Test Date: 10/03/2011
Order Number: 3186804
Dear Regulator,
s 5
Date Printed and Mailed: 10/14/2011
Enclosed are the results of recent testing performed at the following facility:
CHEVRON 98109
1131 OAK ST. X/ST CALIFORIA AVE
BAKERSFIELD, CA. 93304
Testing performed:
Impact Valve
Leak detector tests
Monitor Certification
Secondary Containment -Spill Container
Sincerely,
Dawn Kohlmeyer
Manager, Field Reporting
t
Ad
r Tbnknology
IPURPOSE: COMPLIANCE
TEST DATE: 10/03/11
CLIENT: CHEVRON PRODUCTS COMPANY
145 S. STATE COLLEGE BLVD
SUITE 400
BREA, CA 92821
TINA SCOLARO
714)671 -3356
TANKNOLOGY CERTIFICATE OF TESTING
8501 N MOPAC EXPRESSWAY, SUITE 400 AUSTIN, TEXAS 78759
TELEPHONE (512) 451 -6334 FAX (512) 459 -1459
TEST RESULT SUMMARY REPORT
WORK ORDER NUMBER: 3186804
CUSTOMER PO: 15071518
SITE: CHEVRON 98109
1131 OAK ST. X/ST CALIFORIA AVE
BAKERSFIELD, CA 93304
MANAGER - JALED
661)324 -7621
TEST TYPE: TLD -1
Drnrinr Dina Tinhfnacc Tact Racn14c
LINE
ID
LINE
PRODUCT
LINE
MATERIAL
DELIVERY
TYPE
TEST RESULT
A B C D
FINAL LEAK RATE (gph)
A B C D
IMPACT
VALVE
FUNCTION
Supreme 1 SUPREME DW FIBERG PRESSURE
RESULT
Supreme 1
Y
Plus 2 PLUS DW FIBERG PRESSURE Y
Regular 3 REGULAR DW FIBERG PRESSURE
P
Y
Diesel 4 DIESEL DW FIBERG PRESSURE
ELECTRONI 001095
Y
Gvic+inn I inn I ank I'lafar4nr Taco
LINE
ID
EXISTING LEAK DETECTOR #1 EXISTING LEAK DETECTOR #2
MANUFACTURER MODEL # SERIAL # RESULT MANUFACTURER MODEL # SERIAL # RESULT
Supreme 1 VEEDERROOT ELECTRONI 255795 P
Plus 2 VEEDERROOT ELECTRONI 296578 P
Regular 3 VEEDERROOT ELECTRONI 001095 P
Diesel 4 VEEDERROOT ELECTRONI 153413 P
Now Ronlaramon+ I ino I oak notor+nr Tact
LINE
ID
REP ACED LEA ECTOR #1 REP ED LEAK DET ECTOR #2
MANUFACTURER MODEL # SERIAL # RESULT MANUFACTURER MODEL # SERIAL # RESULT
hor owner aetauea report mtormation, visit www.tanknology.com ana select un -Line [reports -WKAP, or contact your local i anknoiogy omce.
Tester Name: EDWIN PINEDA Technician Certification Number: 8026748
Printed 10/14/2011 07:13 MTUTTLE
INDIVIDUAL TANK INFORMATION AND TEST RESULTS
i Tanknoillogy
TEST DATE: 10 /03/11 8501 N MOPAC EXPRESSWAY, SUITE 400 WORK ORDER NUMBER3186804
CLIENT:CHEVRON PRODUCTS AUSTIN, TEXAS 78759 (512) 451 -6334 SITE:CHEVRON 98109
TANK INFORMATION
Tank ID: supreme 1 Tank manifolded: NO Bottom to top fill in inches: 156.0
Product: SUPREME Vent manifolded: YES Bottom to grade in inches: 161.0
Capacity in gallons: 9,842 Vapor recovery manifolded: YES Fill pipe length in inches: 56.0
Diameter in inches: 91.00 Overfill protection: YES Fill pipe diameter in inches: 4.0
Length in inches: 354 Overspill protection: YES Stage I vapor recovery: DUAL
Material: Dw FIBERG Installed: ATG Stage II vapor recovery: ASSIST
CP installed on:
COMMENTS
TANK TEST RESULTS Test Method: VacuTect LEAK DETECTOR TEST RESULTS Test method: FTA
Start (in) End (in)
Dipped Water Level: New /passed Failed /replaced New /passed Failed /replaced
L.D. #1 L.D. #1 L.D. #2 L.D. #2
Dipped Product Level:
Probe Water Level: Make: VEEDERROOT
Ingress Detected: Water Bubble Ullage Model: ELECTRONIC
Test time: S /N: 255795
Open time in sec:
Inclinometer reading: Holding psi: VacuTect Test Type: NOT
Resiliency cc: NOT
VacuTect Probe Entry Point: TESTED
Test leak rate ml /m: TESTED
Pressure Set Point: Metering psi:
Tank water level in inches: Calib. leak in gph:
Water table depth in inches: Results: PASS
Determined by (method):
Result:
COMMENTS
COMMENTS
LINE TEST RESULTS Test type: TLD -i
LINE A B C D
Material: Dw FIBERG
Diameter (in): 3.0
Length (ft): 250.0
Test psi:
Bleedback cc:
Test time (min): NOT NOT NOT NOT
Start time: TESTED TESTED TESTED TESTED
End time:
Final gph:
Result:
Pump type: PRESSURE
Pump make: FE PETRO
COMMENTS Impact Valves Operational: YES
Printed 10/14/2011 07:13
INDIVIDUAL TANK INFORMATION AND TEST RESULTS
i Tanknabgy
TEST DATE: 10 /03/11 8501 N MOPAC EXPRESSWAY, SUITE 400 WORK ORDER NUMBER3186804
CLIENT:CHEVRON PRODUCTS AUSTIN, TEXAS 78759 (512) 451 -6334 SITE:CHEVRON 98109
TANK INFORMATION
Tank ID: Pius 2 Tank manifolded: No Bottom to top fill in inches: 155.0
Product: PLUS Vent manifolded: YES Bottom to grade in inches: 160.0
Capacity in gallons: 9,842 Vapor recovery manifolded: YES Fill pipe length in inches: 55.5
Diameter in inches: 91.00 Overfill protection: YES Fill pipe diameter in inches: 4.0
Length in inches: 354 Overspill protection: YES Stage I vapor recovery: DUAL
Material: DW FIBERG Installed: ATG Stage II vapor recovery: ASSIST
CP installed on:
COMMENTS
TANK TEST RESULTS Test Method:vacuTect LEAK DETECTOR TEST RESULTS Test method: PTA
Start (in) End (in)
Dipped Water Level: New /passed Failed /replaced New /passed Failed/replaced
L.D. #1 L.D. #1 L.D. #2 L.D. #2
Dipped Product Level:
Probe Water Level: Make: VEEDERROOT
Ingress Detected: Water Bubble Ullage Model: ELECTRONIC
Test time: S /N: 296578
Open time in sec:
Inclinometer reading: Holding psi: VacuTect Test Type: NOT
Resiliency c s NoT
VacuTect Probe Entry Point: TESTED
Test leak rate ml /m: 189.0 TESTED
Pressure Set Point: Metering psi:
Tank water level in inches: Calib. leak in gph: 3.00
Water table depth in inches: Results: PASS
Determined by (method):
Result: COMMENTS
COMMENTS
LINE TEST RESULTS Test type: TLD -1
LINE A B C D
Material: DW FIBERG
Diameter (in): 3.0
Length (ft): 250.0
Test psi:
Bleedback cc:
Test time (min): NOT NOT NOT NOT
Start time: TESTED TESTED TESTED TESTED
End time:
Final gph:
Result:
Pump type: PRESSURE
Pump make: FE PETRO
COMMENTS Impact Valves Operational: YES
Printed 10/14/2011 07:13
INDIVIDUAL TANK INFORMATION AND TEST RESULTS
Tanknobgy
TEST DATE: 10 /03/11 8501 N MOPAC EXPRESSWAY, SUITE 400 WORK ORDER NUMBER3186804
CLIENT:CHEVRON PRODUCTS AUSTIN, TEXAS 78759 (512) 451 -6334 SITE:CHEVRON 98109
TANK INFORMATION
Tank ID: Regular 3 Tank manifolded: NO Bottom to top fill in inches: 155.0
Product: REGULAR Vent manifolded: YES Bottom to grade in inches: 160.0
Capacity in gallons: 9,842 Vapor recovery manifolded: YES Fill pipe length in inches: 55.5
Diameter in inches: 91.00 Overfill protection: YES Fill pipe diameter in inches: 4.0
Length in inches: 354 Overspill protection: YES Stage I vapor recovery: DUAL.
Material: Dw FIBERG Installed: ATG Stage II vapor recovery: ASSIST
CP installed on:
COMMENTS
TANK TEST RESULTS Test Method:VacuTect LEAK DETECTOR TEST RESULTS_ T_ est me_ thod: PTA
Start (in) End (in)
Dipped Water Level: New /passed Failed /replaced New /passed Failed/replaced
Dipped Product Level: L.D. #1 L.D. #1 L.D. #2 L.D. #2
Probe Water Level: Make: VEEDERROOT
Ingress Detected: Water Bubble Ullage Model: ELECTRONIC
Test time: S /N: 001095
Open time in sec:
Inclinometer reading: psi: Holding pVacuTectTestType: NOT
Resiliency cc: NOT
VacuTect Probe Entry Point: TESTED
Test leak rate ml /m: 189.0 TESTED
Pressure Set Point: Metering psi: Tank water level in inches: Calib. leak in gph: 3.00
Water table depth in inches: Results: PASS
Determined by (method):
Result:
COMMENTS
COMMENTS
LINE TEST RESULTS Test type: TLD -1
LINE A B C D
Material: Dw FIBERG
Diameter (in): 3.0
Length (ft): 250.0
Test psi:
Bleedback cc:
Test time (min): NOT NOT NOT NOT
Start time: TESTED TESTED TESTED TESTED
End time:
Final gph:
Result:
Pump type: PRESSURE
Pump make: FE PETRO
COMMENTS Impact Valves Operational: YES
Printed 10/14/2011 07:13
INDIVIDUAL TANK INFORMATION AND TEST RESULTS
r Tankrmfogy
TEST DATE: 10 /03/11 8501 N MOPAC EXPRESSWAY, SUITE 400 WORK ORDER NUMBER3186804
CLIENT:CHEVRON PRODUCTS AUSTIN, TEXAS 78759 (512) 451 -6334 SITE:CHEVRON 98109
Printed 10/14/2011 07:13
TANK INFORMATION
Tank ID: Diesel 4 Tank manifolded: NO Bottom to top fill in inches: 155.5
Product: DIESEL Vent manifolded: NO Bottom to grade in inches: 160.5
Capacity in gallons: 9,842 Vapor recovery manifolded: xo Fill pipe length in inches: 57.0
Diameter in inches: 91.00 Overfill protection: YES Fill pipe diameter in inches: 4.0
Length in inches: 354 Overspill protection: YES Stage I vapor recovery: NONE
Material: DW FIBERG Installed: ATG Stage II vapor recovery: NONE
CP installed on:
COMMENTS
TANK TEST RESULTS Test Method:vacuTect LEAK DETECTOR TEST RESULTS Test method: PTA
Start (In) End (In)
Dipped Water Level: New /passed Failed/replaced New /passed Failed /replaced
Dipped Product Level: L.D. #1 L.D. #1 L.D. #2 L.D. #2
Probe Water Level: Make: VEEDERROOT
Ingress Detected: Water Bubble Ullage Model: ELECTRONIC
Test time: S /N: 153413
Open time in sec:
Inclinometer reading: Holding psi: VacuTect Test Type: NOT
Resiliency NOT
VacuTect Probe Entry Point: TESTED
Test leak rate ml /m: 189.0 TESTED
Pressure Set Point: Metering psi: Tank water level in inches: Calib. leak in gph: 3.00
Water table depth in inches: Results: PASS
Determined by (method):
Result:
COMMENTS
COMMENTS
LINE TEST RESULTS Test type: TLD -i
LINE A B C D
Material: Dw FIBERG
Diameter (in): 3.0
Length (ft): 250.0
Test psi:
Bleedback cc:
Test time (min): NOT NOT NOT NOT
Start time: TESTED TESTED TESTED TESTED
End time:
Final gph:
Result:
Pump type: PRESSURE
Pump make: FE PETRO
COMMENTS Impact Valves Operational: YES
Printed 10/14/2011 07:13
MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State of California
Authority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3 Title 23, California Code of Regulations
This form must be used to document testing and servicing of monitoring equipment. If more than one monitoring system control panel is installed at the facility, a separate
certification or report must be prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank
system owner /operator. The owner /operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date.
A. General Information
Facility Name: CHEVRON 98109
Site Address: 1131 OAK ST. X/ST CALIFORIA AVE
Facility Contact Person: MANAGER - JALED
Make /Model of Monitoring System:TLS350
B. Inventory of Equipment Tested /Certified
Check the appropriate boxes to indicate specific equipment inspected /serviced
City: BAKERSFIELD
Contact Phone No: 324 -7621
Date of Testing /Service: 10/03/2011
Work Order Number: 3186804
CA Zip: 93304
Tank ID: T1 SUPREME Tank ID: T2 PLUS
7 In -Tank Gauging Probe. Model: MAG PROBE X In -Tank Gauging Probe. Model: MAG PROBE
X Annular Space or Vault Sensor. Model: VR-409 Annular Space or Vault Sensor. Model: VR-409
X Piping Sumprrrench Sensor(s). Model: VR -208 Piping Sump/Trench Sensor(s). Model: VR -208
X Fill Sump Sensor(s). Model: VR -208 Fill Sump Sensor(s). Model: VR -208
Mechanical Line Leak Detector. Model: Mechanical Line Leak Detector. Model:
X Electronic Line Leak Detector. Model: ELECTRONIC X Electronic Line Leak Detector. Model: ELECTRONIC
X Tank OverfilUHigh -Level Sensor. Model: PROBE Tank Overfill /High -Level Sensor. Model: PROBE
Other (specify equipment type and model in Section E on page 2). Other (specify equipment type and model in Section E on page 2).
Tank ID: T3 REUOTTIR Tank ID: T4 DIFz5F_L
In -Tank Gauging Probe. Model: MAG PROBE In -Tank Gauging Probe. Model: MAG PROBE
X1 Annular Space or Vault Sensor. Model: VR-409 Annular Space or Vault Sensor. Model: VR-409
X Piping Sump/Trench Sensor(s). Model: VR -208 X Piping Sump/Trench Sensor(s). Model: VR -208
Xj Fill Sump Sensor(s). Model: VR -208 X Fill Sump Sensor(s). Model: VR -208
Mechanical Line Leak Detector. Model: Mechanical Line Leak Detector. Model:
X1 Electronic Line Leak Detector. Model: ELECTRONIC 71 Electronic Line Leak Detector. Model: ELECTRONIC
Tank Overfill /High -Level Sensor. Model: PROBE Tank OverfilUHigh -Level Sensor. Model: PROBE /FLAPPER
Other (specify equipment type and model in Section E on page 2). Other (specify equipment type and model in Section E on page 2).
Dispenser : 1 -2 Dispenser ID: 7 -8
Dispenser Containment Sensor(s) Model: VR -208 X Dispenser Containment Sensor(s) Model: VR -208
X Shear Valve(s). X Shear Valve(s)
Dispenser Containment Float(s) and Chain(s). 7 Dispenser Containment Float(s) and Chain(s).
Dispenser ID: 3-4 Dispenser ID: 9 -10
0 Dispenser Containment Sensor(s) Model: VR -208 Xj Dispenser Containment Sensor(s). Model: VR -208
Shear Valve(s). ShearValve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
Dispenser ID: 5 -6 Dispenser ID:
FRI Dispenser Containment Sensor(s) Model: VR -208 Dispenser Containment Sensor(s). Model:
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification
I certify that the equipment identified in this document was inspected /serviced in accordance with the manufacturers' guidelines.
Attached to this certification is information (e.g manufacturers' checklists) necessary to verify that this information is correct.
and a Site Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also attached
a copy of the (Check all that apply): X System set -up X Alarm history report
a (% Technician Name (print): EDWIN PINEDA Signature:
Certification No.: 8026748 -UT License. No.: 743160 (Class 'A' General Enginering Contractor License)
Testing Company Name:Tanknology Phone No.: (800) 800 -4633
Site Address: 11000 N. MoPac Expressway, suite 500, Austin, TX 78759 Date of Testing /Servicing: 10/03/2011
Monitoring System Certification Page 1 of 3 Based on CA form dated 03/08
Monitoring System Certification
Site Address 1131 OAK ST. X/ST CALIFORIA AVE
D. Results of Testing /Servicing
Software Version Installed: 327.04
Complete the following checklist:
Date of Testing /Service: 10/03/2011
El Yes No' Is the audible alarm operational?
X Yes No' Is the visual alarm operational?
Q Yes No' Were all sensors visually inspected, functionally tested, and confirmed operational?
Q Yes No' Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not
interfere with their proper operation?
El Yes No' N/A If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) operational?
X Yes No' N/A
For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate positive
shut -down? (check all that apply) X Sump/Trench Sensors; X Dispenser Containment Sensors.
Did you confirm positive shut -down due to leaks and sensor failure /disconnection? X Yes 0 No
Fx Yes No' N/A For tank systems that utilize the monitoring system as the primary tank overfill warning device (Le.: no mechanicaloverfillpreventionvalveisinstalled), is the overfill waming alarm visible and audible at the tank fill points(s) and operating
properly? If so, at what percent of tank capacity does the alarm trigger? so
Yes' M No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the
manufacturer name and model for all replacement parts in Section E, below.
Yes' 7X No Was liquid found inside any secondary containment systems designed as dry systems? (check all that apply) Product;
Water. If yes, describe causes in Section E, below.
X Yes No Was monitoring system set -up reviewed to ensure proper settings? Attach set -up reports, if applicable.
Yes No • Is all monitoring equipment operational per manufacturers' specifications?
In Section E below, describe how and when these deficiences were or will be corrected.
E. Comments:
Page 2 of 3 Based on CA form dated 03/08
Monitoring System Certification
Site Address: 1131 OAK ST. X/ST CALIFORIA AVE
F. In -Tank Gauging / SIR Equipment
Check this box if no tank gauging or SIR equipment is installed.
Date of Testing /Service: 10/03/2011
Check this box if tank gauging is used only for inventory control.
Check this box if no tank gauging or SIR equipment is installed.
This section must be completed if in -tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
x Yes No' Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
Q Yes No' Were all tank gauging probes visually inspected for damage and residue buildup?
ElYes No' Was accuracy of system product level readings tested?
QYes No' Was accuracy of system water level readings tested?
El Yes No Were all probes reinstalled properly?
0 Yes No • Were all items on the equipment manufacturers' maintenance checklist completed?
In the Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD) : Check this box if LLDs are not installed.
Complete the following checklist:
x Yes No - N/A For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance?
Check all that apply) Simulated leak rate: 3 g.p.h 0.1 g.p.h 0.2 g.p.h
M Yes No • Were all LLDs confirmed operational and accurate within regulatory requirements?
x Yes No • Was the testing apparatus properly calibrated?
Yes No • x N/A For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
M Yes No' N/A For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak?
x Yes No • N/A For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected?
M Yes No - N/A For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a test?
Q Yes No . N/A For electronic LLDs, have all accessible wiring connections been visually inspected?
LJ Yes No' Were all items on the equipment manufacturers' maintenance checklist completed?
In the Section H, below, describe how and when these deficiencies were or will be corrected.
H. Comments:
Page 3 of 3 Based on CA form dated 03/08
SWRCB, January 2002
Secondary Containment Testing Report Form
Page 1.
Thisform is intendedfor use by contractors performing periodic testing of UST secondary containment systems. Use the
appropriate pages ofthisform to report resultsfor all components tested. The completedform, written test procedures, and
printoutsfrom tests (ifapplicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: CHEVRON 98109
Pass
DateofTesting: 10/03/2011
Facility Address: 1131 OAK ST. X /ST CALIFORIA AVE , BAKERSFIELD, CA, 93304
Facility Contact: MANAGER - JALED
X
Phone: (661) 324 -7621
Date Local Agency Was Notified of Testing:
SWRCB Licensed Tank Tester
Name of Local Agency Inspector (ifpresent during testing): ERNIE MEDINA
2. TESTING CONTRACTOR INFORMATION
Company Name: TANKNOLOGY, INC.
Pass
Technician Conducting Test: EDWIN PINEDA
Repairs
Made
Credentials: X CSLB Licensed Contractor
Not
Tested
SWRCB Licensed Tank Tester
Spill Box 1 SUP FILL
License Type: A -UT License Number: 743160 - 8026748
Manufacturer
Manufacturer Training
Component(s) Date Training Expires
PHILTITE SPILL BUCKET 01/24/2013
OPW SPILL BUCKET 02/03/2013
x
3. SUMMARY OF TEST RESULTS
Component Pass Fail
Not
Tested
Repairs
Made Component Pass Fail
Not
Tested
Repair
Made
Spill Box 1 SUP FILL El El
Spill Box 2 PLU FILL x
Spill Box 3 REG FILL X D
Spill Box 4 DIE FILL X
El F-1 El
11 El F1 El El-
El El El El El El 0 E
El 0 El 0 El El El
0 101
El El El El El
El El 1:1 El El El
El EJ El ED
Ifhydrostatic testing was performed, describe what was done with the water after completion oftests:
WATER FROM SPILL BUCKETS WAS PLACE IN SITE DRUM AFTER TESTING
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
To the best ofmy knowledge, thefacts stated in this document are accurate and infull compliance with legal requirements
Technician's Signature: Ct{?.- Date: 10/03/2011
SWRCB, January 2006
9. Spill Bucket Testing Report Form
Thisform is intendedfor use by contractors performing annual testing of USTspill containment structures. The completedform and
printoutsfrom tests (fapplicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: CHEVRON 98109
Technician Conducting Test: EDWIN PINEDA
Date of Testing: 10/03/2011
Facility Address: 1131 OAK ST. X /ST CALIFORIA AVE , BAKERSFIELD, CA, 93304
Facility Contact: MANAGER - JALED
ICC Service Tech.
Phone: (661) 324 -7621
Date Local Agency Was Notified of Testing:
E
Name of Local Agency Inspector (if present during testing): ERNIE MEDINA
2. TESTING CONTRACTOR INFORMATION
Company Name: TANKNOLOGY, INC.
Technician Conducting Test: EDWIN PINEDA
Credentials 1: CSLB Contractor ICC Service Tech. SWRCB Tank Tester E Other (Specie) A -UT
License Number: 743160-8026748
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: El Hydrostatic Vacuum Other
Test Equipment Used: TAPE MEASURE Equipment Resolution: VISUAL
IN
Identify Spill Bucket(By Tank
Number, Stored Product, etc.)
1 1 SUP FILL 2 2 PLU FILL 3 3 REG FILL 4 4 DIE FILL
Bucket Installation Type: Direct Bury
Contained in Sump
E] Direct Bury
X Contained in Sump
Direct Bury
X Contained in Sump
Direct Bury
X Contained in Sump
Bucket Diameter: 11 11 11 12"
Bucket Depth: 1211 1211 1211 1411
Wait time between applying
vacuum/water and starting test:
10 MIN 10 MIN 10 MIN 10 MIN
Test Start Time (TI ): 0930 0930 0930 0930
Initial Reading (RI ): 1011 1011 10.5 " 12"
Test End Time (TF ): 1030 1030 1030 1030
Final Reading (RF ): 10" 10" 10.5" 12"
Test Duration: 1HR 1HR 1HR 1HR
Change in Reading (R F - RI ): 0 0 0 0
Pass/Fail Threshold or
Criteria:
0 0 0 0
Test Result: 0 Pass Fail 0 Pass Fail 0 Pass 1:1 Fail Pass Fail
Comments - (include information on repairs made prior to testing, and recommendedfollow -upforfailed tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
1 hereby certify that all the information contained in this report is true, accurate, and infull compliance with legal requirements.
Technician's Signature: -,, ,, n A, V, Date: 10/03/2011
I
State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
Work Order: 3186804
ESO) & (ESV) Testing Form - Vemon I- 6125!2007
Emergency Shut Off (ESO) &
Dispenser Emergency Shutoff Valve (ESV)
ANNUAL TEST RECORD LOCATIONS AND TEST DATA
S4 I
Eme en Shut SO Testing Results
On in accordance with "ESO Vendor (3- 21- 05).doc ", from Valero's Retail
Compll;ance Department, as a part of annual compliance testing, this representative tested the
Emergency Shut Off O switches indicated on this sketch. Findin listed below:
Dis eraser Eme enc h toff Valve S Testin Resuits
On C t in. accordance with NFPA 30A this representative tested the automatic - closing feature
ofthe Dispenser Emergency Shutoff VALVE(S) (ESV) located in the supply lines at the base of each
individual island type dispenser indicated on the diagram below. Each device ( # }_ in all,
would automaticalt close. Findings listed below:
Site Map OfLocation tad Pleoeuent ofDevices Tested,
to;o
Zit
I =0 0
EE Dw
4 d
G o S b
Sitl<nature Of Representative: L, , l ,
Testing `
Company: 10 Date: Q ?
Location Name: 0 S Cj Store #: stet` ro fl:
Maintenance log #
Addr+esa: I 0 A City: State:
Emergency Shut Off (ESO) IfNo, Provide
Operational? a N Maintenance log # Date Called
Disp. Emergency Shut Off IfNo. Provide
Valve (ESV) Operational? CY) N Maintenance Log # Hato called
Tanknology Inc. 11000 N. MoPac Expressway, Suite 500, Austin, Texas 78759
0p Tanl wkigy
8501 N MOPAC EXPRESSWAY, SUITE 400
AUSTIN, TEXAS 78759
512) 451 -6334
FAX (512) 459 -1459
TEST DATE:10 /03/11 WORK ORDER NUMBER3186804
CLIENT:CHEVRON PRODUCTS COMPANY SITE:CHEVRON 98109
COMMENTS
COCO SITE, Conducted Witness Annual Monitor Certification Testing with Inspector Ernie Medina
Bakersfield Fire Department. site contacted 9/27/11 and confirmed testing with "WENDY ".
Technician checked in with 2ndSite and WO # 111003 -034 was given. All tests passed.
PARTS REPLACED
QUANTITY DESCRIPTION
HELIUM PINPOINT TEST RESULTS (IF APPLICABLE)
ITEMS TESTED
HELIUM PINPOINT LEAK TEST RESULTS
Printed 10/14/2011 07:13 MTUTTLE
SITE DIAGRAM
r Tanknokogy
8501 N MOPAC EXPRESSWAY, SUITE 400
AUSTIN, TEXAS 78759
512) 451 -6334
FAX (512) 459 -1459
TEST DATE: 10/03/11 WORK ORDER NUMBER3186804
CLIENT:CHEVRON PRODUCTS COMPANY SITE: CHEVRON 98109
III
0
9
Chevron #98109
1131 Oak St.
Bakersfield, CA
93304
T# a F L1O0
STP Diesel
10K
T# 1STPSupreme A
10K L 1
T 3
STP Regular nI
10K L8 Y
t T# 2 APlus DL) 10K L5
cas VENT
O
9•
Printed 10/14/2011 07:13 MTUTTLE
ATG Information Work Order# 3186804
0
11 0100
OCT 3, 2011 12:11 PM
CHEVRON C.S.I. 1920
1131 OAK ST.
BAKERSFIELD,CA,
9-8109PH661- 324 -7621
SYSTEM STATUS REPORT
ALL FUNCTIONS NORMAL
0
0
150301
OCT 3, 2011 12:11 PM
1:CHEVRON C.S.I. 1920
0
0
150302
OCT 3, 2011 12:11 PM
2:1131 OAK ST.
0
0
150303
OCT 3, 2011 12:11 PM
3:BAKERSFIELD,CA.
0
0
150304
OCT 3, 2011 12:11 PM
4:9.8109PH661- 324 -7621
0
0
151700
OCT 3, 2011 12:11 PM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
0
0
150F00
OCT 3, 2011 12:11 PM
MON DD YYYY HH:MM:SS xM
0
0
160100
OCT 3, 2011 12:11 PM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 SUPREME ON
2 PLUS ON
3 REGULAR ON
4 DIESEL ON
0
0
160200
OCT 3, 2011 12:11 PM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 SUPREME
2 PLUS
3 REGULAR
4 DIESEL
0
0
160300
OCT 3, 2011 12:11 PM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 SUPREME 1
2 PLUS 2
3 REGULAR 3
4 DIESEL 4
0
3186804
ATG Information Work Order# 3186804
0
160400
OCT 3, 2011 12:11 PM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 SUPREME 9842
2 PLUS 9842
3 REGULAR 9842
4 DIESEL 9842
O
O
160700
OCT 3, 2011 12:11 PM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 SUPREME 91.00
2 PLUS 91.00
3 REGULAR 91.00
4 DIESEL 91.00
0
0
160900
OCT 3, 2011 12:11 PM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 SUPREME 0.000700
2 PLUS 0.000700
3 REGULAR 0.000700
4 DIESEL 0.000450
O
0
161200
OCT 3, 2011 12:11 PM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINEMANIFOLDED TANKS
1 SUPREME NONE NONE
2 PLUS NONE NONE
3 REGULAR NONE NONE
4 DIESEL NONE NONE
0
0
162100
OCT 3, 2011 12:11 PM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 SUPREME 500
2 PLUS 500
3 REGULAR 500
4 DIESEL 500
O
0
162200
OCT 3, 2011 12:11 PM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 SUPREME 9349
2 PLUS 9349
3 REGULAR 9349
4 DIESEL 9349
0
0
162300
OCT 3, 2011 12:11 PM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 SUPREME 8857
2 PLUS 8857
3 REGULAR 8857
4 DIESEL 8857
0
0
162400
OCT 3, 2011 12:11 PM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 SUPREME 2.0
3186804
ATG Information Work Order# 3186804
2 PLUS 2.0
3 REGULAR 2.0
4 DIESEL 2.0
0
0
162800
OCT 3, 2011 12:11 PM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 SUPREME 9842
2 PLUS 9842
3 REGULAR 9842
4 DIESEL 9842
0
O
162900
OCT 3, 2011 12:11 PM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 SUPREME 1181
2 PLUS 1181
3 REGULAR 1181
4 DIESEL 1181
0
0
170300
OCT 3, 2011 12:11 PM
LIQUID TYPE
SENSOR LOCATION TYPE
1 SUPREME ANNULAR TRI -STATE (SINGLE FLOAT)
2 SUPREME FILL SUMP TRI -STATE (SINGLE FLOAT)
3 SUPREME TURBINE SUMP TRI -STATE (SINGLE FLOAT)
4 PLUS ANNULAR TRISTATE (SINGLE FLOAT)
5 PLUS FILL SUMP TRI -STATE (SINGLE FLOAT)
6 PLUS TURBINE SUMP TRI -STATE (SINGLE FLOAT)
7 REGULAR ANNULAR TRI -STATE (SINGLE FLOAT)
8 REGULAR FILL SUMP TRI -STATE (SINGLE FLOAT)
9 REGULAR TURBINE SUMP TRI -STATE (SINGLE FLOAT)
10 DIESEL ANNULAR TRI -STATE (SINGLE FLOAT)
11 DIESEL FILL SUMP TRI -STATE (SINGLE FLOAT)
12 DIESEL TURBINE SUMP TRI -STATE (SINGLE FLOAT)
13 DISPENSER 1 -2 TRI -STATE (SINGLE FLOAT)
14 DISPENSER 34 TRI -STATE (SINGLE FLOAT)
15 DISPENSER 5.6 TRI -STATE (SINGLE FLOAT)
16 DISPENSER 7-8 TRI -STATE (SINGLE FLOAT)
17 DISPENSER 9 -10 TRI -STATE (SINGLE FLOAT)
18 TRI -STATE (SINGLE FLOAT)
19 TRI -STATE (SINGLE FLOAT)
20 TRI -STATE (SINGLE FLOAT)
21 TRI -STATE (SINGLE FLOAT)
22 TRI -STATE (SINGLE FLOAT)
23 TRI -STATE (SINGLE FLOAT)
24 TRI -STATE (SINGLE FLOAT)
0
0
178500
OCT 3, 2011 12:11 PM
PRESSURE LINE LEAK TANK NUMBER
LINE TANK NUMBER
0 VSUPREME 1
Q 2:PLUS 2
Q ®ULAR 3
0 4:DIESEL 4
Q 5: NONE
0 6: NONE
0
O
190200
OCT 3, 2011 12:11 PM
SOFTWARE REVISION LEVEL
VERSION 327.04
SOFTWARE# 346327 -100 -E
CREATED - 07.02.06.10.28
S- MODULE# 3301604004 -a
SYSTEM FEATURES:
PERIODIC IN -TANK TESTS
3186804
ATG Information
ANNUAL IN -TANKTESTS
ISO
PMC
0
0
IA0100
OCT 3, 2011 12:12 PM
TYPE CODE LENGTH SERIAL NO. D /CODE
TANK 1 SUPREME MAG C000 120.00 380026 4084
TANK 2 PLUS MAG C000 120.00 098643 3154
TANK 3 REGULAR MAG C000 120.00 076897 4944
TANK 4 DIESEL MAG C000 120.00 076891 4944
0
0
IA0200
OCT 3, 2011 12:12 PM
TANK 1 SUPREME MAG GRADIENT= 352.1000
TANK 2 PLUS MAG GRADIENT= 350.6300
TANK 3 REGULAR MAG GRADIENT = 351.0300
TANK 4 DIESEL MAG GRADIENT = 348.8200
0
0
IB0100
OCT 3, 2011 12:12 PM
LIQUID DIAGNOSTIC REPORT
SAMPLE HIGH LOW
SENSOR COUNTER REF REF VALUE
1 5 1025 190 102194
2 5 1025 190 101865
3 5 1025 190 101653
4 5 1025 190 101977
5 5 1025 192 101707
6 5 1025 192 101936
7 5 1025 192 102105
8 5 1025 192 102112
9 5 1024 192 102359
10 5 1024 192 102442
11 5 1024 192 102077
12 5 1024 192 102198
13 5 1019 187 102279
14 5 1019 187 102180
15 5 1019 187 102297
16 5 1019 187 102381
17 5 1026 201 103129
18 5 1026 201 306085056
19 5 1026 201 290151264
20 5 1026 201 284177408
21 5 1025 193 171040208
22 5 1025 193 166954640
23 5 1025 193 180826016
24 5 1025 193 175943536
0
0
130200
OCT 3, 2011 12:12 PM
CHEVRON C.S.I. 1920
1131 OAK ST.
BAKERSFIELD,CA.
9- 8109PH661- 324 -7621
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 SUPREME ANNULAR
OCT 3, 2011 9:10 AM FUEL ALARM
OCT 3, 2011 8:54 AM SENSOR OUT ALARM
MAY 20, 2011 10:39 AM FUEL ALARM
2 SUPREME FILL SUMP
OCT 3, 2011 9:09 AM FUEL ALARM
OCT 3, 2011 8:54 AM SENSOR OUT ALARM
MAY 20, 2011 10:41 AM FUEL ALARM
3 SUPREME TURBINE SUMP
OCT 3, 2011 9:08 AM FUEL ALARM
OCT 3, 2011 8:54 AM SENSOR OUT ALARM
MAY 20, 2011 10:42 AM FUEL ALARM
4 PLUS ANNULAR
OCT 3, 2011 9:30 AM FUEL ALARM
OCT 3, 2011 8:54 AM SENSOR OUTALARM
3186804
Work Order# 3186804
ATG Information Work Order# 3186804
MAY 20, 2011 10:24 AM FUEL ALARM
5 PLUS FILL SUMP
OCT 3, 2011 9:29 AM FUEL ALARM
OCT 3, 2011 8:54 AM SENSOR OUT ALARM
MAY 20, 2011 10:25 AM FUEL ALARM
6 PLUS TURBINE SUMP
OCT 3, 2011 9:28 AM FUEL ALARM
OCT 3, 2011 9:01 AM FUEL ALARM
OCT 3, 2011 8:54 AM SENSOR OUT ALARM
7 REGULARANNULAR
OCT 3, 2011 9:08 AM FUEL ALARM
OCT 3, 2011 8:54 AM SENSOR OUT ALARM
MAY 20, 2011 10:33 AM SENSOR OUT ALARM
8 REGULAR FILL SUMP
OCT 3, 2011 9:03 AM FUEL ALARM
OCT 3, 2011 8:54 AM SENSOR OUTALARM
MAY 20, 2011 10:36 AM FUELALARM
9 REGULAR TURBINE SUMP
OCT 3, 2011 9:02 AM FUEL ALARM
OCT 3, 2011 8:54 AM SENSOR OUT ALARM
MAY 20, 2011 10:37 AM FUEL ALARM
10 DIESEL ANNULAR
OCT 3, 2011 9:14AM FUELALARM
OCT 3, 2011 8:54 AM SENSOR OUT ALARM
MAY 20, 2011 10:44 AM FUEL ALARM
11 DIESEL FILL SUMP
OCT 3, 2011 9:12 AM FUEL ALARM
OCT 3, 2011 8:54 AM SENSOR OUT ALARM
MAY 20, 2011 10:45 AM FUEL ALARM
12 DIESEL TURBINE SUMP
OCT 3, 2011 9:11 AM FUEL ALARM
OCT 3, 2011 8:54 AM SENSOR OUT ALARM
MAY 20, 2011 10:46 AM FUEL ALARM
13 DISPENSER 1 -2
OCT 3, 2011 9:32 AM FUEL ALARM
OCT 3, 2011 8:54 AM SENSOR OUTALARM
MAY 20, 2011 10:49 AM FUEL ALARM
14 DISPENSER 3-4
OCT 3, 2011 9:34 AM FUEL ALARM
OCT 3, 2011 8:54 AM SENSOR OUTALARM
MAY 24, 2011 10:10 AM FUEL ALARM
15 DISPENSER 5-6
OCT 3, 2011 9:35AM FUEL ALARM
OCT 3, 2011 8:54 AM SENSOR OUTALARM
MAY 20, 2011 10:51 AM FUEL ALARM
16 DISPENSER 7-8
OCT 3, 2011 9:36 AM FUELALARM
OCT 3, 2011 8:54 AM SENSOR OUTALARM
MAY 20, 2011 10:54 AM FUEL ALARM
17 DISPENSER 9 -10
OCT 3, 2011 9:37 AM FUELALARM
OCT 3, 2011 8:54 AM SENSOR OUT ALARM
MAY 20, 2011 10:56AM FUEL ALARM
0
O
138200
OCT 3, 2011 12:13 PM
CHEVRON C.S.I. 1920
1131 OAK ST.
BAKERSFIELD,CA
9.8109PH661- 324 -7621
PRESSURE LINE LEAK ALARM HISTORY REPORT
O 1:SUPREME
OCT 3, 2011 11:00 AM PLLD SHUTDOWN ALARM
OCT 3, 2011 11:00 AM GROSS LINE FAIL
OCT 3, 2011 10:04 AM PLLD SHUTDOWN ALARM
OCT 3, 2011 9:56 AM PLLD SHUTDOWN ALARM
OCT 3, 2011 9:37 AM PLLD SHUTDOWN ALARM
OCT 3, 2011 9:36 AM PLLD SHUTDOWN ALARM
OCT 3, 2011 9:35 AM PLLD SHUTDOWN ALARM
OCT 3, 2011 9:34 AM PLLD SHUTDOWN ALARM
OCT 3, 2011 9:32 AM PLLD SHUTDOWN ALARM
OCT 3, 2011 9:10 AM PLLD SHUTDOWN ALARM
0 2:PLUS
OCT 3, 2011 11:07 AM PLLD SHUTDOWN ALARM
OCT 3, 2011 11:07 AM GROSS LINE FAIL
3186804
ATG Information
OCT 3, 2011 10:05 AM
OCT 3, 2011 9:56 AM
OCT 3, 2011 9:37 AM
OCT 3, 2011 9:36 AM
OCT 3, 2011 9:35 AM
OCT 3, 2011 9:34 AM
OCT 3, 2011 9:32 AM
OCT 3, 2011 9:30 AM
0 3:REGULAR
OCT 3, 2011 11:12 AM
OCT 3, 2011 11:12 AM
OCT 3, 2011 10:05 AM
OCT 3, 2011 9:37 AM
OCT 3, 2011 9:36 AM
OCT 3, 2011 9:35 AM
OCT 3, 2011 9:34 AM
OCT 3, 2011 9:32 AM
OCT 3, 2011 9:08 AM
OCT 3, 2011 9:03 AM
0 4:DIESEL
OCT 3, 2011 11:22 AM
OCT 3, 2011 11:22 AM
OCT 3, 2011 10:10 AM
OCT 3, 2011 10:04 AM
OCT 3, 2011 9:37 AM
OCT 3, 2011 9:32 AM
OCT 3, 2011 9:14 AM
OCT 3, 2011 9:12 AM
OCT 3, 2011 9:11 AM
OCT 3, 2011 8:54 AM
0
0
120600
OCT 3, 2011 12:14 PM
CHEVRON C.S.I. 1920
1131 OAK ST.
BAKERSFIELD,CA.
9- 8109PH661- 324 -7621
TANK ALARM HISTORY
TANK 1 SUPREME
HIGH WATER ALARM
OVERFILL ALARM
LOW PRODUCT ALAR
SUDDEN LOSSALARM
HIGH PRODUCT ALARM
INVALID FUEL LEVEL
PROBE OUT 0
PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM
GROSS LINE FAIL
PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM
GROSS LINE FAIL
PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM
OCT 3, 2011 9:56AM
OCT 3, 2011 9:45 AM
M OCT 3, 2011 10:04 AM
MAY 25, 2011 10:59AM
OCT 3, 2011 9:44 AM
OCT 3, 2011 10:04 AM
CT 3, 2011 10:13 AM
OCT 3, 2011 9:41 AM
MAY 25, 2011 11:00 AM
HIGH WATER WARNING OCT 3, 2011 9:56 AM
DELIVERY NEEDED OCT 3, 2011 10:04 AM
MAY 25, 2011 10:59 AM
MAX PRODUCT ALARM OCT 3, 2011 9:44 AM
TANK 2 PLUS
HIGH WATER ALARM OCT 3, 2011 9:56 AM
OVERFILL ALARM OCT 3, 2011 9:50 AM
LOW PRODUCT ALARM OCT 3,201110:05 AM
SUDDEN LOSS ALARM OCT 3, 2011 9:25 AM
HIGH PRODUCT ALARM OCT 3, 2011 9:49 AM
INVALID FUEL LEVEL OCT 3, 2011 10:05 AM
PROBE OUT OCT 3, 2011 10:15 AM
OCT 3, 2011 9:25 AM
HIGH WATER WARNING OCT 3, 2011 9:56 AM
DELIVERY NEEDED OCT 3, 2011 10:04 AM
OCT 3, 2011 9:50 AM
MAY 26, 2011 10:56AM
MAX PRODUCT ALARM OCT 3, 2011 9:49 AM
TANK3 REGULAR
HIGH WATER ALARM OCT 3, 2011 10:05 AM
OVERFILL ALARM OCT 3, 2011 9:59 AM
OCT 3, 2011 9:53 AM
HIGH PRODUCT ALARM OCT 3, 2011 9:58 AM
PROBE OUT OCT 3, 2011 10:14 AM
OCT 3, 2011 9:21 AM
HIGH WATER WARNING OCT 3, 2011 10:05 AM
DELIVERY NEEDED OCT 3, 2011 9:22 AM
3186804
Work Order# 3186804
ATG Information
Work Order# 3186804
JUN 9, 2011 2:00 PM
MAX PRODUCT ALARM OCT 3, 2011 9:58 AM
TANK DIESEL
HIGH WATER ALARM OCT 3, 2011 10:10 AM
OVERFILL ALARM OCT 3, 2011 10:04 AM
LOW PRODUCT ALARM OCT 3, 2011 10:04 AM
HIGH PRODUCT ALARM OCT 3, 2011 10:03 AM
INVALID FUEL LEVEL OCT 3, 2011 10:04 AM
PROBE OUT OCT 3, 2011 10:12 AM
OCT 3, 2011 9:42 AM
HIGH WATER WARNING OCT 3, 2011 10:10 AM
DELIVERY NEEDED OCT 3, 2011 10:04 AM
SEP 14, 2011 10:16 PM
SEP 8, 2011 12:33 PM
MAX PRODUCT ALARM OCT 3, 2011 10:03 AM
3186804