3 84
2505 HALEY BAKERSFIELD CA. 661-873-9343
TANK 1 UN1
PM
TEST STATUS: OFF
RESULT
GALLONS
12642 3514 1971
LEAK DATA NOT AVAILABLE ON THIS TANK
TANK 2 PR1 TEST STATUS: OFF
LEAK DATA NOT AVAILABLE ON THIS TANK
TANK 3 DIESEL
TEST STATUS: OFF LEAK DATA NOT AVAILABLE ON THIS TANK
I21300 DEC 5, 2013 3:27 PM
FOODS CO. 384
EXTERN INPUT NORMAL EXTERN INPUT NORMAL EXTERN INPUT NORMAL
INCHES
71.84 53.86 30.40
WATER DEG F
0.0 64.2
0.0 68.7 0.0 72.7
ULLAGE
7140
4387 8449
2505 HALEY BAKERSFIELD CA. 661-873-9343
DELIVERY REPORT
T 1:UN1 INCREASE DATE I TIME HEIGHT
103,09END: DEC 5, 2013 10:51 AM
72 •3~TART: DEC 5, 2013 10:43 AM
AMOUNT:
END: DEC 81.99
START: DEC 44.82 AMOUNT:
END: DEC 84.85
START: DEC 47.59 AMOUNT:
END: DEC 84.66
4, 2013 5:57PM
4, 2013 5:38 PM
3, 2013 2:07PM
3, 2013 1:46 PM
2, 2013 2: 44 PM
42 • 95TART: DEC 2, 2013 2:23 PM
AMOUNT:
94.89 END: DEC 1, 2013 1:24 AM
51.6lTART: DEC 1, 2013 1:04AM
AMOUNT:
83 .57 END: NOV 30, 2013 2:42AM
55 .1~TART: NOV 30, 2013 2:24 AM
AMOUNT:
91.58 END: NOV 29, 2013 2:46 AM
53 • 6~TART: NOV 29, 2013 2:16 AM
AMOUNT:
95 .61 END: NOV 27, 2013 4:37 PM
57 •2~TART: NOV 27, 2013 4:16PM
AMOUNT:
BB.OB END: NOV 27, 2013 12:24 AM
46 •2~TART: NOV 26, 2013 11:50 PM
AMOUNT:
73 .97 END: NOV 26, 2013 11:16 AM
46 .5~TART: NOV 26, 2013 10:54 AM
AMOUNT:
T 2:PR1 INCREASE DATE I TIME HEIGHT
104• 97END: DEC 5, 2013 10:44 AM
ZO. 5lTART: DEC 5, 2013 10:34 AM
AMOUNT:
END: DEC 56.33
START: DEC 44.32 AMOUNT:
4, 2013 6:03 P~l
4, 2013 5:53PM
55 .49 END: DEC 3, 2013 2:11PM
43 • 3~TART: DEC 3, 2013 2:02 PM
AMOUNT:
76 .76 END: NOV 30, 2013 2:36AM
42 • B~TART: NOV 30, 2013 2:22 AM
AMOUNT:
52.53 END: NOV 29, 2013 2:21AM
40 • 3~TART: NOV 29, 2013 2:12 AM
AMOUNT:
50.BB END: NOV 27, 2013 4:27 PM
38 .5~TART: NOV 27, 2013 4:18PM
AMOUNT:
52 •50 END: NOV 26, 2013 11:29 AM
40.Z~TART: NOV 26, 2013 11:17 AM
AMOUNT:
END: NOV 24, 2013 12:04 AM
GALLONS TC GALLONS WATER TEMP DEG F
18375
12758
5617
14734
6781
7953
15294
7372
7922
15258
6378
8880
17114
8240
8874
15046
9016
6030
16543
8694
7849
17233
9476
7757
15907
7082
8825
13092
7156
5936
18386 0.85
12775 0.00
5611
14698 0.00
6751 0.00
7947
15234 0. 00
7337 0.00
7897
15195 0.00
6345 0.00
8850
17043 0.00
8201 0.00
8842
14977 0.00
8972 0.00
6005
16471 0.00
8652 0.00
7819
17173 0.00
9455 0.00
7718
15884 0.00
7062 0.00
8822
13062 0. 00
7135 0.00
5927
59.11
58.14
63.44
66.31
65.52
66.59
65.82
67.19
65.87
66.84
66.43
66.97
66.16
66.68
64.93
63.12
62.04
63.98
63.25
64.11
GALLONS TC GALLONS WATER TEMP DEG F
7409
929
7367 0.00
923 0.00
6480 6444
3723
2716
1007
3651
2637
1014
5425
2594
2831
3401
2390
1011
3262
2251
1011
3399
2387
1012
4184
3702 0.00
2697 0.00
1005
3625 0.00
2616 0.00
1009
5403 0.00
2573 0.00
2830
3375 0.00
2371 0.00
1004
3240 0.00
2234 0.00
1006
3379 0.00
2369 0.00
1010
4162 0. 00
67.94
68.37
67.85
70.10
70.11
71.08
65.82
71.08
70.53
71.34
69.74
70.53
67.98
70.72
67.30
Page 3
61.79
39 • 9~TART: NOV 23, 2013 11:54 PM
AMOUNT:
48 •07 END: NOV 23, 2013 4:08 AM
35 •6lTART: NOV 23, 2013 3:58AM
AMOUNT:
48 •40 END: NOV 21, 2013 10:19 PM
35 •9~TART: NOV 21, 2013 10:09 PM
AMOUNT:
T 3:DIESEL ~~i~~~SE DATE I TIME
103. 63END: DEC 5, 2013 10:37 AM
START: DEC 5, 2013 10:28 AM 9.08 AMOUNT:
41•83 END: NOV 26, 2013 11:23 AM
27 •3~TART: NOV 26, 2013 11:13 AM
AMOUNT:
40 .31 END: NOV 16, 2013 3:12 AM
25 .5FART: NOV 16, 2013 3:03AM
AMOUNT:
57 •90 END: OCT 20, 2013 5:27PM
49 • 3~TART: OCT 20, 2013 5:17 PM
AMOUNT:
61.93 END: OCT 9, 2013 7:36 PM
49 .1~TART: OCT 9, 2013 7:25 PM
AMOUNT:
50 •74 END: OCT 8, 2013 12:27 PM
5o.o5TART: OCT 8, 2013 12:18 PM
AMOUNT:
52 •60 END: OCT 5, 2013 6:30PM
43 • B~TART: OCT 5, 2013 6:20 PM
AMOUNT:
48•69 END: SEP 30, 2013 2:14 AM
39 .S~TART: SEP 30, 2013 1:59AM
AMOUNT:
46 .00 END: SEP 23, 2013 11:23 PM
3o.z5TART: SEP 23, 2013 11:13 PM
AMOUNT:
39 . 7 4 END: SEP 16, 2013 2: 44 AM
35 .0~TART: SEP 16, 2013 2:36 AM
AMOUNT:
I31800 DEC 5, 2013 3:27 PM
!37400 DEC 5 , 2013 3: 2 7 PM
FOODS CO. 384
2505 HALEY BAKERSFIELD CA, 661-873-9343
PRESSURE LINE LEAK TEST HISTORY
2364
1820
3027
2017
1010
3054
2348 0.00
1814
3009 0.00
2001 0.00
1008
3033 0.00
2043 2026 0. 00
1011 1007
GALLONS TC GALLONS WATER
9756 9704 0.00
300 298 0.00
9456 9406
3176
1678
1498
3008
1515
1493
5046
4033
1013
5526
4013
1513
4198
4111
87
4417
3406
1011
3959
2955
1004
3648
1952
1696
2945
2441
504
3155 0.00
1668 0.00
1487
2986 0.00
1504 0.00
1482
4996 0.00
3994 0.00
1002
5469 0.00
3969 0.00
1500
4152 0.00
4067 0.00
85
4369 0.00
3371 0.00
998
3921 0.00
2924 0.00
997
3607 0.00
1930 0. 00
1677
2911 0.00
2415 0.00
496
Q 1:87 UNLEADED
LAST 3.0 PASS: DEC 5, 2013 1:47 PM
FIRST 0 .10 PASS EACH MONTH:
FIRST 0. 20 PASS EACH MONTH:
Q 2:91 UNLEADED
LAST 3 . 0 PASS:
FIRST 0 .10 PASS EACH MONTH:
FIRST 0. 20 PASS EACH MONTH:
Q 3 :DIESEL
LAST 3.0 PASS:
DEC 5, 2013 11:01 AM
DEC 5, 2013 11:02 AM
69.43
68.08
70.86
69.75
71.66
TEMP DEG F
71.60
72.74
74.30
73.11
75.77
76.81
81.51
81.24
82.83
84.01
84.04
83.96
83.85
82.73
80.95
83.39
84.64
84.59
85.19
83.35
FIRST 0 .10 PASS EACH MONTH:
FIRST 0. 20 PASS EACH MONTH:
I38400 DEC 5, 2013 3: 2 7 PM
FOODS CO. 384
2505 HALEY BAKERSFIELD CA. 661-873-9343
PRESSURE LINE LEAK TEST HISTORY
Q 1: 8 7 UNLEADED
LAST 3.0 PASS:
FIRST 0 .10 PASS EACH MONTH:
Q 2:91 UNLEADED
LAST 3 . 0 PASS:
FIRST 0 .10 PASS EACH MONTH:
Q 3 :DIESEL
LAST 3.0 PASS:
FIRST 0 .10 PASS EACH MONTH:
!38900 DEC 5, 2013 3:27 PM
Il1100 DEC 5, 2013 3: 2 7 PM
FOODS CO • 3 84
2505 HALEY BAKERSFIELD CA. 661-873-9343
PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION TIME Q 3 OTHER 11:02AM
Q 3 OTHER 11:02AM
Q 2 OTHER ll:OlAM
~l~O£I~ER
~1~o8illER
~o~s~illER
~oMA~ER
Q 1 OTHER 10: 52AM
T 1 TANK 10:49AM
T 1 TANK 10:47AM
T 1 TANK 10:47AM
T 1 TANK 10:44AM
T 1 TANK 10:44AM
~0~4~,illER
Q 3 OTHER
10:43AM
T 1 TANK 10:42AM
T 1 TANK 10:39AM
T 1 TANK 10: 39AM
T 2 TANK 10: 38AM
T 2 TANK
10:37AM
T 2 TANK 10:37AM
T 2 TANK
10: 36AM
T 2 TANK 10: 35AM
T 2 TANK 10:34AM
~oM,illER
T 3 TANK 10: 32AM
T 3 TANK 10:32AM
Q 3 OTHER 10:32AM
T 3 TANK 10: 32AM
T 3 TANK 10:31AM
DIESEL
DIESEL
91 UNLEADED
91 UNLEADED
87 UNLEADED
91 UNLEADED
91 UNLEADED
87 UNLEADED
UNl
UN1
UNl
UNl
UNl
DIESEL
DIESEL
UNl
UN1
UNl
PRl
PRl
PRl
PRl
PRl
PRl
DIESEL
DIESEL
DIESEL
DIESEL
DIESEL
DIESEL
DEC 5, 2013 1:47 PM
DEC 5, 2013 11:01 AM
DEC 5, 2013 11:02 AM
ALARM TYPE STATE
PLLD SHUTDOWN ALARM CLEAR
DATE
12-05-13
12-05-13 GROSS LINE FAIL CLEAR
PLLD SHUTDOWN ALARM CLEAR 12-05-13
GROSS LINE FAIL CLEAR 12-05-13
GROSS LINE FAIL CLEAR 12-05-13
PLLD SHUTDOWN ALARM ALARM 12-05-13
GROSS LINE FAIL ALARM 12-05-13
GROSS LINE FAIL ALARM 12-05-13
PROBE OUT CLEAR 12-05-13
OVERFILL ALARM CLEAR 12-05-13
PROBE OUT ALARM 12-05-13
OVERFILL ALARM ALARM 12-05-13
SUDDEN LOSS ALARM CLEAR 12-05-13
PLLD SHUTDOWN ALARM ALARM 12-05-13
GROSS LINE FAIL ALARM 12-05-13
PROBE OUT CLEAR 12-05-13
PROBE OUT ALARM 12-05-13
SUDDEN LOSS ALARM ALARM 12-05-13
PROBE OUT CLEAR 12-05-13
OVERFILL ALARM CLEAR 12-05-13
PROBE OUT ALARM 12-05-13
OVERFILL ALARM ALARM 12-05-13
PROBE OUT CLEAR 12-05-13
PROBE OUT ALARM 12-05-13
PLLD SHUTDOWN ALARM CLEAR 12-05-13
LOW PRODUCT ALARM CLEAR 12-05-13
LOW PRODUCT ALARM ALARM 12-05-13
PLLD SHUTDOWN ALARM ALARM 12-05-13
PROBE OUT CLEAR 12-05-13
OVERFILL ALARM CLEAR 12-05-13
Page 4
T 3 TANK
10:3WI
DIESEL PROBE OUT ALARM 12-05-13
T 3 TANK 10:30AM DIESEL OVERFILL ALARM ALARM 12-05-13
T 3 TANK
10:29AM
DIESEL PROBE OUT CLEAR 12-05-13
T 3 TANK 10: 28AM
DIESEL PROBE OUT ALARM 12-05-13
I 1 INPUT 10:24AM EMERGENCY SHUT OFF EXTERN INPUT ALARM CLEAR 12-05-13
I 1 INPUT
10:22AM
EMERGENCY SHUT OFF EXTERN INPUT ALARM ALARM 12-05-13
Q 2 OTHER 10: 22AM
L16 PIPE 10:22AM
Ll5 PIPE 10:22AM
91 UNLEADED
91 FILL BRINE
91 FILL
Ll4 STP SUMP 91 TURBINE BRINE 10:21AM
L13 STP SUMP 91 TURBINE
10:2WI
Ll2 ANNULAR 87 ANNULAR 10:21AM
~0~2~ER
L11 PIPE 10: 21AM
LlO PIPE 10:21AM
87 UNLEADED
87 FILL BRINE
87 FILL
L 9 STP SUMP 87 TURBINE BRINE 10:21AM ~0~2~ER
L23 PIPE 10:21AM
L22 PIPE 10:21AM
DIESEL
VENT SUMP BRINE
VENT SUMP
L21 PIPE DIESEL FILL BRINE 10:21AM
I11200 DEC 5, 2013 3:27 PM
FOODS CO. 384
2505 HALEY BAKERSFIELD CA. 661-873-9343
NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION TIME T 1 TANK UNl 10:51AM T 1 TANK UNl
10:49AI>I
T 2 TANK 10:41AM
T 2 TANK
10:38AM
T 2 TANK 10:35AM
T 2 TANK 10: 35AI>I
T 2 TANK 10:35AM
T 2 TANK 10:34AM
T 3 TANK 10:32AM
T 3 TANK 10:32AM
T 3 TANK 10:32AM
T 3 TANK 10:32AM T 3 TANK 10:29AM
T 3 TANK 10:28AM
SYSTEM 8: SOAM
SYSTEM 8:50AM
SYSTEM 8:50AM
SYSTEM 8: SOAM
SYSTEM 8:48AM
SYSTEM 8:48AM
SYSTEM 8:47AM
SYSTEM 8:47AM
OTHER 10: 53AM
OTHER 8:01AM
SYSTEM 10:43AM
SYSTEM
10:43AM
PR1
PR1
PRl
PR1
PR1
PRl
DIESEL
DIESEL
DIESEL
DIESEL
DIESEL
DIESEL
PLLD SHUTDOWN ALARM CLEAR 12-05-13
SENSOR OUT ALARM CLEAR 12-05-13
SENSOR OUT ALARM CLEAR 12-05-13
SENSOR OUT ALARM CLEAR 12-05-13
SENSOR OUT ALARM CLEAR 12-05-13
SENSOR OUT ALARM CLEAR 12-05-13
PLLD SHUTDOWN ALARM CLEAR 12-05-13
SENSOR OUT ALARM CLEAR 12-05-13
SENSOR OUT ALARM CLEAR 12-05-13
SENSOR OUT ALARM CLEAR
PLLD SHUTDOWN ALARM CLEAR
12-05-13
12-05-13
SENSOR OUT ALARM
SENSOR OUT ALARM
SENSOR OUT ALARM
ALARM TYPE
LOW TEMP WARNING
LOW TEMP WARNING
CLEAR 12-05-13
CLEAR 12-05-13
CLEAR 12-05-13
STATE DATE
CLEAR 12-05-13
ALARM 12-05-13
LOW TEMP WARNING CLEAR 12-05-13
LOW TEMP WARNING ALARM 12-05-13
DELIVERY NEEDED CLEAR 12-05-13
INVALID FUEL LEVEL CLEAR 12-05-13
INVALID FUEL LEVEL ALARM 12-05-13
DELIVERY NEEDED ALARM 12-05-13
DELIVERY NEEDED CLEAR 12-05-13
DELIVERY NEEDED ALARM 12-05-13
INVALID FUEL LEVEL CLEAR 12-05-13
INVALID FUEL LEVEL ALARM 12-05-13
DELIVERY NEEDED CLEAR 12-05-13
DELIVERY NEEDED ALARM 12-05-13
PRINTER ERROR CLEAR 12-05-13
PAPER OUT CLEAR 12-05-13
PRINTER ERROR ALARM 12-05-13
PAPER OUT ALARM 12-05-13
PRINTER ERROR CLEAR 12-05-13
PAPER OUT CLEAR 12-05-13
PAPER OUT ALARM 12-05-13
PRINTER ERROR ALARM 12-05-13
ISO VAPOR LEAK WARN CLEAR 11-12-13
ISO VAPOR LEAK WARN ALARM 11-10-13
PRINTER ERROR CLEAR 10-30-13
PAPER OUT CLEAR 10-30-13
SYSTEM 10:41AM
SYSTEM 10:41AM
SYSTEM 10:41AM
SYSTEM 10:41AM
SYSTEM 10:41AM
SYSTEM 10:41AM
SYSTEM
10:41AM
SYSTEM 10:41AM
SYSTEM 10:41AM
SYSTEM 10:41AM
SYSTEM 10:41AM
SYSTEM
10:41AM
SYSTEM 10:40AM
SYSTEM
10:40AM
SYSTEM 10:40AM
SYSTEM
10:40AM
SYSTEM 10:40AM
SYSTEM 10:40AM
SYSTEM 10:40AM
SYSTEM 10:40AM
SYSTEM 10:37AM
SYSTEM 10:37AM
SYSTEM 10:37AM
SYSTEM 10:37AM
Il1400 DEC 5, 2013 3: 2 7 PM
FOODS CO . 3 84
2505 HALEY BAKERSFIELD CA. 661-873-9343
CLEARED ALARMS REPORT
ID CATEGORY DESCRIPTION TIME £17o2r~ER DIESEL
£17 o~.lJ1ER DIESEL
£1~0~r~ER 91 UNLEADED
£1~0~ER 91 UNLEADED
£1fo8.lJ1ER 87 UNLEADED
T 1 TANK 10:49AM
T 1 TANK 10:47AM
T 1 TANK 10:44AM
T 1 TANK 10:42AM
T 2 TANK 10:38AM
T 2 TANK 10:37AM
T 2 TANK 10:35AM
£o73~.lJ1ER
UN1
UN1
UN1
UN1
PR1
PR1
PR1
DIESEL
PRINTER ERROR ALARM 10-30-13
PAPER OUT ALARM 10-30-13
PRINTER ERROR CLEAR 10-30-13
PAPER OUT CLEAR 10-30-13
PRINTER ERROR ALARM 10-30-13
PAPER OUT ALARM 10-30-13
PRINTER ERROR CLEAR 10-30-13
PAPER OUT CLEAR 10-30-13
PRINTER ERROR ALARM 10-30-13
PAPER OUT ALARM 10-30-13
PRINTER ERROR CLEAR 10-30-13
PAPER OUT CLEAR 10-30-13
PRINTER ERROR ALARM 10-30-13
PAPER OUT ALARM 10-30-13
PRINTER ERROR CLEAR 10-30-13
PAPER OUT CLEAR 10-30-13
PRINTER ERROR ALARM 10-30-13
PAPER OUT ALARM 10-30-13
PRINTER ERROR CLEAR 10-30-13
PAPER OUT CLEAR 10-30-13
PRINTER ERROR ALARM 10-30-13
PAPER OUT ALARM 10-30-13
PRINTER ERROR CLEAR 10-30-13
PAPER OUT CLEAR 10-30-13
ALARM TYPE STATE
PLLD SHUTDOWN ALARM CLEAR
DATE
12-05-13
12-05-13 GROSS LINE FAIL CLEAR
PLLD SHUTDOWN ALARM CLEAR 12-05-13
GROSS LINE FAIL CLEAR 12-05-13
GROSS LINE FAIL CLEAR 12-05-13
PROBE OUT CLEAR 12-05-13
OVERFILL ALARM CLEAR 12-05-13
SUDDEN LOSS ALARM CLEAR 12-05-13
PROBE OUT CLEAR 12-05-13
PROBE OUT CLEAR 12-05-13
OVERFILL ALARM CLEAR 12-05-13
PROBE OUT CLEAR 12-05-13
PLLD SHUTDOWN ALARM CLEAR 12-05-13
T 3 TANK 10:32AM
DIESEL LOW PRODUCT ALARM CLEAR 12-05-13
T 3 TANK 10:32AM
T 3 TANK 10:31AM
T 3 TANK 10:29AM
I 1 INPUT 10:24AM
£o~2~.lJ1ER
Ll6 PIPE 10:22AM
Ll5 PIPE 10:22AM
DIESEL PROBE OUT CLEAR 12-05-13
DIESEL OVERFILL ALARM CLEAR 12-05-13
DIESEL PROBE OUT CLEAR 12-05-13
EMERGENCY SHUT OFF EXTERN INPUT ALARM CLEAR 12-05-13
91 UNLEADED PLLD SHUTDOWN ALARM CLEAR 12-05-13
91 FILL BRINE SENSOR OUT ALARM CLEAR 12-05-13
91 FILL SENSOR OUT ALARM CLEAR 12-05-13
Page 5
Idt2ru SUMP 91 TURBINE BRINE
Id72ru SUMP 91 TURBINE
L12 ANNULAR 87 ANNULAR 10:21AM
£of2~ER
Lll PIPE 10:21AM
LlO PIPE 10:21AM
87 UNLEADED
87 FILL BRINE
87 FILL
L 9 STP SUMP 87 TURBINE BRINE
10:21AM
£o7z£.lJ1ER
L23 PIPE 10:21AM
L22 PIPE 10:21AM
L21 PIPE 10:21.AM
T 1 TANK 10:51AM
T 2 TANK 10:41AM
T 2 TANK 10: 35AM
T 2 TANK 10: 35AM
T 3 TANK 10: 32AM
T 3 TANK 10:32AI>I
T 3 TANK 10: 29AM
SYSTEM 8:50AM
SYSTEM
8:50AM
SYSTEM 8:48AM
SYSTEM 8:48AM
OTHER 10:53AM
SYSTEM 10:43AM
SYSTEM
10:43AM
SYSTEM 10:41AM
SYSTEM 10:41AM
SYSTEM 10:41AM
SYSTEM 10:41AM
SYSTEM 10:41AM
SYSTEM 10:41AM
SYSTEM 10:40AM
SYSTEM 10:40AM
SYSTEM 10:40AM
SYSTEM 10:40AM
SYSTEM 10:37AM
SYSTEM 10: 37AM
9999FF1B
DIESEL
VENT SUMP BRINE
VENT SUMP
DIESEL FILL BRINE
UN1
PR1
PR1
PR1
DIESEL
DIESEL
DIESEL
SENSOR OUT ALARM CLEAR 12-05-13
SENSOR OUT ALARM CLEAR 12-05-13
SENSOR OUT ALARM CLEAR 12-05-13
PLLD SHUTDOWN ALARM CLEAR 12-05-13
SENSOR OUT ALARM CLEAR 12-05-13
SENSOR OUT ALARM CLEAR 12-05-13
SENSOR OUT ALARM CLEAR 12-05-13
PLLD SHUTDOWN ALARM CLEAR 12-05-13
SENSOR OUT ALARM CLEAR 12-05-13
SENSOR OUT ALARM CLEAR 12-05-13
SENSOR OUT ALARM CLEAR 12-05-13
LOW THIP WARNING CLEAR 12-05-13
LOW TEMP WARNING CLEAR 12-05-13
DELIVERY NEEDED CLEAR 12-05-13
INVALID FUEL LEVEL CLEAR 12-05-13
DELIVERY NEEDED CLEAR 12-05-13
INVALID FUEL LEVEL CLEAR 12-05-13
DELIVERY NEEDED CLEAR 12-05-13
PRINTER ERROR CLEAR 12-05-13
PAPER OUT CLEAR 12-05-13
PRINTER ERROR CLEAR 12-05-13
PAPER OUT CLEAR 12-05-13
ISO VAPOR LEAK WARN CLEAR 11-12-13
PRINTER ERROR CLEAR 10-30-13
PAPER OUT CLEAR 10-30-13
PRINTER ERROR CLEAR 10-30-13
PAPER OUT CLEAR 10-30-13
PRINTER ERROR CLEAR 10-30-13
PAPER OUT CLEAR 10-30-13
PRINTER ERROR CLEAR 10-30-13
PAPER OUT CLEAR 10-30-13
PRINTER ERROR CLEAR 10-30-13
PAPER OUT CLEAR 10-30-13
PRINTER ERROR CLEAR 10-30-13
PAPER OUT CLEAR 10-30-13
PRINTER ERROR CLEAR 10-30-13
PAPER OUT CLEAR 10-30-13
~~H~~~ep~LS Paller SYSTEM_SETUP command set ver 5. 7 Started at 12/5/2013
I10200 DEC 5, 2013 3:22 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
SYSTEM CONFIGURATION
SLOT 1 2
BOARD TYPE
~ 5 6 7 ~ 10 11 12 13
4 PROBE / G.T. PLLD SENSOR BD INTERSTITIAL BD INTERSTITIAL BD INTERSTITIAL BD 8SMARTSENSOR BD 7SMARTSENSOR BD 8SMARTSENSOR BD COMBO I/O BOARD PLLD POWER BD UNUSED UNUSED UNUSED H UNUSED UNUSED 16 UNUSED COMM 1 ELEC DISP INT. COMM 2 SERIAL SAT BD
COMM 3 UNUSED COMM 4 UNUSED COMM 5 RS485 SERIAL BD COMM 6 RS232 SERIAL BD
I10100 DEC 5, 2013 3:22 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
SYSTEM STATUS REPORT
s11: NO VACUUM ALARM
I11100 DEC 5, 2013 3: 22 PM
FOODS CO. 384
2505 HALEY BAKERSFIELD CA. 661-873-9343
PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION TIME Q 3 OTHER 11:02AM Q 3 OTHER 11:02AM
Q 2 OTHER 11:01AM Q 2 OTHER ll:OlAM
~1~08ll1ER ~o~5~lljER
~o~5~lljER
~o\~lljER
T 1 TANK 10:49AM T 1 TANK 10:47AM
T 1 TANK 10: 47AM T 1 TANK 10:44AM T 1 TANK 10:44AM ~0~ 4~lljER
~0~4~lljER
T 1 TANK 10:42AM
T 1 TANK 10:39AM T 1 TANK 10:39AM T 2 TANK 10:38AM
T 2 TANK 10:37AM T 2 TANK 10: 37AM T 2 TANK
10: 36AM
T 2 TANK 10: 35AM T 2 TANK 10: 34AM ~oMI~ER
T 3 TANK 10:32AM T 3 TANK 10:32AM ~oMTilER
T 3 TANK 10:32AM
Iohi%jK
T 3 TANK 10:31AM T 3 TANK
10:30AM
T 3 TANK 10:29AM T 3 TANK 10:28AM I 1 INPUT 10: 24AM I 1 INPUT 10: 22AM ~o~2~TI1ER
L16 PIPE 10:22AM L15 PIPE 10:22AM \:liM~ SUMP
L13 STP SUMP
DIESEL
DIESEL
91 UNLEADED
91 UNLEADED
87 UNLEADED
91 UNLEADED
91 UNLEADED
87 UNLEADED
UN1
UN1
UN1
UN1
UN1
DIESEL
DIESEL
UN1
UN1
UN1
PR1
PR1
PR1
PR1
PR1
PR1
DIESEL
DIESEL
DIESEL
DIESEL
DIESEL
DIESEL
DIESEL
DIESEL
DIESEL
DIESEL
EMERGENCY SHUT OFF
EMERGENCY SHUT OFF
91 UNLEADED
91 FILL BRINE
91 FILL
91 TURBINE BRINE
91 TURBINE
POWER ON RESET 164807 3919 202970 203082 203127 39544 514845 9949365 9928 102072 9852763 9870287 9798228 9823814 9765830 9798012 101521 9786178 9767641 9753587 68839 15029
ALARM TYPE
CURRENT
16§H8
201773 201888 201819 39448
8;mu
m~m 8446209 8440533 101216 487065 ~~um
STATE
PLLD SHUTDOWN ALARM CLEAR
GROSS LINE FAIL CLEAR
PLLD SHUTDOWN ALARM CLEAR
GROSS LINE FAIL CLEAR
GROSS LINE FAIL CLEAR
PLLD SHUTDOWN ALARM ALARM
GROSS LINE FAIL
GROSS LINE FAIL
PROBE OUT
OVERFILL ALARM
PROBE OUT
OVERFILL ALARM
SUDDEN LOSS ALARM
ALARM
ALARM
CLEAR
CLEAR
ALARM
ALARM
CLEAR
PLLD SHUTDOWN ALARM ALARM
GROSS LINE FAIL ALARM
PROBE OUT CLEAR
PROBE OUT ALARM
SUDDEN LOSS ALARM ALARM
PROBE OUT CLEAR
OVERFILL ALARM CLEAR
PROBE OUT ALARM
OVERFILL ALARM ALARM
PROBE OUT CLEAR
PROBE OUT ALARM
PLLD SHUTDOWN ALARM CLEAR
LOW PRODUCT ALARM CLEAR
LOW PRODUCT ALARM ALARM
PLLD SHUTDOWN ALARM ALARM
PROBE OUT CLEAR
OVERFILL ALARM CLEAR
PROBE OUT ALARM
OVERFILL ALARM ALARM
PROBE OUT CLEAR
PROBE OUT ALARM
EXTERN INPUT ALARM CLEAR
EXTERN INPUT ALAR~I ALARM
PLLD SHUTDOWN ALARM CLEAR
SENSOR OUT ALARM CLEAR
SENSOR OUT ALARM CLEAR
SENSOR OUT ALARM CLEAR
SENSOR OUT ALARM CLEAR
DATE
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
Page 1
10:2W1 L12 ANNULAR 10: 21AM Q 1 OTHER
10:21AM L11 PIPE 10:2W1 L10 PIPE 10:21AM
Io ~ 2ill suMP
Q 3 OTHER 10:21AM L23 PIPE
10:21AM L22 PIPE 10:2W1 L21 PIPE 10:2W1
I11200 DEC 5, 2013
87 ANNULAR
87 UNLEADED
87 FILL BRINE
87 FILL
87 TURBINE BRINE
DIESEL
VENT SUMP BRINE
VENT SUMP
DIESEL FILL BRINE
3:22 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION TIME T 1 TANK UN1 10:51AM T 1 TANK UN1
10:49AM T 2 TANK PR1 10:41AM T 2 TANK PR1 10: 38AM T 2 TANK PR1 10: 35AM T 2 TANK PR1 10:35AM T 2 TANK PR1 10:35AM T 2 TANK PR1 10:34AM T 3 TANK DIESEL 10:32AM T 3 TANK DIESEL 10:32AM T 3 TANK DIESEL 10:32AM T 3 TANK DIESEL 10:32AM T 3 TANK DIESEL 10:29AM T 3 TANK DIESEL
10:28AM SYSTEM 8:50AM SYSTEM 8:50AM
SYSTEM 8:50AM SYSTEM 8:50AM SYSTEM
8:48AM
SYSTEM 8:48AM SYSTEM
8:47AM SYSTEM 8:47AM OTHER 10: 53AM
OTHER 8:01AM SYSTEM 10:43AM SYSTEM
10:43AM
SYSTEM 10:4W1 SYSTEM 10:41AM SYSTEM
10:41AM SYSTEM 10:41AM SYSTEM 10:4W1 SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:40AM SYSTEM 10:40AM SYSTEM 10:40AM SYSTEM 10:40AM SYSTEM
10:40AM SYSTEM 10:40AM SYSTEM 10:40AM SYSTEM 10:40AM SYSTE~I 10: 37AM
SYSTEM 10:37AM SYSTEM 10: 37AM SYSTEM 10:37AM
I11300 DEC 5, 2013 3:22 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
ACTIVE ALARMS REPORT
ID CATEGORY DESCRIPTION s11 OTHER 87 VENT
SENSOR OUT ALARM CLEAR
PLLD SHUTDOWN ALARM CLEAR
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
SENSOR OUT ALARM
SENSOR OUT ALARM
SENSOR OUT ALARM
CLEAR
CLEAR
CLEAR
PLLD SHUTDOWN ALARM CLEAR
SENSOR OUT ALARM CLEAR
SENSOR OUT ALARM CLEAR
SENSOR OUT ALARM CLEAR
ALARM TYPE STATE DATE
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
LOW TEMP WARNING CLEAR
LOW TEMP WARNING ALARM
LOW TEMP WARNING CLEAR
LOW TEMP WARNING ALARM
DELIVERY NEEDED CLEAR
INVALID FUEL LEVEL CLEAR
INVALID FUEL LEVEL ALARM
DELIVERY NEEDED ALARM
DELIVERY NEEDED CLEAR
DELIVERY NEEDED ALARM
INVALID FUEL LEVEL CLEAR
INVALID FUEL LEVEL ALARM
DELIVERY NEEDED CLEAR
DELIVERY NEEDED ALARM
PRINTER ERROR CLEAR
PAPER OUT CLEAR
PRINTER ERROR ALARM
PAPER OUT ALARM
PRINTER ERROR CLEAR
PAPER OUT
PAPER OUT
PRINTER ERROR
ISO VAPOR LEAK WARN
ISO VAPOR LEAK WARN
PRINTER ERROR
PAPER OUT
PRINTER ERROR
PAPER OUT
PRINTER ERROR
PAPER OUT
PRINTER ERROR
PAPER OUT
PRINTER ERROR
PAPER OUT
PRINTER ERROR
PAPER OUT
PRINTER ERROR
PAPER OUT
PRINTER ERROR
PAPER OUT
PRINTER ERROR
PAPER OUT
PRINTER ERROR
PAPER OUT
PRINTER ERROR
PAPER OUT
PRINTER ERROR
PAPER OUT
PRINTER ERROR
PAPER OUT
ALARM TYPE NO VACUUM ALARM
CLEAR 12-05-13
ALARM 12-05-13
ALARM 12-05-13
CLEAR 11-12-13
ALARM 11-10-13
CLEAR 10-30-13
CLEAR 10-30-13
ALARM 10-30-13
ALARM 10-30-13
CLEAR 10-30-13
CLEAR 10-30-13
ALARM 10-30-13
ALARM 10-30-13
CLEAR 10-30-13
CLEAR 10-30-13
ALARM 10-30-13
ALARM 10-30-13
CLEAR 10-30-13
CLEAR 10-30-13
ALARM 10-30-13
ALARM 10-30-13
CLEAR 10-30-13
CLEAR 10-30-13
ALARM 10-30-13
ALARM 10-30-13
CLEAR 10-30-13
CLEAR 10-30-13
ALARM 10-30-13
ALARM 10-30-13
CLEAR 10-30-13
CLEAR 10-30-13
DATE TIME
111400 DEC 5, 2013 3 : 22 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
CLEARED ALARMS REPORT
ID CATEGORY DESCRIPTION TIME ~1 ~ o~..illER DIESEL
~1 ~ O~..illER DIESEL
~1~o~..illER 91 UNLEADED
~1~0mER 91 UNLEADED
Q 1 OTHER 87 UNLEADED
ll:OOAM T 1 TANK UN1 10:49AM T 1 TANK UN1 10:47AM T 1 TANK UN1 10:44AM T 1 TANK UN1 10:42AM T 2 TANK PR1 10: 38AM T 2 TANK PR1 10:37AM T 2 TANK PR1 10:3SAM Q 3 OTHER DIESEL 10:32AM
T 3 TANK 10: 32AM T 3 TANK 10: 32AM T 3 TANK 10:31AM T 3 TANK 10:29AM
DIESEL
DIESEL
DIESEL
DIESEL
I 1 INPUT 10:24AM ~oM..illER
EMERGENCY SHUT OFF
91 UNLEADED
Ll6 PIPE 10:22AM LlS PIPE 10:22AM L14 STP SUMP 10:21AM L13 STP SUMP 10: 21AM Ll2 ANNULAR 10:21AM ~0~2~..illER
Lll PIPE 10:21AM L10 PIPE 10: 21AM L 9 STP SUMP 10:21AM Q 3 OTHER I0:21AM L23 PIPE 10:21AM L22 PIPE 10: 21AM L21 PIPE 10: 21AM T 1 TANK 10: SlAM T 2 TANK 10:41AM T 2 TANK 10:35AM T 2 TANK 10: 3SAM T 3 TANK 10:32AM T 3 TANK 10:32AM
T 3 TANK 10:29AM SYSTEM 8: SOAM SYSTEM 8: SOAM SYSTEM 8:48AM SYSTEM 8:48AM OTHER 10: 53AM SYSTEM 10:43AM SYSTEM 10:43AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:41AM SYSTEM 10:40AM SYSTEM 10:40NI SYSTEM 10:40AM SYSTEM 10:40AM SYSTEM 10: 37AM SYSTEM 10:37AM
IllSOO DEC 5, 2013
9999FF1B Il1A00 DEC 5, 2013
91 FILL BRINE
91 FILL
91 TURBINE BRINE
91 TURBINE
87 ANNULAR
87 UNLEADED
87 FILL BRINE
87 FILL
87 TURBINE BRINE
DIESEL
VENT SUMP BRINE
VENT SUMP
DIESEL FILL BRINE
UN1
PR1
PR1
PR1
DIESEL
DIESEL
DIESEL
3:22 PM
3:22 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
SERVICE REPORT
DATE/TIME LABEL
ALARM TYPE STATE
PLLD SHUTDOWN ALARM CLEAR
GROSS LINE FAIL CLEAR
PLLD SHUTDOWN ALARM CLEAR
GROSS LINE FAIL
GROSS LINE FAIL
PROBE OUT
OVERFILL ALARM
SUDDEN LOSS ALARM
PROBE OUT
PROBE OUT
OVERFILL ALARM
PROBE OUT
CLEAR
CLEAR
CLEAR
CLEAR
CLEAR
CLEAR
CLEAR
CLEAR
CLEAR
PLLD SHUTDOWN ALARM CLEAR
LOW PRODUCT ALARM CLEAR
PROBE OUT CLEAR
OVERFILL ALARM CLEAR
PROBE OUT CLEAR
EXTERN INPUT ALARM CLEAR
PLLD SHUTDOWN ALARM CLEAR
SENSOR OUT ALARM
SENSOR OUT ALARM
SENSOR OUT ALARM
SENSOR OUT ALARM
SENSOR OUT ALARM
CLEAR
CLEAR
CLEAR
CLEAR
CLEAR
PLLD SHUTDOWN ALARM CLEAR
SENSOR OUT ALARM CLEAR
SENSOR OUT ALARM CLEAR
SENSOR OUT ALARM CLEAR
PLLD SHUTDOWN ALARM CLEAR
SENSOR OUT ALARM CLEAR
SENSOR OUT ALARM CLEAR
SENSOR OUT ALARM CLEAR
LOW TEMP WARNING CLEAR
LOW TEMP WARNING CLEAR
DELIVERY NEEDED CLEAR
INVALID FUEL LEVEL CLEAR
DELIVERY NEEDED CLEAR
INVALID FUEL LEVEL CLEAR
DELIVERY NEEDED CLEAR
PRINTER ERROR CLEAR
PAPER OUT CLEAR
PRINTER ERROR CLEAR
PAPER OUT CLEAR
ISD VAPOR LEAK WARN CLEAR
PRINTER ERROR CLEAR
PAPER OUT CLEAR
PRINTER ERROR CLEAR
PAPER OUT CLEAR
PRINTER ERROR CLEAR
PAPER OUT CLEAR
PRINTER ERROR CLEAR
PAPER OUT CLEAR
PRINTER ERROR CLEAR
PAPER OUT CLEAR
PRINTER ERROR CLEAR
PAPER OUT CLEAR
PRINTER ERROR CLEAR
PAPER OUT CLEAR
ID LABEL
DATE
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
12-05-13
11-12-13
10-30-13
10-30-13
10-30-13
10-30-13
10-30-13
10-30-13
10-30-13
10-30-13
10-30-13
10-30-13
10-30-13
10-30-13
10-30-13
10-30-13
Page 2
CODE NONE
I11B00 DEC 5, 2013 3:22 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
SERVICE NOTICE SESSION REPORT
START TIME
9999FF1B I20100 DEC 5, 2013 3:22 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA, 661-873-9343
IN-TANK INVENTORY
TANK PRODUCT TEMP 1 UN1 64.15 2 PR1 68.67 3 DIESEL 72.67
I20200 DEC 5, 2013 3: 22 PM
FOODS CO . 3 84 2505 HALEY BAKERSFIELD CA. 661-873-9343
DELIVERY REPORT
T 1:UN1
END TIME
VOLUME TC VOLUME
12668 12631
3516 3494
1971 1960
ULLAGE
7114
4385
8449
HEIGHT
71.96
53.89
30.40
WATER
0.00
0.00
0.00
INCREASE DATE / TIME GALLONS TC GALLONS WATER TEMP DEG F
HEIGHT
103.09END: DEC 5, 2013 10:51 AM
72•3§TART: DEC 5, 2013 10:43 AM
AMOUNT:
END: DEC 81.99 START: DEC 44.82 AMOUNT:
END: DEC 84.85 START: DEC 47.59 AMOUNT:
END: DEC 84.66 START: DEC
42.90 AMOUNT:
4, 2013
4, 2013
3' 2013
3' 2013
2, 2013
2' 2013
94 •89 END: DEC 1, 2013
Sl.GlTART: DEC 1, 2013
AMOUNT:
83.57 END: NOV 30, 2013
SS.1~TART: NOV 30, 2013
AMOUNT:
gl, SB END: NOV 29, 2013
53•6§TART: NOV 29, 2013
NIOUNT:
gs. 61 END: NOV 27, 2013
57• 2rART: NOV 27, 2013
AMOUNT:
5:57 PM
5:38 PM
2:07 PM
1:46 PM
2:44 PM
2:23 PM
1:24 AM
1:04 AM
2:42 AM
2:24 AM
2:46 AM
2:16 AM
4:37 PM
4:16 PM
88 .08 END: NOV 27, 2013 12:24 AM
46 .2~TART: NOV 26, 2013 11:50 PM
AMOUNT:
73•97 END: NOV 26, 2013 11:16 Nl
46 • s§TART: NOV 26, 2013 10:54 Nl
AMOUNT:
T 2: PR1 INCREASE DATE / TIME HEIGHT
104. glND: DEC 5, 2013 10:44 Nl
20.SlTART: DEC 5, 2013 10:34 AM
AMOUNT:
END: DEC 56.33 START: DEC 44.32 NIOUNT:
END: DEC 55.49 START: DEC 43.36 AMOUNT:
4, 2013
4, 2013
3' 2013
3' 2013
76 . 76 END: NOV 30, 2013
42 .8~TART: NOV 30, 2013
AMOUNT:
52• 53 END: NOV 29, 2013
40 •3~TART: NOV 29, 2013
AMOUNT:
END: NOV 27, 2013
6:03 PM
5:53 PM
2:11 PM
2:02 PM
2:36 AM
2:22 AM
2:21 AM
2:12 AM
4:27 PM
18375
12758
18386 0. 85
12775 0.00
5617 5611
14734
6781
7953
15294
7372
14698 0.00
6751 0.00
7947
15234 0. 00
7337 0.00
7922 7897
15258
6378
8880
17114
8240
15195 0. 00
6345 0.00
8850
17043 0. 00
8201 0.00
8874 8842
15046
9016
6030
16543
8694
14977 0.00
8972 0.00
6005
16471 0.00
8652 0.00
7849 7819
17233 17173 0. 00
9476 9455 0.00
7757 7718
15907
7082
15884 0. 00
7062 0.00
8825 8822
13092
7156
5936
13062 0.00
7135 0.00
5927
59.11
58.14
63.44
66.31
65.52
66.59
65.82
67.19
65.87
66.84
66.43
66.97
66.16
66.68
64.93
63.12
62.04
63.98
63.25
64.11
GALLONS TC GALLONS WATER TEMP DEG F
7409
929
7367 0.00
923 0.00
6480 6444
3723
2716
3702 0.00
2697 0.00
1007 1005
3651
2637
3625 0.00
2616 0.00
1014 1009
5425
2594
5403 0.00
2573 0.00
2831 2830
3401
2390
1011
3262
3375 0.00
2371 0.00
1004
3240 0.00
67.94
68.37
67.85
70.10
70.11
71.08
65.82
71.08
70.53
71.34
69.74
50.88
38. 5~TART: NOV 27, 2013 4:18 PM
AMOUNT:
52 _50 END: NOV 26, 2013 11:29 AM
40_2~TART: NOV 26, 2013 11:17 AM
AMOUNT:
61.79 END: NOV 24, 2013 12:04 AM
39• g§TART: NOV 23, 2013 11:54 PM
AMOUNT:
48.0? END: NOV 23, 2013 4:08 AM
35 _6ITART: NOV 23, 2013 3:58AM
AMOUNT:
48_40 END: NOV 21, 2013 10:19 PM
35_9~TART: NOV 21, 2013 10:09 PM
AMOUNT:
T 3 :DIESEL
2251
1011
3399
2387
1012
4184
2364
1820
3027
2017
1010
3054
2043
2234 0.00
1006
3379 0.00
2369 0.00
1010
4162 0.00
2348 0.00
1814
3009 0.00
2001 0.00
1008
3033 0.00
2026 0.00
1011 1007
70.53
67.98
70.72
67.30
69.43
68.08
70.86
69.75
71.66
INCREASE DATE / TIME GALLONS TC GALLONS WATER TEMP DEG F HEIGHT
l03.63END: DEC 5, 2013 10:37 AM
START: DEC 5, 2013 10:28 AM 9.08 AMOUNT:
41.83 END: NOV 26, 2013 11:23 AM
27_3~TART: NOV 26, 2013 11:13 AM
AMOUNT:
40
_
31
END: NOV 16, 2013 3:12 AM
25 _5~TART: NOV 16, 2013 3:03AM
AMOUNT:
57_go END: OCT 20, 2013 5:27PM
49_3~TART: OCT 20, 2013 5:17 PM
AMOUNT:
61.93 END: OCT 9, 2013 7:36 PM
49.l~TART: OCT 9, 2013 7:25PM
AMOUNT:
50_74 END: OCT 8, 2013 12:27 PM
50. oSTART: OCT 8, 2013 12:18 PM
AMOUNT:
52 _60 END: OCT 5, 2013 6:30 PM
43• 8~TART: OCT 5, 2013 6:20 PM
AMOUNT:
48_69 END: SEP 30, 2013 2:14 AM
39 _8~TART: SEP 30, 2013 1:59AM
AMOUNT:
46.00 END: SEP 23, 2013 11:23 PM
30_28TART: SEP 23, 2013 11:13 PM
AMOUNT:
39_ 74 END: SEP 16, 2013 2:44 AM
35_0~TART: SEP 16, 2013 2:36 AM
AMOUNT:
I20300 DEC 5, 2013 3:22 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
TANK 1 UNl TEST STATUS: OFF LEAK DATA NOT AVAILABLE ON THIS TANK
TANK 2 PRl TEST STATUS: OFF LEAK DATA NOT AVAILABLE ON THIS TANK
TANK 3 DIESEL TEST STATUS: OFF LEAK DATA NOT AVAILABLE ON THIS TANK
I20400 DEC 5, 2013 3:22 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
SHIFT REPORT
SHIFT 1 TIME: 6:00 AM
TANK PRODUCT
9756
300
9456
3176
1678
1498
3008
1515
1493
5046
4033
1013
5526
4013
1513
4198
4111
87
4417
3406
1011
3959
2955
1004
3648
1952
1696
2945
2441
504
9704 0.00
298 0.00
9406
3155 0.00
1668 0.00
1487
2986 0.00
1504 0.00
1482
4996 0.00
3994 0. 00
1002
5469 0.00
3969 0.00
1500
4152 0. 00
4067 0.00
85
4369 0.00
3371 0.00
998
3921 0.00
2924 0.00
997
3607 0.00
1930 0.00
1677
2911 0.00
2415 0.00
496
71.60
72.74
74.30
73.11
75.77
76.81
81.51
81.24
82.83
84.01
84.04
83.96
83.85
82.73
80.95
83.39
84.64
84.59
85.19
83.35
1 UNl VOLUME TC VOLUME ULLAGE HEIGHT WATER TEMP
SHIFT 1 STARTING VALUES ENDING VALUES DELIVERY VALUE TOTALS
2 PRl SHIFT 1 STARTING VALUES ENDING VALUES DELIVERY VALUE TOTALS
11703 11657 8079 13174 13141 6608 7953 6482
VOLUME TC VOLUME ULLAGE 3298 3276 4603 3601 3580 4300 1007 704
~u~ 8:88 ~u~
HEIGHT WATER TEMP 51.30 0.00 69.04 54.89 0. 00 67.89
Page 3
3 DIESEL SHIFT 1 STARTING VALUES ENDING VALUES DELIVERY VALUE TOTALS
I20500 DEC 5 , 2013 3: 22 PM
FOODS CO • 3 84 2505 HALEY BAKERSFIELD CA. 661-873-9343
TANK PRODUCT
1 UNl
PRl
DIESEL
I20600 DEC 5, 2013 3:22 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
TANK ALARM HISTORY
TANK 1 UNl
OVERFILL ALARM
LOW PRODUCT ALARM
SUDDEN LOSS ALARM
HIGH PRODUCT ALARM
INVALID FUEL LEVEL
PROBE OUT
DELIVERY NEEDED
LOW TEMP WARNING
TANK 2 PRl
OVERFILL ALARM
LOW PRODUCT ALARM
SUDDEN LOSS ALARM
HIGH PRODUCT ALARM
INVALID FUEL LEVEL
PROBE OUT
HIGH WATER WARNING
DELIVERY NEEDED
LOW TEMP WARNING
TANK 3 DIESEL
OVERFILL ALARM
LOW PRODUCT ALARM
SUDDEN LOSS ALARM
HIGH PRODUCT ALARM
INVALID FUEL LEVEL
PROBE OUT
DELIVERY NEEDED
MAX PRODUCT ALARM
LOW TEMP WARNING
I20700 DEC 5, 2013 3:22 PM
FOODS CO • 3 84 2505 HALEY BAKERSFIELD CA. 661-873-9343
TANK LEAK TEST HISTORY
T l:UNl
LAST GROSS TEST PASSED:
VOLUME TC VOLUME ULLAGE HEIGHT WATER TEMP 8267 32.22 0.00 72.81 2153 2140 8436 30.52 0.00 72.59 1984 1972 0 169
STATUS
NORMAL
NORMAL
NORMAL
DEC 5, 2013 10:44 AM NOV 12, 2013 11:39 AM OCT 31, 2013 1:57 AM
DEC 15,
8~§ ~: DEC 6,
2010 3:26 PM
2013 10:39 AM 2012 2:45 PM 2011 11:38 AM
DEC 6 2011 11: 46 AM ~llt 28: ~8H 1H8 ~
DEC 15 , 2010 2: 55 PM
DEC 5, 2013 10:47 AM DEC 5, 2013 10:39 AM DEC 6, 2012 2: 49 PM
AUG 1, 2013 7:40 PM JUL 20, 2013 9:20 AM APR 23, 2013 7:02 PM
DEC 5, 2013 10:49 AM 8~§ ~: ~m 1U~ ~
DEC DEC DEC ~: ~8H 1U~ ;;tl 6, 2011 11:29 AM
DEC 6, 2012 2:35 PM DEC 15, 2010 3:26 PM
DEC 6, 2012 2: 3 5 PM DEC 6, 2011 11:27 AM DEC 29, 2010 12:35 PM
DEC 6, 2011 11:29 AM
DEC 5, 2013 10:35 AM DEC 6, 2011 11:31 AM DEC 15, 2010 2: 55 PM
DEC 5, 2013 10:37 AM DEC 5, 2013 10:34 AM DEC 6, 2012 2:41 PM
DEC 27, 2010 1:01 PM
DEC 5, 2013 10:34 AM OCT 17, 2013 4:47PM JUL 14, 2013 9:40 PM
8~§ ~: ~8H 1~:H ;;tl DEC 6, 2011 11:31 AM
DEC DEC ~: ~m lu~ ~~
DEC 5, DEC 15,
NOV 12, DEC 6, DEC 29,
DEC 6, DEC 27,
DEC 5, DEC 6, DEC 15,
2013 10:32 AM 2010 3:26 PM
2013 8:33 AM 2012 2:19 PM 2010 12:43 PM
2011 11:58 AM 2010 1:31 PM
2013 10:32 AM 2012 2:25 PM 2010 2:55 PM
DEC DEC DEC ~: ~8B 1sm ~ 6, 2012 2:25 PM
DEC DEC DEC ~: ~8B iU~ ~ 6, 2012 2:26 PM
DEC 27, 2010 1:31PM
DEC 27, 2010 1:33 PM
NO TEST PASSED
LAST ANNUAL TEST PASSED:
NO TEST PASSED
FULLEST ANNUAL TEST PASS
NO TEST PASSED
LAST PERIODIC TEST PASS:
NO TEST PASSED
FULLEST PERIODIC TEST PASSED EACH MONTH:
TEST START TIME
TANK LEAK TEST HISTORY
T 2:PR1
LAST GROSS TEST PASSED:
NO TEST PASSED
LAST ANNUAL TEST PASSED:
NO TEST PASSED
FULLEST ANNUAL TEST PASS
NO TEST PASSED
LAST PERIODIC TEST PASS:
NO TEST PASSED
FULLEST PERIODIC TEST
PASSED EACH MONTH:
TEST START TIME
TANK LEAK TEST HISTORY
T 3: DIESEL
LAST GROSS TEST PASSED:
NO TEST PASSED
LAST ANNUAL TEST PASSED:
NO TEST PASSED
FULLEST ANNUAL TEST PASS
NO TEST PASSED
LAST PERIODIC TEST PASS:
NO TEST PASSED
FULLEST PERIODIC TEST PASSED EACH MONTH:
TEST START TIME
I20800 DEC 5, 2013 3:22 PM
HOURS
HOURS
HOURS
PREVIOUS IN TANK LEAK TEST RESULTS
TANK 1 TEST TYPE ANNUAL PERIODIC
GROSS
TANK 2 TEST TYPE ANNUAL
UN1 START TIME NO TEST DATA AVAILABLE NO TEST DATA AVAILABLE NO TEST DATA AVAILABLE
PR1 START TIME NO TEST DATA AVAILABLE
PERIODIC NO TEST DATA AVAILABLE GROSS NO TEST DATA AVAILABLE
DIESEL START TIME TANK 3 TEST TYPE
ANNUAL PERIODIC GROSS
NO TEST DATA AVAILABLE NO TEST DATA AVAILABLE NO TEST DATA AVAILABLE
I20A00 DEC 5, 2013 3:23 PM
FOODS CO • 3 84 2505 HALEY BAKERSFIELD CA. 661-873-9343
ADJUSTED DELIVERY REPORT
MAG
VOLUME % VOLUME TEST TYPE
VOLUME % VOLUME TEST TYPE
VOLUME % VOLUME TEST TYPE
RESULT RATE HOURS VOLUME
RESULT RATE HOURS VOLU~IE
RESULT RATE HOURS VOLUME
TANK 1 UN1
INCREASE DATE/TIME INCREASE INCREASE DELIVERY DELIVERY
TANK 2 PR1
INCREASE DATE/TIME
TANK 3 DIESEL
INCREASE DATE/TIME
I20B00 DEC 5, 2013 3:23 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
VOLUME TC VOLUME ADJUSTMENT VOLUME TC VOLUME
MAG INCREASE INCREASE DELIVERY DELIVERY
VOLUME TC VOLUME ADJUSTMENT VOLUME TC VOLUME
MAG INCREASE INCREASE DELIVERY DELIVERY VOLUME TC VOLUME ADJUSTMENT VOLUME TC VOLUME
BIR ADJUSTED DELIVERY REPORT
Page 4
T 1:UN1
TC
START END ADJ ADJ
DELIVERY START DATE DELIVERY END DATE VOLUME VOLUME DELIV
DEL IV T 2:PR1 START END ADJ ADJ
TC DELIVERY START DATE DELIVERY END DATE VOLUME VOLUME DELIV
DELIV T 3:DIESEL START END ADJ ADJ
TC DELIVERY START DATE DELIVERY END DATE VOLUME VOLUME DELIV
DELIV
I20C00 DEC 5, 2013 3:23 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
LAST DELIVERY REPORT
T 1:UN1 INCREASE DATE / TIME HEIGHT
103.09END: DEC 5, 2013 10:51 AM
?2.3§TART: DEC 5, 2013 10:43 AM
AMOUNT:
T 2:PR1 INCREASE DATE / TIME HEIGHT
104 • g/ND: DEC 5, 2013 10:44 AM
20.siTART: DEC 5, 2013 10:34 AM
AMOUNT:
T 3 :DIESEL INCREASE DATE / TIME HEIGHT
103,63END: DEC 5, 2013 10:37 AM
START: DEC 5, 2013 10:28 AM 9.08 AMOUNT:
I20D00 DEC 5, 2013 3:23 PM
I21200 DEC 5, 2013 3:23 PM
FOODS CO . 3 84 2505 HALEY BAKERSFIELD CA.
661-873-9343
TANK LEAK TEST HISTORY
T 1: UN1
LAST GROSS TEST PASSED:
NO TEST PASSED
LAST ANNUAL TEST PASSED:
NO TEST PASSED
FULLEST ANNUAL TEST PASS
NO TEST PASSED
LAST PERIODIC TEST PASS:
NO TEST PASSED
FULLEST PERIODIC TEST PASSED EACH MONTH :
TEST START TIME
TANK LEAK TEST HISTORY
T 2: PR1
LAST GROSS TEST PASSED:
NO TEST PASSED
LAST ANNUAL TEST PASSED:
NO TEST PASSED
FULLEST ANNUAL TEST PASS
NO TEST PASSED
LAST PERIODIC TEST PASS:
NO TEST PASSED
FULLEST PERIODIC TEST PASSED EACH MONTH:
TEST START TIME
TANK LEAK TEST HISTORY
T 3 :DIESEL
LAST GROSS TEST PASSED:
NO TEST PASSED
LAST ANNUAL TEST PASSED:
NO TEST PASSED
FULLEST ANNUAL TEST PASS
NO TEST PASSED
LAST PERIODIC TEST PASS:
NO TEST PASSED
HOURS
HOURS
GALLONS TC GALLONS WATER TEMP DEG F
18375
12758
18386 0.85
12775 0.00
5617 5611
59.11
58.14
GALLONS TC GALLONS WATER TEMP DEG F
7409
929
6480
7367 0.00
923 0.00
6444
67.94
68.37
GALLONS TC GALLONS WATER TEMP DEG F
9756
300
9456
9704 0.00
298 0.00
9406
VOLUME % VOLUME TEST TYPE
VOLUME % VOLUME TEST TYPE
71.60
72.74
FULLEST PERIODIC TEST PASSED EACH MONTH:
TEST START TIME HOURS VOLUME % VOLUME TEST TYPE
I21400 DEC 5' 2013 3:23 PM
I21500 DEC 5' 2013 3:23 PM
I21600 DEC 5' 2013 3:23 PM
I21700 DEC 5' 2013 3:23 PM
TANK PROFILE
TANK PRODUCT LABEL 1 UN1 2 PR1
3 DIESEL
I21800 DEC 5' 2013 3:23 PM
I21900 DEC 5' 2013 3:23 PM
TANK CHART SECURITY DISABLED
I21A00 DEC 5, 2013 3:23 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
IN-TANK INVENTORY
PROFILE 4 PTS 4 PTS 4 PTS
TANK PRODUCT VOLUME TC VOLUME 90% ULLAGE HEIGHT
TEMP 1 64.16 2 68.67 3
UN1
PR1
DIESEL
12668
3516
1971
12631
3494
1960
72.67
I21B00 DEC 5' 2013 3:23 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
BIR ADJUSTED DELIVERY REPORT
T 1:UN1
TC DELIVERY START DATE DELIVERY END DELIV T 2: PR1
TC DELIVERY START DATE DELIVERY END DEL IV T 3 :DIESEL
TC DELIVERY START DATE DELIVERY END DELIV
I25100 DEC 5, 2013 3:23 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA, 661-873-9343
CSLD TEST RESULTS TANK PRODUCT
I28100
DEC 5' 2013 3:23 PM
I28200 DEC 5' 2013 3:23 PM
I30100 DEC 5' 2013 3:23 PM
FOODS CO. 384
2505 HALEY BAKERSFIELD CA. 661-873-9343
LIQUID STATUS REPORT
SENSOR LOCATION 1 DISP 1-2 DUAL 2 DISP 3-4 DUAL 3 DISP 5-6 DUAL 4 DISP 7-8 DUAL 5 DISP 9-10 DUAL
6 DISP 11-12 DUAL 7 DISP 13-14 DUAL 8 87 TURBINE 9 87 TURBINE BRINE 10 87 FILL 11 87 FILL BRINE 12 f ANNULAR 13 1 TURBINE 14 91 TURBINE BRINE 15 91 FILL 16 91 FILL BRINE 17 91 DIESEL ANNULAR 18 DIESEL TURBINE 19 DIESEL TURBINE BRINE 20 DIESEL FILL
21 DIESEL FILL BRINE 22 VENT SUMP 23 VENT SUMP BRINE
I30200 DEC 5, 2013 3: 23 PM
RESULT
STATUS SENSOR SENSOR SENSOR
SENSOR SENSOR SENSOR SENSOR SENSOR
SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR
SENSOR SENSOR SENSOR SENSOR SENSOR
DATE
DATE
DATE
NORMAL NORMAL
NORMAL NORMAL NORMAL NORMAL NORMAL
NORMAL
NORMAL NORMAL NORMAL NORMAL NORMAL
NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL
5135 71.96
3594 53.89
7407 30.40
START END
VOLUME VOLUME
START END
VOLUME VOLUME
START END
VOLUME VOLUME
WATER
0.00
0. 00
0.00
ADJ
DELIV
ADJ
DEL IV
ADJ
DELIV
ADJ
ADJ
ADJ
Page 5
FOODS CO. 384 2505 HALEY BAKERSFIELD CA, 661-873-9343
LIQUID ALARM HISTORY REPORT
I30600 DEC 5' 2013 3:23 PM
I30700 DEC 5' 2013 3:23 PM
I31100 DEC 5' 2013 3:23 PM
I31200 DEC 5' 2013 3:23 PM
I31500 DEC 5' 2013 3:23 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
SMART SENSOR STATUS REPORT
SENSOR LOCATION 1 DISP 1-2 VFM 2 DISP 3-4 VFM 3 DISP 5-6 VFM 4 DISP 7-8 VFM
5 DISP 9-10 VFM 6 DISP 11-12 VFM 7 DISP 13-14 VFM
8 DISP 13-14 PS
9 87 PRODUCT 10 87 91 VAPOR 11 87 VENT 12 91 PRODUCT 13 91 VENT
14 DIESEL PRODUCT
15 PMC CANISTER 16 ATM P 17 DIESEL VENT
STATUS SENSOR
LOW LIQUID ALARM SENSOR OUT ALARM
FUEL ALARM
LOW LIQUID ALARM SENSOR OUT ALARM FUEL ALARM
LOW LIQUID ALARM SENSOR OUT ALARM FUEL ALARM
LOW LIQUID ALARM SENSOR OUT ALARM FUEL ALARM
LOW LIQUID ALARM
FUEL ALARM SENSOR OUT ALARM
LOW LIQUID ALARM SENSOR OUT ALARM
FUEL ALARM
LOW LIQUID ALARM FUEL ALARM SENSOR OUT ALARM
SENSOR OUT ALARM FUEL ALARM SENSOR OUT ALARM
SENSOR OUT ALARM
FUEL ALARM FUEL ALARM
SENSOR OUT ALARM SENSOR OUT ALARM
FUEL ALARM
SENSOR OUT ALARM FUEL ALARM FUEL ALARM
SENSOR OUT ALARM ~6~H Li~3~5D At~~~M
SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM
SENSOR OUT ALARM FUEL ALARM FUEL ALARM
SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM
SENSOR OUT ALARM FUEL ALARM FUEL ALARM
SENSOR OUT ALARM ~6~H Li~3~ji;D At~~~M
SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM
SENSOR OUT ALARM FUEL ALARM FUEL ALARM
SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM
SENSOR OUT ALARM FUEL ALARM FUEL ALARM
SENSOR OUT ALARM SENSOR OUT ALARM FUEL ALARM
SENSOR OUT ALARM FUEL ALARM FUEL ALARM
NORMAL SENSOR NORMAL SENSOR NORMAL SENSOR NORMAL SENSOR NORMAL SENSOR NORMAL SENSOR NORMAL SENSOR NORMAL SENSOR NORMAL SENSOR NORMAL NO VACUUM ALARM SENSOR NORMAL SENSOR NORMAL SENSOR NORMAL SENSOR NORMAL SENSOR NORMAL SENSOR NORMAL
I31600 DEC 5' 2013 3:23 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA, 661-873-9343
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION 1 DISP 1-2 VFM DEC 15, 2010 3:59 PM COMMUNICATION ALARM
DISP 3-4 VFM DISP 5-6 VFM DEC 15, 2010 3:59 PM COMMUNICATION ALARM 4 DISP 7-8 VFM DEC 15, 2010 3:26 PM COMMUNICATION ALARM
5 DISP 9-10 VFM 8iVid~1BFM 3:26 PM COMMUNICATION ALARM
6 8iVi3-IS1BFM3' 26 PM COMMUNICATION ALARM 7 8iVi3-IS1~s 3' 26 PM COMMUNICATION ALARM
DEC 6, 2011 10:34 AM COMMUNICATION ALARM DEC 15, 2010 3:26 PM COMMUNICATION ALARM 87 PRODUCT DEC 5, 2013 9:53 AM NO VACUUM ALARM
DEC 5, 2013 9:52 AM HIGH LIQUID ALARM
DEC 5, 2013 9:52 AM NO VACUUM ALARM 10 87 91 VAPOR DEC 5, 2013 9:56 AM HIGH LIQUID ALARM DEC 5, 2013 9:55 AM NO VACUUM ALARM DEC 5, 2013 9:55 AM NO VACUUM ALARM
11 87 VENT DEC 5, 2013 9:56 AM HIGH LIQUID ALARM DEC 5, 2013 9:55 AM HIGH LIQUID ALARM NOV 30, 2013 12:14 AM NO VACUUM ALARM 12 91 PRODUCT DEC 5, 2013 10:02 AM HIGH LIQUID ALARM DEC 5, 2013 10:02 AM NO VACUUM ALARM DEC 5, 2013 9:59 AM NO VACUUM ALARM 13 91 VENT DEC 5, 2013 10:03 AM NO VACUUM ALARM
DEC 5, 2013 9:58 AM NO VACUUM ALARM
14 DEC 6, 2012 10:53 AM HIGH LIQUID ALARM DIESEL PRODUCT DEC 5, 2013 10:06 AM NO VACUUM ALARM DEC S, 2013 10:06 AM HIGH LIQUID ALARM DEC 6, 2012 11:05 AM HIGH LIQUID ALARM 15 PMC CANISTER JAN 24, 2013 8:48 AM SENSOR FAULT ALARM MAR 17, 2012 9:07 AM SENSOR FAULT ALARM JAN 23, 2012 6:09 PM SENSOR FAULT ALARM 16 ATM P 17 DIESEL VENT DEC ~: ~8H i8:8g AM NO VACUUM ALARM
DEC AM HIGH LIQUID ALARM DEC 6, 2012 11: OS AM HIGH LIQUID ALARM
131700 DEC 5' 2013 3:23 PM
131800 DEC 5' 2013 3:23 PM
I31900 DEC 5' 2013 3:23 PM
131AOO DEC 5' 2013 3:23 PM
132200 DEC 5' 2013 3:23 PM
132300 DEC 5' 2013 3:23 PM
133300 ~~RTSSE~n~ I~mLL\oG
DATE SENSOR SERIAL NUMBER TYPE 10-12-15 15:27:48 9 10430074 VAC SENSOR 10-12-15 15:27: so 10 10430073 VAC SENSOR 10-12-15 15:27:52 11 10430072 VAC SENSOR 10-12-15 15:27:53 12 10430102 VAC SENSOR
10-12-15 15:27:56 13 10430101 VAC SENSOR 10-12-15 15:27:58 14 10430070 VAC SENSOR 10-12-15 15:28:01 16 6545 ATM P SENSOR 10-12-15 15:28:56 15 9190010 VAPOR VALVE 10-12-15 15 : 29: 02 2 41742 AIR FLOW METER
10-12-15 15:29:30 4 41748 AIR FLOW METER 10-12-15 15:32:11 6 52271 AIR FLOW METER 10-12-15 15:32:13 7 52274 AIR FLOW METER 10-12-15 15:33:20 8 10835 VAPOR PRESSURE 10-12-16 09:41:41 1 41743 AIR FLOW METER 10-12-16 09:41:59 3 52279 AIR FLOW METER
10-12-16 09:43:24 5 52276 AIR FLOW METER 10-12-16 10:01:52 17 10430068 VAC SENSOR 11-05-02 13:33:15 12 12831 VAC SENSOR 11-05-10 18:14:36 13 12365 VAC SENSOR 12-05-10 10:41:04 17 12160020 VAC SENSOR 12-05-17 13:27:44 17 14113 VAC SENSOR 12-05-17 13:54:42 17 12160020 VAC SENSOR 12-07-30 11:58:05 11 12220003 VAC SENSOR 13-05-24 09:03:34 9 10935 VAC SENSOR
134100 DEC 5' 2013 3:23 PM
134200 DEC 5' 2013 3:23 PM
134600 DEC 5' 2013 3:23 PM
134700 DEC 5' 2013 3:23 PM
134BOO DEC 5' 2013 3:23 PM
134C00 DEC 5' 2013 3:23 PM
135100 DEC 5' 2013 3:23 PM
I35200 DEC 5' 2013 3:23 PM
Page 6
135300 DEC 5, 2013 3:23 PM
I37300 DEC 5 , 2013 3: 23 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
PRESSURE LINE LEAK TEST RESULTS
Q 1:87 UNLEADED
3. 0 GAL/HR RESULTS:
LAST TEST: DEC 5, 2013 1:47 PM PASS
NUMBER OF TESTS PASSED PREY 24 HOURS : 115 SINCE MIDNIGHT : 53
0.10 GAL/HR RESULTS:
NO 0.10 DATA AVAILABLE
0. 20 GAL/HR RESULTS:
NO 0. 20 DATA AVAILABLE
NO-VENT TEST ABORTS: 0 OUT OF 0 TEST
Q 2:91 UNLEADED
3. 0 GAL/HR RESULTS:
LAST TEST: DEC 5 , 2013 11: 01 AM PASS
NUMBER OF TESTS PASSED PREY 24 HOURS : SINCE MIDNIGHT :
0.10 GAL/HR RESULTS:
NO 0.10 DATA AVAILABLE
0. 20 GAL/HR RESULTS:
NO 0. 20 DATA AVAILABLE
NO-VENT TEST ABORTS: 0 OUT OF 0 TEST
Q 3:DIESEL
3. 0 GAL/HR RESULTS:
LAST TEST: DEC 5, 2013 11: 02 AM PASS
NUMBER OF TESTS PASSED PREY 24 HOURS : SINCE MIDNIGHT :
0.10 GAL/HR RESULTS:
NO 0.10 DATA AVAILABLE
0. 20 GAL/HR RESULTS:
NO 0. 20 DATA AVAILABLE
NO-VENT TEST ABORTS:
0 OUT OF 0 TEST
137400 DEC 5, 2013 3:23 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
PRESSURE LINE LEAK TEST HISTORY
Q 1:87 UNLEADED
LAST 3.0 PASS: DEC 5, 2013 1:47 PM
FIRST 0.10 PASS EACH MONTH:
FIRST 0. 20 PASS EACH MONTH:
Q 2 : 91 UNLEADED
LAST 3.0 PASS: DEC 5, 2013 11:01 AM
FIRST 0.10 PASS EACH MONTH:
FIRST 0.20 PASS EACH MONTH:
Q 3:DIESEL
LAST 3.0 PASS: DEC 5, 2013 11:02 AM
FIRST 0.10 PASS EACH ~\ONTH:
FIRST 0. 20 PASS EACH MONTH:
I38100 DEC 5, 2013 3:23 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
PRESSURE LINE LEAK STATUS
LINE HANDLE Q 1:87 UNLEADED
ACTIVE ALARMS:
Q 2:91 UNLEADED
ACTIVE ALARMS:
DISPENSING TEST STATUS
ENABLED TEST COMPLETE
ENABLED TEST COMPLETE
PUMP
OFF
OFF
OFF
OFF
Q 3 :DIESEL
ACTIVE ALARMS:
ENABLED TEST COMPLETE
!38200 DEC 5 , 2013 3: 23 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
PRESSURE LINE LEAK ALARM HISTORY REPORT
Q 1:87 UNLEADED DEC 5, 2013 DEC 5, 2013
DEC 5, 2013
DEC 5, 2013 DEC 5, 2013 DEC 5, 2013 DEC 5, 2013 DEC 5, 2013
DEC 5, 2013 DEC 5, 2013
Q 2:91 UNLEADED DEC 5, 2013
DEC 5, 2013 DEC 5, 2013 DEC 5, 2013 DEC 5, 2013 DEC 5, 2013 DEC 5, 2013 DEC 5, 2013 DEC 5, 2013 DEC 5, 2013
10:52 AM 10:20 AM
9:56 AM
9:55 AM 9:52 AM 9:49 AM 9:49 AM 9:48 AM
9:45 AM 9:45 AM
10:54 AM
10:54 AM 10:20 AM 10:02 AM 9:56 AM 9:49 AM 9:49 AM 9:48 AM 9:45 AM 9:45 AM
Q 3 :DIESEL DEC 5, 2013 10:43 AM DEC 5, 2013 10:43 AM DEC 5, 2013 10:32 AM DEC 5 , 2013 10: 20 AM DEC 5, 2013 10:06 AM DEC 5, 2013 9:49 AM DEC 5, 2013 9:49 AM DEC 5, 2013 9:48 AM 8~§ ~: ~m u~ ~
!38300 DEC 5, 2013 3:23 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
GROSS LINE FAIL PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM GROSS LINE FAIL PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM GROSS LINE FAIL PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM
PRESSURE LINE LEAK TEST RESULTS
Q 1:87 UNLEADED
3. 0 GAL/HR RESULTS:
LAST TEST: DEC 5, 2013 1:47 PM PASS
NUMBER OF TESTS PASSED PREY 24 HOURS : 115 SINCE MIDNIGHT : 53
0 .10 GAL/HR RESULTS:
NO 0.10 DATA AVAILABLE
Q 2:91 UNLEADED
3.0 GAL/HR RESULTS:
LAST TEST: DEC 5, 2013 11:01 AM PASS
NUMBER OF TESTS PASSED PREY 24 HOURS : 49
SINCE MIDNIGHT : 13
0.10 GAL/HR RESULTS:
NO 0.10 DATA AVAILABLE
Q 3: DIESEL
3. 0 GAL/HR RESULTS:
LAST TEST: DEC 5 , 2013 11: 02 AM PASS
NUMBER OF TESTS PASSED
PREY 24 HOURS : SINCE MIDNIGHT :
0.10 GAL/HR RESULTS:
NO 0.10 DATA AVAILABLE
I38400 DEC 5, 2013 3:23 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
PRESSURE LINE LEAK TEST HISTORY
Q 1:87 UNLEADED
LAST 3.0 PASS:
FIRST 0 .10 PASS EACH MONTH:
Q 2:91 UNLEADED
LAST 3.0 PASS:
FIRST 0 .10 PASS EACH MONTH:
Q 3: DIESEL
LAST 3 . 0 PASS:
FIRST 0 .10 PASS EACH MONTH:
DEC 5, 2013 1:47 PM
DEC 5, 2013 11:01 AM
DEC 5, 2013 11:02 AM
OFF OFF
Page 7
I38600 DEC 5' 2013 3:23 PM
I38700 DEC 5' 2013 3:23 PM
I38800 DEC 5' 2013 3:23 PM
!38900 DEC 5' 2013 3:23 PM
!39100 DEC 5' 2013 3:23 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
TANKER LOAD REPORT
T 1:UN1
NO START DATE/TIME VOLUME TEMP END DATE/TIME VOLUME
NO DATA HISTORY
T 2:PR1
NO START DATE/TIME VOLUME TEMP END DATE/TIME VOLUME
NO DATA HISTORY
T 3 :DIESEL
NO START DATE/TIME VOLU~IE TEMP END DATE/TIME VOLUME
NO DATA HISTORY
!39200 DEC 5, 2013 3:23 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
TANKER LOAD REPORT
T 1:UN1
NO DATE/TIME
NO DATA HISTORY
T 2:PR1
NO DATE/TIME
NO DATA HISTORY
T 3 :DIESEL
NO DATE/TI~IE NO DATA HISTORY
I40100 DEC 5, 2013 3:23 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
LOCATION EMERGENCY SHUT OFF
I40200 DEC 5, 2013 3:23 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
I40300
LOCATION EMERGENCY SHUT OFF DEC 5, 2013 10:22 AM ~5~ ~~: ~8B 1U5 ~ m z~: ~8B 1U~ ~ AUG 22, 2013 9:50 AM
DEC 5, 2013 3: 23 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
VOLUME TEMP TC VOLUME
VOLUME TEMP TC VOLUME
VOLUME TEMP TC VOLUME
STATUS OFF
EXTERN INPUT ALARM EXTERN INPUT ALARM EXTERN INPUT ALARM EXTERN INPUT NORMAL EXTERN INPUT NORMAL EXTERN INPUT NORMAL
INPUT / GENERATOR ALARM HISTORY REPORT
INPUT LOCATION
1 EMERGENCY SHUT OFF
9999FF1B I40600
m z~: ~8H iU~ ~ AUG 22, 2013 9:50AM DEC 5, 2013 10:24 AM
SEP 29, 2013 5:29 AM
AUG 22, 2013 9:50 Ml
DEC 5, 2013 3:23 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
RELAY LOCATION
I41100
DEC 5' 2013 3:23 PM
I41200 DEC 5' 2013 3:23 PM
I50100 DEC 5' 2013 3:23 PM
SYSTEM DATE AND TIME
STATUS
EXTERN INPUT ALARM EXTERN INPUT ALARM EXTERN INPUT ALARM EXTERN INPUT NORMAL EXTERN INPUT NORMAL EXTERN INPUT NORMAL
1 OVERFILL
TEMP TOTAL
TEMP TOTAL
TEMP TOTAL
OPEN
I50200 DEC 5' 2013 3:23 PM
I50300 DEC 5' 2013 3:23 PM
I50400 DEC 5' 2013 3:23 PM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED 2 000000 DISABLED
3 000000 DISABLED 4 000000 DISABLED
5 000000 DISABLED 6 000000 DISABLED
I50500 DEC 5, 2013 3:23 PM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS u.s. SYSTEM LANGUAGE ENGLISH
SYSTEM DATE/TIME FORMAT MON DD YYYY HH: MM: 55 XM
I50600 DEC 5, 2013 3:23 PM
PERIODIC TEST WARNINGS: DISABLED
I50700 DEC 5, 2013 3:23 PM
PERIODIC TEST WARNING: DAYS 25
I50800 DEC 5, 2013 3:23 PM
PERIODIC TEST ALARM: DAYS = 30
I50900 DEC 5, 2013 3:23 PM
ANNUAL TEST WARNINGS: DISABLED
I50A00 DEC 5, 2013 3: 23 PM
ANNUAL TEST WARNING: DAYS 355
I50B00 DEC 5, 2013 3:23 PM
ANNUAL TEST ALARM: DAYS 365
I50c00 DEC 5, 2013 3: 23 PM
REMOTE PRINTER DISABLED
I50D00 DEC 5, 2013 3: 23 PM
PRINT TC VOLU~IES
ENABLED
I50E00 DEC 5, 2013 3:23 PM
TEMP COMPENSATION VALUE (DEG F): 60.0
I50F00 DEC 5, 2013 3:23 PM
MON DO YYYY HH: MM: 55 xM
I51100 DEC 5, 2013 3:23 PM
SHIFT BIR PRINTOUTS
DISABLED
I51200 DEC 5 , 2013 3: 23 PM
DAILY BIR PRINTOUTS DISABLED
I51300
DEC 5' 2013 3:23
I51400 DEC 5' 2013 3:23
PM
PM
H-PROTOCOL DATA FORMAT HEIGHT
I51500 DEC 5' 2013 3:23 PM
I51600 DEC 5' 2013 3:23 PM
RE-DIRECT LOCAL PRINTOUT DISABLED
I51700 DEC 5, 2013 3:23 PM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS u.s. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DO YYYY HH:MM:SS xM
Page 8
I51800 DEC 5, 2013 3:23 PM ALTERNATE LANGUAGE CODE PAGE
CODE PAGE SELECTED: WINDOWS
I51900 DEC 5' 2013 3:23 PM
PRECISION TEST DURATION
HOURS: 12
I51AOO DEC 5' 2013 3:23 PM
DAYLIGHT SAVING TIME ENABLED OFF
I51B00
DEC 5' 2013 3:23 PM
DAYLIGHT SAVING TIME
START DATE MAR WEEK SUN 2:00
END DATE NOV WEEK 1 SUN 2:00
I51C00 DEC 5' 2013 3:23 PM
TICKETED DELIVERY DISABLED
I51D00 DEC 5' 2013 3:23 PM
I51E00 DEC 5' 2013 3:23 PM
I52000 DEC 5' 2013 3:23 PM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL 1 2 3 4 5 6 7 8
I52100 DEC 5' 2013 3:23 PM
RECEIVER CONFIGURATION
DIAL TYPE ON DATE ON DATE
ON DATE ON DATE ON DATE ON DATE ON DATE ON DATE
AM
AM
START TIME JAN 5, 2011 JAN 5, 2011 JAN 5, 2011 JAN 5, 2011 JAN 5, 2011 JAN 5, 2011 JAN 5, 2011
JAN 5, 2011
DEVICE
1
LABEL CONFIGURED OFF 2 3 4 5 6
7 8
I52200
DEC 5' 2013 3:23 PM
RECEIVER LABEL
DEVICE LABEL
1 2 3 4 5 6 7 8
I52300 DEC 5' 2013 3:23 PM
RECEIVER TELEPHONE NUMBER
RCVR LOCATION LABEL 1 2 3 ~ 7 8
I52400 DEC 5, 2013 3:23 PM
OFF OFF OFF OFF
OFF OFF OFF
PHONE NUMBER
RECEIVER DIALING DESTINATION TYPE
RCVR LOCATION LABEL 1 2 ~ 5 6 7 8
I52500 DEC 5 , 2013 3: 23 PM
FAX TYPE
COMPUTER COMPUTER COMPUTER COMPUTER COMPUTER COMPUTER COMPUTER COMPUTER
RECEIVER MODEM NUMBER TO DIAL
RCVR LOCATION LABEL 1 2 ~ !
I52600 DEC 5 , 2013 3: 23 PM
RECEIVER RETRY NUMBER
LOCATION LABEL
PORT NUMBER 1 1 1
t
RETR~ NUMBER
DISABLED DISABLED DISABLED DISABLED DISABLED DISABLED DISABLED DISABLED
2 3
3 3 4 3 5 3 6 3
7 3
8 3
I52700 DEC 5' 2013 3:23 PM
RECEIVER RETRY DELAY TIME
RCVR LOCATION LABEL RETRY DELAY
1 3
2 3 3 3 4 3 5 3
6 3
7 3
8 3
I52800 DEC 5, 2013 3:23 PM
RECEIVER CONFIRMATION REPORT FLAG
RCVR LOCATION LABEL 1 CONFIRMATION REPORT
OFF 2 OFF 3 OFF 4 OFF 5 OFF 6 OFF 7 OFF 8 OFF
I52900 DEC 5, 2013 3: 2 3 PM
ALL PHONES
I52A00 DEC 5, 2013 3:23 PM
RECEIVER REPORT LIST
RCVR LOCATION LABEL REPORT LIST
I 52 BOO DEC 5, 2013 3:23 PM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR 1 2 ~ !
I52C00
LOCATION LABEL
DEC 5, 2013 3:23 PM
RECEIVER SETUP REPORT
D 1: -NO ALARM ASSIGNMENTS -
D 2: -NO ALARM ASSIGNMENTS -
D 3: -NO ALARM ASSIGNMENTS -
D 4: -NO ALARM ASSIGNMENTS -
D 5: -NO ALARM ASSIGNMENTS -
D 6: -NO ALARM ASSIGNMENTS -
D 7: -NO ALARM ASSIGNMENTS -
D 8: -NO ALARM ASSIGNMENTS -
I52D00 DEC 5, 2013 3:23 PM
DIAL TYPE ON DATE ON DATE ON DATE ON DATE ON DATE ON DATE ON DATE ON DATE
RECEIVER AUTODIAL ALARM STATUS
RCVR STATUS
1 CLEAR 2 CLEAR 3 CLEAR 4 CLEAR 5 CLEAR
6 CLEAR 7 CLEAR 8 CLEAR
I52E00 DEC 5, 2013 3:24 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
START TIME JAN 5, 2011 JAN 5, 2011 JAN 5, 2011 JAN 5, 2011
JAN 5, 2011 JAN 5, 2011 JAN 5, 2011 JAN 5, 2011
RECEIVER CLEARED ALARMS REPORT DELAY PERIOD
RyVR
2 ~ 5 6 ~
I52F00
LOCATION LABEL
DEC 5, 2013 3:24 PM
RECEIVER ALARM STATUS
D 1: SERVICE REPORT WARN ALARM CLEAR WARNING DELIVERY REPORT WRN NO DIAL TONE ALARM
D 2: SERVICE REPORT WARN ALARM CLEAR WARNING DELIVERY REPORT WRN NO DIAL TONE ALARM
CLEAR CLEAR CLEAR CLEAR
CLEAR CLEAR CLEAR CLEAR
DELAY PERIOD
II j~
DISABLED DISABLED DISABLED
DISABLED DISABLED DISABLED DISABLED DISABLED
Page 9
D 3: SERVICE REPORT WARN ALARM CLEAR WARNING DELIVERY REPORT WRN NO DIAL TONE ALARM
D 4: SERVICE REPORT WARN: ALARM CLEAR WARNING: DELIVERY REPORT WRN: NO DIAL TONE ALARM :
D 5: SERVICE REPORT WARN:
CLEAR CLEAR CLEAR CLEAR
CLEAR CLEAR CLEAR CLEAR
CLEAR
ALARM CLEAR WARNING: CLEAR DELIVERY REPORT WRN: CLEAR NO DIAL TONE ALARM : CLEAR
D 6: SERVICE REPORT WARN: CLEAR ALARM CLEAR WARNING: CLEAR DELIVERY REPORT WRN: CLEAR NO DIAL TONE ALARM : CLEAR
D 7: SERVICE REPORT WARN: CLEAR
ALARM CLEAR WARNING: CLEAR DELIVERY REPORT WRN: CLEAR NO DIAL TONE ALARM : CLEAR
D 8: SERVICE REPORT WARN: CLEAR ALARM CLEAR WARNING: CLEAR DELIVERY REPORT WRN: CLEAR NO DIAL TONE ALARM : CLEAR
I53000 DEC 5' 2013 3:24 PM
I53100
DEC 5' 2013 3:24 PM
RS-232 END OF MESSAGE DISABLED
I53200 DEC 5' 2013 3:24 PM
I53300 DEC 5' 2013 3:24 PM
I53400
DEC 5' 2013 3:24 PM
I53600 DEC 5' 2013 3:24 PM
I53700 DEC 5' 2013 3:24 PM
I53800 DEC 5' 2013 3:24 PM
I54600
DEC 5' 2013 3:24 PM
TANK PER TST NEEDED WRN: DISABLED
I54700 DEC 5' 2013 3:24 PM
TANK PER TST NEEDED WRN: DAYS
I54800 DEC 5' 2013 3:24 PM
TANK PER TST NEEDED ALM: DAYS
I54900 DEC 5' 2013 3:24 PM
TANK ANN TST NEEDED WRN: DISABLED
I54A00 DEC 5, 2013 3:24 PM
25
30
TANK ANN TST NEEDED WRN: DAYS 355
I54B00 DEC 5, 2013 3:24 PM
TANK ANN TST NEEDED ALM: DAYS 365
I54C00 DEC 5, 2013 3:24 PM
I54DOO ~~6 3l662gMNT~~ 2~ob~:
9999FF1B
I55300
DEC 5, 2013 3:24 PM
LINE RE-ENABLE METHOD PASS LINE TEST
I55400 DEC 5, 2013 3:24 PM
I55500
DEC 5, 2013 3:24 PM
I55600 DEC 5, 2013 3:24 PM
LINE PER TST NEEDED WRN: DISABLED
I55700
DEC 5, 2013 3:24 PM
LINE PER TST NEEDED WRN: DAYS 25
I55800 DEC 5, 2013 3:24 PM
LINE PER TST NEEDED ALM: DAYS 30 1 UN1 A 2 PR1 B
3 DIESEL c
4 4
I55900 DEC 5' 2013 3:24 PM I60400 DEC 5' 2013 3:24 PM
LINE ANN TST NEEDED WRN: DISABLED TANK FULL VOLUME
I55A00 TANK PRODUCT LABEL GALLONS
DEC 5' 2013 3:24 PM 1 UN1 19782
2 PR1 7901
LINE ANN TST NEEDED WRN: DAYS 355 3 DIESEL 10420 4 0
I55B00 DEC 5' 2013 3:24 PM
I60500 DEC 5' 2013 3:24 PM
LINE ANN TST NEEDED AL~I: DAYS 365 TANK 4 POINT VOLUMES
9999FF1B TANK PRODUCT LABEL GALLONS
I56000 1 UN1 19782 16033 9897 3741
DEC 5' 2013 3:24 PM 2 PR1 7901 6356 3964 1560 3 DIESEL 10420 8502 5200 1893 ~lASS/DENSITY 4 0 0 0 0
DISABLED I60600 DEC 5' 2013 3:24 PM
I56400 DEC 5' 2013 3:24 PM TANK 20 POINT VOLUMES
ULLAGE: 90% TANK PRODUCT LABEL GALLONS
1 UN1 19782 1603~ 0 0 0 0 0
I56500 0 0 9897 0
DEC 5' 2013 3:24 PM 0 0 0 3741 0 0 0 0
~IAINTENANCE HISTORY PR1 7901 0 0 0 0 6356 0 0
DISABLED 0 0 3964 0 0 0 0 1560
0 0 0 0
I56600 DIESEL 10420 850~ 0 0
DEC 5' 2013 3:24 PM 0 0 0 0 0 5200 0
SERVICE NOTICE: DISABLED 0 0 0 1893
0 0 0 0
4 0 0 0 0 0 0 0 0
I56700 0 0 0 0
DEC 5' 2013 3:24 PM 0 0 0 0
0 0 0 0
I56800 DEC 5' 2013 3:24 PM I60700 DEC 5' 2013 3:24 PM
I56900 TANK DIAMETER
DEC 5' 2013 3:24 PM TANK PRODUCT LABEL INCHES 1 UN1 118.35
I56A00 2 PR1 118.35
DEC 5' 2013 3:24 PM 3 DIESEL 118.38
4 0.00
I5BC00 I60800
DEC 5' 2013 3:24 PM DEC 5' 2013 3:24 PM
RECEIVER SETUP REPORT TANK TILT
TANK PRODUCT LABEL INCHES
D 1: 1 UN1 0.00
-NO ALARM ASSIGNMENTS -2 PR1 0.00 3 DIESEL 0.00
D 2: 4 0.00
-NO ALARM ASSIGNMENTS -I60900
D 3: DEC 5' 2013 3:24 PM
-NO ALARM ASSIGNMENTS -TANK THER~IAL COEFFICIENT
D 4: -NO ALARM ASSIGNMENTS -TANK PRODUCT LABEL 1 UN1 0.000700
D 5: 2 PR1 0.000700
-NO ALARM ASSIGNMENTS -3 DIESEL 0.000450 4 0.000000
D 6: -NO ALARM ASSIGNMENTS -I60A00 DEC 5' 2013 3:24 PM
D 7: -NO ALARM ASSIGNMENTS -TANK FULL VOLUME
D 8: TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UN1
-NO ALARM ASSIGNMENTS -4 PTS 19782 2 PR1 4 PTS 7901 3 DIESEL 4 PTS 10420 4 1 PT 0
I5BD00 DEC 5' 2013 3:24 PM
I60B00
DEC 5' 2013 3:24 PM
CUSTOM ALARM LABELS STICK HEIGHT OFFSET DISABLED ENABLE STATUS
DISABLED
I60COO
I5BE00 DEC 5' 2013 3:24 PM
DEC 5' 2013 3:24 PM TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
I5BF00 1 UN1 0.00
DEC 5' 2013 3:24 PM 2 PR1 0.00 3 DIESEL 0.00
4 0.00
I5E200 I60E00 DEC 5' 2013 3:24 PM DEC 5' 2013 3:24 PM
I60100 DEC 5' 2013 3:24 PM I60F00
DEC 5' 2013 3:24 PM
TANK CONFIGURATION PROBE OFFSET
DEVICE LABEL CONFIGURED
1 UNl ON TANK PRODUCT LABEL INCHES
2 PR1 ON 1 UN1 0.00
3 DIESEL ON 2 PR1 0.00
4 OFF 3 DIESEL 0.00 4 0.00
I60200
DEC 5' 2013 3:24 PM I61000 DEC 5' 2013 3:24 PM
TANK PRODUCT LABEL TANK DELIVERY DELAY
TANK PRODUCT LABEL TANK PRODUCT LABEL
1 UN1 1 UN1 5
2 PR1 2 PR1 5
3 DIESEL 3 DIESEL 5
4 4 1
I60300 DEC 5' 2013 3:24 PM
I61100 DEC 5' 2013 3:24 PM
TANK PRODUCT CODE LEAK TEST METHOD ------
TANK PRODUCT LABEL TEST ON DATE : ALL TANK
Page 10
JUL 23, 2010 START TIME : DISABLED TEST RATE :0, 20 GAL/HR DURATION : 2 HOURS
TST EARLY STOP: DISABLED
I61200 DEC 5, 2013 3:24 PM
TANK MANIFOLDED PARTNERS
TANK T~NKS
2 ~
I61300
PRODUCT LABEL
UN1 PR1 DIESEL
DEC 5, 2013 3:24 PM CSLD PROBABLITY OF DETECTION
I61400 DEC 5, 2013 3:24 PM CSLD CLIMATE FACTOR
I61500 DEC 5' 2013 3:24 PM
TANK PRODUCT LABEL 1 UN1 2 PR1 3 DIESEL
4
I61600 DEC 5' 2013 3:24 PM
TANK PRODUCT LABEL
1 UN1 2 PR1 3 DIESEL 4
I61800 DEC 5' 2013 3:24 PM
I61900
DEC 5' 2013 3:24 PM
I61A00 DEC 5' 2013 3:24 PM
IN-TANK LEAK TEST EARLY
TANK PRODUCT LABEL
1 UN1 2 PR1 3 DIESEL 4
I61B00 DEC 5' 2013 3:24 PM
STOP
SIPHON MANIFOLDED TANKS
NONE NONE NONE NONE
METER DATA NO NO NO NO
CAL UPDATE IMMEDIATE IMMEDIATE IMMEDIATE
IMMEDIATE
TST EARLY STOP: DISABLED DISABLED DISABLED
DISABLED
LINE MANIFOLDED
NONE NONE NONE NONE
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
I61C00 DEC 5, 2013 3:24 PM
CSLD REPORT ONLY
I61D00 DEC 5, 2013 3: 24 PM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL TANKS 1 UN1 2 PR1 3 DIESEL
4
I61E00 DEC 5' 2013 3:24 PM
I61F00 ~~~? 5, 2013 3:24 PM
I62100
DEC 5' 2013 3:24 PM
TANK LOW PRODUCT LIMIT
TANK 1 2 3 4
I62200
PRODUCT LABEL
UN1 PR1 DIESEL
DEC 5, 2013 3:24 PM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL
1 UN1 2 PR1 3 DIESEL 4
I62300
DEC 5' 2013 3:24 PM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL
1 UN1 2 PR1 3 DIESEL 4
I62400 DEC 5' 2013 3:24 PM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL
1 UN1 2 PR1 3 DIESEL
I62500
SIPHON MANIFOLDED TANKS LINE MANIFOLDED
NONE NONE NONE NONE
GALLONS 540 500 251 0
GALLONS 18793 7506 9899 0
GALLONS 17803 7110 9378 0
INCHES 3.0 3.0 3.0
NONE NONE NONE NONE
Page 11
DEC 5' 2013 3:24 PM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL 1 UN1 2 PR1
3 DIESEL
4
I62600 DEC 5' 2013 3:24 PM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL 1 UN1 2 PR1
3 DIESEL 4
I62700 DEC 5' 2013 3:24 PM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL
1 UN1
2 PR1 3 DIESEL
I62800 DEC 5' 2013 3:24 PM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL
1 UN1
2 PR1
3 DIESEL 4
I62900 DEC 5' 2013 3:24 PM
TANK DELIVERY REQUIRED
T~NK
2 3 4
I62A00
PRODUCT LABEL UN1
PR1 DIESEL
DEC 5, 2013 3:24 PM
LIMIT
ANNUAL LEAK TEST MIN VOLU~IE
TANK 1 i
I62B00
PRODUCT LABEL UN1 PR1 DIESEL
DEC 5, 2013 3:24 PM
TANK LAST ANNUAL TEST
TANK 1 2 3 4
I62C00
PRODUCT LABEL UN1 PR1 DIESEL
DEC 5, 2013 3:24 PM
TANK PERIODIC TEST TYPE
TANK 1 2 ~
I62D00
PRODUCT LABEL UN1 PR1 DIESEL
DEC 5, 2013 3:24 PM
TANK LEAK TEST FAIL ALARMS
4
I62E00
PRODUCT LABEL UN1
PR1
DIESEL
DEC 5, 2013 3:24 PM
GALLONS 50 50 50 99
GALLONS 15 u
INCHES 1.0 1.0 1.0
GALLONS 19782 7901
10428
GALLONS
2967 1185 1042 0
GALLONS 989 395 494
DATE ??? ~~~
0
0, 8: 0,
8 0 0
PERIODIC TEST TYPE STANDARD STANDARD STANDARD STANDARD
GROSS TEST FAIL PERIODIC TEST FAIL ANNUAL TEST FAIL
GROSS TEST FAIL PERIODIC TEST FAIL ANNUAL TEST FAIL
GROSS TEST FAIL PERIODIC TEST FAIL ANNUAL TEST FAIL
GROSS TEST FAIL PERIODIC TEST FAIL ANNUAL TEST FAIL
CAPO PROBE CONDUCTIVE BOOT FLAG
TANK PRODUCT LABEL
I62F00 DEC 5, 2013 3:24 PM
MAG PROBE FLOAT SIZE
TANK 1 2 3
I63000
PRODUCT LABEL UN1 PR1 DIESEL
DEC 5, 2013 3:24 PM
IN-TANK LEAK TEST NOTIFY
I63100
PRODUCT LABEL UN1 PR1 DIESEL
DEC 5, 2013 3:24 PM
TANK LEAK TEST AVERAGING
CAPO CONDUCTIVE BOOT:
FLOAT SIZE: 3.0 IN. 3.0 IN.
3.0 IN.
TANK TEST NOTIFY: OFF OFF OFF OFF
ALARM DISABLED ALARM DISABLED ALARM DISABLED
ALARM DISABLED ALARM DISABLED ALARM DISABLED
ALARM DISABLED ALARM DISABLED ALARM DISABLED
ALARM DISABLED ALARM DISABLED ALARM DISABLED
TANK PRODUCT 1 UN1 2 PR1
3 DIESEL
LABEL ANNUAL OFF OFF OFF
PERIODIC OFF OFF OFF
4
I63200
DEC 5' 2013 3:24 PM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL
1 UN1 2 PR1 3 DIESEL 4
I63300 DEC 5, 2013 3:24 PM
OFF
SIPHON BREAK OFF OFF OFF OFF
LEAK TEST REPORT FORMAT: NORMAL
I63400 DEC 5, 2013 3:24 PM
RECONCILIATION WARNING LIMIT
TANK 1 2 3 4
I63500
PRODUCT LABEL
UN1 PR1 DIESEL
DEC 5, 2013 3:24 PM
RECONCILIATION ALARM LIMIT
T1NK
2 ~
I63600
PRODUCT LABEL UN1
PR1
DIESEL
DEC 5, 2013 3:24 PM
PERIODIC LEAK TEST MIN VOLUME
TANK 1 2 3 4
I63900
PRODUCT LABEL UN1
PR1 DIESEL
DEC 5, 2013 3:24 PM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL 1 UN1 END FACTOR: NONE
2 PR1 END FACTOR: NONE
3 DIESEL END FACTOR: NONE
4 END FACTOR: NONE
I63A00 DEC 5, 2013 3:24 PM
GALLONS 0
8
GALLONS 989
395 494 0
OFF
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
PRODUCT LABEL UN1 PUMP THRESHOLD
PR1 DIESEL
I63B00 ¥~~K ~6 ~&i~T MiM~ AND VOLUMES
I63C00 DEC 5, 2013 3:24 PM
TANK 50 POINT FULL VOLUME
TANK 1 2 3 4
I63D00
PRODUCT LABEL UN1 PR1 DIESEL
DEC 5, 2013 3:24 PM
9999FF1B
I68000 DEC 5, 2013 3:24 PM
FOODS CO. 384 2505 HALEY
BAKERSFIELD CA. 661-873-9343
FUEL MANAGEMENT SETUP
DELIVERY WARN DAYS: 0. 0 AUTO PRINT: DISABLED
!8:88~ 10.00%
GALLONS 0 0 0 0
FUEL MANAGEMENT AVERAGE SALES (GALLONS)
UN1 ( TANK 1 )
SUN MON TUE WED THR FRI SAT 0 0 0 0 0 0 0
PR1 ( TANK 2 )
SUN MON TUE WED THR FRI SAT
0 0 0 0 0 0 0
DIESEL ( TANK 3 ) SUN MON TUE WED THR FRI SAT 0 0 0 0 0 0 0
I68100 DEC 5' 2013 3:24 PM
Page 12
I68200 DEC 5' 2013 3:24 PM
I68300 DEC 5' 2013 3:24 PM
I70100 DEC 5' 2013 3:24 PM
LIQUID CONFIGURATION
DEVICE LABEL
1 DISP 1-2 DUAL 2 DISP 3-4 DUAL 3 DISP 5-6 DUAL 4 DISP 7-8 DUAL
5 DISP 9-10 DUAL
6 DISP 11-12 DUAL 7 DISP 13-14 DUAL 8 87 TURBINE 9 87 TURBINE BRINE
10 87 FILL 11 87 FILL BRINE 12 87 ANNULAR 13 91 TURBINE 14 91 TURBINE BRINE
15 91 FILL 16 91 FILL BRINE 17 91 DIESEL ANNULAR 18 DIESEL TURBINE 19 DIESEL TURBINE BRINE 20 DIESEL FILL 21 DIESEL FILL BRINE 22 VENT SUMP 23 VENT SUMP BRINE 24
I70200 DEC 5' 2013 3:24 PM
LIQUID LABEL
DEVICE LABEL
1 DISP 1-2 DUAL 2 DISP 3-4 DUAL 3 DISP 5-6 DUAL 4 DISP 7-8 DUAL 5 DISP 9-10 DUAL
6 DISP 11-12 DUAL 7 DISP 13-14 DUAL 8 87 TURBINE 9 87 TURBINE BRINE 10 87 FILL
11 87 FILL BRINE
12 87 ANNULAR 13 91 TURBINE 14 91 TURBINE BRINE 15 91 FILL
16 91 FILL BRINE 17 91 DIESEL ANNULAR 18 DIESEL TURBINE 19 DIESEL TURBINE BRINE 20 DIESEL FILL
21 DIESEL FILL BRINE 22 VENT SUMP 23 VENT SUMP BRINE 24
I70300 DEC 5, 2013 3:24 PM
LIQUID TYPE
SEN SO~
2 3 4 5 6 7
18 11 12 13 14 15 16 17 18 19 20 21 22 23 24
I70400
LOCATION DISP 1-2 DUAL DISP 3-4 DUAL DISP 5-6 DUAL
DISP 7-8 DUAL DISP 9-10 DUAL DISP 11-12 DUAL DISP 13-14 DUAL 87 TURBINE
87 TURBINE BRINE 87 FILL 87 FILL BRINE 87 ANNULAR 91 TURBINE 91 TURBINE BRINE 91 FILL 91 FILL BRINE 91 DIESEL ANNULAR DIESEL TURBINE DIESEL TURBINE BRINE DIESEL FILL DIESEL FILL BRINE VENT SUMP VENT SUMP BRINE
DEC 5, 2013 3:24 PM
LIQUID CATEGORY
SEN SO~
2 ~
J 11 12 13 14 15 16 H
LOCATION DISP 1-2 DUAL DISP 3-4 DUAL DISP 5-6 DUAL DISP 7-8 DUAL DISP 9-10 DUAL DISP 11-12 DUAL DISP 13-14 DUAL 87 TURBINE 87 TURBINE BRINE 87 FILL 87 FILL BRINE 87 ANNULAR 91 TURBINE 91 TURBINE BRINE 91 FILL 91 FILL BRINE 91 DIESEL ANNULAR DIESEL TURBINE
19 DIESEL TURBINE BRINE 20 DIESEL FILL 21 DIESEL FILL BRINE 22 VENT SUMP H VENT SUMP BRINE
I70600 DEC 5, 2013 3:24 PM
!70700 DEC 5, 2013 3:24 PM
CONFIGURED ON ON ON ON
ON ON ON ON ON
ON ON ON ON ON
ON ON ON ON ON ON ON ON ON OFF
TYPE DW SUMP 2-1 DW SUMP 2-1 DW SUMP 2-1 DW SUMP 2-1 DW SUMP 2-1 DW SUMP 2-1 DW SUMP 2-1
TRI-STATE tSINGLE FLOAT~ TRI-STATE SINGLE FLOAT TRI-STATE SINGLE FLOAT TRI-STATE SINGLE FLOAT DUAL POINT HYDROSTATIC
TRI-STATE tSINGLE FLOAT~ TRI-STATE SINGLE FLOAT TRI-STATE SINGLE FLOAT TRI-STATE SINGLE FLOAT DUAL POINT HYDROSTATIC
TRI-STATE ~SINGLE FLOATl TRI-STATE SINGLE FLOAT TRI-STATE SINGLE FLOAT TRI-STATE SINGLE FLOAT TRI-STATE SINGLE FLOAT TRI-STATE SINGLE FLOAT
TRI-STATE SINGLE FLOAT
CATEGORY DISPENSER PAN DISPENSER PAN DISPENSER PAN DISPENSER PAN DISPENSER PAN DISPENSER PAN DISPENSER PAN STP SUMP STP SUMP PIPING SUMP PIPING SUMP ANNULAR SPACE STP SUMP STP SUMP PIPING SUMP PIPING SUMP ANNULAR SPACE STP SUMP
STP SUMP PIPING SUMP PIPING SUMP PIPING SUMP PIPING SUMP OTHER SENSORS
I70800 DEC 5' 2013 3:24 PM
DEC 5' 2013 3:24 PM VACUUM SENSOR PUMP NUMBER
I70900 DEVICE LABEL PUMP NUMBER
DEC 5' 2013 3:24 PM 9 87 PRODUCT Q 1:87 UNLEADED 10 87 91 VAPOR Q 1: 8 7 UNLEADED 11 87 VENT Q 1:87 UNLEADED
I71100 12 91 PRODUCT Q 2:91 UNLEADED DEC 5' 2013 3:24 PM 13 91 VENT Q 2:91 UNLEADED
14 DIESEL PRODUCT Q 3 :DIESEL 17 DIESEL VENT Q 3:DIESEL
I71200 DEC 5' 2013 3:24 PM I72A00
DEC
I71300 5' 2013 3:24 PM
DEC 5' 2013 3:24 PM VACUUM SENSOR VOLUME
DEVICE LABEL VOLUME
I72100 9 87 PRODUCT 57. 5 GALLONS
DEC 5' 2013 3:24 PM 10 87 91 VAPOR 69. 0 GALLONS 11 87 VENT 25 • 0 GALLONS SMART SENSOR CONFIGURATION 12 91 PRODUCT 57.5 GALLONS
13 91 VENT 25.0 GALLONS
DEVICE LABEL CONFIGURED 14 DIESEL PRODUCT 46.0 GALLONS
1 DISP 1-2 VFM ON 17 DIESEL VENT 25.0 GALLONS
2 DISP 3-4 VFM ON
3 DISP 5-6 VFM ON 4 DISP 7-8 VFM ON I72BOO
5 DISP 9-10 VFM ON DEC 5' 2013 3:25 PM
6 DISP 11-12 VFM ON 7 DISP 13-14 VFM ON VACUUM SENSOR RELIEF VALVE PRESENT
8 DISP 13-14 PS ON
9 87 PRODUCT ON DEVICE LABEL RELIEF VALVE
10 87 91 VAPOR ON 9 87 PRODUCT NO
11 87 VENT ON 12 91 PRODUCT ON 10 87 91 VAPOR NO
13 91 VENT ON 11 87 VENT NO
14 DIESEL PRODUCT ON 12 91 PRODUCT NO
15 PMC CANISTER ON 13 91 VENT NO 16 ATM P ON 14 DIESEL PRODUCT NO
17 DIESEL VENT ON 17 DIESEL VENT NO
18 OFF
19 OFF
20 OFF 21 OFF I72C00 22 OFF DEC 5' 2013 3:25 PM
23 OFF 24 OFF VACUUM SENSOR RELIEF VALVE PRESSURE
DEVICE LABEL RELIEF VALVE PRESSURE I72200 9 87 PRODUCT -9.0 PSI
DEC 5' 2013 3:24 PM 10 87 91 VAPOR -9.0 PSI 11 87 VENT -9.0 PSI
SMART SENSOR LABEL 12 91 PRODUCT -9.0 PSI 13 91 VENT -9.0 PSI
DEVICE LABEL 14 DIESEL PRODUCT -9.0 PSI
1 DISP 1-2 VFM 17 DIESEL VENT -9.0 PSI
2 DISP 3-4 VFM 3 DISP 5-6 VFM
4 DISP 7-8 VFM I74100
5 DISP 9-10 VFM DEC 5' 2013 3:25 PM 6 DISP 11-12 VFM 7 DISP 13-14 VFM 8 DISP 13-14 PS I74200
9 87 PRODUCT DEC 5' 2013 3:25 PM
10 87 91 VAPOR 11 87 VENT 12 91 PRODUCT I74300
13 91 VENT DEC 5' 2013 3:25 PM
14 DIESEL PRODUCT
15 PMC CANISTER 16 ATM P I74400
17 DIESEL VENT DEC 5' 2013 3:25 PM
18 19 20 I74600 21 DEC 5' 2013 3:25 PM 22 23 24 I74700 DEC 5' 2013 3:25 PM
I72300 DEC 5' 2013 3:24 PM I74800
DEC 5' 2013 3:25 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. I74900 661-873-9343 DEC 5' 2013 3:25 PM
I74B00
SMARTSENSOR ASSIGNMENT DEC 5' 2013 3:25 PM DEVICE LABEL CATEGORY 01 DISP 1-2 VFM AIR FLOW METER 02 DISP 3-4 VFM AIR FLOW METER I74COO
03 DISP 5-6 VFM AIR FLOW METER DEC 5' 2013 3:25 PM
04 DISP 7-8 VFM AIR FLOW METER
05 DISP 9-10 VFM AIR FLOW METER
06 DISP 11-12 VFM AIR FLOW METER I74D00 07 DISP 13-14 VFM AIR FLOW METER DEC 5' 2013 3:25 PM
08 DISP 13-14 PS VAPOR PRESSURE
09 87 PRODUCT VAC SENSOR
10 87 91 VAPOR VAC SENSOR I74EOO
11 87 VENT VAC SENSOR DEC 5' 2013 3:25 PM 12 91 PRODUCT VAC SENSOR 13 91 VENT VAC SENSOR 14 DIESEL PRODUCT VAC SENSOR I75100
15 PMC CANISTER VAPOR VALVE DEC 5' 2013 3:25 PM
16 ATM P ATM P SENSOR 17 DIESEL VENT VAC SENSOR 18 UNKNOWN I75200 DEC 5' 2013 3:25 PM
19 UNKNOWN
20 UNKNOWN 21 UNKNOWN I75300
22 UNKNOWN DEC 5' 2013 3:25 PM
23 UNKNOWN 24 UNKNOWN
25 UNKNOWN I75400
26 UNKNOWN DEC 5' 2013 3:25 PM 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN I75500
30 UNKNOWN DEC 5' 2013 3:25 PM 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN I75600
34 UNKNOWN DEC 5' 2013 3:25 PM
35 UNKNOWN
36 UNKNOWN I75700 37 UNKNOWN DEC 5' 2013 3:25 PM
38 UNKNOWN 39 UNKNOWN
40 UNKNOWN I75800 DEC 5' 2013 3:25 PM
I72700 DEC 5' 2013 3:24 PM I75900 DEC 5' 2013 3:25 PM
I72800 DEC 5' 2013 3:24 PM I75A00
DEC 5' 2013 3:25 PM
I72900 LINE LEAK LOCKOUT SETUP
Page 13
------
LOCKOUT SCHEDULE DAILY START TIME: DISABLED STOP TIME : DISABLED
I75B00
DEC 5' 2013 3:25 PM
I75coo DEC 5' 2013 3:25 PM
I75D00 DEC 5' 2013 3:25 PM
I75E00 DEC 5' 2013 3:25 PM
I75F00 DEC 5' 2013 3:25 PM
I7A600 DEC 5' 2013 3:25 PM
I7A700 DEC 5' 2013 3:25 PM
I7A800 DEC 5' 2013 3:25 PM
I7A900 DEC 5' 2013 3:25 PM
9999FF1B I7AC00 DEC 5' 2013 3:25 PM
I7AD00 DEC 5' 2013 3:25 PM
I7AE00 DEC 5' 2013 3:25 PM
I7AF00 DEC 5' 2013 3:25 PM
I7B100 ~G~LI~/; ~&HTI8~ 2 ~ PM METER -TANK MAP
BUS SLOT FUEL_P METER TANK -------------------------------
TANK MAP EMPTY
I7B200 DEC 5, 2013 3:25 PM
METER CALIBRATION OFFSET: 0. 000%
I7B400
DEC 5, 2013 3:25 P~f
I7BC00 DEC 5, 2013 3:25PM
I7BD00 DEC 5, 2013 3:25 PM
PRESSURE LLD SETUP REPORT
Q 1:87 UNLEADED
IN-TANK ALARMS T 1: HIGH WATER ALARM
T 1: LOW PRODUCT ALARM
L[Q~~~U~tN~~R~LMS
L 2: FUEL ALARM L 3: FUEL ALARM L 4: FUEL ALARM L 5: FUEL ALARM L 6: FUEL ALARM L 7: FUEL ALARM L 8: FUEL ALARM L 9: FUEL ALARM LlO: FUEL ALARM L22: FUEL ALARM L23: FUEL ALARM L 1: SENSOR OUT ALARM L 2: SENSOR OUT ALARM L 3: SENSOR OUT ALARM L 4: SENSOR OUT ALARM L 5: SENSOR OUT ALARM L 6: SENSOR OUT ALARM L ?:SENSOR OUT ALARM L 8: SENSOR OUT ALARM L 9: SENSOR OUT ALARM L10: SENSOR OUT ALARM Lll: SENSOR OUT ALARM L22: SENSOR OUT ALARM L23: SENSOR OUT ALARM L 1: SHORT ALARM L 2: SHORT ALARM L 3: SHORT ALARM L 4: SHORT ALARM L 5: SHORT ALARM L 6: SHORT ALARM L 7: SHORT ALARM L 8: SHORT ALARM L 9: SHORT ALARM LlO: SHORT ALARM Lll: SHORT ALARM Ll2: SHORT ALARM L22: SHORT ALARM L23: SHORT ALARM L12: HIGH LIQUID ALARM L 1: LOW LIQUID ALARM L 2: LOW LIQUID ALARM L 3: LOW LIQUID ALARM L 4: LOW LIQUID ALARM L 5: LOIY LIQUID ALARM L 6: LOIY LIQUID ALARM L 7: LOW LIQUID ALARM
Lll: LOW LIQUID ALARM Ll2: LOW LIQUID ALARM
Page 14
PRESSURE LINE LEAK
Q 1: PLLD OPEN ALARM
SMARTSENSOR ALARMS s10: FUEL ALARM
s 9: HIGH LIQUID ALARM s10: HIGH LIQUID ALARM sll: HIGH LIQUID ALARM
ISO SITE ALARMS ISO GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL
ISD HOSE ALARMS ALL: FLOW COLLECT FAIL
Q 2: 91 UNLEADED
IN-TANK ALARMS T 2: HIGH WATER ALARM T 2: LOW PRODUCT ALARM
LIQUID SENSOR ALMS L 1: FUEL ALARM
L 2: FUEL ALARM L 3: FUEL ALARM L 4: FUEL ALARM L 5: FUEL ALARM L 6: FUEL ALARM L 7: FUEL ALARM L13: FUEL ALARM L14: FUEL ALARM Ll5: FUEL ALARM L16: FUEL ALARM L17: FUEL ALARM L22: FUEL ALARM
L23: FUEL ALARM
L 1: SENSOR OUT ALARM L 2: SENSOR OUT ALARM L 3: SENSOR OUT ALARM L 4: SENSOR OUT ALARM L 5: SENSOR OUT ALARM
L 6: SENSOR OUT ALARM
L 7: SENSOR OUT ALARM Ll3: SENSOR OUT ALARM Ll4: SENSOR OUT ALARM L15 :SENSOR OUT ALARM Ll6: SENSOR OUT ALARM
L17: SENSOR OUT ALARM L22: SENSOR OUT ALARM L23: SENSOR OUT ALARM L 1: SHORT ALARM L 2: SHORT ALARM L 3: SHORT ALARM L 4: SHORT ALARM L 5 : SHORT ALARM L 6: SHORT ALARM L 7: SHORT ALARM L13: SHORT ALARM L14: SHORT ALARM Ll5 :SHORT ALARM L16: SHORT ALARM L17: SHORT ALARM L22: SHORT ALARM L23: SHORT ALARM t1l':r6~\i~3~5D At~~~M
L 2: LOIY LIQUID ALARM L 3: LOW LIQUID ALARM L 4: LOW LIQUID ALARM L 5: LOW LIQUID ALARM L 6: LOW LIQUID ALARM L 7: LOW LIQUID ALARM L17: LOW LIQUID ALARM
PRESSURE LINE LEAK Q 2: PLLD OPEN ALARM
SMARTSENSOR ALARMS s10: FUEL ALARM sl2: FUEL ALARM s13: FUEL ALARM s10: HIGH LIQUID ALARM s12: HIGH LIQUID ALARM s13: HIGH LIQUID ALARM
ISO SITE ALARMS ISD GROSS PRES FAIL ISO DEGRD PRES FAIL ISO VAPOR LEAK FAIL ISD VP PRES FAIL ISO VP STATUS FAIL
ISO HOSE ALARMS ALL: FLO\Y COLLECT FAIL
Q 3 :DIESEL
IN-TANK ALARMS T 3: HIGH WATER ALARM T 3: LOW PRODUCT ALARM
L[Q~~~u~tN~~MLMS
L 2: FUEL ALARM L 3: FUEL ALARM L 4: FUEL ALARM
L17: FUEL ALARM
L18 FUEL ALARM L19 FUEL ALARM L20 FUEL ALARM L21 FUEL ALARM L22 FUEL ALARM L23 FUEL ALARM L 1 SENSOR OUT ALARM L 2 SENSOR OUT ALARM
L 3 SENSOR OUT ALARM
L 4 SENSOR OUT ALARM Ll7 SENSOR OUT ALARM Ll8 SENSOR OUT ALARM Ll9 SENSOR OUT ALARM L20 SENSOR OUT ALARM
L21 SENSOR OUT ALARM L22 SENSOR OUT ALARM L23 SENSOR OUT ALARM L 1 SHORT ALARM L 2 SHORT ALARM
L 3 SHORT ALARM L 4 SHORT ALARM L17 SHORT ALARM L18 SHORT ALARM L19 SHORT ALARM L20 SHORT ALARM L21 SHORT ALARM L22 SHORT ALARM L23 SHORT ALARM t1i ~ij~H Li~3~5D At~~~M
L 2 LOW LIQUID ALARM L 3 LOW LIQUID ALARM L 4 LOW LIQUID ALARM
Ll7: LOW LIQUID ALARM
PRESSURE LINE LEAK Q 3: PLLD OPEN ALARM
SMARTSENSOR ALARMS s14: FUEL ALARM s17: FUEL ALARM
s14: HIGH LIQUID ALARM s17: HIGH LIQUID ALARM
I7BE00 DEC 5' 2013 3:25 PM
I7C400 DEC 5' 2013 3:25 PM
I7C500 DEC 5' 2013 3:25 PM
I7C600 DEC 5' 2013 3:25 PM
I7C700 DEC 5' 2013 3:25 PM
I7C800 DEC 5' 2013 3:25 PM
I7C900 DEC 5' 2013 3:25 PM
I80100 DEC 5' 2013 3:25 PM
EXTERNAL INPUT CONFIGURATION
DEVICE LABEL 1 EMERGENCY SHUT OFF
2
I80200 DEC 5' 2013 3:25 PM
EXTERNAL INPUT LABEL
DEVICE LABEL 1 EMERGENCY SHUT OFF 2
I80300 DEC 5' 2013 3:25 PM
EXTERNAL INPUT TYPE
INPUT NAME 1 EMERGENCY SHUT OFF 2
I80400 DEC 5' 2013 3:25 PM
I80600 DEC 5' 2013 3:25 PM
RELAY CONFIGURATION
DEVICE LABEL 1 OVERFILL 2
I80700 DEC 5' 2013 3:25 PM
RELAY LABEL
DEVICE LABEL
1 OVERFILL 2
I80800 DEC 5, 2013 3: 2 5 PM
RELAY SETUP REPORT
R 1: OVERFILL TYPE: STANDARD NORMALLY OPEN
TANK #: NONE
IN-TANK ALARMS ALL: OVERFILL ALARM ALL: HIGH PRODUCT ALARM
R 2: TYPE: STANDARD NORMALLY OPEN
TANK #: NONE
-NO ALARM ASSIGNMENTS -
I80900 DEC 5, 2013 3:26 PM
RELAY ORIENTATION
RELAY DESIGNATION 1 OVERFILL 2
I80A00 DEC 5, 2013 3:26 PM
RELAY TYPE
RELAY DESIGNATION 1 OVERFILL 2
I80B00 DEC 5, 2013 3:26 PM
CONFIGURED ON OFF
TYPE
STANDARD
STANDARD
CONFIGURED ON OFF
ORIENTATION NORMALLY OPEN NORMALLY OPEN
TYPE STANDARD STANDARD
ORIENTATION
NORMALLY OPEN
NORMALLY OPEN
TANK#
Page 15
RELAY TANK ASSIGNMENT
RELAY DESIGNATION 1 OVERFILL 2
I80coo DEC 5' 2013 3:26 PM
EXTERNAL INPUT TYPE
INPUT NAME 1 EMERGENCY SHUT OFF 2
I85100 DEC 5' 2013 3:26 P~l
RESTORE SETUP DATA: DISABLED
I85200 DEC 5' 2013 3:26 PM
SAVE SETUP DATA: DISABLED
I85300 DEC 5' 2013 3:26 PM
CLEAR SETUP DATA: DISABLED
I88100 DEC 5' 2013 3:26 PM
I88200 DEC 5' 2013 3:26 PM
I88500
DEC 5' 2013 3:26 PM
I88600 DEC 5' 2013 3:26 PM
I88700 DEC 5' 2013 3:26 PM
I88800 glj~M ~6A~g13 : 3:26 PM
1 ~EDIM CONNECTION NO E
COMM BOARD 2 ~S-SAT ) CONNECTION NO E
COMM BOARD 5 ~RS-485) CONNECTION NO E
COMM BOARD 6 (RS-232) CONNECTION NONE
I88900 DEC 5' 2013 3:26 PM
I88DOO DEC 5' 2013 3:26 PM
I89100 DEC 5' 2013 3:26 PM
I8A200 DEC 5, 2013 3:26 PM
FOODS CO. 384 2505 HALEY BAKERSFIELD CA. 661-873-9343
SERVICE CODE LIST
STANDARD LABEL CODE ~6mo~~~~~~st~~ 8i82 ~~n~~ll~E~c F~s~~D 818~ NO SOLUTION FOUND 0105
OTHER SOLUTION 0106 REPLACED KEYBOARD 0107 REPLACED DISPLAY 0108 SYSTEM UPGRADE 0109 CONDUCTED TRAINING 0110
OPERATOR ERROR 0111 INSTALLED PAPER 0201 REPLACED PRINTER 0202 NEW LINE SHARE DEY 0203 CLEARED PAPER JAM 0204
REMOVED TANK WATER 0301 PRECISION TANK TEST 0302 RECONNECTED PROBE 0303 REPLACED PROBE 0304 FIX STUCK FLOAT 0305
CLEANED PROBE 0306 CORRECT TANK CHART 0307 RESET ACCUCHART 0308 REPLACED SENSOR 0401 REWIRED SENSOR 0402 REMOVED FUEL 0403
REMOVED WATER 0404 ADJUSTED BRINE LVL 0405 REPAIRED PRIMARY LK 0406 REPAIRED SEC LK 0407 RECHARGED VACUUM 0408
REPLACED VAC TUBING 0409 ADDED COMM BOARD 0501 RESET MODEM 0502 RECONNECT PHONE LN 0503 NEW PHONE NUMBER 0504 NEW IP ADDRESS 0505 REPLACED COMM CABLE 0506 REPLACED DIM MODULE 0601 REPLACED DIM CABLE 0602 DIM MISAPPLICATION 0603 CAB RUN MODE 0604 REPAIRED LEAK 0701 REPAIRED STP CAP 0702 RESTORE STP POWER 0703 CLEAN FUNC ELEMENT 0704 DISBLE FUNC ELEMENT 0705 OUT OF FUEL 0706 REPL LLD TRANSDUCER 0707 REWIRED LLD 0708 REPLACED LLD MODULE 0709 REPLACED CHECK VLV 0710 REPLACE PRODUCT RL Y 0711 REPLACE DISP VALVE 0712
TANK NONE NONE
TYPE STANDARD STANDARD
ORIENTATION NORMALLY OPEN NORMALLY OPEN
TANK#
ELIM WPLLD NOISE 0713 INSTALL MECH LLD 0714 PERFORM LINE TEST 0715 REPLACED MLLD 0716 INSTALL NEW STP 0801 REPLACED UMP 0802 REPL FUNC ELEMENT 0803 REPL CHECK VALVE 0804
PMP NEW IP ADDRESS 0805 REPL CONTROL BOX 0806 REPLACED CAPACITOR 0807 REPLACED SEALS 0808 REPL VAR SPD CNTRL 0809 mcReeLbU~bNTROL 8~5~
REPL VLLD CHECK VLV 0902 VLLD SELF CHECK 0903 VLLD PUMP SELF TST 0904 VLLD OTHER ACTION 0905 CAL VAC ASSIST PUMP 1001
CONDUCTED A/L TEST 1002 BACK PRESSURE TEST 1003 2 IN DECAY TEST 1004 10 IN DECAY TEST 1005 REPAIRED CONT LEAK 1006 RPR VAC ASSIST PUMP 1007 REPL VAC ASSIST PMP 1008 ADJUSTED A/L 1009 SVC VAPOR PROCESSOR 1010 RPR SPILL BUCKET 1101 RPR DELIVERY CAP 1102 RPR VPR EXTR CAP 1103 RPR PROBE RISER CAP 1104 REPLACED FILTER 1201 REPL DISPENSER SW 1202 COLD BOOT SYSTEM 1203 REPAIRED DISPENSER 1204 RESET SHEAR VALVE 1205 REPL SHEAR VALVE 1206 REPAIRED PIPING 1207 REPAIRED BOOT 1208 CALIS LIQUID MTR 1209 REPL DISPENSER PRTR 1210 INSTALLED PAPER 1211 CLEARED PAPER JAM 1212
REPAIRED DOOR LOCK 1213 REPAIRED DOOR SW 1214 REPL HANGING HW 1301 REPLACED NOZZLE 1302 REPLACED BOOT 1303 REPLACED SPOUT 1304
REPL PRIMARY HOSE 1305 REPLACED BREAKAWAY 1306 REPAIRED BREAKAWAY 1307 REPLACED WHIP HOSE 1308 REPL HOSE EXTRACTOR 1309
REPL FLOIY LIMITER 1310
REPL NOZZLE COVER 1311 BAGGED OFF NOZZLE 1312 RETURNED NOZZLE 1313 REPROGRAMMED POS 1401 REPL POS SOFTWARE 1402 COLD BOOT SYSTEM 1403 REPLACED POS 1404 REWIRED POS 1405 RPR OUTSIDE LIGHTS 1501 REPAIRED SIGNAGE 1502 CLEANED STORM DRAIN 1503 SVC OIL WTR SEPRATR 1504 ANN OPERABILITY TST 1601 WEIGHT MEASURES TST 1602 6~~kAf~~Ee~~H TST 1~8~ ~~~LlE~8cKET TEST 1~8~
USER DEFINED LABEL CODE NONE
I8A300 DEC 5, 2013 3:26 PM
I8A400 DEC 5, 2013 3:26 PM
I8BC00 DEC 5, 2013 3:26 PM
RELAY SETUP REPORT
R 1: OVERFILL TYPE: STANDARD
NORMALLY OPEN
TANK #: NONE
IN-TANK ALARMS
ALL: OVERFILL ALARM ALL: HIGH PRODUCT ALARM
R 2: TYPE:
STANDARD NORMALLY OPEN
TANK #: NONE
-NO ALARM ASSIGNMENTS -
I8C100
DEC 5' 2013 3:26 PM
I8C200 DEC 5' 2013 3:26 PM
9999FFlB9999FFlB I90100 DEC 5' 2013 3:26 PM
I/O SYSTEM BOARD PASS
I90200 DEC 5, 2013 3:26 PM SOFTWARE REVISION LEVEL
VERSION 330.01
SOFTWARE# 346330-100-B CREATED -10.07.23.17 .25
S-MODULE# 330160-104-a SYSTEM FEATURES:
PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS BIR ISD
RAM PROM PASS PASS
Page 16
I90300 DEC 5, 2013 3:26 PM PC DIAGNOSTIC DATA PERIPHERAL CONTROLLER
PC SWARE# 330269-002-B CREATED -94.12.16.13.26 PC ROM CHECKSUM = PASSED
PC RESET COUNTS = 91
PC COMM ERRORS = 63 MC CKSUM ERRS = 7 MC->PC COMMS =1158052404 MC<-PC COMMS =1158077687
I90500 DEC 5, 2013 3:26 PM SOFTWARE REVISION LEVEL
VERSION 330. 01
SOFTWARE# 346330-100-B CREATED-10.07.23.17.25
S-~IODULE# 330160-104-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS
BIR ISD
9999FFlB