HomeMy WebLinkAboutFMC 2012MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State ofCalifornia
Authority Cited.' Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code ofRegulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each
monitorine system control panel by the technician who performs the work. A copy ofthis form must be provided to the tank system owner /operator.
The owner /operator must submit a copy of this form to the local agency regulating UST systems within 30 days oftest date.
A. General Information
Facility Name: FREEWAY LIQUORS
Site Address: 2140 EAST BRUNDAGE
Facility Contact Person:
Make /Model of Monitoring System: TLS -350
B. Inventory of Equipment Tested/Certified
Check the appropriate boxes to indicate specific equipment inspected/serviced:
City: BAKERSFIELD
Contact Phone No.:
Bldg. No.:
Zip:
Date of Testing/Servicing: 3/3012012
Tank ID: 91 Tank ID: 87
Z In -Tank Gauging Probe. Model MAGAZIn -Tank Gauging Probe. Model: MAG -1
Z Annular Space or Vault Sensor. Model: 409 Z Annular Space or Vault Sensor. Model: 409
Z Piping Sump / Trench Sensor(s). Model: 208 Z Piping Sump / Trench Sensor(s). Model: 208
Z Fill Sump Sensor(s). Model: 208 Z Fill Sump Sensor(s). Model: 208
Mechanical Line Leak Detector. Model: RED JACKET Z Mechanical Line Leak Detector. Model: RED JACKET
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
Tank Overfill / High -Level Sensor. Model: Tank Overfill / High -Level Sensor. Model:
Other (specify equipment type and model in Section E on Page 2). Other (specify equipment type and model in Section E on Page 2).
Tank ID: WASTE OIL TANK Tank ID:
in -Tank Gauging Probe. Model: WA In -Tank Gauging Probe. Model:
Annular Space or Vault Sensor. Model: 420 Annular Space or VaultSensor. Model:
Piping Sump / Trench Sensor(s). Model: 208 Piping Sump / Trench Sensor(s). Model:
Fill Sump Sensor(s). Model: Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector. Model: Mechanical Line Leak Detector. Model:
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
Tank Overfill / High -Level Sensor. Model: 208 Tank Overfill / High -Level Sensor. Model:
Other (specify equipment type and model in Section E on Page 2). Other (specify equipment type and model in Section E on Page 2).
Dispenser ED: 112 Dispenser ID: 314
Z DispenserContainment Sensor(s), Model: 208 Z Dispenser Containment Sensor(s). Model: 208
10, Shear Valve(s). Z Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
Dispenser ID: 516 Dispenser ID: 718
Z DispenserContainment Sensor(s). Model: 208 Dispenser Containment Sensor(s). Model: 208
Shear Valve(s).
i 'Dispenser Containment Floats) and Chain(s).
Shear Valve(s).
Dispenser Containment Float(s) and Chain(s).
Mispeoser ID: Dispenser fD:
it -Dispenser Containment Sensor(s).
Spear Valve(s).
Model: Dispenser Containment Sensor(s).
Shear Valve(s).
Model:
DispenserContainment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
j *lf'the'facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification - I certify that the equipment identified in this document was inspected /seryiced in accordance with the manufacturers'
guidelines. Attached to this Certification is information (e.g. manufacturers' checklists) necessary to verify that this information is
correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of erating such reports, I have also
attached a copy of the report; (check all that apply): ® System set -up ® Alarm his report
Technician Name (print): RICH PHILLIPS Signature:
Certification No.: A29084 / 1035169 -UT License. No.: 61/ D40 809850
Testing Company Name: RICH ENVIRONMENTAL Phone No.: (661) 392 -8687
Testing Company Address: 5643 BROOKS CT, BAKERSFIELD, CA 93308 Date of Testing/Servicing: 3/30/2012
Page 1 of 5
UN- 036 -114 www.uaidoe&org Rev. 01 /17 /08
Monitoring System Certification
D. Results of Testing/Servicing
Software Version Installed:
d— mm-lafP +hP;nnnwiner PhPt-k1ie +-
Yes No* IIs the audible alarm operational?
Yes No* IIs the visual alarm operational?
Yes No* WWere all sensors visually inspected, functionally tested, and confirmed operational?
Yes No* WWere all sensors installed at lowest point of secondary containment and positioned so that other equipment will
not interfere with their proper operation?
Yes No* IIf alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem)
IS N/A ooperational?
Yes No* FFor pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
N/A mmonitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate
positive shut -down? (Check all that apply) ® Sump/Trench Sensors; ® Dispenser Containment Sensors.
Did you confirm positive shut -down due to leaks and sensor failure /disconnection? ® Yes; No.
Yes No* FFor tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no
N/A mmechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank
fill point(s) and operating properly? If so, at what percent oftank capacity does the alarm trigger? %
Yes* No WWas any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced
and list the manufacturer name and model for all replacement parts in Section E, below.
Yes* ® No WWas liquid found inside any secondary containment systems designed as dry systems? (Check all that apply)
Product; Water. If yes, describe causes in Section E, below.
Yes No* WWas monitoring system set -up reviewed to ensure proper settings? Attach set up reports, if applicable
Yes No* II Is all monitoring equipment operational per manufacturer's specifications?
In Section E below, describe how and -when these deficiencies were or will be corrected.
Comments:
i
Page 2 of 5
UN -036 — 2/4 www.unidoes.org Rev. 01/17/08
Monitoring System Certification
F. In- Tank Gauging / SIR Equipment:
05%Qk
E Check this box iftank gauging is used only for inventory control.
Check this box ifno tank gauging or SIR equipment is installed.
This section must be completed if in -tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
Yes No* Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
Yes p No* Were all tank gauging probes visually inspected for damage and residue buildup?
Yes No* Was accuracy of system product level readings tested?
Yes No* Was accuracy of system water level readings tested?
Yes I No* Were all probes reinstalled properly?
Yes No* I Were all items on the equipment manufacturer's maintenance checklist completed?
In Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD):
Gomnlete the following checklist:
Check this box if LLDs are not installed.
Yes No*
N/A
For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance?
Check all that apply) Simulated leak rate: ® 3 g.p.h.; [3 0.1 g.p.h ; El 0.2 g.p.h.
Yes No* Were all LLDs confirmed operational and accurate within regulatory requirements?
Yes O. No* Was the testing apparatus properly calibrated?
Yes No*
N/A
For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
Yes No*
N/A
For electronic LLDs, does the turbine automatically shut off ifthe LLD detects a leak?
Yes No*
N/A
For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled
or disconnected?
O ,Yes; No*
N/A
For electronic LLDs, does the turbine automatically shut off ifany portion of the monitoring system malfunctions
or fails a test?
Ye's' No*
0 N/A
For electronic LLDs, have all accessible wiring connections been visually inspected?
z Yes No* Were all items on the equipment manufacturer's maintenance checklist completed?
1n Section FL below. describe how and when these deficiencies were or will he corrected_
Comments:
jdA@ -036 — 3/4
I.,
Page 3 of 5
www.unidocs.org Rev. 01/17/08
Monitoring System Certification
UST Monitorim Site Plan
Site Addm.
Lk,5-W
e . O • _ .. 1 - _ 9. • . _ . . . . . . . . _ w . . • . . • _ . . . . . . _ _ _ . a w V . . • .
r • r. • - - _ •L . • . . . . . . . . • _ - • _ - _
PP ,, •
r r _ - . _ - e• . _ • . _ • • r • _ . _ . . • . . . . . . . « • • Y - r -
m . . . . . m . . . / . . . • . . . . . . . • . . . . . . . . r . . . . . • . . . r . . . .
I ::: ::: -- - ::: = == ... ...... .
D* map was &m
Instmedons
0
If you already have a diagram that shows all required information, you may include it, rather than this page, with your
Mmikni motion- On yom site per• slow the general layout oftanks andpiping• Clearly identify
locations oftine following eq:ipme: if iaatallod: monitoring n' -.catiol pawls, sensors monitoring took annular
spaces, sumps, dispenserpans, spill gainers, or otber secondary caui Y areas; mechanical or electronic line leak
detectors; and in -tank liquid level probes (ifused to :eak detection). in "w : +ce provided, note the date this Site Plan
was prepared.
Page ot . 05100r
L
SWRCB, January 2006
Spill Bucket Testing Report Form
Thisform is intendedfor use by contractors performing annual testing ofUSTspill containment structures. The completedform and
printoutsfrom tests (cfapplicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: FREEWAY LIQUORS 7 Date of Testing: 3/30/12
Facility Address: 2140 EAST BRUNDAGE LANE, BAKERSFIELD
Facility Contact: I Phone:
Date Local Agency Was Notified of Testing: 2/23/12
Name of Local Agency Inspector (ifpresent during testing):
2. TESTING CONTRACTOR INFORMATION
Company Name: RICH ENVIRONMENTAL
Technician Conducting Test: RICH PHILLIPS
Credentials: CSLB Contractor X 1CC Service Tech. 0 SWRCB Tank Tester Other (Specify)
License Number(s): 1035169 -UT
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: X Hydrostatic Vacuum Other
Test Equipment Used: VISUAL Equipment Resolution: 0
Identify Spill Bucket (By Tank
Number, Stored Product, etc.
187 2 91 3 4
Bucket Installation Tyam' X Direct Bury
Contained in Sump
X Direct Bury
Contained in Sump
Direct Bury
Contained in Sump
Direct Bury
Contained in Sum
Bucket Diameter: 12" 12"
Bucket Depth: 14" 14"
Wait time between applying
vacuum/water and start oftest: 30 MIN 30 MIN
Test Start Time (Ti): 9:15 9:15
Initial Reading (Ri): 14" 14"
Test End Time (TF): 10:15 1 0:15
Final Reading (RF): 14" I4"
Test Duration (TF — Ti): 1 -HOUR 1 -HOUR
Change in Reading (RF - Rj): 0 0
Pass/Fail Threshold or
Criteria 0.00 0.00
Test Result:. X Pass 0 Fail X Pass Fail 0 Pass Fail 0 Pass Fail
Comments — (include information on repairs made prior to testing, andrecommendedfollow -upforfailed tests)
a. .
CERTIFICATION OF TECHNI 1AN RESPONSIBLE FOR CONDUCTING THIS TESTING
Ihereby certify that allthe information con ed in this report is true, accurate, and infull compliance with legal requirements.
Technician's Signature: Date: 3/3Q/12
State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
RICH ENVIRONMENTAL
5643 BROOKS CT. BAKERSFIELD, CA. 93308
OFFICE (661)392 -8687 FAX (661)392 -0621
PRODUCT LINE LEAK DETECTOR TEST
WORK SHEET
FACILITY NAME: FREEWAY LIQUORS
FACILITY ADDRESS: 2140 E. BRUNDAGE LANE, BAKERSFIELD
PRODUCT LINE TYPE: PRESSURE
PRODUCT LEAK DETECTOR TYPE TEST TRIP PASS
BELOW P.S.I. OR
SERIAL NUMBER 3 G.P.H. FAIL
UNL87 L/D TYPE: RED JACKET YES 10 PASS
SERIAL #_
pREM91 L/D TYPE: RED JACKET YES 11 PASS
SERIAL # _
LID TYPE: _ YES PASS
SERIAL # _ NO FAIL
L/D TYPE:_ YES PASS
SERIAL # _ NO FAIL
I CERTIFY THE ABOVE TESTS WERE CONDUCTED ON THIS DATE ACCORDING TO RED
JACKET PUMPS FIELD TEST APPARATUS TESTING PROCEDURE AND LIMITATIONS.
THE MECHANICAL LEAK DETECTOR TEST PASS / FAIL IS DETERMINED BY USING A
LOW FLOW THRESHOLD TRIP RATE OF 3 GALLONS PER HOUR OR LESS AT 10 P.S.I. I
ACKNOWLEDGE THAT ALL DATA COLLECTED IS TRUE AND CORRECT TO THE BEST
OF MY KNOWLEDGE.
TECHNICIAN: RICH PHIL
SIGNATURE: DATE: 3/30/12
AUTO TRANSMIT SETTINGS:
SOFTWARE REVISION LEVEL
VERSION 329.01 SYSTEM SECURITY AUTO LEAK ALARM LIMIT
SOFTWARE# 346329 -100 -B
09.01.29.15.44 CODE: 000000 DISABLED
AUTO HIGH WATER LIh TCREATED -
S- MODULE# 330160 -004 -a MAINTENANCE HISTORYDISABLED
DISABLED
AUTO OVERFILL LIMIT
SYSTEM FEATURES: DISABLED
PERIODIC IN -TANK TESTS AUTO LOW PRODUCT
ANNUAL 1N -TANK TESTS TANK CHART SECURITY DISABLED
LIMITISDDISABLEDDDISABLEDDISABLED
AUTO DELIVERY START
CUSTOM ALARMS DISABLED
DISABLED AUTO DELIVERY END
DISABLED
AUTO EXTERNAL INPUT ON
SERVICE NOTICE
DISABLED
DISABLED
AUTO EXTERNAL INPUT OFF
DISABLED
AUTO SENSOR FUEL ALARM
SYSTEM SETUP ISO 3166 COUNTRY DISABLED
CODE: AUTO SENSOR WATER ALARM
MAR 30. 2012 11:02 All DISABLED
AUTO SENSOR OUT ALARM
MASS /DENSITY DISABLED
DISABLED
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT RECEIVER SETUP:
N,1DD YYYY HH:MM:SS xM NONE
FR&EWAY•GAS- LIQUORS
2,140•E BRUNDAGE
HAKERPFI,ELD. CA
77b254
SHIFTSHIFT TIME 1 11:00 PM COMMUNICATIONS SETUPSHIFTTIME2DISABLED
SHIFT TIME 3 DISABLED
SHIFT TIME 4 DISABLED
PORT SETTINGS:
TANK PER TST NEEDED WRN
DISABLED COMM BOARD ' 1 (ED1M > AUTO DIAL TIME SETUP:
TANK ANN TST NEEDED WRN RS -232 SECURITYDISABLEDCODE : DISABLED NONE
LINE RE- ENABLE METHOD COMM BOARD 2 (RS -232) PASS LINE TEST BAUD RATE 9600PARITYODDLINEPERTSTNEEDEDWRNSTOPBIT1STOPDISABLEDDATALENGTH: 7 DATALINEANNTSTNEEDEDWRNRS -232 SECURITY
DISABLED CODE : DISABLED
PRINT TC VOLUMES COMM BOARD 3 (FXMOD) ENABLED BAUD RATE 2400PARITYODDTEMP,COMPENSATION STOP BIT 1 STOPVALUE:(BEG F ): 60.0 DATA LENGTH: 7 DATAi3T,1CK' :HEIGHT OFFSET RS -232 SECURITY RS -232 END OF MESSAGE
D19ABLED' CODE : DISABLED DISABLED
UYLAGE: 90: DIAL TYPE TONEANSWERON AUTO DIAL ALARM SETUP
H- PROTOCOL DATA FORMAT 1 RING
MODEM SETUP STRINGHEfGHT
DAYLIGHT SAVING TIME DIAL TONE INTERVAL: 32DISABLED
RE- DIRECT LOCAL PRINTOUT
DISABLED
EURO PROTOCOL PREFIX
s
T 3': 87
2.0
PRODUCT CODE 3
THERMAL COEFF 000700
TANK DIAMETER 90.00
TANK PROFILE 4 PTS
FULL VOL 11527
67.5 INCH VOL 9397
45.0 INCH VOL 5857
22.5 INCH VOL 2289
FLOAT SIZE: 4.0 IN.
WATER WARNING 2.0
HIGH WATER LIMIT: 3.0
MAX OR LABEL VOL: 11527
OVERFILL LIMIT 901/9
TANK PROFILE
10374
HIGH PRODUCT 95Yo
67.5 INCH VOL
10950
DELIVERY LIMIT 12%
22.5 INCH VOL
1383
LOW PRODUCT 500
LEAK ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 99
TANK TILT 0.00
PROBE OFFSET 0.00
SIPHON MANIFOLDED TANKS
TO: NONE
LINE MANIFOLDED TANKS
T#: NONE
LEAK MIN PERIODIC: 0'0
0
LEAK MIN ANNUAL 0%
0
PERIODIC TEST TYPE
STANDARD
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY : 5 MIN
PUMP THRESHOLD 10.00%
IN —TANK SETUP
T 2:91
PRODUCT CODE 2
THERMAL COEFF 000700
TANK DIAMETER 90.00
TANK PROFILE 4 PTS
FULL VOL 11527
67.5 INCH VOL 9397
45.0 INCH VOL 5857
22.5 INCH VOL 2289
FLOAT SIZE: 4.0 IN.
WATER WARNING 2.0
HIGH WATER LIMIT: 3.0
MAX OR LABEL VOL: 11527
OVERFILL LIMIT 90%
10374
HIGH PRODUCT 95vo
10950
DELIVERY LIMIT 12%
1383
LOW PRODUCT 500
LEAK ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 99
TANK TILT 0.00
PROBE OFFSET 0.00
SIPHON MANIFOLDED TANKS
TO: NONE
LINE MANIFOLDED TANKS
TO: NONE
LEAK MIN PERIODIC: 0%
0
LEAK MIN ANNUAL 0•
0
PERIODIC TEST TYPE
STANDARD
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY 5 MIN
PUMP THRESHOLD 10.00%
LEAK TJk T MI~THQU
TEST MONTHLY : ALL TANKWEEKIMON
START TIME : 12:00 AMTESTRATE :0.20 GAL /HRDURATION :'2 HOURS
TST EARLY STOP:DISABLED
LEAK TEST REPORT FORMAT
ENHANCED
LIQUID SE14SOR SETUP
L 1:87 STP SUMP
TRI —STATE (SINGLE FLOAT) CATEGORY : STP SUMP
L 2:91 STP SUMP
TRI —STATE (SINGLE FLOAT) CATEGORY : STP SUMP
L 3:87 FILL
TRI —STATE (SINGLE FLOAT) CATEGORY : PIPING SUMP
L 4:91 FILL
TRI —STATE (SINGLE FLOAT) CATEGORY : PIPING SUMP
L 5:DISP 1 -2
TRI —STATE (SINGLE FLOAT) CATEGORY : DISPENSER PAN
L 6:DISP 3 -4
TRI —STATE (SINGLE FLOAT) CATEGORY : DISPENSER PAN
L 7 :DISP 5 -6
TRI —STATE (SINGLE FLOAT) CATEGORY : DISPENSER PAN
L 8:DISP 7 -8
TRI —STATE (SINGLE FLOAT) CATEGORY : DISPENSER PAN
L 9:87 ANNULAR
TRI —STATE (SINGLE FLOAT) CATEGORY : ANNULAR SPACE
L10:91 ANNULAR
TRI —STATE (SINGLE FLOAT) CATEGORY : ANNULAR SPACE
OUTPUT RELAY SETUP - - -
R 1:DISP RELAY
TYPE:
STANDARD
NORMALLY CLOSED
TANK 0: 3
LIQUID SENSOR ALMS
L 1 :FUEL ALARM
L 2:FUEL ALARM
L 5:FUEL ALARM
L 6:FUEL ALARM
L 7:FUEL ALARM
L 8:FUEL ALARM
L I:SENSOR OUT ALARM
L 2:SENSOR OUT ALARM
L 5:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L B:SENSOR OUT ALARM
ISD'SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
AI::DEGRD COLLECT FAIL
L. '! FLOW COLLECT FAIL
SMARTSENSOR SETUP
5 i:DISP 1 -2
CATEGORY AIR FLOW METER
s 2:DISP 3-4
CATEGORY AIR FLOW METER
s 3 :DISP 5 -6
CATEGORY AIR FLOW PIETER
s 4:DISP 7 -8
CATEGORY AIR FLOW METER
s 5:VP SENSOR
CATEGORY VAPOR PRESSURE
s B:'OARBON CANISTER
CATEGORRY VAPOR VALVE
5 B :ATM PRESSURE
CATEGORY ATM P SENSOR
EVR /ISD SETUP
EVR TYPE: BALANCE
BALANCE NOZZLE TYPE
VST
VAPOR PROCESSOR TYPE
VEEDER -ROOT POLISHER
ANALYSIS TIMES
TIME: 7:59 AM
DELAY MINUTES: 1
ACCEPT HIGH ORVR:
DISABLED
ISD HOSE TABLE
ID FP 'FL HL AA RR
01 00 01 02 01 UU
02 01 02 02 01 UU
03 02 03 02 02 UU
04 03 04 02 02 UU
05 04 05 02 03 UU
06 05 06 02 03 UU
07 06 07 02 04 UU.
08 07 08 02 04 UU
ISD AIRFLOW DIETER MAP
ID SERIAL NUM LABEL
1 35011 DISP 1 -2
2 34033 DISP ,3 -4
3 35513 DISP 5 -6
4 32000 DISP 7 -8
ISD FUEL GRADE HOSE MAP
1 2 3 4
FP MHH MHH MHH MHH AA
00 401 901 501 U U 1
01 402 902 502 U U 1
02 403 903 503 U U 2
03 404 904 504 U U 2
04 405 905 505 U.0 3
05 406 906 506 U U 3
06 407 907 507 U U 4
07 408 908 509 U U 4
LABEL TABLE
1: UNASSIGNED
2: BLEND3
3: REGULAR
4: MID GRADE
5: PREMIUM
6: GOLD
7: BRONZE
8: SILVER
9: BLEND2
10: BLEND4
VEEDER- ROOT POLISHER
q
ALARM HISTORY REPORT
SENSOR ALARM - - - -- L 1:87 STP SUMPSTPSUMP
SENSOR OUT ALARM
MAR 30,. 2012 9 :41 AM
FUEL ALARM
MAR 30, 20I2 9:11 AM
FUEL ALARM
NOV S. 2011 2:21 PM
ALARI -I HISTORY REPORT
L - 2:91SSTpOSUMPARM - - - --
STP SUMP
SENSOR OUT ALARMMAR30, 2012 9:41 AM
FUEL ALARM
MAR 30, 2012 9:15 AM
FUEL ALARM
NOV 8, 2011 2:02 PM
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 3:87 FILL
PIPING SUMP
SENSOR OUT ALAYO
MAR 30. 2012 9 :41 All
FUEL ALARM
MAR 30, 2012 9:16 AM
FUEL ALARM
I,IOV 13, 2D11 4:13 AM
ALARM HISTORY REPORT
SENSOR ALARM -----
L 4 :91 FILL
PIPING SUMP
SENSOR OUT ALARM
MAR 30, 2012 9:41 AM
FUEL ALARM
MAR 30, 2012 9:16 AM
SENSOR OUT ALARM
NOV 8, 2011 11:12 AM
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 5:D1SP 1 -2
DISPENSER PAN
SENSOR OUT ALARM
MAR 30, 2012 9:41 AM
FUEL ALARM
MAR 30. 2012 9:37 AM
SENSOR OUT ALARM
NOV B. 2011 11:12 AM
s,RVOR. TORS
LAR
ENR
ALW
g 0
g:DIV 4a1`1
MtsptlapRUT41A
5050
U• 2p%
M
FuEL30LA
012 g:`
M+
O $ O20
ALA 2 AM
av
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 7:DISP 5 -6
DISPENSER PAN
SENSOR OUT ALARM
MAR 30, 2012 9:41 AM
FUEL ALARM
MAR 30. 2012 9:35 AM
SENSOR OUT ALARM
NOV 8, 2011 11:12 AM
ARM HISTORY REPORT
SEAISORI* ALARMe1 ;
DISA 7_8
SENSOLASER PAN
MAR ''30ALARM20129;41 AM
FUEL ALARMMAR '30. 2012 9;33 Am
SENSOR OUT ALARMNOV9, 2011 11:12 AM
1. .,.
ALARM H 1 STORY !{trux i
SENSOR ALARM - - - --
L 9:87 ANNULAR
ANNULAR SPACE
SENSOR OUT ALARM
MAR 30, 2012 9 :41 AM
FUEL ALARM `
MAR 30, 2012 9:30 AM
FUEL ALARM
NOV 8, 2011 2:45 PM
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L10:91 ANNULAR
ANNULAR SPACE
SENSOR OUT ALARM
MAR 30, 2012 9:41 AM
FUEL ALARM
MAR 30, 2012 9:28 AM
FUEL ALARM
NOV 8. 2011 4:19 PM
MONITOR CERT. FAILURE REPORT
SITE NAME: FREEWAY LIQUORS DATE: 3/30/12
ADDRESS: 2140 EAST BRUNDAGE LANE TECHNICIAN: R
CITY: BAKERSFIELD
po a
PARTS INSTALLED:
AIDA,,f
SIGNATURE:
k ilel !f
y
THE ABOVE NAMED PERSON TAKES FULL RESPONSIBILITY OF NOTIFYING
THE APPROPRIATE PARTY TO HAVE CORRECTIVE ACTION TAKEN TO REPAIR
THE ABOVE LISTED PROBLEMS AND NOTIFYING RICH ENVIRONMANTAL FOR
ANY NEEDED RETESTING. THIS ALSO RELEASES RICK ENVIRONMENTAL OF
ANY FINES OR PENALTIES OCCURING FROM NON - COMPLIANCE.
A COPY OF THIS DOCUMENT HAS BEEN LEFT ON -SITE FOR YOUR
CONVIENENCE.