Main Drain Test Results:
Initial Static Pressure: (psi)
Residual Pressure: (psi)
Restored Static Pressure: (psi)
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Item
Date Of Inspection, Testing, Maintenance: 10/31/2011 System Riser ID: 7338
Description
Property Information:
Fail
Type Of System: 5 CACName: 900 Mohawk
1
0 Wet Pipe 0
Address: 900 Mohawk Dry Pipe
1.2 1
Preaction y P
12.4.4.1.1
Deluge
City: Bakersfieldz
1 Quarterly Gauges - (Dry, Preaction, Deluge
Systems)
Main Drain Test Results:
Initial Static Pressure: (psi)
Residual Pressure: (psi)
Restored Static Pressure: (psi)
Abbreviation Key:
I = Inspection
T =Test
M = Maintenance
A -O = After Operation
MI = Per Manufacturer's Instructions
Item Activity Frequency Description NFPA 25
Reference Fail N/A Pass
1.1 1 Daily
Weekly
Preaction /Deluge Valves - Enclosure
temperature
12.4.3.1 X
1.2 1 Daily
Weekly
Dry Pipe Valves - Enclosure
temperature
12.4.4.1.1 X
1.3 1 Quarterly Gauges - (Dry, Preaction, Deluge
Systems)
5.2.4.2
5.2.4.3 X
1.4 1 Quarterly Control Valves 12.3.2.1 X
1.5 1 Quarterly Alarm Devices 5.2.6 X
1.6 1 Quarterly Gauges (Wet Pipe Systems) 5.2.4.1 X
1.7 1 Quarterly Hydraulic nameplate 5.2.7 X
1.8 1 Quarterly Pipe and Fittings 5.2.2 X
1.9 I Quarterly Sprinklers 5.2.1 X
1.10 1 Quarterly Spare Sprinklers 5.2.1.3 X
1.11 1 Quarterly Fire Department Connections 12.7.1 X
1.12 1 Quarterly Alarm Valves - Exterior Inspection 12.4.1.1 X
1.13 1 QuarterlyQuarter) Preaction /Deluge Valves - Exterior
Inspection 12.4.3.1.6 X
1.14 1 Quarterly Pressure Reducing Valves 12.5.1.1 X
1.15 1 Quarterly Dry Pipe Valves- Exterior Inspection 12.4.4.1.4 X
1.16 1 Quarterly Backflow Preventers 12.6.1 X
1.17 I Annual Buildings 5.2.5 X
State Fire Marshal AES 2 March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 1 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Activity
Date Of Inspection, Testing, Maintenance: 10/31/2011
Description
System Riser ID: 7338
Fail
Property Information:
Pass
Type Of System:
Name: 900 Mohawk
Hangers
x Wet Pipe pQ
Address: 900 Mohawk Dry Pipe v
Annually Seismic Braces
Preaction 1
X
Deluges
ARE M
City: Bakersfield
Hangers (Accessible concealed spaces) 5.2.3.3
Item Activity Frequency Description
NFPA 25
Reference Fail N/A Pass
1.18 1 Annually Hangers 5.2.3 X
1.19 I Annually Seismic Braces 5.2.3 X
1.20 I 5 Years Hangers (Accessible concealed spaces) 5.2.3.3 X
1.21 I 5 Years Seismic Braces (Accessible concealed
spaces)
5.2.3.3 X
1.22 1 5 Years Pipe and Fittings (Accessible concealed
spaces)
5.2.2.3 X
1.23 1 5 Years Sprinklers (Accessible concealed spaces) 5.2.1.1.4 X
1.24 1 5 Years Alarm Valves - Interior Inspection 12.4.1.2 X
1.25 1 5 Years Alarm Valves - Strainers, filters, orifices 12.4.1.2 X
1.26 1 5 Years Check Valves - Interior Inspection 12.4.2.1 X
1.27 1 5 Years Preaction /Deluge Valves - Interior
Inspection 12.4.3.1.7 X
1.28 I 5 Years Preaction/Deluge Valves - trainers,
filters, orifices 12.4.3.1.8 X
1.29 1 5 Years Dry Pipe Valves - Interior Inspection 12.4.4.1.5 X
1.30 1 5 Years Dry Pipe Valves - Strainers, filters, orifices 12.4.4.1.6 X
2.1 T Annually Alarm Devices (90 Sec) 5.3.3
12.2.7 X
2.2 T Annually Main Drain Test (Enter data on Page 1)
12.2.6
12.2.6.1
12.3.3.4
X
2.3 T Annually Antifreeze Test 5.3.4 X
2.4 T Annually Control Valve - Position 12.3.3.1 X
2.5 T Annually Control Valve - Operation 12.3.3.1 X
2.6 T Annually Supervisory 12.3.3.5 X
2.7 T Annually Preaction Valve - Priming Water 12.4.3.2.1 X
2.8 T Annually Preaction Valve - Low Air Pressure Alarm 12.4.3.2.10 X
2.9 T Annually Preaction Valve - Full Flow Trip Test 12.4.3.2.2 X
State Fire Marshal AES 2 March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 2 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 10/31/2011
Property Information:
Name: 900 Mohawk
Address: 900 Mohawk
City: Bakersfield
System Riser ID: 7338
Type Of System: YP Y of CACif
x Wet Pipe 0
Dry Pipe
Preaction ".N
Deluge _.r'
P
F-1 9 '`Re MP
Item Activity Frequency Description
NFPA 25
Reference Fail N/A Pass
2.10 T Annually Dry Pipe Valve - Priming Water 12.4.4.2.1 X
2.11 T Annual/ Y Dry Pipe Valve - Low Air Pressure
Alarm
12.4.4.2.6 X
2.12 T Annual/ Annually Dry Pipe Valve - Quick- Opening
Device 12.4.4.2.4 X
2.13 T Annually Dry Pipe Valve - Trip Test 12.4.4.2.2 X
2.14 T Annually Backflow Preventor Assemblies 12.6.2 X
2.15 T 3 Years Dry Pipe Valve - Full Flow Trip Test 12.4.4.2.2.2 X
2.16 T 5 Years Gauges 5.3.2 X
2.17 T 5 Years Pressure Reducing Valve 12.5.1.2 X
2.18 T 5 Years Fire Department Connection Backflush 12.7.4 X
2.19 T 5 Years Sprinklers - Extra High Temperature 5.3.1.1.1.3 X
2.20 T 5 Years Sprinklers - Corrosive environment or
corrosive water
5.3.1.1.2 X
2.21 T 10 Years Sprinklers - Dry 5.3.1.1.1.5 X
2.22 T 20 Years Sprinklers - Fast Response 5.3.1,1.1.2 X
2.23 T 50 Years Sprinklers 5.3.1.1.1 X
2.24 T 75 Years Sprinklers 75 years in service 5.3.1.1.1.4 X
2.25 T Sprinklers manufactured prior to 1920
Replace
5.3.1.1.1.1 X
3.1 M Annually Control Valves 12.3.4 X
3.2 M Annually Preaction /Deluge Valves 12.4.3.3.2 X
3.3 M Annually Dry Pipe Valves /Quick- Opening
Devices 12.4.4.3.2 X
3.4 M Annually Dry Pipe Valve - Low Point Drains 12.4.4.3.3 X
3.5 M 5 Years Obstruction Investigation Chapter 13 X
State Fire Marshal AES 2 March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 3 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 10/31/2011
Property Information:
Name: 900 Mohawk
Address: 900 Mohawk
City: Bakersfield
System Riser ID: 7338
Type Of System:
o CoX Wet Pipe v .Q
2DryPipe
Preaction 9 QfE] Deluge EM
Item
Deficiencies and Comments:
Deficiencies and Comments Item number must correspond to the Item number
of the activity listed above:
1.5 Local bell is inoperable.
Son light electric was near by and was able to noticed no power was going to bell. Need to check brakers.
vacant/locked suites, 145, 130, 140, 210, 217d, 217b, 215 and 22.
Need to check status of alarm bell.
See Continuation Page(s) (Indicate the number of continuation pages)
PASS f
FAIL -- 10/31/2011
Signature Date
State Fire Marshal AES 2 March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 4 of 5
California Inspection /Test
Quarterly
MIAln=m, Vapeft aidR* dFh8ptlJ;n3rSpsz%
10/31/2011 6r, •, rs =. 3a'r;t r
Property: 900 Mohawk
Owner: Inspection Ref: 7338
Deficiency Summary
These items were deficient and do not meet the requirements of the applicable code at the time of the inspection.
Items marked Recommendation are not required by the applicable code but are opportunities to improve the Life
Safety of the property.
7` gxi7-. +r t`1d:, e 7F -r iii;
C'altfornia Wets f a'= '' ? -
Fail 1.5 Alarm Devices
Local bell is inoperable.
Son light electric was near by and was able to noticed no power was going to bell. Need to check
brakers.
vacant/locked suites, 145, 130, 140, 210, 217d, 217b, 215 and 22.
Need to check status of alarm bell.
NFPA -25 -2002 5.2.6 Alarm devices shall be inspected quarterly to verify that they are free of physical damage.
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 5 of 5