Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 10/2512011 System Riser ID: 7377
Property Information:
Frequency Description
Type Of System: F Cq
Name: Barber Honda Wet Pipe
Address: 4500 Wible Road
A
or
Dry Pipe v 0
1
Preaction
Preaction /Deluge Valves - Enclosure
temperature
j
Deluge EMp
City: Bakersfield
X
Main Drain Test Results:
Initial Static Pressure: (psi)
Residual Pressure: (psi)
Restored Static Pressure: (psi)
Abbreviation Key:
I = Inspection
T =Test
M = Maintenance
A -O = After Operation
MI = Per Manufacturer's Instructions
Item Activity Frequency Description NFPA 25
Reference Fail N/A Pass
1.1 1 Daily
Weekly
Preaction /Deluge Valves - Enclosure
temperature
12.4.3.1 X
1.2 1 Daily
WeekIv
Dry Pipe Valves - Enclosure
temperature
12.4.4.1.1 X
1.3 1 Quarterly Gauges - (Dry, Preaction, Deluge
S stems )
5.2.4.2
5.2.4.3 X
1.4 1 Quarterly Control Valves 12.3.2.1 X
1.5 1 Quarterly Alarm Devices 5.2.6 X
1.6 1 Quarterly Gauges (Wet Pipe Systems) 5.2.4.1 X
1.7 1 Quarterly Hydraulic nameplate 5.2.7 X
1.8 1 Quarterly Pipe and Fittings 5.2.2 X
1.9 1 Quarterly Sprinklers 5.2.1 X
1.10 1 Quarterly Spare Sprinklers 5.2.1.3 X
1.11 1 Quarterly Fire Department Connections 12.7.1 X
1.12 1 Quarterly Alarm Valves - Exterior Inspection 12.4.1.1 X
1.13 I Quarterly Preaction /Deluge Valves - Exterior
Inspection 12.4.3.1.6 X
1.14 1 Quarterly Pressure Reducing Valves 12.5.1.1 X
1.15 1 Quarterly Dry Pipe Valves- Exterior Inspection 12.4.4.1.4 X
1.16 1 Quarterly Backflow Preventers 12.6.1 X
1.17 1 Annual Buildings 5.2.5 X
State Fire Marshal AES 2 March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 1 of 6
ANNEX B
Item
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended b CCR Title 19
Frequency
Date Of Inspection, Testing, Maintenance: 10/25/2011 System Riser ID: 7377
Fail
Property Information:
Pass
Type Of System:
1
Name: Barber Honda
Hangers 5.2.3
A1r°O
X
Q Wet Pipe v .
Address: _4500 Wible Road Dry Pipe y
X
Preaction
Deluge ARE MP
City: Bakersfield
Hangers (Accessible concealed spaces) 5.2.3.3
Item Activity Frequency Description
NFPA 25
Reference Fail N/A Pass
1.18 1 Annually Hangers 5.2.3 X
1.19 1 Annually Seismic Braces 5.2.3 X
1.20 1 5 Years Hangers (Accessible concealed spaces) 5.2.3.3 X
1.21 1 5 Years Seismic Braces (Accessible concealed
spaces)
5.2.3.3 X
1.22 1 5 Years Pipe and Fittings (Accessible concealed
spaces)
5.2.2.3 X
1.23 I 5 Years Sprinklers (Accessible concealed spaces) 5.2.1.1.4 X
1.24 1 5 Years Alarm Valves - Interior Inspection 12.4.1.2 X
1.25 1 5 Years Alarm Valves - Strainers, filters, orifices 12.4.1.2 X
1.26 1 5 Years Check Valves - Interior Inspection 12.4.2.1 X
1.27 1 5 Years Preaction /Deluge Valves - Interior
Inspection 12.4.3.1.7 X
1.28 I 5 Years Preaction/Delugeuge - trainers,
filters, orifices 12.4.3.1.8 X
1.29 1 5 Years Dry Pipe Valves - Interior Inspection 12.4.4.1.5 X
1.30 1 5 Years Dry Pipe Valves - Strainers, filters, orifices 12.4.4.1.6 X
2.1 T Annually Alarm Devices (90 Sec) 5.3.3
12.2.7 X
2.2 T Annually Main Drain Test (Enter data on Page 1)
12.2.6
12.2.6.1
12.3.3.4
X
2.3 T Annually Antifreeze Test 5.3.4 X
2.4 T Annually Control Valve - Position 12.3.3.1 X
2.5 T Annually Control Valve - Operation 12.3.3.1 X
2.6 T Annually Supervisory 12.3.3.5 X
2.7 T Annually Preaction Valve - Priming Water 12.4.3.2.1 X
2.8 T Annually Preaction Valve - Low Air Pressure Alarm 12.4.3.2.10 X
2.9 T Annually Preaction Valve - Full Flow Trip Test 12.4.3.2.2 X
State Fire Marshal AES 2 March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 2 of 6
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended b CCR Title 19
Date Of Inspection, Testing, Maintenance: 10/25/2011
Property Information:
Name: Barber Honda
Address: 4500 Wible Road
City: Bakersfield
System Riser ID: 7377
Type Of System: op Cq4,,
Wet Pipe ;P
Dry Pipe co
Preaction I
DelugeeMp'.
Item Activity Frequency Description
NFPA 25
Reference Fail N/A Pass
2.10 T Annually Dry Pipe Valve - Priming Water 12.4.4.2.1 X
2.11 T Annuallyy ry Pipe Valve - Low Air Pressure
Alarm 12.4.4.2.6 X
2.12 T Annuallyy ry Pipe Valve - Quick- Opening
Device 12.4.4.2.4 X
2.13 T Annually Dry Pipe Valve - Trip Test 12.4.4.2.2 X
2.14 T Annually Backflow Preventor Assemblies 12.6.2 X
2.15 T 3 Years Dry Pipe Valve - Full Flow Trip Test 12.4.4.2.2.2 X
2.16 T 5 Years Gauges 5.3.2 X
2.17 T 5 Years Pressure Reducing Valve 12.5.1.2 X
2.18 T 5 Years Fire Department Connection Backflush 12.7.4 X
2.19 T 5 Years Sprinklers - Extra High Temperature 5.3.1.1.1.3 X
2.20 T 5 Years Sprinklers - Corrosive environment or
corrosive water
5.3.1.1.2 X
2.21 T 10 Years Sprinklers - Dry 5.3.1.1.1.5 X
2.22 T 20 Years Sprinklers - Fast Response 5.3.1.1.1.2 X
2,23 T 50 Years Sprinklers 5.3.1.1.1 X
2,24 T 75 Years Sprinklers 75 years in service 5.3.1.1.1.4 X
2.25 T Sprinklers manufactured prior to 1920
Replace
5.3.1.1.1.1 X
3.1 M Annually Control Valves 12.3.4 X
3.2 M Annually Preaction /Deluge Valves 12.4.3.3.2 X
3.3 M Annually Dry Pipe Valves /Quick- Opening
Devices 12.4.4.3.2 X
3.4 M Annually Dry Pipe Valve - Low Point Drains 12.4.4.3.3 X
3.5 M 5 Years Obstruction Investigation Chapter 13 X
State Fire Marshal AES 2 March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 3 of 6
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 10/25/2011
Property Information:
Name: Barber Honda
Address: 4500 Wible Road
City: Bakersfield
System Riser ID: 7377
Type Of System:
Wet Pipe
pF CAL0x . ,Qy
Dry Pipe (4 -
v
Preaction
71.
Deluge %
Item
Deficiencies and Comments:
Deficiencies and Comments Item number must correspond to the Item number
of the activity listed above:
1.9 Need to add argo chrome escutcheons in the following areas. 1 in oil room,south electrical room, near Dustin Kryger
desk, one near Erma in service,one in file room in general office, one in Steve Ekergen office, one southwest
overhang and five in show room floor.
Need to raise two and lower one head in show room floor.
service waiting room janitors clost in mens restroom need to raise one head.
Over hang near riser need to add two heads.
Replace one painted upright in service department restroom .
Small storage closet near service office need one head.
Snack storage room closed.
1.11 Need FDC sign with address
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 4 of 6
See Continuation Page(s) (Indicate the number of continuation pages)
PASS J '
x FAIL /l 10/25/2011
Signature Date
State Fire Marshal AES 2 March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 5 of 6
California Inspection /Test
Quarterly Wet n q a aepccmmariaFlcsm a,n
10/2512011
Property: Barber Honda
Owner: Inspection Ref: 7377
Deficiency Summary
These items were deficient and do not meet the requirements of the applicable code at the time of the inspection.
Items marked Recommendation are not required by the applicable code but are opportunities to improve the Life
Safety of the property.
CahforriiWt ._ _' --,. --- , F . - ° ;.,
jj •,
p -"';
v
Fail 1.9 Sprinklers
Need to add argo chrome escutcheons in the following areas. 1 in oil room,south electrical room, near
Dustin Kryger desk, one near Erma in service,one in file room in general office, one in Steve Ekergen
office, one southwest overhang and five in show room floor.
Need to raise two and lower one head in show room floor.
service waiting room janitors clost in mens restroom need to raise one head.
Over hang near riser need to add two heads.
Replace one painted upright in service department restroom .
Small storage closet near service office need one head.
Snack storage room closed.
NFPA -25 -2002 5.2.1.1 Sprinklers shall be inspected from the floor level annually. Sprinklers shall be free of
corrosion, foreign materials, paint, and physical damage and shall be installed in the proper orientation (e.g.,
upright, pendant, or sidewall). Any sprinkler shall be replaced that is painted, corroded, damaged, loaded, or in
the improper orientation.
Fail 1.11 Fire Department Connections
Need FDC sign with address
NFPA -25 -2002 12.7.1 Fire department connections shall be inspected quarterly. The inspection shall verify the
following: (a) Connections are visible and accessible, (b) Couplings or swivels are not damaged and rotate
smoothly, (c) Plugs or caps are in place and undamaged, (d) Gaskets are in place and in good condition, (e)
Identification signs are in place, (0 The check valve is not leaking, (g) The automatic drain valve is in place and
operating properly.
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 6 of 6