Test Date: 01/11/2012
Order Number: 3189014
Dear Regulator,
l
Date Printed and Mailed: 02/23/2012
Enclosed are the results of recent testing performed at the following facility:
CIRCLE K 2701270
5634 STINE RD
BAKERSFIELD, CA. 93313
Testing performed:
Leak detector tests
Monitor Certification
Secondary Containment -Spill Container
Sincerely,
b 0-1- KA41-1
Dawn Kohlmeyer
Manager, Field Reporting
Zip %/7 Q1 TANKNOLOGY CERTIFICATE OF TESTING
8501 N MOPAC EXPRESSWAY, SUITE 400 AUSTIN, TEXAS 78759
TELEPHONE (512) 451 -6334 FAX (512) 459 -1459
PURPOSE: COMPLIANCE TEST RESULT SUMMARY REPORT
TEST DATE: 01/11/12 WORK ORDER NUMBER: 3189014
CUSTOMER PO: Joel Lindquist
CLIENT: CIRCLE K STORES SITE: CIRCLE K 2701270
495 E. RINCON, STE. 150 5634 STINE RD
CORONA, CA 92879 BAKERSFIELD, CA 93313
TRISHA YAHNER JOHN - MANAGER
951)270 -5108 (661)8348625
TEST TYPE: TLD -1
Pmrlurt Pina Tinintnacc Tact Raciiltc
LINE'
ID
y
et N
RODUCT
LINE
MATERIAL
x,
rADELIVERY
TYE i
X I' - TEST RESULT 3;
A ,B C D
rte°
Fa
FIN, L LEAKRATE (gp11)tr
A BC
MD
IMPACT
VALVE ^
FUNCTION
T1 -87 1 UNLEADED DW FIBERG PRESSURE
M SERIAL # RESULTS MANUFACTURER
T2 -91 2 PREMIUM DW FIBERG PRESSURE
3
Fxictinn I ina I aak natartnr Tact
g -VLINE ,
SEX INGrLEAK DETECT, R # 'a EXISTING LEAKIDETE TOR #2.'
MANFACTURR i MODEL # M SERIAL # RESULTS MANUFACTURER rMbDEL #, SERIAL,# f l RESULTp; ID_
w_v
3 F
LD2000 08041484 PT1 -87 1 VAPORLESS
T2 -91 2 VAPORLESS LD2000 09111129 P
Now Ranlar_amant I ina I aak natartnr Tact
LIpE
Me' R s °; esC t I
MANUFACTUR MODEL'# SERIAL "# RSARE T MANUFACTURERK MODEL # SERIAL # RESUL
ror owner oetauea report mrormauon, visit www.tanKnojogy.com ana select un -t,ine Keports -wKAP, or contact your iocai i anknology ortice.
Tester Name: EDWIN PINEDA
r
Technician Certification Number: 8026748
Printed 02/23/2012 06:56 MTUTTLE
INDIVIDUAL TANK INFORMATION AND
J'r 733nknology
TEST DATE: 01/11/12 8501 N MOPAC EXPRESSWAY, SUITE 400
CLIENT: CIRCLE K STORES AUSTIN, TEXAS 78759 (512) 451-6334
TEST RESULTS
WORK ORDER NUMBERS189014
SITE:CIRCLE K 2701270
AN zlw-'
11 , , , - - -
4 - - , 4'. NTA,NK,, "i1NFORWkTW01,
11-
11 IOW*9,jNNW &
Tank ID: Ti -87 1 Tank manifolded: NO Bottom to top fill in inches:
Product: UNLEADED Vent manifolded: YES Bottom to grade in inches:
Capacity in gallons: 14,976 Vapor recovery manifolded: YES Fill pipe length in inches:
Diameter in inches: 92.00 Overfill protection: YES Fill pipe diameter in inches: 4.0
Length in inches: 527 Overspill protection: YES Stage I vapor recovery: DUAL
Material: DW FIBERG Installed: ATG Stage 11 vapor recovery: ASSIST
CIP installed on:
COMMENTS
DANKTEST, RESQQT$ kT LEAK EST R
Star (in) End (in)
Dipped Water Level: Now/passed Failed/replaced New/passed Failed/replaced
Dipped Product Level: L.D. #1 L.D. #1 L.D. #2 L.D. #2
Probe Water Level: Make: vApoRLEss
Ingress Detected: Water Bubble Ullage Model: LD2000
Test time: S/N: 08041484
Open time in sec: 3.00
Inclinometer reading: Holding psi: 29
VacuTect Test Type: NOT
Resiliency cc: 140 NOT
VacuTect Probe Entry Point: TESTED
Test leak rate ml/m: 189.0 TESTED
Pressure Set Point: Metering psi: 18
Tank water level in inches: Calib. leak in gph: 3.00
Water table depth in inches: Results: PASS
Determined by (method):
Result:
COMMENTS
COMMENTS
Test
461147N. MW V
Material: DW FIBERG
Diameter (in): 2.0
Length (ft): 160.0
Test psi:
Bieedback cc:
Test time (min): NOT NOT NOT NOT
Start time: TESTED TESTED TESTED TESTED
End time:
Final gph:
Result:
Pump type: PRESSURE
Pump make: FE PETRO
COMMENTS Impact Valves Operational: UNKNOWN
Printed 02/23/2012 06:56
INDIVIDUAL
TEST DATE:01 /11/12
CLIENT:CIRCLE K STORES
TANK INFORMATION AND
p, Tanknology
8501 N MOPAC EXPRESSWAY, SUITE 400
AUSTIN, TEXAS 78759 (512) 451 -6334
TEST RESULTS
WORK ORDER NUMBER3189014
SITE:CIRCLE K 2701270
4 ce NKINFORMATION
Tank ID: T2 -91 2 Tank manifolded: NO Bottom to top fill in inches:
Product: PREMIUM Vent manifolded: YES Bottom to grade in inches:
Capacity in gallons: 11,849 Vapor recovery manifolded: YES Fill pipe length in inches:
Diameter in inches: 92.00 Overfill protection: YES Fill pipe diameter in inches: 4.0
Length in inches: 417 Overspill protection: YES Stage I vapor recovery: DUAL
Material: DW FIBERG Installed: ATG Stage II vapor recovery: ASSIST
CP installed on:
COMMENTS
TANK TEST RESULTSaTesP'MethOd VacuTec.t ` '` w
LEAK,,DETECTOR TESTRESU,L "TS "; ` Testxmethod`•FTA
Start (in) End (in)
Dipped Water Level: New /passed Failed /replaced New /passed Failed /replaced
Dipped Product Level:
L.D. #1 L.D. #1 L.D. #2 L.D. #2
Probe Water Level: Make: vAPoRLEss
Ingress Detected: Water Bubble Ullage Model: LD2000
Test time: S /N: 09111129
Open time in sec: 3.00
Inclinometer reading: Holding psi: 25
VacuTect Test Type: NOT
Resiliency cc: 120 NOT
VacuTect Probe Entry Point: TESTED
Test leak rate ml /m: 189.0 TESTED
Pressure Set Point: Metering psi: 19
Tank water level in inches: Calib. leak in gph: 3.00
Water table depth in inches: Results: PASS
Determined by (method):
Result: COMMENTS
COMMENTS
z LINE TESITTRESULTS z.Test type T, l
r i INEk vP` A- .A
Material: DW FIBERG
Diameter (in): 2.0
Length (ft): 160.0
Test psi:
Bleedback cc:
Test time (min): NOT NOT NOT NOT
Start time: TESTED TESTED TESTED TESTED
End time:
Final gph:
Result:
Pump type: PRESSURE
Pump make: FE PETRO
COMMENTS Impact Valves Operational: UNKNOWN
Printed 02/23/2012 06:56
MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State of California
Authority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3 Title 23, California Code of Regulations
This form must be used to document testing and servicing of monitoring equipment. If more than one monitoring system control panel Is installed at the facility, a separate
certification or report must be prepared for each monitoring system control panel by the technician who performs the work. A copy ofthis form must be provided to the tank
system owner /operator. The owner /operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date.
A. General Information
Facility Name: CIRCLE K 2701270
Site Address: 5634 STINE RD
City: BAKERSFIELD CA Zip: 93313
Contact Phone No: 834 -8625
Date of Testing /Service: 01/11/2012
Facility Contact Person: JOHN - MANAGER
Make /Model of Monitoring System:TLS 350 Work Order Number: 3189014
B. Inventory of Equipment Tested /Certifled
Check the appropriate boxes to indicate specific equipment inspected /serviced
Tank ID: T1 87 Tank ID: T2 91
X In -Tank Gauging Probe. Model: MAG PROBE X In -Tank Gauging Probe. Model: MAG PROBE
X Annular Space or Vault Sensor. Model: VR-409 Annular Space or Vault Sensor. Model: VR -409
X Piping Sumprrrench Sensor(s). Model: VR -208 Piping Sump/Trench Sensor(s). Model: VR -208
Fill Sump Sensor(s). Model: Fill Sump Sensor(s). Model:
x Mechanical Line Leak Detector. H Model: LD -2000 X Mechanical Line Leak Detector. Model: LD -2000
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
X Tank Overfill /High -Level Sensor. Model: PROBE /FLAPER Tank Overfill /High -Level Sensor. Model: PROBE /FLAPPER
Other (specify equipment type and model In Section E on page 2). Other (specify equipmentpfy type and model in Section E on page 2).
Tank ID: Tank ID:
In -Tank Gauging Probe. Model: In -Tank Gauging Probe. Model:
Annular Space orVault Sensor. Model: Annular Space or Vault Sensor. Model:
Piping Sump/Trench Sensogs). Model: Piping Sump/Trench Sensor(s). Model:
Fill Sump Sensogs). Model: Fill Sump Sensogs). Model:
Mechanical Line Leak Detector. Model: Mechanical Line Leak Detector. Model:
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
Tank Overfll /High -Level Sensor. Model: Tank Overfill /High -Level Sensor. Model:
Other (specify equipment type and model in Section E on page 2). Other (specify equipmentpty type and model in Section E on page 2).
Dispenser : 1 -2 Dispenser ID: 7 -8
Dispenser Containment Sensors) Model: 7 Dispenser Containment Sensors) Model:
X] Shear Valve(s). X Shear Valve(s)
IX Dispenser Containment Float(s) and Chain(s). X Dispenser Containment Float(s) and Chaln(s).
Dispenser ID: 3 -4 Dispenser ID:
0 Dispenser Containment Sensors) Model: Dispenser Containment Sensors). Model:
Shear Valve(s). Shear Valve(s).
X Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
Dispenser ID: 5 -6 Dispenser lD:
0 Dispenser Containment Sensors) Model: Dispenser Containment Sensor(s). Model:
rShear Valve(s). Shear Valve(s).
X Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification
I certify that the equipment identified in this document was inspected /serviced in accordance with the manufacturers' guidelines.
Attached to this certification is information (e.g manufacturers' checklists) necessary to verify that this information Is correct.
and a Site Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also attached
a copy of the (Check all that apply): X System set -up Xn Alarm history report
Technician Name (print): EDWIN PINEDA Signature: lv,
Certification No.: 8026748 -UT License. No.: 743160 (Class'A' General Enginering Contractor License)
Testing Company Name:Tanknology Phone No.: (800) 800 -4633
Site Address: 11000 N. MoPac Expressway, suite 500, Austin, TX 78759 Date of Testing /Servicing: 01/11/2012
Monitoring System Certification Page 1 of 3 Based on CA form dated 03/08
Site Address 5634 STINE RD
D. Results of Testing /Servicing
Software Version Installed: 328.03
Complete the following checklist:
Monitoring System Certification
Date of Testing /Service: 01/11/2012
F1 Yes No' Is the audible alarm operational?
Q Yes No . Is the visual alarm operational?
0 Yes No • Were all sensors visually Inspected, functionally tested, and confirmed operational?
Q Yes No Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not
interfere with their proper operation?
Yes No x N/A If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) operational?
x Yes No • NIA For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate positive
shut -down? (check all that apply) x SumpfTrench Sensors; Dispenser Containment Sensors.
Did you confirm positive shut -down due to leaks and sensor failure /disconnection? x Yes No
Yes O No' NIA For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e.: no mechanicaloverfillpreventionvalveisinstalled), is the overfill warning alarm visible and audible at the tank fill points(s) and operating
properly? If so, at what percent of tank capacity does the alarm trigger?
1-71 Yes* No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the
manufacturer name and model for all replacement parts in Section E, below.
Yes* fl No Was liquid found inside any secondary containment systems designed as dry systems? (check all that apply) Product;
Water. If yes, describe causes in Section E, below.
Qx Yes 1-1 No • Was monitoring system set -up reviewed to ensure proper settings? Attach set -up reports, if applicable.
x Yes F1 No • Is all monitoring equipment operational per manufacturers' specifications?
In Section E below, describe how and when these deficiences were or will be corrected.
E. Comments:
Replaced siphon het valve and adjusted lea etec or on t1 87
Page 2 of 3 Based on CA form dated 03/08
Monitoring System Certification
Site Address: 5634 STINE RD
F. In -Tank Gauging / SIR Equipment
Check this box if no tank gauging or SIR equipment is installed.
Date of Testing /Service: 01/11/2012
Check this box if tank gauging is used only for inventory control,
Check this box if no tank gauging or SIR equipment is installed.
This section must be completed if in -tank gauging equipment Is used to perform leak detection monitoring.
Complete the following checklist:
Yes No Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
Yes No Were all tank gauging probes visually inspected for damage and residue buildup?
El Yes No' Was accuracy of system product level readings tested?
IEYes No Was accuracy of system water level readings tested?
x yes No • Were all probes reinstalled properly?
Yes No Were all items on the equipment manufacturers' maintenance checklist completed?
In the Section H, below, describe how and when these deticiencies were or will be corrected.
G. Line Leak Detectors (LLD) : Check this box if LLDs are not installed.
Complete the following checklist:
Q Yes No' NIA
For equipment start -up or annual equipment certification, was a leak simulated to verify LLD performance?
Check all that apply) Simulated leak rate: x 3 g.p.h 0.1 g.p.h 0.2 g.p.h
x Yes No' Were all LLDs confirmed operational and accurate within regulatory requirements?
x Yes No Was the testing apparatus properly calibrated?
FR] Yes No ' NIA For mechanical LLDs, does the LLD restrict product Flow if it detects a leak?
Yes No' NIA For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak?
Yes No ' x NIA For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected?
Yes No ' Q NIA For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a test?
Yes No' 0 NIA For electronic LLDs, have all accessible wiring connections been visually Inspected?
ryn Yes No' Were all items on the equipment manufacturers' maintenance checklist completed?
In the Section H, below, describe how and when these deticiencies were or will be corrected.
H. Comments:
Page 3 of 3 Based on CA form dated 03/08
SWRCB, January 2002 Page 1 .
Secondary Containment Testing Report Form
Thisform is intendedfor use by contractors performing periodic testing of UST secondary containment systems. Use the
appropriate pages ofthisform to report resultsfor all components tested. The completedform, written test procedures, and
printouts from tests (ifapplicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: CIRCLE K 2701270 Date of Testing: 01/11/2012
Facility Address: 5634 STINE RD , BAKERSFIELD, CA, 93313
Facility Contact: JOHN - MANAGER Phone: (661) 834 -8625
Date Local Agency Was Notified of Testing:
Name of Local Agency Inspector (ifpresent during testing): Ernie Medina
2. TESTING CONTRACTOR INFORMATION
Company Name: TANKNOLOGY, INC.
Technician Conducting Test: EDWIN PINEDA
Credentials: CSLB Licensed Contractor SWRCB Licensed Tank Tester
License Type: A- UT I License Number: 743160-8026748
Manufacturer
Manufacturer Training
Component(s) Date Training Expires
OPW SPILL BUCKET 02/03/2013
Spill Box 2 PRE FILL 0000
3. SUMMARY OF TEST RESULTS
Component
Spill Box 2 PRE FILL 0000 00
000 00
MWMOM
000 00
0000 0
If hydrostatic testing was performed, describe what was done with the water after completion oftests:
WATER WAS PUT IN FIVE GALLON BUCKETS AND PLACE IN TRUCK FOR NEXT SITE
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
To the best ofmy knowledge, thefacts stated in this document are accurate and infull compliance with legal requirements
Technician's Signature: Date: 01/11/2012
SWRCB, January 2006
9. Spill Bucket Testing Report Form
Thisform is intendedfor use by contractors performing annual testing of UST spill containment structures. The completedform and
printouts from tests (if applicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: CIRCLE K 2701270 Date of Testing: 01/11/2012
Facility Address: 5634 STINE RD , BAKERSFIELD, CA, 93313
Facility Contact: JOHN - MANAGER Phone: ( 661) 834 -8625
Date Local Agency Was Notified of Testing:
Name of Local Agency Inspector (ifpresent during testing): Ernie Medina
2. TESTING CONTRACTOR INFORMATION
Company Name: TANKNOLOGY, INC.
Technician Conducting Test: EDWIN PINEDA
Credentials : CSLB Contractor a ICC Service Tech. SWRCB Tank Tester El Other (Spec) A- UT
License Number: 743160-8026748
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: El Hydrostatic Vacuum Other
Test Equipment Used: TAPE MEASURE Equipment Resolution: V I SUAL
Identify Spill Bucket By Tank
Number, Stored Product, etc.)
t 1 UNL FILL 2 2 PRE FILL 3 4
Bucket Installation Type:
X Direct Bury
Contained in Sump
X Direct Bury
Contained in Sump
Direct Bury
Contained in Sump
E] Direct Bury
Contained in Sump
Bucket Diameter: 12 " 12 "
Bucket Depth: 14 " 14 "
Wait time between applying
vacuum/water and starting test:
10 MIN 10 MIN
Test Start Time (TI ): 1320 1320
Initial Reading (RI ): 101, 101,
Test End Time (TF ): 1420 1420
Final Reading (RF ): 10" 10"
Test Duration: 1 HR 1 HR
Change in Reading (R F - Rt ): 0 0
Pass/Fail Threshold or
Criteria:
0 0
P F
Test Result, X Pass) `FailXPa'ss Fail E;ailPassAsFaitPeasAn
Comments - (include information on repairs madeprior to testing, and recommendedfollow -upforjailed tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements.
Technician's Signature: 1 n A, ` :,tL, Date: 01/11 /2012
1 Q++. 1...,,.......1 --r «,..0.7 1.., ........1:4:0.7 .... «/......t... U.... —'a, 1......1
Work Order: 3189014
ESO) k (ESV) Testing Foam - Vemion 1- 625nM7
Emergency Shut Off (ESO) &
Dispenser Emergency Shutoff Valve (ESV)
ANNUAL TEST RECORD LOCATIONS AND TEST DATA
Testing
Company: tl Date: olill Z
Location Name: 1 Q Z. Store #:
Y N
Statc ID #:
Address: 15 6TL1 51l tk City: State: C
Emergency Shut fl• SO Testing Results
On Ot in accordance with "ESO Vendor 1,etter (3- 21- 05).doc ", from Valero's Retail
Compliance Department, as a part of annual compliance testing, this representative tested the
Emeraencv Shut Off (ESO) switches indicated on this sketch. Findings listed below:
Emergency Shut Off (ESO) IfNo, Provide
Operational? Y N Maintenance Log # Date Called :
Dispenser Emergency Shutoff Valve (ESV)-Testine Results
On 1 in.accordance with NFPA 30A this representative tested the automatic - closing feature
of the ispenser Emergency Shutoff VALVE(S) (ESV) located in the supply lines at the base of each
individual island type dispenser indicated on the diagram below. Each device ( #) in all,
would automatically close. Findings listed below:
Disp. Emergency Shut Off IfNo, Provide
Valve (ESV) Operational? Y N Maintenance Log # Date Called
Site Map Oflocation and Plaoanentof Devices Tested:
C_dE
E3
6
8co
Sisnature Of Rearesentative: A Vly ",
Tanknology Inc. 11000 N. MoPac Expressway, Suite 500, Austin, Texas 78759
i TankrK*)gy
8501 N MOPAC EXPRESSWAY, SUITE 400
AUSTIN, TEXAS 78759
512) 451 -6334
FAX (512) 459 -1459
TEST DATE:01 /11/12 WORK ORDER NUMBEFG189014
CLIENT:CIRCLE K STORES SITE:CIRCLE K 2701270
COMMENTS
Conducted the Annual Monitor Certification Testing with Inspector Ernie Medina Bakersfield Fire
Department. Site contacted and e- mailed on 1/4/12 and confirmed with "URSHNA ". Veeder Root
light bulb was also replaced today as well. All tests passed, part and labor on separate w /o.
PARTS REPLACED
QUANTITY
a. ,
w „!" _ i F`! ^Y 'x•Y` 3 VIM
a DESCRIPTION <-
p, ' _
Ht:LIUM VINPUINI I t5 I KE5ULT5 (IF APPLICABLE)
Printed 02/23/2012 06:56 MTUTTLE
SITE DIAGRAM
r TanknokVy
8501 N MOPAC EXPRESSWAY, SUITE 400
AUSTIN, TEXAS 78759
512) 451 -6334
FAX (512) 459 -1459
TEST DATE: 01 /11/12 WORK ORDER NUMBER3189014
CLIENT:CIRCLE K STORES SITE: CIRCLE K 2701270
DUMP -
STER
1 CDm
ID8 #4
7 #3
CANOPY ESO
cas
VEN
6
5 # ; STP STP pv
zero
4
A A
8;7=
AIR/ v
E
F F wtk
Printed 02/23/2012 06:56 MTUTTLE
ATG Information
cl
110100
JAN 11, 2012 5:40 PM
CIRCLE K 2701270
5634 STINE RD.
BAKERSFIELD, CA
SYSTEM STATUS REPORT
ALL FUNCTIONS NORMAL
150301
JAN 11, 2012 5:40 PM
1:CIRCLE K 2701270
rl
150302
JAN 11, 2012 5:40 PM
2:5634 STINE RD.
150303
JAN 11, 2012 5:40 PM
3:13AKERSFIELD, CA
150304
JAN 11, 2012 5:40 PM
4:
151700
JAN 11, 2012 5:40 PM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
El
150F00
JAN 11, 2012 5:40 PM
MON DD YYYY HH:MM:SS xM
160100
JAN 11, 2012 5:40 PM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 UNL -REG ON
2 UNL -PREM ON
3 OFF
4 OFF
160200
JAN 11, 2012 5:40 PM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 UNL -REG
2 UNL -PREM
160300
JAN 11, 2012 5:40 PM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 UNL -REG A
2 UNL -PREM B
3 3
4 4
3189014
Work Order # 3189014
ATG Information
160400
JAN 11, 2012 5:40 PM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 UNL -R6G 14976
2 UNL- PFREM 11849
3 0
4 0
160700
JAN 11, 2012 5:40 PM
TANK DIAMI -TER
TANK PRODUCT LABEL INCHES
1 UNL -R6G 120.00
2 UNL -PREM 117.75
3 0.00
4 0.00
n
160900
JAN 11, 2012 5:40 PM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 UNL -RgG 0.000700
2 UNL -PF2EM 0.000700
3 0.000000
4 0.000000
161200
JAN 11, 2012 8:40 PM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 UNL -RE-G NONE NONE
2 UNL -PPEM NONE NONE
3 NONE NONE
4 NONE NONE
0
U
162100
JAN 11, 2012 5:40 PM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL -RFG 1084
2 UNL -PREM 900
3 0
4 0
a
162200
JAN 11, 2012 5:40 PM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL -REG 14227
2 UNL -PREM 11256
3 0
4 0
0
162300
JAN 11, 2012 5:40 PM
TANK OVEF;FILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL -RE -G 13478
2 UNL -PREM 10664
3 0
4 0
162400
JAN 11, 2012 5:40 PM
TANK HIGH WATER LEVEL LIMIT
3109014
Work Order # 3189014
ATG Information
Work Order # 3189014
TANK PRODUCT LABEL INCHES
1 UNL -REG 2.5
2 UNL -PREM 2.5
162800
JAN 11, 2012 5:40 PM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL -REG 14976
2 UNL•PREM 11849
162900
JAN 11, 2012 5:40 PM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL•REG 748
2 UNL•PREM 947
3 0
4 0
170300
JAN 11, 2012 5:40 PM
LIQUID TYPE
SENSOR LOCATION TYPE
1 87 ANNULAR TRI -STATE (SINGLE FLOAT)
2 87 TURBINE TRI -STATE (SINGLE FLOAT)
3 91 ANNULAR TRI -STATE (SINGLE FLOAT)
4 91 TURBINE TRI -STATE (SINGLE FLOAT)
5 TRI -STATE (SINGLE FLOAT)
6 TRI -STATE (SINGLE FLOAT)
7 TRI -STATE (SINGLE FLOAT)
8 TRI -STATE (SINGLE FLOAT)
190200
JAN 11, 2012 5:40 PM
SOFTWARE REVISION LEVEL
VERSION 328.03
SOFTWARE# 346328 -100 -D
CREATED - 08.06.06.17.21
S- MODULE# 330160 -004 -a
SYSTEM FEATURES:
PERIODIC IN -TANK TESTS
ANNUAL IN -TANK TESTS
ISO
120600
JAN 11, 2012 S:41 PM
CIRCLE K 2701270
5634 STINE RD.
BAKERSFIELD, CA
TANK ALARM HISTORY
TANK 1 UNL -REG
HIGH WATER ALARM JAN 11, 2012 3:35 PM
OVERFILL ALARM JAN 11, 2012 3:39 PM
JAN 11, 2012 3:36 PM
JUL 4, 2011 8:43 PM
LOW PRODUCTALARM JAN 11, 2012 3:32 PM
HIGH PRODUCT ALARM JAN 11, 2012 3:39 PM
JAN 11, 2012 3:35 PM
INVALID FUEL LEVEL JAN 11, 2012 3:32 PM
PROBE OUT JAN 11, 2012 3:41 PM
JAN 11, 2012 3:31 PM
JAN 11, 2012 1:13 PM
HIGH WATER WARNING JAN 11, 2012 3:35 PM
MAX PRODUCT ALARM JAN 11, 2012 3:39 PM
LOW TEMP WARNING JAN 11, 2012 3:42 PM
TANK 2 UNL-PREM
3189014
ATG Information
HIGH WATER ALARM JAN 11, 2012 3:55 PM
OVERFILL ALARM JAN 11, 2012 3:33 PM
LOW PRODUCT ALARM JAN 11, 2012 4:07 PM
JAN 11, 2012 3:31 PM
JAN 11, 2012 3:29 PM
HIGH PRODUCT ALARM JAN 11, 2012 3:35 PM
JAN 11, 2012 3:32 PM
INVALID FUEL LEVEL JAN 11, 2012 3:31 PM
PROBE OUT JAN 11, 2012 3:57 PM
JAN 11, 2012 3:29 PM
JAN 11, 2012 1:13 PM
HIGH WATER WARNING JAN 11, 2012 3:55 PM
DELIVERY NEEDED JAN 11, 2012 4:07 PM
JAN 11, 2012 3:31 PM
JAN 11, 2012 3:29 PM
MAX PRODUCT ALARM JAN 11, 2012 3:35 PM
130200
JAN 11, 2012 5:41 PM
CIRCLE K 2701270
5634 STINE RD.
BAKERSFIELD, CA
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 87 ANNULAR
JAN 11, 2012 1:13 PM SENSOR OUT ALARM
JAN 11, 2012 1:11 PM FUEL ALARM
2 87 TURBINE
JAN 11, 2012 1:13 PM SENSOR OUT ALARM
JAN 11, 2012 1:04 PM FUEL ALARM
3 91 ANNULAR
JAN 11, 2012 3:24 PM FUEL ALARM
JAN 11, 2012 1:13 PM SENSOR OUT ALARM
JAN 11, 2012 1:09 PM FUEL ALARM
4 91 TURBINE
JAN 11, 2012 1:13 PM SENSOR OUT ALARM
JAN 11, 2012 1:05 PM FUEL ALARM
110100
JAN 11, 2012 5:41 PM
CIRCLE K 2701270
5634 STINE RD.
BAKERSFIELD, CA
SYSTEM STATUS REPORT
ALL FUNCTIONS NORMAL
3189014
Work Order # 3189014