MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State of California
Authority Cited: Chapter 6 7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code ofRegulations
This form must be used to document testing and servicing of monitoring equipment. A seoarate certification or report must be prepared for each
monitoring "gym control parcel by the technician who performs the work. A copy ofthis form must be provided to the tank system owner /operator.
The owner /operator must submit a copy of this form to. the local agency regulating UST systems within 30 days oftest date.
A. General Information
Facility Name: GOSFORD SHELL Bldg. No.:
Site Address: 4050 GOSFORD RD. City: BAKERSFIELD Zip: 93309
Facility Contact Person: HENG Contact Phone No.: (661) 304 -4083
Make/Model of Monitoring System: TLS -350 Date ofTesting/Servicing: 61212011
B. Inventory of Equipment Tested/Certified
Cheek the appropriate boxes to indicate specific equipment inspected/serviced:
Tank ID: REG. 87 #1 Tank ID: REG. 87 #2
Z In -Tank Gauging Probe. Model: MAG In -Tank Gauging Probe. Model: MAG
Annular Space or Vault Sensor. Model: 304 Annular Space or Vault Sensor. Model: 301
Z Piping Sump / Trench Sensor(s). Model: 208 Piping Sump / Trench Sensor(s). Model: 208
Fill Sump Sensor(s). Model: 208 Fill Sump Sensor(s). Model: 208
Mechanical Line Leak Detector. Model: Mechanical Line Leak Detector. Model:
Electronic Line Leak Detector. Model: VEEDEROOT Electronic Line Leak Detector. Model: VEEDEROOT
Tank Overfill / High -Level Sensor. Model: FLAPPER Tank Overfill / High -Level Sensor. Model: FLAPPER
Other (specify equipment type and model in Section E on Page 2). Other (specify equipment type and model in Section Eon Page 2).
Tank ID: PREM 91 Tank ID: DIESEL
Z In -Tank Gauging Probe. Model: MAG Z In -Tank Gauging Probe. Model: MAO
Z Annular Space orVault Sensor. Model: 301 Z Annular Space or Vault Sensor. Model: 301
Z Piping Sump / Trench Sensor(s). Model: 208 Z Piping Sump / Trench Sensor(s). Model: 208
Fill Sump Sensor(s). Model: 208 Z Fill Sump Sensor(s). Model: 208
D Mechanical Line Leak Detector. Model: D Mechanical Line Leak Detector, Model:
Z Electronic Line Leak Detector. Model: VEEDEROOT Z Electronic Line Leak Detector. Model: VEEDEROOT
Z Tank Overfill / High -Level Sensor. Model: FLAPPER Z Tank Overfill / High -Level Sensor. Model: FLAPPER
D Other (specify equipment type and model in Section E on Page 2). D Other (specify equipment type and model in Section E on Page 2).
Dispenser ID: 112 Dispenser ID: 314
Dispenser Containment Sensor(s). Model: 208 Dispenser Containment Sensor(s). Model: 208
Shear Valve(s). Z Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
Dispenser ID: 516 Dispenser ID: 718
Z Dispenser Containment Sensor(s). Model: 208 Z Dispenser Containment Sensor(s). Model: 208
Shear Valve(s). Shear Valve(s).
D Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
Dispenser ID: Dispenser ID:
Dispenser Contaimnent Sensor(s). Model: D Dispenser Containment Sensor(s). Model:
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
Ifthe facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C Certification - I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers'
guidelines. Attached to this Certification is information (e.g. manufacturers' checklists) necess o verify that this information is
correct and a Plot Plan showing the layout of monitoring equipmenL For any equi ment capabl enerating such reports, 1 have also
attached a copy of the report; (check all that apply): ® System set -up g Alarm ' report
Technician Name (print): RICH PHILLIPS Signature:
Certificatiori No.: A29M 1 1035169 -UT License. No.: C61 I D40 809860
Testing Company Name: .RICH ENVIRONMENTAL Phone No.: (661) 392 -8687
Testing Company Address: 5643 BROOKS CT. BAKERSFIELD, CA. 93308 Date ofTesting/Servicing: 612/2011
Page 1 of 5
UN-036 —1/4 www.unidocs.org Rev. 01/17/08
17— 5 $`f
Monitoring System Certification
D. Results of Testing/Servicing
Software Version Installed: 327.04
Com lete the foliowin checklist:
Yes No* Is the audible alarm operational?
Yes No* Is the visual alarm operational?
Yes No* Were all sensors visually inspected, functionally tested, and confirmed operational?
Yes No Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will 1notinterferewiththeirproperoperation?
Yes [] No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem)
N/A operational?
Yes No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
N/A monitoring system detects a leak, fails to operate, or is electrically disconnected? Ifyes: which sensors initiate
positive shut -down? (Check all that apply) ® Sump/Trench Sensors; ® Dispenser Containment Sensors.
Did you confirm positive shut -down due to leaks and sensor failure /disconnection? ® Yes; No.
Yes No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no
N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank
fill point(s) and operating properly? Ifso, at what percent oftank capacity does the alarm trigger? %
Yes* ® No Was any monitoring equipment replaced? Ifyes, identify specific sensors, probes, or other equipment replaced
and list the manufacturer name and model for all replacement parts in Section E, below.
Yes* ® No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply)
Product; Water. Ifyes, describe causes in Section E, below.
Yes p No* Was monitoring system set -up reviewed to ensure proper settings? Attach set up reports, if applicable
Yes No* Is all monitoring equipment operational per manufacturer's specifications?
In Section E below, describe bow and when these deficiencies were or will be corrected.
F. Comments:.
Page 2 of 5
UN -036 — 2/4 www.unidocs.org Rev. 01/17/08
Monitoring System Certification
F. In -Wank Gauging / SIR Equipment: Check this box if tank gauging is used only for inventory control.
Check this box if no tank gauging or SIR equipment is installed.
This section must be completed if in -tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
Yes No* Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
Yes No* Were all tank gauging probes visually inspected for damage and residue buildup?
Yes No* Was accuracy of system product level readings tested?
Yes No* Was accuracy ofsystem water level readings tested?
Yes No* Were all probes reinstalled properly?
Yes I No* Were all items on the equipment manufacturer's maintenance checklist completed?
In Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD):
ramnlwtp thr fnllnwinv eheckliat-
Check this box ifLLDs are not installed.
Yes No* For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance?
N/A Check all that apply) Simulated leak rate: ® 3 g.p.h.; 0.1 g.p.h ; 0.2 g.p.h.
Yes No* Were all LLDs confirmed operational and accurate within regulatory requirements?
Yes No* Was the testing apparatus properly calibrated?
Yes No* For mechanical LLDs, does the LLD restrict product flow ifit detects a leak?
N/A
0 Yes No* For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak?
N/A
Yes No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled
N/A or disconnected?
Yes No* For electronic LLDs, does the turbine automatically shut offif any portion of the monitoring system malfunctions
N/A or fails a test?
Yes No* For electronic LLDs, have all accessible wiring connections been visually inspected?
0 N/A
Yes p No* Were all items on the equipment manufacturer's maintenance checklist completed?
In Section H, below, describe bow and when these deficiencies were or will be corrected.
H. Comments:
L N- 036 — 3/4 .
Page 3 of 5
www.unidocs.org Rev. 01/17108
Ming System Certification
Monitorine .Site
Bite Address:
i
IQs: = - - -,
b - - - . . . . . . . . . . . . . . . . . . . . . . e . . . • - - - - - ..
r - .
r . .. . r - - - - - . - - - . - - - - . .
r - - - - - - - - - - - - - - - - • • - - -
J- 3 - - - - - - - - - - - - - - -- -...... -..
Date map was drawn: .
Ins' - actions
zags
If you already have a diagram that shows all required information, you may include it, rather than this page, with your
Monitori4g S.ystesn Certification. On your site plan, show the general layout`oftanks and piping. CIearly identify
locations of the following equipment, if installed: monitoring systetit control panels; sensors monitoring tank annularspaces,'sumps, dispenser pans, spill containers, or other secondary containment areas; mechanical or electronic line leak
detectors; and:in ;tank liquid level probes (ifused for leak detection). In the space provided, note the date this Site Plan
was prepared.
Page _ o f_ 0510D
za
Monitoring System Certification Form: Addendum for Vacuum/Pressure Interstitial Sensors
1. Results of Vacuum/Pressure Monitoring Equipment Testing
This page should be used to document testing and servicing of vacuum and pressure interstitial sensors. A copy of
this form must be included with the Monitoring System Certification Form, which must be provided to the tank
system owner /operator. The owner /operator must submit a copy of the Monitoring System Certification Form to the
local agency regulating UST systems within 30 days oftest date.
Manufacturer: NIA Model: System Type: Pressure; Vacuum
Sensor IID
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
How was interstitial communication verified?
Leak Introduced at Far End ofInterstitial Space;' Gauge; Visual Inspection; Other (Describe in Sec. J, below)
Was vacuum /pressure restored to operating levels in all interstitial spaces? Yes No (Ifno, describe in Sec. J, below)
J. Comments: N/A
Page 4 of 5
If the sensor successfully detects a simulated vacullm/pressure leak introduced in the interstitial space at the furthest point from thesensor, vacuum/pressure has been demonstrated to be communicating throughout the interstice.
UN -036A -1 /1 www.uftidDcs.org Rev. 01/26/06
23Lki " , SWRCB, January 2006
Spill Bucket Testing Report Form
Thisform is intendedfor use by contractors performing annual testing ofUST spill containment structures. The completedform and
printouts from tests (fapplicable), should beprovided to thefacility owner /operatorfor submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: SHELL STATION Date ofTesting: 6/2/11
Facility Address: 4050 GOSFORD RD. BAKERSFIELD
Facili Contact: HENG Phone: (661) 3044083
Date Local Agency Was Notified of Testing :
Name of Local Agency Inspector (fpreseni during testing):
2. TESTING CONTRACTOR INFORMATION
Company Name: RICH ENVIRONMENTAL
Technician Conducting Test: RICH PHILLIPS
Credentials': CSLB Contractor X ICC Service Tech. SWRCB Tank Tester Other (Spec)
License Number(s): 1035169 -UT
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: X Hydrostatic Vacuum Other
Test Equipment Used: VISUAL Equipment Resolution: 0.00
Identify Spill Bucket (By Tank
Number, StoredProduct, etc. )
MMM
1
REGULAR 87 -FILL
2 PREMHUM 91-
FILL
3
DIESEL FILL
4
REG 87 #2
Bucket Installation Type: Direct Bury
X Contained in Sump
Direct Bury
X Contained in. Sump
Direct Bury
X Contained in Sump
Direct Bury
X Contained in Sum
Bucket Diameter: 12" 12" 12" 12"
Bucket Depth: 14" 14" 14" 14"
Wait time between applying
vacuum/water and start oftest:
30 MIN 30 MIN 30 MIN 30 MIN
Test Start Time (T): 10:00AM 10:00AM 10:00AM 10:00AM
Initial Reading (Ri): 12" 12" 12" 12"
Test End Time (TF): 11:00AM 1 l :00AM 11:00AM 11:00AM
Final Reading (RF): 12" 12" 12" 12"
Test Duration (TF — Tj): 1 -HOUR 1 -HOUR 1 -HOUR I -HOUR
Change in Reading (RF - Ri): 0 0 0 0
Pass/Fail Threshold or
Criteria: 0.00 0.00 0.00 0.00
IBM my ®r
Comments -- (include information on repairs made prior to testing; andrecommendedfollow -upforfailed tests)
CERTIFICATION OF TEICHN!lPfiN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the Information co in this report is true, accurate, and infull compliance with legal requirements.
Technician's Signature: Date: 6/2/11
State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
c1z3 &y
RICH ENVIRO"ENTAL
5643 BROOKS CT. BAKERSFIELD, CA. 93308
OFFICE (661)392 -8687 FAX (661)392 -0621
PRODUCT LINE LEAK DETECTOR TEST
WORK SHEET
W /O#:
FACILITY NAME: GOSFORD SHELL
FACILITY ADDRESS: 4050 GOSFORD RD. BAKERSFIELD
PRODUCT LINE TYPE: PRESSURE
PRODUCT LEAK DETECTOR TYPE TEST TRIP PASS
BELOW P.S.I. OR
SERIAL NUMBER 3 G.P.H. FAIL
REG87 L/D TYPE: VEEDEROOT
YES 11 PASS
SERIAL # 150749
PREM91 LID TYPE : VEEDEROOT
YES 11 PASS
SERIAL # 150747
DIESEL LID TYPE : VEEDEROOT
YES 11 PASS
SERIAL # 210783
L/D TYPE YES PASS
SERIAL # NO FALL
I CERTIFY THE ABOVE TESTS WERE CONDUCTED ON THIS DATE ACCORDING TO RED
JACKET PUMPS FIELD TEST APPARATUS TESTING PROCEDURE AND LIMITATIONS.
THE MECHANICAL LEAK DETECTOR TEST PASS / FAIL IS DETERMINED BY USING A
LOW FLOW THRESHOLD TRIP RATE OF 3 GALLONS PER.HOUR.OR LESS AT 10 P.S.I. I
ACKNOWLEDGE THAT ALL DATA COLLECTED IS TRUE AND CORRECT TO THE BEST
OF MY KNOWLEDGE.
TECHNICIAN: RICH PHILL
SIGNATURE: DATE: 6/2/11
SOFTWARE REVISION LEVEL
VERSION 327.04
SOFTWf3REO 346327 -100 -E
CREATED - 07.02.OE.10.28
S- MODULEP 330160 -004 -a
SYSTEM FEATURES:
PERIODIC IN -TANK TESTS
ANNUAL IN-TANK TESTS
ISD
PMC
SYSTEM SETUP - - - - - -
JUN 2. 2011 2:16 PM
SYSTEM UNITS
Ury,S. SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE. /TIME FORMAT
MON DD YYYY HH : Mtll : SS xM
GOSFORD SHELL
4050 GOSFORD RD
BAKERSFIELD CA
RE- DIRECT LOCAL PRINTOUT
DISABLED
EURO PROTOCOL PREFIX
S
SYSTEM SECURITY
CODE : 000000
MAINTENANCE HISTORY
DISABLED
TANK CHART SECURITY
DISABLED
CUSTOM ALARMS
DISABLED
MASS,,DENS I TY
DISABLED
COMMUNICATIONS SETUP
SHIFT TIME 1 5:00 AM aSHIFTTIME2DISABLED PORT SETTINGS:
SHIFT TIME 3 DISABLED
SHIFT TIME 4 DISABLED
TANK PER TST NEEDED WRN
DISABLED
TANK ANN TST NEEDED WRN
DISABLED
LINE RE- ENABLE METHOD
PASS LINE TEST j
LINE PER TST NEEDED WRN I
DISABLED
LINE ANN TST NEEDED WRN 1
DISABLED
PRINT TC VOLUMES
ENABLED
TEMP COMPENSATION
VALUE (DEG F >: 60.0
STICK HEIGHT OFFSET
DISABLED
ULLAGE: 904
H- PROTOCOL DATA FORMAT
HEIGHT
PRECISION TEST DURATION
HOURS: 12
DAYLIGHT SAVING TIME
ENABLED
START DATE
APR WEEK I SUN
START TIME
2:00 AM
END DATE
OCT WEEK 6 SUN
END TIME
2:00 AM
COMM BOARD I (FXMOD)
BAUD.RATE 2400
PARITY ODD
STOP BIT I STOP
DATA.LENGTH: 7 DATA
RS- 232.SECURITY
CODE : DISABLED
DIAL TYPE TONE
ANSWER ON I RING
MODEO,,:SETUP STRING
DIAL TONE INTERVAL: 32
COMM BOARD : 2 (EDIM 1
RS -232 SECURITY
CODE : DISABLED
COMM BOARD. 3 (RS -232)
BAUD RATE 9600
PARITY NONE
STOP BIT :.2 STOP
DATA LENGTH: 8 DATA
RS -232 SECURITY
CODE : DISABLED
AUTO TRANSMIT SETTINGS
AUTO LEAK ALARM LIMIT
DISABLED
AUTO HIGH WATER LIMIT
DISABLED
AUTO OVERFILL LIMIT
DISABLED
AUTO LOW PRODUCT
DISABLED
AUTO THEFT LIMIT
DISABLED
AUTO DELIVERY START
DISABLED
AUTO DELIVERY END
DISABLED
AUTO EXTERNAL INPUT ON
DISABLED
AUTO EXTERNAL INPUT OFF
DISABLED
AUTO---SENSOR FUEL ALARM
DISABLED
AUTO SENSOR WATER ALARM
DISABLED
AUTO-SENSOR OUT ALARM
DISABLED
RECEIVER SETUP:
j NONE
AUTO DIAL TIME SETUP:
NONE
RS -232 END OF MESSAGE
DISABLED
AUTO DIAL ALARM SETUP
YZ 38
f N_TANK SETUP - - - - - --------- -- -- - -
T 1:87 -1
PRODUCT CODE 1
THERMAL COEFF :.000? 00
TANK DIAMETER 92.00
TANK. PROFILE 1 PT
FULL VOL 11627
FLOAT SIZE: 4.0 IN.
WATER WARNING 2.0
HIGH WATER LIMIT: 3.0
MAX OR LABEL VOL: 11627
OVERFILL LIMIT 90%
2
10464
HIGH PRODUCT 95%
000700
11045
DELIVERY LIMIT 15%
92.00
1744
LOW PRODUCT 500
LEAK ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 50
TANK•. TILT 3.75
PROBE OFFSET 0.00
SIPHON IIIANIFOLDED TANKS
T #: NONE
LINE MANIFOLDED TANKS
T#: 02
LEAK. MIN PERIODIC: 10%
1,162,
LEAK MIN ANNUAL 10%
1162
PERIODIC TEST TYPE
STANDARD
T 2:87 -2
PRODUCT CODE
THERMAL COEFF
TANK DIAMETER
TANK PROFILE
FULL VOL
FLOAT SIZE: 4,0 IN. FLOAT SIZE: 4.0 IN.
y2 3S''j
2,0
T 3:91
2.0
HIGH WATER LIMIT:.
2 PRODUCT CODE 3
MAX OR LABEL VOL:
000700 THERMAL COEFF 000700
OVERFILL LIMIT
92.00 TANK DIAMETER 92.00
TNK TST SIPHON BREAK:OFF.
1 PT TANK PROFILE I PT
H I GH PRODUCT
9728 FULL VOL 9729
FLOAT SIZE: 4,0 IN. FLOAT SIZE: 4.0 IN.
WATER WARNING 2,0 WATER WARNING : 2.0
HIGH WATER LIMIT:. 3.0 HIGH WATER LIMIT: 3.0
MAX OR LABEL VOL: 9728 MAX OR LABEL VOL: 9728
OVERFILL LIMIT 500.1 OVERFILL LIMIT 90%
TNK TST SIPHON BREAK:OFF.
8755 8755
H I GH PRODUCT 95y HIGH PRODUCT 95%
9241 9241
DELIVERY LIMIT. 14% DELIVERY LIMIT 14%
1361 1361
LOW PRODUCT 500 LOW PRODUCT 500
LEAK ALARM LIMIT: 99 LEAK ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 50 SUDDEN LOSS LIMIT: 50
TANK TILT 2,29 TANK TILT 2.19
PROBE OFFSET 0.00 PROBE OFFSET 0.00
SIPHON MANIFOLDED TANKS
T#: NONE
LINE MANIFOLDED TANKS
T#: 01
SIPHON MANIFOLDED TANKS
T#: NONE..
LINE MANIFOLDED TA14:S
T #: NONE
LEAK MIN PERIODIC: 10% LEAK MIN PERIODIC: 10
972 972
LEAK MIN ANNUAL 1.0% LEAK MIN ANNUAL 10%
972 972
PERIODIC: TEST TYPE PERIODIC TEST TYPE
STANDARD STANDARD
PUMP THRESHOLD 10.00%
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY 3 MIN
PUMP THRESHOLD 10.00%
ANNUAL TEST FAIL
ANNUAL PEST FAIL ALARM DISABLED
ALARM DISABLED I PERIODIC TEST FAIL
PERIODIC TEST FAIL ALARM DISABLED
ALARM DISABLED GROSa. %ST FA I L ,..,
GROEw TEOT FAIL i ALARM *D] A LEb
ALARM DISABLED- ANN TEST AVERAGING: OFF
ANN TEST AVERAGING: OFF PER TEST AVERAGING: OFF
PER TEST AVERAGING: OFF 1" TANK TEST - NOTIFY: OFF
TANK TEST NOTIFY: OFF TNK TST SIPHON BREAK:OFF.
TNK TST SIPHON BREAK:OFF DELIVERY DELAY 3 MIN
DELIVERY DELAY 3 MIN PUMP THRESHOLD 10.00%
PUMP THRESHOLD 10.00%
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY 3 MIN
PUMP THRESHOLD 10.00%
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER 'LEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY 3 MIN
PUMP THRESHOLD 10.00%
Q 2:91
TYP:2.Oi3.0IN FIBERGLASS
2.0IN DIA LEN: 400 FEET
3.0IN DIA LEN: 0 FEET'
SHUTDOWN RATE: 3.0 GPH
LOW PRESSURE SHUTOFF:NO
LOW PRESSURE O PSI
T 3:91
DISPENSE MODE:
STANDARD
SENSOR: NON - VENTED
PRESSURE OFFSET: O.OPSI
L l;Mlt 1 t5'f METHOD
T 4:DIESEL TEST WEEKLY ALL TANK Q 3:DIESELPRODUCTCODE4MON
THERMAL COEFF :•000450
TANK DIAMETER 92.00 START TIME : DISABLED TYP:2.0r3.0IN FIBERGLASS
TANK PROFILE 1 PT TEST.RATE :0.20 GAL /HR 2.0IN DIA LEN: 400 FEET
FULL VOL 9728 DURATION 2 HOURS
3.OIN DIA LEN: 0 FEET
TST EARLY STOP:DISABLEFi
FLOAT SIZE: 4.0 IN. LEAK TEST REPORT FORMAT
SHUTDOWN RATE: 3.0 GPH
LOW PRESSURE SHUTOFF:NO
WATER WARNING 2.0 NORMAL LOW PRESSURE 0 PSI
HIGH WATER LIMIT: 3.0 T 4:DIESEL
MAX OR LABEL VOL' 9926 DISPENSE MODE:
STANDARDOVERFILLLIMIT90%
8955 SENSOR: NON- VENTED
HIGH PRODUCT 95%: PRESSURE OFFSET: O.OPSI
9241
DELIVERY LIMIT 14:
1361
LOW PRODUCT : 500 PRESSURE LINE LEAK SETUPLEAKALARMLIMIT: 99
SUDDEN LOSS LIMIT: 50
TANK TILT 0.91
PROBE OFFSET 0.00 Q 1;87
TYF:2.O, /3.OIN.FIBERGLASS
SIPHON MANIFOLDED TANKS. SI 2.0IN DIA LEN: 400 FEET
TO: NONE
LINE MANIFOLDED TANKS 3.0IN.DIA LEN: 0,FEET
LINE -LEAK LOCKOUT- SETUP-
TO: NONE LOCKOUT SCHEDULE
SHUTDOWN RATE: 3.0 GPH DAILY
LEAK MIN PERIODIC: 10i LOW PRESSURE SHUTOFF:NO
LOW PRESSURE 0 PSI
START TIME: DISABLED
STOP TIME DISABLED972
T 1:
ENSLEAKMINANNUAL : 10% DISPENSE MODE: 72 MANIFOLDED: ALTERNATE
SENSOR: NON- VENTED
PRESSURE OFFSET: O.OPSIPERIODICTESTTYPE
STANDARD
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER 'LEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY 3 MIN
PUMP THRESHOLD 10.00%
Q 2:91
TYP:2.Oi3.0IN FIBERGLASS
2.0IN DIA LEN: 400 FEET
3.0IN DIA LEN: 0 FEET'
SHUTDOWN RATE: 3.0 GPH
LOW PRESSURE SHUTOFF:NO
LOW PRESSURE O PSI
T 3:91
DISPENSE MODE:
STANDARD
SENSOR: NON - VENTED
PRESSURE OFFSET: O.OPSI
L 1:87 -1 STP
TRI -STATE (SINGLE FLOAT)
CATEGORY : STP SUMP
L 2:07 -2 STP
TRI -STATE (SINGLE FLOAT)
CATEGORY : STP SUMP
L '3:91 STP
TRI -STATE (SINGLE FLOAT)
CATEGORY : STP SUMP
L 4 :DIESEL STP
TRI -STATE (SINGLE FLOAT)
CATEGORY : STP SUMP
L 5:07 -1 FILL-
TRI -STATE (SINGLE_FLOAT)
CATEGORY : OTHER SENSORS
L 6:87 -2 FILL
TRI-STATE (SINGLE FLOAT)
CATEGORY : OTHER SENSORS
L 7:91 FILL
TRI -STATE (SINGLE FLOAT)
CATEGORY : OTHER SENSORS
L 6:DSL FILL
TRI -STATE (SINGLE
CATEGORY : OTHER
L.9:87 -1 ANN
TRI -STATE (SINGLE
CATEGORY : ANNULAI
L]0:87 -2 ANN
TRI -STATE (SINGLE
CATEGORY : ANNULAI
L11:91 ANN
TRI -STATE (SINGLE
CATEGORY : ANNULAF
L12:DSL ANN
TRI -STATE (SINGLE
CATEGORY : ANNULAF
13:DISP 1 -2
FRI -STATE (SINGLE
ATEGORY : DISPENS
14:DISP 3 -4
RI-STATE ( SINGLE
ATEGORY : DISPENS
L15:DISP 5 -6
TRI -STATE (SINGLE. FL
CATEGORY : DISPENSER
16 :DISP 7 -6
TRI -STATE (SINGLE FL
CATEGORY : DISPENSER
EXTERNAL INPUT SETUP
NONE` -- - - - --
OUTPUT — RELAYtuP.;.a_,...,r
R 1:87 - 2 STP
TYPE:
PUMP CONTROL OUTPUT
TANK, 4: 2
IN -TANK ALARMS
T 2:HIGH'WATER ALARM
T 2:LOW PRODUCT ALARM
LIQUID SENSOR ALMS
L. I rFZL ALARM
L 2:FLIL ALARM
L13:FUEL ALARM
L14:FUEL ALARM
L15 :FUEL ALARM
L16:FUEL ALARM
L ]:SENSOR OUT ALARM
L 2::SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L14:.SENSOR OUT ALARM
L15:SENSOR OUT ALARM
L16:SENSOR OUT ALARM
PRESSURE LINE LEAK
0 I:GROSS LINE FAIL
PLLD LINE DISABLE SFTU
Q 1:87
III -TANK ALARMS
T ]:HIGH WATER ALARM
T ]:LOW PRODUCT ALARM
LIQUID SENSOR ALMS
L 1 :FUEL ALARM
L 2:FUEL:ALARM
L13 :FUEL ALARM
L14:FUEL ALARM
L15:FUEL ALARM
L16:FUEL ALARM
L ]:SENSOR OUT.ALARM.
L 2:SENSOR OUT ALARM
L13:.SENSOR OUT ALARM
LIA :SENSOR OUT:ALARM
L15:SENSOR OUT ALARM
L]6:SENSOR OUT ALARM
ISD SITE ALARMS
ISD. GROS PRES 'FA IL
ISD DEGRD PRES 'FAIL
ISD VAPOR LEAK.FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAI
ALL:DEGRD COLLECT FAI
Q 2 :91
IN-TANK ALARMS
T 3:HIGH WATER ALARM
T 3:LOW PRODUCT ALARM
LIQUID SENSOR ALMS
L 3:FUEL ALARM
L)3:FUEL ALARM
L14:FUEL ALARM
L15 ;FUEL ALARM
L16:FUEL ALARM
L 3:SENSOR OUT ALARM
L13:S£NSOR OUT ALARM
L14:SENSOR OUT ALARM
L15:SENSOR OUT ALARM
L)6:SENSOR OUT ALARM
ISU SITE ALARMS
ISD GROSS PRES FAIL
f'SD DEGRD PRES FAIL
ISD..VAPOR LEAK FAIL
I.SD :Ho5z. ALARM'SALL 'GROSS-' COLLECT FAI;
A -.DEGRD COLLECT FAI
G.3:DIESEL
IN -TANK ALARMS
T 4:HIGH WATER ALARM
T 4:LOW PRODUCT ALARM
LIQUID SENSOR ALMS
L 4:FUEL ALARM
L14:FUEL ALARM
L 16 : FUEL ALARM
L 4:SENSOR OUT ALARM
L14:SENSOR OUT ALARM
L16:SENSOR OUT.ALARM
7 y
SMARTSE14SOR SETUP
s 1:DISP 1 -2 FM i
CATEGORY AIR FLOW METH -,l
a 2 :DISP 3 -4 FM
CATEGORY AIR FLOW METE{
s ":DISP 5 -6 FM
CATEGORY AIR FLOW METER41;
s 4:DIGP 7 -8 FM I
CATEGORY AIR FLOW METED
s 5:DISP 5 -6 PS
CATEGORY VAPOR PRESSURE
EVR /ISD SETUP
EVR TYPE: VACUUM ASSIST
VACUUM ASSIST TYPE
HEAL`! VAC .
NOZZLE A/L RANGE
MAX: 1.15 MIN: 0.95
VAPOR PROCESSOR TYPE
NO VAPOR PROCESSOR
ANALYSIS TIMES
TIME: 10:00 AM
DELAY MINUTES: 1.
ALARM HISTORY REPORT
ALARM -- L 1:Ei7 -1 STPSTPSUMP
FUEL ALARMJUN212011 ,1.0:01 -NJ
FUEL ALARMJUN2, 2011 9 :46 AM
LARM HISTORY REPORT
SENSOR ALARM -- 2:67-2 STP ___ fP SUMP
JEL ALARMJN2, 2011 l o : 01 AI °I
IEL ALARM
iN 2- 201 1 ' 9: 35 AM
ACCEPT HIGH ORVP,.:
AD SERIAL
DISABLED
1 12173
ISD HOSE TABLE
2 12179
ID FP FL HL AA RR --
01 01 01 02 -01 LIU
02 02 02 02 01 UU,,
03 03 03 02 02 UU
04 04 04 02 02 UU
05.'05 05 02 03 UU
06 06 06 02 03. UU
07 07 07 02 04 UU
08 00 08 02 04 UU
ISD AIRFLOW METER MAP
AD SERIAL NUM LABEL
1 12173 DISP 1 -2 F
2 12179 DISP 3 -4 F
3 12182 DISP 5 -6 F
4.1765 DISP 7-8 F
ISD FUEL GRADE HOSE MAP
1 2 3 4
FP MHH MHH MHH MHH AA
01 -201 101 901 U U 1.
02 202 902 102 U U 1
03 203 103 903.3 U 2
04 1.04 204 904 3 U 2
05 205 105 905 U U 3.
06 206.106 906 U U 3
07 207 107.907 3 U 4
08 20B 1.0.8 908 3 U 4
LABEL TABLE
1: UNASSIGNED
2: BLEND3
3: REGULAR.
4: MID.GRADE
5 PREIl I UH
6: GOLD
7: BRONZE
13: SILVER
9: BLEND2
10 BLEND4
PHC SETUP
PROCESSOR CONTROL LEVEL:
ALARM HISTORY REPORT
SENSOR ALARM - L 3:91 STPSTPSUMP
FUEL ALARMJUN2, 2011 10:01 AM
FUEL ALARMJUN2, 2011 9 :40 AM
YZ
ALARM HISTORY REPORT
SENSOR ALARM - - --
L 4 :DIESEL STP
STP SUMP
FUEL ALARM
JUN 2, 2011 10:0.1 AM
FUEL ALARM
JUN 21.2011 9:92 AM
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 5:87 -1 FILL
OTHER SENSORS
FUEL ALARM
JUN 2. 2011 10:01 Ahl
FUEL ALARM
JUN 2. 2011 9:48 AM
ALARM HISTORY REPORT
SENSOR ALARM -- --
L 6:87 -2 FILL
OTHER SENSORS
FUEL, ALARM
JUN 2, 2011 10:02 AM
FUEL ALARM
JUN 2, 2011 9:36 AM
ALARM HISTORY REPORT
SEI4SOR ALARM - - - --
L 7:91 FILL
OTHER SENSORS
FUEL ALARM
JUN 2, 2011 10:02 AM
UEL- AL ARM
JUN -2 201:1 9:40 AM
ALARM HISTORY REPORT
L B:PS -ENSOR ALARM - - --
OTHER SENSORFUELALNMSORS
JUN 2, 2011 10:02 AM
FUEL ALARMJUN2. 2011 9:33 AM
ALARM HISTORY REPORT
SENSOR ALARM - ----
L 9:87 -1 ANN
ANNULAR SPACE
SENSOR OUT ALARM
JUN 2, 2011 10:01 AM
FUEL ALARM
JUN 2. 201.1. 9:46 AM
iLARt °1 HISTORY REPORT
SEI4SOR ALARM
1_10:07 -2 ANNANNULARSPPI -E
SENSOR OUT ALARM
JUN 2. 2011 10:01 AM
FUEL ALAR
2 11 9:36 AM
JUPJ •
ALARM HISTORY REPORT
SENSOR ALARM
L11:91 ANN
111INULAR SPACE
SENSOR OUT ALARM
JUN 2, 2011 10:01 AM
l.1EL ALARhI
JUN 2. 2011 9:40 AM
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L12:DSL ANN
ANNULAR SPACE
FUEL ALARM
JUN 2. 20t1 10:14 AM
FUEL. ALARM ..
JUN 2, 2011 10:02 AM
SE14SOP OUT ALARM
JUN 2, 2011 10 :01 AM
i -ARPI HISTORY REPORT
SENSOR ALARM - - - --
A3:IjISP 1 -2
1SPENSER PAN
SENSOR OUT ALARM
JUN 2. 2011 10 :01 AM
UEL ALARM
7UN 2. 2011 9 :55 AM
F
LARil HISTORY REPORT
SENSOR ALARM - - - --
J 4:DISP 3 -4
A SPENSER PAN
SENSOR OUT ALARM
JUN 2, 2011 10:01 Aft
iUEL ALARM
UN 2, 2011 9:54 AM
I
ALARM HISTORY REPORT
SENSOR ALARM --
L15:DISP 5 -6
DISPENSER PAN
SENSOR OUT ALARM
JUN 2. 2011 10:01 AM
FUEL ALARM
JUN 2, 2011 9:53 AM
ALARM HISTORY REPORT
SENSOR ALARM
L16:DISP 7--8
DISPENSER PAN
SENSOR OUT ALARM
JUN 2, 2011 10:01 AM
FUEL ALARM
JUN 2, 2011 9:53 AM
ALARM HISTORY REPORT
SENSOR ALARM - - - -- Q 1:87
PLLD SHUTDOWN ALARMJUN2, 2011 10:45 AM
Yz ry
ALARM HISTORY REPORT
SENSOR ALARM - -- --
Q 2:51
PLLD SHUTDOWN ALARM
JUN 2, 2011 10:41 AM
GROSS LINE FAIL
JUN 2, 2011 10:41 AM
PLLD SHUTDOWN ALARM
JUN 2, 2011 10:01 AM
PLLD SHUTDOWN ALARM
JUN 2, 2011 9 :55 AM
PLLD SHUTDOWN ALARM
JUN 2. 2011 9:54 AM
PLLD SHUTDOWN ALARM
JUN 2. 2-011 9:53 AM
PLLD SHUTDOWN ALARM.
JUN 2, 2011 9.:53 AM
PLLD SHUTDOWN ALARM
JUN 2. 2011 9 :.40 AM
PLLD SHUTDOWN ALARM
APR. 20. 2011 10 :02 AM
GROSS, LINE FAILJUN2; 2011 10:45 AM ALARM HISTORY REPORT
PLLD SHUTDOWN ALARM SENSOR ALARM -- - JUN 2, 2011 10:01 AM 0 3:DIESEL
PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM
JUN 2, 2011 10:36 AM
JUN 2, 2011 9:55 AM GROSS LINENE FAIL
PLLD"--V4UTDOWN ALARM
2- 2011 10: 36 AtK
JUN 2,'2011 9:54 AM PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM
JUN 2, 2011 10:01 AM
JUN 2, 2011. 9:53 AWI PLLD SHUTSDOWN ALARM
PLLD SHUTDOWN ALARM
JUN 2011 9:54 AM
JUN 2. 2011 9:53 AN.. PLLD SHUTDOWN ALARMJUN. 2. 2011 9:53 AMPLLDSHUTDOWNALARMJUN2, 2011 9:46 AM PLLD SHUTDOWN ALARM
PLLD SHUTDOWN ALARM
JUN 2, 2011 9:32 AM
JUN 2, 2011 9:35 AM
PLLD SHUTDOWN ALARMAPR20, 2011 10:02 AM
VZ,3
MONITOR CERT. FAILURE REPORT
SITE NAME: GOSFORD SHELL DATE : 6/2/11
THE FOLLOWING COMPONENTS WERE REPLACED/REPAIRED TO COMPLETE
TESTING.
REPAIRS;
L LABOR:
PARTS INSTALLED : jl- o —
NAME : TITLE:
SIGNATURE
THE ABOVE NAMED PERSON TAKES FULL RESPONSIBILITY OF NOTIFYING
THE APPROPRIATE PARTY TO HAVE CORRECTIVE ACTION TAKEN TO REPAIR
THE ABOVE LISTED PROBLEMS AND NOTIFYING RICH ENVIRONMANTAL FOR
ANY NEEDED RETESTING. THIS ALSO RELEASES RICH ENVIRONMENTAL OF
ANY FINES OR PENALTIES OCCURING FROM NON - COMPLIANCE.
A COPY OF THIS DOCUMENT HAS BEEN LEFT ON -SITE FOR YOUR
CONVIENENCE.