HomeMy WebLinkAboutFMC 2011MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State ofCalifornia
Authority Cited: Chapter 6 7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be
prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided
to the tank system owner /operator. The owner /operator must submit a copy of this form to the local agency regulating UST systems
within 30 days of this date.
A. General Information
Facility Name: Shell
Site Address: 4700 Coffee Road
Facility Contact Person: Matt Jeffries
Make /Model of Monitoring System: Gilbarco EMC
B. Inventory of Equipment Tested /Certified
Check the appropriate boxes to Indicate specific equipment Inspected /serviced:
City: Bakersfield
Bldg. No.:
Zip: 93308
Contact Phone No.: 661 -496 -7006
Date of Testing/Servicing: 8/30/2011
Tank ID: 10000 gal. Regular (North) Tank ID: 10000 gal. Regular (South)
X] In -Tank Gauging Probe. Model: 847390-107 x] In -Tank Gauging Probe. Model: 847390 -107
x] Annular Space or Vault Probe. Model: 794390-420 X] Annular Space or Vault Sensor. Model: 794390 -420
x] Piping Sump / Trench Sensor(s). Model: 794380-208 Piping Sump / Trench Sensor(s). Model: 794380 -208
X] Fill Sump Sensor(s) Model: 794380 -208 Fill Sump Sensor(s). Model: 794380 -208
J Mechanical Line Leak Detector. Model: FX1V x] Mechanical Line Leak Detector. Model: FX1V
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
U Tank Overfill / High Level Sensor. Model: OPW -61 -SO Tank Overfill / High Leval Sensor. Model: OPW -6I -SO
Other (specify equip. type and model in Sec. E on Pg. 2) Other (specify equip. type and model in Sec. E on Pg. 2)
Tank ID: 10000 gal. Super Tank ID: 10000 gal. Diesel
x] In -Tank Gauging Probe. Mode 1:847390 -107 x] In -Tank Gauging Probe. Model: 847390 -107
rxj Annular Space or Vault Sensor. Mode1:794390 -420 x] Annular Space or Vault Sensor. Model: 794390 -420
L] Piping Sump / Trench Sensor(s). Model: 794380-208 X] Piping Sump / Trench Sensor(s). Model: 794380 -208
x] Fill Sump Sensors(s). Model:794308- 208 X] Fill Sump Sensor(s). Model: 794380 -208
x_1 Mechanical Line Leak Decector. Model:FX1y x] Mechanical Line Leak Detector. Model: FX1DV
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
x] Tank Overfill / High Level Sensor. Model:OPW -6I -SO x] Tank Overfill / High Level Sensor. Model: OPW -6I -SO
Other (specify equip. type and model in Sec. E on Pg. 2) Other (specify equip. typs and model in Sec. E on Pg. 2)
Dispenser ID: 1 & 2 Dispenser ID: 3 8t 4
x] Dispenser Containment Sensor(s). Model: 794390 -420 X] Dispenser Containment Sensor(s). Model: 794390 -420
xl Shear Valve(s). X] Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s)
Dispenser ID: 6&6 Dispenser ID: 78,8
U Dispenser Containment Sensor(s). Model: 794390 - 420 x] Dispenser Containment Sensor(s). Model: 794390 -420
x] Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chains(s). Dispenser Containment Float(s) and Chain(s).
Dispenser ID: Dispenser ID:
Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s). Model:
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s) Dispenser Containment Float(s) and Chain(s).
If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification -1 certify that the equipment identified in this document was inspected /services in accordance with the
manufacturers' guidlines. Attached to this Certification is information (e.g. manufacturers' checklist) necessary to verify that
this information is correct and a plot plan showing the layout of monitoring equipment. For equipment capable of generating
such reports, 1 have attached a copy of the report; (check all that apply) x System Set -up Cx] Alarm history report
Technician Name (print): Krlstopher Karns Signature: ,O 6 t Ie....• -.
Certification No: 834106
Testing Company Name: Confidence UST Services, Inc.
Site Address: 4700 Coffee Road, Bakersfield, CA 93308
License No: 804904
Phone No: 800- 339 -9930
Date of Testing/Servicing: 8/30/2011
D. Results of Testing /Servicing
Software Version Installed: 329.00
Complete the following checklist:
Lx] Yes No* Is the audible alarm operational?
x Yes No* Is e Visua a arm operationa ?
x Yes No* Were all sensors visually inspected, functionally tested, and confirmed operational?
x I Yes No* Were all sensors installed at the lowest point of secondary containment and positioned so that other
equipment will not interfere with their proper operation?
Lj Yes No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) Hx N/A operational?
x Yes No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary
N/A containment monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes:
which sensors irritate positive shut -down? Lx] Sump/Trench Sensors [x] Dispenser Containment Sensors
Did you confirm positive shut -down due to leaks and sensor failure /disconnected'? [X] Yes; No;
Yes No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no
U N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visual and audible at
the tank fill point(s) and operating properly? If so, at what percent oftank capasity does the alarm
trigger? 61-SO %
Yes* No Was any monitoring equipment replaced? If Yes, identify specific sensors, probes, or other equipment
replaced and list the manufacturer name and model for all replacement parts in Section E, below.
Yes* U No Was liquid found inside any secondary containment systems designed as dry systems?
Product; Water. Ifyes, describe causes in Section E, below.
x N * Was monitoring system set -up reviewed to ensure proper settings? Attach set -up reports, if applicable.
LxJ Yes No* I Is all monitoring equipment operational per manufacturer's specifications?
In Section E below, describe how and when these deficiencies were or will be corrected.
E. Comments: Replaced the 8' goodyear hoses on Disp. #1 and #7.
F. In -Tank Guaging / SIR Equipment: Check this box if tank guaging is used only for inventory control.
Check this box if tank guaging or SIR equipment is installed.
This section must be completed if in -tank guaging equipment is used to perform leak detection monitoring.
Complete the following checklist:
U Yes No* Has all input wiring been inspected for proper enter and term ination,including testing for ground faults?
x Yes No* Were all tank guaging probes visually inspected for damage and residue buildup?
x Yes No* Was accuracy of system product level readings tested?
x Yes No* Was accuracy of system water level readings tested?
x Yes No* Were all probes reinstalled properly?
U Yes No* I Were all items on the equipment manufacturer's maintenance checklist completed?
In the Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD): Check this box if LLD's are not installed.
Complete the following checklist:
Lx] Yes No* For equip. start-up or annual equipment certification, was a leak simulated to varify LLD performance?
Check all that apply) Simulated leak rate: E3 g.p.h.: 0.1 g.p.h.; 0.2 g.p.h.;
x Yes No* Were all LLD's confirmed operational and accurate within regulatory requirments?
x Yes No Was the testing apparatus properly calibrated?
Yes No* For mac anica LLD's, does the LLD restrict product flow if it detects a leak?
N/A
Yes rj No* For electronic LLD's, does the turbine automatically shut off ifthe LLD detects a leak?
Lx] N/A
Yes No* For electronic LLD's, does the turbine automatically shut off if any portion of the monitoring system is
x] N/A disabled or disconnected?
Yes 7 No* For electronic LLD's, does the turbine automatically shut off if any portion of the monitoring system
X] N/A malfunction or fails a test?
F-1 Yes No* For electronic LLD's, have all accessible wiring connections been visually inspected?
U N/A
LxI Yes No Were all items on the equipment manufacturer's maintenance checklist completed?
In the section H, below, describe how and when these deficiencies were or will be corrected.
H. Comments:
BROONSIDE MARKET
4100 COFFIE RD
BAKERSFIELD CA 93308
661- 588 -1338
AUG 30, 2011 8- :48'AM
SYSTEM WA7'US REPORT
ALL FUNCTIONS NORMAL
INVENTORY REPORT
T I:UIESEL
VOLUME = 3548 GALS
ULLAGE - 6604 GALS
909 ULLAGE= 5588 BLS
TC VOLUME - 3542 GALS
HEIGHT - 36.45 11NCHE
WATER VOL - 0 GALS
WATER a 0,00 INCHES
TEMP 93.1 DEG F
T 2:.UNLEADED SOUTH
VOLUME - 656,1 GALS
ULLAGE = 3591 GALS
9M 'ULLAGE- 2575 GALS
TO VOLUME - 6454 GALS
HEIGHT - 58.97 INCHES
WATER VOL - 0 GAL-9
WATER - 0.00 INCHES
TEMP = 83.1 DEC F
T 3:UNLEADED NORTH
VOLUME 6861 GAYS
ULLACE - 3291 GALS
9M ULLAGE- 2275 GALS
TO VOLUME - 6750 GALS
HEIGHT = 61.27 INCHES
WATER VOL - 0 GALS
WETTER = G.00 INCHES
TEMP - 83.0 DEC F
T 4:SUPREME
VOLUME 7841 GALS
ULLAGE - Ml GALS
909 ULLAGE- 1295 GALS
TC VOLUME - 7682 GALS
HEIGHT - 69 ..07 INCHES
WATER VOL - 1-3 GALS
WATERER m 0,.80 INCHES
89..0 DEG F
X.9xxx END x?; -k 3N
SOFTWARE REVISION LEVEL
VERSION 39.00
SOFTWAREO 346399 -100 -A
C:P.EATED - 08. 10.09.17 ,'08
S- MODULEO 330160-004 -a
SYSTEM FEATURES:
PERIODIC IN -TANK TESTS
ANNUAL IN-TANK TESTS
ID
S5`YTEM SETUP
AUG 30. 2011 8:48 AM
SYSTEM UNITS
U.S..
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATElT- I ME FORMAT
MON DD YYY1' HH : MM : SS xM
BROOKSIDE.MARKET
4700 COFFIE RI) BAI:ERSF8- 1'IEL4 -CA 9330861 -58.338
SHIFT TIME 1 1:00 AM
SHIFT TIME 2 DISABLED
SHIFT TIME 3 DISABLED
SHIFT TIME 4 DISABLED
TANK PER TST NEEDED WRN
D:1,SABLED
TANK ANN TST NEEDED WRN
DISABLED
LINE RE- ENABLE METHOD
PASS LINE' TEST
LI.NE PER TST NEEDED WRN
DISABLED
LINE. 'ANN TST NEEDED WRN
D ISABL:ED
PRINT TC VOLUMES
ENABLED
TEMP cOMPENSATION
VALUE (1)EG, F ) . :. 60.0
SIICSCKKHEFGHT OFFSET
ULLAGE: 9OX
H- PROTOCOL,DATA FORMAT
HEIGHT
DAYLIGHT SAVING TIME
D1BABUD
RE- DIRECT LOCAL PRINTOUT
DISABLED
EURO PROTOCOL PREFIX
S
SYSTEM SECURITY - CODE : 000000
MAINTENANCE HISTORY
DISABLED
THSAB
CHART SECURITY
4USTOM ALARMS
DISABLED
3ERV.ICE ,NOTICE
DISABLED
ISO 3166 COU.NtRY
CODE:
MASSo,4ENSITY
DISABLED
COMMUNICATIONS SETUP
POaT SETTI NGS::
COMM BOARD : 3 '(ED.IM )
RS-202 SECUR LTY
CODE : DISABLED
COMM BOARD 5 (mom S
SAUD RATE 9600
PARITY NONE
STOP BI.T I STOP
DATA LENGTH: B DATA
R8 -232 SECURITY
CODE DISABLED
COMM BOARD 6 (RS -.232)
BAUD. RATE 9600
PARITY NONE
STOP BIT 1 STOP
DATA LENGTH 8 DATA
RS =232 SECURITY
CODE : DISABLED
AUTO TRANSMIT SETTINGS:
AUTO LEAK ALARM LIMIT
D.I SA8LED
AUTO .HIGH IJATEP. LIMIT
DISABLED
AUTO'OVERFIL'L LIMIT
AUTO LLO(4 PRODUCT
DFW. LED
AUTO THEFT LIMIT
D I SABL.ED
AUTO DELIVERY4TART
DI..SAIILED
AUTO' DEL [VERY END
DI S#1BLED.
AUTO EXTERNAL INPUT ON
DISABLED
AUTO EXTERNAL INPUT OFF
DISABLED..
AUTO: SENSOR FUEL AIARpt
DISABLED
AUTO. SENSOR WATER. ALARM
D L'SABLED
AUTO SEN66R OUT ALARM
DISABLED
RS-232 END OF MESSAGE
DISABLED
C,
I N -TANI: SETUP
T I:DIESEL
PRODUc* f CODE t
THERMAL COEFF :.000045
TANK DIAMETER 95.75
TANK PROFILE t PT
FULL VOL 10152'
FLOAT SIZE: :1.0 IN.
WATER. WARNING 2.0
HIGH WATER LIMIT: 3.0
MAX OR LABEL VOL: 10152
OVERFILL LIMIT 95%
TANK DIAMETER
9644
HIGH PRODUCT 95%
FULL VOL
9644
DELIVERY LIMIT 5%
MAX OR LABEL VOL:
507
LOW PRODUCT 500
LEAX ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 99
TANK TILT 0.90
PRONE OFFSET 0.00
SIPHON MANIFOLDED TANKS
Tit: NONE
L114E MANIFOLDED TANKS
Ti:: NONE
LEAK MIN PERIODI":: 04
0
LEAK MIN ANNUAL 17
101
PERIODIC TEST TYPE
OUI":
LIQUID SENSOR SETUP OUTPUT RELAY SETUP
T 4:SUPREME
PRODUCT CODE 4
THERMAL COEFF :.000700 L 1:REGULAR SOUTH R 1 : REC;ULAR SOUTH
TYPE: TAN)' DIAMETER 95.75 TRI -STATE (SINGLE FLOAT) STANDARDTANKPROFILEIPTCATEGORY : ANNULAR SPACE NORMALLY CLOSEDFULLVOL10152
TANK 9: 2
FLOAT SIZE: 4.0 1N. 1. 2:REGULAR SOUTH
WARNING 2.0
TR l - STATE (S I NGLE FLOAT)
CATEGORY : PIPING SUMP IJ- TAIJIC ALARMS
HIGH WATER LIMIT: 3.0 T 2:LOW PRODUCT ALARM
MAX OR LABEL VOL: 10152 L 3:REGULAR SOUTH LIQUID SENSOR ALMS
L 3:FUEL ALARMOVERFILLLIMIT95r. TRI .STATE (SINGLE FLOAT.) L13:FUEL ALARM9644CATEGORY : STP SUMP L14:FUEL ALARMHIGHPRODUCT95Y. L15:FUEL ALARM9654
DFL I VERY LIMIT 5% L 4 'REGULAR NORTH L16 : FUEL ALARM
L 2:SENSOR OUT ALARM507TR:.:' PATE (SINGLE FLOAT)
ANNULAR SPA(:E L 3:SENSOR OUT ALARM
LUW PRODUCT 5D0 L13:SENSOR OUT ALARM
L14 : SENSOR OUT ALARMLEAKALARMLIMIT: 99 L16:SENSOR OUT ALARMSUDDENLOSSLIMIT: 99
TANK TILT 2.30 L 5:REGULAR NORTH OUT ALARML16:
HIGHPROBEOFFSET0.00 TRI - STATE (SINGLE FLOAT) L 3:H1GH LIQUID ALARML
L13:H1GH LIQUID ALARMCATEGORY : PIPING SUMP L1.4:HIGH LIQUID ALARM
SIPHON MANIFOLDED TANKS L15:HIGH LIQUID ALARM
L16:HIGH LIQUID ALARMTO: NONE L 6:REGULAR NORTH
LINE MANIFOLDED TANK`; TRI -STATE (SINGLE FLOAT) ISD SITE ALARMSTO: NONE CATEGORY . STP SUMP ISD GROSS PRES FAIL
JSD DEGRD PRES FAIL
L.fAI; MIN PERIODIC: 0% L QPREME ISD VAPOR LEAK FAIL
ISD VP PRES FAIL0TRI -STATE (SINGLE FLOAT) ISD VF STATUS FA I LGATE( •')RY : ANNULAR SPACE
LEAK MIN ANNUAL l: ISD HOSE ALARMS101ALL:FLOW COLLECT FAIL
PERIODIC 'TEST TYPE
L B:SUPREME
TRI -STATE (SINGLE FLOAT) PMC ALARMS
VP EMISSIONS FAILU1C1: CATEGORY PIP 1 NG SL4 IP VP PRESSURE FAIL
ANNUAL TEST FAIL
ALARM DISABLED L 9:SUPREME R 2:REGULAR NORTH
TPI -STATE (SINGLE FLOAT) TYPE:
STANDARDRDPlayIUliIC: TEST FAIL CATEGORY ! STP SUMP NORMALLY CLOSEDALARMDISABLED
Gxo. :s TEST FAIL LIO:DIESEL TANK 0: 3
ALARM DISABLED TRI -STATE (SINGLE FLOAT)
CATEGORY ' ANNULAR SPACE IN -TANK ALARMSANN 'TEST AVERAGING: OFF T 3:LOW PRODUCT ALARMPERTESTAVERAGING: OFF
TANK TEST NOTIFY: OFF L11:DIESEL LIQUID SENSOR ALMS
L 6:FUEL ALARMTRI- -STATE (SINGLE FLOAT) L13:FUEL ALARMTNKTSTSIPHONBREAK:OFF CATEGORY : PIPING SUMP L14:FUEL ALARM
DELIVERY DELAY : 15 I °IIN L15:FUEL ALARM
L16:FUEL ALARMPUMPTHRESHOLD10.00% L12:DIESEL
TRI -STATE (SINGLE FLOAT) L 5:SENSOR OUT ALARM
CATECORY : STP SUMP L 6 :SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L14:SENSOR OUT ALARM
L13:D1SPENSER 1 -2 L15 :SENSOR OUT ALARM
TRI -STATE (SINGLE FLOAT) L16:SENSOR OUT ALARM
CATEGORY : DISPENSER PAN L 6:HIGH LIQUID ALARM
L13:HIGH LIQUID ALARM
L14:HIGH LIQUID ALARM
LI5:HIGH LIQUID ALARM
L14:DISPENSER 3 -4 ISD SITE ALARMSTRI - STATE iSINGLE FLOAT)
CATEGORY : DISPENSER PA14 ISD GROSS PRES FAILLE-A)'. TEST METHOD ISD DEGRD PRES FAIL
TEST QN I+;-:TE ALL 'TANK- ISD VAPOR LEAK FAIL
ISD VP PRES FAILOCT9. 20108
START '1'11"11" : DISABLED L15:DISPENSER 5 -6 ISD VP STATUS FAIL
TEST RATE :0.20 43AL /HR TRI -STATE (SINGLE FLOAT) ISD HOSE ALARMSDURATION2HOURSCATEGORY : DISPENSER PAN ALL:FLOW COLLECT FAIL
TST EHRL`; STOP :DISABLED PMC ALARMS
LEAK TEST REPORT FORMAT L1.6:D[SPENS}3R 7 -8 VP EMISSIONS FAIL
VP PRESSURE FAILNORMALTRI- STATE (SINGLE FLOAT)
CATEGORY : DISPENSER PAN
R,3:UPREME R 7:0.1 SP 5 -6 EVRZISD SETUPTYPE,.! , TYPE.:.
STANDARD STANDARD
NORMALLY CLOSED NORMALLY CLOSED
TANK 9: 4 TANK 0: NONE E"VR TYPE:' BALANCE
BALANCE NOZZLE TYPE
I N -TANK ALARIhG L.I QU ID ,SENSOR ALMS, VST
T 4: LOW PRODUCT ALARM L f'5::,F'UEL- ALARM c, ; VAPOR PROCESSOR T',FE
LIQUID SENSOR ALMS R a :dmi> 7--8 VST VAPOR PROCESSOR,
L 9:FUEL ALARM TYPE ". L13:FUEL ALARM
LJ•4:FUEL ALARM
STANDARD
NORMALLY CLOSED ANAL%iSIS TIMES
L15:FUEL ALARM t1ME:, 9,:00 AM
L18 : FUEL ALARM TANK' u : NONE DELAY M-1 NUM: 1
L•13:SENSOR OUT ALARM
L 44 : SENSOR OUT ALARML95: SENSOR OUT ALARM LI.OU LD :SENSOR ALMS ACCEPT HIGH ORVR :
L16:SENSOR OUT ALARM L..16 :FUEL ALARM DISABLED
ISD SITE ALARMS R 9; dSD HOSE TABLE
ID FP FL HL AA RRI•SD CROSS PRES FAIL T5'tyE : ISD OEGRD PRES FAIL STANDARD
011
01 01 - -02 01 ULI -- ISD V(\POR LEAK FAIL NORMALLY 'CL:OSED 02 02 02 02' 01 UUISDVPPRESFAIL03030302Q2UUISDVPSTATUSFAILTANK' 0: I-PNE OA 04 OA 02 02 UU
ISD ROSE Ai_ARMS 05 05 05 02 03 UU
06 04 06 02 03 UUALL:FLOW COLLECT FAIL IQUID:SENSOF ALItiS 07 07 d2' 04 UU
PMG ALARMS ALI:: FUEL. ALARM 0808 08 09 02 04 UU
VP EM1SSI.ONS FAIL RIO.:VST CONTROL OPENVPPRESSUREFAILTYPE: TSD AIRFLOW METER MAP
R 4:DIESEL VAPOR PROCESSOR
NOVAPOR CLOSED ID- SERIAL,NUM LABEL. -
y
TlPE:
STANDARD, NO . AL:ARIyI A I GNMSNTS' - 1', 28082 DISP .1--2 F
2 24,945 D I SP 3 -4• FNORMALLYCLOSED325313D1SP5 -E F
TANK 0: 1 R1'J`:VST CONTROL CLOSED 4.24957 D18P 7-8 F
TYPE:
tN -TANK ALARMS STANDARD
NORMALLY CLOSED fSD FUEL GRADE HOSE MAP
T -I :LOW PRODUCT ALARM Flp h1,HH MHH MHH MHH_AATANK0: NONE x'
201I. OU 1 D SENSOR ALMS 01 101 30d 9 U 1L_ 12 : FUEL ALARII 02 102. 302'202 9 U 11.1, 6:FUEL .ALARM I'N. -TANK ALARMS 03 104 :303 203 U U 2LI'I:SENSOR O.UT ALARM ALL:.OVERFILL ALARM 04 : 204 U U 2104304L12:SENSOR OUT ALARM ALL:HfGH•PRODUCT ALARM 05 105 305 205 U U 3L16:SENSOR OUT ALARM 06 1,06 306 206 U U. 3
ISD S l l ALARMS 07 1,07 .307 207 4 U '.4
19D GROSS PRES FAIL 08 108 308,208'4 U 4
ISD.DEGRD PRES FAIL
ISD VAPOR LEAK FAIL LABEL TAHLEISDVPPRESFAIL
ISD VP STATUS FAIL 1': UNASSIGNED -
R 5.: D I SP 1-2 2: BLEND3 , 3: REGULM' TYPE:
STANDARD MARTSEIVSOR SETUP 4:.M'[D' GRADE
PREMIUMNORMALLYCLOSED6: 6: GOLD
TANK 4: NONE n, s I_ :D.I.SP- 1• -2 FLOW METER 7' BRONZE
8; SILVERCATEGORYAIRFLLOW . METER 9.: BLEND2
L GU1D SENSOR ALMS s 2i1)1SP 3 -J. FLOW METER 10: BIEND4
L13:FUEL ALARM CATEGO9V AIR FLOW METERL !:SENSOR OUT ALARM
L 2:SENSOR OUT ALARM 5 3:DlSP 5- 6.FLOW METER.
CATEGORY AIR ;FLOW -METERR61: D 1 SIP 3 -4
TYPE: s 4:DISP 7 -8 FLOW METERSTANDARDCATEGORYAIRPLOW. METERNORMALLYCLOSED
s 7 :. PRESSURE SEry°SORTAWN : NONE CATEGORY VAPOR PRESSURE PMC` ,SETUP
LIOU1D SENSOR ALMS PMC VERSION: 01.04
L14:FUEL ALARM
ALL:SENSOR OUT ALARM VAPOR PROCESSOR TYPEVSTVAPORPROCESSOR
PROCESSOR CONTROL LEVEL:
FULL
MAX RUNT'11hE MINUTES: .30
014: Q . 200 •L NCwE
OFF': =0.200 INCHES
ALARM H1 S'fOR`! REPORT AU P.M HISTORY REPORT NLARI"l HISTORY REPORT
SENSOR ALARM - - - --
L I: P.EGULAP, SOUTH
ANNULAR SPACE
FUEL Aij Rw
AUG 19. 2010 10:17 AM
SENSOR OUT ALARM
AU1 :: 18, 2009 1 J : 32 AM
FUEL HLAkM
ALIG 18, 2009 10:55 AN
v '• . ,. v ENE x T > ..
ALARM HISTORY REPORT
I--.- SENSOR ALtyPM - - - --
L 3 : W-ULAR SOUTH
STP SUMP
FUEL ALARM
DEC 6. 2010 10:12 AM
FUEL ALARM
AUG 19. 2010 9:59 AM
SENSOR OUT ALARM
AUK; 18, 2009 11 :32 AI-I
r. -k END * x x x
ALARM III STORY REPORT
SENSOR ALARM - - - --
L 4:RE(-.:ULAR NORTH
ANNULAR SPACE
FUEL ALARM
AUG 19, 2010 10 :16 AM
E:NSOR OUT ALARM
Auc. 18. 2009 11:32 km
FUEL ALARM
AUK; 18, 2009 10:53 HM
ie k * x 3, CND C% ti :e t *
SENSOR ALARM - - - --
L 5:REGULAP. NORTH
PIPING SUMP
FUEL ALARM
AUG 19. 2010 10:11 HM
SENSOR OUT ALARM
AUG 18. 2009 11:32 AM
FUEL ALARM
AUG 18, 2009 10:16 "1
X A x x x END . . - .. . .
ALARM HISTORY REPORT
SENSOR ALARM --
L 6: REGULAR NORTH
STF SUMP
FUEL. ALARM
AUG J9. 2010 10:00 AM
SENSOR OW ALARM
AUG 18. 2009 11 :32 AM
FUEL ALARM
AUC 18. 2009 10:29 AM
t* 1< R x END q -i x r h
L- 2:P.ECULAR SOUTH
P 11.1 w. su1'IF
FUEL HJ.i.IRM
MAP. 10. 20 t 1 4:57 PM
FIJEI. NLApm
JAN 30. 2011 5:12 PP1
FUEL, ALARM
DEG 18. 2010 1 :55 PM
I--.- SENSOR ALtyPM - - - --
L 3 : W-ULAR SOUTH
STP SUMP
FUEL ALARM
DEC 6. 2010 10:12 AM
FUEL ALARM
AUG 19. 2010 9:59 AM
SENSOR OUT ALARM
AUK; 18, 2009 11 :32 AI-I
r. -k END * x x x
ALARM III STORY REPORT
SENSOR ALARM - - - --
L 4:RE(-.:ULAR NORTH
ANNULAR SPACE
FUEL ALARM
AUG 19, 2010 10 :16 AM
E:NSOR OUT ALARM
Auc. 18. 2009 11:32 km
FUEL ALARM
AUK; 18, 2009 10:53 HM
ie k * x 3, CND C% ti :e t *
SENSOR ALARM - - - --
L 5:REGULAP. NORTH
PIPING SUMP
FUEL ALARM
AUG 19. 2010 10:11 HM
SENSOR OUT ALARM
AUG 18. 2009 11:32 AM
FUEL ALARM
AUG 18, 2009 10:16 "1
X A x x x END . . - .. . .
ALARM HISTORY REPORT
SENSOR ALARM --
L 6: REGULAR NORTH
STF SUMP
FUEL. ALARM
AUG J9. 2010 10:00 AM
SENSOR OW ALARM
AUG 18. 2009 11 :32 AM
FUEL ALARM
AUC 18. 2009 10:29 AM
t* 1< R x END q -i x r h
ALARM HISTORY REPORT ALARM HISTORY REPORT ALARM HISTORY REPORT
SEN.SftR ALARM - - ---
L 9:SUPREME
ANNULAR SPACE
FUEL ALARM
AUG 19. 2010 IU :15 AM .
SEPISOR OUT ALARM
AUG I8. 2009 11:32 AM
FUEL ALARM
AlIG 18. 2009 10:5! AN
r. t A A X END :t x k x%
ALARM HI S1'ORY REPORT
SENSOR ALARM - - -- L $ : SUPREME
PIPING SUMP
FUEL ALARM
MAR 20 • 2011 5:19 Pi °1
FUEL ALARM
DEC 19. 2010 3 :32 AM
FUEL ALARM
AUG 19. 2010 10:13 AM
y t} v• E1111 h• .. n
SENSOR ALARM -- --
1_ 9,SUPREME
STP SL"P
FUEL ALARM
SEP 24, 2010 8:35 AM
SENSOR OUT ALARM
AUG 19. 2010 10:23 AM
FUEL ALARM
AUG 19, 2010 10:00 AM
A A END k •r. x s x
ALARM H1STOPY REPORT
SEW30R ALARM
L10:0113S£L
ANNULAR SPACE
SENSOR OUT ALARM
AUG 19. 2010 10 :23 AM
FUEL Al-ARM
AUG 19, 2010 10:18 All
SEhEOR OUT ALARM
AUG 18, 2009 12:03 PM
u t} r. X END s A N k
SENSOR AL V;51 -
LII:AIESEL
PIPING SUIlp
FUEL ALARM
JUN 24, 2011 11:30 AN
FUEL ALARM
DEC 18. 2010 6:53 PM
SENSOR OUT ALARM
AUG 19. 2010 10:23 AM
v END k e
ALARM HISTORY REPORT
SENSOR ALARM --
L12:DIESEL
STP "P
FUEL ALARM
MAR 23. 2011 12:31 F11
FUEL. ALARM
DEC 16. 6,010 4 :10 PM
SENSOR OUT ALARM
AUG 19, 2010 10 :23 AM
4 END .:xxxm
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L I 0 : 111 SPENSER 1-2
DISPENSER PAN
SENSOR OUT ALARM
AUG 19. 2010 10:23 All
FUEL. ALARM
AUG 19, 2010 10:01 AM
FUEL ALARM
AUG 19. 2010 9:46 AM
t L . t END -i . i x
ALARM HISTORY REPORT
SENSOR ALARM - -- -
L14:DISPENSER 3 -4
DISPENSER PAN
SENOR OU'f ALARM
AUC: 19. 2010 10:23 W
FUEL ALARM
AIJG 19. 2010 10 :02 All
FUEL. ALARM
RUG 19. 2010 9:45 (4111
w x 0: END _. .. .. x i
ALARIII HISTORY REPORT
SENSOR ALARM - -- -
L.. 15 : D I SPENSER 5 -6
DISPENSER PAN
SENSOR OUT ALARM
AUG 19, 2010 10:23 All
FUEL ALARM
AUG 19, 2010 10:02 AM
FUEL ALARM
AUG 19. 2010 9:43 A1'1
v e r t T END 1* A n >`
ALARM HISTORY REPORT
SENSOR - - - --
L16:DISPENSEI•: ' / -i:
DISPENSER F'F,N
SENSOR OUT ALARM
AUG Iy. 2010 10 :23 AM
FUEL ALARM
AUG 19, 2010 10 :03 HM
FLIEL ALARM
AUG 19, 2010 9:40 A( °I
tAI•rx END AxA• x
SENSOR ALARM - - - --
L 9:SUPREME
STP SUMP
FUEL ALARM
AUG 30, 2011 9:10 AM
SENSOR ALARM - - - --
1. b:REGULAR NORTH
STP SUMP
FUEL. ALARM
AUG 30. 2011 9:10 AM
0
SENSOR ALARM - - - --
L 3:REGULAR SOUTH
STP SUMP
FUEL ALARM
AUG 30, 2011 9 :11 All
SENSOR mLARM
LIF:DIESEL
STP SUMP
FUEL ALARM
AUG 30. 2011 9:12 #V l
SENSOR ALARhI - - --
1-13 :13ISPENSER 1 -2
DISPENSER PAN
FUEL ALARM
AUG 30. 2011 9:13 AM
SENSOR ALARM - - - --
1.111'DISPENSER 3 -4
D I I NFOISER PAN
FUEL ALARM
AUG ,jU, 201) 9:14 All
SENSOR ALARM - - - --
1.1 5 : E' 1SPENSER 5-6
DISPENSER PAN
FUEL_ ALARM
AUG 30. 2011 9:16 AM
SENSOR ALARM - - - --
1-16 :1DISPENSER 7 -8
DISPENSER PAN
FUEL ALARM
A00 30 • '2011 9:18 AM
r-h12CR ALARH
L 7 ::SUPREME
ANNULAR SPACE
FUEL ALARM
AUG 30. 2011 9 :19 AM
SENSOR ALARM - - - --
1. I : REGULAR SOUTH
ANNULAR SPA,--'E
FUEL ALARM
AUG: 30. 2011 9:20 NM
S;ENSOR ALARM - -- -
L ,l : REGULAR NORTH
ANNUIJiR SPACE
FUEL. AI.ARM
AUG 30, 2011 9:20 AIM
SENSOR ALARf'I - - --
L10:DIEyEI-
ANNIiLAR SPACE
FUEL ALARM
AUG 30. 2011 9:20 Ahl
BROO1;S I DE MARKET
4700 COFFIE RD
BAKER.SFIELD CA 93308
661 - 588 -1338
AUG 30, 2011 9:21 AM
svgrEhl STATUS REPORT
L 1 : FUEI. ALARM
L 3:FUEL ALARM
L 4: FUEL ALARM
L E.: FUEL ALARM
L 7:FUEL ALARM
L 9:FUEL ALARM
L 1 O : FUEL ALARM
1.12:FUEL ALARM
L13:FUEL ALARM
L14:FUEL ALARM
L)5:FUEL ALARM
I_ i E.: FUEL AbL011
INVENTOR' REPORT
T ):DIESEL
VOLUME = 3543 GALS
ULLAGE = 6609 GALS
90% ULLAGE= 5593 GALS
TC VOLUME - 3537 GALS
HEIGHT = 36.41 1NCHES
WATER VOL = 0 GALS
WATER = 0.00 INCHES
TEMP - 93.1 DEG F
T 2:UNLEADED SOUTH
VOLUME - 6547 GALS
ULLAGE - 3605 GALS
90:> ULLAGE= 2589 GALS
TC VOLUME = 6440 GALS
HEIGHT - 58.87 INCHES
WATER VOL = 0 GALS
WATER = 0.00 1NCHES
TEMP - 83.1 DEC F
T 3: UNLEADED NORTH
VOLUME = 6860 GALS
ULLAGE - 3292 GALS
90: ULLAGE= 2276 GALS
TC VOLUME = 6749 GALS
HEIGHT = 61.27 INCHES
WATER VOL - 0 GALS
WATER = 0.00 INCHES
TEMP = 83.0 DEG F
T 4 : SUF'REhIE
VOLUME 7838 GALS
ULLAGE - 2314 GALS
90% ULLAGE= 1298 GALS
TC VOLUME - 7678 GALS
HEIGHT - 69.04 INCHES
WATER VOL = 13 GALS
WATER = 0.82 INCHEC3
TEMP m 89.0 DE(; F
xx',iX END y u *t
SEI SOF ALARM -- --
L 2:REGULAR SOUTH
PIPING SUMP
FUEL ALARM
AUG 30, 2011 9:24 AM
S1: NF.;OR ALARf1
L 5:PEGULAR NORTH
pIPING SUMP
FUEL ALARM ti:25 AUG; 30. 2011
f EN'oOR ALARM -- -'-
L S:t:UPREME
PIPING SUMP
FUEL ALARM
AUG 30. 2011 9:25 AM
SENSOR ALAR"'
L1I :DIESEL.
PIP11,IG FI
FUELF
AUG 30, 3011 9 :2t• P41
BROOICSIDE MARKET '-'-' SENSOR ALARM - - - --
4700 COME RD L 9:SUPREME
BAKERSFIELD CA 93308 STP SUMP
661 -588 -1338 SENOR OUT ALARM
AUG 30. 2011 9:32 AM
AUG 30. 2011 9:26 HM
SYSTEM STATUS REPORT
ALL FUNCTIONS NORMAL
INVENTORY REPORT SENSOR ALAP111 - - - --
SENSOR ALARM --
ULLAGE
L 6:REGULAR NORTH
T I:DIE56L
90% ULLAGE o
STP SUMP
VOLUME = 3544 GALS SENSOR OUT ALARM
ULLAGE o 6608 GALS AUG 30. 2011 9:32 HM
90% ULLAGE- 5592 GALS
0.00 INCHES
TC VOLUME = 3538 GALS
83.1 DEG F
HEIGHT = 36.41 INCHES
INCHES
WATER VOL = 0 GALS
0
0.00
WATER = 0.00 INCHES
TEMP
TEMP o 93.1 DEC F
L 2:REGULAR SOUTH
T ":UNLEADED
VOLUME o
SOUI'H
6548 CAI-S SENSOR ALARM --
ULLAGE 3604 GAL.. L 7:
SUSENSO
90% ULLAGE o 588 GALS ANNULAR SPACE
SENSOR OUT ALARMALARMTCVOLUMEo
HEIGHT Q
6441 GALS
58.87 INCHES AUG 30 2011 AM
WATER VOL o 0 GALS
PIPING SUMPMPALA
WATER . 0.00 INCHES
U ALARM RM
TEF1P Q 83.1 DEG F
AUG 30. 2011 AM
T 3:uNLEADED NORTH
VOLUME = 6861 GALS
ULLAGE a 3291 GALS
7843
90% ULLAGE- 2275 GALS SENSOR ALARM -- ' TC VOLUME a 6750 GALS L B :SUPREMEHEIGHTa61.28 1NCHES PIPING SUMP MPALA41ATERVOL =
WATER a
0 GAL.„'
0.00 INCHES U ALARMRM
83.0 DEG F AUG 30. 2011 AM
T 4:SUPREME
VOLUME = 7843 GALS
ULLAGE o 2309 GALS
9(r4 ULLAGE- t293 GALS
TC VOLUME = 7683 GALS
HEIGHT ' = 69.09 INCHES
WATER VOL =
WATER =
0
0.00
GALS
INCHES SENSOR ALARM --
TEMP 89.0 DEC: F L 2:REGULAR SOUTH
PIP[ 14G SUMP
SEN30R OUT ALARM
t ENDR_e A(K:30. 2011 9:32 AM
SENSOR ALARM - - - --
L10:D1ESEL
SENSOR ALARM - -- ANNULAR. SPACE
L 5:REGULAR NORTH SENSOR OUT ALARM
PIPING SUMP AUG 30. 2011 9:32 AM
SENSOR OUT ALARM
AUG 30. 2011 9:32 HM
SENSOR ALARM - - - --
L1.3:DISPENSER 1 -2
SENSOR ALARM - - -- DISPENSER ;PAN
L ):REGULAR SOUTH SENOR OUT ALARP1
A14NUI -AR SPACE AUG 30, 2011 9 :32 IAM
SENSOR. OUT ALARM
AUG 30.. 2011 9:32 Al-I
1-
SENSOR ALARM - - - -_
L 3:REC:ULAR SOUTH
STP SUMP
SENSOR OUT ALARM
AUG 30. 2011 9:32 AM
BROOYS 1DE MARKET
4700 COFFIE RD
WERSFIELD CA 93300
661- 588 -1338
AUG 0. 2011 9:33 Ail
SENSOR ALARM - - - -- SYSTEM STATUS'REPORTLCREGULARNORTH
ANNULAR SPACE ALL FUNCTIONS NORMALSENSOROUTALARM
AUG 30. 2011 9:32 AM INVENTORY REPORT
T l:D1ESEL
VOLUME = 3541 GALS
ULLA13E = 6611 GALS
90% ULLAGE= 5595 GALS
TC VOLUME = 3535 GALS
HEIGHT - 36.39 1140HES
WATER VOL - 0 GALS
SENSOR ALARM - - - -- WATER = 0.00 INCHESLII:UIEN TEMP = 93.1 DECDEG FPIPINGSUMP
SENSOR OUT ALARM
AUG 30. 2011 9:32 Art T 2: UNLEADED SOUTH
VOLUME = 6547 GALS
ULLAGE - 3605 GALS
90% ULLAGE- 2589 GALS
TG VOLUME = 6441 GALS
HEIGHT - 58.87 INCHES
WATER VOL - 0 GALS
WATER a 0.00 INCHES
TEMP - 83.1 DEG F
SENSOR ALARM - - - --
L12:DIESEL T 3:UNLEADED NORTH
STP SUMP VOLUME - 6861 GALSSENSOROUTALARMULLAGE - 3291 GALSAUG30. 2011 9:32 AM 90%. ULLAGE = 2275 GALS
TG' VOLUME - 6750 GALS
HEIGHT - 61.27 INCHES
WATER VOL - 0 GALS
WATER = 0.00 INCHES
TEMP - 83.0 DEG F
T 4:SUPREME
VOLUME - 7840 GALSSEPP.30k ALARM - - - -- ULLAGE - 2312 GALSL14:DISPENSER 3 -4 90% ULLAGE- 1296 GALSDISPENSERPANTCVOLUME = 7680 GALSSENSOROUTALARMHEIGHT - 69.06 INCHESAUG30, 2011 9:32 AM WATER VOL - 0 GALS
WATER = 0.00 INCHES
TEMP = , 89.0 DEG F
xxW END ;sXAA
SENSOR ALARM
L15:DISPENSER 5 -6
DISPENSER PAN
SENSOR OUT ALARM
AUG 30. 2011 9:32 AM
SEIkSOR ALARM
L16:D1SPENSER 7 -8
DISPENSER PAN
SENSOR OUT ALARM
ALr, 30. 201;1 9:32 AM
SWRCB, January 2006
Spill Bucket Testing Report Form
Thisform is intendedfor use by contractors performing annual testing ofUST spill containment structures. The completedform and
printoutsfrom tests (ifapplicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: Shell I Date ofTesting: 8/30/2011
Facility Address: 4700 Coffee Road, Bakersfield, CA 93308
Facility Contact: Matt Jeffries I Phone: 661 - 496 -7006
Date Local Agency Was Notified of Testing: 7/26/2011
Name of Local Agency Inspector (ifpresent during testing): Ester Duran
2. TESTING CONTRACTOR INFORMATION
Company Name: Confidence UST Services, Inc.
Technician Conducting Test: Kristopher Karns
Credentials: X CSLB Contractor X ICC Service Tech. X SWRCB Tank Tester Other (Specify)
License Number(s): CSLB: 804904 ICC: 5264406 -UT SWRCB# 09 -1743
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: X Hydrostatic Vacuum Other
Test Equipment Used: Lake Test Equipment Resolution: 0.0625"
Identify Spill Bucket (By Tank
Number, Stored Product, etc.)
1 Regular (North) 1-i—Regular South) 3 Super 4 Diesel
Bucket Installation Type: Direct Bury
X Contained in Sump
Direct Bury
X Contained in Sump
Direct Bury
X Contained in Sump
Direct Bury
X Contained in Sum
Bucket Diameter: 12.00" 12.00" 12.00" 12.00"
Bucket Depth: 12.50" 13.00" 13.50" 13.00"
Wait time between applying
vacuum /water and start of test:
5 min. 5 min. 5 min. 5 min.
Test Start Time (Ti): 9:00 AM 9:00 AM 9:00 AM 9:00 AM
Initial Reading (Ri): 10.00" 10.50" 10.50" 10.25"
Test End Time (TO: 10:00 AM 10:00 AM 10:00 AM 10:00 AM
Final Reading (RF): 10.00" 10.50" 10.50" 10.25"
Test Duration (TF - Tj): 1 hour 1 hour 1 hour 1 hour
Change in Reading (RF - Rj): 0.00" 0.00" 0.00" 0.00"
Pass/Fail Threshold or
Criteria: 0.0625" 0.0625" 0.0625" 0.0625"
Test Result: X Pass Fail X Pass Fail X Pass Fail X Pass Fail
Comments - (include information on repairs made prior to testing, and recommendedfollow -up forfailed tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements.
Technician's Signature: Date: 8/30/2011
State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
G0#FtDRact'
UST
Cam[Awa ,,,.,00,10,0CMr. Invoice No.. 27356
Site: Shell
4700 Coffee Road
Bakersfield, CA 93308
Repairs Requested: Replace 8' Goodyear hoses on dispenser #1,
and #7 due to the old hoses being ripped.
Repairs completed: I replaced the 8' Goodyear hoses on #1, and
7 due to old hoses being ripped. Once the new hoses were installed
they were tested for proper operation.
Required Repairs, Still Pending: No further repairs are required.
Technician Name: Kristopher Karns
Signature: 41;Z
Date: 8/30/2011
1= Veeder Root TLS 350
2= Emergency Shut Off Switch
3= Veeder Root ATG Probe
4= Veeder Root 208 Sump Sensor
5= Veeder Root 420 Annular Sensor
6= Veeder Root 420 Dispenser Sen.
7= Red Jacket FX1 V LLD
8= Red Jacket FX1 DV LLD
9= 10000 Gallon Regular North STP
10= 10000 Gallon Reg South STP
11= 10000 Gallon Super STP
12= 10000 Gallon Diesel STP
13= Regular North Fill Sump
14= Regular South Fill Sump
15= Super Fill Sump
16= Diesel Fill Sump
3,4,7,11
0
4,15
O
She[
4700 Coffee Road
Bakersfield,CA 93308
8/30/2011
2 4 * 6 * v
3,4,7,9 3,4,7,1 3,4,8,1 2
4,13 4,14 4,16
O O O
1