HomeMy WebLinkAbout2012 FMC RESULTSMONITORING SYSTEM CERTIFICATION P2 sS For Use By All Jurisdictions Within the State ofCalifornia Authority Cited: - Chapter 6 7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code ofRegulations This form must be used to document testing and servicing ofmonitoring equipment. A separate certification or report must be prepared for each monitoring system control panel by the technician who performs the work. A copy ofthis form must be provided to the tank system owner /operator. The owner /operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date. A. General Information Facility Name: Costco Wholesale Bldg. No: 688 Site Address: 3800 Rosedale Hwy. City: Bakersfield Zip: 93308 Facility Contact Person: Lisa Contact Phone No.: (661) 6360832 Make /Model of Monitoring System: Veeder -Root TLS 350 -R Date of Testing/Servicing: 6/6/2012 B. Inventory of Equipment'Tested /Certified Check the appropriate boxes to indicate specific equipment inspected/serviced Tank ID: 87A Tank ID: 87B In -Tank Gauging Probe. Model: 847390 -109 In -Tank Gauging Probe. Model: 847390 -109 Annular Space or Vault Sensor Model: 794380 -301 Annular Space or Vault Sensor Model: 794380 -301 Piping Sum / Trench Sensor(s). Model: 794380 -352 Piping Sum / Trench Sensor(s). Model: 794380 -352 Fill Sump Sensor(s). Model: 794380 -352 Fill Sump Sensor(s). Model: 794380 -352 Mechanical Line Leak Detector Model: Mechanical Line Leak Detector Model: Electronic Line Leak Detector Model: V/R PLLD Electronic Line Leak Detector Model: V/R PLLD Tank Overfill / High-Level Sensor Model: 847390 -109 Tank Overfill / High-Level Sensor Model: 847390 -109 Other (specify equipment type and model in Section E on Page 2). Other (specify equipment type and model in Section E on Page 2). Tank ID: 91 Tank ID: In -Tank Gauging Probe. Model: 847390 -109 In -Tank Gauging Probe. Model: 0 Annular Space or Vault Sensor Model: 794380 -301 L1 Annular Space or Vault Sensor Model: Piping Sum / Trench Sensor(s). Model: 794380 -322 Piping Sum / Trench Senso s). Model: Fill Sump Sensor(s). Model: 794380 -352 LIFill Sump Sensor(s). Model: El Mechanical Line Leak Detector Model: LIMechanical Line Leak Detector Model: Electronic Line Leak Detector Model: V/R PLLD 0 Electronic Line Leak Detector Model: Tank Overfill / High-Level Sensor Model: 847390 -109 El Tank Overfill / High-Level Sensor Model: Other (specify equipment type and model in Section E on Page 2). LJ Other (specify equipment type and model in Section E on Page 2). Dispenser ID: 1/2 El Dispenser Containment Sensor(s). Model: F±1 Shear Valve(s). Dispenser Containment Float(s) and Chain(s). 794380 -208 Dispenser ID: 3/4 F±1 Dispenser Containment Sensor(s). Model: OShear Valve(s). Dispenser Containment Float(s) and Chain(s). 794380 -208 Dispenser ID: 5/6 21 Dispenser Containment Sensor(s). Model: FZI Shear Valve(s). Dispenser Containment Float(s) and Chain(s). 794380 -208 Dispenser ID: 7/8 P] Dispenser Containment Sensor(s). Model: ElShear Valve(s). Dis enser Containment Float(s) and Chain(s). 794380 -208 Dispenser ID: 9/10 21 Dispenser Containment Sensor(s). Model: 2 Shear Valve(s). Dis enser Containment Float(s) and Chain(s). 794380 -208 Dispenser ID: 11/12 2 Dispenser Containment Sensor(s). Model: Shear Valve(s). Dis enser Containment Float(s) and Chain(s). 794380 -208 If the facility contains more tanks or dispensers, copy this form. Include information for every tank and C. Certification I certify that the equipment identified in this document was inspected /se ( eof manufacturers' guidelines. Attached to this Certification is information (e.g. manufacturers' checklists) nece information is correct and a Plot Plan showing the layout of monitoring equipment. For any equipment c pa reports, 1 have also attached a copy ofthe report; (check all that apply): Q System Setup Technician Name(print): William S. Karras Signature: Certification No: A26028 License. No: rat the facility. i accordance with the v rify that this crating such Alarm History Report 888712 Testing Company Name: W.S.K. & Sons Inc. Phone No: (951) 906 -3023 Test Company Address: 34455 Sunlight Dr. Yucaipa, CA 92399 Date of Testing/Servicing: 6/6/2012 Monitoring System Certification Page I of D. Results of Testing/Servicing Software Version Installed: 328.03 Complete the followine checklist: P Yes H No* Is the audible alarm operational? Yes No* Is the visual alarm operational? LJJ Yes LJ No* Were all sensors visually inspected, functionally tested, and confirmed operational? Yes No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not interfere with their proper operation? Yes LJ No* Ifalarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) operational? El N/A Yes No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: -which sensors initiate positive shut -down? (Check all that apply) Dump/Trench Sensors; ELpenser Containment Sensors. Did you confirm positive shut -down due to leaks and sensor failure /disconnection? Yes Q No N/A Yes No* For tanks stems that utilize the monitoring system as the primary tank overfill warning device i.e. no N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank fill oint(s ) and operating ro erl ? If so, at what percent oftank capacity does the alarm trigger? 90% El Yes* No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E, below. Yes* No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) Product Water If yes, describe causes in Section E, below. Yes No* Was monitoring system set-up reviewed to ensure proper settings? Attach set up reports, if applicable Yes I L1 No* Is all monitoring equipment o erational per manufacturer's specifications? In Section E below, describe how and when these deficiencies were or will he corrected. Page 2 of4 F. III -'Tank Gauging / SIR Equipment: Check this box iftank gauging is used only for inventory control Check this box ifno tank gauging or SIR equipment is installed. This section must be completed if in -tank gauging equipment is used to perform leak detection monitoring. Complete the following checklist: Yes No* Has all input wiring been inspected for proper entry and termination, including testing for Kound faults? Yes No* Were all tank gauging probes visually inspected for damage and residue buildup? Yes No* Was accuracy ofsystem product level readings tested? Yes 77 No* Was accuracy of system water level readings tested? Yes No* Were all probes reinstalled properly? Yes I Lj No* I Were all items on the equipment manufacturer's maintenance checklist completed? In the Section H, below, describe how and when these deficiencies were or will be corrected. G. Line Leak Detectors (LLD): Complete the following checklist: Check this box if LLDs are not installed Yes LJ No* Forequipment start-u or annual equipment certification, was a leak simulated to verify LLD erformance? N/A Check all that apply) Simulated leak rate: 3 .h.; E 0.1 g.p.h LJ 0.2 .h. LJ Yes M No* Were all LLDs confirmed operational and accurate within regulatory requirements? 7 Yes 7 No* Was the testing apparatus properly calibrated? El Yes No* For mechanical LLDs, does the LLD restrict product flow if it detects a leak? P/1 N/A Yes No* For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak? N/A 2 Yes El No* For electronic LLDs, does the turbine automatically shut off if any portion ofthe monitoring system is disabled N/A or disconnected? Yes No* For electronic LLDs, does the turbine automatically shut off if any portion ofthe monitoring system 7 N/A malfunctions or fails a test? LZJ Yes Ej No* For electronic LLDs, have all accessible wiring connections been visually inspected? N/A Yes No* I Were all items on the equipment manufacturer's maintenance checklist completed? In the Section H, below, describe how and when these deficiencies were or will be corrected. H. Comments: Page 3 of4 SWRCR, lanumy 2002 page Of Secondary Containment Testing Report Form YydsfohP is bamdedfor we by A perfoubWpgno,*cUwMofMTswmdarymmm m sYstOux WedveCOfi&aC&ft qpprvpr Ue pages ofdilsform to rqwn r altsfor all camponews tested Ae conrleft0fix7m wrOm wmPl'Ocedures- aFsd PrbuW&frow ft& (fapps! Awdd be propW to dwfgci* OwnOrlopawarforsubwwd to d local regulakwY 4ROM7 1. FACZLXrY MFORMATION Feca-ft Nramw. DaW ofT 3too 20 cc w crE L — fiAdn- gr- Phow. Agency Was NGdfWofTesting: 5 / I;,— Nmw'OfLocidAamcVbMectw(ifVre=WdwbeladW): 0 1 - T-lV II SPEQ-bA- 10io— )- Ly 7 WVIAIO FAXILU 131csm Lfteww Cake= 0 SW M L=wd TwkTOSW M-7. 71 "17F Ni I l- ------ 111 ME fflm=v WMEW lffwlwllw Tw IMM All aooin nr c o or oo r oo aoo r c ot rs 0000 ono o oo: Nby&osb* hWmg ww pw&nud, demd)e Audww &= Vn& ft WM aft CaMpUbw Of WItL Le 6K 51t -W- i n A VCA A M*Ob RESPONSEBIA FOR COFG[) TTSTENG iTechnician's Si SWRCB, January 2002 DTI' —4 Page of __ U . of With CmUmment Boxes Spi COUUummmt Boris acre Prescn , but were Not Tested o Tess Method Developed By: Spell Bucket m;anafacdurr fflndustry Standard Professional weer other (Specify) Test A athod Used: Pressure Vac mun Hyd tic 0 Other l fy) Test lewd: tSLc&( EaiurommoakResohdi+om: rBucimt 7)& Dom #17 aa. SPlll Box #'K 7t3 Sp® Box # SPA Boa # 12, p b L2 ob 1 L 6C 1ti, as as Wait time between applying pwmawM,wmmVwater and IS A4 l S A? IV Teri Batt `IIIQC: Ub goc, A a, yD e b A Initial (- o l a. a o a a Test End, Virtu: 06 A M4 Final R,ea fh* (RF): I iq. p Li 0 C, o 6 " Test IDuraolkm: j , D A-' R[-)= PassfFaif 7.reshold or Test RMUIIL. Pass Fail Pass Vass FAR D P Fail Ox[ * b#bnion on Mwft madeEYE to ksft andrecafltmmded, fogrn ,upfoI' ailedBests) C r- SWRCB, January 2002 Page of 90 S'Ii i VER ML CONTAPII'IENT BOXES Kwility is Not EquWed With Spill/OverfillSpill/Overfill Contamment Boxes S dVOvetiffl Containment Boxes and Present, but were Not Tested Test Method Developed By. Spill Bucket Manafactum Industry Standard Professional lughum Odw (Specify) Test Method Used: 0 Pressure vacuum ydrostadc Other (') Tea Used: aFL- I Fruirnneo RawhAimm- BudCet lDi6m . Sp® Box # 7%4- Spill Box #P 'p Spill Box #e)eM sP® Box # 2+00 l 2, cr-> 12.,C) ic) Bucket Depth: p a 5 Wait time between applying test Test Start Time: OU a Initial Reading (RIL): D(o to 0 Test ffindTime: 9:00 4 DO Z ; OO C Final Readieg (Rp): Oo G 00 00 Test IDurafion: Change y' tl Pass(Fail 1res old or Cfitelia: . s5 /P SS Pf Test Resat ftff Ttil FsM fasa Fml COMMPC# — (hWfi& Pform *= on repaft madeprkr to Laft and rBGdAU1tP.i &dfQUow -MpfbrffIPdtm&8) t t K® I CEO 9 i 1 J ja Or 9 i ja Or CP IQP °P P Q S P- 4 Q D dos dole dos dL `don dw o a 4+ fl o a H H a a a fl- a a a a a a a H a a fl H a na ja O dos dole dos dL `don dw BAKERSFIELD CITY FIRE DEPARTMENT — INSPECTION RECORD - Post this Card at the Job Site and DO NOT Remove for Duration of WoTk Inspection Request Phone No. (661) 326-3979 UST NEW INSTALL JOB DESCRIiTION: yCP" (Z_ DESCRIPTION DATE SIGNATURE BACKFILL PRIMARY PIPE SECONDARY PIPE SECONDARY CONTAINMENT SENSORS AUTHORIZATION FOR FUEL_ ELECTRICAL SEAK-OFF NK7TE k LIST REMOVAL DESCRIPTION DATE SIGNATURE IREMARKS: I AST NEW INSTALL DESCRIPTION DATE SIGNATURE MODIFICATIONS MINOR / MAJOR AST REMOVAL DESCRIPTION DATE SIGNATURE EVRIJPGRADE R 'R'.,'T '&Xl,N,0 AN UA L, - Q $ L,-A 0/ 0 R LA_ST,S YS T MSAH A, L V B CNST A:W QQMPHIVA DIAC -EPTE[B4O MISC. ACTIVITY T Ul r-'tl It =EESFIEUM- K—ER K D ,A'ATMENTOL BUILDING ADDRESS: 3191CO JOB DESCRIiTION: yCP" (Z_ OCCUPANCY TYPE: OWNER: PERMIT NO. 33 CONTRACTOR: PHONE # --05tZ LIST REMOVAL DESCRIPTION DATE SIGNATURE IREMARKS: I AST NEW INSTALL DESCRIPTION DATE SIGNATURE MODIFICATIONS MINOR / MAJOR AST REMOVAL DESCRIPTION DATE SIGNATURE EVRIJPGRADE R 'R'.,'T '&Xl,N,0 AN UA L, - Q $ L,-A 0/ 0 R LA_ST,S YS T MSAH A, L V B CNST A:W QQMPHIVA DIAC -EPTE[B4O MISC. ACTIVITY T Ul r-'tl I t =EESFIEUM- K—ER K D ,A'ATMENTOL BUILDING ADDRESS: 3191CO JOB DESCRIiTION: yCP" (Z_ OCCUPANCY TYPE: OWNER: PERMIT NO. 33 CONTRACTOR: PHONE # --05tZ FD 1743 YSTEM SETUP - 1JN' 6, 2012 9:35 AM STEM UNITS J.a. V/STEM LANGUAGE ENGLISH lSTEI1 DATE /T I ME FORMAT 1ON DD YYYY HH : MIH : SS xM 237901 Costco 6e3 s300 Rosedale Hiahwa Bakersfield, CA SHIFT TIME 1 DISABLED SHIFT TIME 2 DISABLED SHIFT TIME 3 DISABLED SHIFT TIME 4 DISABLED SHIFT BIR PRINTOUTS DISABLED DAILY BIR PRINTOJTS DISABLED I I CKETED DEL I VER -i DISABLED TANK PER TST NEEDED WRN ISABLED LANK ANN- TST NEEDED WRN I SABLED LINE RE- ENABLE METHOD r13S LINE TEST INE PER TST NEEDED WRN iISABLED INE ANN TST NEEDED WRN SABLED RINT TC VOLUMES NABLED EMP COMPENSATION ALUE (DEG F ) : 6O.0 710')< HEIGHT OFFSET NABILED LLAGE: 90% PROTOCOL DATA FORMAT 7' IGHT RECISIO14 TEST DURATION OURS: 12 ` 20 GPH LINE TEST] JTO- CONFIRM: ENABLED 10 GPH LINE TEST JTO- CONFIRM: ENABLED INT PRECISION LINE ST RESULTS: DISABLED kYLIGHT SAVING TIME TABLED r Mr:,I NTENANCE HISTORY DISABLED TANK CHART SECURITY I) ISABLED A C JST011 ALARMS DISABLED SERVICE NOTICE ENABLED DELIVERY OVERRIDE ENABLED ht9 SS. /DENSITY DISABLED COMMUNICATIONS SETUP PORT :SETT I NGS : COMM BOARD : 1 (ED 111 ) RS -232 SECURITY CODE : DISABLED COMM BOARD 2 (RS -232) BAUD RATE 9690 PARITY ODD STOP BIT 1 STOP DATA LENGTH: 7 DATA RS -232 SECURITY CODE : DISABLED COMM BOARD 3 (S -SAT BAUD RATE 9600 PARITY NONE STOP BIT 1 STOP DATA LENGTH: 8 DATA RS -232 SECURITY CODE : DISABLED DTR NORMAL STATE: HIGH AUTO 'TRANSMIT SETTINGS: ART DATE AUTO LEAK ALARM LIMIT R WEEK 2 SUN DISABLED ART TIME AUTO HIGH WATER LIMIT 00 AM DISABLED D DATE AJTO OVERFILL LIMIT J WEEK 1 SJN DISABLED TIME AUTO LOW PRODUCT Do AM D I SABLED AUTO THEFT LIMIT DIRECT LOCAL PRINTOUT DISARLED TABLED A UTrJ DELIVERY START DISABLED O PROTOCOL PREFIX AUTO DELIVERY END DISABLED T AJTO XTERfJAL IN': -UT ON DISABLED AUTO IkXTERNAL INPUT OFF TEM SECURITY I,ISki D E : 000000 AUTO SENSOR FUEL ALARM DISABLED AUTO SENSOR WATER ALARM DISABLED AJTO SENSOR OUT ALARM DISABLED RECEIVER SETUP: D 6:VEEDER ROOT (FMS) Cie RCVR TYPE: COMPJTER PORT NO: 3 RETRY NO: 5 RETRY DELAY: 5 CONFIRMATION REPORT: OFF AUTO DIAL TIME S` -TUP: D B :VEEDER ROOT (FMS) DIAL WEEKLY MON DIAL 'TIME : 12 :55 AM DECEIVER REPORTS: 1,3 --932 END OF MESSAGE DISABLED AUTO DIAL ALARM :SETUP D B:VEEDER ROOT (FMS) IN -TANK ALARMS iALL:LEAK ALARM ALL:HIGH WATER ALARM ALL:OVERFILL ALARM ALL:LOW PRODUCT ALARM ALL:SUDDEN LOSS ALARM ALL:HIGH PRODUCT ALARM ALL:INVALID FUEL LEVEL i1LL:PROBE OUT ALL:HIGH WATER WARNING ALL:DELIVERY NEEDED ALL:MAX PRODUCT ALARM ALL:GROSS TEST :FAIL ALL:PERIODIC TENT FAIL ALL:ANNUAL TEST FAIL ALL:PER TST NEEDED WRN ALL:ANN TST NEEDED WRN ALL:PER TST NEEDED ALM ALL:ANN TST NEEDED ALM ALL:TANK TEST ACTIVE ALL:NO CSLD IDLL? TIME LEAK MIN ANNUAL : 80% 15960 PERIODIC TEST TY' ?E STANDARD ANUAL TEST FAIL ALARM ;DISABLED PERIODIC TEST FAIL ALARM :DISABLED GROSS TEST FAIL, ALARM, DISABLED ANN .'TEST AVERAG'I NG : OFF P: -R 'TEST AVERAGING: OFF TANK TEST NOTIFY: OFF TNK TST SIPHON BREAK:OFF DELIVERY DELAY I MIN STICK OFFSET 0.00 PJMP 'THRESHOLD 10.00% T 3:Premium PRODUCT CODE 2 HERMAL COEFF :.000700 FLOAT SIZE: 4.0 IN. NK DIAMETER 119.63 TANK PROFILE 4 PTS FULL VOL 19951 89.'7 INCH VOL 16216 59.9 INCH VOL 10017 29.9 INCH VOL 3781 I'ETER DATA YES END FACTOR: NONE AL 'UPDATE: MATER WARN I NG 1.0 HIGH WATER LIMIT: 1.0 AX OR LABEL VOL: 19951 VERFILL LIMIT 90% ROBE OFFSET 17956 ilGH PRODUCT 95% 18953 SLIVERY LIMIT 22% IMMEDIATE MATER WARN I NG 1.0 HIGH WATER LIMIT: 1.0 AX OR LABEL VOL: 19951 VERFILL LIMIT 90% ROBE OFFSET 17956 ilGH PRODUCT 95% 18953 SLIVERY LIMIT 22% 4500 OW PRODUCT 739 EAK ALARM LIMIT: 8 UDDE N LOSS LIMIT: 25 ANK T I LT 0.00 ROBE OFFSET 0.00 IPHON MANIFOLDE'D TANKS 1: NONE NE MANIFOLDED 'TANKS t: NONE AK MIN PERIODIC: 80 %s 15960 AK MIN ANNUAL 80% 15960 PERIODIC TEST TYPE STANDARD ANNUAL TEST FAIL ALARM DISABLED PERIOjIC TEST FAIL ALARM DISABLED GROSS, TEST FAIL ALARM 711 SABLED ANN TEST AVERAGING: OFF PER 'TEST AVERAGING: OFF TANK TEST NOTIFY: OFF TNK TST SIPHON B.REAK:OFF DELIVERY DELAY 1 MIN STICK OFFSET 0.00 PUP'1P 'THRESHOLD 10.00% LEAK TEST METHOD TEST ON DATE : A:--L TANK JAN 1, 1996 START TIME : DISABLED TEST RATE :0.20 GAL./HR DURATION : 2 HOURS TST EARLY STOP:DISABLED LEAK 'TEST REPORT FORMAT NORMAL PRESSURE LINE LEAK SETUP G 1:UNL 87A T'YP:1.5IN ENVIRN GFLEXII LINE LENGTH: 173 FEET 0.20 GPH TEST: REPETITIV 0.10 ,PH TEST: AUTO SHUTDOWN RATE: 3.0 GPH 1.OlAl PRESSURE SHUTOFF : YES LOW PRESSURE : 5 PSI 7. 1:Unleaded DISPENSE MODE: STANDARD JEIVSCR: HIGH PRESSURE PRESSURE OFFSET: O.OPSI G 2:UNL 87B TYP:1.5IN ENVIRN GFLEXII LINE LENGTH: 175 FEET 0.20 GPH TEST: R'-PE'TITIV 0.10 GPH TEST: AJTO SHUTDOWN RATE: 3.0 GPH LOW PRESSURE SHU'T'OFF :YES LOW PRESSURE : 5 Psi T 2:Unleaded DISPENSE MODE: STANDARD SENSOR: HIGH PRESSURE PRESSURE OFFSET: O.OPSI G 3:PREMIUM 91 T'YP:1.5IN ENVIRN GFLEXII LINE LENGTH: 283 FEET 0.20 GPH TEST: REPETITIV 0.10 GPH TEST: A'JTO SHUTDOWN RATE: 3.0 GPH LOW PRESSURE SHUTOFF :YES LOW PRESSURE : 5 PSI T 3:Premium DISPENSE MODE: STANDARD SENSOR: HIGH PRESSURE PRESSURE OFFSET: O.OPSI LINE LEAK LOCKOUT SETUP LOCKOUT SCHEDULE DAILY S'TAR'T TIME' DISABLED STOP TIME : DISABLED LIQUID SENSOR SETUP L 1 : U INLEAD A ANNULAR RI -STATE (SINGL:E FLOAT) CATEGORY : ANNULAR SPACE P, I. 2:UNLEAD A FILL DUAL FLT. DISCRIMINATING CATEGORY : PIPING. SUMP I. 3:UNLEAD A STP DUAL FLT. DISCRIMINATING, CATEGORY : STP SUMP L 4:UNLEAD B ANNULAR TRI -STATE (SINGLE FLOAT) CATEGORY : ANNULAR SPACE I. 5:UNLEAD B FILL. DUAL FLT. DISCRIMINATING Gi:ATEG'ORY : PIPING SUMP I. 6:UNLEAD B STP DUAL FLT. DISCRIMINATING C;ATEGl3RY : STP SJMP I. 7: PREM I UM ANNULAR TRI -STATE (SINGLE. FLOAT) CATEGORY : ANNULAR SPACE L 8:PREMIUM FILL DUAL FLT. DISCRIMINATING CATEGORY : PIPING SUMP L 9:PREMIUM STP DUAL FLT, DISCRIMINATING CATEGORY : STP SUMP L10:DISP PAN 1.2 7RI- :S,TATE (SINGLE FLOAT) CATEGORY : DISPENSER PAN L11:DISP PAN 3,4 T,4I - :-','PATE (SINGLE' FLOAT) CATEGORY : DISPENSER PAN L12:DISP PAN 5.6 TRI- :PATE (SINGLE FLOAT) CATEGORY : DISPENSER PAN L13 :DISP PAN 7,8 TRI -STATE (SINGLE, FLOAT) C,= TEGORY : DISPENSER PAN L14:DISP PAN 9,10 TRI-STATE (SINGLE FLOAT) r:;,iTEGORY : DISPENSER PAN L15:DISP PAN 11,12 T'R I - SPATE ( S I NGL.= FLOAT CATEGORY : DISPENSER PAN GUTPUT RELAY SETUP R 1 :OVERFILL ALARM TYPE: STANDARD NORMALLY OPEN TANK ti: NONE IN -TANK ALARMS ALL :HIGH WATER ALARM ALL:OVERFILL ALARM ALL:LOW PRODUCT ALARM ALL:SUDDEN LOSS ALARM ALL:HIGH PRODUCT ALARM ALL:INVALID FUEL LEVEL ALL:PROBE OUT ALL:HIGH WATER WARNING ALL : DELI VERY NEEDED ALL:MAX PRODUCT ALARM LIQUID SENSOR ALMS ALL:FUEL ALARM ALL:SENSOR OUT ALARM ALL :SHORT ALARM ALL:WATER ALARM ALL :HIGH LIQUID ALARM ALL:LOW LIQUID ALARM ALL:LIQUID WARNING R 2 : NIEMBERSH I P IfYPE: STANDARD NORMALLY OPEN TANK 0: NONE IN -TANK ALARMS ALL:LEAK ALARM ALL :HIGH WATER ALARH ALL :OVERFILL ALARM ALL:LOW PRODUCT ALARM ALL:SUDDEN LOSS ALARM ALL:PROBE OUT LIQUID SENSOR ALMS ALL:FUEL ALARM ALL:SENSOR OUT ALARM ALL :SHORT ALARM ALL:WATER ALARM ALL:HIGH LIQUID ALARM ALL:LOW LIQUID ALARM ALL:LIQUID WARNING PLLD LINE DISABLE SETUP 4) 1 : UNL 87A IN -TANK ALARMS T I:HIGH WATER ALARM T I :LOW PRODUCT ALARM LIQUID SENSOR ALMS L I:FUEL ALARM L ':FUEL ALARM 3:FUEL ALARM L 6:FUEL ALARM 10:FUEL ALARM L11 :FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM L14:'FUEL ALARM L15:FUEL ALARM L I :SENSOR OUT ALARM L 2:SENSOR OUT ALARM 3: SENSOR OUT ALARM L a :SENSOR OUT ALARM 10:ISENSOR OUT ALARM L11:SENSOR OUT ALARM L12 :SENSOR OUT ALARM L13:SENSOR OUT ALARM L14 :SENSOR OUT ALARM L15:SENSOR OUT ALARM 1 :SHORT ALARM L 2:SHORT ALARM L 3 :SHORT ALARM 6 : SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM L13:SHORT ALARM 14:SHORT ALARM L15:SHORT ALARM 3:HIGH LIQUID ALARM L 6:HIGH LIQUID ALARM L '2 :LIQUID WARNING L 3:LIQUID WARNING L 6:LIQUID WARNING PRESSURE LINE LEAK g 1:PLLD OPEN ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK :AIL ISD SETUP FAIL ISD SENSOR OUT : =AIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL 0 2:UNL 87B IN -TANK ALARMS T 2:HIGH WATER ALARM T 2 :LOW PRODUCT ALARM LIQUID SENSOR ALMS L 3:FUEL ALARM L 4:FUEL ALARM L 5:FUEL ALARM L 6:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM 7 12:FUEL ALARM L13:FUEL ALARM L14:FUEL ALARM 15:FUEL ALARM 1L 3:SENSOR OUT i =,LARM L 4:SENSOR OUT ALARM 5:SENSOR OUT ALARM L 6 :SENSOR OUT ALARM lL 10: SENSOR OUT i4LARM L11 :SE NSOR OUT ALARM L12:SENSOR OUT ALARM L13:SENSOR OUT ALARM LI4:SENSOR OUT ALARM L15:SENSOR OUT ALARM 3 :SHORT ALARM 4:SHORT ALARM L 5:SHORT ALARM L 6:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM u12:SHORT ALARM 1: -3::3HOFIRT ALARM t} (oo ok L14:SH0RT ALARM 715:'SH0RT ALARM S:HIGH LIQUID ALARM 6:HIGH LIQUID ALARM L 3:LIQUID WARNING 5:LIQUID WARNING 6:LIQUID WARNING PRESSURE LINE LEAK i 2:PLLD OPEN ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD SETUP FAIL ISD :SENSOR OUT FAIL IUD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL G 3:PREMIUM 91 IN -TANK ALARMS T 3:HIGH WATER ALARM T 3:L0W PRODUCT ALARM LIQUID SENSOR ALMS L 7:FUEL ALARM L 8:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM 11:FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM 14:FUEL ALARM 15:FUEL ALARM 7:SENS0R OUT ALARM L B :SENSOR OUT ALARM 9:SENS0R OUT ALARM L10:SENS0R OUT ALARM L11:SENS0R OUT ALARM L12:SENS0R OUT ALARM L13:SENS0R OUT ALARM L14:SENS0R OUT ALARM L15:SENS0R OUT ALARM 7:3)H0RT ALARM L 8:SH0RT ALARM L 9:SH0RT ALARM 1 10::SH0RT ALARM L11:SH0RT ALARM L12:SH0RT ALARM L13:SH0RT ALARM LL 14 : SHORT ALARM L15:SH0RT ALARM L B:HIGH LIQUID ALARM L 9:HIGH LIQUID ALARM L B:LIQUID WARNING L 9:LIQUID WARNING PRESSURE LINE LEAK Q 3:PLLD OPEN ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD 'VAPOR LEAK FAIL ISD SETUP FAIL ISD SENSOR OUT FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL REiCONCILIATION SETUP I: D l l °I 1: G AUTOMATIC DAILY CLOSING TIHW : 2:00 AM AUTO 13HIFT 01 CL.'OSING TIME: DISABLED AUTO SHIFT 02 CLOSING TIME: DISABLED AUTO SHIFT 93 CLOSING TIME: DISABLED AUTO SHIFT 04 CLOSING TIME: DISABLED PERI +ODIC RECONCILIATION MODE: 20915 MONTHLY ALARM: 1- DISABLED TEMP COMPENSATION VF S'T'ANDARD 3- 3 21366 PETER CALIBRATION DISP OFFSET: 0.000% 21367 BUS ;SLOT FUEL ME'T'ER TANK 3 1 1 1 1 3 1 1 2 3 3 1 2 1 1 3 1 2 2 3 3 1 3 1 1 3 1 3 2 3 3 1 4 1 1 3 1 4 2 3 3 1 5 1 1 3 1 5 2 3 3 1 6 1 1 3 1 6 2 3 3 1 7 1 1 3 1 7 2 3 3 1 8 1 1 3 1 8 2 3 3 1 9 1 1 3 1 9 3 3 1 10 1 1 3 1 10 3 3 1 11 1 1 3 1 11 3 3 1 12 1 1 3 1 12 2 3 SI'MART:SENSOR SETU? 1:VF DISP 1 -2 CATEGORY AIR FLOW METER 2:VF DISP 3 -4 CATEGORY AIR FLOW DIETER 3:VF DISP 5 -6 CATEGORY AIR FLOW METER 4:VF DISP 7 -8 CATEGORY AIR FLOW DIETER 5:'VF DISP 9 -10 CATEGORY AIR FLOW METER 6:'VF DISP 11 -12 CATEGORY AIR FLOW METER s B:PRES SENSOR 3 -4 CATEGORY VAPOR PRESSURE EVR./ I SD SETUP EVR TYPE: VACUUM ASSIST VACUUM ASSIST TYPE HEALY VAC NOZZLE A/L RANGE mAX: 1.15 MIN: 0.95 VAPOR PROCESSOR TYPE NONE ANALYSIS TIMES TIME: 5:00 AM DELAY MINUTES: ACCEPT HIGH ORVR: DISABLED ISD HOSE TABLE ID FP FL HL AA RR O1 01 01 09 01 UU 02 02 02 09 J 1 UU 03 03 03 09 02 UU 04 04 04 09 02 UU 05 05 05 09 03 UU 06 06 06 09 03 UU 07 07 07 09 04 UU 03 03 08 09 04 UU 09 09 09 09 05 UU 10 10 10 09 05 UU 11 11 11 09 06 UU 12 12 12 09 06 UU I :SD AIRFLOW METER MAP ID SERIAL NUM LABEL 1 20915 VF DISP 1- 2 21353 VF DISP 3- 3 21366 VF DISP 5- 4 21367 VF DISP 7- 5 21338 VF DISP 9- 6 21164 VF DISP 11 ISD FUEL GRADE HOSE MAP 1 2 3 4 FP MHH MHH MHH MHH AA 01 101 201 U U U U 1 02 102 202 U U U U 1 03 103 203 U U U U 2 04 104 204 U U U U 2 r7 105 205 U U U U 3 66 106'206 U U U U 3 07 107 207 U U U U 4 08 108 208 U U U U 4 09 109 209 U U U U 5 10 110 210 U U U U 5 it 111 211 U U U U 6 12 112 212 U U U U 6 LABEL. TABLE 1: UNASSIGNEq 2: BLENDS 3: 'REGULAR 4 : MID GRADE 5: PREMIUM 6: GOLD 7: BRONZE 3: SILVER 9: BLEND2 10: BLEND4 P(1C ;SETUP FMC VERSION* 01.01 VAPOR PROCESSOR 'TYPE NONE PROCESSOR CONTROL LEVEL: NONE cOF'TWARE REVISION LEVEL tiERSION 328.03 OFTIAIARE# 346328 -100 -D CREATED - 08.06.06.17.21 MODULE# 330160 -164 -a 23YSTEM FEATURES: PERIODIC IN -TANK TESTS ANNUAL IN -TANK TENTS BIR ISD F L 0.10 AUTO 0.20 REPETITIV I,i ?LLD 0.10 AUTO 0.'20 REPETITIV D''EL I VERY NEEDED MAV 21, 2012 7:04 PM HAY 13, 2012 4:03 PM MAY 11, 2012 12:04 PM LOW TEMP WARNING END JUN 6, 2012 8:28 AM SEP 7, 2011 11:56 PM JUL 6, 2011 9:21 AM ALARM HISTORY REPORT R u END LOW PRODUCT ALARM T 3:Premlum OCT 19, 2010 1:51 PM ALARM HISTORY REPORT Mi3R 30, 2010 4:19 PM PM LOW PRODUCT ALARM rwG 7, 2008 11:08 All IN-TANK AM ALARM SUDDEN LOSS ALARM IN -TANK ALARM - - - -- APR 17, 2011 1:16 AM SUDDEN LOSS ALARM FEB 27, 2011 5 :41 T 1:Unleaded T 2:Unleaded APR 4. 2010 4:05 SEP 7, 2011 11:46 PM JUN 6. 2012 tiA AUG '7, 2008 11:22 AM FEB 23, 2012 SEP 3, 2010 5:56 AM OVERFILL ALARM AUG 31, 2010 6:47 AM JUN 6, 2012 6:27 All APR 20. 2012 11:49 All HIGH PRODUCT ALARM SEP 30, 2011 12:15 PM SEP 4. 2008 7:47 PM AUG 7, 2008 11:18 All LOW PRODUCT ALARM OCT 19, 2010 2:48 PM INVALID FUEL LEVEL MAR 30, 2010 2:06 PM P,UG 7, 2008 11'08 AM AUG 7, 2008 11:11 AM PROBE OUT SUDDEN LOSS ALARM JUN 6, 2012 8::31 AM SEP 7, 2011 11 :46 PM JUN 6, 2012 8:29 All APR 4, 2010 3:49 PM SEP 7, 2011 11:37 PM APR 4, 2010 3:42 PM HIGH PRODUCT ALARM DELIVERY NEEDED JUN 6, 2012 8:27 All MAY 21. 2012 6:57 PM JUL 6, 2011 9:20 AM MAY 15. 2012 6:25 Pll JUL 14, 2010 9:10 AM MAY 13, 2012 3:56 PM INVALID FUEL LEVEL PUG 7. 2008 11:11 AM LOW TEMP WARNING JUN 6, 2012 8:32 AM PROBE OUT JUL 14, 2010 9:17 AM JUN 6, 2012 8:27 AM AUG 7, 200e 11:26 AM JUN 6, 2012 8:25 All SEP 7, 2011 11:47 PM D''EL I VERY NEEDED MAV 21, 2012 7:04 PM HAY 13, 2012 4:03 PM MAY 11, 2012 12:04 PM LOW TEMP WARNING END JUN 6, 2012 8:28 AM SEP 7, 2011 11:56 PM JUL 6, 2011 9:21 AM us_ V ALARM HISTORY REPORT R u END IN -TANK ALARM T 3:Premlum OVERFILL ALARM JUN 6, 2012 8:34 AM APR 25, 2012 2:36 PM AUG 27. 2011 12:35 PM LOW PRODUCT ALARM FEB 27, 2011 7:'35 AM AUG 7. 2008 11:08 AM ALARM HISTORY REPORT SUDDEN LOSS ALARM IN -TANK ALARM - - - -- APR 17, 2011 1:16 AM FEB 27, 2011 5 :41 All T 2:Unleaded APR 4. 2010 4:05 Phl OVERFILL ALARM HIGH PRODUCT ALARM JUN 6. 2012 8:31 AM AUG '7, 2008 11:22 AM FEB 23, 2012 8:10 All OCT 12, 2011 PM1:20 P INVALID FUEL LEVEL FEB 27, 2011 7:36 AM AUG 7, 2008 11:07 AM us_ V eAvmz VUl JUN 6, 2012 8:34 AM JUN 6, 2012 8:32 AM JUL 6, 2011 9:28 AM DELIVERY NEEDED FEB 27, 2011 7:06 AM JUL 15, 2009 9:38 AM APR 30, 2009 10:36 AM I` "AX PRODUCT ALARM AJG 7. 2008 11:22 All LOW TEMP WARNING J UN 6. 2012 8: 35 All AUG 7, 2008 11:27 All x A A A END X A x x HARM H I STORY RE`_JOR'F SENSOR ALARM - - - -- I. 1:UNLEAD A ANNULAR P:NNULAR SPACE FJEL ALARM JUN 6. 2012 8:02 AM NSOR OUT ALARM JUL 6, 2011 9:13 All FUEL ALARM JUL 6. 2011 9:02 AM X x* x X E14D * K A A X ALARM HISTORY REPORT SENSOR ALARM - - - -- L 2:UNLEAD A FILL PIPING SUMP FUEL ALARM J iN 6. 2012 8:73 All TENSOR OUT ALARM JUL 6, 2011 9:13 AM FJEL. ALARM JUL 6, 2011 9:03 AM A E x 0 A 0( END # x x x ALARM HISTORY REPORT SENSOR ALARM - - - -- L 3:UNLEAD A STP c''TP :SUMP LIQUID WARNING JUN 6, 2012 8:04 All SENSOR OUT ALARM JUL 6, 2011 9:13 AM LIQUID WARNING JUL 6, 2011 9:04 All x x A x A END # u## X ALARM HISTORY RE::DORT SENSOR ALARM - - - -- L 4:UNLEAD B ANNULAR ANNULAR SPACE FUEL ALARM JUN 6, 2012 8:05 All S' "N:3OR OUT ALARM JUL S. 2011 9:13 All FUEL ALARM JUL 6. 2011 9:34 All ALARM HISTORY REPORT SENSOR ALARM L 5:UNLEAD B FILL PIPING SUMP SENSOR OUT ALARM JUN 6, 2012 8:21 AM LIQUID WARNING JUN 6, 2012 8:08 AM SENSOR OUT ALARM JUL 6, 2011 9:13 All x x * A A END A A X) x ALARM HISTORY REPORT SENSOR ALARM - - - -- L 6:UNLEAD B STP TP BUMP LIQUID WARNING JUN 6, 2012 8:09 AM SENSOR OUT ALARM JUL 6. 2011 9:13 AM LIQUID WARNING JUL 6, 2011 9:06 All 54 # x x X END x o A* x ALARM HISTORY REPORT SENSOR. ALARM - - - -- L ":PREMIUM ANNULAR ANNULAR SPACE I=JEL ALARM JUN 6. 2012 8:10 AM SENSOR OUT ALARM JUL 6, 2011 9:13 AM FUEL ALARM JUL G.. 2011 9:,37 All AL.ARIh HISTORY RE:POR'I• SENSOR ALARM - - - -- L 8:9REMIUM FILL PIPING SUMP LIQUID WARNING JUN 6, 2012 8:11 AM SENSOR OUT ALARM JUL 6, 2011 9:13 AM LIQUID WARNING JUL 6, 2011 9:08 All x' w* A END X K x)i x ALARM HISTORY REPORT SENSOR ALARM - - - -- L 9:PREMIUM STP S'rP SUMP LIQUID WARNING JUN 6, 2012 8:12 AM SENSOR OUT ALARM JUL 6, 2011 9:13 All LIQUID WARNING JUL 6, 2011 9:08 All x A# x A END # K x x# F;LARM HISTORY REPORT SENSOR ALARM - - - -- I.10 :DISP PAN 1.2 DISPENSER PAN FJEL ALARM JUN 6, 2012 8:13 AM FUEL ALARM NOV '20, 2011 2:27 rl °1 1:JEL ALARM E.P 25, 2011 it-19 AIh ALARM HISTORY REPORT SENSOR ALARM - - - -- I.11:DISP PAN 3,4 DISPENSER PAN FUEL ALARM JUk 6. 2012 8:13 AM A SENSOR OUT ALARM JUL 6, 2011 9:13 All 1:JEL ALARM JUL 6. 2011 9:39 AIh x +( A A END X u X x ALARM HISTORY REPORT SENSOR ALARM - - - -- L12:DISP PAN 5,6 DISPENSER PAN FUEL ALARM JUN 6, 2012 8:14 All SENSOR OUT ALARM JUL 6, 2011 9:13 AM FUEL ALARM JUL 6, 2011 9:10 AI °1 x x 4** END A n A x PLARM HISTORY RE = ORT SENSOR ALARM - - - -- L13:DISP PAN 7,8 DISPENSER PAN SENSOR OUT ALARM JUN 6, 2012 8:21 AM FUEL ALARM JUN 6,2'012 8:14 AM c_TUr DATA WARNING MAY 8, 2012 9:48 PI °1 ALARM HISTORY REPORT SENSOR ALARM ----- L14:DISP PAN 9,10 DISPENSER PAN FUEL ALARM JUN 6, 2012 8:15 AM SENSOR OUT ALARM JUL 6, 2011 9:13 All FUEL ALARM JUL 6, 2011 9:11 All END f :-ARM HISTORY REPORT SENSOR ALARM - - - -- L15:DISP PAN 11,12 DISPENSER PAN FUEL ALARM JUN 6, 2012 8:14 All SENSOR OUT ALARM JUL 6, 2011 9:13 AM FUEL ALARM JUL 5, 2011 9:11 AM PILARM HISTORY REPORT SENSOR ALARM - - - -- L 1:UNLEAD A ANNULAR ANNULAR SPACE FUEL ALARM JUN 6, 2012 8:02 AM SENSOR OUT ALARM JUL 6, 2011 9:13 All FUEL ALARM JUL 6, 2011 9:02 All A_ARM HISTORY REPORT SENSOR ALARM - - - -- G 1:UNL 87A I-'LLD SHUTDOWN ALARM JUN 6, 2012 9:25 All GROSS, LINE FAIL JUN 6, 2012 9:25 All F)-LD SHUTDOWN ALARM JJN 5, 2012 8:21 AM V PLLD SHUTDOWN ALARM JJN 6, 2012 8:15 All PLLD SHUTDOWN ALARM JUN S. 2012 8:14 All PLLD ;SHUTDOWN ALARM JUN 6. 2012 8:14 AM P7 LD SHUTDOWN ALARM JUN 6, 2012 8:14 All PLLD .SHUTDOWN ALARM JUN 6. 2012 8:13 All PLLD SHUTDOWN ALARM JUN 6. 2012 8:13 AM PLLD :SHUTDOWN ALARM JUN 6, 2012 8:09 All A* a A x END x w x K X ALARM HISTORY REPORT SENSOR ALARRM - - - -- G 2:UNL 87B PLLD SHUTDOWN ALARM JUN 6, 2012 9:10 AM GROSS LINE FAIL JUN 6, 2012 9:10 All PLLD SHUTDOWN ALARM JUN 6, 2012 8:21 AM PLLD SHUTDOWN ALARM JUhJ 6, 201,2 8:15 AM PLLD ;SHUTDOWN ALARM JUN 6, 2012 8:14 AM PLLD :SHUTDOWN ALARM JUN 6, 2012 8:14 AM F*.LD SHUTDOWN ALARM JUN 6, 2012 8:14 AI1 P?: LD SHUTDOWN ALARM JUN 6, 2012 8:13 AM a PLLD ,:SHUTDOWN ALARM JUN 6. 2012 8:13 All PLLD .SHUTDOWN ALARM JUN 6, 2012 8 :09 All x*** A END X* x A A t c ALARM HISTORY RE' OR'r SENSOR ALARM - - - -- G 3:PREMIUM 91 PLLD SHUTDOWN ALARM JUN 6, 2012 8:57 All GROSS LINE FAIL JUN 6, 2012 8:57 AM PLLD SHUTDOWN ALARM JUN 6, 2012 8:21 All PLLD :SHUTDOWN ALARM JUN 6. 2012 8:15 AM PLLD SHUTDOWN ALARM JUN 6, 2012 8:14 All PLLD SHUTDOWN ALARM JUN 6, 2012 8:14 All PLLD SHUTDOWN ALARM JUN 6, 2012 8:14 AM PLLD ;SHUTDOWN ALARM JUN 6, 2012 8:13 All PLLD SHUTDOWN ALARM JUN 6, 2012 8:13 AM P:-LD SHUTDOWN ALARM JUN S, 2012 8:12 All 207901 Costco 683 0900 Rosedale Hiahwa Bakersfield. CA JUN 6, 2012 9:38 All LAST POWER OUTAGE REPORT T 1:Unleaded PROBE SERIAL NUM 609830 POWER REMOVED JAN 1, 1970 12:00 AM VOLUME 0 GALS WATER VOL 0 GALS TEMP a 0.0 DEG F POWER RESTORED AUG 7, 2008 2:37 All Vi)LUIIIE = 13853 GALS WATER VOL = 0 GALS TEMP = 88.7 DEG F GROSS VOLUME CHANGE 13855 GALS T 2:Unleaded PROBE SERIAL NUM 444350 POWER REMOVED JAN 1. 1970 12:00 All VOLUME 0 GALS WATER VOL 0 GALS TEMP 0.0 DEG F POWER RESTORED PUG 7, 2008 2:37 AM VOLUME = 14173 GALS WATER VOL = 0 GALS TEMP - 88.5 DEG F GROSS VOLUME CHANGE 14178 GALS T 3:Premium PROBE SERIAL NUM 563562 POWER REMOVED JAN 1. 1970 12:00 All VOLUME = 0 GALS WATER VOL m 0 GALS TEMP = 0.0 DEG F I-XJER RESTORED PUG 7. 2008 2:37 All Ii-)LUP1E = 13824 GALS WATER VOL - 0 GALS TEMP = 87.5 DEG F GROSS VOLUME CHANGE 13824 GALS 7 4:PrEmiurn 10 DATA HISTORY IA