BAKERSFIELD FIRE DEPARTMENT
OFFICE OF ENVIRONMENTAL SERVICES
INSPECTOR CRAIG PERKINS
1501 TRUXTUN AVE.
BAKERSFIELD, CA 93301
Test Date: 5/10/2012
Order Number: 3402214
Dear Regulator,
Date Printed and Mailed: 5/29/2012
Enclosed are the results of recent testing performed at the following facility:
CHEVRON # 355920
JITB # 7723
10 UNION AVENUE
BAKERSFIELD, CA 93307
Testing performed:
ATG
IMPACT VALVE
LEAK DETECTOR
SPILL BUCKET TEST
Sincerely,
b o0
Dawn Kohlmeyer
Manager, Field Reporting
Appendix VI
Copies of Monitoring System Certification form and UST Monitoring Plot Plan available at http: / /www.swrcb.ca.gov.)
MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State of California
Authority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of
Regulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each monitoring
system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner /operator. The
owner /operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date.
A. General Information
Facility Name: CHEVRON # 355920 Bldg. No.:
Site Address: JITB # 772310 UNION AVENUE
Facility Contact Person: MINTA
City: BAKERSFIELD
Contact Phone No.: 861 -0543
Make /Model of Monitoring System: Veeder Root TLS 350
B. Inventory of Equipment Tested /Certified
Check the appropriate boxes to indicate spedflc eauipment Inspected /serviced:
Zip: 93307
Date ofTesting /Servicing: 5/10/2012
Tank ID: Unleaded - REGULAR Tank ID: Diesel - Diesel
r In -Tank Gauging Probe. Model: MAG PROBE r In -Tank Gauging Probe. Model: MAG PROBE
r Annular Space or Vault Sensor. Model: VR-409 r Annular Space or Vault Sensor, Model: VR -409
r Piping Sump / Trench Sensor(s). Model: VR -208 r Piping Sump / Trench Sensor(s). Model: VR-208
r FIII Sump Sensor(s). Model: VR -208 We Fill Sump Sensor(s). Model: VR-208
ri Mechanical Line Leak Detector. Model: Vaporless LD -2000 r Mechanical Line Leak Detector. Model: Veeder Root Fx1DV
r Electronic Line Leak Detector. Model: r Electronic Line Leak Detector. Model:
r Tank Overfill / High -Level Sensor. Model: ATG r Tank Overfill / High -Level Sensor. Model: ATG
E Other (specify equipment a and model in Section E on Page 2). I Other(specify equipment a and model In Section E on Page 2).
Tank ID: Premium - PREMIUM Tank ID:
r In -Tank Gauging Probe. Model: MAG PROBE r In -Tank Gauging Probe. Model:
71 Annular Space or Vault Sensor. Model: VR-409 r Annular Space or Vault Sensor. Model:
r' Piping Sump / Trench Sensor(s). Model: VR -208 Fj Piping Sump / Trench Sensor(s). Model:
r Fill Sump Sensor(s). Model: VR-208 r FIII Sump Sensor(s). Model:
F-7 Mechanical Line Leak Detector. Model: Vaporless LD 2000 r Mechanical Line Leak Detector. Model:
j Electronic Line Leak Detector. Model: j Electronic Line Leak Detector. Model:
r Tank Overfill / High -Level Sensor. Model: ATG j__j Tank Overfill / High -Level Sensor. Model:
i Other (specify equipment a and model in Section E on Page 2). i Other (specify equipment a and model in Section E on Page 2).
Dispenser 1/2 Dispenser 7/8ID: ID:
r Dispenser Containment Sensor(s). Model: VR -208 ri Dispenser Containment Sensor(s). Model: VR -208
P Shear Valve(s). r Shear Valve(s).
r Dispenser Containment Float(s) and Chaln(s). j Dispenser Containment Float(s) and Chaln(s).
Dispenser 3/4 Dispenser 9/10ID: ID:
r Dispenser Containment Sensor(s). Model: VR -208 r Dispenser Containment Sensor(s). Model: VR -208 .
r Shear Valve(s). r Shear Valve(s).
r Dispenser Containment Floats and Chain(s). r Dispenser Containment Floats and Chain(s).
Dispenser 5/6 Dispenser 11/12ID: ID:
ri Dispenser Containment Sensor(s). Model: VR -208 r Dispenser Containment Sensor(s). Model: VR -208
r Shear Valve(s), r Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). r Dispenser Containment Float(s) and Chain(s).
If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification - I certify that the equipment identified in this document was inspected /serviced in accordance with the manufacturers' guidelines. Attached to
this Certification Is information (e.g. manufacturers' checklists) necessary to verify that this Information is correct and a Plot Plan showing the layout of
monitoring equipment. For any equipment capable of generating such reports, I have also attached a copy of the report; (check all that apply): r System set-
up r Alarm history report
Technician Name (print): Edwin Pineda
Certification No.: B37453
Signature:
License. No.:
Erk c.N 11} .A e- k,
743160 Class 'A'
Testing Company Name: Tanknology Phone No.: (800) 800 -4633
Testing Company Address: 11000 N. MoPac Expressway Suite 500
Monitoring System Certification Page 1 of 3
Date of Testing /Servicing: 5/10/2012
12/07
D. Results of Testing/ Servicing
Software Version Installed: 328.03
Complete the following checklist:
C: Yes C` No* Is the audible alarm operational?
Yes f' No* Is the visual alarm operational?
Yes C' No* Were all sensors visually Inspected, functionally tested, and confirmed operational?
Yes r, No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not Interfere wit
their proper operation?
r Yes 111 No* If alarms are relayed to a remote monitoring station, Is all communications equipment (e.g. modem) operational?
0, N/A
f:, Yes tv No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment monitoring
M N/A system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors Initiate positive shut -down? (Check
all that apply) pp y) Fel Sump/Trench Sensors; r Dispenser Containment Sensors.
Did you confirm positive shut -down due to leaks and sensor failure /disconnection? r- Yes; r No
Yes No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no mechanical overfill
r N/A prevention valve is installed), is the overfill warning alarm visible and audible at the tank fill point(s) and operating properly? If
so at what percent of tank capacity does the alarm trigger? 90%
Yes* r No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the
manufacturer name and model for all replacement parts in Section E below.
r Yes* r No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply)
P Product; r Water. If yes, describe causes In Section E below.
M Yes C, No* Was monitoring system set -up reviewed to ensure proper settings? Attach set up reports, if applicable
f:' Yes rt,- No* Is all monitoring equipment operational per manufacturer's specifications?
In Section E below, describe how and when these deficiencies were or will be corrected.
REPLACED SIPHON JET VALVE ON DIESEL
Monitoring System Certification Page 2 of 3 12/07
F. In -Tank Gauging / SIR Equipment: r7, Check this box if tank gauging is used only for inventory control.
Check this box if no tank gauging or SIR equipment Is Installed.
This section must be completed if in -tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
re. Yes r No* Has all Input wiring been inspected for proper entry and termination, Including testing for ground faults?
is Yes No* Were all tank gauging probes visually Inspected for damage and residue buildup?
r Yes` No* Was accuracy of system product level readings tested?
Yes No* Was accuracy of system water level readings tested?
Yes r No* lWere all probes reinstalled properly?
Yes r No* lWere all Items on the equipment manufacturer ?s maintenance checklist completed?
In the Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD): r Check this box if LLDs are not installed.
Complete the following checklist:
I: Yes C' No* For equipment start-up or annual equipment certification was a leak simulated to verify LLD performance? (Check all that4-
r apply) Simulated leak rate: r 3 g.p.h.; r--, 0.1 g.p.h; 0.2 g.p.h. N/A
r-- Yes r No* Were all LLDs confirmed operational and accurate within regulatory requirements?
f: Yes r No* Was the testing apparatus properly calibrated?
r, Yes C No* For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
r N/A
7 Yes r No* For electronic LLDs, does the turbine automatically shut off If the LLD detects a leak?
M N/A
r Yes C No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected?
r N/A
C Yes r No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or falls a test?
r- N/A
r Yes r No* For electronic LLDs, have all accessible wiring connections been visually Inspected?
F- N/A
t: Yes I % No* Were all Items on the equipment manufacturer's maintenance checklist completed?
In the Section H, below, describe how and when these deficiencies were or will be corrected.
Page 3 of 3 12/07
SWRCB, January 2002
Secondary Containment Testing Report Form
Page 1 of 1
This form is intendedfor use by contractors performing periodic testing of UST secondary containment systems. Use the appropriate
pages ofthis form to report resultsfor all components tested. The completed form, written test procedures, and printouts from tests
ifapplicable), should be provided to the facility owner /operatorfor submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: CHEVRON # 355920 jDate of Testing: 5/10/2012
Facility Address: JITB # 7723 10 UNION AVENUE, BAKERSFIELD, CA 93307
Facility Contact: MINTA Phone: 861 -0543
Date Local Agency Was Notified of Testing: 4 /30/2012
Name ofLocal Agency Inspector (if present during testing): Ernie Medina
2. TESTING CONTRACTOR INFORMATION
Company Name: TANKNOLOGY INC.
Pass
Technician Conducting Test: Edwin Pineda
Not
Tested
Credentials: W' CSLB Licensed Contractor r SWRCB Licensed Tank Tester
License Type: A -UT License Number: 743160- 8026748
Manufacturer
Manufacturer Training
Component(s) Date Training Expires
PHILTITE SPILL BUCKET 8/2/2012
OPW SPILL BUCKET 2/3 /2013
3. SUMMARY OF TEST RESULTS
Component Pass Fail Not
Tested
Repair's
Made
Component Pass Fail
Not
Tested
Repairs
Made
Spill Box Unleaded regular fill X
Spill Box Premium premium fill X
Spill Box Diesel diesel fill X
If hydrostatic testing was performed, describe what was done with the water after completion of tests: WATER WAS PUT IN SITE
DISPOSAL DRUMS
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
To the best of my knowledge, the facts stated in this document are accurate and in full compliance with legal requirements
Technician's Signature: DA :N ( f) .A Date: 5/10/2012
W0: 3402214
Page 1 of 1
SPILL /OVERFILL CONTAINMENT BOXES
Facility is Not Equipped With Fill Riser Containment Sumps
Fill Riser Containment Sumps are Present, but were Not Tested r
Test Method Developed By: r Spill Bucket Manufacturers Industry Standard r Professional Engineer
r Other (Specify):
Test Method Used By: r Pressure M Vacuum C., Hydrostatic
r Other (Specify):
Test Equipment Used: KE TEST Equipment Resolution: LO.0625 in.
b 7v.,'.ty,.i. - >:7 rx' ni. a:_ , « -:`:; •5. : «i:" -Sr' ?a .i .: ,':;'k «..'k .rYi?ka_crv_ :r:. att.°Mr''d, z;.; a2s
y.p
xPREMIUM
g`." 4r`rl "K R, E'k'K7GP,1,,.:
i TankUli ea'dedx,EGULAR TaK,PSeITIIU silelTankDiesel SpIII Box #" ^'_
l , n FIII Dlrect n FIII DlrectK
Dl
FIII: ,Direct zP
Bucket Diameter: 11.00 11.00 11.00
Bucket Depth: 14.00 14.00 14.00
Wait time between applying
pressure /vacuum /water and 0 min 0 min 11 min m i n
starting test
Test start 'nme: 09:20:00 09:20:00 09:20:00
Initial Reading oy,: 12.00 in. H2O 12.00 in. H2O 11.00 in. H2O
Test End Time: 10:20:00 10:20:00 10:20:00
Final Reading ow: 12.00 in. H2O 12.00 In. H2O 11.00 In. H2O
Test Duration: 1 hr 1 hr 1 hr
Change in Reading rA,: 0.00 In. H2O 0.00 In. H2O 0.00 In. H2O
Pass /Fall Threshold or Criteria: 0.00 0.00 0.00
aTestResults r Pass tFr.`..
Comments ? (include information on repairs made prior to testing, and recommended follow -up for failed tests)
WO: 3402214
Tanknolog Site Diagram
This site diagram is for reference only and is not drawn to scale)
Work Order: 3402214 Date: 5/10/2012
Site ID / Name: 355920 / CHEVRON # 355920
Address: ]ITB # 772310 UNION AVENUE
City: BAKERSFIELD State: CA Zip: 93307
9
10 L13 45L11 #
1 #
6 #2 l9
11 dsl #7 #3 dsl 8
412 L14 #8 L12 dsl #4 L10 mdslz
F U L3 UL L2 STP I L1
0
F6D
L7 L6 LS GAS'
TP STP I A
ESO SUP
W.O.# SC1- 3402214
I10100
MAY 10, 2012 1:47 PM
CHEVRON 2000
10 UNION AVE.
BAKERSFIELD
STA.35 -5920
SYSTEM STATUS REPORT
ALL FUNCTIONS NORMAL
150301
MAY 10, 2012 1:47 PM
1:CHEVRON 2000
150302
MAY 10, 2012 1:47 PM
2:10 UNION AVE.
I50303
MAY 10, 2012 1:47 PM
3:BAKERSFIELD
150304
MAY 10, 2012 1:47 PM
4:STA.35 -5920
I51700
MAY 10, 2012 1:47 PM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE /TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50F00
MAY 10, 2012 1:47 PM
MON DD YYYY HH:MM:SS xM
I60100
MAY 10, 2012 1:47 PM
TANK CONFIGURATION
DEVICE LABEL
1 UNLEADED
2 PREMIUM
3 DIESEL
4
160200
CONFIGURED
ON
ON
ON
OFF
Cust Ref*: PO# 15092506
MAY'10, 2012 1:47 PM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 UNLEADED
2 PREMIUM
3 DIESEL
4
3
I60300
MAY 10, 2012 1:47 PM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 UNLEADED 1
2 PREMIUM 2
3 DIESEL 3
4 4
I60400
MAY 10, 2012 1:47 PM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 19703
2 PREMIUM 10369
3 DIESEL 7029
4 0
I60700
MAY 10, 2012 1:47 PM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 UNLEADED 117.75
2 PREMIUM 117.75
3 DIESEL 118.00
4 0.00
160900
MAY 10, 2012 1:47 PM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
SIPHON MANIFOLDED TANKS
1 UNLEADED 0.000700
2 PREMIUM 0.000700
3 DIESEL 0.000450
4
DIESEL
0.000000
I61200
MAY 10, 2012 1:47 PM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 UNLEADED NONE NONE
2 PREMIUM NONE NONE
3 DIESEL NONE NONE
4 NONE NONE
I62100
MAY 10, 2012 1:47 PM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 500
2 PREMIUM 500
3 DIESEL 500
4 0
I62200
MAY 10, 2012 1:47 PM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 18718
2 PREMIUM 9850
3 DIESEL 6677
4 0
I62300
MAY 10, 2012 1:47 PM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 17732
2 PREMIUM 9332
3 DIESEL 6326
4 0
162400
MAY 10, 2012 1:47 PM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 2.0
2 PREMIUM 2.0
3 DIESEL 2.0
I62800
MAY 10, 2012 1:47 PM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 19703
2 PREMIUM 10369
3 DIESEL 7029
4 0
162900
MAY 10, 2012 1:47 PM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 2955
2 PREMIUM 1555
3 DIESEL 1054
4 0
I70300
MAY 10, 2012 1:47 PM
LIQU'ID TYPE
10, 2012 10:00
SENSOR LOCATION TYPE
10, 2012
1 UNLEADED ANNULAR TRI -STATE SINGLE FLOAT)
2 UNLEADED STP SUMP TRI -STATE SINGLE FLOAT)
3 UNLEADED FILL TRI -STATE SINGLE FLOAT)
4 SPLIT TANK ANNULAR TRI -STATE SINGLE FLOAT)
5 PREMIUM STP SUMP TRI -STATE SINGLE FLOAT)
6 PREMIUM FILL TRI -STATE SINGLE FLOAT)
7 DIESEL STP SUMP TRI -STATE SINGLE FLOAT)
8 DIESEL FILL TRI -STATE SINGLE FLOAT)
9 DISP. 1 -2 TRI -STATE SINGLE FLOAT)
10 DISP. 3 -4 TRI -STATE SINGLE FLOAT)
11 DISP. 5 -6 TRI -STATE SINGLE FLOAT)
12 DISP. 7 -8 TRI -STATE SINGLE FLOAT)
13 DISP. 9 -10 TRI -STATE SINGLE FLOAT)
14 DISP. 11 -12 TRI -STATE SINGLE FLOAT)
15
2012
TRI -STATE SINGLE FLOAT)
16
10,
TRI -STATE SINGLE FLOAT)
I90200
MAY 10, 2012 1:47 PM
SOFTWARE REVISION LEVEL
VERSION 328.03
SOFTWARE# 346328 -100 -D
CREATED - 08.06.06.17.21
S- MODULE# 330160 -004 -a
SYSTEM FEATURES:
PERIODIC IN -TANK TESTS
ANNUAL IN -TANK TESTS
ISD
I20600
MAY 10, 2012 1:47 PM
CHEVRON 2000
10 UNION AVE.
BAKERSFIELD
STA.35 -5920
TANK ALARM HISTORY
TANK 1 UNLEADED
HIGH WATER ALARM MAY 10, 2012 10:00 AM
OVERFILL ALARM MAY 10, 2012 9:54 AM
HIGH PRODUCT ALARM MAY 10, 2012 9:54 AM
INVALID FUEL LEVEL MAY 10, 2012 9:51 AM
PROBE OUT MAY 10, 2012 10:07 AM
MAY 10, 2012 9:50 AM
HIGH WATER WARNING MAY 10, 2012 10:00 AM
DELIVERY NEEDED MAY 10, 2012 9:51 AM
APR 27, 2012 3:23 PM
APR 23, 2012 8:47 PM
MAX PRODUCT ALARM MAY 10, 2012 9:54 AM
LOW TEMP WARNING MAY 10, 2012 10:09 AM
TANK 2 PREMIUM
HIGH WATER ALARM MAY 10, 2012 10:01 AM
OVERFILL ALARM MAY 10, 2012 9:56 AM
HIGH PRODUCT ALARM MAY 10, 2012 9:57 AM
INVALID FUEL LEVEL MAY 10, 2012 9:53 AM
PROBE OUT MAY 10, 2012 10:11 AM
MAY 10, 2012 9:52 AM
HIGH WATER WARNING MAY 10, 2012 10:01 AM
DELIVERY NEEDED MAY 10, 2012 9:52 AM
1
MAY 9, 2012 7 :59 PM
APR 18, 2012 3:14 AM
MAX PRODUCT ALARM MAY 10, 2012 9:57 AM
TANK 3 DIESEL
ALARM
OCT 3, 2011 4:22
HIGH WATER ALARM MAY 10, 2012 9:56 AM
OVERFILL ALARM MAY 10, 2012 10:03 AM
2012
MAY 10, 2012 9:58 AM
LOW PRODUCT ALARM MAY 10, 2012 9:49 AM
HIGH PRODUCT ALARM MAY 10, 2012 10:03 AM
ALARM
MAY 10, 2012 9:58 AM
INVALID FUEL LEVEL MAY 10, 2012 10:06 AM
AM
MAY 10, 2012 9:49 AM
PROBE OUT MAY 10, 2012 10:05 AM
2012
MAY 10, 2012 9:48 AM
HIGH WATER WARNING MAY 10, 2012 9:56 AM
DELIVERY NEEDED MAY 10, 2012 9:48 AM
MAY 5, 2012 6:16 AM
ALARM
MAR 6, 2012 7:21 AM
MAX PRODUCT ALARM MAY 10, 2012 10:04 AM
I30200
MAY 10, 2012 1:47 PM
CHEVRON 2000
10 UNION AVE.
BAKERSFIELD
STA.35 -5920
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UNLEADED ANNULAR
MAY 10, 2012 9:33 AM FUEL ALARM
MAY 10, 2012 9:24 AM SENSOR OUT ALARM
OCT 3, 2011 4:22 PM FUEL ALARM
2 UNLEADED STP SUMP
MAY 10, 2012 9:31 AM FUEL ALARM
MAY 10, 2012 9:31 AM FUEL ALARM
MAY 10, 2012 9:24 AM SENSOR OUT ALARM
3 UNLEADED FILL
MAY 10, 2012 9:31 AM FUEL ALARM
MAY 10, 2012 9:24 AM SENSOR OUT ALARM
APR 13, 2012 9:04 AM FUEL ALARM
4 SPLIT TANK ANNULAR
MAY 10, 2012 9:28 AM FUEL ALARM
MAY 10, 2012 9:24 AM SENSOR OUT ALARM
OCT 3, 2011 4:24 PM FUEL ALARM
5 PREMIUM STP SUMP
MAY 10, 2012 9:29 AM FUEL ALARM
MAY 10, 2012 9:24 AM SENSOR OUT ALARM
OCT 3, 2011 4:24 PM FUEL ALARM
6 PREMIUM FILL
MAY 10, 2012 9:30 AM FUEL ALARM
MAY 10, 2012 9:24 AM SENSOR OUT ALARM
APR 24, 2012 6:13 PM SENSOR OUT ALARM
7 DIESEL STP SUMP
MAY 10, 2012 9 :24 AM SENSOR OUT ALARM
MAY 10, 2012 9:19 AM FUEL ALARM
OCT 3, 2011 4:25 PM FUEL ALARM
8 DIESEL FILL
MAY 10, 2012 9:24 AM SENSOR OUT ALARM
MAY 10, 2012 9:18 AM FUEL ALARM
APR 25, 2012 9:45 PM FUEL ALARM
h 9 DISP. 1 -2
MAY 10, 2012 9:34 AM FUEL ALARM
MAY 10, 2012 9:24 AM SENSOR OUT ALARM
OCT 3, 2011 4:25 PM FUEL ALARM
10 DISP. 3 -4
MAY 10, 2012 9:34 AM FUEL ALARM
MAY 10, 2012 9:24 AM SENSOR OUT ALARM
OCT 3, 2011 4:26 PM FUEL ALARM
11 DISP. 5 -6
MAY 10, 2012 9:35 AM FUEL ALARM
MAY 10, 2012 9:24 AM SENSOR OUT ALARM
OCT 3, 2011 4:26 PM FUEL ALARM
12 DISP. 7 -8
MAY 10, 2012 9:36 AM FUEL ALARM
MAY 10, 2012 9:24 AM SENSOR OUT ALARM
OCT 3, 2011 4:26 PM FUEL ALARM
13 DISP. 9 -10
MAY 10, 2012 9:36 AM FUEL ALARM
MAY 10, 2012 9:24 AM SENSOR OUT ALARM
OCT 3, 2011 4:27 PM FUEL ALARM
14 DISP. 11 -12
MAY 10, 2012 9:37 AM FUEL ALARM
MAY 10, 2012 9:24 AM SENSOR OUT ALARM
OCT 3, 2011 4:27 PM FUEL ALARM
I10100
MAY 10, 2012 1:48 PM
CHEVRON 2000
10 UNION AVE.
BAKERSFIELD
STA.35 -5920
SYSTEM STATUS REPORT
ALL FUNCTIONS NORMAL