HomeMy WebLinkAbout4100 TRUXTUN AVENUE (2)r ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25, Chapter 5 as amended by CCR, Title 19 Date Of Inspection, Testing, Maintenance: 03/15/2012 System Riser ID: 7431 Property Information: Type Of System: r OF CqC Name: Emerald Center O Wet Pipe 0 Z Address: 4100 Truxtun Avenue E] Dry Pipe y Preaction Deluge FE Mph City: Bakersfield Main Drain Test Results: Abbreviation Key: Initial Static Pressure: (psi) I = Inspection T = Test Residual Pressure: (psi) M = Maintenance A -0 = After Operation Restored Static Pressure: (psi) MI = Per Manufacturer's Instructions Item Activity Frequency Description NFPA 25 Fail N/A PassReference 1.1 1 Daily Preaction /Deluge Valves - Enclosure 12.4.3.1 XWeeklytemperature 1.2 1 Daily Dry Pipe Valves - Enclosure temperature 12.4.4.1.1 XWeekly 1.3 1 Quarterly Gauges - (Dry, Preaction, Deluge Systems) 5.2.4.2 5.2.4.3 X 1.4 1 Quarterly Control Valves 12.3.2.1 X 1.5 1 Quarterly Alarm Devices 5.2.6 X 1.6 1 Quarterly Gauges (Wet Pipe Systems) 5.2.4.1 X 1.7 1 Quarterly Hydraulic nameplate 5.2.7 X 1.8 1 Quarterly Pipe and Fittings 5.2.2 X 1,9 1 Quarterly Sprinklers 5.2.1 X 1.10 1 Quarterly Spare Sprinklers 5.2.1.3 X 1.11 1 Quarterly Fire Department Connections 12.7.1 X 1.12 1 Quarterly Alarm Valves - Exterior Inspection 12.4.1.1 X 1.13 1 Quarterly Preaction /Deluge Valves - Exterior Inspection 12.4.3.1.6 X 1.14 1 Quarterly Pressure Reducing Valves 12.5.1.1 X 1.15 1 Quarterly Dry Pipe Valves- Exterior Inspection 12.4.4.1.4 X 1.16 1 Quarterly Backflow Preventers 12.6.1 X 117 I Annual Buildings 5.2.5 X State Fire Marshal AES 2 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 June 17, 2008 Page 1 of 6 ANNEX B Item Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25, Chapter 5 as amended by CCR, Title 19 Frequency Date Of Inspection, Testing, Maintenance: 03/15/2012 System Riser ID: 7431 N/A Property Information: 1.18 Type Of System: CAC7 0Name: Emerald Center 5.2.3 X Wet Pipe 1 1.19 I p Address: 4100 Truxtun Avenue 5.2.3 Dry Pipe y 1.20 Preaction Hangers (Accessible concealed spaces) 5.2.3.3 Deluge f E Mp City: Bakersfield 1.21 1 5 Years Item Activity Frequency Description NFPA 25 Reference Fail N/A Pass 1.18 1 Annually Hangers 5.2.3 X 1.19 I Annually Seismic Braces 5.2.3 X 1.20 I 5 Years Hangers (Accessible concealed spaces) 5.2.3.3 X 1.21 1 5 Years Seismic Braces (Accessible concealed spaces) 5.2.3.3 X 1.22 I 5 Years Pipe and Fittings (Accessible concealed spaces) 5.2.2.3 X 1.23 I 5 Years Sprinklers (Accessible concealed spaces) 5.2.1.1.4 X 1.24 1 5 Years Alarm Valves - Interior Inspection 12.4.1.2 X 1.25 1 5 Years Alarm Valves - Strainers, filters, orifices 12,4,1,2 X 1.26 1 5 Years Check Valves - Interior Inspection 12.4,2.1 X 1.27 I 5 Years Preaction /Deluge Valves - Interior Inspection 12.4.3.1.7 X 1.28 1 5 Years Preaction/Deluge Valves - Strainers, filters, orifices 12.4.3.1.8 X 1.29 1 5 Years Dry Pipe Valves - Interior Inspection 12.4.4.1.5 X 1.30 1 5 Years Dry Pipe Valves - Strainers, filters, orifices 12.4.4.1.6 X 2.1 T Annually Alarm Devices (90 Sec) 5.3.3 12.2.7 X 2.2 T Annually Main Drain Test (Enter data on Page 1) 12.2.6 12.2.6.1 12.3.3.4 X 2.3 T Annually Antifreeze Test 5.3.4 X 2.4 T Annually Control Valve - Position 12.3.3.1 X 2.5 T Annually Control Valve - Operation 12.3.3.1 X 2.6 T Annually Supervisory 12.3.3.5 X 2.7 T Annually Preaction Valve - Priming Water 12.4.3.2.1 X 2.8 T Annually Preaction Valve - Low Air Pressure Alarm 12.4.3.2.10 X 2.9 T Annually Preaction Valve - Full Flow Trip Test 12.4.3.2.2 X State Fire Marshal AES 2 June 17, 2008 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 2 of 6 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25, Chapter 5 as amended by CCR, Title 19 Date Of Inspection, Testing, Maintenance: 03/15/2012 System Riser ID: 7431 Property Information: Type Of System: F Cq040Name: Emerald Center Address: 4100 Truxtun Avenue Wet Pipe cr aps Dry Pipe y a El Preaction % Deluge w' JP City: Bakersfield NFPA 25 Item Activity Frequency Description Reference Fail N/A Pass 2.10 T Annually Dry Pipe Valve - Priming Water 12.4.4.2.1 X 2.11 T Annually Dry Pipe Valve - Low Air Pressure Alarm 12.4.4.2.6 X 2.12 T Annually Dry Pipe Valve - Quick- Opening Device 12.4.4.2.4 X 2.13 T Annually Dry Pipe Valve - Trip Test 12.4.4.2.2 X 2.14 T Annually Backflow Preventor Assemblies 12.6.2 X 2.15 T 3 Years Dry Pipe Valve - Full Flow Trip Test 12.4.4.2.2.2 X 2.16 T 5 Years Gauges 5.3.2 X 2.17 T 5 Years Pressure Reducing Valve 12.5.1.2 X 2.18 T 5 Years Fire Department Connection Backflush 12.7.4 X 2.19 T 5 Years Sprinklers - Extra High Temperature 5.3.1.1.1.3 X 2.20 T 5 Years Sprinklers - Corrosive environment or 5.3.1.1.2 X corrosive water 2.21 T 10 Years Sprinklers - Dry 5.3.1.1.1.5 X 2.22 T 20 Years Sprinklers - Fast Response 5.3.1.1.1.2 X 2.23 T 50 Years Sprinklers 5.3.1.1.1 X 2,24 T 75 Years Sprinklers 75 years in service 5.3.1.1.1.4 X 2.25 T Sprinklers manufactured prior to 1920 - 5.3.1.1.1.1 XReplace 3.1 M Annually Control Valves 12.3.4 X 3.2 M Annually Preaction /Deluge Valves 12.4.3.3.2 X 3.3 M Annually Dry Pipe Valves /Quick- Opening Devices 12.4.4.3.2 X 3.4 M Annually Dry Pipe Valve - Low Point Drains 12.4.4.3.3 X 3.5 M 5 Years Obstruction Investigation Chapter 13 X State Fire Marshal AES 2 June 17, 2008 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 3 of 6 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 03/15/2012 System Riser ID: 7431 Property Information; Name: Emerald Center Address: 4100 Truxtun Avenue Type Of System: Wet Pipe , CF CAC X Q ,y 2 Dry Pipe Preaction 9 P Deluge MA City: Bakersfield Deficiencies and Comments: Item Deficiencies and Comments Item number must correspond to to the Item number of the activity listed above: 1.9 Three (3) heads on 3rd floor extenior are above stucco, starwell one painted upright. need 14' ladder. suite 304 Kim's office replace one standard 401 rusted head. Head painted west side of elevator on 1 st floor, and 9 other lightly painted in carport. Ste.200 -Head need to be added in hallway in front of draw station. Ste.200- Nurses Station - Texture on head. Ste.200 -In front of room #5 -Head has texture on it, in front off room 3, one in exam room 10, one in hallway in front of Maria Garcia office, restroom near lobby,one near confrance room, and 2 in hallway near break room, suite 200. quik response heads that need to be changed over to standard in the following, one in hallway near room 6, one in file room, 4 in therapy room and lower one head over tred mill. Ste.200 -X -Ray Room -Two (2) heads have texture on them. Ste.200 -Head in restroom has texture on it. Ste.200 -Room next to check out has one (1) chrome E2 esc. missing. 401 esc. has fallen off ground floor by Elevator. One (1) rec. esc. 3rd floor Dr. Reeds Office above desk chair. West Covered Parking -Two (2) painted heads. Ste. 300 -Front Looby Locked -Two (2) esc. missing E -1 1.11 FDC sign needs address. Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 4 of 6 See Continuation Page(s) PASS x FAIL State Fire Marshal AES 2 Indicate the number of continuation pages) w( Signature 03/15/2012 Date March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 5 of 6 California Inspection/Test WhptaS A InepeCm eMReddFrtSpdnMar Systd e Quarterly Wet ......- ............... ............................._. . 3115/2012 Wrr. W x 61,arreert at:ara41 ld Property: Emerald Center Owner: Inspection Ref: 7431 Deficiency Summary These items were deficient and do not meet the requirements of the applicable code at the time of the inspection. Items marked Recommendation are not required by the applicable code but are opportunities to improve the Life Safety of the property. 7"'t'z. {E a `mod , fir t•. },."_c ewer ar't,n` F`r ' t,''`° c - "{,5 :I *. Fail 1.9 Sprinklers Three (3) heads on 3rd floor extenior are above stucco, starwell one painted upright. need 14' ladder. suite 304 Kim's office replace one standard 401 rusted head. Head painted west side of elevator on 1 st floor, and 9 other lightly painted in carport. Ste.200 -Head need to be added in hallway in front of draw station. Ste.200- Nurses Station - Texture on head. Ste.200 -In front of room #5 -Head has texture on it, in front off room 3, one in exam room 10, one in hallway in front of Maria Garcia office, restroom near lobby,one near confrance room, and 2 in hallway near break room, suite 200. quik response heads that need to be changed over to standard in the following, one in hallway near room 6, one in file room, 4 in therapy room and lower one head over tred mill. Ste.200 -X -Ray Room -Two (2) heads have texture on them. Ste.200 -Head in restroom has texture on it. Ste.200 -Room next to check out has one (1) chrome E2 esc. missing. 401 esc. has fallen off ground floor by Elevator. One (1) rec. esc. 3rd floor Dr. Reeds Office above desk chair. West Covered Parking -Two (2) painted heads. Ste. 300 -Front Looby Locked -Two (2) esc. missing E -1 NFPA -25 -2002 5.2.1.1 Sprinklers shall be inspected from the floor level annually. Sprinklers shall be free of corrosion, foreign materials, paint, and physical damage and shall be installed in the proper orientation (e.g., upright, pendant, or sidewall). Any sprinkler shall be replaced that is painted, corroded, damaged, loaded, or in the improper orientation. Fail 1.11 Fire Department Connections FDC sign needs address. NFPA -25 -2002 12.7.1 Fire department connections shall be inspected quarterly. The inspection shall verify the following: (a) Connections are visible and accessible, (b) Couplings or swivels are not damaged and rotate smoothly, (c) Plugs or caps are in place and undamaged, (d) Gaskets are in place and in good condition, (e) Identification signs are in place, (t) The check valve is not leaking, (g) The automatic drain valve is in place and operating properly. Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 6 of 6