HomeMy WebLinkAboutFMC 2014MONITORING SYSTEM CERTIFICATION For Use By All Jurisdictions Within the State of California Authority Cited: Chapter 6. 7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner/operator. The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date. A. General Information Facility Name: Metro Station Bldg. No.: ____ _ Site Address: 4600 Stine Road City: Bakersfield, CA Zip: .::...93:....:3:....:1...::.3 __ _ Facility Contact Person: George Farah Contact Phone No.: (661) 831-0836 Make/Model of Monitoring System: Veeder-Root TLS 350 Date ofTesting/Servicing: 3/19/2014 B. Inventory of Equipment Tested/Certified -----------I --~ •• ----------------"fi ----------dlserviced . - Tank ID: 12,000 gal. Regular 1 Tank ID: 12,000 gal. Regular 2 1811n-Tank Gauging Probe. Model: 847390-107 1811n-Tank Gauging Probe. Model: 847390-107 181 Annular Space or Vault Sensor. Model: 794390-420 181 Annular Space or Vault Sensor. Model: 794390-420 181 Piping Sump I Trench Sensor(s). Model: 794380-208 181 Piping Sump I Trench Sensor(s). Model: 794380-208 0 Fill Sump Sensor(s). Model: 0 Fill Sump Scnsor(s). Model: 181 Mechanical Line Leak Detector. Model: FX-1V 181 Mechanical Line Leak Detector. Model: FX-1V 0 Electronic Line Leak Detector. Model: 0 Electronic Line Leak Detector. Model: 181 Tank Overfill/ High-Level Sensor. Model: 847390-107 181 Tank Overfill/ High-Level Sensor. Model: 847390-107 0 Other (specifY equipment type and model in Section Eon Page 2). 0 Other (specifY equipment type and model in Section Eon Page 2). Tank ID: 12,000 gal. Su~er Tank ID: 12,000 gal. Diesel 181 In-Tank Gauging Probe. Model: 847390-107 181 In-Tank Gauging Probe. Model: 847390-107 181 Annular Space or Vault Sensor. Model: 794390-420 181 Annular Space or Vault Sensor. Model: 794390-420 181 Piping Sump I Trench Sensor(s). Model: 794380-208 181 Piping Sump I Trench Sensor(s). Model: 794380-208 D Fill Sump Scnsor(s). Model: 0 Fill Sump Sensor(s). Model: 181 Mechanical Line Leak Detector. Model: FX-1V 181 Mechanical Line Leak Detector. Model: FX-1 DV 0 Electronic Line Leak Detector. Model: 0 Electronic Line Leak Detector. Model: 181 Tank Overfill/ High-Level Sensor. Model: 847390-107 181 Tank Overfill I High-Level Sensor. Model: 847390-107 0 Other (specify equipment type and model in Section E on Page 2). 0 Other (specify equipment type and model in Section Eon Page 2). Dispenser ID: 1&2 Dispenser ID: 3&4 181 Dispenser Containment Sensor(s). Model: 794380-208 181 Dispenser Containment Sensor(s). Model: 794380-208 181 Shear Valvc(s). 181 Shear Valvc(s). 0 Dispenser Containment Float(s) and Chain(s). 0 Dispenser Containment Float(s) and Chain(s). Dispenser ID: 5 & 6 Dispenser ID: 7&8 181 Dispenser Containment Sensor(s). Model: 794380-208 181 Dispenser Containment Sensor(s). Model: 794380-208 181 Shear Valve(s). 181 Shear Valve(s). D Dispenser Containment Float(s) and Chain(s). 0 Dispenser Containment Float(s) and Chain(s). Dispenser ID: 9 & 10 Dispenser TD: 181 Dispenser Containment Sensor(s). Model: 794380-208 0 Dispenser Containment Sensor(s). Model: 181 Shear Valve(s). 0 Shear Valve(s). 0 Dispenser Containment Float(s) and Chain(s). 0 Dispenser Containment Float(s) and Chain(s). •If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility. C. Certification -I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers' guidelines. Attached to this Certification is information (e.g. manufacturers' checklists) necessary to verify that this information is correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also attached a copy of the report; (check all that apply): IZ! System set-up IZ! Alarm history report Technician Name (print): Bradley Seykora Signature:_.,....::, ~,Jr.:::::._ ~-4~---==--------- Certification No.: B40738 License. N~----=:8.::.04.:.9 :::..::....:..._ ____________ _ Testing Company Name: Confidence UST Services, Inc. Phone No.: (800) 339-9930 Site Address: 4600 Stine Road, Bakersfield, CA 93313 Date of Testing/Servicing: 3/19/2014 Page 1 of 3 Monitoring System Certification D. Results of Testing/Servicing Software Version Installed: ......::.3:::.3..:.;1.:.::0..::.0 _____________ _ c he foil heckr . .,'-• 18J Yes D No* Is the audible alarm operational? I8J Yes D No* Ts the visual alarm operational? I8J Yes D No* Were all sensors visually inspected, functionally tested, and confirmed operational? 18J Yes D No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not interfere with their proper operation? DYes D No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem) 18J N/A operational? I8J Yes D No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment D N/A monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate positive shut-down? {Check all that apply) I8J Sump/Trench Sensors; I8J Dispenser Containment Sensors. Did you confirm positive shut-down due to leaks and sensor failure/disconnection? l8l Yes; D No. 18J Yes D No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no D N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank fill point(s) and operating properly? If so, at what percent of tank capacity does the alarm trigger? 90% I8J Yes* D No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E, below. DYes* I8J No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) D Product; D Water. Tfyes, describe causes in Section E, below. 18J Yes D No* Was monitoring system set-up reviewed to ensure proper settings? Attach set up reports, if applicable 18J Yes D No* Is all monitoring equipment operational per manufacturer's specifications? * In Section E below, describe how and when these deficiencies were or will be corrected. E. Comments: The 91 and diesel grade LLD's were replaced during testing. Page 2 of 3 ~'f\D~+. 0 (\ ~ust ~ces.~ •OQHPc.JANC.CWJ'Ilot~ Leak Detector Test Results Sheet Customer Address: Work Order: 32144 Site Address: El Manahri, Inc. Test Date: 3/19/2014 Metro Station 4600 Stine Road Bakersfield, CA 93313 Site Contact: George Farah Technician: Bradley Seykora Phone: 661-831-0836 Phone: 800-339-9930 Product Type LLD Type Model Serial No. Regular UNL Mechanical FX1V N/A Regular UNL Mechanical FX1V N/A Premium UNL Mechanical FX1V N/A Diesel Mechanical FX1DV N/A Check Valve 4600 Stine Road Bakersfield, CA 93313 ICC No.: 8111231 Bleed Leak Off ML. Rate Holding Tested: Pressure 12 PSI 150ml 3gph@ 10 psi 12 PSI 150 ml 3gph@ 10 psi 2 PSI 35 ml 3gph@ 10 psi 10 PSI 95 ml 3gph@ 10 psi 3gph@ 10 psi 3 gph@ 10 psi 3gph@ 10 psi 3gph@ 10 psi Technician Name: ~ Signature: Technician No.: 8111231 3/19/2014 Date: / Pass/Fail Pass Pass Pass Pass METRO STAtiON 4600 STltlf...:ROAD ,BAKERSFIE~. CA ,., I ~ f I 1NAR 19. 2014 7:41 AN I SYSTEM STATUS REPORT ------------ALL FUNCTIONS NORMAL INVENTOR'/ REPORT T I :REGULAR 1 ~ VOLUME • 2892 GALS ULLAGE • 9108 GALS 901! ULLAGE.. 7908 GALS TC VOLUME • 2867 GALS HEIGHT • 28.01 INCHES WATER VOL • 0 GALS WATER • 0.00 INCHES TEMP • 71.0 DEG F T 2:REGULAR 2 VOLUME • 2896 GALS ULLAGE • 9104 GALS 9W. ULLAGE• 7904 GALS TC VOLUME • 2873 CAts HEIGHT • 28.03 INCHES WATER VOL • 0 GALS WATER = 0.00 INCHES TEMP • 70.1 DEG F T 3:SUPER ""VOI.:UME . • 2380 GALS ULLAGE • 9620 GALS 9W. ULLAGE• 8420 GALS f. TC VOLI..tiE "' 2357 GALS ·HEIGHT • 24.37 ltiCHES WATER VOL • 0 GALS -UATER .. 0. 00 1 NCHES' -TEMP • 72.8 DEG F T 4:DIESEL VOLUME • 3094 GALS ULLAGE • 8906 GALS 9W. ULLAGE• 7706 GALS TC VOLUME • 3079 GALS HEIGHT • 29,41 INCHES WATER VOL • 20 GALS WATER • 0. 97 1 NCHES TEMP • 71.6 DEG F MANIFOLDED TANKS ltNEflTORY TOTALS T l :REGULAR I T 2:REGULAR 2 VOLUME • 5786 GALS TC VOLUME • 5740 GALS X X X X * END X ~ * X X SOFTWARE REVISION LEVEL VERSION 331.00 SOFTWAREP 346331-100-A CREATED-11.02.10.12,31 S-MODULE~ 33DL60:D04-a SYSTEM FEATURES: PERIODIC IN-TAtlK TESTS ANNUAL IN-TAifK TESTS ISD/APM SYSTEM SETUP ------------MAR 19. 2014 7:41 AH S'ISTEM UNITS u.s. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TINE FORMAT NON DD Y'l\"1 HH :MM :ss >J1 METRO STATION 4600 STiflE ROAD BAAERSFIELD. CA SHIFT TINE I DISABLED SHIFT TINE 2 DISABLED SHIFT TIME 3 DISABLED SHIFT TIME 4 DISABLED TANK PER TST NEEDED WRN DISABLED TANK ANN TST NEEDED WRN DISABLED LINE RE-EfiABLE METHOD PASS 1.1 NE TEST LINE PER TST NEEDED WRtl DISABLED LINE ANti TST NEEDED WRN DISABLED PRINT TC VOLUMES ENABLED TEMP COMPENSATION VALUE <DEG F >: 60.0 STICK HEIGHT OFFSET DISABLED ULLAGE: 90¥. H-PROTOCOL DATA FORMAT HEIGHT DAYLIGHT SAVING TIME DISABLED RE-DIRECT LOCAL PRINTOUT DISABLED EURO PROTOCOL PREFIX s SYSTEM SECURITY CODE : 000000 HAI NTENANCE HISTORY DISABLED TANK CHART SECURITY DISABLED CUSTOM ALARMS DISABLED SERVICE NOTICE DISABLED ISO 3166 COUNTRY CODE: ---r VAPOR MOtnTORlNG TYPE CARB ISO MASS/DENSITY COt1'1UNICATIOtiS SETUP PORT SETTINGS: COHH BOARD : I <EDIH > RS-232 SECURITY CODE .: DISABLED COMM BOARD : 2 <RS-232> BAUD RATE : 9600 PARITY : tlONE STOP BIT : 1 STOP DATA LENGTH: 9 DATA RS-232 SECURITY CODE ; DISABLED COMM BOARD : 3 <RS-232> BAUD RATE ; 1200 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 9 DATA RS-232 SECURITY CODE : DISABLED AUTO TRANSMIT SETTltlGS: AUTO LEAK ALARM LIMIT DISABLED AUTO HIGH WATER LIMIT DISABLED AUTO OVERFILL LIMIT DISABLED AUTO LOW PRODUCT DISABLED AUTO THEFT LIMIT DISABLED AUTO DELIVERY START DISABLED AUTO DELIVERY END DISABLED AUTO EXTEP.NAL INPUT ON DISABLED AliTO EXTEP.NAL I NPliT OFF DISABLED AUTO SENSOR FUEL ALARM DISABLED AUTO SENSOR WATER ALARM DISABLED AUTO SENSOR OUT ALARH DISABLED RS-232 END OF MESSAGE DISABLED HI-TANK SETUP T I :REGULAR I PRODUCT CODE THERMAL COEFF TANK DIAMETER "TANK PROFILE FULL VOL FLOAT SIZE: 1 .000750 96.50 1 PT 12000 4,0 IN. WATER WARNING : 1.5 HIGH WATER Lll·llT: 3.0 WATER ALARM FILTER: LOW MAX OR LABEL VOL: 12000 OVERFILL LIMIT : SOY. : 10800 HIGH PRODUCT : 95Y. : 11400 DELIVERY LIMIT : 15% : 1800 LOW PRODUCT : 400 LEAY. ALARM LIMIT: 99 SUDDEN LOSS LIMIT: 99 TANK TILT : 0.00 PROBE OFFSET : 0.00 SIPHON MANIFOLDED TAIIKS Til: NONE LINE MANIFOLDED TAIIKS Tit: 02 LEAK MIN PERIODIC: 0% 0 LEAK HI N ANNUAL : 0% 0 PERIODIC TEST TYPE STAIIDARD ANNUAL TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED GROSS TEST FAIL ALARM DISABLED Atltl TEST AVERAGING: OFF PER TEST AVERAGING: OFF TAIIK TEST NOTIFY: OFF TNX TST SIPHON BREAY.:OFF DELIVER\' DELAY : 5 MIN PU·IP THRESHOLD : IO.OW. T 2:REGULAR 2 PRODUCT CODE THERMAL COEFF TANK DIAMETER TAN~ PROFILE FULL VOL 2 .000?50 96.50 I PT 12000 FLOAT SIZE: 4.0 IN. WATER WARNING : 2.0 HIGH WATER LIMIT: 3.0 WATER ALARM FILTER: LOW MAX OR LABEL VOL: OVERFILL LIMIT HIGH PRODUCT DELIVER\' LH11T LOW PRODUCT : LEAK ALARM LIMIT: SUDDEN LOSS LIMIT: TA~ TILT PROBE OFFSET 12000 90Y. 10800 95!'. 11400 1~~ 1800 400 99 99 0.00 o.oo SIPHON MANIFOLDED TANKS Til! tiOIIE LINE MANIFOLDED TANKS Til: 01 LEAK MIN PERIODIC: . LEAl: MIN ANNUAL : 0% 0 OY. 0 PERIODIC TEST TYPE STANDARD ANNUAL TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED GROSS TEST FAIL ALARM DISABLED ANN TEST AVERAGING: OFF PER TEST AVERAGING: OFF TAtiK TEST NOTIFY: OFF TNK TST SIPHON BREAK:OFF DELIVERY DELAY : 5 MIN PUMP THRESHOLD : 10.00% T 3:SUPER PRODOCT CODE THERMAL COEFF TANK DIAMETER TANK PROFILE FULL VOL FLOAT SIZE: 3 .000750 96,50 I PT 12000 4.0 IN. WATER WARNWG : 1.5 HIGH WATER LIMIT: 2.0 WATER ALARI1 FILTER: LOW t1AX OR LABEL VOL: 12000 OVERFILL LIMIT : 90% : 10800 HIGH PRODUCT : 95% : 11400 DELIVERY LIMIT : 15% : 1800 LOW PRODUCT : 400 LEAK ALARI1 LIMIT: 99 SUDDEN LOSS LIMIT: 99 TANK TILT : 0,00 PROBE OFFSET : 0.00 SIPHON MANIFOLDED TAtiKS Til: tl<>tiE LINE MANIFOLDED TANKS Til: NONE LEAK MIN PERIODIC: LEAK MIN ANNUAL : . 0% 0 0% 0 PERIODIC TEST TYPE STANDARD ANNUAL TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED GROSS TEST FAIL ALARM DISABLED AtiN TEST AVERAGING: OFF PER TEST AVERAGING: OFF TANK TEST tlOTIFV: OFF TNK TST SIPHON BREAK:OFF DELIVERY DELAY : 5 Hill Pl.t1P THRESHOLD : lO.OOY. T 4:DIESEL PRODUCT COPE THERMAL COEFF TAtiK DIAttETER TAtn: PROFILE FULL VOL FLOAT SIZE: 4 .000450 96.50 I PT 12000 4.0 IN. WATER WARNING : 2.0 HIGH WATER LIHIT: 3.0 WATER ALARM FILTER: LOW HAX OR LABEL VOL: OVERFILL LIMIT : HIGH PRODUCT . DELIVERY LIMIT : . LOW PRODUCT : LEAK AlARM LIMIT: SUDDEN LOSS LIMIT: TAM{ TILT : PROBE OFFSET : 12000 90% 10800 95Y. 11400 15~ 1800 400 99 99 o.oo o.oo SIPHON MANIFOLDED TAW\S Til: NONE LINE MANIFOLDED TANKS Til: fiOtiE LEAK MIN PERIODIC: . . 0% 0 PERIODIC TEST TYPE STAtlDARD PERIODIC TEST FAIL AlARH DISABLED CROSS TEST FAIL ALARM DISABLED PER TEST AVERAGING: OFF TANK TEST NOTIFY: OFF TtlK TST SIPHON BREAK:OFF DELIVERY DELAY : 5 HIN Plt1P THRESHOLD : 10.00% LEAK TEST f'1ETHOD TEST ON DATE : ALL TANK FEB 10. 2011 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATIOtl : 2 HOURS TST EARLY STOP:DISABLED LEAK TEST REPORT FORMAT NORMAL LIQUID SENSOR SETUP . L I :DISP 1-2 : TRI-STATE <SINGLE FLOAT> ' CATEGORY : DISPENSER PAN L. 2!DISP 3-4 TRI-STATE <SINGLE FLOAT> CATEGORY : DISPENSER PAN L 3!DISP 5-6 TRI-STATE <SINGLE FLOAT) CATEGORY : DISPENSER PAN L 4:DISP 7-8 TRI-STATE <SINGLE FLOAT> CATEGORY : DISPENSER PAN L 5!DISP 9-10 TRI-STATE <SINGLE FLOAT> CATEGORY : DISPENSER PAN L 9!REGULAR I STP TRI-STATE <SINGLE FLOAT> CATEGORY : STP SUMP LIO:RECULAR I ANtl TRI-STATE <SINGLE FLOAT> CATEGORY : ANNULAR SPACE Ltt:REGULAR 2 STP TRI-STATE <SINGLE FLOAT> CATEGORY : STP Slt1P L12!REGULAR 2 ANN TRI-STATE (SINGLE FLOAT> CATEGORY : ANNULAR SPACE L13!SUPER STP TRI-STATE <SINGLE FLOAT> CATEGORY : STP Slt1P L14 !SUPER AWl TRI-STATE <SINGLE FLOAT> CATEGORY : ANNULAR SPACE LIS:DIESEL STP TRI-STATE <SINGLE FLOAT> CATEGORY : STP SUMP LIG!DIESEL ANN TRI-STATE <SINGLE FLOAT> CATEGORY : ANNULAR SPACE Pll'1P SENSOR SETUP S I :REGULAR I TANK ;t: I DISPENSE MODE: MANIFOLDED: ALTERNATE S 2:REGULAR 2 TANK 11: 2 DISPENSE NODE: MAtliFOLDEO: ALTERNATE OliTPUT RELAY SETUP R I !REGULAR I TYPE: PUMP CONTROL OUTPUT TANK 11: I ltl-TAtlK ALARMS T 1 :HIGH WATER ALARM T 1 !LOW PRODUCT ALARM LIQUID SENSOR AlJ1S L 2:FUEL AlARH L 3!FUEL AlARM L 4:FUEL AlARM L 5!FUEL ALARM L 9:FUEL ALARM LII:FUEL ALARM L 2!SENSOR OUT ALARM L 3:SENSOR OUT ALARM L 4:SENSOR OUT ALARM L 5:SENSOR OUT ALARM L 9:SENSOR OUT ALARM Lll :SENSOR OUT ALARM L 2:SHORT ALARM L 3:SHORT ALARM L 4!SHORT ALARM L 5:SHORT AL.ARM L 9:SHORT AlARM L11 :SHORT ALARM ISO SITE AlARMS ISO GROSS·PRES FAI~ lSD DEGRD PRES FAIL lSD VAPOR LEAK FAIL lSD VP PRES FAIL lSD VP STATUS FAIL lSD SETUP FAIL lSD SENSOR OUT FAIL PC-lSD FAILURE lSD HOSE ALARMS ALt:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL!FLOW COLLECT FAIL R 2:RECULAR 2 T'iPE: Plt1P CotiTROL OUTPUT TANK ll: 2 IN-TANK ALARMS T 2:HIGH I.-lATE?. ALARM T 2:LOW PRODUCT ALARM LIQUID SENSOR ALMS L 2:FUEL ALARM L 3:FUEL ALARM L 4 :FUEL ALARH L S:FUEL ALARH L 9:FUEL ALARM Lll :FUEL ALARM L 2:SEtlSOR OUT ALARM L 3:SENSOR OUT ALARH L 4 :SENSOR OUT ALARM L S:SENSOR OUT AlARM L 91SEflSOR OUT ALARM Lll :SENSOR OUT AlARM L 2:SHORT ALARM L 3 :SHORT ALARM L 4 :SHORT ALARM L 51SHORT AlARM L 9:SHORT AlARM Lll :SHORT AlARM ISO SITE ALARMS lSD GROSS PRES FAIL lSD DEGRD PRES FAIL lSD VAPOR LEAK FAIL lSD VP PRES FAIL lSD VP STATUS FAIL lSD SETUP FAIL lSD SENSOR OUT FAIL PC-lSD FAILURE ISO HOSE ALARMS ALL:CROSS COLLECT FAIL ALL:OECRD COLLECT FAIL ALL:FLOU COLLECT FAIL R 3:SUPER TYPE: STAtiDARD NORMALLY CLOSED TANK ll: 3 IN-TANK ALARMS T 3:HIGH WATER ALARM T 3:LOW PRODUCT ALARM LIQUID SENSOR ALMS L 2:FUEL AlARM L 3:FUEL ALARM L 4:FUEL ALARM L S:FUEL ALARM Lt3:FUEL ALARM L 21SEtlSOR OUT ALARM L 3:9ENSOR OUT ALARM L 4 :SENSOR OUT AlARM L S:SEflSOR OUT ALARM Ll31SENSOR OUT ALARM L 2!SHORT ALARH L 31SHORT ALARM L 4:SHORT ALARM L S:SHORT ALAJ(I1 L13:SiiORT ALARM ISO SITE Al.AAMS lSD GROSS PRES FAIL lSD DEGRD PRES FAIL ISO VAPOR LEAK FAIL lSD VP PRES FAIL lSD VP STATUS FAIL ISO SETUP FAIL lSD SENSOR OUT FAIL PC-ISO FAILURE lSD HOSE ALARMS ALL!CROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 4!DIESEL TYPE: STANDARD NORMALLY CLOSED TANK 11: 4 I N·TANK AlARMS T 4 :HIGH WATER ALARM T 41LOW PRODUCT AlARM LIQUID SENSOR ALMS L I :FUEL ALARM L 2:FUEL ALARM L ::l:FUEL AlARM L 151 FUEL ALARM L 1 :SENSOR OUT ALAJ<M L 21SEtiSOR OUT ALAR~I L ::l:SEtiSOR OUT ALARM L15:SENSOR OUT Al.AJ<H L I :SHORT ALAJ<M L 2 :SHORT ALARM L ::l!SHORT AtAJ<M LIS:SHOJ<T ALARM j R 5:0VERFILL ALARM ! TYPE: ! STANDAJ<D NORMALLY OPEN TANK 11: NONE I N·TAtu: ALARMS AtL:OVERFILL ALARM ALLIHIGH PRODUCT ALARM SMARTSENSOR SETUP 5 2:FM 3-4 CATEGORY AIR FLOW METER :s 3:FH 5-6 CATEGORY AIR FLOW METER :1 4:FH 7-8 CATEGORY AIR FLOW METER ::~ s:FH 9-to CATEGORY AIR FLOW METER :1 6!VP PRESSURE SEN. CATEGORY VAPOR PRESSURE :1 ?:CANISTER CATEGORY VAPOR VALVE :s e:ATH P SENSOR CATEGORY ATH P SENSOR I EVRI'ISD SETUP I ! EVR TYPE: BALANCE BALANCE NOZZLE TYPE vsr ; VAPOR PROCESSOR TYPE VEEDER-ROOT POLISHER I ANALYSIS TIMES II TIME: 11:59 PH DELAY NINLITES: ! ACCEPT HIGH ORVR: E~IABLED lSD HOSE TABLE ID FP FL HL AA RR 01 03 03 02 01 03 02 04 04 02 01 03 03 05 05 02 02 03 04 06 06 02 02 03 05 07 07 02 03 03 06 08 08 02 03 03 07 09 09 02 04 03 OB 16 10 02 04 03 lSD AIRFLOW METER MAP ID SERIAL NU.'1 LABEL I 40348 2 40070 3 40350 4 40356 FN 3-4 FN 5-6 FN 7-8 FN 9-10 lSD FUEL GRADE HOSE HAP I 2 3 4 FP MHH MHH MHH MHH AA ---·-·--------------01 I U U U U U U U 0 02 2 u u u u u u u 0 03 201 101 901 3 u 1 04 202 102 902 3 U I OS 203 103 903 3 U 2 06 204 104 904 3 u 2 07 105 905 205 u u 3 09 206 106 906 u u 3 09 207 107 907 u u 4 16 209 lOB 908 U U 4 LABEL TABLE I UNASSIGUED 2 BLEND3 3 REGULAR 4 HID GRADE 5 PREMIUM 6 GOLD 7 BRONZE B SILVER 9 BLEND2 10 BLEND4 PMC SETUP ~ VERSION: 01.04 VAPOR PROCESSOR TYPE VEEDER-ROOT POLISHER ALARM HISTOR'I REPORT -----SENSOR ALARM -----L 1 :DtSP 1-2 DISPEIISER PAll SENSOR OUT ALARM MAR 25. 2013 1:49 PH FUEL ALARM MAR 25. 2013 1:42 PH SETUP DATA WARNitlG APR 17. 2012 11:56 AM M M M M ~ END ~ K K K K ALARM HISTORY REPORT -----SENSOR ALARM -----1. 2:DISP 3-4 DISPENSER PAN FUEL ALARM MAR 25. 2013 2:34 PM FUEL ALAP.M MAR 25. 2013 1:57 PH SENSOR OUT ALARM MAR 25. 2013 1:49PM K K K M K END M K M K K ; ALARM HISTORY REPORT : -----SENSOR ALARM ----- 1 1 1. 3:DISP 5-6 DISPEtiSER PAtl ' FUEl. Al.ARM AUG 30. 2013 10:59 AM SENSOR OUT ALARM NAR 25. 2013 1:49PM FUEL ALAP.t1 -MAR 25. 2013 I :43 PI-I K * M * K END K M K M M ALARM HISTORY REPORT -----SEtiSOR ALARM -----1. 4:DISP 7-8 DISPENSER PAN SENSOR OUT ALARM MAR 25. 2013 1:49PM FUEL ALARM MAR 25. 2013 1:44PM SETUP DATA WARtH NG APR 17. 2012 11:56 AM M M M M K END K M M M M ALARM HISTORY REPORT -----SENSOR ALARM -----L 5:DlSP 9-10 DlSPEUSER PAN SENSOR our ALAAt1 t1AR 25. 2013 1 :49 PN FUEL ALARM MAR 25. 2013 1:46PM SETUP DATA WARNING APR 17. 2012 11:56 AM ;; ~< ;.; ;.; >i END i\ M )( M * ALAR/'1 HISTORY REPORT -----SENSOR ALARM -----L 9:RECULAR 1 STP STP SUMP SENSOR our ALARM MAR 25. 2013 1:49PM FUEL ALARM NAR 25. 2013 1:37PM SETUP DATA ~RtHNG APR 17. 2012 11:56 AH j( x j( j( j( EtiD x x !t. j( j( l ALARM HISTORY REPORT -----SENSOR ALARM -----LIO:RECULAR I ANN ANNULAR SPACE SENSOR OUT ALARM NAR 25. 2013 1:49PM FUEL ALARM HAR 25. 2013 t:39 PM SETUP DATA WARNING APR 17. 2012 11:56 AM W M M M M END M M M M M ALARt1 HISTORY REPORT -----SENSOR ALARM -----LII:RECULAR 2 STP STP SUMP SENSOR OUT ALARM MAR 25. 2013 1:49 PH FUEL ALARM MAR 25. 2013 t:35 PM SETUP DATA ~RNING APR 17. 2012 11:56 AM M )( M * M END K * K * )( ALARM HISTORY REPORT -----SENSOR ALARM -----LI2:RECULAR 2 ANtl ANNULAR SPACE SENSOR our ALARM NAR 25. 2013 1:49PM FUEL ALARM MAR 25. 2013 I :36 Pt1 SETUP DATA WARti!NG APR 17. 2012 11:56 AM j( * M j( )( END * M ~ j( j( ALARM HISTORY REPORT -----SENSOR ALARM -----Lt3:SUPER STP STP SUMP SENSOR OUT ALARM MAR 25. 2013 1:49PM FUEL ALARM MAR 25. 2013 1:39PM SETUP DATA WARNING APR 17. 2012 11:56 AM * M M M M END * >i * ;.; M ALARM HISTORY REPORT ----SENSOR ALARM -----Lt4:SUPER ANtt ANNULAR SPACE SENSOR Our ALARl1 MAR 25, 2013 1:49PM FUEL ALARM MAR 25. 2013 1:38 PN SETUP DATA WARNING APR 17, 2012 11:56 AH M M M M M E~D M M M M M ALARM HISTORY REPORT -----SENSOR ALARM ----l.t5:DIESEL STP STPSUMP FUEL ALARM NOV 21. 2013 8:48PM FUEL ALARM NOV 21. 2013 8:46 FH FUEL ALARM NOV 21. 2013 7:31 PM M M M M K END M M M M M ALARM HISTORY REPORT ----SEilSOR ALARM -----L16:DIESEL ANN ANNULAR SPACE SENSOR Our ALARM MAR 25, 2013 1:49PM FUEL ALARM MAR 25. 2013 1:34 PH SETUP DATA WAR Ill NG APR 17, 2012 11:56 AM M * * * )( END M M ;; M M IN-TAI~K ALARH -----T 4:DIESEL DELIVERY llEEDED MAR 19. 2014 9:32AM 1----IN-TANK ALARH -----T 4:01ESEL PROBE OlJT MAR 19. 2014 9:32 AH ----IN-TANK ALARM ---;- T 2:REGULAR 2 • . SUDDEN LOSS ALARM -~ MAR 19. 2014 9:33AM ----IN-TANK ALARM -----T 2:REGULAR 2 DELIVERY NEEDED MAR 19. 2014 9:33AM ----IN-TANK ALARI-1 -----T 2:RECULAR 2 PROBE OUT MAR 19. 2014 9:34 AM ----I N-TAtiK ALARM -----T 1 :REGULAR. I . SUDDEf4LOSSc-ALARM .. --··· f1AR 19,· 20r.r:·9~·M- ----lfl-TANK ALARM -----T I :REGULAR I DELIVERY NEEDED MAR 19. 2014 9:34 AM ----IN-TANl: ALARM ----- T I :REGULAR I PROBE OUT HAP. 19. 2014 9:34 AM ----IN-TANK ALAP.H -----1 T 2:REGULAR 2 LOW TEHP WAR Ill NG 11AR 19. 2014 9:34 AH IN-TANK ALARM -----T 3:SUPER DELIVERY NEEDED MAR 19. 2014 9:34 tV'! ----lfi-TAtlh ALARM -----T 3:SUPER PROBE OUT HAR 19. 2014 9:35 AN -~-~-----. ----lN-TANY. ALAP.M -----T 1 :REGULAR 1 WVALlD FUEL LEVEL HAR 19. 2014 9:35 AH ----IN-TANK ALARM -----T I :REGULAR I HIGH WATER WARtHNG HAR 19. 2014 9:39AM I -----SENSOR ALARM -----L16:DIESEL AWl ANNULAR SPACE FUEL ALARM NAR 19. 2014 9:46AM -----SENSOR ALARM -----1.12:REGULAR 2 ANN ANNULAR SPACE FUEL ALARM t~R 1~. 2014 9:46 AM -----SENSOR ALARM -----LJO:REGULAR 1 ANN ANNULAR SPACE FUEL ALARM MAR 19. 2014 9:47 AM -----SENSOR ALARM -----Lt4:SUPER ANN ANNULAR SPACE FUEL ALARM MAR 19. 2014 9:48AM T 1 :RECULAR 1 ItNEilTORY ttiCREASE II.CREASE STAP.T HAR 19• 2014 9:41 AM T 1: INVALID FUEL LEVEL VOLUME -545 GALS HEIGHT " 9,80 INCHES WATER = 1.51 lt~HES TEMP = 68.5 DEG F INCREASE Etm MAR 19. 2014 9:49 AH VOLLtiE I HEIGHT WATER TEMP -9650 GALS • 72.34 INCHES • 0.00 INCHES oo 69,7 DEG F GROSS IriCREASE'" 9105 TC NET INCREASE• 9038 T 2:REGULAR 2 I tl\IENTORY I IICREASE I NCR EASE START MAR 19. 2014 9:41 AM VOLLtiE HEIGHT WATER TEMP • 9817 GALS oo 73.57 INCHES .. 0.00 INCHES oo 70.1 OEG F I tiCREASE END MAR 19. 2014 9:48AM VOLUME HEIGHT WATER TEMP A 9917 GALS • 73.57 INCHES • 0.00 INCHES " 70.2 DEG F CROSS INCREASE"' 0 TC NET INCREASE• -1 MANIFOLDED TANKS INVENTOR\' INCREASE T 1 :REGULAR I T 2:RECULAR 2 VOLUME • 9105 GALS . ---· ·--·- -----SENSOP. ALARM -----Ll3:SUPER STP STP SUMP FUEL ALARM MAR 19. 2014 9:50AM METRO STATION 4600 STINE ROAD BAKERSFIELD. CA MAR 19. 2014 9:51 AH S\'STEN STATUS REPORT ALL FUNCTIONS NORMAL -----SEtSOR ALARM -----LIO:REGULAR 1 ANN ANNULAR SPACE FUEL ALARM MAR 19. 2014 9:53AM -----SENSOR ALARM -----LI4:SUPER ANN ANflULAR SPACE FUEL AlAR/"1 MAR 19. 2014 9:54 AM -----SENSOR ALARM ----- L 9:REGULAR I STP STP 8UHP FUEL ALARI1 MAR 19.-2014 9:56 AM ' -----SENSOR ALARM ----- Ll1:REGULAR 2 STP STPSLt1P fUEL ALARM MAR 19. 2014 9:59 AM -----SENSOR ALARM -----LI5:0IESEL STP STPSUMP FUEL ALARM MAR 19. 2014 10:02 AM ----IN-TANK ALARM -----T 4:DIESEL HIGH PRODUv~ A~1 MAR 19. 2014 10:06 AM ----I N-TAf« ALARt1 -----T 4:DIESEL OVERfILL ALARM • MAR 19. 2014 10:08 AM ----IN-TANK ALARM -----T 4:0IESEL PROBE OUT HAR 19. 2014 1o:oa AM ----IN-TANK ALARM -----T 2:REGULAR 2 OVERFILL ALARM MAR 19. 2014 10:09 Al'l ----IN-TAW: ALAPJ1 -----T 2:REGULAP. 2 PROBE OUT MAR 19. 2014 10:10 AM T 4:DIESEL I NVEN'TOR'I INCREASE INCREASE START MAR 19. 2014 10:06 AM VOLUME • ?935 CAts HEIGHT • 60.61 lt-K:HES WATER -0. 00 INCHES TE11P • 74.9 DEC F INCREASE END MAR 19. 2014 10:13 AH VOLUME • 10152 GALS HEIGHT • 76.11 INCHES WATER .. 0.00 INCHES TEMP • 74.9 DEC F GROSS INCREASE• 2217 TC NET INCREASE• 2202 METRO STATION 4600 STINE ROAD BAKERSFIELD. CA MAR 19. 2014 10:13 AH SYSTEN STATUS REPORT ALL FUIICTlONS NORMAL PlttP SENSOR SETUP S I :REGULAR I TANK 11: I DISPENSE NODE: HAtHFOLOED: ALL PUMPS S 2:REGULAR 2 TANK 11: 2 DISPENSE HODE: MANIFOLDED: ALL PUt-IPS T I :REGULAR I I tNEtiTORY INCREASE lt.CREASE START MAR 19. 2014 10:09 AM VOLlJ1E HEIGHT WATER TEMP • 9650 GALS a 72.35 ltlCHES • 0.00 INCHES " 73.1 DEC F INCREASE END MAR 19. 2014 10:15 AM VOLUME HEIGHT WATER TEMP • 9650 GALS • 72.35 WCHES • 0.00 1t:CHES a 73.3 DEG F CROSS INCREASE• 0 TC NET INCREASE• -1 T 2:RECULAR 2 INVENTORY INCREASE INCREASE START MAR 19. 2014 10!09 AM VOLlJ1E HEIGHT WATER TEMP -9817 GALS • 73.57 INCHES • 0.00 INCHES " 74.4 DEC F I NCR EASE END MAR 19. 2014 10!15 AM VOLU!·IE HEIGHT WATER· TEMP • 11032 GALS -95;;39 INCHES ---0,00 INCHES .. 74.4 DEC F GROSS lt.CREASE= 1515 TC NET WCREASE:a 1499 MAtHFOLDED TANKS I NVEtiTOR'I INCREASE T 1 :REGULAR 1 T 2:RECULAR 2 VOLUME • 1515 GALS -----SENSOR ALARM -----L 1 !DISP 1-2 DISPENSER PAN FUEl. ALARM MAR 19. 2014 10:16 AI'! -----SEtlSOR ALARM -----L 2!DISP 3-4 DISPEt.SER PAfl FUEL ALARH f1AR 19. 2014 10!17 AM -----SENSOR ALARM -----L 3!DISP 5-6 DISPENSER PAN FUEL ALARM MAR 19. 2014 10!19 Al1 -----SEtlSOR ALARM ----L 4!DISP 7-B DISPEf.SER PAtl FUEL ALARM MAR 19. 2014 10:20 AM -----SEt.SOR ALARM ---L 5:D1SP 9-10 DISPENSER PAfl FUEL ALARM MAR 19. 2014 10:22 AM ----IN-TANK ALARM -----T I :REGULAR 1 OVERFILL ALARM MAR 19. 2014 10!24 AM ----IN-TANK ALARM -----T 1 :REGULAR 1 PR<lBE our MAR 19. 2014 10:24 AM ----IN-TANK ALARM -----T 3:SUPER OVERFILL ALAJ\'t1 MAR 19. 2014 10:26 AM ----IN-TANK ALARM -----T 3:SUPER DELIVERY NEEDED MAR 19. 2014 10!26 AN ----I N-TAflK ALARM -----T 3:SUPER PROBE our MAR 19. 2014 10:26 Al"l ----IN-TANK ALARM -----T 3!SUPER INVALID FUEL LEVEL MAR 19. 2014 10:27 AM ----I N-TAtiK ALARt1 -----T 3!SUPER HIGH WATER WARtHNG HAR 19. 2014 10!30 AM T I :RECut.AR I I NVENTOR'I I llCREASE I NCR EASE START MAR 19. 2014 10:25 AM VOLIJ1E HEIGHT WATER TEMP 0 GALS • 0.00 INCHES • 0.00 INCHES 0.0 DEC F INCREASE END MAR 19. 2014 10:30 AM VOLIJ1E HEIGHT WATER TEMP .. 11347 GALS " 86.55 WCHES c 0.00 ltlCHES • 74.5 DEC F GROSS ltiCREASE• 11347 TC !lET lllCREASE• 11222 T 2:REGUL.AR 2 I tNEIITORY INCREASE I tlCREASE START MAR 19. 2014 10:25 AM VOLUME HEIGHT l~ATER TEMP • 2875 GALS = 27.89 ltlCHES : 0.00 INCHES .. 70,3 DEC F I NCREASE END MAR 19. 2014 10:30 AM VOLIJ1E HEIGHT WATER TEMP • 2876 GALS • 27.90 ItiCHES • 0.00 INCHES • 70.3 DEC F CROSS INCREASE • TC NET ltiCREASEa MANIFOLDED TANYS INVENTORY INCREASE T I :REGut.AR I T 2:REGULAR 2 VOLUME • 11348 GALS ----I tl-TANK ALARM -----T 3:SUPER OVERFILL ALARM MAR 19. 2014 10!31 AN ----Itl-TANK ALARM -----T 3:SUPER PROBE OUT ~R 19. 2014 10:32 AM ----IN-TANK ALARM -----T 3:SUPER INVALID FUEL LEVEL MAR 19. 2014 10:32 AM ----I tl-TAtlK ALARM -----T 3:SUPER PROBE OUT MAR 19. 2014 10:32 AM ----ltl-TANK ALARM -----T 3:SUPER DELIVERY NEEDED MAR 19. 2014 10:33 AM T 3:SUPER I NVEtiTORV IIICREASE INCREASE START MAR 19. 2014 10:25 AM VOLUME HEIGHT WATER TEMP -10219 GALS • 76.63 IIICHES • 0.00 INCHES • 74.9 DEC F INCREASE END MAR 19. 2014 10:33 AH VOLUME HEIGHT WATER TEMP = 11350 GALS " 86.58 INCHES " 0.00 11\'CHES "' 74.9 OI::C F GROSS INCREASE= 1131 TC NET lt.'CREASE= I II 9 -----SENSOR ALARM -----L S:DISP 9-10 DISPENSER PAN SENSOR OUT ALARM MAR 19. 2014 10:40 AM -----SENSOR ALARH -----L 4:DISP 7-9 DISPEtSER PAN SEtSOR OUT ALARM MAR 19. 2014 10:40 AM -----SENSOR ALARM -----L I :DISP 1-2 DISPENSER PAN SENSOR OUT ALARM HAR 19. 2014 10:40 AM ----SEtiSOR ALARM ----- L 2:DISP 3-4 DISPENSER PAN SENSOR Our ALARM MAR 19. 2014 10:40 AM I ----SENSOR ALARM ----L 3:DJSP 5-6 DISPEUSER PAN SENSOR our ALARM MAR 19. 2014 10:40 AH ----SENSOR ALARI1 -----L 9:P.EGULAR 1 STP STP SllfiP SENSOR our ALARM MAR 19. 2014 10:40 AM -----SENSOR ALARM -----L12:REGULAR 2 ANti ANNULAR SPACE SENSOR our ALARM MAR 19. 2014 10:-10 Al·l ----SENSOR ALARM -----L13!SUPER STP STPSUMP SEtlSOR Our ALARM MAR 19. 2014 10:40 AM -----SEtSOR ALARM -----L10!RECULAR 1 Atltl ANNULAR SPACE SEtiSOR our ALARM MAR 19. 2014 10!40 AM -----SENSOR ALARM -----Lll !REGULAR 2 STP STP Sli1P SENSOR our ALARM MAR 19. 2014 10!40 AM -----SENSOR ALARM ----L14:SOPER AWl ANNULAR SPACE SENSOR Our ALARM MAR 19. 2014 10:40 AH -----SE~SOR ALARM ----- L15:DIESEL STP STP SUMP SENSOR OUT ALARM HAR 19. 2014 10:40 AM -----SENSOR ALARM ----L16:D1ESEL AfiN ANNULAR SPACE SENSOR Our ALARM MAR 19. 2014 10:40 AM T 3:SUPER I NVENTORV I tiCREASE J NCREASE START MAR 19. 2014 10:33 AM VOLli1E • 21:32 GALS HEIGHT • 22.54 INCHES WATER -0.00 INCHES TEMP • 79,4 DEC F INCREASE END NAP. 19. 2014 10:40 AM VOLLtfE HEIGHT WATER TEMP • 2379 CALS " 24.36 ltiCHES " 0.00 ltiCHES c 79.1 DEC F' CROSS INCREASE• 2~7 TC NET INCREASE• 244 METRO STATION 4600 STINE ROAD BAKERSFIELD. CA MAR 19. 2014 10!41 AM SYSTEM STATUS REPORT ALL FUNCTIONS tlORHAL SWRCB, January 2006 Spill Bucket Testing Report Form This form is intended f or use by contractors performing annual testing ofUST spill containment structures. The completed form and printouts from tests (if applicable), should be provided to the facility owner/operator for submittal to the local regulat01y agency. 1 FACILITY INFORMATION Facility Name: Metro Station I Date ofTesting: 3/19/2014 Facility Address: 4600 Stine Road Facility Contact: George Farah I Phone: 661-831-0836 Date Local Agency Was Notified of Testing: 2/6/2014 Name of Local Agency Inspector (if present during testing): None 2. TESTING CONTRACTOR INFORMATION Company Name: Confidence UST Services, Inc. Technician Conducting Test: Bradley Seykora Credentials 1: lEI CSLB Contractor lEI ICC Service Tech. 0 SWRCB Tank Tester 0 Other (Specify) License Number(s): CSLB# 804904 ICC# 8111231-UT 3. SPILL BUCKET TESTING INFORMATION Test Method Used: lEI Hydrostatic []Vacuum 0 Other Test Equipment Used:. Lake Test Equipment Resolution: 0.0625" Identify Spill Bucket (By Tank 1 Regular #1 2 Regular #2 3 Super 4 Diesel Number, Stored Product, etc) Bucket installation Type: x Direct Bury x Direct Bury x Direct Bury x Direct Bury 0 Contained in Sump 0 Contained in Sump L Contained in Sump 0 Contained in Sump Bucket Diameter: 12.00" 12.00" 12.00" 12.00" Bucket Depth: 13.50" 13.75" 13.50" 14.00" Wait time between applying 5 min. 5 min. 5 min. 5 min. vacuum/water and start of test: Test Start Time (T1): 10:15 AM !0:15AM 10:15 AM 10:15 AM Initial Reading (R1): 9.50" 10.25" 9.75" 10.50" Test End Time (TF): 11:15 AM I 1:15AM I 1:15AM 11:15AM Final Reading (RF): 9.50" 10.25" 9.75" 10.50" Test Duration (T F-T.): I hour I hour I hour I hour Change in Reading (RF-R1): 0.00" 0.00" 0.00" 0.00" Pass/Fail Threshold or 0.0625" 0.0625" 0.0625" 0.0625" Criteria: Test Result: lEI Pass 0 Fail lEI Pass 0 Fail lEI Pass 0 Fail lEI Pass 0 Fail Comments-(include information on repairs made prior to testing, and recommended[ollow-up[or[ailed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true, accurate, ami in filii compliance with legal requirements. Teohnk;an's s;gnatu•e: ~ Date:_ 0311912014 ~ ,. 1 State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements may be more stringent. Name: Street: City: Terms: "8UILD WITH CONfiDENCE" Lic.970703 "'COMPLIANCE WITH CONFIDENCE" Lie. 804904 Toll Free #: 1-800-339-9930 Confidence UST 16250 Meacham Road Bakersfield CA 93314 Descriotion of work performed: • / ., TRAVEL and LABOR Date Technician(s) Name , Labor Travel Date Techn1cian(s) Name Labor Travel · Date Technician(s) Name Travel Labor Travel Job Order /Invoice #: .321'1'1 Date Called nmo I To~ Site Name: ,A,(,~ S1a-.~~~ Street: 'ftoo Sti~ ~c..c-1 City: ~rs..P.,'.e ld state1J A--Zip: 9'3'513 Store No: (0.5 Hour Minimum Labor Charge) OVERTIME (5:00 PM • 7:00AM) Start End Total OT Start OTEnd OTTotal l. L,._.:;: Start End Total OT Start OTEnd OTTotal Zl..rS Start End Total OT Start OTEnd OTTotal SUPPLIES· MATERIALS • RENTALS Check One Qty. UST Parts Srte Parts )0 )0 )() COMMENTS