HomeMy WebLinkAbout930 WIBLE ROADANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 12/27/2011 System Riser ID: 7087 Property Information: Type Of System: CqC,. Name: Wible Wood Center Op Wet Pipe p2 Address: 930 Wible Road Dry Pipe Pass Preaction Q Deluge qqEMp. City: Bakersfield Daily Weekly Main Drain Test Results: Initial Static Pressure: (psi) Residual Pressure: (psi) Restored Static Pressure: (psi) Abbreviation Key: I = Inspection T =Test M = Maintenance A -O = After Operation MI = Per Manufacturer's Instructions Item Activity Frequency Description NFPA 25 Reference Fail N/A Pass 1.1 1 Daily Weekly Preaction /Deluge Valves - Enclosure temperature 12.4.3.1 X 1.2 1 Daily Weekly Dry Pipe Valves - Enclosure temperature 12.4.4.1.1 X 1.3 1 Quarterly Gauges - (Dry, Preaction, Deluge Systems) 5.2.4.2 5.2.4.3 X 1.4 1 Quarterly Control Valves 12.3.2.1 X 1.5 1 Quarterly Alarm Devices 5.2.6 X 1.6 1 Quarterly Gauges (Wet Pipe Systems) 5.2.4.1 X 1.7 1 Quarterly Hydraulic nameplate 5.2.7 X 1.8 1 Quarterly Pipe and Fittings 5.2.2 X 1.9 1 Quarterly Sprinklers 5.2.1 X 1.10 1 Quarterly Spare Sprinklers 5.2.1.3 X 1.11 I Quarterly Fire Department Connections 12.7.1 X 1.12 1 Quarterly Alarm Valves - Exterior Inspection 12.4.1.1 X 1.13 I Quarterly Preaction /Deluge Valves - Exterior Inspection 12.4.3.1.6 X 1.14 1 Quarterly Pressure Reducing Valves 12.5.1.1 X 1.15 1 Quarterly Dry Pipe Valves- Exterior Inspection 12.4.4.1.4 X 1.16 1 Quarterly Backflow Preventers 12.6.1 X 1.17 1 Annual Buildings 5.2.5 X State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 1 of 5 ANNEX B Item Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Frequency Date Of Inspection, Testing, Maintenance: 12/27/2011 System Riser ID: 7087 Fail Property Information: Pass 1.18 1 Annually Hangers Type Of System: Name: Wible Wood Center Wet Pipe c0er .p Address: 930 Wible Road Dry Pipe y° X Preaction 1 5 Years Hangers (Accessible concealed spaces) E] Deluge City: Bakersfield 1.21 1 Item Activity Frequency Description NFPA 25 Reference Fail N/A Pass 1.18 1 Annually Hangers 5.2.3 X 1.19 1 Annually Seismic Braces 5.2.3 X 1.20 1 5 Years Hangers (Accessible concealed spaces) 5.2.3.3 X 1.21 1 5 Years Seismic Braces (Accessible concealed spaces) 5.2.3.3 X 1.22 1 5 Years Pipe and Fittings (Accessible concealed spaces) 5.2.2.3 X 1.23 1 5 Years Sprinklers (Accessible concealed spaces) 5.2.1.1.4 X 1.24 1 5 Years Alarm Valves - Interior Inspection 12.4.1.2 X 1.25 1 5 Years Alarm Valves - Strainers, filters, orifices 12.4.1.2 X 1.26 1 5 Years Check Valves - Interior Inspection 12.4.2.1 X 1.27 1 5 Years Preaction /Deluge Valves - Interior Inspection 12.4.3.1.7 X 1.28 1 5 Years Preaction/Deluge Valves - Strainers, filters, orifices 12.4.3.1.8 X 1.29 1 5 Years Dry Pipe Valves - Interior Inspection 12.4.4.1.5 X 1.30 1 5 Years Dry Pipe Valves - Strainers, filters, orifices 12.4.4.1.6 X 2.1 T Annually Alarm Devices (90 Sec) 5.3.3 12.2.7 X 2.2 T Annually Main Drain Test (Enter data on Page 1) 12.2.6 12.2.6.1 12.3.3.4 X 2.3 T Annually Antifreeze Test 5.3.4 X 2.4 T Annually Control Valve - Position 12.3.3.1 X 2.5 T Annually Control Valve - Operation 12.3.3.1 X 2.6 T Annually Supervisory 12.3.3.5 X 2.7 T Annually Preaction Valve - Priming Water 12.4.3.2.1 X 2.8 T Annually Preaction Valve - Low Air Pressure Alarm 1 12.4.3.2.10 X 2.9 T Annually Preaction Valve - Full Flow Trip Test 12.4.3.2.2 X State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 2 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 12/27/2011 Property Information: Wible Wood Center Address: 930 Wible Road City: Bakersfield System Riser ID: 7087 Type Of System: p CA4/, 0 Wet Pipe o,A Dry Pipe n Preaction P DelugeENjp; Item Activity Frequency Description NFPA 25 Reference Fail N/A Pass ' 2.10 T Annually Dry Pipe Valve - Priming Water 12.4.4.2.1 X 2.11 T Annually Valve - Low Air Pressure AlarmA 12.4.4.2.6 X 2.12 T Annuallyy ry Pipe Valve - Quick - Opening Device 12.4.4.2.4 X 2.13 T Annually Dry Pipe Valve - Trip Test 12.4.4.2.2 X 2.14 T Annually Backflow Preventor Assemblies 12.6.2 X 2.15 T 3 Years Dry Pipe Valve - Full Flow Trip Test 12.4.4.2.2.2 X 2.16 T 5 Years Gauges 5.3.2 X 2.17 T 5 Years Pressure Reducing Valve 12.5.1.2 X 2.18 T 5 Years Fire Department Connection Backflush 12.7.4 X 2.19 T 5 Years Sprinklers - Extra High Temperature 5.3.1.1.1.3 X 2.20 T 5 Years Sprinklers - Corrosive environment or corrosive water 5.3.1.1.2 X 2.21 T 10 Years Sprinklers - Dry 5.3.1.1.1.5 X 2.22 T 20 Years Sprinklers - Fast Response 5.3.1.1.1.2 X 2.23 T 50 Years Sprinklers 5.3.1.1.1 X 2.24 T 75 Years Sprinklers 75 years in service 5.3.1.1.1.4 X 2.25 T Sprinklers manufactured prior to 1920 Replace 5.3.1.1.1.1 X 3.1 M Annually Control Valves 12.3.4 X 3.2 M Annually Preaction /Deluge Valves 12.4.3.3.2 X 3.3 M Annually Dry Pipe Valves /Quick- Opening Devices 12.4.4.3.2 X 3.4 M Annually Dry Pipe Valve - Low Point Drains 12.4.4.3.3 X F3.5 m7 5 Years Obstruction Investigation Chapter 13 X State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 3 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended bv CCR Title 19 Date Of Inspection, Testing, Maintenance: 12127/2011 Property Information: Name: Wible Wood Center Address: 930 Wible Road City; Bakersfield System Riser ID: 7087 Type Of System: y' I(, ca oWetPipe Q p Dry Pipe Preaction Deluge ARE MN Item Deficiencies and Comments: Deficiencies and Comments Item number must correspond to the Item number of the activity listed above: 1.9 Suite 920 -Need to add four (4) heads. (3 in the front and 1 in the Office) Add one (1) alum. esc. Suite 942 - Caring Corner -Five (5) 401 esc. missing and replace one (1) head bent deflector. Suite 944 -Afif -Two (2) 401 alum. esc. missing. Suite 948 -1 Do Tuxedos - Replace 3" vic on end of line. Eight (8) esc. need replacing. Outside overhang-Replace five 5 401 esc. See Continuation Page(s) (Indicate the number of continuation pages) PASS x FAIL `,._ _ /l 12/27/2011 Signature Date State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 4 of 5 California Inspection /Test Quarterly Wet Dnq%lft=bro ImpaLftmaR*idFUcSpVareym% 12/27/2011 Property: Wible Wood Center Owner: Inspection Ref: 7087 7 Deficiency Summary These items were deficient and do not meet the requirements of the applicable code at the time of the inspection. Items marked Recommendation are not required by the applicable code but are opportunities to improve the Life Safety of the property. Fail 1.9 Sprinklers Suite 920 -Need to add four (4) heads. (3 in the front and 1 in the Office) Add one (1) alum. esc. Suite 942 - Caring Corner -Five (5) 401 esc. missing and replace one (1) head bent deflector. Suite 944 -Afif -Two (2) 401 alum. esc. missing. Suite 948 -1 Do Tuxedos - Replace 3" vic on end of line. Eight (8) esc. need replacing. Outside overhang - Replace five (5) 401 esc. NFPA -25 -2002 5.2.1.1 Sprinklers shall be inspected from the floor level annually. Sprinklers shall be free of corrosion, foreign materials, paint, and physical damage and shall be installed in the proper orientation (e.g., upright, pendant, or sidewall). Any sprinkler shall be replaced that is painted, corroded, damaged, loaded, or in the improper orientation. Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 5 of 5