HomeMy WebLinkAboutFMC 2011MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State ofCalifornia
Authority Cited: Chapter 6 7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code ofRegulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be
prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided
to the tank system owner /operator. The owner /operator must submit a copy ofthis form to the local agency regulating UST systems
within 30 days of this date.
A. General Information
Facility Name: Arco AM PM Bldg. No.:
Site Address: 900 Monterey Street City: Bakersfield Zip: 93305
Facility Contact Person: Alondra Hemandez Contact Phone No.: 661 - 835 -8044
Make/Model of Monitoring System: Veeder Root TLS 350
B. Inventoryy of Equipment Tested /CertifiedChecktheappropriateboxestoIndicatespecificequipmentInspected/serviced:
Date ofTesting/Servicing: 9/6/2011
Tank ID: 12000 gal. Regular Master Tank ID: 12000 gal. Regular Slave
x] In -Tank Gauging Probe. Model: 847390 -107 x] In -Tank Gauging Probe. Model: 847390 -107
x] Annular Space or Vault Probe. Model: 794390 -420 X] Annular Space or Vault Sensor. Model: 794390 -420
x] Piping Sump / Trench Sensor(s). Model: 794380 -208 x] Piping Sump / Trench Sensor(s). Model: 794380 -208
X] Fill Sump Sensor(s) Model: 794380 -208 Fill Sump Sensor(s). Model: 794380 -208
Mechanical Line Leak Detector. Model: Mechanical Line Leak Detector. Model:
N Electronic Line Leak Detector. Model: Red Jacket g Electronic Line Leak Detector. Model: Red Jacket
x] Tank Overfill / High Level Sensor. Model: 847390 -107 Tank Overfill / High Leval Sensor. Model:
Other (specify equip. type and model in Sec. E on Pg. 2) Other (specify equip. type and model in Sec. E on Pg. 2)
Tank ID: 12000 gal. Super Tank ID:
x] In -Tank Gauging Probe. Model: 847390-107 In -Tank Gauging Probe. Model:
x] Annular Space or Vault Sensor. Mode1:794390 -420 Annular Space or Vault Sensor. Model:
x] Piping Sump / Trench Sensor(s). Model: 794380 -208 Piping Sump / Trench Sensor(s). Model:
x] Fill Sump Sensors(s). Model: 794380 -208 Fill Sump Sensor(s). Model:
x1 Mechanical Line Leak Decector. . Model: FE Petro Mechanical Line Leak Detector. Model:
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
x] Tank Overfill / High Level Sensor. Model: 847390 -107 1 Tank Overfill / High Level Sensor. Model:
El Other (specify equip. type and model in Sec. E on Pg. 2) Other (specify equip. typs and model in Sec. E on Pg. 2)
Dispenser ID: 1& 2 Dispenser ID: _3 & 4
c Dispenser Containment Sensor(s). Model: 794380 -208 x] Dispenser Containment Sensor(s). Model: 794380 -208
7 Shear Valve(s). x] Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s)
Dispenser ID: 5 & 6 Dispenser ID: 7 & 8
x] Dispenser Containment Sensor(s). Model: 794380 -208 X] Dispenser Containment Sensor(s). Model: 794380 -208
x] Shear Valve(s). X] Shear Valve(s).
Dispenser Containment Float(s) and Chains(s). Dispenser Containment Float(s) and Chain(s).
Dispenser ID: 9 & 10 Dispenser ID: 11 & 12
X] Dispenser Containment Sensor(s). Model: 794380 -208 x] Dispenser Containment Sensor(s). Model: 794380 -208
x] Shear Valve(s). x] Shear Valve(s).
Dispenser Containment Float(s) and Chain(s) Dispenser Containment Float(s) and Chain(s).
Ifthe facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification - I certify that the equipment identified in this document was inspected /services in accordance with the
manufacturers' guidlines. Attached to this Certification is information (e.g. manufacturers' checklist) necessary to varify that
this information is correct and a plot plan showing the layout of monitoring equipment. For equipment capable of generating
such reports, I have attached a copy of the report; (check all that apply) x Syyste Set -up ( Alar ory report
Technician Name (print): Bryan A Self Signature:
Certification No: B37501 License No: 804904
Testing Company Name: Confidence UST Services, Inc. Phone No: 800- 339 -9930
Site Address: 900 Monterey Street, Bakersfield, CA 93305 Date of Testing/Servicing: 91612011
D. Results of Testing /Servicing
Software Version Installed: 331.01
Complete the following checklist:
Lx] Yes No* Is the audible alarm operational?
x Yes No* Is a Visua a arm operational?
x Yes No* Were all sensors visually inspected, functionally tested, and confirmed operational?
x I Yes No* Were all sensors installed at the lowest point of secondary containment and positioned so that other
equipment will not interfere with their proper operation?
Yes No* Ifalarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) Hx N/A operational?
x Yes No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary
N/A containment monitoring system detects a leak, fails to operate, or is electrically disconnected? Ifyes:
which sensors initate positive shut -down? [x] Sumparench Sensors [] Dispenser Containment Sensors
Did you confirm positive shut -down due to leaks and sensor failure /disconnected? [X] Yes; No;
X] Yes No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no
r ] N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visual and audible at
the tank fill point(s) and operating properly? Ifso, at what percent oftank capasity does the alarm
trigger? I 9p I %
Yes* X] No Was any monitoring equipment replaced'? If Yes, identify specific sensors, probes, or other equipment
replaced and list the manufacturer name and model for all replacement parts in Section E, below.
Yes* U No Was liquid found inside any secondary containment systems designed as dry systems?
Product; Water. Ifyes, describe causes in Section E, below.
x Was monitoring system set -up reviewed to ensure proper settings? Attach set -up reports, if applicable.
W yes No* Is all monitoring equipment operational per manufacturer's specifications?
In Section E below, discribe how and when these deficiencies were or will be corrected.
E. Comments:
F. In -Tank Guaging / SIR Equipment: Check this box if tank guaging is used only for inventory control.
Check this box if tank guaging or SIR equipment is installed.
This section must be completed if in -tank guaging equipment is used to perform leak detection monitoring.
the following checklist:
U Yes No* Has all input wiring been inspected for proper enter and termination,including testing for ground faults?
x Yes No* Were all tank guaging probes visually inspected for damage and residue buildup?
x Yes No* Was accuracy of system product level readings tested?
x Yes No* Was accuracy of system water level readings tested?
Yes No* Were all probes reinstalled properly? xl
x] Yes No* I Were all items on the equipment manufacturer's maintenance checklist completed?
In the Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD):
Complete the following checklist:
Check this box if LLD's are not installed.
x] Yes No* For equip. start-up or annual equipment certification, was a leak simulated to varify LLD performance?
Check all that apply) Simulated leak rate: [x]3 g.p.h.: 0.1 g.p.h.; 0.2 g.p.h.;
x Yes No* Were all LLD's confirmed operational and accurate within regulatory requirments?
x Yes No* Was the testing apparatus properly calibrated?
es No For machanical LLD s, does the LLD restrict product flow n it detects a leak?
N/A
x] Yes No* For electronic LLD's, does the turbine automatically shut off if the LLD detects a leak?
N/A
x] Yes No* For electronic LLD's, does the turbine automatically shut off if any portion of the monitoring system is
N/A disabled or disconnected?
x] Yes No* For electronic LLD's, does the turbine automatically shut off if any portion of the monitoring system
N/A malfunction or fails a test?
U Yes No* For electronic LLD's, have all accessible wiring connections been visually inspected?
N/A
x Yes No Were all items on the equipment manufacturer's maintenance checklist completed?
In the section H, below, describe how and when these deficiencies were or will be corrected.
H. Comments: The Super has a FE Petro Mechanical LLD and both ofthe Regular have Red Jacket Electrical LLD's.
ARCO 5526
900 MONTEREY ST
BAI:ERSF I ELD•- CA93305 M
805 -861 -1972 -
SEP 6 P011 12:40 PM
SYSTEM - STATUS - REPORT -
T 3:LOW PRODUCT ALARM
INVENTORY REPORT
I
T I:UNLEADED SYPHON I
VOLUME = 3268 GALS t
ULLAGE = 8359 GALS
90% ULLAGE- 7196 GALS !
TC VOLUME - 3209 GALS
HEIGHT = 30.32 INCHES
WATER VOL - 0 GALS
WATER = 0.00 INCHES
TEMP = 85.4 DEC F
T 2:UNLEADED MAIN
VOLUME = 3454 GALS
ULLAGE o 8.173 GALS
90%tULLAGE- 7010 GALS
TC•- VOLUME - 3387 GALS
HE;IGHT - 3i.52 INCHES
WATER VOL m 0 GALS
INTER - . 0.00 INCHES
TEMP - 87.3 DEG F
T.3:PREMIUM
VollME,,,' - 1185 GALS
UL:LAG ' - 10442 GALS
90P. ULLAGE- 9279 GALS
TO VOLUME - 1160 GALS
HEd4:3HT - 15.19 1 NCHES
WATER VOL - 0 GALS
WATER o 0.00 INCHES
TEMP = 89.4 DEG F
X x x r, A END * w x A%
SOFTWARE REVISION LEVEL
VERSION 331.01
SOFTWAREU 346331 -100 -B
CREATED - 11.03.22.16.29
S- MODULEU 330160 -004 -a
SYSTEM FEATURES:
PERIODIC IN -TANK TESTS
ANNUAL IN -TANK TESTS
ISD/APM
SYSTEM SETUP - - - - - -
SEP 6. 2011 12:10 PM
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM' DATE /T I ME FORMAT
MON DD YYYY HH:hIM:SS xM
ARCO 5526
900 MONTEREY ST
BAKERSFIELD.l;A93305
805 -861 -1972
SHIFT TIME 1 6:00 AM
SHIFT TIME 2 DISABLED
SHIFT TIME 3 DISABLED
SHIFT TIME 4 DISABLED
TANK PER TST NEEDED WRN
DISABLED
TANK ANN TST NEEDED WRN
DISABLED
LINE RE- ENABLE'METHOD
PASS LINE TEST
LINE PER TST NEEDED WRN
DISABLED
LINE ANN TST NEEDED WRN
DISABLED
PRINT TC VOLUMES
ENABLED
TEMP COMPENSATION
VALUE (DEG F ): 60.0
STICK HEIGHT OFFSET
D I,SABLED
OLLAGE: 90%
HE;
H.- PROTOCOL DATA FORMAT
IGHT
DAYLIGHT SAVING TIME
ENABLED
START DATE
APR WEEK 1 SUN
START TIME
2:00 AM
END DATE
OCT WEEK 6 SUN
END •T I ME
2:00 AM
RE- DIRECT' LOCAL PRINTOUT'
DISABLED
EURO PROTOCOL PREFIX
9
SYSTEM SECURITY
CODE : 000000
MAINTENANCE HISTORY
DISABLED
TANK CHART SECURITY
DISABLED
CUSTOM ALARMS
DISABLED
SERVICE NOTICE
DISABLED
ISO 3166 COUNTRY
CODE:
VAPOR MONITORING TYPE
GARB ISD
MASS /DENSITY
DISABLED
COMMUNICATIOI3 SL-TUP IN-TANK SETUP T 2: UNLEADED MA I N
PRODLr;T CODE 2
PORT ShTfINi S: T 1:UNLEADED SYPHON THERMAL COEFF ;.QORI
TANK DIAMETER
00
92.00
COMM BOARD : 1 ICEDIM
PRODUCT CODE
THERMAL COEFF :.000700
I TANK PROFILE
FULL VOL
4 PTS
11627RS-232 SECURITY
CODE DISABLED
TANK DIAMETER
TANK PROFILE
92.00
q pT$ 69.0 IJNGH VOL 9438
FULL VOL : 11627 46.0 INCH VOL
23.0 INCH VOL
5814
2190
BOARD 5 <RS -4851CAUS 69.0 INCH VOL 9438
BAUD RATE 9600 46.0 INCH VOL 5814
EVEN 23.0 [NCH VOL 2190 FLOAT SIZE: il.0 IN.
OP BIT
DATA LENG'fH : 1 DATA
RS -232 SECURITY FLOAT SIZE: q,0 N, WATER,WARNiNG
HIGH WATER LIMIT:
2.0
3.0CODE : DISABLED WATER WARNING 2.0 WATER ALARM FILTER: LOW
COMM WARD : 6 IRS -2321BAUDRATE
HIGH WATER LIMIT:
WATER ALARM FILTER:
3.0
LOW MAX OR LABEL VOL: 11627
9600 OVERFILL LIMIT : 90`4
PARITY :NONE
STOP BIT I STOP MAX OR LABEL VOL: 11627 HIGH PRODUCT
t0464
95s:
DATA LEND —TH: 8 DATA OVERFILL LIMIT • 90%c 11045
RS -232 SECURITY
CORE',.: DISABLED HIGH PRODUCT
464J04b4 DELIVERY LIMIT :
4
10%
11045 4 ^ It 62
DELIVERY LIMIT : Im., LOW PRODUCT 1250
AUTO TkANSM { T SETT ! PIG. , : 1162 LEAK ALARM LIMIT: 99
AUTO LEAK ALARM LIMIT LOW PRODUCT 1250 SUDDEN LOSS LIMPS':
TANK TILT
99
2.00
DISABLED
AUTO HIGH WATER LIMIT
LEAK ALARM LIMIT:
SUDDEN LOSS LIMIT:
99
99 PROBE OFFSET 0.00
DISABLED TANK TILT 2.00
AUTO OVERFILL LIMIT PROBE OFFSETOFFSET 0. SIPHON MANIFOLDED TANKSDISABLEDTO: NONE
AUTO LOW PRODUCTDISABLED SIPHON MANIFOLDED TANKS MANIFOLDED TANKS
AUTO THEFT LIMIT TO: NONE TO: NONE
DISABLED LINE MANIFOLDED TANKS
AUTO DELIVERY START TO: NONE LEAK M1I4 PERIODIC: 3rf4
DISABLED 3488F{I)7O DELIVERY ENDDISABLED 3LEHKMINDER1OLI 30 %
3488 LEAK MIN ANNUAL 30%
AUTO EXTERNAL INPUT ON 3488DISABLED
AUTO EXTERNAL INPUT OFF LEAK MIN ANNUAL : 30'4
DISABLED x488 PERIODIC TEST TYPEAUTOSENSORFUELALARMSTANDARDDISABLED
AUTO SENSOR WATER ALAPPI PERIODIC TEST TYPE ANNUAL TEST FAILDISABLEDSTANDARDALARMDISABLEDAUTOSENSOROUTALARMDISABLEDAINUAITESTFAILL
ALARM DISABLED PERIODIC TEST FAILPERIODIC
DISABLED
PERIODIC TEST FAIL GROSS TEST FAILALARMDISABLEDALARM DISABLED
GROSS TEST FAIL
ALARM D 1 SABL.ED ANN T>rST AVERR -,ING: OFF
PER TEST AVEP.AG I DG.: OFF
R5 -232 END OF MEfr,3AGEDISABLED
ANN TEST AVERHGI (Vr;
PER TEST AVERAGING:
OFF
OFF TANK ' TEST 140T I FY : OFF
TANK TEST NOTIFY: OFF TNK TST SIPHON BREAK:OFF
TNK TST SIPHON BREAK:OFF DELIVERY DELAY
PUMP THRESHOLD
5 MIN
10.00'x:
DELI'VERY.DELAY : 5 MIN
PUMP THRESHOLD : 10.007:
L 7:PREMIUM ANNULAR
T 3:PREMIUM LEAK TEST METHOD TRI - STATE,(SINGLE FLOAT)
PRODUCT CODE 3 CATEGORY ANNULAR SPACE
THERMAL COEFF :.000700 TEST ON DATE,: ALL TANK
TANK DIAMETER 92.00 14AR22. 2011
TANK PROFILE 4 PTS START TIME : DISABLED
FULL VOL : 11627 TEST RATE :0.20 GAL /HR L B:PREMIUI.1 FILL SUMP
69.0 INCH VOL : 9438 DURATION 2 HOURS TRJ -STATE (SINGLE FLOAT)
46.0 INCH VOL 5814 CATEGORY : OTHER :SENSORS
23.0 INCH VOL 2190 TST EARLY STOP:DISABLED
LEAK TEST REPORT FORMAT
FLOAT SIZE: 4.0 IN. NORMAL TRI RB I NE SUMPS7TEUSI
WATER WARNING 2.0 CATEC'.QRY : -STP SUMP
HIGH WATER LIMIT: 3.0
WATER ALARM FILTER: LOW
1-10:1 -2 UDC
MAX OR LABEL VOL: 11627 TRI -STATE (SINGLE FLOAT)
OVERFILL LIMIT 90% CATEGORY : DISPENSER PAN
10464
HIGH PRODUCT 95%
11045
DELIVERY LIMIT 10% 1-11:3-4 UDC
1 162 L I WU I D SENSOR `:ETUP TRI -STATE (S i NCLE -FLOAT)
CATEGORY : DISPENSER ,PAN
LOW PRODUCT 1500
LEAK ALARM LIMIT: 99 L 1:FINNULAR S`:PF101
SUDDEN LOSS LIMIT: 99 TRI -STATE :(SINGLE FLOAT)'
TANK TILT 3.00 CATEGORY ANNULAR SPACE L12:5 -6 UDC
PROBE OFFSET 0.00 TR,I -STATE (SINGLE FLOAT)
CATEGORY : DISPENSER PAN
SIPHON MANIFOLDED TANKS L 2 :SYPHON FILL SL41P
TO: NONE TRI -STATE (SINGLE FLOAT)
LINE MANIFOLDED TANI:S CATEGORY ; OTHER SENSORS L13:7-0 UDC
Td: NONE TRI -STATE !SINGLE FLOAT)
CATEGORY : DISPENSER PAN
LEAK MIN PERIODIC,: 30% L 3:SYPHON TURBINE SUMP
3488 TRI -STATE (91,NGLE FLOAT)
CATEGORY : PIPINt. SUMP L.14:9 -10 UDC
LEAK Ihtl N ANNUAL : 30% TR 1•- )STATE (.SINGLE FLOAT)
3488 CATEGORY : DISPENSER PAN
L 4:ANNULAR MAIN UNL
TR 1 -STATE (S 1 h1GLE FLOAT)
PERIODIC TEST 'TYPE CATEGORY ANNULAR :SPACE
STANDARD L15:11 -12 UDC,
TRI -STATE (S1 WLE FLOAT)
ANNUAL TEST FAIL CATEGORY DISPENSER PAN
ALARM DISABLED L 5 : MA 6N• UNL FILL
TRI-STATE FLOAT)
PERIODIC TEST FAIL.
SINGLE•
CATEGORY OTHER SENSORS
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED L 6:MAlN UNL TURBINE
TRI- STATE (SINGLE FLOAT)
ANN TEST AVERAGING: OFF CATEGORY : STP SUMP
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY 5 MIN
PUMP THRESHOLD 10.00k
OUTPUT RELAY SETUP EVR /ISD SETUP
R I:UNLEADED SHUTDOWN EVR TYPE: BALANCETYPE:
STANDARD
NORMALLY CLOSED BALANCE NOZZLE TYPE
VST
TANK 0: 2 SMARTSENSOR SETUP
y - - - VAPOR PROCESSOR TYPE
VEEDER -ROOT POLISHER
N -TANK ALARMS 3 1 : 1 -2 AFM
CATEGORY AIR FLOW PIETERALL:LEAK ALARM ANALYS -I'S TIMES
LIQUID fiENSOk ALMS 2:3-4 AFM T IME't y :'AM
L !:FUEL ALARM CATEGORY AIR FLOW METERCATEGORY DELAY MINUTES: i
L 2:FUEL ALARM s 3:5 -6 AFML3:FUEL ALARM CATEGORY AIR FLOW METER ACCEPT HIGH ORVR.' L 4:FUEL ALARM DISABLEDL5:FUEL ALARM s 4 :7 -8 AFML6:FUEL ALARM
LIO:FUEL ALARM CATEGORY A,IR FLOW METER ISD HOSE TABLE
LII:FUEL ALARM ID FP FL HL AA RR
12:FUEL ALARM • LLALARM s 5:9 -10 AFM
CATEGORY AIR FLOW METER 00 01• 02 Ol 02FUELALARM01
02 01 02 02 01 02L14:FUEL ALARM s 6:11 -12 AFM 03 02 03 02 02 02L15:FUEL ALARMFUELA CATEGORY AIR FLOW METER 0.4 03 04 02, 02 02
AL5 :
OUT aLAkhl 05' 04 05 02 03 02ALL:SHORT ALARM s B:ATMP - _ 06, -06 06 02 03 02
CATEGORY ATM P SENSOR 07 06 07 02 04 02ISDSITEALARMS080708020402ISDGROSSPRESFAIL
UVAPORISDDEGRDPEESFAILCATEGORY PRESSURE 110 09 10 02 05 02ISDVAPORLEAKFAIL1110II020602ISDVPs16:CCVP 12 11 12 02 OG 02STATUSSFAISDVPSTATUSFAILCATEGORYVAPORVALVEISDSETUPFAIL
SD SENSOR OUT FAIL ISD AIRFLOW METER MAP
SD HOSE ALARMS ID SERIAL NUM LABEL
ALL :FLOW COLLECT FAIL 1 36585 1 -2 AFM
R 2:PREM1UM SHUTDOWN 2 52453 3 -4 AFM
3 38276 5 -6 AFMTYPE:
STANDARU 4 53958 7 -8 AFM
NORMALLY CLOSED 5 36669 9 -10 AFM
6 36796 11 -12 AFM
TANK 0: 3
ISD FUEL GRADE HOSE MAP
LIQUID SENSOR ALMf3 1 2 3 4
FP MHH MHH AAL7 :FUEL ALARM
L 8:FUEL ALARM
IHHH -MHH
00 401 901 501 U U IL9:FUEL ALARM 01 402 902 502 U U 1LIO :FUEL ALARM 02 403 903 503 U U 2LII:FUEL ALARM 03 404 904 504 U U 2L12:FUEL ALARM 04 905 a5 5 U U050405 3L13:FUEL ALARM 05
405
505 U U 3L14:FUEL ALARM 06 407 907 507 U U 4L15:FUEL 07 408 908 508 U U 4OUTALL:SENSOR OUT AL!~P.MT 0808 409 909 509 U U 5ALL:SHORT ALARM 410 910 510 U 11 5
ISD SITE ALARMS 10 411 911 511 U U
11 412 912 512 U U
6
6ISDGROSSPRESSFAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL LABEL TABLE' ISD VP PRES FAIL
ISD VP STATUS FAIL 1: UNASSIGNEDISDSETUPFAIL
ISD BENSOR OUT FAIL 2: BLENDS
3: REGULAR
ISD HOSE ALARMS
4: MID GRADE
5: PREMIUMALL:FLOW COLLECT FAIL 6: GOLD
R 3:OVERFILL ALARM 7: BRONZE
8: SILVERTYPE: 9: BLEND2STANDARD10: BLEND4NORMALLYOPEN
TANK 0: NONE
I N -TANK ALARMS
ALL:OVERFILL ALARM
PMC SETUP
PMC VERSION: 01.04
VAPOR PROCESSOR TYPE
VEEDEP. —ROOT POLISHER
ALARM H1STORV REPORT
SYSTIII ALARM
PAPER OUT
SEP 3. 2011 8:16 PM
PRINTER ERROR
SEP 3, 2011 8:16 PM
x x x+ r END x xxpi
ALARM HIST0RV REPORT
I N —TANI: ALARM
T 1:UNLEADED SYPHON
LOW PRODUCT ALARM
SEP 2. 2011 3:99 PM
AUG 31' - 2011 11,: 5$ All
AUG 29,: 20, 1 9 :013 AM
1 NVAL I D FUEL LEk /lEI.
AUG 12. 2011 7:34 PM
AUG G. 2011 2125 PM
AUG 2. 2011 6:05 PM
PROBE OUT
JUL 6. 2011 9:02 AM
DELIVERY NEEDED
SEP 2, 2011 4 :23 PM
AUG 31. 2011 12:43 Phl
AUG 29. 2011 9:46 AM
M; i x 0' x END X x :4 .A A,
ALARM HISTORY REPORT
IN—TANK ALARM —
T 2:UNLEADED MAIN
LOW PRODUCT ALARM
S!"P 2: 20 t' 1 a : 27 PM
AUG 31. 201'1 1:12 PM
AUG 29. 2011 10:12 AM
INVALID FUEI. LEVEL
AUG 12. 2011 7:58 PM
AUG 6, 2011 3:09 Phi
AUG 2, 2011 6 :45 PM
PROBE OUT
JUL 6. 2011 10:13 AM
JUL 6. 2011 10:11 AM
JUL 6. 2011 9 :22 AM
DELIVERY NEEDED
SEP 2. 2011 4 :57 PM
AUG 29. 2011 11:06 AM
AUG'26. 2011 9:41 PM
kxXxV END xr Axw
6
ALART9 HISTORY REPORT
IN —TANK, ALARM
T 3:PREMlUM
1:01+1 PRODLI: T ALARM
SEP 5. 2011 12 :56 PM
AUG 31, 2011 6:08 PM
AUG 29, 2011 5:56 AM
INVALID FUEL LEVEL
SEP 2. 2011 10:05 AM
AUG 12, 2011 11:26 AM
AUG 2. 2011 6 :13 PIl
DELIVERY NEEDED
SEP 3. 2011 8:37 PM
SEP 1, 2011 2:19 PM
AUG 24. 2011 8 :28 PM
xxrixEND;cRxr
ALARM HISTORY REPORT
SENSOR ALARM - -- --
L 1:ANNULAR SYPHON
ANNULAR SPACE
SETUP DATA WARNING
MAR 22, 2011 8:03 AM
k m w x X END JA x x k
ALARM HISTORY REPORT
SENSOR ALARM _ - --
L 2 : SYPHON FILL SUt °1P
OTHER SENSORS
SETUP DATA WARNING
MAR 22,. 2011 8:03 AM
x x x x x EIVD A h 4 :, , i
ALARM HISTORY REPORT
SEWPOR ALARIN - - - --
L 3:SYPHON TURBINE SUMP
PIPING SUMP
SETUP DATA WARNING
MAR 22, 2011 8:03 AM
A x A* w END N x A ;i x
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 4 :ANNULAR'MAIN UNL
ANNULAR SPACE
SETUP DATA WARNING
MAR 22. 2011 8:03 11M
ALARM HISTOW, REPORT
SENSOR ALARM - - - --
L 5:MAIN UNL FILL
OTHER SENSORS
SETUP DATA WARNING
MAR 22. 2011 8:03 AM
A x x x x END K x is [ w
ALARM HISTORY REPORT
SENSOR ALARM --- --
L 6:11AIN UNL TURBINE
STP SUMP
SETUP DATA WARNING
MAR 22. 2011 8:03 AM
X x x x x END K A x x x
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 7:PREMIUM ANNULAR
ANNULAR SPACE
SETUP DATA WARNING
MAR 22. 2011 8:03 AM
a
ALARM HISTORY REPORT
SENSOR ALARM - -- --
L 8 :,PREM.1 Uhl FILL SUMP
OTHER SENSORS
SETUP DATA WARNING
MAR 22. 2011 8:03 AM
R xhxxEND. - W W W.1r
ALARM HISTORY REPORT
SENSOR HL(iRM - - - --
L S :PREMIUM TURBI.NE SUMP
STP SUMP
SETUP DATA WARNING
MAR 22, 2011 8:03 AM
x x x X END k
ALARM HISTORY REPORT
SENSOR ALARM --- --
L10:I -2 UDC,
DISPENSER PAN
SETUP DATA WARNING
MAR 22, 2011 8:03 All
k END w x x w x ii ii r if x END x "r, k 3ikxxxkENDxxxxx
ALARM HISTORY REPORT
SENSOR ALARM - --
L11:3 -a UDC:
DISPENSER PAN
SETUP DATA WARNING
MAR 22. 2011 8:03 AM
V 9 x r t END A. x X x x
ALARM HISTORY REPORT
SENSOR ALMR11 -_ - --
L12:5-6 UDC
DISPENSER PAN
SETUP DATA WARNI W-'-
MAR 22. 2011 9:03 AM
x x x x k END A A A x if
ALARM HISTORY REPORT
SENSOR ALARM - - - --
1-13:7-8 UDC
DISPENSER PAN
SETUP DATA WARN I W-;
MAR 22. 2011 8:03 AM
x is N x X END W x k A x
ALARM HISTORY REPORT
SENSOR.ALARM -- - --
L1 1: -I0 UDC
D1 S1;ENSER PAN
SETUP DATA WARNING
MAR 22, 2011 8:03 AM
x x w w x END 9 X w x x
ALAR11 HISTORY REPORT
SENSOR ALARM -- - --
L15:11 -12 UDC
DISPENSER PAN
SETUP DATA WARNING
MAR 22, 2011 8:03 AM
x X x K k END x x W w w
T 3:LOW PRODUCT ALARM
T 3:INVALID FUEL LEVEL.
T 3:DELIVERY NEEDEDI
r
ARCO 5526
900 MONTEREY ST
WEPSI=IELD.CA93305
805 - 861-1972
SEP 6. 2011 12:50 PM
I
SYSTEM STATUS REPORT
T 3:LOW PRODUCT ALARM
T 3:INVALID ,FUEL LEVEL
T 3 : DELIVER` ' NEEDED
ARCO- 5526
900 MONTEREY ST
BAICERSFIELD.CA93305
805 -861 - 1972`
SEP 6. 2011 12:50 PM
SYSTEM STATUS REPORT
T 3:LOW PRODUCT ALARM
T 3:INVALID FUEL LEVEL
T 3:DELIVERY NEEDED
ARCO 5526
900 MONTEREY ST
i EAKERSFIELD.CA93305
805 - 861 -1972
SEP 6. 2011 12:50 PM
SYSTEM STATUS REPORT
T 3:LOW PRODUCT ALARM
T 3:INVALID FUEL LEVEL
1 3:DELIVERY NEEDED''
IN -TANK ALARM - - - --
T 3:PREMIUM
HIGH PRODUCT ALARM
SEP 6.. 2011 12:51 PM
1N -TANX ALARM -- - --
T 3:PREMIUM
LOW TEMP WARNING
SEP 6. 2011 12:51 PM
IN-TAN)" ALARM - ---
T 2 :UNLEADED MAIN
LOW PRODUCT ALARM
SEP 6. 2011 12:51 PM
IN -TANK ALARM - -- --
T 2 :UNLEADED MAIN
DELIVERY NEEDED
SEP 6. 2011 12:51 PM
1N -TANK ALARM - - - --
T 2 :UNLEADED MAIN
LOW TEMP WARNING
SEP 6. 2011 12:52 PM
IN -TANK ALARM - - - --
T I :UNLEADED SYPHON
LOW PRODUCT ALARM
SEP 6. 2011 12:52 PM
IN -TANK ALARM - - - --
T I:UNLEADED SYPHON
DELIVERY NEEDEU
SEP 6. 2011 12:52 PM
IN -TANK ALARM - - - --
T 2:UNLEADED MAIN
OVERFILL ALARM
SEP 6. 2011 12 :53 PM
IN -TANK ALARM - - - --
T !:UNLEADED SYPHON
INVALID FUEL LEVEL
SEP 6. 2011 12:54 PM
ARCO 5526
900 MONTEREY ST
BAKERSFIELD.C493305
805 -861 -1972
SEP 6, 2011 12:56 PM
SYSTEM STATUS REPORT
T 2 :OVERFILL ALARM
T 3:HIGH PRODUCT Ni-ARM
m
ARCO 5526
900 MONTEREY ST
BAKERSFIELD,CA93305
805 -861 -1972
SEP 6. 2011 12:56 PM
SYSTEM STATUS REPORT
T 2:OVERFILL ALARM
T 3:HIGH PRODXT ALARM
ARCO 55'26
900 MONTEREY ST
BAKERSFIELD.CA93305
805 -861 -1972
SEP 6, 2011 12:56 PM
SYSTEM STATUS REPORT
T 2 :OVERF 1 LL ALiiP.M
T 3: H 1 GH PRODLY T ALARM
ALARM HISTOk1 REPORT
SENSOR ALARM - -- -
1-15:11-12 UDC
DISPEK9ER PAN
SETUP DATA WARNING
MAR 22, 2011 8:03 AM
A. ;i x x x END x* A x W
T 2:UNLEADED MAIN
INVENTORY INCREASE
INCREASE START
SEP 6. 2011 12:51 PM
VOLUME = 1131 GALS
HEIGHT - 14.72 INCHES
WATER . 0.00 INCHES
TEMP = 87.3 DEC F
INCREASE END
SEP 6, 2011 12:58 PIN
VOLUME a 10670 GALS
HEIGHT d 78.82 INCHES
WATER = 0.00 INCHES
TEMP . 90.2 DEG F
GROSS INCREASE= 9539
TC PIET INCREASE- 9335
T I* UNLEADED SYPHON
INVENTORY INCREASE
INCREASE START
SEP 6. 2011 12:52 PM
VOLUME = IOV9 GALS
HEIGHT - 14.44 INCHES
WATER = 0.00 INCHES
TEMP = 85.4 DEG F
INCREASE END
SEP 6. 2011 1:00 P11
VOLUME a 9527 GALS
HEIGHT = 69.64 INCHES
WATER = O.UO INCHES
TEMP - 90.8 DEG F
ARCO 5526
900 MONTEREY ST
BAXERSFIELD.CA93305
805- 861 -1972
SEP 6. 2011 1:19 PM
SYSTEPI STATUS REPURT
T 3:HIGH PRODUCT ALARM
SENSOR ALARM
L 3:SYPHON TURBINE SUMP
PIPIPN3 SUMP
FUEL ALARM
SEP 6. 2011 .1:21 PM
SENSOR ALARM
L 6 : KA I N UNL TURBINE
STP SUMP
FUEL ALARM
SEP 6. 2011 1:23 PIN
SENSOR ALARM
L 9:PREMIUM TURBINE SUMP
STP SUMP
FUEL ALARM
SEP 6, 2011 1:24 PM
ARCO 5526
900 MONTEREY ST
BAKERSFI ELI) .CA93305
805-861 -1972
SEP 6. 2011 1:24 PM
SYSTEM STATUS REPORT
T 3: H IGHPRODM-r ALARM
L 3:FUEL ALARM
L 6:FUEL ALARM
L 9:FUEL ALARM
INVENTORY REPORT
T I:UNLEADED SYPHON
VOLUME = 9528 GALS
ULLAGE a 2099 GALS
90% ULLAGE- 936 GALS
TO VOLUME - 9209 GALS
HEIGHT - 69.65 INCHES
WATER VOL e 0 GALS
WATER = 0.00 INCHES
TEMP o 107.8 DEG F
T 2:UNLEADED MAIN
VOLUME = 10671 GALS
ULLAGE - 956 GALS
90 ULLAGE- 0 GALS
TO VOLUME - 10314 GALS
HEIGHT = 78.93 INCHES
WAFER VOL = 0 GALS
WATER = 0.00 INCHES
TEMP a 107.7 DEG F
T 3 :PREMIUM
VOLUME 11281 GALS
ULLAGE = 346 GAL..S
90s: ULLAGE- 0 GALS
TO VOLUME = 10897 GALS
HEIGHT = 85.25 INCHES
WATER VOL - 15 GALS
WATER - 0.95 INCHES
TEMP = 108.4 DEG F
GROSS INCREASE= 8428
TO NET INCREASE- 8242 x END
i
ARCO 5526
900 MONTEREY ST
EAKERSFIELD•CA93305
805 -861 -1972
SEP 6. 2011 1:24 PM.
SYSTEM STATUS•REPORT
t 3:H1GH PRODUCT ALARM
L 3:FUEL ALARM
L 6:FUEL ALARM
L 9:FUEL ALARM
INVENTORY REPORT
T I:UNLEADED SYPHON
VOLUME - 9528 C;ALS
ULLAGE - 2099 GALS
90% ULLAGE- 936 GALS
TC VOLUME = 9209 GALS
HEIGHT - 69.65 INCHES
WATER VOL - 0 GALS
WATER - 0.00 INCHES
TEMP - 107.8 DEC F
T 2:UNLEADED MAIN
VOLUME = 10671 GALS
ULLAGE = 956 GALS
90% ULLAGE- 0 GALS
TC VOLUME = 10314 GALS
HEIGHT = 78.83 INCHES
WATER VOL 0 GALS
WATER = 0.00 INCHES
TEMP 107.7 DEC F
T 3:PREMIUM
VOLUME = 11281 GALS
ULLAGE - 346 GALS
90% ULLAGE- 0 GALS
TC VOLUME = 10897 GALS
HEIGHT - 85.25 INCHES
WATER VOL - 15 GALS
WATER = 0.95 INCHES
TEMP - 108.4 DEC F
x x x x x Elgrl x A x x x
ARCO 5526
900 MONTEREY ST
BAKERSFIELD.CA93305
805 -861 -1972
SEP 6, 2011 1:24 PM
SYSTEM STATUS REPORT
T 3:HIGH PRODUCT ALARM
L 3:FUEL ALARM
L 6:FUEL ALARM
L 9:FUEL ALARM
INVENTORY REPORT°
T I:UNLEADED SYPHON
VOLUME = 9528 GALS
ULLAGE - 2099 GALS
909 ULLAGE- 936 GALS
TO VOLUME - 9208 GALS
HEIGHT - 69.65 INCHES
WATER VOL - 0 GALS
WATER - 0.00 INCHES
TEMP - 107.8 DEC F
T 2:UNLEADED MAIN
VOLUME - 10671 GALS
ULLAGE = 956 GALS
90% ULLAGE- 0 GALS
TC VOLUME - 10314 GALS
HEIGHT - 78.83 INCHES
WATER VOL - 0 GALS
WATER = 0.00 INCHES
TEMP - 107.7 DEG F
T 3:PREMIUM
VOLUME = 11280 GALS
ULLA:.E = 347 GALS
90% ULLAGE- 0 GALS
TO VOLUME - 10897 GALS
HEIGHT = 85.24 INCHES
WATER VOL - 15 GALS
WATER - 0.95 INCHES
TEMP - 108.5 DEG F
x x x x x END x 9 x x x
n
ARCO 5526
900 MONTEREY ST
BAKERSFIELD.CA93305
805 - 861-1972
SEP 6. 2011 1:24 PM
SYSTEM STATUS REPORT
T 3:HICHPRODUCT ALARM
L 3:FUEL ALARM
L 6:FUEL ALARM
L 9:FUEL ALARM
INVENTORY REPORT
T I:UNLEADED SYPHON
VOLUME 9528 GALS
ULLAGE m 2099 GALS
904 ULLAGE- 936 GALS
TO VOLUME = 9208 GALS
HEIGHT - 69.65 11NCHES
WATER VOL - 0 GALS
WATER - 0.00 INCHES
TEMP - 1.07. 8 DEG F
T 2:UNLEADED MAIN
VOLUME = 10671 GALS
ULLAGE = 956 GALS
909 ULLAGE- 0 GALS
TO VOLUME - 10314 GALS
HEIGHT - 78.83 INCHES
WATER VOL - 0 GALS
WATER = 0.00 INCHES
TEMP - 107.7 DEG F
T 3:PREMIUM
VOLUME = 11280 GALS
ULLAGE 347 GALS
909 ULLAGE- 0 GALS
TC VOLUME - 10897 GALS
HEIGHT - 85.24 INCHES
WATER VOL - 15 GALS
WATER - 0.95 INCHES
TEMP - 108.5 DEG F
XXXXw END XXXXx
SE14BOR ALARM
L 9:PREMIUM TURBINE SUMP
STP SUMP
FUEL ALARM
SEP 6. 2011 1:25 PM
SENSOR ALARM - - - -- ARCO 5526L8:PREMIUM FILL SUMP ARCO 5526 900 MONTEREY ST
OTHER SENSORS 900 MONTEREY ST BAKERSFIELD.CA93305FUELALARMBAKERSFIEL.D.CA93305 805- 861 -1972
SEP 6, 2011 1:26 PM 805-861 -1972
SENSOR ALARM - - - --
L 5:MAIN UNL FILL
OTHER SENSORS
FUEL ALARM
SEP 6. 2011 1:27 PM
SENSOR ALARM - - - --
L 2:5YPHON FILL SUMP
OTHER SENSORS
FUEL ALARM
SEP 6, 2011 1 :30 P1i
ARCO 5526
900 MONTEREY ST
BAKEk1417 IELD- CA93305
805 - 861-1972
SEP 6 - 201 1 1 :3'D P11
SYSTEM STATUS REPORT
T 3:HIGH PRODUCT ALARM
L 2:FUEL ALARM
SENSOR. ALARM
L I:ANNUU R SYPHON
ANNULAR SPACE
FUEL ALARM
SEP 6, 2011 1:33 PM
SEP 6. 2011 1:35 PM
SYSTEM STATUS REPORT
T 3:HIGH PRODUCT ALARM
L 1:FUEL ALARM
SEIC40P ALARM - - - --
L 4:ANNULAR MAIN UNL
ANNULAR SPACE -
FUEL ALARM
SEP 6. 2011 1:39 PM
SENSOR ALARM --- --
L 7': NREM 1 UPI ANNULAR
ANNULAR SPACE
FUEL ALARM
SEP 6. 2011 '1:44 PM
SENSOR ALARM --- --
L 7:PREMIUM ANNULAR
ANNULAR SPACE
FUEL ALARM
SEP 6. 2011 1:44 PM
SEP 6. 2011 1:45 P1l
SYSTEM STATUS REPORT
T 3:HIGH PRODUCT ALARM
L 7:FUEL ALARM
IN -TANK ALARM - -- --
T 2 : UNLEADED MAI N
HIGH PRODUCT ALARM
SEP 6, 2011 1 :49, PM
IN-TANK ALARM -- - --
T 2:UNLEADED MAIN
MAX PRODUCT ALARM
SEP 6, 2011 1:49 PM
ARCO 5526
900 MONTEREY ST
6AKERSFIELD.CA93305
805 - 861 -1972
SEP 6, 2011 1:50 PM
SYSTEM STATUS REPORT
T 2:HIGH PRODUCT ALARM
T 2:MAX PRODW7 ALARM
T 3:1-11(;H PRODUCT ALARM
ARCO 5526
900 MONTEREI' ST
BAKERSFIELD.CA93305
805 - 861 -1972
SEP 6. 2011 1:50 P11.
SYSTEM - STATUS - REiPORT
T 2:HICH PRODUCT ALARM
T 2:MAX PRODUCT ALARM
T 3:HIGH PRODUCT ALARM
ARCO 5526
900 MONTEREY ST
BAYERSFIELD.CA93305
805 - 861-1972
SEP 6. 2011 1:50 PM
SYSTEM STATUS REPORT
T 2:H1GHPRODUCT ALARM
T 2:MAX PRODUCT ALARM
T 3:HIGH PRODUCT ALARM
SENSOR ALARM - - - --
L10:1-2 UDC
DISPENSER PAN
FUEL ALARM
SEP 6, 2011 1 :53 PM
T I:UNLEADED SYPHON
INVENTORY INCREASE
INCREASE sTAKrr
SEP 6. 20111 1:4e PM
VOLUME 9527 GALS
HEIGHT - 69.64 INCHES
WATER 000 INCHES
TEMP 10i A DEC F
INCREASE END
SEP 6. 2011 1:55-Ph1
VOLUME' - 9706 GALS
HEIGHT - 71.18 INCHES
WATER - 0.00 LNCHES
TEMP - 107.8 DEG F
GROSS INCREASE- 209
TC NET INCREASE- 203
SENSOR ALARM --- --
1.11:3-4 UDC
DISPENSER PAN
FUEL ALARM
SEP 6. 2011 1:57 PM
SENSOR ALARM - -- --
L13:7 -S UDC
DISPENSER PAN
FUEL ALARM
SEP 6. 2011 1:59 PM
SEP60R ALARM - - - --
L12:5-6 UDC
DISPENSER PAN
FUEL ALARM
SEP 6. 2011 2:00 PM
SEN50R ALARM
L14:9-10 Urr<.'
DISPENSER PAN
FUEL ALAR11
SEP 6. 2011 2:01 PM
SENSOR ALARM -- - --
L15:11-12 UK'
DISPENSER PAN
FUEL ALARM
SEP 6. 2011 2:03 PM
SENSOR ALARM
L13:7 -8 UDC
DISPENSER PAN
SENSOR OUT ALARM
SEP 6, 2011 2:05 PM
SENSOR ALARM - - - --
L 9: PREM I UM TURB 114E SUMP
STP SUMP
SENSOR OUT ALARM
SEP 6. 2011 2:05 PM
SENSOR ALARM
L14:9 -10 UDC
DISPENSER PAN
SENSOR OUT ALARM
SEP 6. 2011 2 :05 PM
SENSOR ALARM - - - --
L 1:ANNULAR SYPHON
ANNULAR. SPACE
SENSOR OUT ALARM
SEP 6, 2011 2:05 PM
SENSOR ALARM - - - --
1-10:1-2 UDC
DISPENSER PAN
SENSOR OUT ALARM
SEP 6, 2011 2:05 PM
SEW-OR ALARM - -- --
1-1,5:11 -12 UDC
DISPENSER PAN
ttENSOR OUT ALARM
SEP 6, 2011 2:05 PM
SENSOR ALARM --
L 2:SYPfWN FILL SUMP.
OTHER SENSORS
SENSOR OUT ALARM
SEP 6. 2011 2:05 P11
SENSOR ALARM -- ---
L 1' 1 : 3- 4 UDC
DISPENSER PAP!
SENSOR OUT ALARM
SEP 6, 2011 . 2:05 PM
SENSOR ALARM -- ---
L 3:SYPHON TURDINE SUMP
PIPING SUMP
SENSOR OUT ALARM
SEP 6, 2011 2:05 PM
SENSOR ALARM - - - --
L12:5-6 Utt
DISPENSER PAN
SENSOR OUT ALARM
SEP 6, 2011 2:05 PM
SENSOR ALARM - - - --
L 5:MAIN UNL FILL
OTHER SENSORS
SENSOR OUT ALARM
SEP 6, 2011 2:05 PM
ARCO 5526
900 MONTEREY ST
BAMERSFIELD,CA93305
805 - 861 -1972
SEP 6. 2011 2:05 PM
SYSTEM STATUS REPORT
T 3:HIGH PRODUCT ALARM
L I:SENSOR OUT ALARM
L 2:SENSOR OUT ALARM
L 3 :SENSOR OUT ALARM
L 4:SENSOR OUT ALARM
L 5:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
LIO:SENSOR OUT ALARM
LII:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L14:SENSOR OUT ALARM
L 15 : SEPItSOR OUT ALARM
0
ARCO 5526
900 MONTEREY ST
BAKERSFIELD- CA93305
805 -861 -1972
SEP 6, 2011 2:05 P1l
SYSTEM STATUS REPORT
T 3: H I GH PRODUCT AI..ARM
L 1:SENSOR OUT ALARM
L 2:SENSOR OUT ALARM
L 3:SENSOR OUT ALARM
L 4 : SEIVSOR OUT ALr -RM
L 5:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
LIO:SENSOR OUT ALARM
L I I : SENSOR OU1' ALARM
L12:SENSOR OUT ALARM
L13 : SENSOR OUT ALARM
L14:SENSOR OUT ALARM
L15. :SENSOR OUT ALARM
SENSOR ALARM - - --
L 4tANNULAR MAIN UNL
ANNULAR SPACE
SENSOR OUT ALARM
SEP 6, 2011 2:05 PM
SENSOR ALARM - - - --
L-6: MA I N U14L 'TURBINE
STS? SUMP
SENSOR OUT ALARM
SEP 6.. 2611, 2:05 PM
SENSOR ALARM
L ?:PREMIUM ANNULAR
ANNULAR SPACE
SENSOR OUT ALARM
SEP 6, 2011 2:05 PM
SENSOR ALARM -- - --
L B:PREMIUM FILL SUMP
OTHER SENSORS
SENSOR OUT ALARM
SEP 6, 2011 2:06 PI-1
TENSOR ALARM - - - --
L13:74 UDC-
DISPENSER PAN
SENSOR OUT ALARM
SEP 6. 2011 2:08 PM
SENSOR ALARM - - - --
14:9-10 UDC
DISPENSER PAN
SENSOR OUT ALARM
SEP 6, 2011 2:09 PM
SENSOR (ALARM - - - --
L !:ANNULAR SYPHON
ANNULAR SPACE
SENSOR OUT ALARM
SEP 6. 2011 2:09 P11
SENSOR ALARM - - - --
L 9:PREMIUM TURBINE SUMP
STP SUMP
SENSOR OUT ALARM
SEP 6. 2011 2:09 PM
SENSOR ALAPI.1 - - - --
L15:11-12 UDC
DISPENSER PAN
SENSOR OUT ALARM
SEP 6. 2011 2:09 PM
SENSOR ALARM
LID: 1-2 UDC
DISPENSER PAN
SENSOR OUT ALARM
SEP 6. 2011 2:09 PM
SENSOR ALARM - - - --
L 5:MAIN UNL FILL
OTHER SENSORS
SENSOR OUT ALARM
SEP E. 20i1 2:09 PM
SENSOR ALARM - - - --
L 6:MAIN UNL TURBINE
STP SUMP
SENSOR OUT ALARM
SEP 6. 2011 2:09 PIH
SENSOR ALARM - - - --
L B:PREMIUM'FILL SUMP
OTHER ,SENSORS
SENSOR OUT ALARM
SEP 6, 2011 * 2:09 P11
i
SENSOR ALARM - --
L 2:SYFHO0 FILL'SUMP
OTHER. SENSORS -
SENSOR OUT ALARM
SEP, 6. 2011 2:09 PM
I
SENSOR ALARM - ----
L 3.:SYPHON TURBINE SUMP
PIPING SUMP
SENSOR OUT ALARM
SEP 6, 2011 2:09 PI•I
SENSOR ALARM - - - --
L 4:ANNULAR MAIN IJNL
ANNULAR SPACE
SENSOR"OUT ALARM
SEP 6, 2011 2:09 PM
SENSOR ALARM - - - --
LIC:3 -4 UDC
D•1SPE14SER PAN
SENSOR OUT ALARM
SEPa 6. 2011 2:09 PM
SENSOR ALARM - - - --
L12:5-6 UDC
DISPENSER PAN
SENSOR OUT ALARM
SEP 6. 2011 2:09 PM
SENSOR ALARM - - - --
L 7:PREMIUM ANNULAR
ANNULAR SPACE
SENSOR OUT ALARM
SEP 6, 2011 2:09 PM
ARCO 5526
900 MC- NTEREY ST
BAI'MF I ELD - CA93305
805 -861 -1972
SEP 6. 2011 2:09 PM
SYSTEM STATUS REPORT
T 3:H1GH PRODUCT ALARM
IN -TANK ALARM - - - -- - - -- IN -TANK ALARM - - - -- - - -- IN -TANK. ALARM -- --
T 2:UNLEADED MAIN T 3:PREMIUM T 2:UNLEAISED MAIN
HIGH PRODUCT ALARM PROBE OUT PROBE OUT
SEP 6. 2011 2:21 PM SEP 6. 2011 2:24 PM SEP 6. 2011 2:26 PM
IN -TANK ALARM - - - -- - - -- IN -TANK ALARM - - - -- __ -- IN-TANX ALARM - - - -- f 2: UIVI.EADED MA I N T 3: PREM 1 Uhl T 2: UNLEADED MA IN
MAX PRODUCT ALARM 1 LAVAL I D FUEL LEVEL LOW TEMP WAR141 Ni`
SEP 6, 2011 2:21 PM SEP 6. 2011 2:25 PM SEP 6, 2011 2:27 Pl1
AKO 5526 IN -TANK ALARM - - - -- 1N-TANX: ALARM ----'
900 MONTEREY ST T 3:PREMIUM • T I:UNLEADED SYPHONBAKERSFI,ELD- CA93305 LOW PRODUCT ALARM MAX PRODUCT ALARM
805-861-11972 SEP 6. 2011 2:25 PM SEP 6, 2011 2:27 PM
SEP 6. 2011 2:22 PIi
SYSTEM S'PATUS REPORT
T 2 :HIGH PRODU C -T ALARM
T 2:MAX PRODUCT ALARM IN-TANK ALARM - - - -- IN -TANi, ALARM - - ---
T 3:PREMIUM T I:UNLEADED SYPHONDELIVERYNEEDEDHIGHPRODUCTALARMSEP6. 2011 2 :25 PM SEP 6. 2011 2:27 PM
IN -TANK ALARM - - - --
T 3:PREMIUM - - -- IN -TANK ALARM - - - -- - - -- 1N -TANK ALARM -- - --
HIGH PRODUCT ALARM T 2:UNLEADED MAIN T I:UNLEADED SYPHONSEP6. 2011 2:24 PM HIGH PRODO3'T ALARM OVERFILL ALARM
SEP 6, 2011 2:25 PM SEP 6, 2011 2 :28 PM
1N -TANK ALARM - - - --
T 3:PREMIUM - - -- IN -TANI' ALARM - - IN -TANi: ALARM - ---- MAX PRODUA T ALARM T 2:UNLEADED MAIN T I:UNLEADED SYPHONSEP6, 2011 2:24 PM MAX PRODLk-,T ALARM PROBE OUTSEP6. 2011 2:25 PM SEP 6. 2011 2:28 Pit
IN -TANK ALHRil - - - --
T 3:PREMIUM - - -- IN -TANY ALARM - - - -- - -- IN -TANK ALAP.M - - - -- OVERFILL ALARM T 2:UNLEADED MAIN T I:UNLEADED SYPHONSEP6. 2011 2:24 PH OVERFILL ALARM LOW TEMP WARNINGSEP6.. 2011 2:26 P14 SEP 6. 2011 2:29 PM
T 3:PREMIUM
INVENTORY INCREASE
INCREASE START
SEP 6. 2011 2:23 PM
VOLUME - 8114 GALS
HEIGHT - 60.09 INCHES
WATER - 0.76 INCHES
TEMP - 109.1 DEC F
INCREASE END
SEP 6. 2011 2:30 PM
VOLUME - 11627 GALS
HE1r,HT - 108.25 INCHES
WATER - 1.07 INCHES
TEMP - 108.5 DEG F
GROSS INCREASE- 3513
TC NET INCREASE- 3396
T 2:UNLEADED MAIN
I NVENTOR`,' I NCREASE
INCREASE START
SEP 6. 2011 2:25 PM
VOLUME - 9576 GALS
HEIGHT - 70.00 INCHES
WATER - 1.02 INCHES
TEMP - 106.8 DEG F
INCREASE END
SEP 6. 2011 2:32 PM
VOLUME - 11627 GALS
HEIGHT - 108.32 INCHES
WATER - 1.25 INCHES
TEMP - 108.4 DEG F
GROSS INCREASE- 2051
TC NET INCREASE- 1983
ARCO 5526
900 MONTEREY ST
SAKERSFIELD.CA933U5
805 -861 -1972
SEP 6. 2011 2:32 PM
SYSTEM STHTUS REPORT
T 3:LOW PRODIA:T ALARM
T 3:DELIVERY NEEDED
ARCO 5526
900 MONTEREY ST
BAKERSFIELD.CA93305
805 - 861 -1972
SEP 6, 2011 2:32 PM
SYSTEM STATUS REPORT
T 3:LOW PRODUCT ALARM
T 3:DELIvERY NEEDED
ARM 5526
900 MONTEREY ST
BAKERSFIELD.CA93305
805 - 861 -1972
SEP 6. 2011 2:.32 Phl
SYSTEM STATUS REPORT
T 3:LOW PRODUCT ALARM
T 3:DELIVERY NEEDED
ARCO 5526
900 MONTEREY ST
BAXERSFIELD.CA93305
805-861 -1972
SEP 6, 2011 2:32 P11
SYSTEM STATUS REPORT
r 3:LOW PRODUCT ALARM
T 3:DELIVERY NEEDED
a
ARCO 5526
900 MONTEREY ST
BAXERSFIELD.CA93305
805- 861 -1972
SEP 6. 201,1 2:32 PM
SYSTEM STATUS REPORT
T 3:LOW PRODUCT ALARM
T 3:15ELIVERY WEEDED
T I:UNLFADED SYPHON
INVENTORY INCREASE
INCREASE START
SEP 6. 2011 2:27 PM
VOLUME - 9737 GALS
HEIGHT - 71.19 INCHES
WATER - 0.00 INCHES
TEMP - 109.2 DEG F
I NCREA.SE END
SEP 6. 2011 2:31 PM
VOLUME - 11627 GALS
HEIGHT - 111.66 1NCHES
WATER - 0.00 INCHES
TEMP - 109.1 DEG F
GROSS INCREASE- 1090
TC NET INCREASE- 1827
SWRCB, January 2006
Spill Bucket Testing Report Form
Thisform is intendedfor use by contractors performing annual testing of USTspill containment structures. The completedform and
printoutsfrom tests (ifapplicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: Arco AM PM I Date of Testing: 9/6/2011
Facility Address: 900 Monterey Street, Bakersfield, CA 93305
Facility Contact: Alondra Hernandez I Phone: 661- 835 -8044
Date Local Agency Was Notified of Testing: 8/22/2011
Name of Local Agency Inspector (fpresent during testing): Ernie Medina
2. TESTING CONTRACTOR INFORMATION
Company Name: Confidence UST Services, Inc.
Technician Conducting Test: Bryan A Self
Credentials: Z CSLB Contractor Z ICC Service Tech. Z SWRCB Tank Tester Other (Sped)
License Number(s): CSLB# 804904 ICC# 8022804 SWRCB# 11 -1756
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: x Hydrostatic Vacuum Other
Test Equipment Used: Lake Test Equipment Resolution: 0.0625"
Identify Spill Bucket (By Tank
Number, Stored Product, etc.)
1 Regular Master 2 Regular Slave 3 Super 4
Bucket Installation Type: Direct Bury
x Contained in Sump
Direct Bury
x Contained in Sump
Direct Bury
x Contained in Sump
Direct Bury
Contained in Sum
Bucket Diameter: 14.00" 14.00" 14.00"
Bucket Depth: 12.00" 12.00" 12.00"
Wait time between applying
vacuum /water and start of test:
5 min. 5 min. 5 min.
Test Start Time (Ti): 1:00pm 1:00pm 1:00pm
Initial Reading (RQ: 9.75" 10.25" 9.75"
Test End Time (TF): 2:00pm 2:00pm 2:00pm
Final Reading (RF): 9.75" 10.25" 9.75"
Test Duration (TF — Tj): 1 hour 1 hour 1 hour
Change in Reading (RF - Ri): 0.00" f 0.00" 0.00"
Pass/Fail Threshold or
Criteria: 0.0625" 0.0625" 0.0625"
Test Result: 9 Pass Fail x Pass Fall Z Pass Fail Pass Fail
Comments — (include information on repairs made prior to testing, and recommendedfollow -upforfailed tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements.
Technician's Signature: Date: 9/6/2011
State laws and regulations do not cuVently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
Key
1) VeederRooT TLS 350
2) ESO
3) Exterior Overfill Alarm
4) ATG Probe
5) VeederRoot 208 Sump Senser
6) VeederRoot 209 Annular Senser
7) VeederRoot Red Jackit LLD
8) F.E.Petro LLD
9) Fill SB
10) Vapor SB
roll
Arco AM /PM
900 Monterey ST
Bakersfield CA, 93305
ILI
2 5
O 9 10 0 8
Super
2 5
09100 7
Re ular
2 5
O 90 10 40 7
Regular