HomeMy WebLinkAboutFMC RESULTS 2011MONITORING SYSTEM CERTIFICATION For Use By All Jurisdictions Within the State ofCalifornia Authority Cited: Chapter 6 7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code ofRegulations This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner /operator. The owner /operator must submit a copy of this form to the local agency regulating UST systems within 30 days of this date. A. General Information Facility Name: #233 D & G Liquor Site Address: 2732 Brundage Lane Facility Contact Person: Omero Garcia Make /Model of Monitoring System: Veeder -Root TLS 350 B. Inventory of Equipment Tested /Certified esChecktheappropriatebox to Indicate specific equipment Impected/serviced: City: Bakersfield Bldg. No.: Zip: 93304 Contact Phone No.: 661- 393 -7000 Date of Testing/Servicing: 8/16/2011 Tank ID: 12000 gal. Regular Tank x1 ID: 12000 gal. Diesel In -Tank Gauging Probe. Model: 847390 -107x] In -Tank Gauging Probe. Model: 847390 -107 Annular Space or Vault Probe. Model: Annular Space or Vault Sensor. Model: Piping Sump / Trench Sensor(s). Model: Piping Sump / Trench Sensor(s). Model: Fill Sump Sensor(s) Model: Fill Sump Sensor(s). Model: Mechanical Line Leak Detector. Model: Mechanical Line Leak Detector. Model: N Electronic Line Leak Detector. Model: WPLLD x] Electronic Line Leak Detector. Model: WPLLD 1x_1 Tank Overfill / High Level Sensor. Model: 847390 -107 Cx] Tank Overfill / High Leval Sensor. Model: 847390 -107 Other (specify equip. type and model in Sec. E on Pg. 2) Other (specify equip. type and model in Sec. E on Pg. 2) Tank ID: 12000 gal. Super Tank ID: x] In -Tank Gauging Probe. Model:847390 -107 In -Tank Gauging Probe. Model: Annular Space or Vault Sensor. Model: Annular Space or Vault Sensor. Model: Piping Sump / Trench Sensor(s). Model: Piping Sump / Trench Sensor(s). Model: Fill Sump Sensors(s). Model: Fill Sump Sensor(s). Model: Mechanical Line Leak Decector. Model: Mechanical Line Leak Detector. Model: x] Electronic Line Leak Detector. Model:WPLLD Electronic Line Leak Detector. Model: x] Tank Overfill / High Level Sensor. Model: 847390-107 Tank Overfill / High Level Sensor. Model: Other (specify equip. type and model in Sec. E on Pg. 2) Other (specify equip. typs and model in Sec. E on Pg. 2) Dispenser ID: 1 & 2 Dispenser ID: x] Dispenser Containment Sensor(s). Model: 794390 -208 Dispenser Containment Sensor(s). Model: x] Shear Valve(s). Shear Valve(s). Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s) Dispenser ID: Dispenser ID: Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s). Model: Shear Valve(s). Shear Valve(s). Dispenser Containment Float(s) and Chains(s). Dispenser Containment Float(s) and Chain(s). Dispenser ID: Dispenser ID: Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s). Model: Shear Valve(s). Shear Valve(s). Dispenser Containment Float(s) and Chain(s) Dispenser Containment Float(s) and Chain(s). If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility. C. Certification - I certify that the equipment identified in this document was inspected /services in accordance with the manufacturers' guidlines. Attached to this Certification is information (e.g. manufacturers' checklist) necessary to varify that this information is correct and a plot plan showing the layout of monitoring equipment. For equipment capable of generating such reports, I have attached a copy of the report; (check all that apply) x" jn Set -up Alar to report Technician Name (print): Bryan A Self Signature: Certification No: B37601 License No: 804904 Testing Company Name: Confidence UST Services, Inc. Phone No: 800 - 339 -9930 Site Address: 2732 Brundage Lane , Bakersfield, CA 93304 Date of Testing/Servicing: 8/1612011 D. Results ofTesting /Servicing Software Version Installed: 327.04 Complete the following checklist: Yes x1 No* Is the audible alarm operational? Yes x No* Is the Visual alarm operational? xgx Yes No* Were all sensors visually inspected, functionally tested, and confirmed operational? Yes No* Were all sensors installed at the lowest point of secondary containment and positioned so that other equipment will not interfere with their proper operation? Yes No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) Hx N/A operational? x Yes No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary N/A containment monitoring system detects a leak, fails to operate, or is electrically disconnected? Ifyes: which sensors initate positive shut -down? Sump /Trench Sensors [X] Dispenser Containment Sensors Did you confirm positive shut -down due to leaks and sensor failure /disconnected? U Yes; No; U Yes No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visual and audible at the tank fill point(s) and operating properly? If so, at what percent of tank capasity does the alarm trigger? 90 % Yes* U No Was any monitoring equipment replaced? If Yes, identify speci fic sensors, probes, or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E, below. Yes* xj No Was liquid found inside any secondary containment systems designed as dry systems? Product; Water. If yes, describe causes in Section E, below. j x N Was monitoring system set -up reviewed to ensure proper settings? Attach set -up reports, if applicable. Lx-J Yes No* I Is all monitoring equipment operational per manufacturer's specifications? In Section E below, discribe how and when these deficiencies were or will be corrected. E. Comments: F. In -Tank Guaging / SIR Equipment: [X] Check this box if tank guaging is used only for inventory control. Check this box if tank guaging or SIR equipment is installed. This section must be completed if in -tank guaging equipment is used to perform leak detection monitoring. Complete the following checklist: U Yes No* Has all input wiring been inspected for proper enter and termination,including testing for ground faults? x Yes No* Were all tank guaging probes visually inspected for damage and residue buildup? x Yes No* Was accuracy of system product level readings tested? x Yes No* Was accuracy of system water level readings tested? x Yes No* Were all probes reinstalled properly? Yes No* I Were all items on the equipment manufacturer's maintenance checklist completed? In the Section H, below, describe how and when these deficiencies were or will be corrected. G. Line Leak Detectors (LLD): Check this box if LLD's are not installed. Complete the following checklist: Cx] Yes No* For equip. start-up or annual equipment certification, was a leak simulated to varify LLD performance? Check all that apply) Simulated leak rate: [x]3 g.p.h.: 0.1 g.p.h.; 0.2 g.p.h.; x Yes No* Were all LLD's confirmed operational and accurate within regulatory requirments? x Yes No* Was the testing apparatus properly calibrated? Yes No For mac anica LLD's, does the LLD restrict product ow if it detects a leak? x N/A x] Yes No* For electronic LLD's, does the turbine automatically shut off if the LLD detects a leak? N/A L] Yes No* For electronic LLD's, does the turbine automatically shut off if any portion of the monitoring system is N/A disabled or disconnected? x] Yes No* For electronic LLD's, does the turbine automatically shut off if any portion of the monitoring system N/A malfunction or fails a test? r ] Yes No* For electronic LLD's, have all accessible wiring connections been visually inspected? N/A x Yes No Were all items on the equipment manufacturer's maintenance checklist completed? In the section H, below, describe how and when these deficiencies were or will be corrected. H. Comments: D AND G 233 SYSTEM SETUP 2732 BRUNDAGE Lry BAKERSFFILD GA 9330 AUG i6 2011 B:AI - - - 661- 326 -1083 AUG 16, 2011 8:40 AM SYSTEM UNITS VOLUME U.S. GALS SYSTEM LANGUAGE SYSTEM STATUS REPORT ENGLISH SYSTEM DATE /TIME FORMAT T 2:DELIVERY NEEDED MON DD YYYY HH:MM:SS xM T 3:13ELIVERY NEEDED D AND G 233 GALS GALS 2732 BRUNDAGE LN W I:ANNUAL LINE FAIL BAKERSFFILD CA 9330 INCHES 661 - 326 -1083 INVENTORY REPORT SHIFT TIME I DISABLED GALS INCHES SHIFT TIME 2 DISABLED TEMP - SHIFT TIME 3 DISABLED T I:UNLEADED SHIFT TIME 4 DISABLED VOLUME - 5136 GALS ULLAGE - 6862 GALS TANK PER TST NEEDED WRN 904: ULLAGE- 5662 GALS DISABLED TC VOLUME - 5030 GALS TANK ANN TST NEEDED WRN HEIGHT - 42.57 INCHES DISABLED WATER VOL o 0 GALS WATER 0.00 INCHES LINE RE- ENABLE METHOD TFI'IP - 90.0 DEC F PASS LINE TEST ' A X x% r END o( x A x x SOFTWARE REVISION LEVEL VERSION 327.04 SOFTWrAREA 346327 -100 —E CREATED — 07.02.06.10.28 S— PIODULEa 330160 -062 —A SYSTEM FEATURES: PERIODIC IN—TANK TESTS ANNUAL 1N—TANK TESTS CSLD PLLD 0.10 AUTO 0.20 REPETITIV WPLLD 0.10 AUTO 0.20 REPETiTIV H— PROTOCOL DATA FORMATHEIGHT PRECISION TEST DURATIONHOURS: 12 0.20 GPM LINE TEST AUTO — CONFIRM: ENABLED 0.10 GPM LINE TEST AUTO — CONFIRM: ENABLED PRINT PRECISION LINE TEST RESULTS: DISABLEDDAYLIGHTSAVING, TIMEENABLED START DATE MAR WEEK 2 SUN START TIME 2:00 AM END DATE NOV WEEK I SUN END TIME 2:00 AM RE- DIRECT LOCAL PRINTOUT DISABLED EURO PROTOCOL PREFIXS SYSTEM SECURITY CODE : 000000 MA114TENANCE HISTORYDISABLED TANK CHART SECURITY DISABLED CUSTOM ALARMS DISABLED MASS /DENSITY DISABLED LINE PER TST NEEDED WRN T 2: PREIi I U1.1 DISABLED VOLUME 1322 GALS LINE ANN TST NEEDED WRN ULLAGE - 10679 GALS DISABLED 90 %i ULLAGE- TC VOLUME a 9478 1295 GALS GALS PRINT TC VOLUMES HEIGHT o 16.06 INCHES ENABLEG WATER VOL - WATER 15 0.91 GALS INCHES TEMP COMPENSATION TEMP - 88.6 DEG F VALUE (DEC F ): 60.0 STICK. HEIGHT OFFSET DISABLED T 3:DIESEL ULLAGE: 90%4 VOLUME . 1231 GALS ULLAGE - 10769 GALS 90Y ULLAGE 9569 GALS TC VOLUME - 1060 GALS HEIGHT - 15.29 INCHES WATER VOL - 0 GALS WATER - 0.00 INCHES TEMP - 90.9 DEG F A X x% r END o( x A x x SOFTWARE REVISION LEVEL VERSION 327.04 SOFTWrAREA 346327 -100 —E CREATED — 07.02.06.10.28 S— PIODULEa 330160 -062 —A SYSTEM FEATURES: PERIODIC IN—TANK TESTS ANNUAL 1N—TANK TESTS CSLD PLLD 0.10 AUTO 0.20 REPETITIV WPLLD 0.10 AUTO 0.20 REPETiTIV H— PROTOCOL DATA FORMATHEIGHT PRECISION TEST DURATIONHOURS: 12 0.20 GPM LINE TEST AUTO — CONFIRM: ENABLED 0.10 GPM LINE TEST AUTO — CONFIRM: ENABLED PRINT PRECISION LINE TEST RESULTS: DISABLEDDAYLIGHTSAVING, TIMEENABLED START DATE MAR WEEK 2 SUN START TIME 2:00 AM END DATE NOV WEEK I SUN END TIME 2:00 AM RE- DIRECT LOCAL PRINTOUT DISABLED EURO PROTOCOL PREFIXS SYSTEM SECURITY CODE : 000000 MA114TENANCE HISTORYDISABLED TANK CHART SECURITY DISABLED CUSTOM ALARMS DISABLED MASS /DENSITY DISABLED COMMUNICATIONS SETUP PORT SETTINGS: COMM BOARD ) (RS-232) BAUD RATE 9600 PARITY NONE STOP BIT I S'L'OP DATA LENGTH: 8 DATA RS -232 SECURITY CODE : DISABLED AUTO TRANSMIT SETTINGS: AUTO LEAK ALARM L1141T DISABLED AUTO HIGH WATER LIMIT DISABLED AUTO OVERFILL LIMIT DISABLED AUTO LOW PRODUCT DISABLED AUTO THEFT LIMIT DISABLED AUTO DELIVERY START DISABLED AUTO DELIVERY END DISABLED AUTO EXTERNAL INPUT ON DISABLED AUTO EXTERNAL INPUT OFF DISABLED AUTO SENSOR FUEL ALARM DISABLED AUTO SENSOR WATER ALARM DISABLED AUTO SENSOR OUT ALARM DISABLED RS -232 END OF MESShGF DISABLED IN -TANK SETUP T 1:UNLEADED PRODUCT CODE 1 THERMAL r,OEFF :.000700 TANK DIAMETER 96.00 TANK PR FULLEVOL )2000 FLOAT SIZE: 4.0 IN, WATER WARNING : 2.0 HIGH WATER LIMIT: 3.0 MAX OR LABEL VOL: 12000 OVERFILL LIMIT. 0.00 PROBE OFFSET 10900 HIGH PRODUCT 95%' 400 DELIVERY LIMIT SU 1600 LOW PRODUCT : 600 LEAK ALARM LIMIT; 99 SUDDEN LOSS LIMIT: 96.00 TANK TILT 0.00 PROBE OFFSET 0.00 SIPHON MANIFOLDEE, TNNKB TO! NONE LINE MANIFOLDED TANKS 7a: NONE LEAK MIN PERIODIC: )20 LEAK MIN ANNUAL 120 PERIODIC TEST T%' ANDARD ANNUAL TEST FAIL ALARM DISABLED PERIODIC TEST ROSS TEST FAIL ALARM DISABLED ANN TEST AVERAGING: OFF PER TEST AVERAGING: OFF TANY. 11:3T NOTIFY; OFF TNK TST SIPHON BREAK:OFF DELIVERY DELAY 1 11114 PUMP THRESHOLD IQ -OD T 2:PREMIUM PRODUCT CODE 2 THERMAL COEFF 000700 TAN, DIAMETER 96.00 TANK PROFILE I PT FULL VOL 12000 FLOAT SIZE: 4.0 IN. WATER WARN) PIG 2.0 HIGH WATER LIMIT: 3.0 MAX OR LABEL VOL: 12000 OVERFILL LIMIT 90% 10800 HIGH PRODUCT 95%' 11400 DELIVERY LIMIT SU 1900 LOW PRODUCT 600 LEAK ALARM LIMIT: 99 SUDDEN LOSS LIMIT: 99 TANK TILT 0.00 PROBE OFFSET 0.00 SIPHON MANIFOLDED TANKS TO: NONE LINE MANIFOLDED TANKS TO: NONE LEAK MIN PERIODIC: 13t 120 LEAK MIN ANNUAL ly: 120 PERIODIC TEST TYPE STANDARD ANNUAL TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED GROSS TEST FAIL ALARM DISABLED ANN TEST AVERAGING: OFF PER TEST AVERAGING: OFF TANK TEST NOTIFY: OFF TIVK TST SIPHON BREAK : OFF DELIVERY DELAY 1 MIN PUMP THRESHOLD W.00% T 3:DIESEL PRODUCT CODE 3 THERMAL COEFF 004500 TANK DIAMETER 96.U0 TANK PROFILE 1 PT FULL VOL 12000 FLOAT SIZE: 4.0 IN. WATER WARNING 2.0 HIGH WATER LIMIT: 3.0 MAX OR LABEL VOL: 12000 OVERFILL LIMIT 904 10800 HIGH PRODUCT 95% 11400 DELIVERY LIMIT 15%: 1800 LOW PRODUCT 600 LEAK ALARM LIMIT. 99 SUDDEN LOSS LIMIT: 99 TANK TILT 0.00 PROBE OFFSET 0.00 SIPHON MANIFOLDED TANKS TO: NONE LINE MANIFOLDED TANKS TO: NONE LEAK MIN PERIODIC: 1%: 120 LEAK MIN ANNUAL 1% 120 PERIODIC TEST TYPE STANDARD ANNUAL TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED GROSS TEST FAIL ALARM DISABLED ANN TEST AVERAGING: OFF PER TEST AVERAGING: OFF TANK TEST NOTIFY: OFF TNK TST SIPHON BREAK:OFF DELIVERY DELAY : I MIN PUMP THRESHOLD 10.0030 LEAK. TEST METHOD TEST CSLD ALL TANK Pdn954 CLIMATE FACTOR:MODERATE GROSS TEST AUTO - CONFIRM: DISABLED REPORT ONLY: DISABLED TST EARLY STOP:DISABLED LEAK TEST REPORT FORMAT NORMAL WPLLD LINE LEAK SETUP W I:DIESEL TYP:2.0 IN STEEL LINE LENGTH: 100 FEET 0.20 GPH TEST: REPETITIV 0.10 GPH TEST: AUTO SHUTDOWN RATE: 3.0 CPH T 3:DIESEL DISPENSE MODE: STANDARD PRESSURE OFFSET:- 5.OPS1 W 2:UNLEADED TYP:2.0 IN STEEL , LINE LENGTH: 100 FEET 0.20 GPH TEST: MONTHLY 0.10 GPH TEST: AUTO SHUTDOWN RATE: 3.0 GPH T I:UNLEADED DISPENSE MODE: STANDARD PRESSURE OFFSET: O.OPSI W 3:PREMIUM TYP:2.0 IN STEEL LINE LENGTH: 100 FEET 0.20 GPH TEST: REPETITIV 0.10 GPH TEST: AUTO SHUTDOWN RATE: 3.0 GPH T 2:PREMIUM DISPENSE MODE: STANDARD PRESSURE OFFSET:- 5.OPSI LINE LEAK LOCKOUT SETUP LOCKOUT SCHEDULE DAILY START TIME: DISABLED STOP TIME : DISABLED LIQUID SENSOR SETUP L I:DISP I TRI -STATE (SINGLE FLOAT) CATEGORY : DISPENSER PAN OUTPUT RELAY SETUP R t:OVERFILL ALARM TYPE: STANDARD NORMALLY OPEN IN-TANK ALARMS ALL :OVERFILL ALARM ALL:HIGH PRODUCT ALARM ALL:MIAX PRODUCT ALARM WPLLD LINE DISABLE SETUP W I :DIESEL LIQUID SENSOR ALMS ALL:FUEL ALARM ALL:SENSOR OUT ALARM ALL:SHORT ALARM W 2:UNLEADED LIQUID SENSOR ALMS ALL :FUEL ALARM ALL:SENSOR OUT ALARM ALL:SHORT ALARM W 3:PREmIUM LIQUID SENSOR ALMS ALL:FUEL ALARM ALL:SENSOR OUT ALARM ALL:SHORT ALARM ALARM HISTORY REPORT SYSTEM ALARM - - - -- PRINTER ERROR AUG 7. 2011 7:02 AM x x x n X END x x x A x ALARM HISTORY REPORT IN -TANK ALARM - - - -- T I:UNLEADED DELIVERY NEEDED AUG 5. 2011 4:06 P11 JUL 24, 2011 2:20 PM JUL S. 2011 6:54 AM xxkxx END :x0x ALARM HISTORY REPORT IN-TANK ALARM T 2:PREMIUM DELIVERY NEEDED AUG 7, 2011 7:O0 AM JUL 12, 2011 7:04 AM x•.,AxxEND « «x ALARM HISTORY }':Ell0RT IN-TANK mLfiRM - - - -- T 3:DIESEL DELIVERY NCLoLD AUG 1. 2011 7 : ; r-'i PM JUL 21, 2011 5:01 PM FEB b. 2007 8:U5 AM x x W X END x r x A.4 e ALARM HISTORY REPORT SENSOR ALARM - - - -- L I :DISP 1 DISPENSER PAN x A x 'st K END w X X X x D AND G 233 2732 BRUNDAGE LN BAKERSFFILD CA 9330 661 - 326 -1063 AUG 16, 2011 8:56 AM SYSTEM STATUS REPORT W I:ANNUAL LINE FAIL D AND C 233 2732 BRUNDAGE LN BAKERSFFILD CA 9330 661-326 -1083 AUG 16. 2011 9:03 AM k SYSTEM STATUS REPORT W I:ANNUAL LINE FAIL e D AND G 233 2732 BRUNDAGE LN BAKERSFFILD CA 9330 661 - 326 -1083 AUG 16, 2011 9:04 AM LEAK TEST REPORT T I:UNLEADED PROBE SERIAL NUM 750368 NO TEST DATA AVAILABLE x x x x x END x x x x x D AND G 233 2732 BRUNDAGE LN 13AKERSFFILD CA 9330 661- 326 -1083 AUG 16. 2011 9:04 AM LEAK TEST REPORT T 2:PREMIUM PROBE SERIAL NUf1 204409 NO TEST DATA AVAILABLE A x x x x END x x x x x F D AND G 233 2732 BRUNDAGE LN BAKERSFFILD CA 9330 661 -326 -1083 AUG 16. 2011 9:04 AM LEAK TEST REPORT T 3:DIESEL PROBE SERIAL NUM 204305 NO TEST DATA AVAILABLE x x A x x END x x x x x T 2:PREMIUM INVENTORY INCREASE INCREASE START AUG 16, 2011 9:02 AM VOLUME - 7082 GALS HEIGHT - 54.82 INCHES WATER - 1.02 INCHES TEMP - 79.4 DEC F INCREASE END AUG 16, 2011 9:04 AM VOLUME 7171 GALS HEIGHT 55.39 INCHES WATER 0.00 INCHES TEMP 79.3 DEG F GROSS INCREASE- 89 TC NET INCREASE- 89 CSLD MONTHLY REPORT AUG 16. 2011 9:05 AM CURRENT MONTH 0.2 GAL /HR TEST T 1:UNLEADED PROBE SERIAL NUM 750368 NO TEST DATA AVAILABLE CSLD MONTHLY REPORT AUG 16, 2011 9:05 All CURRENT MONTH 0.2 GAL,,HR TEST T 2:PREMILIM PROBE SERIAL NUM 204409 NO TEST DATA AVAILABLE CSLD MONTHLY REPORT AUG 16. 2011 9 :05 AM CURRENT MONTH 0.2 GAL/HR TEST T 3:DIESEL PROBE SERIAL NUM 204305 NO TEST DATA AVAILABLE D AND G 233 2732 BRUNDAGE LN BAKERSFFILD CA 9330 661- 326-1083 AUG 16. 2011 9:05 AM CSLD TEST RESULTS AUG 16. 2011 9:05 AM T 1:UNLEAD£D PROBE SERIAL NUM 750368 0.2 GAL /HR TEST PER: AUG 16. 2011 PASS T 2:PREMIUM PROBE SERIAL NUM 204409 0.2 GAL /HR TEST PER: AUG 16, 2011 PASS T 3:DIESEL PROBE SERIAL NUM 204305 0.2 GAL /HR TEST PER: AUG 16, 2011 PASS A x A W)* END x k A x x D AND G 233 2732 BPUNDA03E LN BAKERSFFILD CA 9330 661- 326 -1083 AUG 16. 2011 9:06 AM CSLD FULLEST LAST PASS AUG 16, 2011 9:06 AM T I:UNLEADED PROBE SERIAL NUM 750368 0.2 GAL,,HR TEST PER: AUG 9, 2011 T 2:PREMIUM PROBE SERIAL NUM 204409 0.2 GAL /HR TEST PER: AUG 3, 2011 T 3:DIESEL PROBE SERIAL NUM 204305 0.2 GAL /HP. TEST PER: AUG 1, 2011 A A A A A END A X % 9 X D AND G 233 2732 BRUNDAGE LN BAKERSFFILD CA 9330 661-326 -1083 AUG 16. 2011 9:06 All CSLD TEST RESULTS AUG 16, 2011 9:06 AM T ):UNLEADED PROBE SERIAL NUM 750368 0.2 GAL/HR TEST PER: AUG 16. 2011 PASS T 2:PREMIUM PROBE SERIAL NUM 204409 0.2 GAL /HR TEST PER: AUG 16, 2011 PASS T 3:DIEBEL PROBE SERIAL NUM ''204305 0.2 GAL /HR TEST PER: AUG 16. 2011 PASS A X X A A END x x x x x D AND C 233 2732 BRUNDAGE LN BAKERSFFJLD CA 9330 661 - 326 -1083 AUG 16. 2011 9:06 All CSLD TEST RESULTS AUG 16. 2011 9:06 All T I :UNLEADED PROBE SERIAL NUM 750368 0.2 GAL /HR TEST PER: AUG 16. 2011 PASS T 2:PREMIUM PROBE SERIAL NUM 204409 0.2 GAL /HR TEST PER: AUG 16, 2011 PASS T 3:01EBEL PROBE SERIAL NUM 204305 0.2 GAL /HR TEST PER: AUG 16, 2011 PASS X X x At w END x K x} w L AND G 233 2732 BRUNDAGE LN BA}tERSFFILD CA 9330 661- 326 -1083 AUG 16. 2011 9:06 AM LEAK TEST REPORT T I:UNLEADED PROBE SERIAL NUM 750368 NO TEST DATA AVAILABLE A x x A A END x x t x x D AND G 233 2732 BRUNDA13E LN BAKERSFFILD CA 9330 661- 326 -1083 AUG 16, 2011 9:06 AM LEAK TEST REPORT T 2:PREMIUM PROBE SERIAL NUM 204409 NO TEST DATA AVAILABLE A K x x w E14D x x x x x D AND G 233 2732 BRUNDAGE LN BAKERSFFILD CA 9330 661-326 -1083 AUG 16. 2011 9:06 AM LEAK TEST REPORT T 3:DIESEL PROBE SERIAL NUM 204305 NO TEST DATA AVAILABLE X A x x x END x x x x x CSLD DIAGNOSTI+: CSLD .MONTHLY REPORT T 3:DIESEL W I:DIESEL CSLD DIAGNOSTICS AUG 16, 2011 8:29 AM AUG 16. 2011 9:07 AM T I:UNLEADED AUG 16. 2011 8:29 AM TOTAL TESTS: 26/80 PROBE SERIAL NUM 750368 0.07 GAL/HR TOTAL TIME: T I:UNLEADED NUM 204405 TOTAL TESTS: 26/80 CURRENT MONTH 1210 GALS PROBE SERIAL NUM 750368 AUG 16. 2011 6:34 AM 0.2 GAL /HR TEST CURRENT MONTH AVE VOLUME: TEST RATE: -0.02 CAL /MR THRUPUT EST: 578 GALS AUG 16, 2011 6:34 AM TOTAL TESTS: 18/78 T I:UNLEADED THRUPUT EST: TEST RATE: -0.02 GAL /HR TOTAL TIME: 32.3 MRS PROBE SERIAL NUM 750368 TOTAL TEST'S: 18/78 AVE VOLUME: 5361 GALS P1:24.690 P2:23.444 PSI TOTAL TIME: 32.3 MRS POS REJECTS: 0 NO TEST DATA AVAILABLE AVE VOLUME: 5361 GALS THRUPUT EST: 16347 GALS POS REJECTS: 0 DISPENSE STATE: ACTIVE r THRUPUT EST: 16346 GALS T 2:PREMIUM DISPENSE STATE: ACTIVE PROSE SERIAL NUM 204409 NO TEST DATA AVAILABLET2:PREI'IIUM PROBE SERIAL NUM 204409 T 2:PREMIUM T 3:DIESEL PROBE SERIAL NUM 204409 AUG 16. 2011 7:43 AM PROBE SERIAL NUM 204305TESTRATE: 0.02 CAL /HR AUG 16. 2011 743 AM TOTAL TESTS: 20/80 NO TEST DATA AVAILABLE TEST RATE: 0.02 GAL/HR TOTAL TIME: 35.7 MRS TOTAL TESTS: 20/80 AVE VOLUME: 1563 GALS TOTAL TIME: 35.7 MRS POS REJECTS: 0 AVE VOLUME: 1563 GALS THRUPUT EST: 1471 GALS POS REJECTS: 0 DISPENSE STATE: ACTIVE -t THRUPUT EST: 1471 GALS DISPENSE STATE: ACTIVE R T 3:DIEBEL PROBE SERIAL NUM 204305 T 3:DIESEL W I:DIESEL T I:UNLEADED DISPENSING ENABLED PROBE SERIAL NUM 204305 AUG 16, 2011 8:29 AM CSL[, MONTHLY REPORT PENDING140TESTDATA TEST RATE: 0.07 GAL/HR AUG 16. 2011 8:29 AM TOTAL TESTS: 26/80 AUG 16, 2011 9: 0'% AM TEST RATE: 0.07 GAL/HR TOTAL TIME: 52.4 HRS NUM 204405 TOTAL TESTS: 26/80 AVE VOLUME: 1210 GALS NO TEST DATA TOTAL TIME: 52.4 MRS POS REJECTS: 0 CURRENT MONTH AVE VOLUME: 1210 GALS THRUPUT EST: 578 GALS 0.2 CAL.HR TEST POS REJECTS: 0 DISPENSE STATE: ACTIVE ,k 0.20 GPM THRUPUT EST: 566 GALS P1:45.054 P2:40.414 PSI NO TEST DATA T I:UNLEADED DISPENSE STATE: ACTIVE x PROBE SERIAL NUM 750368 NO TEST DATA AVAILABLE CSLD MONTHLY REPORT AM LINE LEAK DIALAUG16. 2011 9:07 A AUG 16. 2011 9:08 AM CURRENT MONTH 0.2 GAL /HR TEST W I:DIESEL T I:UNLEADED DISPENSING ENABLEDPROBESERIALNUM750368TESTING0.20 GAL /HR PENDING140TESTDATAAVAILABLEPUMPOFF HANDLE OFF TOTAL MESSAGE:6949T2:PkEMIUM CRC:O PARITY:GPROBESERIALNUM204405 0.10 GPM: ACTIVE NO TEST DATA AVAILABLE 3.0 GPM P1:26.226 P2:26.240 PSIT3:DIESEL PROBE SERIAL NUM 204305 0.20 GPM P1:45.054 P2:40.414 PSI NO TEST DATA AVAILABLE MID TEST P1:24.690 P2:23.444 PSI W 2:UNLEADED DISPENSING ENABLED TEST COMPLETE PENDING PUMP OFF HANDLE OFF TOTAL MESSWw E:66303 CRC:1 PARITY:O 0.10 GPH: IDLE 3.0 CPH P1:38.820 P2:38.754 PSI 0.20 GPH P1:32.190 P2:32.196 PS MID TEST P1:35.928 P2:35.194 PSI W 3 : PREII I UM DISPENSING ENABLED TEST COMPLETE PENDING PUMP OFF HANDLE OFF TOTAL MESSA+3E:9783 CRC:O PARITY:O 0.10 GPH: IDLE 3.0 GPH P1:22.230 P2:22.302 PSI 0.20 GPH P1:42.474 P2:42.404 PSI MID TEST PI :22.192 P2:22.406 PSI D AND G 233 2732 BRUNDAGE LN BAKERSFFILD CA 9330 661- 326 -1063 AUG 16, 2011 9:08 AM LEAK TEST REPORT T I :UNLEADED PROBE SERIAL NUM 750368 NO TEST DATA AVAILABLE xxxx 9 END xxAxA D AND G 233 2732 BRUNDAGE LN BAKERSFFILD CA 9330 661- 326 -1083 AUG 16, 2011 9:08 AM LEAK TESf REPORT T 2:PREMIUM PROBE SERIAL NUM 204409 NO TEST DATA AVAILABLE x; w)kmrNDxxxxX D AND G 233 - 2732 BRUNDAGE LN BAKERSFFILD CA 9330 661- 326 -1083 AUG 16, 2011 9:08 AM LEAK TEST REPORT T 3:DIESEL PROBE SERIAL NUM 204305 NO TEST DATA AVAILABLE xxxxx END AXxfk D AND G 233 2732 BRUNDAGE LN BAKERSFFILD CA 9330 661-326 -1083 AUG 16, 2011 9:OB AM CSLD TEST RESULTS AUG 16, 2011 9108 AM T i :UNLEADEDPROBESERIAL (dUt'I 750368 0.2 GAL /HR TEST PER: AUG 16, 2011 PASS T 2:PREMIUMPROBESERIAL NUM 204409 0.2 GAL/HR TEST PER: AUG 16. 2011 PASS T 3:DIES£L pROBE SERIAL NUM 204305 0.2 GAL /HR TEST PER: AUG 16, 2011 PASS A w AA END %% )i %A D AND C 233 2732 BRUNDAGE LN W 3:PREMIUM 9:22AM FAIL LAST 3.0 GAL /HR PASS: BAKERSFFILD CA 9330 8.2011 12:13AM FAIL AUG 16, 2011 8:57 AM 661- 326 -1083 5.2011 5:25PM FAIL AUG 3.0 GAL/HR RESULTS: AUG 16. 2011 9:08 AM 28.2011 12:54PM FAIL x x x END i K k ;< D AND G 233 JUL LAST TEST: 9:03AM FAIL 2732 BRUNDAGE LN WPLLD LINE LEAK AUG 16,2011 7:45AM PASS BAKERSFFILD CA 9330 TEST RESULTS 661 -326 -1083 NUMBER OF TESTS PASSED PREY 24 HOURS 11 AUG 16. 2011 9:12 AM SINCE MIDNIGHT 2 W I:DIESEL SYSTEM STATUS REPORT 3.0 GAL /HR RESULTS: 0.20 GAL /HR RESULTS: W I:ANNUAL LINE FAIL LAST TEST: AUG 14.2011 5:51AM PASS AUG 16,2011 8:57AM PASS AUG 9,2011 11:41PM PASS AUG 6,2011 I:40AM PASS NUMBER OF TESTS PASSED AUG 1.2011 3:29PM PASS PREV 24 HOURS : 6 JUL 26.2011 3:49PM PASS SINCE MIDNIGHT 4 JUL 22.2011 11:45PM PASS JUL 18,2011 7:51PM PASS JUL 14.2011 7:05PM PASS JUL 10.2011 7:43PM PASS 0.20 GAL/HR RESULTS: JUL 6.2011 2:26PM PASS AUG 13.2011 7:03PM PASS D AND G 233 AUG 11.2011 8:15PM PASS 0.10 GAL/HR PESULTS: 2732 BRUNDAGE LN AUG 9,2011 4:49PM PASS BAKERSFFILD CA 9330 AUG 7.2011 10:35AM PASS JUL 1.2011 5:14AM PASS 661- 326 -1083 AUG 5.2011 4:52PM PASS AUG 3.2011 1:14PM PASS AUG 16. 2011 9:15 AM AUG 1,2011 6:07PM PASS JUL 28.2011 4:OOPM PASS WPLLD LINE LEAK JUL 26.2011 11:42PM PASS TEST HISTORY JUL 26,2011 8:30AM PASS 0.10 GAL /HR RESULTS: W I:DIESEL AUG 13.2011 9:22AM FAIL LAST 3.0 GAL /HR PASS: AUG 8.2011 12:13AM FAIL AUG 16, 2011 8:57 AM AUG 5.2011 5:25PM FAIL AUG 1.2011 6:39PM FAIL JUL 28.2011 12:54PM FAIL x x x END i K k ;< FIRST 0.20 GAL/HR PASS JUL 26.2011 9:03AM FAIL EACH MONTH: AW 1, 2011 6:07 PM JUL 24, 2011 2:19 PM FIRST 0.10 CAL /HR PASS EACH MONTH: 0 A x x x x END x x .: x% W 2:UNLEADED 3.0 GAL/*HR RESULTS: LAST TEST: AUG 16.2011 8:51AM PASS NUMBER OF TESTS PASSED PREV 24 HOURS 84 SINCE MIDNIGHT 13 0.20 GAL /HR RESULTS: AU.', 6.2011 4:31AM PASS JUL 3.2011 1:32AM PASS 0.10 GAL /HR RESULTS: JUL 3.2011 2:04AM PASS D AND G 233 2732 BRUNDAGE LN BAKERSFFILD CA 9330 661 - 326 -1083 AUG 16. 2011 9:15 AM WPLLD LINE LEAK TEST HISTORY W 2:UNLEADED LAST 3.0 GAL/HR PASS.: AUG 16. 2011 8:51 AM FIRST 0.20 GAL/HR PASS EACH MONTH: AUG 6. 2011 4:31 AM JUL 3. 2011 1:32 AM FIRST 0.10 GAL /HR PASS EACH MONTH: JUL 3. 2011 2:04 AM APR 30. 2011 2:53 AM 0 '* w x x END w x A x A D AND G 233 2732 BRUNDAGE LN BAKERSFFILD CA 9330 661- 326 -1083 AUG 16, 2011 9:16 AM WPLLD LINE LEAK TEST HISTORY W 3:PREMIUM LAST 3.0 GAL.,HR PASS: AUG 16, 2011 7:45 AM FIRST 0.20 GAL/MR PASS EACH MONTH: AUG 1, 2011 3:29 PM JUL 6. 2011 :26 PM JUN 30. 2011 3:15 PM FIRST 0.10 GAL/,HR PASS EACH MONTH: JUL 1, 2011 5:14 AM MAY 7, 2011 1:20 HM x x* x x END K A x x x D AND G 233 2732 BRUNDAGE LN BAKERSFFILD CA 9330 661- 326 -1083 AUG 16, 2011 9:56 AM SYSTEM STATUS REPORT T 2 : DEL I V£R`( NEEDED T 3 : DEL I vFJZ a NEEDED W !:ANNUAL LINE FAIL INVENTORY REPORT T I:UNLEADED VOLUME - 4996 GALS ULLAGE - 7004 GALS 901: ULLAGE- 5804 GALS TC VOLUME - 4890 GALS HEIGHT - 41.67 INCHES WATER VOL - 0 GALS WATER - 0.00 INCHES TEMP - 90.1 DEC F T 2:PREMIUM VOLUME - 1311 GALS ULLAGE - 10689 GALS 90M ULLAGE- 9489 GALS TC VOLUME - 1284 GALS HEIGHT - 15.97 INCHES WATER VOL - 17 GALS WATER - 0.65 INCHES TEMP - 88.7 DEG F T 3:DIESEL VOLUME - 1191 GALS ULLAGE - 10809 GALS 909 ULLAGE- 9609 GALS TC VOLUME - 1024 GALS HEIGHT - 14.94 INCHES WATER VOL - 0 GALS WATER = 0.00 INCHES TEMP - 91.0 DEG F A x x x x END x x x x R I D AND G 233 2732 BRUNDAGE LN BAKERSFFILD CA 9330 661-326 -1083 AUG 16. 2011 10:02 AM SYSTEM STATUS REPORT T 2:DELIVERY NEEDED T 3:DELIVERY NEEDED W I:ANNUAL LINE FAIL INVENTORY REPORT T 1 :UNLEADED VOLUME - 4997 GALS ULLAGE - 7003 GALS 90% ULLAGE- 5BD3 GALS TO VOLUME - 4891 GALS HEIGHT - 41.68 INCHES WATER VOL - 0 GALS WATER - 0.00 INCHES TEMP - 90.1 DEG F T 2:PREMIUM VOLUME - 1311 GALS ULLAGE - 10669 GALS 90y ULLAGE- 9489 GALS TC VOLUME - 1284 GALS HEIGHT - 15.97 INCHES WATER VOL - 17 GALS WATER - 0.85 INCHES TEMP - 88.7 DEG F T 3:01ESEL VOLUME - 1191 GALS ULLACE - 10809 GALS 90% ULLAGE- 9609 GALS TC VOLUME - 1024 GALS HEIGHT - 14.94 INCHES WATER VOL - 0 GALS WATER - 0.00 INCHES TEMP - 91.0 DEG F xAx,xx END xxxxx 4 D AND G 233 2732 BRUNDAGE LN BAKERSFFILD CA 9330 661- 326 -1083 AUG 16. 2011 10:02 AM WPLLD LINE LEAK TEST HISTORY W I:DIESEL LAST 3.0 GAL /HR PASS: AUG 16. 2011 9:35 AM FIRST 0.20 GALiHR PASS EACH MONTH: AUG 1. 2011 6:07 PM JUL 24. 2011 2:19 PM FIRST 0.10 GAL /HR PASS EACH MONTH: A x R. x END x x x x 4 D AND G 233 2732 BRUNDAGE LN BAKERSFFILD CA 9330 661-326-1083 AUG I6. 2011 10:02 AM WPLLD LINE LEA}: TEST HISTORY W 2:UNLEADED LAST 3.0 GAL /HR PASS: AUG 16. 20111 - 9:35 AM FIRST 0.20 GHL;'HR PASS EACH MONTH: AUG 6, 2011 4:31 AM JUL 3, 2011 1:32 AM FIRST 0.10 GAL /HR PASS EACH MONTH: JUL 3. 2011 2:04 AM APR 30. 2011 2:53 AM x x x x x END x x x A A D AND G 233 2732 BRUNDAGE LN BAKERSFFILD CA 9330 661- 326 -1083 AUG 16, 2011 10:02 AM WPLLD LINE LEAK TEST HISTORY W 3:PREMIUM LAST 3.0 GAL/'HR PASS: AUG 16. 2011 9:36 AM FIRST 0.20 GAL/HR PASS EACH MONTH: AUG 1. 2011 3:29 PM JUL 6. 2011 2:26 PM JUN 30, 2011 3:15 PM FIRST 0.10 GAL /HR PASS EACH MONTH: JUL 1, 2011 5:14 AM MAY 7. 2011 1:28 All A R x x x END x x x x x CSLD DIAGNOSTICS T I:UNLEADED PROBE SERIAL NUM 750368 AUG 16. 2011 6:34 AM TEST RATE: -0.02 GAL /HR TOTAL TESTS: 18/78 TOTAL TIME: 32.3 HRS AVE VOLUME: 5361 GALS POS REJECTS: 0 THRUPUT EST: 16525 GALS DISPENSE STATE: IDLE x CSLD MONTHLY REPORT AUG 16, 2011 10:03 AM CURRENT MONTH 0.2 GAL /HR TEST T ):UNLEADED PROBE SERIAL NUM 750368 NO TEST DATA AVAILABLE T 2:PREMIUM PROBE SERIAL NUM 204409 NO TEST DATA AVAILABLE T 3:DIESEL PROBE SERIAL NUM 204305 NO TEST DATA AVAILABLE D AND G 233 2732 BRUNDAGE LN BAKERSFFILD CA 9330 661- 326 -1083 AUG 16. 2011 10:45 AM SYSTEM STATUS REPORT T 2 :DELIVERY NEEDED T 3:DELIVER`! NEEDED j i W I:ANNUAL LINE FAIL I WPLLD LINE LEAK ALARM W 1:DIESEL GROSS LINE FAIL AUG 16, 2011 10:49 AM WPLLD LINE LEAK ALARM W I:DIESEL WPLLD SHUTDOWN ALM AUG 16, 2011 10:49 AM D AND G 233 2732 BRUNDAGE LN BAKERSFFILD CA 9330 661 -326 -1083 AU(; 16. 2011 10:49 AM SYSTEM STATUS REPORT T 2:DELIVERY NEEDED T 3 :DELIVERY NEEDED W I:GROSS LINE FAIL W (:WPLLD SHUTDOWN ALM W I:ANNUAL LINE FAIL WPLLD LINE LEAK mLARh1 W 2:UNLEADED GROSS LINE FAIL AUG 16. 2011 10:56 AM WPLLD LINE LEAK ALARM W 2:UNLEADED WPLLD SHUTDOWN ALM AUG 16, 2011 10:56 AM t D AND G 233 2732 BRUNDAGE LN BHKERSFFILD CA 9330 661 - 326 -1083 AUG 16, 2011 11:06 AM SYSTEM STATUS REPORT T 2:DELIVERY NEEDED T 3:DELIVERY NEEDED W I :GROSS LINE FAIL W 1:WPLLD SHUTDOWN ALM W I:ANNUAL LINE FAIL W 2:GROSS LINE FAIL W 2:WPLLD SHUTDOWN ALM WPLLD L114E LEA(. ALARM W 3:PREINIUM GROSS LINE FAIL AUG 16, 2011 11:10 AM WPLLD LINE LEAK. ALAWI W 3:PREMIUM WPLLD SHUTDOWN ALM AUG 16, 2011 11:10 AM W 2:UNLEADEDLINELEAKALARMWPLLDLINELEAK ALARMWPLLD W I: DIINE D AND C 233 WPLLD SHUTDOWN ALM WPLLD SHUTDOWN ALM AUG 16. 2011 9:26 AM 2732 BRUNDAGE LN AUG 16, 2011 9 :23 HM BAI;ERSFF I LD CA 9330 661-326-1083 AUG 16. 2011 11:10 AM SYSTEM STATUS REPORT WPLLD LINE LEAK ALARM T 2:DELIVERY NEEDED WPLLD LINE LEAF: ALARM W 3:PREMW2:UNLEADED WPLLD SHUTDOWN T 3:DELIVERY NEEDED WPLLD SHUTDOWN ALM 26 AMAUG16. 2011 9:6 AUG 16, 2011 923 AM W I:GROSS LINE FAIL W l :WPLLD SHUTDOWN ALM W 1:ANNUAL LINE FAIL W 2:GR0SS LINE FAIL W 2:WPLLD SHUTDOW14 ALM SENSOR ALARM -- -- WPLLD LINE LEAK ALARM L 1:DISP IW3:GROSS LINE FAIL W 3 :PREMIUM DISPENSER PANWPLLDSHUTDOWNALMSENSOROUTALARM W 3:WPLLD SHUTDOWN ALM AUG, 16. 2011 9:23 AM AUG 16, 2011 9;26 Art SENSOR ALARM - - - -- - - -- IN -TANK ALARM -- - -- L 1 :D1SP 1 T 3:DIESELDISPENSERPANINVALIDFUEL LEVELFUELALARMAUG16. 2011 9:26 AM AUG 16. 2011 9:23 AM IN -TANK ALARM - - - -- - IN -TANK ALARM - -- -- T 3:DIESEL T 3:DIES LOW PRODUCT ALARM AUG 16. 2011 9:25 AM AUG }6. 2011 9:2OVERFILLALARM6 AM IN -TANK ALARM - - - -- - - -- IN -TANK ALARM T 3 :DIESEL T IDIESEL DELIVERY NEEDEDPROBEOUT AUG 16, 2011 9.:25 AM AUG l6, 2011, 9:26 AM WPLLD LINE LEAK ALARM W i:D1ESEL WPLLD SHUTDOWN ALI AUG 16. 2011 9 :26 Am T 3:DIESEL INVENTORY INCREASE INCREASE START AUG 16. 2011 9 :24 AM VOLUME - 7399 GALS HEIGHT - 56.84 INCHES WATER - 1.00 INCHES TEMP - 82.3 DEC F INCREASE END AUG 16, 2011 9:27 AM VOLUME - 11065 GALS HEIGHT - 63.35 INCHES WATER = 0.00 INCHES TEMP = 85.2 DEC F GROSS INCREASE- 3666 TC NET INCREASE- 3153 D AND G 233 2732 BRUNDAGE LN BAKERSFFILD CA 9330 661 -326 -1083 AUG 16, 2011 9 :27 AM SYSTEM STATUS REPORT T 3 :DELIVER'! NEEDED W I:ANNUAL LINE FAIL 1N -TANK ALARIN - - - -- T I:UNLEADED OVERFILL ALARM AUG 16. 2011 9 :28 AM D AND G 233 2732 BRUNDAGE LN BAKERSFFILD CA 9330 661- 326 -1083 AUG 16, 2011 9:28 AM SYSTEM STATUS REPORT T I :OVERFILL ALARM T 3 :DELIVERY NEEDED W I :ANNUAL LINE FAIL ARCHIVE UTILITY SAVE SETUP DATA START TIME: AUG 16. 2011 9:28:25 AM ARCHIVE UTILITY SAVE SETUP DATA: END TIME: AUG 16. 2011 9:29:30 AM BYTES : 8320 ti IN-TANK mLARM - - --- T 2:PREMIUM OVERFILL ALARM AUG 16. 2011 9:30 AM I T I:UNLEADED 1 NVE14TORY INCREASE INCREASE START AUG 16. 2011 9:27 AM VOLUME - 8680 GALS HEIGHT - 65.21 INCHES WATER - 0.00 INCHES TEMP - 85.0 DEG F INCREASE END AUG 16. 2011 9:30 AM VOLUME - 11075 GALS HEIGHT - 83.44 INCHES WATER - 0.00 INCHES TEMP - 85.7 DEG F GROSS IW- REASE- 2395 TC NET INCREASE- 2348 IN -TA14K ALARM - - - -- T 2 : PREM I UM PROBE OUT AUG 16. 2011 9:30 AM D AND G 233 2732 BRUNDAGE LN BAKERSFFILD CA 9330 661-326 -1083 AUG 16, 2011 9:30 AM SYSTEM STATUS REPORT T 2:PROBE OUT T 3:DELIVEP.Y NEEDED W I:ANNUAL LINE FAIL 1N -T14NK. ALARM - - - -- T 2:PREMIUM DELIVERY NEEDED AUG 16. 2011 9:33 AP1 D AND G 233 2732 BRUNDAGE LN BAItERSFFILD CA 9330 661- 326 -1083 AUG 16. 2011 933 AM SYSTEM STATUS REPORT T 2:PROBE OUT T 2 :DELIVERY NEEDED T 3:DELIVERY NEEDED W I :ANNUAL LINE FAIL T 2:PREMIUM INVENTORY INCREASE INCREASE START AUG 16, 2011 9:29 All VOLUME - 7172 GALS HEIGHT - 55.39 INCHES WATER - 0.00 114CHES TEMP - 64.8 DEG F INCREASE END AUG 16, 2011 9:35 AM VOLUME - 11142 GALS HEIGHT - 84.07 INCHES WATER - 0.00 INCHES TEMP a 86.1 DEG F GROSS INCREASE- 3970 TO NET INCREASE- 3891 f SWRCB, January 2006 Spill Bucket Testing Report Form This form is intendedfor use by contractors performing annual testing of UST spill containment structures. The completedform and printoutsfrom tests (fapplicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: #233 D and G Date of Testing: 8/16/2011 Facility Address: 2732 Brundage Lane , Bakersfield, CA 93304 Facility Contact: Omero Garcia I Phone: 661- 393 -7000 Date Local Agency Was Notified of Testing: 7/13/2011 Name of Local Agency Inspector (fpresent during testing): Ester Duran 2. TESTING CONTRACTOR INFORMATION Company Name: Confidence UST Services, Inc. Technician Conducting Test: Bryan A Self Credentials: X CSLB Contractor X ICC Service Tech. X SWRCB Tank Tester Other (Spec) License Number(s): CSLB #804904 iCC #8022804 -UT Tank Tester# 1 1 -1756 3. SPILL BUCKET TESTING INFORMATION Test Method Used: x Hydrostatic Vacuum Other Test Equipment Used: Lake Test Equipment Resolution: 0.0625" identify Spill Bucket (By Tank Number, Stored Product, etc. 1 Regular 2 Diesel 3 Super 4 Bucket Installation Type: Direct Bury x Contained in Sump Direct Bury x Contained in Sump Direct Bury x Contained in Sump Direct Bury Contained in Sum Bucket Diameter: 12.00" 12.00" 12.00" Bucket Depth: 13.50" 14.25" 14.25" Wait time between applying vacuum /water and start of test: 5 min. 5 min. 5 min. Test Start Time (Ti): 9:00am 9:00am 9:00am Initial Reading (Rj): 10.00" 9.75" 10.00" Test End Time (TF): 10:00am 10:00am 10:00am Final Reading (RF): 10.00" 9.75" 10.00" Test Duration (TF — Tj): I hour 1 hour 1 hour Change in Reading (RI.- - Ri): 0.00" 0.00" 0.00" Pass /Fail Threshold or Criteria: 0.0625" 0.0625" 0.0625" Test Result. X Pass Fail X Pass Fail X Pass Fail Pass Fail Comments — (include information on repairs made prior to testing, and recommendedfollow -upforfailed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true, accurate, and infull compliance with legal requirements. Technician's Signature: Date: 8/16/2011 State laws and regulations do not cu&KY require testing to be performed by a qualified contractor. However, local requirements may be more stringent. Cr0 VIDFj 0 T:01W coHV AHMWIm ODWI avu• Invoice No: 27344 Re air Lo : During annual monitoring system certification I noticed that the TLS 350 is currently showing a W 1 annual lin fail, since the system is passing a monthly .02 GPH line test the inspector was unconcerned. 7-day" Re uired Re airs: Comments: Updated 04 /19/06 TATT Team