HomeMy WebLinkAboutFMC RESULTS 2011MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State ofCalifornia
Authority Cited: Chapter 6 7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code ofRegulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be
prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided
to the tank system owner /operator. The owner /operator must submit a copy of this form to the local agency regulating UST systems
within 30 days of this date.
A. General Information
Facility Name: #233 D & G Liquor
Site Address: 2732 Brundage Lane
Facility Contact Person: Omero Garcia
Make /Model of Monitoring System: Veeder -Root TLS 350
B. Inventory of Equipment Tested /Certified
esChecktheappropriatebox to Indicate specific equipment Impected/serviced:
City: Bakersfield
Bldg. No.:
Zip: 93304
Contact Phone No.: 661- 393 -7000
Date of Testing/Servicing: 8/16/2011
Tank ID: 12000 gal. Regular Tank
x1
ID: 12000 gal. Diesel
In -Tank Gauging Probe. Model: 847390 -107x] In -Tank Gauging Probe. Model: 847390 -107
Annular Space or Vault Probe. Model: Annular Space or Vault Sensor. Model:
Piping Sump / Trench Sensor(s). Model: Piping Sump / Trench Sensor(s). Model:
Fill Sump Sensor(s) Model: Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector. Model: Mechanical Line Leak Detector. Model:
N Electronic Line Leak Detector. Model: WPLLD x] Electronic Line Leak Detector. Model: WPLLD
1x_1 Tank Overfill / High Level Sensor. Model: 847390 -107 Cx] Tank Overfill / High Leval Sensor. Model: 847390 -107
Other (specify equip. type and model in Sec. E on Pg. 2) Other (specify equip. type and model in Sec. E on Pg. 2)
Tank ID: 12000 gal. Super Tank ID:
x] In -Tank Gauging Probe. Model:847390 -107 In -Tank Gauging Probe. Model:
Annular Space or Vault Sensor. Model: Annular Space or Vault Sensor. Model:
Piping Sump / Trench Sensor(s). Model: Piping Sump / Trench Sensor(s). Model:
Fill Sump Sensors(s). Model: Fill Sump Sensor(s). Model:
Mechanical Line Leak Decector. Model: Mechanical Line Leak Detector. Model:
x] Electronic Line Leak Detector. Model:WPLLD Electronic Line Leak Detector. Model:
x] Tank Overfill / High Level Sensor. Model: 847390-107 Tank Overfill / High Level Sensor. Model:
Other (specify equip. type and model in Sec. E on Pg. 2) Other (specify equip. typs and model in Sec. E on Pg. 2)
Dispenser ID: 1 & 2 Dispenser ID:
x] Dispenser Containment Sensor(s). Model: 794390 -208 Dispenser Containment Sensor(s). Model:
x] Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s)
Dispenser ID: Dispenser ID:
Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s). Model:
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chains(s). Dispenser Containment Float(s) and Chain(s).
Dispenser ID: Dispenser ID:
Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s). Model:
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s) Dispenser Containment Float(s) and Chain(s).
If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification - I certify that the equipment identified in this document was inspected /services in accordance with the
manufacturers' guidlines. Attached to this Certification is information (e.g. manufacturers' checklist) necessary to varify that
this information is correct and a plot plan showing the layout of monitoring equipment. For equipment capable of generating
such reports, I have attached a copy of the report; (check all that apply) x" jn Set -up Alar to report
Technician Name (print): Bryan A Self Signature:
Certification No: B37601 License No: 804904
Testing Company Name: Confidence UST Services, Inc. Phone No: 800 - 339 -9930
Site Address: 2732 Brundage Lane , Bakersfield, CA 93304 Date of Testing/Servicing: 8/1612011
D. Results ofTesting /Servicing
Software Version Installed: 327.04
Complete the following checklist:
Yes x1 No* Is the audible alarm operational?
Yes x No* Is the Visual alarm operational?
xgx Yes No* Were all sensors visually inspected, functionally tested, and confirmed operational?
Yes No* Were all sensors installed at the lowest point of secondary containment and positioned so that other
equipment will not interfere with their proper operation?
Yes No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) Hx N/A operational?
x Yes No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary
N/A containment monitoring system detects a leak, fails to operate, or is electrically disconnected? Ifyes:
which sensors initate positive shut -down? Sump /Trench Sensors [X] Dispenser Containment Sensors
Did you confirm positive shut -down due to leaks and sensor failure /disconnected? U Yes; No;
U Yes No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no
N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visual and audible at
the tank fill point(s) and operating properly? If so, at what percent of tank capasity does the alarm
trigger? 90 %
Yes* U No Was any monitoring equipment replaced? If Yes, identify speci fic sensors, probes, or other equipment
replaced and list the manufacturer name and model for all replacement parts in Section E, below.
Yes* xj No Was liquid found inside any secondary containment systems designed as dry systems?
Product; Water. If yes, describe causes in Section E, below. j
x N Was monitoring system set -up reviewed to ensure proper settings? Attach set -up reports, if applicable.
Lx-J Yes No* I Is all monitoring equipment operational per manufacturer's specifications?
In Section E below, discribe how and when these deficiencies were or will be corrected.
E. Comments:
F. In -Tank Guaging / SIR Equipment: [X] Check this box if tank guaging is used only for inventory control.
Check this box if tank guaging or SIR equipment is installed.
This section must be completed if in -tank guaging equipment is used to perform leak detection monitoring.
Complete the following checklist:
U Yes No* Has all input wiring been inspected for proper enter and termination,including testing for ground faults?
x Yes No* Were all tank guaging probes visually inspected for damage and residue buildup?
x Yes No* Was accuracy of system product level readings tested?
x Yes No* Was accuracy of system water level readings tested?
x Yes No* Were all probes reinstalled properly?
Yes No* I Were all items on the equipment manufacturer's maintenance checklist completed?
In the Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD): Check this box if LLD's are not installed.
Complete the following checklist:
Cx] Yes No* For equip. start-up or annual equipment certification, was a leak simulated to varify LLD performance?
Check all that apply) Simulated leak rate: [x]3 g.p.h.: 0.1 g.p.h.; 0.2 g.p.h.;
x Yes No* Were all LLD's confirmed operational and accurate within regulatory requirments?
x Yes No* Was the testing apparatus properly calibrated?
Yes No For mac anica LLD's, does the LLD restrict product ow if it detects a leak?
x N/A
x] Yes No* For electronic LLD's, does the turbine automatically shut off if the LLD detects a leak?
N/A
L] Yes No* For electronic LLD's, does the turbine automatically shut off if any portion of the monitoring system is
N/A disabled or disconnected?
x] Yes No* For electronic LLD's, does the turbine automatically shut off if any portion of the monitoring system
N/A malfunction or fails a test?
r ] Yes No* For electronic LLD's, have all accessible wiring connections been visually inspected?
N/A
x Yes No Were all items on the equipment manufacturer's maintenance checklist completed?
In the section H, below, describe how and when these deficiencies were or will be corrected.
H. Comments:
D AND G 233 SYSTEM SETUP
2732 BRUNDAGE Lry
BAKERSFFILD GA 9330 AUG i6 2011 B:AI - - -
661- 326 -1083
AUG 16, 2011 8:40 AM SYSTEM UNITS
VOLUME
U.S.
GALS
SYSTEM LANGUAGE
SYSTEM STATUS REPORT ENGLISH
SYSTEM DATE /TIME FORMAT
T 2:DELIVERY NEEDED MON DD YYYY HH:MM:SS xM
T 3:13ELIVERY NEEDED D AND G 233
GALS
GALS
2732 BRUNDAGE LN
W I:ANNUAL LINE FAIL BAKERSFFILD CA 9330
INCHES
661 - 326 -1083
INVENTORY REPORT SHIFT TIME I DISABLED
GALS
INCHES
SHIFT TIME 2 DISABLED
TEMP -
SHIFT TIME 3 DISABLED
T I:UNLEADED SHIFT TIME 4 DISABLED
VOLUME - 5136 GALS
ULLAGE - 6862 GALS TANK PER TST NEEDED WRN
904: ULLAGE- 5662 GALS DISABLED
TC VOLUME - 5030 GALS TANK ANN TST NEEDED WRN
HEIGHT - 42.57 INCHES DISABLED
WATER VOL o 0 GALS
WATER 0.00 INCHES LINE RE- ENABLE METHOD
TFI'IP - 90.0 DEC F PASS LINE TEST '
A X x% r END o( x A x x
SOFTWARE REVISION LEVEL
VERSION 327.04
SOFTWrAREA 346327 -100 —E
CREATED — 07.02.06.10.28
S— PIODULEa 330160 -062 —A
SYSTEM FEATURES:
PERIODIC IN—TANK TESTS
ANNUAL 1N—TANK TESTS
CSLD
PLLD
0.10 AUTO
0.20 REPETITIV
WPLLD
0.10 AUTO
0.20 REPETiTIV
H— PROTOCOL DATA FORMATHEIGHT
PRECISION TEST DURATIONHOURS: 12
0.20 GPM LINE TEST
AUTO — CONFIRM: ENABLED
0.10 GPM LINE TEST
AUTO — CONFIRM: ENABLED
PRINT PRECISION LINE
TEST RESULTS: DISABLEDDAYLIGHTSAVING, TIMEENABLED
START DATE
MAR WEEK 2 SUN
START TIME
2:00 AM
END DATE
NOV WEEK I SUN
END TIME
2:00 AM
RE- DIRECT LOCAL PRINTOUT
DISABLED
EURO PROTOCOL PREFIXS
SYSTEM SECURITY
CODE : 000000
MA114TENANCE HISTORYDISABLED
TANK CHART SECURITY
DISABLED
CUSTOM ALARMS
DISABLED
MASS /DENSITY
DISABLED
LINE PER TST NEEDED WRN
T 2: PREIi I U1.1 DISABLED
VOLUME 1322 GALS LINE ANN TST NEEDED WRN
ULLAGE - 10679 GALS DISABLED
90 %i ULLAGE-
TC VOLUME a
9478
1295
GALS
GALS PRINT TC VOLUMES
HEIGHT o 16.06 INCHES ENABLEG
WATER VOL -
WATER
15
0.91
GALS
INCHES TEMP COMPENSATION
TEMP - 88.6 DEG F VALUE (DEC F ): 60.0
STICK. HEIGHT OFFSET
DISABLED
T 3:DIESEL ULLAGE: 90%4
VOLUME . 1231 GALS
ULLAGE - 10769 GALS
90Y ULLAGE 9569 GALS
TC VOLUME - 1060 GALS
HEIGHT - 15.29 INCHES
WATER VOL - 0 GALS
WATER - 0.00 INCHES
TEMP - 90.9 DEG F
A X x% r END o( x A x x
SOFTWARE REVISION LEVEL
VERSION 327.04
SOFTWrAREA 346327 -100 —E
CREATED — 07.02.06.10.28
S— PIODULEa 330160 -062 —A
SYSTEM FEATURES:
PERIODIC IN—TANK TESTS
ANNUAL 1N—TANK TESTS
CSLD
PLLD
0.10 AUTO
0.20 REPETITIV
WPLLD
0.10 AUTO
0.20 REPETiTIV
H— PROTOCOL DATA FORMATHEIGHT
PRECISION TEST DURATIONHOURS: 12
0.20 GPM LINE TEST
AUTO — CONFIRM: ENABLED
0.10 GPM LINE TEST
AUTO — CONFIRM: ENABLED
PRINT PRECISION LINE
TEST RESULTS: DISABLEDDAYLIGHTSAVING, TIMEENABLED
START DATE
MAR WEEK 2 SUN
START TIME
2:00 AM
END DATE
NOV WEEK I SUN
END TIME
2:00 AM
RE- DIRECT LOCAL PRINTOUT
DISABLED
EURO PROTOCOL PREFIXS
SYSTEM SECURITY
CODE : 000000
MA114TENANCE HISTORYDISABLED
TANK CHART SECURITY
DISABLED
CUSTOM ALARMS
DISABLED
MASS /DENSITY
DISABLED
COMMUNICATIONS SETUP
PORT SETTINGS:
COMM BOARD ) (RS-232)
BAUD RATE 9600
PARITY NONE
STOP BIT I S'L'OP
DATA LENGTH: 8 DATA
RS -232 SECURITY
CODE : DISABLED
AUTO TRANSMIT SETTINGS:
AUTO LEAK ALARM L1141T
DISABLED
AUTO HIGH WATER LIMIT
DISABLED
AUTO OVERFILL LIMIT
DISABLED
AUTO LOW PRODUCT
DISABLED
AUTO THEFT LIMIT
DISABLED
AUTO DELIVERY START
DISABLED
AUTO DELIVERY END
DISABLED
AUTO EXTERNAL INPUT ON
DISABLED
AUTO EXTERNAL INPUT OFF
DISABLED
AUTO SENSOR FUEL ALARM
DISABLED
AUTO SENSOR WATER ALARM
DISABLED
AUTO SENSOR OUT ALARM
DISABLED
RS -232 END OF MESShGF
DISABLED
IN -TANK SETUP
T 1:UNLEADED
PRODUCT CODE 1
THERMAL r,OEFF :.000700
TANK DIAMETER 96.00
TANK PR
FULLEVOL )2000
FLOAT SIZE: 4.0 IN,
WATER WARNING : 2.0
HIGH WATER LIMIT: 3.0
MAX OR LABEL VOL: 12000
OVERFILL LIMIT.
0.00
PROBE OFFSET
10900
HIGH PRODUCT
95%'
400
DELIVERY LIMIT
SU
1600
LOW PRODUCT : 600
LEAK ALARM LIMIT; 99
SUDDEN LOSS LIMIT:
96.00
TANK TILT 0.00
PROBE OFFSET 0.00
SIPHON MANIFOLDEE, TNNKB
TO! NONE
LINE MANIFOLDED TANKS
7a: NONE
LEAK MIN PERIODIC: )20
LEAK MIN ANNUAL
120
PERIODIC TEST T%'
ANDARD
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST
ROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANY. 11:3T NOTIFY; OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY 1 11114
PUMP THRESHOLD IQ -OD
T 2:PREMIUM
PRODUCT CODE 2
THERMAL COEFF 000700
TAN, DIAMETER 96.00
TANK PROFILE I PT
FULL VOL 12000
FLOAT SIZE: 4.0 IN.
WATER WARN) PIG 2.0
HIGH WATER LIMIT: 3.0
MAX OR LABEL VOL: 12000
OVERFILL LIMIT 90%
10800
HIGH PRODUCT 95%'
11400
DELIVERY LIMIT SU
1900
LOW PRODUCT 600
LEAK ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 99
TANK TILT 0.00
PROBE OFFSET 0.00
SIPHON MANIFOLDED TANKS
TO: NONE
LINE MANIFOLDED TANKS
TO: NONE
LEAK MIN PERIODIC: 13t
120
LEAK MIN ANNUAL ly:
120
PERIODIC TEST TYPE
STANDARD
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TIVK TST SIPHON BREAK : OFF
DELIVERY DELAY 1 MIN
PUMP THRESHOLD W.00%
T 3:DIESEL
PRODUCT CODE 3
THERMAL COEFF 004500
TANK DIAMETER 96.U0
TANK PROFILE 1 PT
FULL VOL 12000
FLOAT SIZE: 4.0 IN.
WATER WARNING 2.0
HIGH WATER LIMIT: 3.0
MAX OR LABEL VOL: 12000
OVERFILL LIMIT 904
10800
HIGH PRODUCT 95%
11400
DELIVERY LIMIT 15%:
1800
LOW PRODUCT 600
LEAK ALARM LIMIT. 99
SUDDEN LOSS LIMIT: 99
TANK TILT 0.00
PROBE OFFSET 0.00
SIPHON MANIFOLDED TANKS
TO: NONE
LINE MANIFOLDED TANKS
TO: NONE
LEAK MIN PERIODIC: 1%:
120
LEAK MIN ANNUAL 1%
120
PERIODIC TEST TYPE
STANDARD
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY : I MIN
PUMP THRESHOLD 10.0030
LEAK. TEST METHOD
TEST CSLD ALL TANK
Pdn954
CLIMATE FACTOR:MODERATE
GROSS TEST
AUTO - CONFIRM: DISABLED
REPORT ONLY:
DISABLED
TST EARLY STOP:DISABLED
LEAK TEST REPORT FORMAT
NORMAL
WPLLD LINE LEAK SETUP
W I:DIESEL
TYP:2.0 IN STEEL
LINE LENGTH: 100 FEET
0.20 GPH TEST: REPETITIV
0.10 GPH TEST: AUTO
SHUTDOWN RATE: 3.0 CPH
T 3:DIESEL
DISPENSE MODE:
STANDARD
PRESSURE OFFSET:- 5.OPS1
W 2:UNLEADED
TYP:2.0 IN STEEL ,
LINE LENGTH: 100 FEET
0.20 GPH TEST: MONTHLY
0.10 GPH TEST: AUTO
SHUTDOWN RATE: 3.0 GPH
T I:UNLEADED
DISPENSE MODE:
STANDARD
PRESSURE OFFSET: O.OPSI
W 3:PREMIUM
TYP:2.0 IN STEEL
LINE LENGTH: 100 FEET
0.20 GPH TEST: REPETITIV
0.10 GPH TEST: AUTO
SHUTDOWN RATE: 3.0 GPH
T 2:PREMIUM
DISPENSE MODE:
STANDARD
PRESSURE OFFSET:- 5.OPSI
LINE LEAK LOCKOUT SETUP
LOCKOUT SCHEDULE
DAILY
START TIME: DISABLED
STOP TIME : DISABLED
LIQUID SENSOR SETUP
L I:DISP I
TRI -STATE (SINGLE FLOAT)
CATEGORY : DISPENSER PAN
OUTPUT RELAY SETUP
R t:OVERFILL ALARM
TYPE:
STANDARD
NORMALLY OPEN
IN-TANK ALARMS
ALL :OVERFILL ALARM
ALL:HIGH PRODUCT ALARM
ALL:MIAX PRODUCT ALARM
WPLLD LINE DISABLE SETUP
W I :DIESEL
LIQUID SENSOR ALMS
ALL:FUEL ALARM
ALL:SENSOR OUT ALARM
ALL:SHORT ALARM
W 2:UNLEADED
LIQUID SENSOR ALMS
ALL :FUEL ALARM
ALL:SENSOR OUT ALARM
ALL:SHORT ALARM
W 3:PREmIUM
LIQUID SENSOR ALMS
ALL:FUEL ALARM
ALL:SENSOR OUT ALARM
ALL:SHORT ALARM
ALARM HISTORY REPORT
SYSTEM ALARM - - - --
PRINTER ERROR
AUG 7. 2011 7:02 AM
x x x n X END x x x A x
ALARM HISTORY REPORT
IN -TANK ALARM - - - --
T I:UNLEADED
DELIVERY NEEDED
AUG 5. 2011 4:06 P11
JUL 24, 2011 2:20 PM
JUL S. 2011 6:54 AM
xxkxx END :x0x
ALARM HISTORY REPORT
IN-TANK ALARM
T 2:PREMIUM
DELIVERY NEEDED
AUG 7, 2011 7:O0 AM
JUL 12, 2011 7:04 AM
x•.,AxxEND « «x
ALARM HISTORY }':Ell0RT
IN-TANK mLfiRM - - - --
T 3:DIESEL
DELIVERY NCLoLD
AUG 1. 2011 7 : ; r-'i PM
JUL 21, 2011 5:01 PM
FEB b. 2007 8:U5 AM
x x W X END x r x A.4
e
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L I :DISP 1
DISPENSER PAN
x A x 'st K END w X X X x
D AND G 233
2732 BRUNDAGE LN
BAKERSFFILD CA 9330
661 - 326 -1063
AUG 16, 2011 8:56 AM
SYSTEM STATUS REPORT
W I:ANNUAL LINE FAIL
D AND C 233
2732 BRUNDAGE LN
BAKERSFFILD CA 9330
661-326 -1083
AUG 16. 2011 9:03 AM
k
SYSTEM STATUS REPORT
W I:ANNUAL LINE FAIL
e
D AND G 233
2732 BRUNDAGE LN
BAKERSFFILD CA 9330
661 - 326 -1083
AUG 16, 2011 9:04 AM
LEAK TEST REPORT
T I:UNLEADED
PROBE SERIAL NUM 750368
NO TEST DATA AVAILABLE
x x x x x END x x x x x
D AND G 233
2732 BRUNDAGE LN
13AKERSFFILD CA 9330
661- 326 -1083
AUG 16. 2011 9:04 AM
LEAK TEST REPORT
T 2:PREMIUM
PROBE SERIAL NUf1 204409
NO TEST DATA AVAILABLE
A x x x x END x x x x x
F
D AND G 233
2732 BRUNDAGE LN
BAKERSFFILD CA 9330
661 -326 -1083
AUG 16. 2011 9:04 AM
LEAK TEST REPORT
T 3:DIESEL
PROBE SERIAL NUM 204305
NO TEST DATA AVAILABLE
x x A x x END x x x x x
T 2:PREMIUM
INVENTORY INCREASE
INCREASE START
AUG 16, 2011 9:02 AM
VOLUME - 7082 GALS
HEIGHT - 54.82 INCHES
WATER - 1.02 INCHES
TEMP - 79.4 DEC F
INCREASE END
AUG 16, 2011 9:04 AM
VOLUME 7171 GALS
HEIGHT 55.39 INCHES
WATER 0.00 INCHES
TEMP 79.3 DEG F
GROSS INCREASE- 89
TC NET INCREASE- 89
CSLD MONTHLY REPORT
AUG 16. 2011 9:05 AM
CURRENT MONTH
0.2 GAL /HR TEST
T 1:UNLEADED
PROBE SERIAL NUM 750368
NO TEST DATA AVAILABLE
CSLD MONTHLY REPORT
AUG 16, 2011 9:05 All
CURRENT MONTH
0.2 GAL,,HR TEST
T 2:PREMILIM
PROBE SERIAL NUM 204409
NO TEST DATA AVAILABLE
CSLD MONTHLY REPORT
AUG 16. 2011 9 :05 AM
CURRENT MONTH
0.2 GAL/HR TEST
T 3:DIESEL
PROBE SERIAL NUM 204305
NO TEST DATA AVAILABLE
D AND G 233
2732 BRUNDAGE LN
BAKERSFFILD CA 9330
661- 326-1083
AUG 16. 2011 9:05 AM
CSLD TEST RESULTS
AUG 16. 2011 9:05 AM
T 1:UNLEAD£D
PROBE SERIAL NUM 750368
0.2 GAL /HR TEST
PER: AUG 16. 2011 PASS
T 2:PREMIUM
PROBE SERIAL NUM 204409
0.2 GAL /HR TEST
PER: AUG 16, 2011 PASS
T 3:DIESEL
PROBE SERIAL NUM 204305
0.2 GAL /HR TEST
PER: AUG 16, 2011 PASS
A x A W)* END x k A x x
D AND G 233
2732 BPUNDA03E LN
BAKERSFFILD CA 9330
661- 326 -1083
AUG 16. 2011 9:06 AM
CSLD FULLEST LAST PASS
AUG 16, 2011 9:06 AM
T I:UNLEADED
PROBE SERIAL NUM 750368
0.2 GAL,,HR TEST
PER: AUG 9, 2011
T 2:PREMIUM
PROBE SERIAL NUM 204409
0.2 GAL /HR TEST
PER: AUG 3, 2011
T 3:DIESEL
PROBE SERIAL NUM 204305
0.2 GAL /HP. TEST
PER: AUG 1, 2011
A A A A A END A X % 9 X
D AND G 233
2732 BRUNDAGE LN
BAKERSFFILD CA 9330
661-326 -1083
AUG 16. 2011 9:06 All
CSLD TEST RESULTS
AUG 16, 2011 9:06 AM
T ):UNLEADED
PROBE SERIAL NUM 750368
0.2 GAL/HR TEST
PER: AUG 16. 2011 PASS
T 2:PREMIUM
PROBE SERIAL NUM 204409
0.2 GAL /HR TEST
PER: AUG 16, 2011 PASS
T 3:DIEBEL
PROBE SERIAL NUM ''204305
0.2 GAL /HR TEST
PER: AUG 16. 2011 PASS
A X X A A END x x x x x
D AND C 233
2732 BRUNDAGE LN
BAKERSFFJLD CA 9330
661 - 326 -1083
AUG 16. 2011 9:06 All
CSLD TEST RESULTS
AUG 16. 2011 9:06 All
T I :UNLEADED
PROBE SERIAL NUM 750368
0.2 GAL /HR TEST
PER: AUG 16. 2011 PASS
T 2:PREMIUM
PROBE SERIAL NUM 204409
0.2 GAL /HR TEST
PER: AUG 16, 2011 PASS
T 3:01EBEL
PROBE SERIAL NUM 204305
0.2 GAL /HR TEST
PER: AUG 16, 2011 PASS
X X x At w END x K x} w
L AND G 233
2732 BRUNDAGE LN
BA}tERSFFILD CA 9330
661- 326 -1083
AUG 16. 2011 9:06 AM
LEAK TEST REPORT
T I:UNLEADED
PROBE SERIAL NUM 750368
NO TEST DATA AVAILABLE
A x x A A END x x t x x
D AND G 233
2732 BRUNDA13E LN
BAKERSFFILD CA 9330
661- 326 -1083
AUG 16, 2011 9:06 AM
LEAK TEST REPORT
T 2:PREMIUM
PROBE SERIAL NUM 204409
NO TEST DATA AVAILABLE
A K x x w E14D x x x x x
D AND G 233
2732 BRUNDAGE LN
BAKERSFFILD CA 9330
661-326 -1083
AUG 16. 2011 9:06 AM
LEAK TEST REPORT
T 3:DIESEL
PROBE SERIAL NUM 204305
NO TEST DATA AVAILABLE
X A x x x END x x x x x
CSLD DIAGNOSTI+: CSLD .MONTHLY REPORT
T 3:DIESEL
W I:DIESEL
CSLD DIAGNOSTICS
AUG 16, 2011 8:29 AM
AUG 16. 2011 9:07 AM
T I:UNLEADED
AUG 16. 2011 8:29 AM
TOTAL TESTS: 26/80
PROBE SERIAL NUM 750368
0.07 GAL/HR
TOTAL TIME:
T I:UNLEADED
NUM 204405
TOTAL TESTS: 26/80
CURRENT MONTH
1210 GALS
PROBE SERIAL NUM 750368
AUG 16. 2011 6:34 AM 0.2 GAL /HR TEST
CURRENT MONTH AVE VOLUME:
TEST RATE: -0.02 CAL /MR
THRUPUT EST: 578 GALS
AUG 16, 2011 6:34 AM
TOTAL TESTS: 18/78 T I:UNLEADED
THRUPUT EST:
TEST RATE: -0.02 GAL /HR
TOTAL TIME: 32.3 MRS PROBE SERIAL NUM 750368 TOTAL TEST'S: 18/78
AVE VOLUME: 5361 GALS
P1:24.690 P2:23.444 PSI
TOTAL TIME: 32.3 MRS
POS REJECTS: 0 NO TEST DATA AVAILABLE AVE VOLUME: 5361 GALS
THRUPUT EST: 16347 GALS POS REJECTS: 0
DISPENSE STATE: ACTIVE r THRUPUT EST: 16346 GALS
T 2:PREMIUM DISPENSE STATE: ACTIVE
PROSE SERIAL NUM 204409
NO TEST DATA AVAILABLET2:PREI'IIUM
PROBE SERIAL NUM 204409 T 2:PREMIUM
T 3:DIESEL PROBE SERIAL NUM 204409
AUG 16. 2011 7:43 AM PROBE SERIAL NUM 204305TESTRATE: 0.02 CAL /HR AUG 16. 2011 743 AM
TOTAL TESTS: 20/80 NO TEST DATA AVAILABLE TEST RATE: 0.02 GAL/HR
TOTAL TIME: 35.7 MRS TOTAL TESTS: 20/80
AVE VOLUME: 1563 GALS TOTAL TIME: 35.7 MRS
POS REJECTS: 0 AVE VOLUME: 1563 GALS
THRUPUT EST: 1471 GALS POS REJECTS: 0
DISPENSE STATE: ACTIVE -t THRUPUT EST: 1471 GALS
DISPENSE STATE: ACTIVE R
T 3:DIEBEL
PROBE SERIAL NUM 204305 T 3:DIESEL
W I:DIESEL
T I:UNLEADED DISPENSING ENABLED
PROBE SERIAL NUM 204305
AUG 16, 2011 8:29 AM CSL[, MONTHLY REPORT
PENDING140TESTDATA
TEST RATE: 0.07 GAL/HR AUG 16. 2011 8:29 AM
TOTAL TESTS: 26/80 AUG 16, 2011 9: 0'% AM TEST RATE: 0.07 GAL/HR
TOTAL TIME: 52.4 HRS
NUM 204405
TOTAL TESTS: 26/80
AVE VOLUME: 1210 GALS
NO TEST DATA
TOTAL TIME: 52.4 MRS
POS REJECTS: 0 CURRENT MONTH AVE VOLUME: 1210 GALS
THRUPUT EST: 578 GALS 0.2 CAL.HR TEST POS REJECTS: 0
DISPENSE STATE: ACTIVE ,k
0.20 GPM
THRUPUT EST: 566 GALS
P1:45.054 P2:40.414 PSI
NO TEST DATA
T I:UNLEADED DISPENSE STATE: ACTIVE x
PROBE SERIAL NUM 750368
NO TEST DATA AVAILABLE
CSLD MONTHLY REPORT
AM LINE LEAK DIALAUG16. 2011 9:07 A AUG 16. 2011 9:08 AM
CURRENT MONTH
0.2 GAL /HR TEST W I:DIESEL
T I:UNLEADED DISPENSING ENABLEDPROBESERIALNUM750368TESTING0.20 GAL /HR
PENDING140TESTDATAAVAILABLEPUMPOFF
HANDLE OFF
TOTAL MESSAGE:6949T2:PkEMIUM CRC:O PARITY:GPROBESERIALNUM204405
0.10 GPM: ACTIVE
NO TEST DATA AVAILABLE
3.0 GPM
P1:26.226 P2:26.240 PSIT3:DIESEL
PROBE SERIAL NUM 204305 0.20 GPM
P1:45.054 P2:40.414 PSI
NO TEST DATA AVAILABLE
MID TEST
P1:24.690 P2:23.444 PSI
W 2:UNLEADED
DISPENSING ENABLED
TEST COMPLETE
PENDING
PUMP OFF
HANDLE OFF
TOTAL MESSWw E:66303
CRC:1 PARITY:O
0.10 GPH: IDLE
3.0 CPH
P1:38.820 P2:38.754 PSI
0.20 GPH
P1:32.190 P2:32.196 PS
MID TEST
P1:35.928 P2:35.194 PSI
W 3 : PREII I UM
DISPENSING ENABLED
TEST COMPLETE
PENDING
PUMP OFF
HANDLE OFF
TOTAL MESSA+3E:9783
CRC:O PARITY:O
0.10 GPH: IDLE
3.0 GPH
P1:22.230 P2:22.302 PSI
0.20 GPH
P1:42.474 P2:42.404 PSI
MID TEST
PI :22.192 P2:22.406 PSI
D AND G 233
2732 BRUNDAGE LN
BAKERSFFILD CA 9330
661- 326 -1063
AUG 16, 2011 9:08 AM
LEAK TEST REPORT
T I :UNLEADED
PROBE SERIAL NUM 750368
NO TEST DATA AVAILABLE
xxxx 9 END xxAxA
D AND G 233
2732 BRUNDAGE LN
BAKERSFFILD CA 9330
661- 326 -1083
AUG 16, 2011 9:08 AM
LEAK TESf REPORT
T 2:PREMIUM
PROBE SERIAL NUM 204409
NO TEST DATA AVAILABLE
x; w)kmrNDxxxxX
D AND G 233 -
2732 BRUNDAGE LN
BAKERSFFILD CA 9330
661- 326 -1083
AUG 16, 2011 9:08 AM
LEAK TEST REPORT
T 3:DIESEL
PROBE SERIAL NUM 204305
NO TEST DATA AVAILABLE
xxxxx END AXxfk
D AND G 233
2732 BRUNDAGE LN
BAKERSFFILD CA 9330
661-326 -1083
AUG 16, 2011 9:OB AM
CSLD TEST RESULTS
AUG 16, 2011 9108 AM
T i :UNLEADEDPROBESERIAL (dUt'I 750368
0.2 GAL /HR TEST
PER: AUG 16, 2011 PASS
T 2:PREMIUMPROBESERIAL NUM 204409
0.2 GAL/HR TEST
PER: AUG 16. 2011 PASS
T 3:DIES£L
pROBE SERIAL NUM 204305
0.2 GAL /HR TEST
PER: AUG 16, 2011 PASS
A w AA END %% )i %A
D AND C 233
2732 BRUNDAGE LN W 3:PREMIUM
9:22AM FAIL LAST 3.0 GAL /HR PASS:
BAKERSFFILD CA 9330
8.2011 12:13AM FAIL AUG 16, 2011 8:57 AM
661- 326 -1083
5.2011 5:25PM FAIL
AUG
3.0 GAL/HR RESULTS:
AUG 16. 2011 9:08 AM
28.2011 12:54PM FAIL x x x END i K k ;<
D AND G 233
JUL
LAST TEST:
9:03AM FAIL
2732 BRUNDAGE LN
WPLLD LINE LEAK AUG 16,2011 7:45AM PASS BAKERSFFILD CA 9330
TEST RESULTS 661 -326 -1083
NUMBER OF TESTS PASSED
PREY 24 HOURS 11 AUG 16. 2011 9:12 AM
SINCE MIDNIGHT 2
W I:DIESEL
SYSTEM STATUS REPORT
3.0 GAL /HR RESULTS: 0.20 GAL /HR RESULTS:
W I:ANNUAL LINE FAIL
LAST TEST: AUG 14.2011 5:51AM PASS
AUG 16,2011 8:57AM PASS AUG 9,2011 11:41PM PASS
AUG 6,2011 I:40AM PASS
NUMBER OF TESTS PASSED AUG 1.2011 3:29PM PASS
PREV 24 HOURS : 6 JUL 26.2011 3:49PM PASS
SINCE MIDNIGHT 4 JUL 22.2011 11:45PM PASS
JUL 18,2011 7:51PM PASS
JUL 14.2011 7:05PM PASS
JUL 10.2011 7:43PM PASS
0.20 GAL/HR RESULTS: JUL 6.2011 2:26PM PASS
AUG 13.2011 7:03PM PASS D AND G 233
AUG 11.2011 8:15PM PASS 0.10 GAL/HR PESULTS: 2732 BRUNDAGE LN
AUG 9,2011 4:49PM PASS BAKERSFFILD CA 9330
AUG 7.2011 10:35AM PASS JUL 1.2011 5:14AM PASS 661- 326 -1083
AUG 5.2011 4:52PM PASS
AUG 3.2011 1:14PM PASS AUG 16. 2011 9:15 AM
AUG 1,2011 6:07PM PASS
JUL 28.2011 4:OOPM PASS WPLLD LINE LEAK
JUL 26.2011 11:42PM PASS TEST HISTORY
JUL 26,2011 8:30AM PASS
0.10 GAL /HR RESULTS: W I:DIESEL
AUG 13.2011 9:22AM FAIL LAST 3.0 GAL /HR PASS:
AUG 8.2011 12:13AM FAIL AUG 16, 2011 8:57 AM
AUG 5.2011 5:25PM FAIL
AUG 1.2011 6:39PM FAIL
JUL 28.2011 12:54PM FAIL x x x END i K k ;< FIRST 0.20 GAL/HR PASS
JUL 26.2011 9:03AM FAIL EACH MONTH:
AW 1, 2011 6:07 PM
JUL 24, 2011 2:19 PM
FIRST 0.10 CAL /HR PASS
EACH MONTH:
0 A x x x x END x x .: x%
W 2:UNLEADED
3.0 GAL/*HR RESULTS:
LAST TEST:
AUG 16.2011 8:51AM PASS
NUMBER OF TESTS PASSED
PREV 24 HOURS 84
SINCE MIDNIGHT 13
0.20 GAL /HR RESULTS:
AU.', 6.2011 4:31AM PASS
JUL 3.2011 1:32AM PASS
0.10 GAL /HR RESULTS:
JUL 3.2011 2:04AM PASS
D AND G 233
2732 BRUNDAGE LN
BAKERSFFILD CA 9330
661 - 326 -1083
AUG 16. 2011 9:15 AM
WPLLD LINE LEAK
TEST HISTORY
W 2:UNLEADED
LAST 3.0 GAL/HR PASS.:
AUG 16. 2011 8:51 AM
FIRST 0.20 GAL/HR PASS
EACH MONTH:
AUG 6. 2011 4:31 AM
JUL 3. 2011 1:32 AM
FIRST 0.10 GAL /HR PASS
EACH MONTH:
JUL 3. 2011 2:04 AM
APR 30. 2011 2:53 AM
0 '* w x x END w x A x A
D AND G 233
2732 BRUNDAGE LN
BAKERSFFILD CA 9330
661- 326 -1083
AUG 16, 2011 9:16 AM
WPLLD LINE LEAK
TEST HISTORY
W 3:PREMIUM
LAST 3.0 GAL.,HR PASS:
AUG 16, 2011 7:45 AM
FIRST 0.20 GAL/MR PASS
EACH MONTH:
AUG 1, 2011 3:29 PM
JUL 6. 2011 :26 PM
JUN 30. 2011 3:15 PM
FIRST 0.10 GAL/,HR PASS
EACH MONTH:
JUL 1, 2011 5:14 AM
MAY 7, 2011 1:20 HM
x x* x x END K A x x x
D AND G 233
2732 BRUNDAGE LN
BAKERSFFILD CA 9330
661- 326 -1083
AUG 16, 2011 9:56 AM
SYSTEM STATUS REPORT
T 2 : DEL I V£R`( NEEDED
T 3 : DEL I vFJZ a NEEDED
W !:ANNUAL LINE FAIL
INVENTORY REPORT
T I:UNLEADED
VOLUME - 4996 GALS
ULLAGE - 7004 GALS
901: ULLAGE- 5804 GALS
TC VOLUME - 4890 GALS
HEIGHT - 41.67 INCHES
WATER VOL - 0 GALS
WATER - 0.00 INCHES
TEMP - 90.1 DEC F
T 2:PREMIUM
VOLUME - 1311 GALS
ULLAGE - 10689 GALS
90M ULLAGE- 9489 GALS
TC VOLUME - 1284 GALS
HEIGHT - 15.97 INCHES
WATER VOL - 17 GALS
WATER - 0.65 INCHES
TEMP - 88.7 DEG F
T 3:DIESEL
VOLUME - 1191 GALS
ULLAGE - 10809 GALS
909 ULLAGE- 9609 GALS
TC VOLUME - 1024 GALS
HEIGHT - 14.94 INCHES
WATER VOL - 0 GALS
WATER = 0.00 INCHES
TEMP - 91.0 DEG F
A x x x x END x x x x R
I
D AND G 233
2732 BRUNDAGE LN
BAKERSFFILD CA 9330
661-326 -1083
AUG 16. 2011 10:02 AM
SYSTEM STATUS REPORT
T 2:DELIVERY NEEDED
T 3:DELIVERY NEEDED
W I:ANNUAL LINE FAIL
INVENTORY REPORT
T 1 :UNLEADED
VOLUME - 4997 GALS
ULLAGE - 7003 GALS
90% ULLAGE- 5BD3 GALS
TO VOLUME - 4891 GALS
HEIGHT - 41.68 INCHES
WATER VOL - 0 GALS
WATER - 0.00 INCHES
TEMP - 90.1 DEG F
T 2:PREMIUM
VOLUME - 1311 GALS
ULLAGE - 10669 GALS
90y ULLAGE- 9489 GALS
TC VOLUME - 1284 GALS
HEIGHT - 15.97 INCHES
WATER VOL - 17 GALS
WATER - 0.85 INCHES
TEMP - 88.7 DEG F
T 3:01ESEL
VOLUME - 1191 GALS
ULLACE - 10809 GALS
90% ULLAGE- 9609 GALS
TC VOLUME - 1024 GALS
HEIGHT - 14.94 INCHES
WATER VOL - 0 GALS
WATER - 0.00 INCHES
TEMP - 91.0 DEG F
xAx,xx END xxxxx
4
D AND G 233
2732 BRUNDAGE LN
BAKERSFFILD CA 9330
661- 326 -1083
AUG 16. 2011 10:02 AM
WPLLD LINE LEAK
TEST HISTORY
W I:DIESEL
LAST 3.0 GAL /HR PASS:
AUG 16. 2011 9:35 AM
FIRST 0.20 GALiHR PASS
EACH MONTH:
AUG 1. 2011 6:07 PM
JUL 24. 2011 2:19 PM
FIRST 0.10 GAL /HR PASS
EACH MONTH:
A x R. x END x x x x 4
D AND G 233
2732 BRUNDAGE LN
BAKERSFFILD CA 9330
661-326-1083
AUG I6. 2011 10:02 AM
WPLLD LINE LEA}:
TEST HISTORY
W 2:UNLEADED
LAST 3.0 GAL /HR PASS:
AUG 16. 20111 - 9:35 AM
FIRST 0.20 GHL;'HR PASS
EACH MONTH:
AUG 6, 2011 4:31 AM
JUL 3, 2011 1:32 AM
FIRST 0.10 GAL /HR PASS
EACH MONTH:
JUL 3. 2011 2:04 AM
APR 30. 2011 2:53 AM
x x x x x END x x x A A
D AND G 233
2732 BRUNDAGE LN
BAKERSFFILD CA 9330
661- 326 -1083
AUG 16, 2011 10:02 AM
WPLLD LINE LEAK
TEST HISTORY
W 3:PREMIUM
LAST 3.0 GAL/'HR PASS:
AUG 16. 2011 9:36 AM
FIRST 0.20 GAL/HR PASS
EACH MONTH:
AUG 1. 2011 3:29 PM
JUL 6. 2011 2:26 PM
JUN 30, 2011 3:15 PM
FIRST 0.10 GAL /HR PASS
EACH MONTH:
JUL 1, 2011 5:14 AM
MAY 7. 2011 1:28 All
A R x x x END x x x x x
CSLD DIAGNOSTICS
T I:UNLEADED
PROBE SERIAL NUM 750368
AUG 16. 2011 6:34 AM
TEST RATE: -0.02 GAL /HR
TOTAL TESTS: 18/78
TOTAL TIME: 32.3 HRS
AVE VOLUME: 5361 GALS
POS REJECTS: 0
THRUPUT EST: 16525 GALS
DISPENSE STATE: IDLE x
CSLD MONTHLY REPORT
AUG 16, 2011 10:03 AM
CURRENT MONTH
0.2 GAL /HR TEST
T ):UNLEADED
PROBE SERIAL NUM 750368
NO TEST DATA AVAILABLE
T 2:PREMIUM
PROBE SERIAL NUM 204409
NO TEST DATA AVAILABLE
T 3:DIESEL
PROBE SERIAL NUM 204305
NO TEST DATA AVAILABLE
D AND G 233
2732 BRUNDAGE LN
BAKERSFFILD CA 9330
661- 326 -1083
AUG 16. 2011 10:45 AM
SYSTEM STATUS REPORT
T 2 :DELIVERY NEEDED
T 3:DELIVER`! NEEDED j
i W I:ANNUAL LINE FAIL
I
WPLLD LINE LEAK ALARM
W 1:DIESEL
GROSS LINE FAIL
AUG 16, 2011 10:49 AM
WPLLD LINE LEAK ALARM
W I:DIESEL
WPLLD SHUTDOWN ALM
AUG 16, 2011 10:49 AM
D AND G 233
2732 BRUNDAGE LN
BAKERSFFILD CA 9330
661 -326 -1083
AU(; 16. 2011 10:49 AM
SYSTEM STATUS REPORT
T 2:DELIVERY NEEDED
T 3 :DELIVERY NEEDED
W I:GROSS LINE FAIL
W (:WPLLD SHUTDOWN ALM
W I:ANNUAL LINE FAIL
WPLLD LINE LEAK mLARh1
W 2:UNLEADED
GROSS LINE FAIL
AUG 16. 2011 10:56 AM
WPLLD LINE LEAK ALARM
W 2:UNLEADED
WPLLD SHUTDOWN ALM
AUG 16, 2011 10:56 AM
t
D AND G 233
2732 BRUNDAGE LN
BHKERSFFILD CA 9330
661 - 326 -1083
AUG 16, 2011 11:06 AM
SYSTEM STATUS REPORT
T 2:DELIVERY NEEDED
T 3:DELIVERY NEEDED
W I :GROSS LINE FAIL
W 1:WPLLD SHUTDOWN ALM
W I:ANNUAL LINE FAIL
W 2:GROSS LINE FAIL
W 2:WPLLD SHUTDOWN ALM
WPLLD L114E LEA(. ALARM
W 3:PREINIUM
GROSS LINE FAIL
AUG 16, 2011 11:10 AM
WPLLD LINE LEAK. ALAWI
W 3:PREMIUM
WPLLD SHUTDOWN ALM
AUG 16, 2011 11:10 AM
W 2:UNLEADEDLINELEAKALARMWPLLDLINELEAK ALARMWPLLD
W I:
DIINE
D AND C 233 WPLLD SHUTDOWN ALM WPLLD SHUTDOWN ALM
AUG 16. 2011 9:26 AM
2732 BRUNDAGE LN AUG 16, 2011 9 :23 HM
BAI;ERSFF I LD CA 9330
661-326-1083
AUG 16. 2011 11:10 AM
SYSTEM STATUS REPORT
WPLLD LINE LEAK ALARM
T 2:DELIVERY NEEDED WPLLD LINE LEAF: ALARM W 3:PREMW2:UNLEADED WPLLD SHUTDOWN
T 3:DELIVERY NEEDED WPLLD SHUTDOWN ALM 26 AMAUG16. 2011 9:6
AUG 16, 2011 923 AM
W I:GROSS LINE FAIL
W l :WPLLD SHUTDOWN ALM
W 1:ANNUAL LINE FAIL
W 2:GR0SS LINE FAIL
W 2:WPLLD SHUTDOW14 ALM SENSOR ALARM -- -- WPLLD LINE LEAK ALARM L 1:DISP IW3:GROSS LINE FAIL W 3 :PREMIUM DISPENSER PANWPLLDSHUTDOWNALMSENSOROUTALARM
W 3:WPLLD SHUTDOWN ALM AUG, 16. 2011 9:23 AM AUG 16, 2011 9;26 Art
SENSOR ALARM - - - -- - - -- IN -TANK ALARM -- - -- L 1 :D1SP 1 T 3:DIESELDISPENSERPANINVALIDFUEL LEVELFUELALARMAUG16. 2011 9:26 AM
AUG 16. 2011 9:23 AM
IN -TANK ALARM - - - -- - IN -TANK ALARM - -- --
T 3:DIESEL T 3:DIES
LOW PRODUCT ALARM
AUG 16. 2011 9:25 AM AUG }6. 2011 9:2OVERFILLALARM6 AM
IN -TANK ALARM - - - -- - - --
IN -TANK ALARM
T 3 :DIESEL T IDIESEL
DELIVERY NEEDEDPROBEOUT
AUG 16, 2011 9.:25 AM AUG l6, 2011, 9:26 AM
WPLLD LINE LEAK ALARM
W i:D1ESEL
WPLLD SHUTDOWN ALI
AUG 16. 2011 9 :26 Am
T 3:DIESEL
INVENTORY INCREASE
INCREASE START
AUG 16. 2011 9 :24 AM
VOLUME - 7399 GALS
HEIGHT - 56.84 INCHES
WATER - 1.00 INCHES
TEMP - 82.3 DEC F
INCREASE END
AUG 16, 2011 9:27 AM
VOLUME - 11065 GALS
HEIGHT - 63.35 INCHES
WATER = 0.00 INCHES
TEMP = 85.2 DEC F
GROSS INCREASE- 3666
TC NET INCREASE- 3153
D AND G 233
2732 BRUNDAGE LN
BAKERSFFILD CA 9330
661 -326 -1083
AUG 16, 2011 9 :27 AM
SYSTEM STATUS REPORT
T 3 :DELIVER'! NEEDED
W I:ANNUAL LINE FAIL
1N -TANK ALARIN - - - --
T I:UNLEADED
OVERFILL ALARM
AUG 16. 2011 9 :28 AM
D AND G 233
2732 BRUNDAGE LN
BAKERSFFILD CA 9330
661- 326 -1083
AUG 16, 2011 9:28 AM
SYSTEM STATUS REPORT
T I :OVERFILL ALARM
T 3 :DELIVERY NEEDED
W I :ANNUAL LINE FAIL
ARCHIVE UTILITY
SAVE SETUP DATA
START TIME:
AUG 16. 2011 9:28:25 AM
ARCHIVE UTILITY
SAVE SETUP DATA:
END TIME:
AUG 16. 2011 9:29:30 AM
BYTES : 8320
ti
IN-TANK mLARM - - ---
T 2:PREMIUM
OVERFILL ALARM
AUG 16. 2011 9:30 AM
I
T I:UNLEADED
1 NVE14TORY INCREASE
INCREASE START
AUG 16. 2011 9:27 AM
VOLUME - 8680 GALS
HEIGHT - 65.21 INCHES
WATER - 0.00 INCHES
TEMP - 85.0 DEG F
INCREASE END
AUG 16. 2011 9:30 AM
VOLUME - 11075 GALS
HEIGHT - 83.44 INCHES
WATER - 0.00 INCHES
TEMP - 85.7 DEG F
GROSS IW- REASE- 2395
TC NET INCREASE- 2348
IN -TA14K ALARM - - - --
T 2 : PREM I UM
PROBE OUT
AUG 16. 2011 9:30 AM
D AND G 233
2732 BRUNDAGE LN
BAKERSFFILD CA 9330
661-326 -1083
AUG 16, 2011 9:30 AM
SYSTEM STATUS REPORT
T 2:PROBE OUT
T 3:DELIVEP.Y NEEDED
W I:ANNUAL LINE FAIL
1N -T14NK. ALARM - - - --
T 2:PREMIUM
DELIVERY NEEDED
AUG 16. 2011 9:33 AP1
D AND G 233
2732 BRUNDAGE LN
BAItERSFFILD CA 9330
661- 326 -1083
AUG 16. 2011 933 AM
SYSTEM STATUS REPORT
T 2:PROBE OUT
T 2 :DELIVERY NEEDED
T 3:DELIVERY NEEDED
W I :ANNUAL LINE FAIL
T 2:PREMIUM
INVENTORY INCREASE
INCREASE START
AUG 16, 2011 9:29 All
VOLUME - 7172 GALS
HEIGHT - 55.39 INCHES
WATER - 0.00 114CHES
TEMP - 64.8 DEG F
INCREASE END
AUG 16, 2011 9:35 AM
VOLUME - 11142 GALS
HEIGHT - 84.07 INCHES
WATER - 0.00 INCHES
TEMP a 86.1 DEG F
GROSS INCREASE- 3970
TO NET INCREASE- 3891
f
SWRCB, January 2006
Spill Bucket Testing Report Form
This form is intendedfor use by contractors performing annual testing of UST spill containment structures. The completedform and
printoutsfrom tests (fapplicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: #233 D and G Date of Testing: 8/16/2011
Facility Address: 2732 Brundage Lane , Bakersfield, CA 93304
Facility Contact: Omero Garcia I Phone: 661- 393 -7000
Date Local Agency Was Notified of Testing: 7/13/2011
Name of Local Agency Inspector (fpresent during testing): Ester Duran
2. TESTING CONTRACTOR INFORMATION
Company Name: Confidence UST Services, Inc.
Technician Conducting Test: Bryan A Self
Credentials: X CSLB Contractor X ICC Service Tech. X SWRCB Tank Tester Other (Spec)
License Number(s): CSLB #804904 iCC #8022804 -UT Tank Tester# 1 1 -1756
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: x Hydrostatic Vacuum Other
Test Equipment Used: Lake Test Equipment Resolution: 0.0625"
identify Spill Bucket (By Tank
Number, Stored Product, etc.
1 Regular 2 Diesel 3 Super 4
Bucket Installation Type: Direct Bury
x Contained in Sump
Direct Bury
x Contained in Sump
Direct Bury
x Contained in Sump
Direct Bury
Contained in Sum
Bucket Diameter: 12.00" 12.00" 12.00"
Bucket Depth: 13.50" 14.25" 14.25"
Wait time between applying
vacuum /water and start of test: 5 min. 5 min. 5 min.
Test Start Time (Ti): 9:00am 9:00am 9:00am
Initial Reading (Rj): 10.00" 9.75" 10.00"
Test End Time (TF): 10:00am 10:00am 10:00am
Final Reading (RF): 10.00" 9.75" 10.00"
Test Duration (TF — Tj): I hour 1 hour 1 hour
Change in Reading (RI.- - Ri): 0.00" 0.00" 0.00"
Pass /Fail Threshold or
Criteria: 0.0625" 0.0625" 0.0625"
Test Result. X Pass Fail X Pass Fail X Pass Fail Pass Fail
Comments — (include information on repairs made prior to testing, and recommendedfollow -upforfailed tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information contained in this report is true, accurate, and infull compliance with legal requirements.
Technician's Signature: Date: 8/16/2011
State laws and regulations do not cu&KY require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
Cr0
VIDFj
0
T:01W
coHV AHMWIm ODWI avu•
Invoice No: 27344
Re air Lo :
During annual monitoring system certification I noticed that the TLS 350 is currently showing a W 1 annual lin
fail, since the system is passing a monthly .02 GPH line test the inspector was unconcerned.
7-day" Re uired Re airs:
Comments: