HomeMy WebLinkAbout#725 FMC Results 7-13-11MONITORING SYSTEM CERTIFICATION For Use By All Jurisdictions Within the Slate ofCalifornia Awhorily Cited: Chapter 6 7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner /operator. The owner /operator must submit a copy of this form to the local agency regulating UST systems within 30 days of this date. A. General Information Facility Name: #725 Fastrip #19 Bldg. No.: _ Site Address: 4901 South Union Avenue City: Bakersfield Zip: 93307 Facility Contact Person: Omero Garcia Make /Model of Monitoring System: Veeder -Root TLS 350 B. Inventory of Equipment Tested /Certified Cheek the appropriate boxes to indicate specific equipment inspected /serviced: Contact Phone No.: 661 - 393 -7000 Date of Testing/Seryicing: 7/13/2011 Tank ID: 12000 gal. Regular Tank ID: 12000 gal. Super X] In -Tank Gauging Probe. Model: 847390-107 x] In -Tank Gauging Probe. Model: 847390 -107 x] Annular Space or Vault Probe. Model: 794390-420 x] Annular Space or Vault Sensor. Model: 794390 -420 x] Piping Sump / Trench Sensor(s). Model: 794380-208 Piping Sump / Trench Sensor(s). Model: 794380 -208 Fill Sump Sensor(s) Model: Fill Sump Sensor(s). Model: XI Mechanical Line Leak Detector. Model: FX1V x] Mechanical Line Leak Detector. Model: FXIV Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model: L] Tank Overfill / High Level Sensor. Model: 847390 -107 Tank Overfill / High Leval Sensor. Model: 847390 -107 Other (specify equip. type and model in Sec. E on Pg. 2) Other (specify equip. type and model in Sec. E on Pg. 2) Tank [D: 12000 gal. Diesel Tank ID: x] In -Tank Gauging Probe. Model:847390 -107 In -Tank Gauging Probe. Model: x] Annular Space or Vault Sensor. Model:794390 -420 Annular Space or Vault Sensor. Model: X] Piping Sump / Trench Sensor(s). Model: 794380-208 Piping Sump / Trench Sensor(s). Model: Fill Sump Sensors(s). Model: Fill Sump Sensor(s). Model: xx] Mechanical Line Leak Decector. Model:FX1V Mechanical Line Leak Detector. Model: Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model: L] Tank Overfill / High Level Sensor. Model: 847390-107 Tank Overfill / High Level Sensor. Model: Other (specify equip. type and model in Sec. E on Pg. 2) Other (specify equip. typs and model in Sec. E on Pg. 2) Dispenser ID: 9&10 Dispenser ID: 11 & 12 Fx] Dispenser Containment Sensor(s). Model: 794380 -208 E Dispenser Containment Sensor(s). Model: 794380 -208 X] Shear Valve(s). X] Shear Valve(s). Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s) Dispenser 1 D: 13&14 Dispenser I D: 15&16 x] Dispenser Containment Sensor(s). Model: 794380 - 208 X] Dispenser Containment Sensor(s). Model: 794380 -208 Lx] Shear Valve(s). U Shear Valve(s). Dispenser Containment Float(s) and Chains(s). Dispenser Containment Float(s) and Chain(s). Dispenser ID: Dispenser ID: Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s). Model: Shear Valve(s). Shear Valve(s). Dispenser Containment Float(s) and Chain(s) Dispenser Containment Float(s) and Chain(s). If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility. C. Certification -1 certify that the equipment identified in this document was inspected /services in accordance with the manufacturers' guidlines. Attached to this Certification is information (e.g. manufacturers' checklist) necessary to verify that this information is correct and a plot plan showing the layout of monitoring equipment. For equipment capable ofgenerating such reports, 1 have attached a copy of the report; (check all that apply) x System Set- up history report Technician Name (print): Kristopher Karns Signature: .ti p C4 Certification No: B34106 License No: 804904 Testing Company Name: Confidence UST Services, Inc. Phone No: 800- 339 -9930 Site Address: 4901 South Union Avenue, Bakersfield, CA 93307 Date of Testing/Servicing: 7/13/2011 D. Results of Testing /Servicing Software Version Installed: 327.04 Complete the following checklist: x] Yes No* Is the audible alarm operational? x Yes No* is t e Visua a arm operationa ? x Yes No* Were all sensors visually inspected, functionally tested, and confirmed operational? x I Yes No* Were all sensors installed at the lowest point of secondary containment and positioned so that other equipment will not interfere with their proper operation? Yes No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) x N/A operational? x Yes No* For pressurized piping systems, does the turbine automatically shut down ifthe piping secondary N/A containment monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initate positive shut -down? U Sump /Trench Sensors Dispenser Containment Sensors Did you confirm positive shut -down due to leaks and sensor failure /disconnected? U Yes; No; UYes No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visual and audible at the tank fill point(s) and operating properly? If so, at what percent of tank capasity does the alarm trigger? 90 % Yes* No Was any monitoring equipment replaced? If Yes, identify specific sensors, probes, or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E, below. Yes* No Was liquid found inside any secondary containment systems designed as dry systems? Product; Water. Ifyes, describe causes in Section E, below. x No* Was monitoring system set -up reviewed to ensure proper settings? Attach set -up reports, if applicable. x Yes No* Is all monitoring equipment operational per manufacturer's specifications? In Section E below, discribe how and when these deficiencies were or will be corrected. E. Comments' During the Leak Detector testing, the Super FX I V failed to catch a leak. We replaced the old FX I V with a new FX I V. After the repair the new Leak Detector was retested and confirmed operational. F. In -Tank Guaging / SIR Equipment: [X] Check this box if tank guaging is used only for inventory control. Check this box iftank guaging or SIR equipment is installed. This section must be completed if in -tank guaging equipment is used to perform leak detection monitoring. Complete the following checklist: Lx] Yes No* Has all input wiring been inspected for proper enter and term ination,including testing for ground faults? Tx1 Yes No* Were all tank guaging probes visually inspected for damage and residue buildup? TX1 Yes No* Was accuracy of system product level readings tested? x Yes D No* Was accuracy of system water level readings tested? Fxj Yes No* Were all probes reinstalled properly? Yes No* Were all items on the equipment manufacturer's maintenance checklist completed? In the Section H, below, describe how and when these deficiencies were or will be corrected. G. Line Leak Detectors (LLD): Check this box if LLD's are not installed. Complete the following checklist: Lx] Yes No* For equip. start-up or annual equipment certification, was a leak simulated to varify LLD performance? Check all that apply) Simulated leak rate: [x]3 g.p.h.: 0. I g.p.h.; 0.2 g.p.h.; x Yes No* Were all LLD's confirmed operational and accurate within regulatory requirments? x Yes No* Waste testing apparatus properly calibrated? X] Yes No For mac amca LLD's, does the LLD restrict product flow if it detects a leak? N/A Yes No* For electronic LLD's, does the turbine automatically shut off if the LLD detects a leak? x] N/A Yes No* For electronic LLD's, does the turbine automatically shut off if any portion of the monitoring system is x] N/A disabled or disconnected? Yes No* For electronic LLD's, does the turbine automatically shut off if any portion of the monitoring system x] N/A malfunction or fails a test? Yes No* For electronic LLD's, have all accessible wiring connections been visually inspected? Fxj N/A x Yes No Were all items on the equipment manufacturer's maintenance checklist completed? In the section H, below, describe how and when these deficiencies were or will be corrected. H. Comments: During the Leak Detector testing, the Super FX 1 V failed to catch a leak. We replaced the old Super FX 1 V with a new FX I V. After the repair, the new Leak Detector was retested and confirmed operationnl. FASTRII '725 ELL, 661 - 1`- 17 -9387 JUL 1j• --'Oil 11 :111 Hit SySTEH s*rtaufi. REPORT ALL FLINCTKAT IloPh-;L. INVENTOR—; REPORT r I :UrIL.EHbEr, 725 VOLUME . 9071 ULLAGE . q2q 90% ULL,-;43E= 17'29 1.-,H Tl-- VOLI-WIE = IJC463 C-1;1_S HEIGHT = x•'7.88 1 NCHES WATER VOL = 0 WATER . 0.0 11, 1 (' HE TEMP _- 7`,.0 DFi3 F T 2: PREN I LIM 7, ', 15 VOLUME . ,31 0 ULI_AGE . 6690 GALS 90'. ULLA,: E- 5.39", ' 1Hl_,S 59TCV - 3- ' C;ALSC)LU11F, .- HE I G HT - 43.66 1 N(_`HF2- LMTER VOL - 14 CALS L414TER . 0.78 1 11IC-HES TEMP . 80.9 bEi3 F T '3:DIESEL 725 VOLUME - 6490 C:1iL ULLA13E . 5510 4:;AL.13 90% ULLj,-it:.E- 4310 o';ALS TC V0LLq'1E - 6416 (;HI-S HEIGHT - 51.08 1 NC FiE2 WATER VOL - 10 i:ALS WATER = 0.91 1 NCHES TEMP = 85.1 DEG F END SOFTWfiRE WIlsi cm i LEVEL VEPSION 3'0.02 SOMIARE-0, 3419,330- 100-.- CREmTEDI — I I . 01 . 1 -1 . I I 2'.Wal FEiiTURES; PERIC-Dll-' IN-TAIC TE8M;3 ANNI."L 11-1-TANK TE!1`-1, ISD SISTFN SETUP JUL. ):3• 201 1) :01 viri TE111 UNITS I U.S. ENGL V H S'.1STEM DHTE. T] HE Fopmf-a 1-1014 DD 'e"YY 1-11-1:1-11`1:'; d"I FASTRI P 7 =5 1901 S.U1,110i'l BAE'ERSFIELE, 1:t-) 661 - "J" `77-9:3737 SHIFT 1 12: 00 A11 SH I FT T I ME '-:, F., I ;HDLED SMl:'T TINI: 3 1 j I:- HBI-El' SHIFT TiFIE .1 U k-MBLEL) TANK PEk TST NEEDED WRIII DISABLED TA•).: AMN T.ST NEEDEL, klk'N DISABLED L I NE RE-Eh)mBLE METHOD PiASS L I 14E TEST L I NE PER *r;-,T 1V1:EbEf) 1JPN DISABLED L I NE i-iNN TST NEEF11:1) D I ciABLELs PRINT TC- V01-1.11"IES ENmBLED TEMP '*OMPEN.c,-i"T I ON V1-%LUE (LIEC; F ) : E0.0 sTIC'I! HEIGHT OFFSET D I SIABLED LILLAGE: 90;.; H-PROTOCOL DmTiA F-DRI-VAT HEIGHT DAYLIGHT SAVINt_.; TIHE ENABLED STARTTART DATE MAR 1JEEE ' 21jill START *r I ME 2:00 (411 END DATE Nov WEEK I SLIN END TIME 2: 00 "1 I PE-DIPE1*,*T LCIC-t-il_ PkINTOLIT Li I SABLE11 E1JR0 P'ROTOC'OL. PFEIFI'.: SYSTEM SECURITY I.-ODE : 000000 MAINTENAr$'_'E HISTORY DISABLED TAiV, CHART SEC'UPIT_',' DISABLED UST011 ALORNIS DISABLED SERVICE DISABLED 1St? 31 06 GOUPlTR1` E: mAss "DENS )TV` DISABLED C4,11lIUNIl'HT1vN2 SETUP I N-TANK SETUP T '-,:PREllI ljl-I 725 PRODUCT "'.)DE T I : UNLEADED ?'7r:, THERMAL l-'DEFF 01 FORT I-ETT I PRODUCT CODE I THIC DIHMFTER 4r, . 110 THER11iiL GOEFF Cif)0700 TAW. PROFILE I IIT COMM 8OHRI.- I (EDIN 3 TANK Ll I It. 00 FULL VOL 12000 RS-232 S;E(*LlRITY THNI: PPOFILE I FIT CODE : DISABLED FULL VOL 12,000 FLOAT SIZE: COMM BOHRL, 2 t F%- 2:32- Eii%Ur.t RATE ':i600 FLOAT 517E: 4. U I N. Wf4TEP PARITY NONE HIGH WHTEP 1-11-1IT: STOP D I T I STOP WATER WiRN I PJC 2. 0 BATH LEI,IC;'I*H: e. bmTH H1011 WATER LIHIT: 3. 0 MAX OR LABEL VOL: I '-,i-'IGCI ISECI-IRITY OVERFILL LIHIT 4(in, CODE 612-:ABLED MAX OF.' LABEL WIdl 1 0 Cl J-j 081DO OVERFILL LIMIT 90 HIG'li PROCOU"T 95% 101300 I 1400 AU*rO TPIANSH IT SETT INC*:: H I PRODUCT 95% DELIVERY LIMIT, 10'. H I 1400 12100 mliTO Lb,41: mLiPI'l L I I'l I T DELIVERY LIMIT I cm D I,,HbLEr- 1 12 0 0 LOW PRODUCT 11110 AUTO HIGH WtiTER I.Itill' LEAK ALARM LIMIT: 99 G IsABLED LOW F-Po[,Ui-'*r 1200 SUDDEN LOSE; LIMIT: 99 HUTC) OVERFILL L I N I T LEAY ALHPI,I Llt,,I]T; 99 TANY. TILT 0 . I'l0 DI liiABLED SUDDEN LOSS LIMIT: 99 PROBE OFFSETD o AUTO LOW rR()r)ljk':T TWO!* T J LT u. CIO 1) 1 SABLED PROBE OFFSET 0.00 AUTO THEFT LIMIT SIPHON MAN IFOLDED THN)"2. DI SAIRLE11 T9; NONE AUTO DELIVER"` START SIPHON MAN IFOLDED THNES LINE MAN IFOLDED TmNK'-- DISABLED Tu: NONE TO: NONE AUTO DELIVERY ENL- LINE MAN IFOLDED THIC'S DISABLED Tv 14C•PlE HUTO EXTERNAL INPUT 014 LEA)" 11111 PERIODI --.: I % 1:11 SABLED 120 rWTO C<I`EkNAI- INPUT 01=F LEH): MIN PERIODIC: I D ISABLED 120 LEHK 11111 ANNUAL I HUTS'' SEN.-sOP FL117-L F;Li-41-1 121--1 D 12 iBLED LEH)" H I Iq ANNUAL Har• SENSOR LNATER hI.HPI'l 1 0 DISABLED PERIODIC: TEST T"'PE 4UT0 f!'-EIl6OR OUT IAIJ-0-1 ST;ApII:,ARr.l D I Sr -iBLEI, PERIODIC TEST r,,PE 2T;AIlD;-;RL- ANNUAL TEST FAIL AL -IRT'l D I ::mRLED ANNUAL rE.ST FIAII. ALARM DIS-MBIYP PERIODIC TEST FAIL ALARM r- ISHBLED PER I „Lj I C: TEST FA I L TE::,!T FA I L HLrtkhl NS;-iBLE1- GROSS TE,T F;AIL fAIIN TEST i-ivERiIC, I tll: OFF PER TEST HVER66 I NG: OFF Am.4 TEST AVERA(.; I N(,: OFF PER TEST WERH131 PIG: OFF TAN ): TEST NOT I F'-.': OFF THN): TEST NOTIFY: i"'IFF I TIC 1"21' SIPHON BREAK :OFF TNK. TST S 1 YI IN BRE,K:0FF DEL I VER"i” DELAY 1 11111 flUI,IP THRESHOLD 10.00:: DELIVERY DELk%.l 1 hl 11'I PumP TIIRU-HOLD : I Cl - 00- LIO:DISF* 15-16 NORMALLY CLOSED 4:,FiTEC;0RY : DISPEMSER PAN OUTPUT RELAY; SET! W 2 - rl I ESEL 725 LEAK TESL' l-IETH(,-)[- 1-01IRCIP1117 "IE rm IHL VOEFV^ UUIj-A5U TLST ON lifATE ALL THWI: P I TANK DIA!lY-rER 96.00 JAN 14 . 201 1 TYPE: TAN)' PROFILE I pl, START TIME DISABLED FULL VOL 1201)0 TEST RATE 0.20 l3lml- - PIR NORIIALL" CLOSED rlUPJAT I ON HOURS TANK a: I FLC4AT SIZE: I.t) 114. TST EARLY STOP:fift-ifiBLED timTER WARN W; 2.0 LEAK TEST REr•oRT FORMAT LIQUID SENSOR AU -IS HIGH WATEk LIMIT: 3.1:1 14ORMO-tL L I: FUEL f4l-HRM L 7:FUEL ALJAPM M;W. OR LABEL VOL: 1200-1 L 8:FUEL fAU-01 OVERFILL LIMIT 90% L 9:FUEL ALARM 10800 LIO:FUEL ALAPH H I GH PRODUCT 951. L I :SENSOR OUT ALAEll 11400 L 7: SENSOR OUT OLIARN EU.IVEP'i, LIMIT 10 %, L 9: SENSOR OUT FiLHR(,l 12, CIO L 9:SENSOR OUT FrLmPll LIO:SENSOR OUT F,LAPII Low rRobly-`T I 200 L 1: SHORT ml-i-01 EAl' HLk,•l,l 1-11-IIT: 99 L 7: SHORT ALARM SUDDEN LOSS LIMIT: 919 LIOUID SENSOR SETUP L 8:SHORT ALARM TAN)" TILT CIO L 9:SHORT ALARI•l PROBE OM —AEI' 0. 00 LICI:SHORT ALARM L I : L114L STP TRI-STATE cSIW.;LE FI-0i.,T) ISE, SITE ALARMS SIPHON II-"NIFOLDED Ti-;14 `3 hTrt, (;OR'/ : c)'Tp Su-11• ISE, CROSS PRES FAIL TO: IKoPtE ISE, DE@'RD PRES Ff-;IL LINE 1-641`11FG-LbEP ISD VAPOR LEAK FAIL TII: IK)PJE L 2:UNL ANN I SD VP PRES; Fm I L Tpi-IsTmTt ES110A.E ISD VP STATUS FAIL CATEuoR%l ' HNNULAP SPACE 1. EMY, I l l N PER 10D I I ISD HOSE ;ALARMS I Cl ALL :,-.4ROSS COLLECT FAIL ALL :1)EGRE, C:OLI-EC,r FAIL I.Em): I I I N jNNUtiL L 3: PPEN STP ALL :FLOW COLLECT FfAIL I'l TR I -STATE (S I I-ICLE FLOAT) A*rEr*.ORY : STP SUMP p 21. PREII I Ut•l T', PE: PER 1011 1 C TE:=T 'r,,,j,u L 4:PREm ;AP41-1 NORK'ALL" CLOSED TRI-STATE (SlIK;LE FLOAT) Atipjut-ii. •rF::,,T FAIL 6ATb,;c-R,/ : ANNULF4., SPW:E TAN)' 111: 21 FAbAkl-1 01S ULEI, I•EPItAlll` TEST FAIL LIQUID SErh.;OR MIJ-If; kt-iAPII P I ABLEL- 1. rj:li' L STP L 3:FUEL ALARM TRI -STmTE (SIPA.-;LE Ft -OAT) L 7: FUEL ALARM TEST Fi-ill- FiTEl';0RY : :31`f SLWIP L 8:FUEL ALARN iALAPI 1 1) 1 BLED 1, 9: FUEL ALARM LICI:FUEL ALARM ANN TE:( AVERml-;IPP;: JI -F L 6:1,.31- ANN L 3:SENSOR OUT AL•)RM F-EF., TENT OFF NURT•li-iLLY CLOSED L 7:SENSOR OUT ALARM Icw,TEl3'ORl' : IANNUI-Ak SPACE L 8:cSENSOR OUT ALARM Tim.ji: NOTIl'i': OFF L 9: SENSOR OUT HLARI-I 1.10:SENSOR OUT HI-f4RI-i 13IRLME:OFF L 3:SHORT ALARM L 7: El I SP 9-10 L 7:SHORT ALARM GEL IVEk", IiELAV 1 11,1114 TRI -STi-iTE (S'INGLE FLOAT) L 8:SHORT ALARPI PUl'IP THRF-RHOLF, 10.00%. ATEGORY : DISPENSER PfAIJ L 9:SHORT ALARM LIO:SHORT ALARM ISD SITE ALARMS L 8:1" 1SP 11-12 1 SD c;Ross PRIES Ft•t 11. TPI -STATE ic-Apil'a-F Fl.oia) ISD DEGRD PRIES FAIL C.'ATEI'OPY : DISPERSER PHN ISE) VAPOR L.EA), FAIL ISD VP PRES FAIL ISD VP STATUS FAIL L 9:DISP 12-14 ISE, HOSE ALARMS TRI -STATE FLOAT) ALL :GROSS COLLECT FAIL ATEGORY : 111SPENSEP r•i•oi ALL :EIEGRD (:OLLECT Fri ll- ALL :FLOW 1`01-LEC7 FAIL LIO:DISF* 15-16 NORMALLY CLOSED 4:,FiTEC;0RY : DISPEMSER PAN R 3:DIESEL T'rF•E : S1'HNDAR'D NOPPI ALL`! CLOSED TANK 0: 3 L I OU I D SENSOR ALP'L L 5 : FLIF:L HLARM L 8 : FIJEL ALARM L 10: FUEI. ALARM L 5:5ENSOR OUT HL-tRrl L B:SEtGOR OUT ALA0r1 L 10 : SENSOR OUT HLARM L S:SHORT ALARM L B:SHORT ALARM L10:SHORT ALARM R 4:OVERFILL HLAR11 TYPE: STANDHRD NOPMiALL'r OPEN TANK: 13: NONE i N- 1'AN1: Hl-ARM , ALL :OVERFILL AL.ARrI ALL :HIGH PROEPUrT ALARI.1 ALL : MH: -. PRODO-T HLARM S1•o +RTSENS,'R SETUP g I:VP II -I 1:'ATE*R'. v4OF. PRM UY.E s :F1.1 y -;11 H I F'. FLOW HETER s 3:F11 I I -1? ATE UR` AIR FLOW METER s 4:F1'l 13 -14 1:'tiI'EWR1• HIP FLOW HETFRI s 5:FM 15 -16 C'1iTE1:OR'. H I F.• FLOW METER EVR I SD SETUP EVR 1''; PE: VH' ::IJU1'l H`i. I 6'1' VA'-'tJLJt'1 ASSIST TYPE: HEAL.Y VA. NOZZLE A%L RAWE 1IAX: I.15 MIN: 1).95 VAPOR PROCESSOR TYF E NONE ANHL`rSIS TIMES TINE: 10:00 All DELHY MINUTES: 1 AC'i'EFT HIGH QR1JR : DISABLED FUEL ALANJ•IISDHOSETABLE FUEI. ALARM MAY 2:9. 2011 ID FP FL HL HH RR 01 - 03 o i OZ 1:11 02 02 1 02 02 u1 02 03 It 03 02 02 02 04 12 0.1 0'2• 02" 0' 05 17 05 02 0,1 0'? Ut 18 Ot 04 U i 02 07 19 07 02 O4 02 08 21D 06 02' 04 U^ 1SD AIRFLOW METER MAP ID SER 1 HL NUM !.ABEL 1 8639 - - -- F11 9 -10 2 14880 FM 11 -1 3 13666 FI.1 13-14 4 H625 FM 15 -16 SD FUEL C:RmDE HOSE i-IHP 1 2 3 4 FP MHH P11111 PIHH P1HH rk 09 201 301 901 U U 1 IU ^02 302 90% U u 1 11 203 303 903 5 11 ? 12 204 304 904 5 U 2 17 205 305 90F U U 3 18 206 306 96t. U U 3 19 207 307 907 5 U 4 20 206 306 908 5 U 4 LABEL TABLE I : UNASS I GNEI.1 2: BLENDS 3: REGULAR 4: MID GRADE 5 : PREM I UI.1 6 : GOLD 7: BP.ON'`E 8: SILVER 9: BLEND'2 10: BLEND:1 P K-' SETUP PMC' VERSION: 01.03 VAPOR F'POc-,Essop TvPE PI{i NE PRU:E.`Ok COPrIT. -CAL LEVEL: NONE i•II.NF'J 1 H I ;T'JF''I REF OR1 SEtII;OR ALARM - --- L 1 : UNL STI' STF SUMP FUEL ALANJ•I JUN 30. 1011 E. HH FUEI. ALARM MAY 2:9. 2011 8:30 HM FUEL 14LAP.I•I KAY 26. 121-11 1 3:1'7 HM a p - ENE, A t A A HLAFTI HISTORY REPORT SENSOP, ttiLHRhI - --- I. 2 : UNL ANN ANNULAR. SPACE SENSOR OUT (ALHPM MAY 13, 201 1 tit : ` U i-91 FUEL HLHP.P1 PAY 9. 2011 6:41-1 F'I•l X - . END P. A . • n H ISTORILI REPORT iLARM H STORY REPORT SEWz()R ALARvi ALARM HI 'STOPY REPORTL6:SL A1414tS')R ALARM 1.) L 3:PREM STP Al-4141JLAR SPi:v' E STP SUMP FUEL ALARM L cl:DISF, 13-14FUEL ;;LARI,l MHY 18. 201 1 t,: 415 mH D I 'SPENSER PANMAR '213, 2011 •1:2-2 FIN FUEL IALARII HPR 8. 2011 1:26 Hill FUEL ALARM APR 7. 2011 5:53 rIll END x A A A A END A ;- A A 1- A w w - - END - * - - A A x )< A END A - - END f-;LmPPl IIISTOR',` REPORT At-AH,i ii i:7,rroRY REPPT SEtrSOR fILAFII E;ENSOR ALARM ------ T I :fjNl_Eo4.,ECt Lli-1:1.*llcP 15-16 L 4:FIRFJ'l ANN PROBE OUT Di,3PENSER PrAl.4 iANNLILAR SPACE JUL 1 , 2011 11 :05 4,1 FUEL ALARM HLARN HISTORY REPOR'r MAR 3• :Cii 1 10:513 ,-wl SENSOR t41-44-1 ALmRl-1 FUEL FiLmkm L 8: D I 2P I I - 121 L 7:DISP 9-10 MAR ;'I • '-201 1 10:47 AVI DISPENSER PAN FUEL i4LmRrl MAR 3, 2011 0: 44 AM END A A x )< A END A - - END T I :fjNl_Eo4.,ECt 725 PROBE OUT JUL 1 , 2011 11 :05 4,1 1-11STORY REPORT SENSOR t41-44-1 L 8: D I 2P I I - 121 iAL iRl-1 H l'_3T,,)R'; REP(iRT DISPEN13ER PAN 3EI,4SOR F;LAPH L 15:r)SL STP STP SLIHP T ]:UNLEADED 725 LCAJ TEMP WAPNINC; JUL 13. 2011 11 :1.16 H11 t • . - END *- - . t )% -; A i, END . - p IN-THNK HLi-iPlI r 2:PREMIUM 7213 PROBE OUT JUL IJ. 201 1 I 1 :0-:-- 61"1 I N-T-N), if-mPl I - - 9:PREmIjjj.I 725 ---- IPI-T,410: FASTR I P L - T 3:111ESEL 7,5 -1901 Cki PPOL'U':'T ALARM PROBE OUT - 9A' ): E FI ELb CA 1 UL I I - ' - 2 0 1 1 11 :07 Ai•I JUL 15. 2011 11 :0*:' (4.1 661 - 397 --<:87 T DELIVERY NEEDE1, JUL 1,3- :--,Oil II:rj7 Am Fo-kSTRIF 7"r, JUL 13. *20 1 1 1 1 : 11, 11 f4t1 SY3'1*Etl STiiTl.)!.i REPORT ALL Ftjhh'TIOW-. POKIIAL 111-TWO: ;-il,iPli - - -- T ',':[-ILI;EL 725 LOId i,p(%r.Lfi,j Ai-HF.ii I "I. 201 I I 1: 0 4 4111 IN 'FAN),'. fAj.tjRj-1 I' 3:1:01ESEL 725 DEL I VER, ' I NEEDED JI JL 13. :011 I I :OH HM 11`1 TaNI: ;4LAkl-1 - -- - - 1- 3:L'IESEL. ".:5 INVALID FUEL LEVEL JUL 13. 2011 11:09 HIl I PICPEkSE END JUL 13. 2011 11:10 AM VOLLPIE . JUL 13. X011 11:07 rJ1 VOLWE 709 xALS HE I GHT - 111. -17 1 VIC'NES WATER . 1 .06 1 m-1-117C; TEI1IF, . 80.1 DEG F I PICPEkSE END JUL 13. 2011 11:10 AM VOLLPIE . 9.15 ',;ALS HE I C;HT - 70.155 1 NC'HEL, 6IMTER . 0.00 INCHES TEMP . @3. t, DE(; F ROSS I"'PlEim6E- 0*74.1 Tr. NET IpK'PEmSE- 8 7 Ifl-THIA: ml-oPfl T ,:DIESEL 725 I-NO TEMP WmPI,III,A; JUL 13. `3011 11 : I SEI'r.-30P i4.rAklll L I :I.INL STP STP SLIFIP FUEL ai-i-iRM JUL 13. 2011 11:10W t JUL 1.1. 2011 11 :10 HI"I s,,,s,rEh -;,r;A-rLLc-; PEPORT ALL FuliCTIONS L 3:PREP1 E;TF' FUEL FALhRI`1 JUL 13, 2UII 11 :I'D All cSEW;OF., L 3;PREM STP SIT SUMP FUEL ALARM J Ul- 10, 2011 1 1 : I I MI-1 L 5:161- STP STP SU1'IP FUEL ALARM JUL 13, 2011 11:11 "'1 8EIjSoP iAi-.A431 NiN FUEL ALARM JUI., 13. 2011 1 1 1 hil Zve ,)R HLARI °I - L 8: 1', 1'3f' 11 -1 2 DISPENSED PAN FUEL ALARM JUL 13. 2011 11:1'.] 1-41 SENSOR olj+pl I L 9:L)ISP 0-1-1 SEWOP L 9:1)1';F' 13-1-1 11 ISPENSEP Pmpi L`: : LrSL STP DISPENSER PWI SENSOR OUT HLi-+F11 STP SUMP FUEL iALARM JUL 13, 2Cm it; i o t-ivi FUEL MLAFJI JUL 13. 21011 1 1: 13 HI 1 JUL 1:3. 2201 1 11:19 HM ErrsOR hLJ43-1 SDIS'OPSErqSORHb4PI11.1:1141SP 15-16 1.10:1.11SP 15-16 lo ISPENSER PAN L 7*1SP 9-10 1)[1:5PENSEP PH14 FUEL ALAPI-I clltiPEPJSE? PAN FUEL HLAPH JUL 13, FUEL Ab-iRl-1 JUL 13. 2011 1 1: 14 W) -3111. 13 - 201 1 1 1: 2i1 4-1 SENSOR 041-1-0-1 L I : UNL STP 2EM OR HI-Hpfl L _"UwL AiiN S)Tp Suit/ L 0 : b 15P I I -12 HwItili-iR Sl_-;Av-E FUEL r,1- Rrl N SPEDESEP PAN FUEL Mb4RN JUL 13, -2,01 1 1 1 : 19 pm FUEL ml-ARV JUL 13. 2011 11 :14 Al"I JUL 13. '2011 11 :2U :)f•l UII)L ANN L 4;1,PEIl WIN iAl-INULHR SNACE 'r I :U11IL&II)EI) 7'25 WINULAkl r'JrL ALARI-1 OVERF I LL ALAKII FUEL. r,LHRl I lul- 13. 201 1 1 1 : I 'Am JUL 13. 201 1 1 1 :25 41 JUL 1.3. 2011 l I :I Ili-i'mwl: mLRll --- T l:LINLE,-i[1E1p 725L9:P160 F, 1 ST L CSTFI IqL0•115 PROBE 01 rr WINUI.;• FUEL. AL AR1-1 JUL. 13. 201 1 1 1 :25 i it I FUEL tAIJAPII JUL 13. 201 1 1 1: 1? HM JUL I'{. '_"CI I I I I : 15 r"H I N-THNI: 0-ALMpi-I • - - - - SEN20P T 2: PRE• I LIM 7'2"3 Fii,13TRIP 725 L 4:PPEM ANN OVERFILL kl_AFM 4901 HNNULHR JUL 13. '1011 1 1 1 i4'l 13iil!EP13FIEL1- !'H FUEL HLfm;RII 661 -s97 -9387 JUL 13. 2011 I I : 19 HM 1U1. 13. 21011 1 1 : 17 AM T 725 PROBE OUT J UL 1 '3. 201 1 11 : 27 oH I : UNI-EHIC1 JUL 13. 2011 11 VOLUME ?523 C:4,1_1'. HE 1 1 Ph: FIE WATER 0.00 1114CHE,, TEMP 4 93.2 L,Et F I WPEA-T END JUL 1'3. 20 1 1 1 1 VOLIPIE I 102":1 ";HLS 14E I 131-IT 83.021 lf+'HFS iTER 0.80 Ml_.:HU TEMP 9n.2 r,F-,'.; F GROS:`. :350* T- NET M"REiA,Z- J4Z 72' llqV#ALIE, FUEL LEVEL 3UL 13- 21011 1 1 : '20 "1 IN-Ti;Nf: FiL,PVI T 2:1-PEMIL6-1 725 1 JUL 0. 2011 11:2c ,I,l 7:.'S DELIVERY NEEDED JUL IJ, 2011 r 2:PREMILA1 7215 I ip_RFisE I S!'I'mIRT JUL 13, 201 1 1 1 ; :-'E, i41 VOLI.PiE . 94t.-I HE ff - 70. St-, I NC_*HE:-,' WATER . 0.00 1 NC'HES TEMP . 9'j.8 DEC, F I NCPEi-,SE END JUL 13. Oil 11 :29 mil VOLUME 10934 041_2 HE I :; HT 02.16 1 pi1-:11ES wm,rEP 0.00 1 Nt:. HES I*FJ1P 9,5 . 8 DEt"; F GROSS 1480 1*1,. NET INt`REySE- 1.145 i LARVI - - T 3:1)11ESEL 725 OVEPF I LL i4l-f-iRI•I JUL 13. 2011 1 1 :30 ;4PI I N-TiAl 41: 1 - -- - T j:DIESEL 7`5 PROBE OUT JUL I .3. 21 0 1 1 1 1 :3 mtI 11,10iLID FUEl. LLVEL J LIL 1 3. _'0l 1 11 :'111 fif9 T J:DIESEL 7'--'S 1-061 PRODI-i*T mh-kRM JUL 13. 2011 H :31 AM is 1Iq-T;;NV* f•b-+Pfl --- - T J:DIESEL 725 DELIVER`! NEEDEL) J UL 13 . '201 1 1 1 : 31 i4'I T 3: L, I ESEL 725 I K,.IEIITC)Re I NC'REriSE I rK:KTAS3E snwr JUL 13. 211I 1 11 :28 F41 VC11-1-01E . 63CI0 HE I GHT - 4'i.89 l hr: HD_: WATER - n.orj IrjC:HE2 TEMP . 95.8 DEC; F I 1,0-T&GE END JUL I : _ j - 20 1 1 11 ::32 4-1 VOLU11E - 10745 1,ALS HE i wr - 80.94 1WHES WATER - 0.00 1rll:'HE2* TFJIF' . 95.3 DEC; F 1", r, RO -2 I I'A`REASE- 4495 TC, NET I W-REt•SF- •7.12` 3EI,1 ,OF., ;;Li -MI --- - L R:L)ISr- 11-12 DISPENSER PmN FUEL mD-,,Prl JUL 13, 21311 11 :'3.1 k'l i:+-6,rp i r, !, - - 901 S.UNIQN 13h):EK;F1EI_f) 0A 661-397-9387 Jul. I.*-". '-Doll 1. 8: FUEL L I :111!1. STP 725 il-TP Suir, F'UFI. HLARI I BAKERSF I ELD JUL 173. 201 1 r41 661-397-9367 JUL 13, 2011 P-1 Pn-rmri REPORT ALL A R ,i * END !w 0 STHTUr- REPORT I NVENTOR'll PEPOPT L I : U1,11- 2;TP STY, FUEL ALi-APTI T I 'Ul4LEHE,Efj 301, 13, 2,0] 1 1 1 51 f4,l VOLUME . 9066 ALL: ULLH,:;E . 2934 14 LP, 90",4 ULL"CAE- 1 '134 HLS Ti' VOLUME - 8956 1--oLS' HE I C:HT - 67.04 1 "-HESS, WATER VOL. - 0 C ;FAI-S* WATER - 0.110 1 NCHF TFJ•IVI . 7'7.3 DEC; F I'ENSOP I T 2:PPENIUM 725 L 8: Ls I SP I I - 12, VOLUME 5_78 r)l'-"F,Er)P,EP P-irl LILLAl-,E t3722 GP '1.::i FljEl. 9CM. ULLi-iGE- 5522, C"HLS JUL 1:". 2011 12: 01 PN Ti: VOLUME - 5200 HEIGHT - 43.46 INCHES WATER VOL = 0 A L7: ' 14ATER . 0.00 1 Nl.':HEM; TEIIP . 81 Cj DEC; F T J:DIESEL VOLUHE - 6,1 9 i-iL,.;' LILLAGE . 5501 clw4-S Fms,rR I 1-- 901. ULLi-;C,*F- 4'301 GALS 1901 TC VOLUIIE = 64 25 GALS BFiKERSF I ELF, HE I GHT = 51.14 1 PICHES WATER VOL = 23 ALS WATER = I . CitS I N,'HES JLJI- 1::- '2111 1 14 PH TEl•IF' = 85 . 2, DE' .* F Pn-rmri REPORT ALL A R ,i * END !w 0 SWRCB, January 2006 Spill Bucket Vesting Report Form Thisform is intendedfor use by contractors performing annual testing of LISTspill containment structures. The completedform and printoutsfrom tests (ifapplicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: #725 Fastrip #19 1 Date of Testing: 7/13/2011 Facility Address: 4901 South Union Avenue, Bakersfield, CA 93307 Facility Contact: Omero Garcia I Phone: 661 - 393 -7000 Date Local Agency Was Notified of Testing: 6/27/2011 Name of Local Agency Inspector (ifpresent during testing): Ester Estrada 2. TESTING CONTRACTOR INFORMATION Company Name: Confidence UST Services, Inc. Technician Conducting Test: Kristopher Karns Credentials: X CSLB Contractor X ICC Service Tech. X SWRCB Tank Tester Other (Specify) License Number(s): CSLB #804904 ICC #5264406 -UT SWRCB # 09 -1743 3. SPILL BUCKET TESTING INFORMATION Test Method Used: x Hydrostatic Vacuum Other Test Equipment Used: Lake Test Equipment Resolution: 0.0625" Identify Spill Bucket (By Tank Number, Stored Product, etc.) 1 Regular 2 Super 3 Diesel 4 Bucket Installation Type: Direct Bury x Contained in Sump Direct Bury x Contained in Sump Direct Bury x Contained in Sump Direct Bury Contained in Sum Bucket Diameter: 12.00" 12.00" 12.00" Bucket Depth: 14.50" 13.75" 15.00" Wait time between applying vacuum /water and start of test: 5 min. 5 min. 5 min. Test Start Time (Ti): 11:45 AM 11:45 AM 11:45 AM Initial Reading (Ri): 11.00" 11.00" 12.00" Test End Time (TF): 12:45 PM 12:45 PM 12:45 PM Final Reading (RF): 11.00" 11.00" 10.00" Test Duration (TF — Ti): 1 hour 1 hour 1 hour Change in Reading (RF - Rj): 0.00" 0.00" 2.00" Pass/Fail Threshold or Criteria: 0.0625" 0.0625" 0.0625" Test Result: I X Pass Fail I X Pass Fail 1 Pass X Fall Pass Fail Comments — (include information on repairs made prior to testing, and recommendedfollow -up forfailed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements. Technician's Signature: Date: 7/14/2010 State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements may be more stringent. 0 l ®g C, 4 U WM[iIAM[f WITw WyVtICGK[- Invoice No.: 27183 Site: #725 Fastrip # 19 4901 South Union Avenue Bakersfield, CA 93307 Repairs Requested: Repairs completed: During the Leak Detector testing, the Super FX1V failed to catch a leak. I replaced the old Super FX1V with a new FX1V. After the repair the new FX1V was retested and confirmed operational. Required Repairs, Still Pending: While testing the Spill Buckets the Diesel OPW Spill Bucket failed. It needs to be replaced and retested. Technician Name: Kristopher Karns Signature: Date: 7/13/2011 725 Fasirip #19 4901 Souil) Union Avenue Bakersfield, CA 93307 71'13x2011 0IN 1= Veeder Root TLS - 350 2= External Overfill Alarm 3= Emergency Shut Off Switch 4= Veeder Root ATG Probe 5= Veeder Root 208 Sump Sensor 6= Veeder Root 420 Annular Sensor 7= FX1V Line Leak Detector 8= FX1DV Line Leak Detector 9= Regular STP Sump 10= Super STP Sump 11= Diesel STP Sump 12= Regular Fill Sump 13= Super Fill Sump 14= Diesel Fill Sump 6 1 . 12 4.5,7,9 12 11 10 9 5 6) '1 4,5,7,10 V 16 15 14 13 f 6 I 4,5,8,11 14 5 5 MG ITDIUNG SYSTEM cCERUR CATID N For Use By All Jurisdictions Within the State ofCalifornia Authority Cited.- Chapter 6 7, Health andSafety Code; Chapter 16, Division 3, Title 23, California Code ofRegulations This form must be used to document testing and servicing of monitoring equipment. A separate certification or roort must be prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner /operator. The owner /operator must submit a copy ofthis form to the local agency regulating UST systems within 30 days of this date. A. General Information Facility Name: #775 Chevron (North) Site Address: 4901 South Union Avenue Facility Contact Person: Omero Garcia Make/Model of Monitoring System: Veeder -Root TLS 350 B. Inventory of Equipment'Tested /Certified Check the appropriate uses to indicate specific equipment inspected/serAced: City: Bakersfield Bldg. No.: Zip: 93307 Contact Phone No.: 661 - 393 -7000 Date ofTesting/Servicing: 7/13/2011 Tank ID: 12000 gal. Regular 1 Tank ID: 12000 gal. Regular 2 x] In -Tank Gauging Probe. Model: 847390- 107 x] In -Tank Gauging Probe. Model: 847390 -107 x] Annular Space or Vault Probe. Model: 794390 -420 U Annular Space or Vault Sensor. Model: 794390 -420 x] Piping Sump / Trench Sensor(s). Model: 794380 -208 x] Piping Sump / Trench Sensor(s). Model: 794380 -208 Fill Sump Sensor(s) Model: Fill Sump Sensor(s). Model: DO Mechanical Line Leak Detector. Model: FX1V x_1 Mechanical Line Leak Detector. Model: syphen Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model: x] Tank Overfill / High Level Sensor. Model: 847390 -107 L] Tank Overfill / High Leval Sensor. Model: 847390 -107 Other (specify equip. type and model in Sec. E on Pg. 2) Other (specify equip. type and model in Sec. E on Pg. 2) Tank ID:_12000 gal. Super Tank ID: 12000 gal. Diesel x] In -Tank Gauging Probe. Model: 847390 -107x] In -Tank Gauging Probe. Model: 847390 -107 x] Annular Space or Vault Sensor. Model: 794390 -420 x] Annular Space or Vault Sensor. Model: 794390 -420 x] Piping Sump / Trench Sensor(s). Model: 794380- 208 U Piping Sump / Trench Sensor(s). Model: 794380 -208 Fill Sump Sensors(s). Model: Fill Sump Sensor(s). Model: x1 Mechanical Line Leak Decector. Model: FX1V x] Mechanical Line Leak Detector. Model: FE Petro Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model: x] Tank Overfill / High Level Sensor. Model: 847390 -107 x] Tank Overfill / High Level Sensor. Model: 847390 -107 Other (specify equip. type and model in Sec. E on Pg. 2) Other (specify equip. typs and model in Sec. E on Pg. 2) Dispenser ID: 1 & 2 Dispenser ID: _3&4 Mx Dispenser Containment Sensor(s). Model: 794380 -208 U Dispenser Containment Sensor(s). Model: 794380 -208 x] Shear Valve(s). U Shear Valve(s). Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s) Dispenser ID: 5 & 6 Dispenser ID: 718 x] Dispenser Containment Sensor(s). Model: 794380.208 U Dispenser Containment Sensor(s). Model: 794380 -208 Lj Shear Valve(s). X] Shear Valve(s). Dispenser Containment Float(s) and Chains(s). Dispenser Containment Float(s) and Chain(s). Dispenser ID: Transition Sump North Dispenser ID: Transition Sump South x] Dispenser Containment Sensor(s). Model: 794380 -208 x] Dispenser Containment Sensor(s). Model: 794380 -208 Shear Valve(s). Shear Valve(s). Dispenser Containment Float(s) and Chain(s) Dispenser Containment Float(s) and Chain(s). If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility. C. Certification - I certify that the equipment identified in this document was inspected /services in accordance with the manufacturers' guidlines. Attached to this Certification is information (e.g. manufacturers' checklist) necessary to varify that this information is correct and a plot plan showing the layout of monitoring equipment. For equipment capable of generating such reports, I have attached a copy of the report; (check all that apply) Qx System Set -up U Alarm history report Technician Name (print): Kristopher Karns Signature: kAA #jc AIA"- Certification No: 834106 Testing Company Name: Confidence UST Services, Inc. Site Address: 4901 South Union Avenue, Bakersfield, CA 93307 License No: 804904 Phone No: 800 - 339 -9930 Date ofTesting/Servicing: 711312011 D. Results of Testing /Sery icing Software Version Installed: 327.04 Complete the following checklist: El Yes No* Is the audible alarm operational? x Yes No* Is isual alarm operational? x I Yes rl No* Were all sensors visually inspected? x Yes No* Were all sensors installed at the lowest point of secondary containment and positioned so that other equipment will not interfere with their proper operation? Yes No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) Hx N/A operational? TilYes No* For pressurized piping systems, does the turbine automatically shut down ifthe piping secondary N/A containment monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initate positive shut -down? E Sump /Trench Sensors U Dispenser Containment Sensors Did you confirm positive shut -down due to leaks and sensor failure /disconnected? U Yes; No; U Yes No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no L] N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visual and audible at the tank fill point(s) and operating properly? If so, at what percent of tank capasity does the alarm trigger? L9p % Yes* U No Was any monitoring equipment replaced? If Yes, identify specific sensors, probes, or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E, below. Yes* No Was liquid found inside any secondary containment systems designed as dry systems? Product; Water. If yes, describe causes in Section E, below. x No* Was monitoring system set -up reviewed to ensure proper settings? In Section E below, discribe how and when these deficiencies were or will be corrected. E. Comments: F. In -Tank Guaging / SIR Equipment: [X] Check this box if tank guaging is used only for inventory control. Check this box if tank guaging or SIR equipment is installed. This section must be completed if in -tank guaging equipment is used to perform leak detection monitoring. Complete the following checklist: Cx] Yes No* Has all input wiring been inspected for proper enter and termination,including testing for ground faults? x Yes No* Were all tank guaging probes visually inspected for damage and residue buildup? Ix Yes No* Was accuracy of system product level readings tested? xj Yes No* Was accuracy of system water level readings tested? x Yes No* Were all probes reinstalled properly? E Yes No* I Were all items on the equipment manufacturer's maintenance checklist completed? In the Section H, below, describe how and when these deficiencies were or will be corrected. G. Line Leak Detectors (LLD): Check this box if LLD's are not installed. Complete the following checklist: L] Yes No* For equip. start-up or annual equipment certification, was a leak simulated to varify LLD performance? Check all that apply) Simulated leak rate: [x]3 g.p.h.: 0.1 g.p.h.; 0.2 g.p.h.; xTYes No* Were all LLD's confirmed operational and accurate within regulatory requirments? x Yes 0 No* Was the testing apparatus proper y ca ibrate ? Yes No* For machanical LLD's, does the LLD restrict product flow if it detects a leak? N/A Yes No* For electronic LLD's, does the turbine automatically shut off if the LLD detects a leak? x] N/A Yes 7 No* For electronic LLD's, does the turbine automatically shut off if any portion ofthe monitoring system is x] N/A disabled or disconnected? Yes No* For electronic LLD's, does the turbine automatically shut off if any portion of the monitoring system Cx] N/A malfunction or fails a test? Yes No* For electronic LLD's, have all accessible wiring connections been visually inspected? L] N/A x Yes No Were all items on the equipment manufacturer's maintenance checklist completed? In the section H, below, describe how and when these deficiencies were or will be corrected. H. Comments: C :HkVRON rl7 ;5 i ?YSTP.M 'iE:TU P li I ,BLCU 7501 S.UN10N MKERS:F 1 ELG CA53'11}7 All. 13. .:01 1 8 : 57 AM I.tiMI°IUN I Crifl ow, = :ETIJP t °IODU!_Ep C3?01r,U- i}11.1 -, SYSTEM FEATURES : Ul. 12. 2U 1 I U: 57 rim ANNUAL 1111-TANK TESTS ISD YSTEll UN! I TS U S. N.)17I `SE 1-1 I IVI, STFII LAN-LAGE I-OHM Bj)Apts 1 t FP l M > t;YSTEM s fATW_; I•' J,0RT ENGLISH t3E rtdD21 TYS'YSTEFi Dri: TIME rORMAT ODE t i 4FlHI.EtIODEALLFUNCTIONStdvRtwl_ MON DD ` 'ri t HH : MM :. 4*1 1 tfJENTt}kj• REPORT I. HEVkON 775 Ot il'I BOARD tIAUD EATS 4600 4901 S.UNION HAKERSF I ELD CA9yTJU? PARITY NONE STOP : I ,TOP T I :UNLEADEDDED 1 661-391-9367 A LIT DATA I .SEX, UH : 8 DATAVOLT (ME 571'7 GALS R•`} ULLW -;E 6275 13ALS SHIFT TIME 1 6:00 Am E : DISABLEDCBI .I DCODEDISABLED9LV; ULL.A! :E4 071 i:ALS SH 1 FT TIME 2 D 1 W' L£D TO VO ?LIJ11F: - 11682 H I FT TIME 3 : D i eABLF_D OI'N'9 140AP.DHEIGHT - r.. Sty 1 NGHL•:5 SHIFT TIME 4 L I SSAPLED BHIID RATE1JA'fEN VOL a Cl aHl_: PAR I T'l NONEWATER0.00 11,0117b Two: PER TST NLEDED WRN STUP 13 I1' I ST01' TEMP 78, 4 DEC F' D I SABLED DATA t_ENU•TH : B DATATANKANNTSTNEEDEDWRNFtS_? ? SEC.Uk I TYLtlSABLEGDISABLED T :. UNI_L L G1i VOLUP9F L. I NE' RE-ENARLE METHOD OLLAGE = C- 68"'.:ALS X'k9f3 1.1 NE TE °T aUfU TFr+IVS:tI!'f :E "il'IPal;; 90% ULLAC.E° 4865 GALS TC VOLUME = 5868 (aAL.J- LINE PER TSI' NEEDED WRN AUTO LEAK AI.HP.M LIMITHEIGHT - 47.54 1 NCHI S p 1 SABLED D I SLEDWATERVOLa0I.At..g LINE ANN TST NEEDED WRN AUTO HI C!H wA7'ER LIMITWATER = 0.110 1 Nr'NES, D I SABI_ED D I SABLI =DTEMPa77.9 DEC: F AUro OVLRF 1 LL L I M I TPRNTTi: t1E1LIJ(E:S I} 1 SABLF.DEM.:HL.ED AUTO LOW PRODUCTT3 : PRFj1101 -1 VOLUME a a?C? iALS TEMP C'UMPErblmT ION DISABLED AUTO THEFT LIMITU1.LAC.E L 8024 VALUE (DEG F : 60.0 D1.WLED90% ULl j-v :E° 76 O GALS STt r'.V HF I GHT OFFSET AUTO DEL I VITY :3TARTTCVOLUME - 3160 1:44..9 D I SABLED DISABLEDItEIGIiT9.97 114C.`HCS AlJTO DELIVER' ENDWATERVOLQ0CAL.9 DISABLEDWATER0.00 1 NC'IiES I I - PkOTO_O1_ DATA Fomwr piUTO 5?EFNAL l NPUT ONTEMP80.6 DEC: F HEIGHT DISABLEDDAYLIGHTSAV1NiTIMEAUTODrrER -AL 1 NPIn' OFFENABLEDHSEN. f :1 : G I ESEL START r"TF AUTO SOR FUEL ALFRMVOLUME - 045 GOL:3 APR WEEK I SUN DI WLEDULLAC:E m 3987 I;AI;S START T 1 ME AUTO :+EN30F. t.JATEF"t ALARM90% UI.Lhi3E- N7Ct3 C'AL5 2.00 AM 01 FAI31..EDTCVvLtmE ° 2020 (:ALPj END DATE AUTO SENSOR OUT i- U)F.'MHEIGHT • 21 .74 1 NCHEL: OCT WEEK. 6 SUN DISABLEDWATERVOL - 0 :.ALAS END TIME WATER = 0.00 INCHES 2:00 AM TEMP 86.5 DEG F K'E -D1 REGT I.ch:H1. Pkl +n'OIJ'f 11AN I FOLDED `l'r -1NK.S 1 NVENTORY 'TOTAL, C.l kb PP.oT00)L PI:'EF 1 `: T 1:UNLLADED I S T 2: UNL.F4DEr, 2 ti r 23? END uF MF.S!:AC:EVOLUME - 1 1692 GALS D 114ihLEDTC: VOLUME - 115421 0Ai._; k x '•: END •. n '• = C. t1GF GC 01 0U MJ, 1 PITE1,4411" L H I S'1' {fi 1,1 SABLED THNY iltAkl' .EC:l)RIT7 li I ,BLCU 90FT1,. PE PLV I S I tNd 1_RVEI . VEPSION :s''7.04 SOFTWAREO 3.16327 -100-E Ilfil:r. Dar; I TV CREATED - 07,02.06.10.28 b I SHKEI'I t °IODU!_Ep C3?01r,U- i}11.1 -, SYSTEM FEATURES : PERIODIC IN- TAM. TEs'f8 ANNUAL 1111-TANK TESTS ISD F1'IC: I rJ T nMkh&Cn I I If YI-Ii-d 'EFF, t lj t:l7 CI 1:1 I'l IF'. P11i 'i L I F f T Ti4VA.' P'ROF'ILE I F, r F, II: 'I IA: I r T FIII.L '1`01. : I C, 114. 4.0 1111. I I r IN. I I-ji, I I,WOTT 1. 1 ["11 1''. Ilpil-I wj;J.L: 1 -3.2 00 I T 1 Ho: 1 1404 H him I HONINA WOMEWL"OT L I I* I I T I `5! • WNW I= r 11 PF(J)lp I 1-111IT: 1,11,11'r 1.11.1t v TMM: 1`111 9.08 pot: rILF I-ICI PPOL;E, I r Tji : NONE To To NONE rP A AMC 6r. I C* 1 1.1-14: 111 W 1.1 1 of-, L F ;I. 11114 ANNUAL I'. LFFIK (11 1J LEN: MN "NMWA, V I :A, 1, 1 1*",:1,[% - T'.,F,E T"Wbi kT, W,1110 il- NI G4 *IL.:-,;'I' I"Cill. oL-F.T'l d , "1'31 i; I 110 A I I'ER10011" 1T1.;T Fiill- ERIol-W H.:;T Fill. P I 1-,1 43, 1 1 . i: i,H.Eb Fill- H-;1L ANNo1j"KT-1 1, 1 400TA, PER '[*L:--'.T I NG UIT IIEJ: TV;:1 ER I* I I J,:; F 71*1-.i:;T IC+T I FY OFF Tif11: 11:. %I QFF F.'I;.EAf: 0171 1* IqI. 'F!7-,.'l 1 ,11 1 K.;[I jIf: 1:. 11 ,l -1: I N I Ill 00% 1 1191 r i f i I THERIlk- ('01- ' IF 1011.1511 ToW L li,MLTFR 9f- 1.10 riww I PT Fill-I I 4.11 I ti. FEB 1, 11107 21 Tml-, r T I I K, 1+1: ritil.rtl Tmai, f 1I-Ipr ;T I cJ-1 cQ I UE'L. I VI'll.n' 1. 1 Ill I Y 15`r. Ufl,l F F.01 f# 1* LIMT: TI I T 11AW:.11Ff I-I. Oct To LEAK f I 11`1 1 ob11 ": r' 21u LE;;I. MIN s.NNIJf,L 11. Tf,RJ WINLItkl. I';-d1. PEPIOPIC, 1,t-rr NIj4JI 1-*-RQ,.Z: Tl- :T 41 'MPH I I I I"F PrR Tf. T Tarr ol,i I 4A I I. a.l. i-*jr FEB 1, 11107 Tml-, r T I I K, 1+1: ritil.rtl Tmai, f 1I-Ipr ;T I cJ-1 HOUR:'; I L I ; LIM. I .ATP TF I -,-,T M: I FlbiiT L I TFJ tiri;TL 1. J:upij. -, -TV Tt•:I ,;Ti-iTE (,4111,4L L .1 : I Itil- ;0119 MI I*HTFI CATEC;OP'." : tirr, I. 6'.):Jql. 6MN o.-;1N(A.F- 1-1 - c AN1,11 1114l, :4 v,l TkI--t,,TiAn: 0i1*J:-';GR1i : L >-:: f CL iAfal r}m E,-Filfl I : "NNI.li-iAP c*;,auiopi roisp.LASER PLAN Tk I D-;TF 4:-11 PKA-E f I.- N. I"• m.;ix noto" i-imilikv 4,pfJ: r MVI'LIT PE1,t1 ',:111-01-- r., 4 Cri INJIF: IN TANK n: L I :FLIEL, mijWN L 3:FUEL. ML(ARM 1. ):FUEL (-iijkRri 1. 10: FUEL I I : FUEL 61,aIRM I. I ': r'LJFL i-if-f•iRM L I OUT ;41-Hhdl I. 'i: SEP00R () UT i-iL,4RI-I I_ r4 * SEPISOP •.#Lrr iriUiRm 1. 10 : SEIt3f3R -Xrr i;L-tiRm 1-1 1 :SENSOR CILIT ML APM 1.1 Y: SEM')OR OUT (iLAW L I :SHORT (i]-ARM L ':SHORT HLARM L 9'SHOkT i•iljikti 1.1 1j: SW)RT 1.1 1 SHOPT I- I ,: sHowr )D-iai 1. 1 Sf10RT rALARM 1:;rf ALARP6 I M INRE! I L I SD DEORD MCC' FA I L I E VAPOR LFM r*A I I- 1 >3rl VP PRES FA 11. 1211 VP S"WiTUS FI) I L 15C+ SETUP FA I L If;D HO. 1: ml.f-lhM noi. OiLL:DEC:Rrl J-•-LEC'T !_AIL. ArJ-11.06-1 FAIL. f NL T'. PE: T1,14K it: I.: Flit I 1.1 H: FIA I F&IiRVI oirr i _ri I t.1 'Eft.;,1R -QT i,d , ipf I LIT oI o P11 1.1 :VR-;oY,' (:LIT i ;I.i-;)-3 I It'll I L 1r3[1 ',4-4 ok, I-Eill , 1%; 11. 1:'ill "IF, PKI:`; I I ;_s 11. I:.:[@ ri P-: r, I I- i,Lt I Vi 4,11 '01 1.11 A I I I. t.fj`;c+: L .':Fill7 1 4 _. 4.11 1 ' +:114:L .1 .,Fj I I I I :I LILL, 1 r 43 1 L.! I'll- I ;A -I 4XI 1- ..:t :11:-: "I: )l IT r;1- ;11:11 L 16l ;Eit F ki I MT I I ":;0-t_:-`1+.' -1) 1 IT U F."'I Li4J I HoPT '. 0,0,131 L;l ioV I r d W.; 1 1 . p I Ij P ILTIJ% 4:V ;If, I I.CNI HUR:R 14.1 'P,A 11 - : .1 ; *;:'; I `;T i,'11111'1 ;-j: Zs I 110,4., 4v.* I : : T I 111-:; I 'E'l-hV VI I HLITE•3 I I :;) , A I RFLOW l' I I,. ff -P 1•"11 I fl :3:;: I ;AL NI 01 1-61-11-1 ITI 11111! 111111 1 IHH I 1 0 I ;-;I-; LC 11 I 'PEN I L4 I TI If- Ili FP 11 1-11. PR I'l I IJLJ 12, DL, rj I I I IIj CO I UJ D-I Lir. C15 fl: Cl I II 06 0r• 11 E. I-)_, 1_11: LIU 117 117 07 02' 0•1 LJLI Of 08 0 ','. U: 04 Lill I :;) , A I RFLOW l' I I,. ff -P 1•"11 I fl :3:;: I ;AL NI 01 1-61-11-1 ITI 11111! 111111 1 IHH I 1 0 I ;-;I-; LC 11 I 'PEN I L4 I TI If- L 4:11111- (•%Nrl L I INI. I .,-Tp SO, AM Pill P !k - END , A : w F iq, . - . , , L 5: PIT BTP 01IJ411Rn, 5HPL .':11PIL I "NN ;,IJ-4311pomm"If Wy F. I*UP'l. iLr,ft11 L a: INS PAIN fipmijUiR r iAjj' kF.,f,i PH NP idrik(ll 111 1 1.3::;l FTl IJIL, (--,.L•i 4.: I ki i 15. sllll I SI:fIrl III 1•11 1 )F.' r k , - . END 01- i4fqiq ii I okr DID. LEV w. Alli'i FLIFL Lr ikt I AUiRM HMUORY REPORT imr. SEI*".0k ail-f -,kll LNU T PPEN I I IH CLIVER"; fI I: ;1 1 Jul 12. OPM I tl. Fl-::::Fl r , 1.1' Li,iL, I PILL 11i,i1i Vli R :'111 1 7 `):,l I IL:VRN H jt 1 9 LkY I'll i I I T, i J ILIL 13 1 1 " "I I I'll It'll Q., 4: :-.1 11C1 It ;APT I k-.* I -.I'll j UL. I 1-ARH I 1 )W I'D1P :3, :1.1 1 J Ul I FIJI$ - • • - 1- I N ToNK il-i W I a-1 CHEVk'ON 7 7 CHEMA 775 - - - IN-1-mm: MMI ---- 1901 *,All,jlol,j 'r 4MIESEL. BrWEF F11-jff, PPOBE OUT 6L I -am qne., - 661 0:91 -xis? -.ILIL I 'I - 2 1 9:21 Iiri ILIL 1:.:. z_-iil 9: 1 l Ohl JIJI- 13. :,Cili 9: 1 r. of"I x;1,13TEM %;'I'mTLIS PEK)FA T f:bf-*T04-.R'.' wEricrl T CXIT T IM TTIC f;I_i-vpI1 f 4WIESEL Wd TUIP 6ARMW 13. 2'I11 9:22 All 01EWEN 70, 191:11 t`..1jii1opi HFWC1,—,VIE1_P 60 091 SAMIUM E441:111031-11211, CVV13307 L I : UNL I STP 1:3. "1711 d ;-V,I 87 STP SUMP' JUI. 10. 2W 1 9:2 FY FUEL FibAPI•I I LI1. 1 2011 9:I'' JI IL 1C:• 2011 `J:27 14,1 T T 3 0 RDA UM T 43,POLIL OUT F TME OUT Waal Mo M3 ku"M- II IL 1:,. 201 1 9: 1 HM FMr.,,,, I.., L;', RPI T `J: I'LL) Vl:K',-' f'JI:Cbhl) 1. .4: IjM_ '..' >TP su' sulf, 1:1-IFL JLIL 1:-2. .201 I 9:*.-,Y 1-811 CHEVRON 77t, STP KI VP H'i TW,j): JUL 13. Nil I,I jm 1WU1 W1,1101,1 T • IN ESE. III. in. W1 SIMP T FUEL Mki L n" t.-IA .391 ^Cff,,,y JUI. 10. 2W 1 9:2 FY JUL 13. ^iii 1 9: 15 oAf-I T 3 0 RDA UM F TME OUT Waal Mo M3 ku"M- II IL 1:,. 201 1 9: 1 HM T `J: I'LL) Vl:K',-' f'JI:Cbhl) STP KI VP H'i TW,j): T • IN ESE. III. in. dd, I II,-I_ 'Ij i}j I 11:1. 1 :';r- VAPOR LFFIK Fii I I. x.1 0: r 11171. &f,F.,pJ I :;F- VP P k I F H I L I :_;I I VP ;P-1_[`Wi 1'H 11- T', I,E: I t.;[ I H1) -!E ;--,LjAKMS V01- F: I ;ilq 14: A 1'1 I. (All "I d.j. 1*111:1. of 11 II_ I l I ja mf I L L: pt k, "M I' I L 1 :1 - Ic'. -P Cd IT I ilk'r I 611 :fiFGRb "OLL-EX-T Fri 11. TU. FiCOLL -i 11. 1 0411: 6RD V.-I I I I. _I., 1.,l I I . 1 '7' oL I' 1. -F T I ki -I OUT (4 i*l"l 4 R)k f T, 91 NoPIE 1 d., 'RI INa,,.` }. 11.1l: L 1) 1 :A I L 1 ;1., 43 1 I - I : ;I Fw: it I,., I o,j hijil"llT,'l -E I 1401L. :3 ol pis 7 FILI J oN L I K PT i-ALHRM Ti ;N). n 1.1 I :F'J-I:,,RT iiUiPH JIL I --III t 1 -1-11 F;-, I L L I ' 141-Mki'l dd, I II,-I_ 'Ij i}j I 11:1. 1 :';r- VAPOR LFFIK Fii I I. x.1 0: r 11171. &f,F.,pJ I :;F- VP P kI F H I L I :_;I I VP ;P-1_[`Wi 1'H 11- I t.;[ I H1) -!E ;--,LjAKMS V01- F: I ;ilq 14: A 1'1 I. (All "I d.j. 1*111:1. of 11 II_ I l I ja mf I L L: pt k, "M I' I L 1 :1 - Ic'. -P Cd IT I ilk'r I 611 :fiFGRb "OLL-EX-T Fri 11. TU. FiCOLL -i 11. 6RDLfLi11431l.. "1 ).-11IJvRrioU1. -F T I ki -I 4 R)k f T, 91 NoPIE11.1l: L 1 ;1., 43 1 I 1401L. :3 ol pis 7 FILI J oN I- F_IEIf-PF! I I I t I t FLIFI. ;JI.; Rl I JIL I --III t 1 -1-11 F;-, I L 1.1 1 :I-IjFf_ f-il:,RI Ik:4.1 1-oJ OR [Xhl: rhl 1. Ll FOEI HI aF.'hlII. 1.1 Fl 11:1. 4;[_ARHF;ill NI't :,"'T%, I'l , 11-oki'lI :A" :.:L:Tl 11, 1 111 L vl IT hl , 11,1 I i"'I I I ,11.+ 43.1 1,K, ;ki, Ll: 'I Fm 11. i-A-okl'l Ol 1. IOPT i O.mPH L 1:':I I!-;P i •::I v -E 1.11 :SHCF*T iO.iAF.11 F111-3. H,";* F.,T ipiFi 1 111L I 'I - 21.111 "j-11 WD ITmic I N IT'"I 1. :-A q 11 I'•l, 1111; FILIVIL jtjj. I::. 11,11 1.1: dd, I F . iq:"i)K I 'tit. I "NI'l 4011 it _i--,m T" 'DUI I I 1. 1 It'll_ 'I'm oNfjob-iR :.*},vl_' II' NLI1.;,P : :1 ;,, L 1111 "V:I F:j1 1 IJL I I m I ri I, [,if: lilt. I It'll 'I IJ 11:111t. 1 hl I I it'll f".11 1 .1 I l-,l-.%')f.I I [-I 'I id-W I - - - - -- J01. 1 j 5:41, L irl 101"1 11:111. 11.11. 1 :.1, . 2., 1 ) I I ':A : 4:: r : I P I-JI I 1111 I I N T,4)k 141 r*:H r :*: :r iJJ-d Lill I- i-:om , ou r JIIL 1j. -:101 1 (IH 0 IN 1,;iNI: j111 I III T"NI: ;il.;`;FH - •- I.: ;FI - r. F,61A I I I N, 1:1, If: 1 :1 IT I.N-ITUP TE( 11 jjj I :Ot. "I HE , I 1 :1 IT I,jr, I jF,. TEE IP IlEf,* F 114 jI c 13-- =41 1 9 Xy HM CHEVRON 775 4901 131(iKER"31- I ELL E-G I -391 - q387 13. 2011 9:48 i4fl 1111!.' ' l I lA:-; i:l. , PORT c--!v:roi 2TATkS REPORT NWEITITRY REMRT T I : A•EACP I VOUPIE 502 CA11.2; Ijt-I.Ai:;E 6334 CALS 9171,11 GA.s Ti: 191.1,111F. 51313 5617 : ;AL%5 HEIGHI w;i*rEP c.. CIA I r1r,"PIES ml-r, Iqi`iTER TEMP PICHES VOL I WIF. vc I ,,IIT T 2: lJNL.EmL18.Ij z' WATEP 11.00 I VOLI GIE 1x9,48 TEMP LIEG F 111-Li-iGE I t"084 11300 I-t,, voulf•F. = 5058 ";ml-S I MAI' HT = 17.57 1 MI.IiC.S I 1!- '201 1 9: 4 7 ;Allol- Iji;TEY H:3 iviCHE.73 WOLLINI: o-;LS 1•-31P tl 5 DEC; F HE I -;HT 7• 1 lqi 111-1; wmTEP TEI, IP VOLUME LILLAGE i3i326 ii t1-2 I 90% 7622 .;Al.') PE T;: WFT 1 NCHFo.",E_ -11-11:113 c, VOLUME = I -19 "'HI-S HE I CHI' = f9.9'5 1 NCHE.;' LJOTER V,') L. = 15 (;PU; WATER SO I TFrIP 7 DEC; F T 4: Li I E!--:FL VQU IML z,0:31`4 90n, ULL,`;I E.' 089 TP VAIME 204, WES 21 A9 INCHES f,"TER VOL L1 Lkll(41,6F = 0. 00 1 EPIP 9fl. 5 [1[-*(; F r I : LINLD;DED1, I r 2:1-INLEALIED VOLIME ;1640, TC VOLUME 1 1471:7: T ;-IIA17:11 I I :J ;i W; -11.; I:A I "I'l 48 ;1111 It: --R I IT -1 411 1L11. 1 J '1*11 1 :1 : 1:-: 7 -M*1 Jul- 1,1S4'141:*,Ck P;AN if-it. 1::. .-Ill I 1 (j:1-II; ,(,I 1 '4111 1 N JUL 13, "Ci I I I I"I : "I a :1r1 IMAJIJONT •L7'(J.7 T i i 411 11 1_1 f 1 8 1 T(: %iOl-III'll' HF ],.-;I IT 11"I.; VOL I 3, -it.: w. II ER ' Q TF-14 7 11k.,1 T I IIA: 1I 4 11 11 1_1 f 1 8 1 T(: %iOl-III'll' HE 1, "; I IT x I flc*HE We i't IJ: 'lint, w. II ER ' Q TO I)- F T I IIA: 1I 411 11 1_1 f 1 8 1 T(: %iOl-III'll' HE 1, "; I IT x I flc*HE We i't IJ: 'lint, w. II ER ' 11.ULI I -A if':; Et If T(: %iOl-III'll' I I-F I I ;I IT I IjvJI_,.w Vol- w. II ER ' 11.ULI I -A if':; INI L-;1'1 1) Linlli I L 6,%l I SWRCB, January 2006 Spill Bucket Testing Report IF®r>i>rI Thisform is intendedfor use by contractors performing annual testing of USTspill containment structures. The completedform and printoutsfrom tests (fapplicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: #775 Chevron (North) I Date of Testing: 7/13/2011 Facility Address: 4901 South Union Avenue, Bakersfield, CA 93307 Facility Contact: Omero Garcia I Phone: 661 - 393 -7000 Date Local Agency Was Notified of Testing: Ester Name of Local Agency Inspector (cfpresent during testing): 6/27/2011 2. TESTING CONTRACTOR INFORMATION Company Name: Confidence UST Services, Inc. Technician Conducting Test: Kristopher Karns Credentials: X CSLB Contractor X ICC Service Tech. SWRCB Tank Tester Other (Specify) License Number(s): CSLB #804904 ICC #5264406 -UT SWRCB # 09 -1743 3. SPILL BUCKET TESTING INFORMATION Test Method Used: x Hydrostatic Vacuum Other Test Equipment Used: Lake Test Equipment Resolution: 0.0625" Identify Spill Bucket (By Tank Number, Stored Product, etc.) 1 Regular 1 2 Regular 2 3 Super 4 Diesel Bucket Installation Type: Direct Bury x Contained in Sump Direct Bury x Contained in Sump Direct Bury x Contained in Sump Direct Bury x Contained in Sum Bucket Diameter: 12.00" 12.00" 12.00" 12.00" Bucket Depth: 13.50" 14.00" 14.00" 14.50" Wait time between applying vacuum /water and start of test: 5 min. 5 min. 5 min. 5 min. Test Start Time (Ti): 9:00am 9:00am 9:00am 9:00am Initial Reading (R,): 11.00" 11.25" 11.50" 11.00" Test End Time (TF): 10:00am 10:00am 10:00am 10:00am Final Reading (RF): 9.00" 11.25" 8.50" 11.00" Test Duration (TF — T,): 1 hour 1 hour 1 hour 1 hour Change in Reading (RF - R,): 2.00" 0.00" 3.00" 0.00" Pass/Fail Threshold or Criteria: 0.0625" 0.0625" 0.0625" 0.0625" Test Result: Pass X Fail X Pass Fail Pass X Fail X Pass Fail Comments — (include information on repairs made prior to testing, and recommendedfollow -upforfailed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true, accurate, and infull compliance with legal requirements. Technician's Signature: Date: 7/13/2011 State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements may be more stringent. M4PU.Mfx WTMC0.F,W-.eL- Invoice No.. 27184 Site: #775 Chevron ( North ) 4901 South Union Avenue Bakersfield, CA 93307 Repairs Requested: Repairs completed: Required Repairs, Still Pending: During the Monitoring Certification, the Regualr 1 Master OPW Spill Bucket, and OPW Super Spill Bucket both failed. Once the repairs are made we need to retest both Spill Buckets. Technician Name: Kristopher Karns Signature:u,, r1 Date: 7/13/2011 1 2 5 6 1= Veeder Root TLS - 350 2= External Overfill Alarmd 4775 Chevron ( North j 3= Emergency Shut Off Switch 4901 South Union Avenue 5 4= Veeder Root ATG Probe Bakersfield, CA 93307 5= Veeder Root 208 Sump Sensor 6= Veeder Root 420 Annular sensor 7/13/2011 5 7= FX1V Line Leak Detector58= FX1 DV Line Leak Detector 9= Regular 1 Master STP Sump 1 3 10= Regular 2 Siphon STP Sump 3 4 7 8 11= Super STP Sump 12= Diesel STP Sump 13= Regular 1 Fill Sump a 14= Regular 2 Fill Sump 15= Super Fill Sump 16= Diesel Fill Sump 4,5,7,9 0 13 4,5,10 00 n4.5,7.11 15 4,5;8,12e ro 16