HomeMy WebLinkAboutFMC 201291 4 11000 N. MoPac Expressway, Suite 500 Austin, Texas 78759 Phone: (512) 451 -6334 Fax: (512) 459 -1459 BAKERSFIELD FIRE DEPARTMENT OFFICE OF ENVIRONMENTAL SERVICES INSPECTOR CRAIG PERKINS 1501 TRUXTUN AVE. BAKERSFIELD, CA. 93301 Test Date: 01/11/2012 Order Number: 3189014 Dear Regulator, l Date Printed and Mailed: 02/23/2012 Enclosed are the results of recent testing performed at the following facility: CIRCLE K 2701270 5634 STINE RD BAKERSFIELD, CA. 93313 Testing performed: Leak detector tests Monitor Certification Secondary Containment -Spill Container Sincerely, b 0-1- KA41-1 Dawn Kohlmeyer Manager, Field Reporting Zip %/7 Q1 TANKNOLOGY CERTIFICATE OF TESTING 8501 N MOPAC EXPRESSWAY, SUITE 400 AUSTIN, TEXAS 78759 TELEPHONE (512) 451 -6334 FAX (512) 459 -1459 PURPOSE: COMPLIANCE TEST RESULT SUMMARY REPORT TEST DATE: 01/11/12 WORK ORDER NUMBER: 3189014 CUSTOMER PO: Joel Lindquist CLIENT: CIRCLE K STORES SITE: CIRCLE K 2701270 495 E. RINCON, STE. 150 5634 STINE RD CORONA, CA 92879 BAKERSFIELD, CA 93313 TRISHA YAHNER JOHN - MANAGER 951)270 -5108 (661)8348625 TEST TYPE: TLD -1 Pmrlurt Pina Tinintnacc Tact Raciiltc LINE' ID y et N RODUCT LINE MATERIAL x, rADELIVERY TYE i X I' - TEST RESULT 3; A ,B C D rte° Fa FIN, L LEAKRATE (gp11)tr A BC MD IMPACT VALVE ^ FUNCTION T1 -87 1 UNLEADED DW FIBERG PRESSURE M SERIAL # RESULTS MANUFACTURER T2 -91 2 PREMIUM DW FIBERG PRESSURE 3 Fxictinn I ina I aak natartnr Tact g -VLINE , SEX INGrLEAK DETECT, R # 'a EXISTING LEAKIDETE TOR #2.' MANFACTURR i MODEL # M SERIAL # RESULTS MANUFACTURER rMbDEL #, SERIAL,# f l RESULTp; ID_ w_v 3 F LD2000 08041484 PT1 -87 1 VAPORLESS T2 -91 2 VAPORLESS LD2000 09111129 P Now Ranlar_amant I ina I aak natartnr Tact LIpE Me' R s °; esC t I MANUFACTUR MODEL'# SERIAL "# RSARE T MANUFACTURERK MODEL # SERIAL # RESUL ror owner oetauea report mrormauon, visit www.tanKnojogy.com ana select un -t,ine Keports -wKAP, or contact your iocai i anknology ortice. Tester Name: EDWIN PINEDA r Technician Certification Number: 8026748 Printed 02/23/2012 06:56 MTUTTLE INDIVIDUAL TANK INFORMATION AND J'r 733nknology TEST DATE: 01/11/12 8501 N MOPAC EXPRESSWAY, SUITE 400 CLIENT: CIRCLE K STORES AUSTIN, TEXAS 78759 (512) 451-6334 TEST RESULTS WORK ORDER NUMBERS189014 SITE:CIRCLE K 2701270 AN zlw-' 11 , , , - - - 4 - - , 4'. NTA,NK,, "i1NFORWkTW01, 11- 11 IOW*9,jNNW & Tank ID: Ti -87 1 Tank manifolded: NO Bottom to top fill in inches: Product: UNLEADED Vent manifolded: YES Bottom to grade in inches: Capacity in gallons: 14,976 Vapor recovery manifolded: YES Fill pipe length in inches: Diameter in inches: 92.00 Overfill protection: YES Fill pipe diameter in inches: 4.0 Length in inches: 527 Overspill protection: YES Stage I vapor recovery: DUAL Material: DW FIBERG Installed: ATG Stage 11 vapor recovery: ASSIST CIP installed on: COMMENTS DANKTEST, RESQQT$ kT LEAK EST R Star (in) End (in) Dipped Water Level: Now/passed Failed/replaced New/passed Failed/replaced Dipped Product Level: L.D. #1 L.D. #1 L.D. #2 L.D. #2 Probe Water Level: Make: vApoRLEss Ingress Detected: Water Bubble Ullage Model: LD2000 Test time: S/N: 08041484 Open time in sec: 3.00 Inclinometer reading: Holding psi: 29 VacuTect Test Type: NOT Resiliency cc: 140 NOT VacuTect Probe Entry Point: TESTED Test leak rate ml/m: 189.0 TESTED Pressure Set Point: Metering psi: 18 Tank water level in inches: Calib. leak in gph: 3.00 Water table depth in inches: Results: PASS Determined by (method): Result: COMMENTS COMMENTS Test 461147N. MW V Material: DW FIBERG Diameter (in): 2.0 Length (ft): 160.0 Test psi: Bieedback cc: Test time (min): NOT NOT NOT NOT Start time: TESTED TESTED TESTED TESTED End time: Final gph: Result: Pump type: PRESSURE Pump make: FE PETRO COMMENTS Impact Valves Operational: UNKNOWN Printed 02/23/2012 06:56 INDIVIDUAL TEST DATE:01 /11/12 CLIENT:CIRCLE K STORES TANK INFORMATION AND p, Tanknology 8501 N MOPAC EXPRESSWAY, SUITE 400 AUSTIN, TEXAS 78759 (512) 451 -6334 TEST RESULTS WORK ORDER NUMBER3189014 SITE:CIRCLE K 2701270 4 ce NKINFORMATION Tank ID: T2 -91 2 Tank manifolded: NO Bottom to top fill in inches: Product: PREMIUM Vent manifolded: YES Bottom to grade in inches: Capacity in gallons: 11,849 Vapor recovery manifolded: YES Fill pipe length in inches: Diameter in inches: 92.00 Overfill protection: YES Fill pipe diameter in inches: 4.0 Length in inches: 417 Overspill protection: YES Stage I vapor recovery: DUAL Material: DW FIBERG Installed: ATG Stage II vapor recovery: ASSIST CP installed on: COMMENTS TANK TEST RESULTSaTesP'MethOd VacuTec.t ` '` w LEAK,,DETECTOR TESTRESU,L "TS "; ` Testxmethod`•FTA Start (in) End (in) Dipped Water Level: New /passed Failed /replaced New /passed Failed /replaced Dipped Product Level: L.D. #1 L.D. #1 L.D. #2 L.D. #2 Probe Water Level: Make: vAPoRLEss Ingress Detected: Water Bubble Ullage Model: LD2000 Test time: S /N: 09111129 Open time in sec: 3.00 Inclinometer reading: Holding psi: 25 VacuTect Test Type: NOT Resiliency cc: 120 NOT VacuTect Probe Entry Point: TESTED Test leak rate ml /m: 189.0 TESTED Pressure Set Point: Metering psi: 19 Tank water level in inches: Calib. leak in gph: 3.00 Water table depth in inches: Results: PASS Determined by (method): Result: COMMENTS COMMENTS z LINE TESITTRESULTS z.Test type T, l r i INEk vP` A- .A Material: DW FIBERG Diameter (in): 2.0 Length (ft): 160.0 Test psi: Bleedback cc: Test time (min): NOT NOT NOT NOT Start time: TESTED TESTED TESTED TESTED End time: Final gph: Result: Pump type: PRESSURE Pump make: FE PETRO COMMENTS Impact Valves Operational: UNKNOWN Printed 02/23/2012 06:56 MONITORING SYSTEM CERTIFICATION For Use By All Jurisdictions Within the State of California Authority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3 Title 23, California Code of Regulations This form must be used to document testing and servicing of monitoring equipment. If more than one monitoring system control panel Is installed at the facility, a separate certification or report must be prepared for each monitoring system control panel by the technician who performs the work. A copy ofthis form must be provided to the tank system owner /operator. The owner /operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date. A. General Information Facility Name: CIRCLE K 2701270 Site Address: 5634 STINE RD City: BAKERSFIELD CA Zip: 93313 Contact Phone No: 834 -8625 Date of Testing /Service: 01/11/2012 Facility Contact Person: JOHN - MANAGER Make /Model of Monitoring System:TLS 350 Work Order Number: 3189014 B. Inventory of Equipment Tested /Certifled Check the appropriate boxes to indicate specific equipment inspected /serviced Tank ID: T1 87 Tank ID: T2 91 X In -Tank Gauging Probe. Model: MAG PROBE X In -Tank Gauging Probe. Model: MAG PROBE X Annular Space or Vault Sensor. Model: VR-409 Annular Space or Vault Sensor. Model: VR -409 X Piping Sumprrrench Sensor(s). Model: VR -208 Piping Sump/Trench Sensor(s). Model: VR -208 Fill Sump Sensor(s). Model: Fill Sump Sensor(s). Model: x Mechanical Line Leak Detector. H Model: LD -2000 X Mechanical Line Leak Detector. Model: LD -2000 Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model: X Tank Overfill /High -Level Sensor. Model: PROBE /FLAPER Tank Overfill /High -Level Sensor. Model: PROBE /FLAPPER Other (specify equipment type and model In Section E on page 2). Other (specify equipmentpfy type and model in Section E on page 2). Tank ID: Tank ID: In -Tank Gauging Probe. Model: In -Tank Gauging Probe. Model: Annular Space orVault Sensor. Model: Annular Space or Vault Sensor. Model: Piping Sump/Trench Sensogs). Model: Piping Sump/Trench Sensor(s). Model: Fill Sump Sensogs). Model: Fill Sump Sensogs). Model: Mechanical Line Leak Detector. Model: Mechanical Line Leak Detector. Model: Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model: Tank Overfll /High -Level Sensor. Model: Tank Overfill /High -Level Sensor. Model: Other (specify equipment type and model in Section E on page 2). Other (specify equipmentpty type and model in Section E on page 2). Dispenser : 1 -2 Dispenser ID: 7 -8 Dispenser Containment Sensors) Model: 7 Dispenser Containment Sensors) Model: X] Shear Valve(s). X Shear Valve(s) IX Dispenser Containment Float(s) and Chain(s). X Dispenser Containment Float(s) and Chaln(s). Dispenser ID: 3 -4 Dispenser ID: 0 Dispenser Containment Sensors) Model: Dispenser Containment Sensors). Model: Shear Valve(s). Shear Valve(s). X Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s). Dispenser ID: 5 -6 Dispenser lD: 0 Dispenser Containment Sensors) Model: Dispenser Containment Sensor(s). Model: rShear Valve(s). Shear Valve(s). X Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s). If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility. C. Certification I certify that the equipment identified in this document was inspected /serviced in accordance with the manufacturers' guidelines. Attached to this certification is information (e.g manufacturers' checklists) necessary to verify that this information Is correct. and a Site Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also attached a copy of the (Check all that apply): X System set -up Xn Alarm history report Technician Name (print): EDWIN PINEDA Signature: lv, Certification No.: 8026748 -UT License. No.: 743160 (Class'A' General Enginering Contractor License) Testing Company Name:Tanknology Phone No.: (800) 800 -4633 Site Address: 11000 N. MoPac Expressway, suite 500, Austin, TX 78759 Date of Testing /Servicing: 01/11/2012 Monitoring System Certification Page 1 of 3 Based on CA form dated 03/08 Site Address 5634 STINE RD D. Results of Testing /Servicing Software Version Installed: 328.03 Complete the following checklist: Monitoring System Certification Date of Testing /Service: 01/11/2012 F1 Yes No' Is the audible alarm operational? Q Yes No . Is the visual alarm operational? 0 Yes No • Were all sensors visually Inspected, functionally tested, and confirmed operational? Q Yes No Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not interfere with their proper operation? Yes No x N/A If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) operational? x Yes No • NIA For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate positive shut -down? (check all that apply) x SumpfTrench Sensors; Dispenser Containment Sensors. Did you confirm positive shut -down due to leaks and sensor failure /disconnection? x Yes No Yes O No' NIA For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e.: no mechanicaloverfillpreventionvalveisinstalled), is the overfill warning alarm visible and audible at the tank fill points(s) and operating properly? If so, at what percent of tank capacity does the alarm trigger? 1-71 Yes* No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E, below. Yes* fl No Was liquid found inside any secondary containment systems designed as dry systems? (check all that apply) Product; Water. If yes, describe causes in Section E, below. Qx Yes 1-1 No • Was monitoring system set -up reviewed to ensure proper settings? Attach set -up reports, if applicable. x Yes F1 No • Is all monitoring equipment operational per manufacturers' specifications? In Section E below, describe how and when these deficiences were or will be corrected. E. Comments: Replaced siphon het valve and adjusted lea etec or on t1 87 Page 2 of 3 Based on CA form dated 03/08 Monitoring System Certification Site Address: 5634 STINE RD F. In -Tank Gauging / SIR Equipment Check this box if no tank gauging or SIR equipment is installed. Date of Testing /Service: 01/11/2012 Check this box if tank gauging is used only for inventory control, Check this box if no tank gauging or SIR equipment is installed. This section must be completed if in -tank gauging equipment Is used to perform leak detection monitoring. Complete the following checklist: Yes No Has all input wiring been inspected for proper entry and termination, including testing for ground faults? Yes No Were all tank gauging probes visually inspected for damage and residue buildup? El Yes No' Was accuracy of system product level readings tested? IEYes No Was accuracy of system water level readings tested? x yes No • Were all probes reinstalled properly? Yes No Were all items on the equipment manufacturers' maintenance checklist completed? In the Section H, below, describe how and when these deticiencies were or will be corrected. G. Line Leak Detectors (LLD) : Check this box if LLDs are not installed. Complete the following checklist: Q Yes No' NIA For equipment start -up or annual equipment certification, was a leak simulated to verify LLD performance? Check all that apply) Simulated leak rate: x 3 g.p.h 0.1 g.p.h 0.2 g.p.h x Yes No' Were all LLDs confirmed operational and accurate within regulatory requirements? x Yes No Was the testing apparatus properly calibrated? FR] Yes No ' NIA For mechanical LLDs, does the LLD restrict product Flow if it detects a leak? Yes No' NIA For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak? Yes No ' x NIA For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? Yes No ' Q NIA For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a test? Yes No' 0 NIA For electronic LLDs, have all accessible wiring connections been visually Inspected? ryn Yes No' Were all items on the equipment manufacturers' maintenance checklist completed? In the Section H, below, describe how and when these deticiencies were or will be corrected. H. Comments: Page 3 of 3 Based on CA form dated 03/08 SWRCB, January 2002 Page 1 . Secondary Containment Testing Report Form Thisform is intendedfor use by contractors performing periodic testing of UST secondary containment systems. Use the appropriate pages ofthisform to report resultsfor all components tested. The completedform, written test procedures, and printouts from tests (ifapplicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: CIRCLE K 2701270 Date of Testing: 01/11/2012 Facility Address: 5634 STINE RD , BAKERSFIELD, CA, 93313 Facility Contact: JOHN - MANAGER Phone: (661) 834 -8625 Date Local Agency Was Notified of Testing: Name of Local Agency Inspector (ifpresent during testing): Ernie Medina 2. TESTING CONTRACTOR INFORMATION Company Name: TANKNOLOGY, INC. Technician Conducting Test: EDWIN PINEDA Credentials: CSLB Licensed Contractor SWRCB Licensed Tank Tester License Type: A- UT I License Number: 743160-8026748 Manufacturer Manufacturer Training Component(s) Date Training Expires OPW SPILL BUCKET 02/03/2013 Spill Box 2 PRE FILL 0000 3. SUMMARY OF TEST RESULTS Component Spill Box 2 PRE FILL 0000 00 000 00 MWMOM 000 00 0000 0 If hydrostatic testing was performed, describe what was done with the water after completion oftests: WATER WAS PUT IN FIVE GALLON BUCKETS AND PLACE IN TRUCK FOR NEXT SITE CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING To the best ofmy knowledge, thefacts stated in this document are accurate and infull compliance with legal requirements Technician's Signature: Date: 01/11/2012 SWRCB, January 2006 9. Spill Bucket Testing Report Form Thisform is intendedfor use by contractors performing annual testing of UST spill containment structures. The completedform and printouts from tests (if applicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: CIRCLE K 2701270 Date of Testing: 01/11/2012 Facility Address: 5634 STINE RD , BAKERSFIELD, CA, 93313 Facility Contact: JOHN - MANAGER Phone: ( 661) 834 -8625 Date Local Agency Was Notified of Testing: Name of Local Agency Inspector (ifpresent during testing): Ernie Medina 2. TESTING CONTRACTOR INFORMATION Company Name: TANKNOLOGY, INC. Technician Conducting Test: EDWIN PINEDA Credentials : CSLB Contractor a ICC Service Tech. SWRCB Tank Tester El Other (Spec) A- UT License Number: 743160-8026748 3. SPILL BUCKET TESTING INFORMATION Test Method Used: El Hydrostatic Vacuum Other Test Equipment Used: TAPE MEASURE Equipment Resolution: V I SUAL Identify Spill Bucket By Tank Number, Stored Product, etc.) t 1 UNL FILL 2 2 PRE FILL 3 4 Bucket Installation Type: X Direct Bury Contained in Sump X Direct Bury Contained in Sump Direct Bury Contained in Sump E] Direct Bury Contained in Sump Bucket Diameter: 12 " 12 " Bucket Depth: 14 " 14 " Wait time between applying vacuum/water and starting test: 10 MIN 10 MIN Test Start Time (TI ): 1320 1320 Initial Reading (RI ): 101, 101, Test End Time (TF ): 1420 1420 Final Reading (RF ): 10" 10" Test Duration: 1 HR 1 HR Change in Reading (R F - Rt ): 0 0 Pass/Fail Threshold or Criteria: 0 0 P F Test Result, X Pass) `FailXPa'ss Fail E;ailPassAsFaitPeasAn Comments - (include information on repairs madeprior to testing, and recommendedfollow -upforjailed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements. Technician's Signature: 1 n A, ` :,tL, Date: 01/11 /2012 1 Q++. 1...,,.......1 --r «,..0.7 1.., ........1:4:0.7 .... «/......t... U.... —'a, 1......1 Work Order: 3189014 ESO) k (ESV) Testing Foam - Vemion 1- 625nM7 Emergency Shut Off (ESO) & Dispenser Emergency Shutoff Valve (ESV) ANNUAL TEST RECORD LOCATIONS AND TEST DATA Testing Company: tl Date: olill Z Location Name: 1 Q Z. Store #: Y N Statc ID #: Address: 15 6TL1 51l tk City: State: C Emergency Shut fl• SO Testing Results On Ot in accordance with "ESO Vendor 1,etter (3- 21- 05).doc ", from Valero's Retail Compliance Department, as a part of annual compliance testing, this representative tested the Emeraencv Shut Off (ESO) switches indicated on this sketch. Findings listed below: Emergency Shut Off (ESO) IfNo, Provide Operational? Y N Maintenance Log # Date Called : Dispenser Emergency Shutoff Valve (ESV)-Testine Results On 1 in.accordance with NFPA 30A this representative tested the automatic - closing feature of the ispenser Emergency Shutoff VALVE(S) (ESV) located in the supply lines at the base of each individual island type dispenser indicated on the diagram below. Each device ( #) in all, would automatically close. Findings listed below: Disp. Emergency Shut Off IfNo, Provide Valve (ESV) Operational? Y N Maintenance Log # Date Called Site Map Oflocation and Plaoanentof Devices Tested: C_dE E3 6 8co Sisnature Of Rearesentative: A Vly ", Tanknology Inc. 11000 N. MoPac Expressway, Suite 500, Austin, Texas 78759 i TankrK*)gy 8501 N MOPAC EXPRESSWAY, SUITE 400 AUSTIN, TEXAS 78759 512) 451 -6334 FAX (512) 459 -1459 TEST DATE:01 /11/12 WORK ORDER NUMBEFG189014 CLIENT:CIRCLE K STORES SITE:CIRCLE K 2701270 COMMENTS Conducted the Annual Monitor Certification Testing with Inspector Ernie Medina Bakersfield Fire Department. Site contacted and e- mailed on 1/4/12 and confirmed with "URSHNA ". Veeder Root light bulb was also replaced today as well. All tests passed, part and labor on separate w /o. PARTS REPLACED QUANTITY a. , w „!" _ i F`! ^Y 'x•Y` 3 VIM a DESCRIPTION <- p, ' _ Ht:LIUM VINPUINI I t5 I KE5ULT5 (IF APPLICABLE) Printed 02/23/2012 06:56 MTUTTLE SITE DIAGRAM r TanknokVy 8501 N MOPAC EXPRESSWAY, SUITE 400 AUSTIN, TEXAS 78759 512) 451 -6334 FAX (512) 459 -1459 TEST DATE: 01 /11/12 WORK ORDER NUMBER3189014 CLIENT:CIRCLE K STORES SITE: CIRCLE K 2701270 DUMP - STER 1 CDm ID8 #4 7 #3 CANOPY ESO cas VEN 6 5 # ; STP STP pv zero 4 A A 8;7= AIR/ v E F F wtk Printed 02/23/2012 06:56 MTUTTLE ATG Information cl 110100 JAN 11, 2012 5:40 PM CIRCLE K 2701270 5634 STINE RD. BAKERSFIELD, CA SYSTEM STATUS REPORT ALL FUNCTIONS NORMAL 150301 JAN 11, 2012 5:40 PM 1:CIRCLE K 2701270 rl 150302 JAN 11, 2012 5:40 PM 2:5634 STINE RD. 150303 JAN 11, 2012 5:40 PM 3:13AKERSFIELD, CA 150304 JAN 11, 2012 5:40 PM 4: 151700 JAN 11, 2012 5:40 PM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM El 150F00 JAN 11, 2012 5:40 PM MON DD YYYY HH:MM:SS xM 160100 JAN 11, 2012 5:40 PM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 UNL -REG ON 2 UNL -PREM ON 3 OFF 4 OFF 160200 JAN 11, 2012 5:40 PM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 UNL -REG 2 UNL -PREM 160300 JAN 11, 2012 5:40 PM TANK PRODUCT CODE TANK PRODUCT LABEL 1 UNL -REG A 2 UNL -PREM B 3 3 4 4 3189014 Work Order # 3189014 ATG Information 160400 JAN 11, 2012 5:40 PM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 UNL -R6G 14976 2 UNL- PFREM 11849 3 0 4 0 160700 JAN 11, 2012 5:40 PM TANK DIAMI -TER TANK PRODUCT LABEL INCHES 1 UNL -R6G 120.00 2 UNL -PREM 117.75 3 0.00 4 0.00 n 160900 JAN 11, 2012 5:40 PM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 UNL -RgG 0.000700 2 UNL -PF2EM 0.000700 3 0.000000 4 0.000000 161200 JAN 11, 2012 8:40 PM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 UNL -RE-G NONE NONE 2 UNL -PPEM NONE NONE 3 NONE NONE 4 NONE NONE 0 U 162100 JAN 11, 2012 5:40 PM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNL -RFG 1084 2 UNL -PREM 900 3 0 4 0 a 162200 JAN 11, 2012 5:40 PM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNL -REG 14227 2 UNL -PREM 11256 3 0 4 0 0 162300 JAN 11, 2012 5:40 PM TANK OVEF;FILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 UNL -RE -G 13478 2 UNL -PREM 10664 3 0 4 0 162400 JAN 11, 2012 5:40 PM TANK HIGH WATER LEVEL LIMIT 3109014 Work Order # 3189014 ATG Information Work Order # 3189014 TANK PRODUCT LABEL INCHES 1 UNL -REG 2.5 2 UNL -PREM 2.5 162800 JAN 11, 2012 5:40 PM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 UNL -REG 14976 2 UNL•PREM 11849 162900 JAN 11, 2012 5:40 PM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 UNL•REG 748 2 UNL•PREM 947 3 0 4 0 170300 JAN 11, 2012 5:40 PM LIQUID TYPE SENSOR LOCATION TYPE 1 87 ANNULAR TRI -STATE (SINGLE FLOAT) 2 87 TURBINE TRI -STATE (SINGLE FLOAT) 3 91 ANNULAR TRI -STATE (SINGLE FLOAT) 4 91 TURBINE TRI -STATE (SINGLE FLOAT) 5 TRI -STATE (SINGLE FLOAT) 6 TRI -STATE (SINGLE FLOAT) 7 TRI -STATE (SINGLE FLOAT) 8 TRI -STATE (SINGLE FLOAT) 190200 JAN 11, 2012 5:40 PM SOFTWARE REVISION LEVEL VERSION 328.03 SOFTWARE# 346328 -100 -D CREATED - 08.06.06.17.21 S- MODULE# 330160 -004 -a SYSTEM FEATURES: PERIODIC IN -TANK TESTS ANNUAL IN -TANK TESTS ISO 120600 JAN 11, 2012 S:41 PM CIRCLE K 2701270 5634 STINE RD. BAKERSFIELD, CA TANK ALARM HISTORY TANK 1 UNL -REG HIGH WATER ALARM JAN 11, 2012 3:35 PM OVERFILL ALARM JAN 11, 2012 3:39 PM JAN 11, 2012 3:36 PM JUL 4, 2011 8:43 PM LOW PRODUCTALARM JAN 11, 2012 3:32 PM HIGH PRODUCT ALARM JAN 11, 2012 3:39 PM JAN 11, 2012 3:35 PM INVALID FUEL LEVEL JAN 11, 2012 3:32 PM PROBE OUT JAN 11, 2012 3:41 PM JAN 11, 2012 3:31 PM JAN 11, 2012 1:13 PM HIGH WATER WARNING JAN 11, 2012 3:35 PM MAX PRODUCT ALARM JAN 11, 2012 3:39 PM LOW TEMP WARNING JAN 11, 2012 3:42 PM TANK 2 UNL-PREM 3189014 ATG Information HIGH WATER ALARM JAN 11, 2012 3:55 PM OVERFILL ALARM JAN 11, 2012 3:33 PM LOW PRODUCT ALARM JAN 11, 2012 4:07 PM JAN 11, 2012 3:31 PM JAN 11, 2012 3:29 PM HIGH PRODUCT ALARM JAN 11, 2012 3:35 PM JAN 11, 2012 3:32 PM INVALID FUEL LEVEL JAN 11, 2012 3:31 PM PROBE OUT JAN 11, 2012 3:57 PM JAN 11, 2012 3:29 PM JAN 11, 2012 1:13 PM HIGH WATER WARNING JAN 11, 2012 3:55 PM DELIVERY NEEDED JAN 11, 2012 4:07 PM JAN 11, 2012 3:31 PM JAN 11, 2012 3:29 PM MAX PRODUCT ALARM JAN 11, 2012 3:35 PM 130200 JAN 11, 2012 5:41 PM CIRCLE K 2701270 5634 STINE RD. BAKERSFIELD, CA LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 87 ANNULAR JAN 11, 2012 1:13 PM SENSOR OUT ALARM JAN 11, 2012 1:11 PM FUEL ALARM 2 87 TURBINE JAN 11, 2012 1:13 PM SENSOR OUT ALARM JAN 11, 2012 1:04 PM FUEL ALARM 3 91 ANNULAR JAN 11, 2012 3:24 PM FUEL ALARM JAN 11, 2012 1:13 PM SENSOR OUT ALARM JAN 11, 2012 1:09 PM FUEL ALARM 4 91 TURBINE JAN 11, 2012 1:13 PM SENSOR OUT ALARM JAN 11, 2012 1:05 PM FUEL ALARM 110100 JAN 11, 2012 5:41 PM CIRCLE K 2701270 5634 STINE RD. BAKERSFIELD, CA SYSTEM STATUS REPORT ALL FUNCTIONS NORMAL 3189014 Work Order # 3189014