MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State of California
Authority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of
Regulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for
each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system
owner /operator. The owner /operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date.
A. General Information
Facility Name: ARCO AMPM Bldg.
Site Address: _ 6450 White Ln. City: Bakersfield Zip:
Facility Contact Person: Contact Phone No.:
Make/Model of Monitoring System: Veeder -Root TLS -350 Date of Testing /Servicing: _.5j 17 / 2012
B. Inventory of Equipment Tested /Certified
Check the appropriate boxes to Indicatespecific equipment Ins acted /serviced:
Tank ID: North 87 UL Tank ID: 91 UL
X In -Tank Gauging Probe. Model: Maa. X In -Tank Gauging Probe. Model: Mao.
X Annular Space orVault Sensor. Model: 794390 -409 X Annular Space or Vault Sensor. Model: 794390 -409
X Piping Sump / Trench Sensor(s). Model: 794380 -208 X Piping Sump / Trench Sensor(s). Model: 794380 -208
X Fill Sump Sensor(s). Model: 794380 -208 X Fill Sump Sensor(s). Model: 794380 -208
u Mechanical Line Leak Detector. Model: u Mechanical Line Leak Detector. Model:
X Electronic Line Leak Detector. Model: Series 8484 X Electronic Line Leak Detector, Model: Series 8484
Tank Overfill / High -Level Sensor. Model: Tank Overfill / High -Level Sensor. Model:
Other(specify equipment type and model in Section E on Page 2). Other(specify equipment type and model in Section E on Page 2).
Tank 10: South 87 UL Tank ID:
In -Tank Gauging Probe. Model: X In -Tank Gauging Probe. Model: Maa.
X Annular Space or Vault Sensor. Model: 794390 -409 Annular Space or Vault Sensor. Model:
X Piping Sump / Trench Sensor(s). Model: 794380 -208 Piping Sump / Trench Sensor(s). Model:
X Fill Sump Sensor(s). Model: 794380 -208 Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector. Model: Mechanical Line Leak Detector. Model:
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
Tank Overfill / High -Level Sensor. Model: Tank Overfill / High -Level Sensor. Model:
Other specify a ui ment and model in Section E on Pa e 2 . Other (seecify a ui ment a and model in Section E on Page 2).
Dispenser ID: 1 -2 Dispenser ID: 7 -8
X Dispenser Containment Sensor(s). Model: 794380 -208 X Dispenser Containment Sensor(s). Model: 794380 -208
X Shear Valve(s). X Shear Valve(s).
Dis enser Containment Floats and Chain(s). Dispenser Containment Floats and Chain(s).
Dispenser ID: 3 -4 Dispenser ID: 9 -10, 11 -12
X Dispenser Containment Sensor(s). Model: 794380 -208 X Dispenser Containment Sensor(s). Model: 794380 -208
X Shear Valve(s). X Shear Valve(s).
Dis enser Containment Floats and Chain(s). Dispenser Containment Floats and Chain(s).
Dispenser iD'. 5 -6 Dlspenser ID: 13- 14.15 -16
X Dispenser Containment Sensor(s). Model: 794380 -208 X Dispenser Containment Sensor(s). Model: 794380 -208
X Shear Valve(s). X Shear Valve(s).
Dispenser Containment Floats and Chains Dispenser Containment Floats and Chain(s).
If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification - 1 certify that the equipment identified in this document was Inspected /serviced In accordance with the manufacturers'
guidelines. Attached to this Certification is information (e.g. manufacturers' checklists) necessary to verify that this Information Is correct
and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also attached a
copy of the report; (check all that apply): X System set -up X Alarm history report
I I
Technician Name (print): Bruce W. Hinslev Signature: g W
Certification No.: A25212 License. No.: 971259
Testing Company Name: Advanced Compliance Phone No.:(661) 7064321
Testing Company Address: 3707 Littlefalls Ct. Bakersfield, Ca. 93312 Date of Testing /Servicing: 5 / 17 / 2012
Monitoring System Certification Page 1 of4 12/07
2/21/07
D. Results of Testing/Servicing
Software Version Installed: 131.00
Comolete the followina checklist:
X Yes No` Is the audible alarm operational?
X Yes No" Is the visual alarm operational?
X Yes No` Were all sensors visually inspected, functionally tested, and confirmed operational?
X Yes No" Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not interfere with their
proper operation?
Yes No` If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) operational?
X N/A
X Yes No" For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment monitoring system
N/A detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate positive shut -down? (Check all that apply)
X Sump/Trench Sensors; X Dispenser Containment Sensors. Did you confirm positive shut -down due to leaks A sensor
failure /disconnection? X Yes; No.
Yes No' For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no mechanical overfill prevention
X N/A valve is installed), is the overfill warning alarm visible and audible at the tank fill point(s) and operating properly? If so, at what percent
of tank capacity does the alarm trigger? %
Yes' X No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the
manufacturer name and model for all replacement parts in Section E, below.
Yes' X No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) Product; Water. If
es, describe causes in Section E, below.
X Yes No' Was monitoring system set -up reviewed to ensure proper settings? Attach set up reports, if applicable
X Yes No- Is all monitoring equipment operational per manufacturer's specifications?
In Section E below, describe how and when these deficiencies were or will be corrected.
Comments:
2/21/07
Monitoring System Certification Page 2 of 4 12/07
2/21/07
F. In -Tank Gauging / SIR Equipment: X Check this box if tank gauging is used only for inventory control.
Check this box if no tank gauging or SIR equipment is installed.
This section must be completed if in -tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
Yes No* Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
Yes n No' Were all tank gauging probes visually inspected for damage and residue buildup?
Yes No' Was accuracy of system product level readings tested?
Yes No' Was accuracy of system water level readings tested?
Yes No' Were all probes reinstalled properly?
Yes No' Were all items on the equipment manufacturer's maintenance checklist completed?
In the Section H, below, describe how and when these deficiencies were orwill be corrected.
G. Line Leak Detectors (LLD): Check this box if LLDs are not installed.
Complete the following checklist:
X Yes No' For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance? (Check all
N/A that apply) Simulated leak rate: X 3 g.p.h.; 110.1 g.p.h ; [10.2 g.p.h.
X Yes No' Were all LLDs confirmed operational and accurate within regulatory requirements?
X Yes No* Was the testing apparatus properly calibrated?
Yes No' For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
X N/A
X Yes No* For electronic LLDs, does the turbine automatically shut off ifthe LLD detects a leak?
N/A
X Yes No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or
N/A disconnected?
X Yes n No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or
N/A fails a test?
X Yes No' For electronic LLDs, have all accessible wiring connections been visually inspected?
N/A
X Yes No* Were all items on the equipment manufacturer's maintenance checklist completed?
In the Section H, below, describe how and when these deficiencies were or will be corrected.
H. Comments:
Monitoring System Certification Page 3 of 4 12/07
4 2/21/07
Monitoring System Certification
UST Monitoring Site Plan
Site Address: 6450 White Ln. Bakersfield, Ca.
Date map was drawn: L/ 17 / 2012 .
Instructions
If you already have a diagram that shows all required information, you may include it, rather than this page, with your Monitoring System
Certification. On your site plan, show the general layout of tanks and piping. Clearly identify locations of the following equipment, if installed:
monitoring system control panels; sensors monitoring tank annular spaces, sumps, dispenser pans, spill containers, or other secondary
containment areas; mechanical or electronic line leak detectors; and in -tank liquid level probes (if used for leak detection). In the space
provided, note the date this Site Plan was prepared.
Monitoring System Certification Page 4 of 4 12/07
5 2/21/07
SWRCB, January 2006
Spill Bucket Testing Report Form
Thisform is intendedfor use by contractors performing annual testing ofUST spill containment structures. The completedform and
printoutsfrom tests (ifapplicable), should be provided to the facility owner /operatorfor submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: ARCO AMPM I Date ofTesting: 5/17/2012
Facility Address: 6450 White Ln. Bakersfield, Ca.
Facility Contact: Phone:
Date Local Agency Was Notified ofTesting : 5/8/2012
Name of Local Agency Inspector (ifpresent during testing): Ester Duran
2. TESTING CONTRACTOR INFORMATION
Company Name: Advanced Compliance
Technician Conducting Test: Bruce W. Hinsley
Credentials': X CSLB Contractor ICC Service Tech. SWRCB Tank Tester Other (Specify)
License Number(s): 971259
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: X Hydrostatic Vacuum Other
Test Equipment Used: Visual Equipment Resolution:
Identify Spill Bucket (By Tank
Number, Stored Product, etc.
1 87 UL N. 2 87 UL S. 3 91 UL 4
Bucket Installation Type: Direct Bury
X Contained in Sump
Direct Bury
X Contained in Sump
Direct Bury
X Contained in Sump
Direct Bury
Contained in Sum
Bucket Diameter: 11" 11" 11"
Bucket Depth: Ill, 11" 11"
Wait time between applying
vacuum /water and start of test:
10 min. 10 min. 10 min.
Test Start Time (Tj): 12:15 12:15 12:15
Initial Reading (Ri): 9.50" 9.00" 09.00"
Test End Time (TF): 13:15 13:15 13:15
Final Reading (RF): 9.50" 9.00" 09.00"
Test Duration (TF — Tj): 1 Hr. I Hr. 1 Hr.
Change in Reading (RF - Rj): 0.0" 0.0" 0.0"
Pass/Fail Threshold or
Criteria: 0.25" 0.25" 0.25"
Test Result: X Pass Fail X Pass Fail X Pass Fail Pass Fail
Comments — (include information on repairs made prior to testing, and recommendedfollow -upforfailed tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements.
Technician's Signature: w Date: 5117/2012
State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
Advanced CompHanee
3704 Littlefalls Ct.
Bakersfield, Ca. 93308
661 - 706 -4321 Fax# 661 -589 -9329
VAPORLESS MANUFACTURING, INC.
LDT -890 Leak Detector Test Record
Contractor: Advanced Compliance Customer: ARCO AMPM
Date: 5/17/2012 Location: 6450 White Ln. Bakersfield, Ca.
Product: 87 UL Technician: Bruce W. Hinsle
Submersible Pump Identification
Manufacturer: Red'acket Model No.:
Serial No.: Notes:
Leak Detector Identification
Manufacturer: Veeder -Root Description: PLLD
Diaphragm-type:
para. 22
Tamper -proof seal installed:
Piston-type:
Other Style Leak Detector:
Notes:
Leak Detector in Submersible Pump Test at Dispenser
Operating Pump Pressure (psi): 32 para. 15
Gallons per hour rate: 3.0 para. 22
Line pressure with pump shut off (psi): 20 para. 23
Bleed -back Test with pump off (ml): 150 para. 26
Step-through time to full flow (secs): N/A ara. 30
Leak detector stays in leak search position (Yes/No): N/A para. 42
Leak Detector Test
Pass / Fail Notes:
Pass
Complete thermal expansion test before failing leak detector
Advanced CC®lrnpHance
3704 Littlefalls Ct.
Bakersfield, Ca. 93308
661 - 706 -4321 Fax# 661 -589 -9329
VAPORLESS MANUFACTURING, INC.
LDT -890 Leak Detector Test Record
Contractor: Advanced Compliance Customer: ARCO AMPM
Date: 5/17/2012 Location: 6450 White Ln. Bakersfield, Ca.
Product: 91 UL Technician: Bruce W. Hinsle
Submersible Pum p Identification
Manufacturer: Red'acket Model No.:
Serial No.: Notes:
Leak Detector Identification
Manufacturer: Veeder -Root Description: PLLD
Diaphragm-type: Piston-type:
Tamper -proof seal installed: Other Style Leak Detector:
Notes:
Leak Detector in Submersible Pump Test at Dispenser
Operating Pump Pressure (psi): 28 para. 15
Gallons per hour rate: 3.0 para. 22
Line pressure with pump shut off (psi): 19 para. 23
Bleed -back Test with pump off (ml): 95 para. 26
Step-through time to full flow (secs): N/A ara. 30
Leak detector stays in leak search position (Yes/No): N/A para. 42
Leak Detector Test
Pass / Fail Notes:
Pass
Complete thermal expansion test beforefailing leak detector
I
SYSTEM SETUP
MAY 17, 2012 1:29 PI,1
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE. ,,TIME FORMAL'
MON DD YYYY HH :1,11^1: SS xM
ARCO 82818
6450 WHITE LANE
BAKERSFIELD CA.
TANKS-NOT-SYPHONED
SHIFT TIME I DISABLED
SHIFT TIME 2 DISABLED
SHIFT TIME 3 DISABLED
SHIFT TIME 4 DISABLED
TANK PER TST NEEDED WRN
DISABLED
TANK ANN TST NEEDED WRN
DISABLED
LINE RE- ENABLE METHOD
PASS L 114E TEST
LINE PER TST NEEDED WRN
DISABLED
LINE ANN TST NEEDED WRN
DISABLED
PRINT TC VOLUMES
ENABLED
TEMP COMPENSATION
VALUE (DEG F ): 60.0
STICK HEIGHT OFFSET
DISABLED
ULLAGE: 90%
H- PROTOCOL DATA FORMAT
HEIGHT
PRECISION TEST DURATION
HOURS: 12
DAYLIGHT SAVING TIME
ENABLED
START DATE
APR WEEK 1 SUN
START TIME
2:00 AM
END DATE
OCT WEEK 6 SUN
END TIME
2:00 AM
REDIRECT LOCAL PRINTOUT
DISABLED
EURO PROTOCOL PREFIX
S
SYSTEM SECURITY
CODE : 000000
MAINTENANCE HISTORY
DISABLED
TANK CHART SECURITY
DISABLED
CUSTOM ALARMS
DISABLED
SERVICE 140T I CE
DISABLED
ISO 3166 COUNTRY
CODE:
VAPOR MONITORING TYPE
GARB ISD
MASS /DENSITY
DISABLED
COMMUNICATIONS SETUP
PORT SETT I 1,1GS :
COh11,1 BOARD : 3 ( ED 1 M i
RS -2.32 SECURITY
CODE : DISABLED
COMM BOARD 5 (RS -485)
BAUD RATE 2400
PARITY EVEN
STOP BIT l STOP
DATA LENGTH: 7 DATA
RS -232 SECURITY
CODE : DISABLED
C:OMM BOARD 6 (RS-232)
BAUD RATE 2400
PARITY ODD
STOP BIT I STOP
DATA LENGTH: 7 DATA
RS -232 SECURITY
CODE : DISABLED
AUTO TRANSMIT SETTINGS:
AUTO LEAK ALARM LIMIT
DISABLED
AUTO HIGH WATER LIMIT
DISABLED
AUTO OVERFILL LIMIT
DISABLED
AUTO LOW PRODUCT
DISABLED
AUTO THEFT LIMIT
DISABLED
AUTO DELIVER! START
DISABLED
AUTO DELIVERY END
DISABLED
AUTO EXTERNAL INPUT ON
DISABLED
AUTO EXTERNAL INPUT OFF
DISABLED
AUTO SENSOR FUEL ALARM
DISABLED
AUTO SENSOR WATER ALARM
DISABLED
AUTO SENSOR OUT ALARM
DISABLED
RS -232 ENI) OF MESSAGE
DISABLED
IN -TANK, SETUP
T 1:87 SOUTH
PRODUCT CODE 1
THERMAL COEFF :.000700
TANK. DIAMETER 9'2 .00
TANK PROFILE 20 PTS
FULL VOL 11627
87.4 INCH VOL : 11422
828 INCH VOL 1 1066
78..2 INCH VOL 10500
73.6 INCH VOL : 10049
69.0 I NCH VOL 9438
64.4 INCH VOL 8775
59.8 I NCH VOL : 8085
55.2 I14CH VOL : 7350
50.6 INCH VOL 6590
46.0 INCH VOL : 5814
41.4 INCH VOL 5040
36.8 INCH VOL 4290
32.2 INCH VOL 3555
27.6 INCH VOL 2850
23.0 INCH VOL 2190
18.4 I NCH VOL 1580
13.8 INCH VOL 1035
9.2 INCH VOL 560
4.6 INCH VOL 200
FLOAT SIZE: 2.0 IN.
WATER WARNING 0.8
HIGH WATER LIMIT: 1.5
WATER ALARM FILTER: LOW
MAX OR LABEL VOL: 11627
OVERFILL LIMIT 90%
10464
HIGH PRODUCT 95%
11045
DELIVERY LIMIT 100
1162
LOW PRODUCT 500
LEAK ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 50
TANK TILT 0.00
PROBE OFFSET 0.00
SIPHON I11ANIFOLDED TANKS
TO: NONE
LINE MANIFOLDED TANKS
TO: 02
LEAK, MIN PERIODIC: 25%
2906
LEAK 1 °1I N ANNUAL 50%
5813
PERIODIC TEST TYPE
STANDARD
ANNUAL TESALARMLDISABLED
PERIODIC TALARMADISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING; OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY
13 ,
1OPUMPTHRESHOLD
T 2:87 CENTER
WATER WARNING :
PRODUCT
THERMAL
CODE
COEFF
1
000700
TANK DIAMETER
LO1
052000TANKPROFILE
OVERFILL LIMIT
20 P
11627
92.00
FULL VOL
HIGH PRODUCT
87.4 INCH VOL 11422
02,13 I NCH VOL 16611066
78.2 INCH VOL 10500
73.6 INCH VOL 1903969.0 INCH VOL
64.4 INCH VOL 8775
59.8 INCH VOL 8085
55.2 INCH VOL 7350
50.6 INCH VOL 6590
46.0 INCH VOL 5814
41.4 INCH VOL 0504504036.0 INCH VOL
VOL
32.2 INCH VOL 3555
27.6 INCH VOL 2550
23.0 INCH VOL 190219C18.4 INCH VOL 1
158C
13.8 INCH VOL 56056C9.2 INCH VOL
4.6 INCH VOL
3555
FLOAT SIZE: 2.0 IN
WATER WARNING : 0.1
HIGH WATER LIMIT: 1•'
WATER ALARM FILTER: LO1
MAX OR LABEL VOL: 1190' OVERFILL LIMIT
92.00
1046
HIGH PRODUCT 95
1104
DELIVERY LIMIT 116
LOW PRODUCT : 5C
LEAK ALARM LIMIT:
INCH
SUDDEN LOSS LIMIT: 0ITANKTILT0 IPROBEOFFSET
11066
SIPHON MANIFOLDED TANK'
TO: NONE
LINE MANIFOLDED TANKS
T#: DI
73.6
LEAK 1,1111 PERIODIC:: 25%
2906
LEAK. MIN ANNUAL 50%
5813
PERIODIC- TEST TYPE
STANDARD
ANNUAL TEST FAIL
ALARP9 DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK::OFF
DELIVERY DELAY 3 MIN
PUMP THRESHOLD : 10.00%
T 3 :91 NORTH
PRODUCT CODE 2
THERMAL COEFF 000700
TANK: DIAMETER 92.00
TANK'. PROFILE 20 PTS
FULL VOL 11627
87.4 INCH VOL 11422
82.8 INCH VOL 11066
78.2 INCH VOL 10500
73.6 INCH VOL 10049
69.0 INCH VOL 9438
64.4 INCH VOL 8775
59.8 INCH VOL 8085
55.2 INCH VOL 7350
50.6 INCH VOL 6590
46.0 INCH VOL 5814
41.4 INCH VOL 5040
36.8 INCH VOL 4290
32.2 INCH VOL 3555
27.6 INCH VOL 2850
23.0 INCH VOL 2190
18.4 INCH VOL 1580
13.8 INCH VOL 1035
9.2 INCH VOL 560
4.6 IIVCH VOL 200
FLOAT SIZE: 2.0
WATER WARNING 0.8
HIGH WATER LIMIT: 1.5
WATER ALARM FILTER: LOW
MAX OR LABEL VOL: 11627
OVERFILL LIMIT 901/6
10464
HIGH PRODUCT 95%
11045
DELIVERY LIMIT 10%
1162
LOW PRODUCT 500
LEAK. ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 50
TANK TILT 0.00
PROBE OFFSET 0.00
SIPHON MANIFOLDED TANKS
T#: NONE
LINE HANIFOLDED TANKS
TO: NONE
LEAK MIN PERIODIC: 25%
2906
LEAK. MIN ANNUAL 5014
5813
PERIODIC TEST TYPE
STANDARD
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC: TEST FLAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIP °HON BREAK:OFF
DELIVER' DELAY 3 111 I N
PUMP THRESHOLD 10.00%
LEAK TEST METHOD
TEST ON DATE : ALL TANK:
FEB 6. 2007
START TIME : DISABLED
TEST RATE :0.20 GAL /HR
DURATfON : 2 HOURS
TST EARLY STOP:DISABLEL,
LEAK TEST REPORT FORMAT
NORMAL
PRESSURE LINE LEAF: SETUP
0 (:REGULAR
TYP : 2.0/3.0 I N FIBERGLASS
01N DIA LEN: 1200 FEET
3.0111 DIA LEN: 0 FEET
SHUTDOWN RATE: 3.0 GPH
LOW PRESSURE SHUTOFF:NO
LOW PRESSURE : 0 PSI
T 1:67 SOUTH L 4:87 AUX OUTPUT RELAY SETUPDISPENSEMODE: TRI —STATE FLOAT) MANIFOLDED: ALTERNATE CATEGORY
SINGLE
ANNULAR SPACESENSOR: NON— VENTED R 1 :87 AUx
PRESSURE OFFSET: O.OPSI TYPE:
PUMPPUMP CONTROL OUTPUT' MECHANICAL BLENDER: NO 5:87 FILL AUX TANK 4: 2
TRI —STATE SINGLE FLOAT)
CATEGORY PIPING SUMP
IN —TANK ALARMS
T 2:HIGH WATER ALARM
L 6:87 STP AUK'. T 2 : LOW PRODUCT ALARM
TRI —STATE SINGLE FLOAT)
CATEGORY STP SUMP LIQUID SENSOR ALMS
L 3:FUEL ALARM
L 6:FUEL ALARM
L 7:91 ANNULAR L 9:FUEL ALARM
TRI —STATE SINGLE FLOAT) L10:FUEL ALARM
Q 2:PREI °IIUM CATEGORY ANNULAR SPACE L11:FUEL ALARM
L12:FUEL ALARM
TYP:2.0,,3.OIN FIBERGLASS L13:FUEL ALARM2.01N DIA LE14: 200 FEET L14:FUEL ALARM
L 8 :91 FILL L15:FUEL`ALARM
3.0Ifd DIA LEN: 0 FEET TRI —STATE SINGLE FLOAT) L 3:SENS+F OUT ALARM
SHUTDOWN RATE: 3.0 GPH CATEGORY PIPING SUMP L 6 :SEN20R OUT ALARM
L 9:SENSOR OUT ALARMLOWPRESSURESHUTOFF :YES LIO :SENSOR OUT ALARMLOWPRESSURE : 0 PSI L 9 :91 STP LII:SENSOR OUT ALARM
T 3:91 NORTH TRI —STATE SINGLE FLOAT) L12 :SENSOR OUT ALARM
CATEGORY STP SUMP L13:SENSOR OUT ALARMDISPENSEMODE: L14:SENSOR OUT ALARMSTANDARDL15:SENSOR OUT ALARMSENSOR: NON — VENTED Ll0:DISP 1 -2 L 3:SH0RT ALARMPRESSUREOFFSET: O.OPSI TRI —STATE SINGLE FLOAT) L 6 :SHORT ALARM
CATEGORY DISPENSER PAN L 9:SHORT ALARMMECHANICALBLENDER: NO 1-10:SHORT ALARM
L11:SHORT ALARM
L)2:SH0RT ALARM
L11:DISP 3 -4 L13:SHORT ALARM
TRI —STATE SINGLE FLOAT) L14 :SHORT ALARM
CATEGORY DISPENSER PAN L15 :SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES WARN
L12:DISP 5 -6 ISD GROSS PRES: FAIL
TRI —STATE SIf*3LE FLOAT)
CATEGORY DISPENSER PAN ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAILLINELEAKLOCKOUTSETUP
ISD HOSE ALARMS
LOCKOUT SCHEDULE L13:DISP 7 -8 ALL:GROSS COLLECT FAILDAILYTRI —STATE SINGLE FLOAT) ALL:DEGRD COLLECT FAILSTARTTIME: DISABLED CATEGORY DISPENSER PAN ALL:FI.OW COLLECT FAILSTOPTIME : DISABLED
R ':':OVERFILL ALARM
TYPE:
L14 :DISP 9 -10 STANDARD
TRI —STATE SINGLE FLOAT) NORMALLY OPEN
CATEGORY DISPENSER PAN
TANK 0: NONE
L15:DISP 11 -12 IN —TANK ALARM'S
TRI— STATE (SINGLE FLOAT) ALL:OVERFILL ALARM
CATEGORY : DISPENSER PAN ALL:HIGH PRODUCT ALARM
LIQUID SENSOR SETUP ALL:MAk PRODUCT ALARM
L 1:87 ANNULAR MAIN
TRI —STATE (SINGLE FLOAT)
CATEGORY : ANNULAR SPACE
L 2:87 FILL IhA I N
TRI —STATE (SINGLE FLOAT)
CATEGORY : OTHER SENSORS
L 3:87 STP MAIN
TRI —STATE < SINGLE FLOAT)
CATEGORY : STP SUMP
ISD SETUP FAIL
ISD GROSS ^PRES FAIL ISD HOSE TABLEPLLDLINEDISABLESETUPISDDEGRDPRESFAILIDFPFLHL AA RR
ISD VAPOR LEAK FAIL
ALL:GROSS COLLECT FAIL
ISD SETUP FAIL 01 00 01 02 01 Ol0I:REGULAR ISD SENSOR OUT FAIL 02 01 02 02 01 Ol
4:
03 02 03 02 02 01IN -TANK ALARMS ISD HOSE ALARMS 04 03 04 02 02 01T1:HIGH WATER ALARM ALL:GROSS COLLECT FAIL U5 04 05 02 03 01T2:HIGH WATER ALARM ALL:DEGRD COLLECT FAIL 06 05 06 02 03 01T1:LOW PRODUCT ALARM ALL:FLOW COLLECT FAIL 07 06 07 02 04 01
9:
08 07 08 02 04 01LIQUIDSENSORALMS
10:
09 08 09 02 05 O1L3:FUEL ALARM 10 09 10 02 05 O1L6:FUEL ALARM 11 10 11 02 06 01L9:FUEL ALARM 12 11 12 02 06 o1L1O :FUEL ALARM
L11:FUEL ALARM
L11:FUEL ALARM
L1:2 :FUEL ALARM
L12:FUEL ALARM ISD AIRFLOW METER MAPL13:FUEL ALARM
HEALY VAC
ID SERIAL NUM LABELL14:FUEL ALARM
L15:FUEL ALARM
NOZZLE AiL RANGE
1 14891 DISP 1 -1L3:SENSOR OUT ALARM SMARTSEhJSOR SETUP 2 14879 DISP 3 -4L6:SENSOR OUT ALARM 3 14877 DISP 5 -6L9:SENSOR OUT ALARM
VAPOR PROCESSOR TYPE
4 14894 DISP 7 -8LIO:SENSOR OUT ALARM I:DISP 1 -2 5 14838 DISP 9 -10LlI:SENSOR OUT ALARM CATEGORY AIR FLOW METER 6 14878 DISP 11 -12L12:SENSOR OUT ALARM
VAPOR PROCESSOR TYPEL15:SENSOR OUT ALARM
L13:SENSOR OUT ALARM s 2:DISP 3 -4
L 9:SHORT ALARM
L14:SENSOR OUT ALARM CATEGORY AIR FLOW METER ISD FUEL GRADE HOSE MAPL15:SENSOR OUT ALARM
PROCESSOR CONTROL LEVEL:
1 2 3 4L3:SHORT ALARM s 3:DISP 5 -6 FP MHH MHH MHH MHH AAL6:SHORT ALARM CATEGORY AIR FLOW METER
ACCEPT HIGH ORVR:
L 9:SHORT ALARM 00 401 501 901 U U 11-10:SHORT ALARM s 4:DISP 7 -8 01 402 502 902 U U 1Lll:SHORT ALARM CATEGORY AIR FLOW METER 02 403 503 903 U U 2L12:SHORT ALARM 03 404 504 904 U U 2L13:SHORT ALARM s 5:DISP 9 -10 04 405 505 905 U U 3L14:SHORT ALARM CATEGORY AIR FLOW METER 05 406 506 906 U U 3L15:SHORT ALARM 06 407 507 907 U U 4
s 6:DISP 11 -12 07 408 508 908 U U 4ISDSITEALARMSCATEGORYAIRFLOWMETER08409509909UU5ISDGROSSPRESFAIL09410510910UU5ISDDEGRDPRESFAILs8:PRESSURE SENSOR 10 411 511 911 U U 6ISDVAPORLEAKFAILCATEGORYVAPORPRESSURE11412512912UU6
ISD SETUP FAIL
ISD SENSOR OUT FAIL LABEL TABLE
ISD HOSE ALARMS 1: UNASSIGNEDALL:GROSS COLLECT FAIL 2: BLENDS
ALL:DEGRD COLLECT FAIL 3: REGULARALL:FLOW COLLECT FAIL 4: MID GRADE
5: PREN I UM02:PREMIUM 6: GOLD
7: BRONZE114 -TANK ALARMS 8 : SILVERT3:HIGH WATER ALARM 9: BLEND2
T 3:LOW PRODUCT ALARM 10: BLEND4
E'VR /ISD SETUPLIQUIDSENSORALMS
L 9:FUEL ALARM
LIO:FUEL ALARM
L11:FUEL ALARM EVR TYPE: VACUUM ASSISTL1:2 :FUEL ALARM VACUUM ASSIST TYPEL13:FUEL ALARM HEALY VACL14:FUEL ALARM
L15:FUEL ALARM NOZZLE AiL RANGEL9:SENSOR OUT ALARM MAX: 1.15 MIN: 0.95L10:SENSOR OUT ALARM PMC SETUPLII :SENSOR OUT ALARM VAPOR PROCESSOR TYPEL12:SENSOR OUT ALARM NONE PMC VERSI0h1: 01.04L13:SENSOR OUT ALARM
L14:SENSOR OUT ALARM VAPOR PROCESSOR TYPEL15:SENSOR OUT ALARM ANALYSIS TIMES NONE
L 9:SHORT ALARM TIME: 9:45 AM1-10 :SHORT ALARM DELAY MINUTES: I PROCESSOR CONTROL LEVEL: L11:SHORT ALARM 14ONE
L12:SHORT ALARM
L13:SHORT ALARM ACCEPT HIGH ORVR: L14:SHORT ALARM DISABLEDL15:SHORT ALARM
SOFTWARE REVISION LEVEL
VERSION 131.00
SOFTWARE# 346131 -100 -A
CREATED - 11.02.10.13.03
S- HODULE0 300160-004-a
SYSTEM FEATURES:
PERIODIC IN -TANK, TESTS
ANNUAL IN -TANK TESTS
I STS ,,APM
PRESSURE LINE LEAK DIAG
MAY 17, 2012 1:31 Pil
0 1- REGULAR
DISPENSING ENABLED
DISPENSING
PUMP ON
HANDLE ON
34.131 PSI
A!D COUNTS
LOW REF = 5819 CNTS
HIGH REF - 1490 1_NTS
SENSOR = 1951 CNTS
0 2:PREMIUM
DISPENSING ENABLED
TEST COI °iPLETE
PUMP OFF
HANDLE OFF
20.076 PSI
A./D COUNTS
LOW REF = 5819 CNTS
HIGH REF - 1490 CNTS
SENSOR = 2686 CNTS
ALARI.9 HISTORY REPORT
SYSTEM ALARM - - --
PAPER OUT
MAY 9, 2012 4:15 AM
PRINTER ERROR
MAY 9. 2012 4:15 AM
x x END
ALARM HISTORY REPORT
IN -TANK ALARM - - - --
T 1:07 SOUTH
OVERFILL ALARM
APR 12, 2012 9:17 AM
APR 3, 2012 4:25 AM
LIAR 19, 2012 1:55 PM
LOW PRODUCT ALARM
SEP 8, 2011 10:54 PM
AUG 19, 2011 8:28 PM
HIGH PRODUCT ALARI °I
JAN 5, 2012 9:29 Phl
PROBE OUT
SEP 7. 2011 2:45 PM
SEP 7, 2011 11:50 All
SEP 7, 21711 11:47 All :..
HIGH WATER WARNING
DEC 1, 2011 1:09 All
OCT 19. 2011 1:50 PM
DELIVERY NEEDED
APR 27. 2012 7:41 PM
APR 20, 2012 5:12 PM
SEP 8, 2011 7:58 Pll
LOW TEMP WARNING
SEP 7, 2011 11:47 AM
SEP 7. 2011 11:41 All
SEP 7. 2011 11:38 All
A A x* END x* x x x
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 1:07 ANNULAR MAIN
ANNULAR SPACE
FUEL ALARM
MAY 17, 2012 9:52 AM
SETUP DATA WARNING
AUG 31, 2011 11:58 AM
SETUP DATA WARNING
AUG 31, 2011 9:20 AM
x X A x END w x x ri A
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 2:87 FILL MAIN
OTHER SENSORS
FUEL ALARM
MA;' 17, 2012 9:44 AM
n nA x E ND ri; t n X
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 3:87 STP MAIN
STP SUMP
FUEL ALARM
MAY 17, 2012 10:22 AM
x :; ;; z A END x_ A)(
I
ALARM HISTORY REPORT
SENSOR ALARM --
L 4:87 AUX
ANNULAR SPACE
FUEL ALARM
MAY 17, 2012 9:54 AM
SETUP DATA WARNING
AUG 31, 2011 11:51 AM
SETUP DATA WARNING
AUG 31. 2011 9:20 All
x x x x x END x x x x x
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 5:87 FILL AUX
PIPING SUMP
FUEL ALARM
MAY 17, 2012 9:46 AM
x x x x x END x x x x X
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 6:87 STP AUX
STP SUMP
FUEL ALARM
MAY 17, 2012 10:18 AM
x X X END x x x x
ALARM HISTORY REPORT
SENSOR ALAR111 - - - --
L 7:51 ANNULAR
ANNULAR SPACE
FUEL ALARM
MAY 17, 2012 9:55 All
SETUP DATA WARNING
AUG 31. 2011 11:44 All
SETUP DATA WARNING
AUG 31. 2011 9:20 All
x x x x x END x X x x x
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 8:91 FILL
PIPING SUMP
FUEL ALARM
MAY 17, 2012 9:48 AM
A x x x x END x X X x X
ALARM HISTORY REPORT
SENSOR ALARM - - - -- L 9:91 STP
STP SUMP
FUEL ALARM
MAY 17. 2012 10:14 All
x x x x x END x x x )e X
ALARM HISTORY REPORT
SENSOR ALARM - - - -- L10:DISP 1 -2DISPENSER. PAN
FUEL ALARM
MAY 17, 2012 10:10 All
X x x x x END x* x x x
ALARM HISTORY REPORT
SENSOR ALARM - - -- L11:DISP 3 -4
DISPENSER PAN
FUEL ALARM
MAY 17, 2012 10:09 All
x x x x x ENE) X t X x x