MONITORING SYSTEM CERTIFICATION
For Use ByAl/ Juilsdictions Within the State ofCalifornia
Authority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code ofRegulations
This form must be used to document testing and servicing ofmonitoring equipment. A separate certification or report must be prepared
for each monitoring system control panel by the technician who performs the work. A copy of this form trust be provided to the tank
system owner /operator. The owner /operator must submit a copy of this form to the local agency regulating UST systems within 30
days oftest date.
A. General Information
Facility Name: Sprint Bakersfield Bldg. No.:
Site Address: 715 E. summer City: _Bakersfield Zip: 93385
Facility Contact Person: Doye
Make/Model of Monitoring System: Veeder -Root TLS 350
B. Inventory of Equipment Tested/Certified
Checkthe appropriate boxes to Indicate specific eaulpment Inspected/serviced:
Contact Phone No.: (_217 _)_663 -9440
Date of Testing/Servicing: _102-262-2011
Tank 11): Diesel 550 gal Tank ID:
In -Tank Gauging Probe. Model: Mug I O In -Tank Gauging Probe. Model:
Annular Space or Vault Sensor. Model: 794390- 409 O Annular Space or Vault Sensor. Model:
IM Piping Sump / Trench Sensor(s). Model: 794380 -208 L] Piping Sump / Trench Sensor(s). Model:
Fill Sump Sensor(s). _ Model: Fill Sump Sensor(s). _. Model:
O Mechanical Line Leak Detector. Model: Mechanical Line Leak Detector. Model:
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
Tank Overfill / High -Level Sensor. Model: flapper/ VR ext Alarm Tank Overfill / High -Level Sensor. Model:
Other (specify ui ment type and model in Section E on Page 2). Other (specifX equipment aand model in Section E on Page 2).
Tank ID: TankID:
In -Tank Gauging Probe. Model: O In -Tank Gauging Probe. Model:
Annular Space or Vault Sensor. Model: Annular Space or Vault Sensor. Model:
Piping Sump / Trench Sensor(s). Model: Piping Sump / Trench Sensor(s). Model:
Fill Sump Sensor(s). Model: Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector. Model: Mechanical Line Leak Detector. Model:
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
Tank Overfill / High -Level Sensor. Model: Tank Overfill / High -Level Sensor. Model:
Cl Other (specify equipment a and model in Section E on Pa e 2 . O Other (specify ui mart a and model in Section E on Page 22.
Dispenser ID: Dispenser ID:
Dispenser Containment Sensor(s). Model: O Dispenser Containment Sensor(s). Model:
Shear Valve(s). Shear Valve(s).
O Dispenser Containment Floats and Chain(s). DiTenser Containment Floats and Chain(s).
Dispenser ID: Dispenser ID:
Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s). Model:
Shear Valve(s). O Shear Valve(s).
Dispenser Containment Floats and Chain(s). Dispenser Containment Floats and Chain(s).
Dispenser ID: Dispenser ID:
Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s). Model:
Shear Valve(s). ShearValve(s).
Dis enser Containment Floats and Chains . Dispenser Containment Floats and Chain(s).
If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification -I certify that the equipment Identlfled in this document was Inspected/serviced in accordance with the manufacturers'
guidelines. Attached to this Certification is information (e.g. manufacturers' checklists) necessary to verify that this Information is
correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also
attached a copy ofthe report; (check aft that app(i): ® System set -tip ® ri history report
Technician Name (print): Peter Jauregui III Signature: 5—
Certification No.: B34641 License, No.: 708231
Testing Company Name: _Jauregui &Culver inc
Site Address: 959 W. Mission Ave Escondido CA 92025
Page 1 of 3
Monitoring System Certification
Phone No.: (_760J_734 -0518
Date of Testing/Servicing: _10 / 26/2011
03/01
D. Results of Testing/Servicing
Software Version Installed: 17.01
Complete the followine checklist:
Yes No* Is the audible alarm operational?
Yes No* Is the visual alarm operational?
Yes No* Were all sensors visually inspected, functionally tested and confirmed operational?
Yes No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will
not interfere with their proper operation?
Yes No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem)
N/A operational?
Yes No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
IM N/A monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate
positive shut -down? (Check all that apply) Sump/Trench Sensors; Dispenser Containment Sensors.
Did you confirmpositive shut -down due to leaks and sensor failure /disconnection? Yes; No.
Yes No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no
N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank
fill point (s) and operating properly? If so at what percent of tank capacity does the alarm trigger? 90 %
Yes* No Was any monitoring equipment replaced? if yes, identify specific sensors, probes, or other equipment replaced
and list the manufacturer name and model for all replacement parts in Section E, below.
Yes* No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply)
Product; Water. Ifyes, describe causes in Section E, below.
Yes No* Was monitoring system set-up reviewed to ensure proper settings? Attach set up reports, ifapplicable
Yes I O No* Is all monitorin& equipment o erational per manufacturer's specifications?
In Section E below, describe how and when these deficiencies were or will be corrected.
E. Comments:
Page 2 of 3 03/01
F. In -Tank Gauging / SIR Equipment: ® Check this box if tank gauging is used only for inventory control.
Check this box ifno tank gauging or SIR equipment is installed.
This section must be completed if in -tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
Yes No* Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
Yes No* Were all tank gauging probes visually inspected for damage and residue buildup?
R]Yes No* Was accuracy ofsystem product level readings tested?
Yes No* Was accuracy ofsystem water level readings tested?
Yes No* Were all probes reinstalled properly?
Yes No* Were all items on the equipment manufacturer's maintenance checklist completed?
In the Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD):
Complete the following checklist:
IT Check this box if LLDs are not installed.
Yes No* For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance?
N/A Check all that apply) Simulated leak rate: 3 g.p.h.; 0.1 g.p.h ; 0.2 g.p.h.
Yes No* Were all LLDs confirmed operational and accurate within regulatory requirements?
Yes No* Was the testing apparatus properly calibrated?
Yes No* For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
N/A
Yes No* For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak?
N/A
Yes No* For electronic LLDs, does the turbine automatically shut off if any portion ofthe monitoring system is disabled
N/A or disconnected?
Yes No* For electronic LLDs, does the turbine automatically shut off ifany portion ofthe monitoring system malfunctions
N/A or fails a test?
Yes No* For electronic LLDs, have all accessible wiring connections been visually inspected?
N/A
Yes No* Were all items on the equipment manufacturer's maintenance checklist completed?
In the Section H, below, describe how and when these deficiencies were or will be corrected.
H. Comments:
Page 3 of 3 03 /01
UNDERGROUND STORAGE TANK MONITORING SYSTEM CERTIFICATION
Permit Number:
UST Monitoring Site Plan
Site Address: 7I5 E. SUMNER City: BAKERSFIELD Zip: 93385-
TLS 350
Generator
Room
Main
Overfill Building
Alarm
Fill/Piping Sump Ow /tank probe
Annular O
DIESEL
Fiberglass Tank
550 Gal
I ......... I.......
I ...............
Date map was drawn: 2009
If you already have a diagram that shows all required information, you may include it, rather than this page, with your
Monitoring System Certification. On your site plan, show the general layout of tanks and piping. Clearly identify locations
of the following equipment, if installed: monitoring system control panels; sensors monitoring tank annular spaces, sumps,
dispenser pans, spill containers, or other secondary containment areas; mechanical or electronic line leak detectors; and in-
tank liquid level probes (ifused for leak detection). In the space provided, note the date this Site Plan was prepared,
4
SWRCB, January 2006
Spill Bucket Testing Report Form
Thisform is intendedfor use by contractors peifonning annual testing ofUSTspill contaimnent structures. The completedform and
printoutsfrom tests (ifapplicable), should be provided to thefacility otivner/opei•atoi•for submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: Sprint Bakersfield Date ofTesting: 10/19/2011
Facility Address: 715 E. Sumner, Bakersfield, Ca 93385
Facility Contact: Doye Phone: 217 - 663 -9440
Date Local Agency Was Notified of Testing
Name ofLocal Agency Inspector (ifpresent during testing):
2. TESTING CONTRACTOR INFORMATION
Company Name: Jauregui & Culver inc
Technician Conducting Test: Peter Jauregui III
Credentials: x CSLB Contractor x ICC Service Tech. SWRCB Tank Tester 0 Other (Spec)
License Number(s): 708231, 5315297
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: x Hydrostatic Vacuum Other
Test Equipment Used: Water and Tape Measure Equipment Resolution: 0 Loss
r.,.,.,
Identify Spill Bucket (By Tank
Manber, Stored Product, etc.
Diesel 2 3 4
Bucket Installation Type: Direct Bury
X Contained in Sump
Direct Bury
0 Contained in Sump
Direct Bury
Contained in Sump
Direct Bury
Contained in Sum
Bucket Diameter: 12”
Bucket Depth: 13"
Wait time between applying
vacuum/water and start oftest: 20 min
Test Start Time (Tr): 8:40
Initial Reading (RD: 11 %:"
Test End Time (TF): 9:40
Final Reading (RF): 11 h"
Test Duration (TF — Tt): I hr
Change in Reading (RF -R): 0 change
Pass/Fail Threshold or
Criteria: 0 loss
Test Result:. X Pass Fail Pass Fail 0 Pass Fail O Pass 0 Fail
Comments — (include information on repairs madeprior to testing, and reconunendedfolloiv -tipforfailed tests)
Test water was deemed non hazardous and removed from site for future testinl7.
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
l hereby certify that all the information contained in this report is true, accurate, and infull compliance with legal requirements.
Technician's Date: 11 /26/2011
State laws and regulations do t 9 q rrrently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
SPRINT
AUTO TRANSMIT SETTINGS:
VOLUME 412 GALS
715 SUMNER STREET
ULLAGE 136 GALS AUTO LEAK ALARM LIMIT
BAKERSFIELD, CA
DISABLED
TO VOLUME = 408 GALS
661 -332 -8592 COMMUNICATIONS SETUP
OCT 26, 2011 10:06 AM
WATER VOL = 0 GALS AUTO OVERFILL LIMIT
WATER = 0.00 INCHES
PORT SETTINGS:
TEMP - 79.0 DEG F
SYSTEM STATUS, REPORT 001 °1M BOARD 1 (RS -232)
BAUD RATE 9600
ALL FUNCTIONS NORMAL PARITY ODD
STOP BIT 1 STOP
INVENTORY REPORT DATA LENGTH: 7 DATA
T 1:DIE2EL AUTO TRANSMIT SETTINGS:
VOLUME 412 GALS
ULLAGE 136 GALS AUTO LEAK ALARM LIMIT
90e ULLAGE - B1 GALS DISABLED
TO VOLUME = 408 GALS AUTO HIGH WATER LIMIT
HEIGHT - 33.26 INCHES DISABLED
WATER VOL = 0 GALS AUTO OVERFILL LIMIT
WATER = 0.00 INCHES DISABLED
TEMP - 79.0 DEG F AUTO LOW PRODUCT
DISABLED
AUTO LIMITSYSTEMSETUP
DISABLEDFT
OCT 26. 201! 10:06 -- _
AUTO DELIVERY START
DISABLED
AUTO DELIVERY END
DISABLED
AUTO EXTERNAL INPUT ON
SYSTEM UNITS DISABLED
U. . US AUTO EXTERNAL INPUT OFF
S LANGUAGE DISABLED
ENGLISHE AUTO SENSOR FUEL ALARM
SYSTEM DATE /TIME FORMAT DISABLEDMONDDYYYYHH:MM:SS XM AUTO SENSOR WATER ALARM
DISABLED
SPRINTIVTPR AUTO SENSOR OUT ALARMSUMMERSTREETDISABLED
BAKERSFIELD, CA
661 -332 -8592
SHIFT TIME I DISABLED
SHIFT TIME 2 DISABLED
SHIFT TIME 3 DISABLED RS -232 SECURITY
SHIFT TIME 4 DISABLED CODE : 000000
TANK PERIODIC WARNINGS
DISABLED
TANK ANNUAL WARNINGS
DISABLED
LINE PERIODIC WARNINGS RS -232 END OF MESSAGE
DISABLED DISABLEDLINEANNUALWARNINGS
DISABLED
PRINT TO VOLUMES
ENABLED
TEMP COMPENSATION
VALUE (DEG F ): 60.0
STICK HEIGHT OFFSET
DISABLED
H--PROTOCOL DATA .FORMAT
HEIGHT
DAYLIGHT SAVING TIME
ENABLED
START DATE
APR WEEK I SUN
START TIME
2:00 AM
END DATE
OCT WEEK 4 SUN
END TIME
2:00 AIM
RE- DIRECT LOCAL PRINTOUT
DISABLED
SYSTEM SECURITY
CODE : 000000
I N -TANI' SETUP
T I:DIESEL
PRODUCT CODE I
THERMAL COEFF :.000450
TANK DIAMETER 48.00
TANK PROFILE 4 PTS
FULL VOL 548
36.0 INCH VOL 448
24.0 INCH VOL 274
12.0 INCH VOL 100
FLOAT SIZE: 4.0 IN. 8496
WATER WARNING 110
HIGH WATER LIMIT: 2.0
MAX OR LABEL VOL: 548
OVERFILL LIMIT 90yo
493
HIGH PRODUCT 91%
496
DELIVERY LIMIT 50%
274
LOW PRODUCT 50
LEAK ALARM LIMIT: 25
SUDDEN LOSS LIMIT: 99
TANS: TILT 0.00
MANIFOLDED TANKS
T #: NONE
LEAK MIN PERIODIC: 25%
137
LEAK MIN ANNUAL 25%
137
PERIODIC TEST TYPE
STANDARD
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY . 1 MIN
LEAK TEST METHOD. SOFTWARE REVISION LEVEL
VERSION 17.01
TEST DAILY TANK l SOFTWARE# 346017 -100 -B
CREATED - 98.12.04.11.35
START TIME : 12:00 AM
TEST RATE :0.20 GAL /HR S- MODULE# 330160 -100 -a
DURATION 2 HOURS SYSTEM FEATURES:
PERIODIC IN -TANY. TESTS ALARM HISTORY REPORT
ANNUAL IN -TANK TESTS
BIR SENSOR ALARM - - - --
LEAK TEST REPORT FORMAT L ]:DIESEL SUMP
NORMAL PIPING BUMP
FUEL ALARM
OCT 26. 2011 8:08 AM
FUEL ALARM
DEC 6, 2010 10:03 AM
FUEL ALARM
OCT 6, 2009 9:59 AM
ALARM HISTORY REPORT
SYSTEM ALARM - - - --
LIQUID SENSOR SETUP PAPER OUT
JUN 7, 2011 2:00 Ali
PRINTER ERROR
L I:DIESEL SUMP JUN 7, 2011 2:00 AM
TRI -STATE (SINGLE FLOAT) BATTERY IS OFF
CATEGORY : PIPING SUMP JAN 1, 1996 8:00 AM
SOFTWARE MODULE WARP!
JAN 1, 1996 8:OO AM x END * x x x
L 2:DIESEL AN14ULAR
TRI -STATE (SINGLE FLOAT)
CATEGORY : ANNULAR SPACE
ALARM HISTORY REPORT
IN -TANK ALARM - - - --
T 1 :DIESEL
OVERFILL ALARM ALARM HISTORY REPORT
DEC 6. 2010 10:12 AM
OCT 6, 2009 10:09 AM SENSOR ALARM - - - --
OCT 3, 2008 10:06 Ali L 2 :DIESEL ANNULAR
ANNULAR SPACE
EXTERNAL INPUT SETUP LOW PRODUCT ALARM FUEL ALARM
OCT 17, 2005 12:52 PM OCT 26, 2011 9:35 AM
NONE
HIGH PRODUCT ALARM FUEL ALARMJUN15, 2007 6:47 AM OCT 26, 2011 8:O6 All
INVALID FUEL LEVEL FUEL ALARM
OCT 3. 2008 10 :08 AN OCT 26, 2011 8:05 AM
OCT 17, 2005 12:52 PN1
PROBE OUT
DEC 6, 2010 11:02 Ali
DEC 6, 2010 10:08 AM
OCT 6, 2009 11 :07 AM
OUTPUT RELAY SETUP
DELIVERY 14EEDED
R I:ALARM DEC 6, 2010 10:08 Ali
TYPE: APR 11, 2010 2:19 PM
STANDARD OCT 6, 2009 11:07 AM
NORMALLY OPEN
IN -TANK ALARMS
T ]:LEAK ALARM
T ]:HIGH WATER ALARM
T ]:OVERFILL ALARM
T 1:BUDDEN LOSS ALARM
T ]:HIGH PRODUCT ALARM
T I:PROBE OUT
T I:GROSS TEST FAIL
LIQUID SENSOR ALMS
L ]:FUEL ALARM
L 2:FUEL ALARM
L ]:HIGH LIQUID ALARM
LOW TEMP WARNING
NOV 30, 2007 8:45 AM
X x X k END x* X X X
UNDERGROUND STORAGE TANKS
SECONDARY SYSTEM PINS
CERTIFICATION FORM wRfM' f
25
BAKERSFIELD FIRE DEPARTMENT
Prevention Services
2101 H Street
Bakersfield, CA 93301
Phone: 661-326-3979 • Fax: 661-852-2171
Page 1 of 4
FACILITY ADDRESS FACILITY to DATE
715 Smywr - -o3 io
10
UST ANNULAR SPACE TANK 1 TANK 2 TANK 3
START TIME JD,•Z' qoi
25
BAKERSFIELD FIRE DEPARTMENT
Prevention Services
2101 H Street
Bakersfield, CA 93301
Phone: 661-326-3979 • Fax: 661-852-2171
Page 1 of 4
FACILITY ADDRESS FACILITY to DATE
715 Smywr - -o3 io
10
UST ANNULAR SPACE TANK 1 TANK 2 TANK 3 TANK 4
START TIME JD,•Z' qoi
INITIAL PRESSURE 0"n Ili
END TIME Ilf 25 'u"
i/ ; S • *,
FINAL PRESSURE 0;,,
CERTIFICATION (Signature)
r
V-0-
SECONDARY PIPING
4LIN
1 I E 2 LINE 3 LINE 4
START TIME
INITIAL PRESSURE
END TIME I/; XS ``" i/ ; S • *,
FINAL PRESSURE
CERTIFICATION (Signature)
FD 2098 (Rev OWN)
FACILITY ADDRESS jIfACILITY A
715 C &ioi n er- S}, rgakKs •Ale 1t/ 93 Fo/s
LITY ID
01Y7,
D /.2b ol i
Al2 1E FA D
Y Cl A
rill
ftOE SUMPS SUMP 1 SUMP 2 SUMP 3 SUMP 4
START TIME J0,f3/ /p; it
INITIAL HEIGHT,
OF WATER 1 aqa/, 69%
TIME
WATER HEIGHT
TIME
WATER HEIGHT
TIME
WATER HEIGHT
CERTIFICATION (Signature)
OVERFILL BUCKETS OVERFILL 1 OVERFILL 2 OVERFILL 3 OVERFILL 4
START TIME
O Lip
INITIAL HEIGHT
OF WATER
TIME
WATER HEIGHT
TIME
WATER HEIGHT
CERTIFICATION (Signature)
Page 2 of 4 FD 2098 (Rev 08!07)
FAC
SPRINT BAKERSFIELD
715 E. SUMNER
BAKERSFIELD CA. 93385
JAUREGUI AND CULUER INC_..
1.0/26/2011 10:47 AM
SUMP LEAK TEST REPORT
DSL FIL
TEST STARTED 10:31 AM
TEST STARTED 10/26/2011
BEGIN LEVEL 1.6992 IN
END TIME 10:46 AM
f END DATE 16/26/2011
i END LEVEL 1.6987 [N
LEAK THRESHOLD 0.662 IN
TEST RESULT PASSED
SPRINT BAKERSFIELD
715 E. SUMNER
BAKERSFIELD CA. 93385
JAUREGUI AND CULUER. INC.
10/26/2011 11:02 k-1
SUMP LEAK TEST REPORT
DSL FIL
TEST STARTED 10:47 Am
TEST STARTED 10/26/2011
BEGIN LEVEL 1.6987 IN
END TIME 11:02 Rl
END DATE 10/26/2011
END LEVEL 1.6986 IN
LEAK THRESHOLD 0.002 IN
TEST RESULT PASSEII