HomeMy WebLinkAbout2011 RESULTSMONITORING SYSTEM CERTIFICATION'
For Use By All Jurisdictions Within the State ofCalifornia
Authority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be
prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided
to the tank system owner /operator. The owner /operator must submit a copy of this form to the local agency regulating UST systems
within 30 days of this date.
A. General Information
Facility Name: #562 Fastrip #6 Bldg. No.: _
Site Address: 1640 South Chester Avenue City: Bakersfield Zip: 93304
Facility Contact Person: Omero Garcia
Make /Model of Monitoring System: Veeder -Root TLS 350
B. Inventory of Equipment Tested /Certified
Check the appropriate hone to in cafe specific equipment Inspectedleemiced:
Contact Phone No.: 661 - 393 -7000
Date of Testing/Servicing: 9/13/2011
Tank ID:_12000 gal. Regular Tank ID: 12000 gal. Regular 2
X] In -Tank Gauging Probe. Model: 847390-107 In -Tank Gauging Probe. Model: 847390 -107
Fx] Annular Space or Vault Probe. Model: 794390-420 X] Annular Space or Vault Sensor. Model: 794390 -420
xxj Piping Sump / Trench Sensor(s). Model: 794380-208 Piping Sump / Trench Sensor(s). Model: 794380 -208
Fill Sump Sensor(s) Model: Fill Sump Sensor(s). Model:
LI Mechanical Line Leak Detector. Model:FX1y x] Mechanical Line Leak Detector. Model: FX1y
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
U Tank Overfill / High Level Sensor. Model: 847390 -107 U Tank Overfill / High Leval Sensor. Model: 847390 -107
Other (specify equip. type and model in Sec. E on Pg. 2) Other (specify equip. type and model in Sec. E on Pg. 2)
Tank ID: 12000 gal. Super Tank ID: 12000 gal. Diesel
x] In -Tank Gauging Probe. Model:847390 -107 In -Tank Gauging Probe. Model: 847390 -107
x] Annular Space or Vault Sensor. Model - 794390 -420 x] Annular Space or Vault Sensor. Model: 794390.420
U Piping Sump / Trench Sensor(s). Model:794380- 208 U Piping Sump / Trench Sensor(s). Model: 794380 -208
Fill Sump Sensors(s). Model: Fill Sump Sensor(s). Model:
xx Mechanical Line Leak Decector. Model:FX1V E Mechanical Line Leak Detector. Model: FX1Dy
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
xj Tank Overfill / High Level Sensor. Model:847390 -107 x] Tank Overfill / High Level Sensor. Model: 847390 -107
Other (specify equip. type and model in Sec. E on Pg. 2) Other (specify equip. typs and model in Sec. E on Pg. 2)
Dispenser ID: 1 & 2 Dispenser ID: 3 & 4
Fx] Dispenser Containment Sensor(s). Model: 794380 -208 U Dispenser Containment Sensor(s). Model: 794380 -208
X] Shear Valve(s). x] Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s)
Dispenser ID: 6&6 Dispenser ID: 7 & 8
U Dispenser Containment Sensor(s). Model: 794380 - 208 x] Dispenser Containment Sensor(s). Model: 794380 -208
x] Shear Valve(s). U Shear Valve(s).
Dispenser Containment Float(s) and Chains(s). Dispenser Containment Float(s) and Chain(s).
Dispenser ID: Transition Sump (South) Dispenser ID: Transition Sump (North)
x] Dispenser Containment Sensor(s). Model: 794380 - 208 Lx] Dispenser Containment Sensor(s). Model: 794380 -208
X] Shear Valve(s). E Shear Valve(s).
Dispenser Containment Float(s) and Chain(s) Dispenser Containment Float(s) and Chain(s).
If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification -1 certify that the equipment identified in this document was inspected /services in accordance with the
manufacturers' guidlines. Attached to this Certification is information (e.g. manufacturers' checklist) necessary to varify that
this information is correct and a plot plan showing the layout of monitoring equipment. For equipment capable of generating
such reports, I have attached a copy of the report; (check all that apply) x System Set -up E Alarm istory report
Technician Name (print): Bradley Seykora Signature:
Certification No: 840738 License No: 804904
Testing Company Name: Confidence UST Services, Inc. Phone No: 800- 339 -9930
Site Address: 1640 South Chester Avenue, Bakersfield, CA 93304 Date of Testing/Servicing: 9/13/2011
D. Results of Testing /Servicing
Software Version Installed: 329.01
Complete the following checklist:
Lx] Yes No* Is the audible alarm operational?
x Yes I No* Is the Visual alarm operational?
x Yes No* Were all sensors visually inspected, functionally tested, and confirmed operational?
x I Yes No* Were all sensors installed at the lowest point of secondary containment and positioned so that other
equipment will not interfere with their proper operation?
El Yes No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) Hx N/A operational?
x Yes No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary
N/A containment monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes:
which sensors initate positive shut -down? E Sump /Trench Sensors [x] Dispenser Containment Sensors
Did you confirm positive shut -down due to leaks and sensor failure /disconnected? [X] Yes; No;
U Yes No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no
L] N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visual and audible at
the tank fill point(s) and operating properly? If so, at what percent of tank capasity does the alarm
trigger? 9p %
Yes* U No Was any monitoring equipment replaced? If Yes, identify specific sensors, probes, or other equipment
replaced and list the manufacturer name and model for all replacement parts in Section E, below.
Yes* No Was liquid found inside any secondary containment systems designed as dry systems?
Product; Water. If yes, describe causes in Section E, below.
JxD_7 No* Was monitoring system set -up reviewed to ensure proper settings? Attach set -up reports, if applicable.
Lxj Yes I Ej No* I Is all monitoring equipment operational per manufacturer's specifications?
In Section E below, discribe how and when these deficiencies were or will be corrected.
E. Comments:
F. In -Tank Guaging / SIR Equipment: [X] Check this box if tank guaging is used only for inventory control.
Check this box if tank guaging or SIR equipment is installed.
This section must be completed if in -tank guaging equipment is used to perform leak detection monitoring.
Complete the following checklist:
X] Yes No* Has all input wiring been inspected for proper enter and termination,including testing for ground faults?
x Yes No* Were all tank guaging probes visually inspected for damage and residue buildup?
x Yes No* Was accuracy of system product level readings tested?
x Yes No* Was accuracy of system water level readings tested?
x Yes No* Were all probes reinstalled properly?
Yes No* I Were all items on the equipment manufacturer's maintenance checklist completed?
In the Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD): Check this box if LLD's are not installed.
Complete the following checklist:
x] Yes No* For equip. start-up or annual equipment certification, was a leak simulated to varify LLD performance?
Check all that apply) Simulated leak rate: 3 g.p.h.: 00.1 g.p.h.; 0.2 g.p.h.;
x Yes No* Were all LLD's confirmed operational and accurate within regulatory requirments?
x Yes No Was the testing apparatus properly calibrated?
Yes No* For mac anica LLD's, oes t e LLD restrict product flow if it detects a leak?
N/A
Yes No* For electronic LLD's, does the turbine automatically shut off if the LLD detects a leak?
L] N/A
Yes No* For electronic LLD's, does the turbine automatically shut off if any portion of the monitoring system is
x] N/A disabled or disconnected?
Yes No* For electronic LLD's, does the turbine automatically shut off if any portion of the monitoring system
L] N/A malfunction or fails a test?
Yes No* For electronic LLD's, have all accessible wiring connections been visually inspected?
L] N/A
x Yes No Were all items on the equipment manufacturer's maintenance checklist completed?
In the section H, below, describe how and when these deficiencies were or will be corrected.
H. Comments:
SOFTWARE REVISION LEVEL
VERSION 329.01
SOFTWAREO 346329 -100 -B
CREATED - 09.01.29.15.44
S- MODULEO 330160 -004 -e
SYSTEM FEATURES:
ISO SITE ALARM - - -- PERIODIC IN -TAN); TESTSISDGROSSPRESWARNANNUALIN -TANK. TESTSSEP12. 2011 10:02 on ISD
FASTRIP `6
MIND- l:HESTEF. SYSTFM yETUPBAI(ERSF I ELD A
661 - 347 -660* SEP 1 J. '20l 1 l` : i -u; p19
SEP 13. 2011 12:05 PM
SYSTEM UNIT::,
U.S. S'fSTEM STATUS' hEPORT SYSTEM LAIVCUFu;E
ENGLISH
ISD CROSS PRES WARN SYSTEM DATE, T 1 I•IE FORMAT
MON DD VYYY HH : Mtl : SS <M
INVENTORY REPORT FASTRIP 562
M 1 NG- C:HESTER
BAI:ERSF I ELD CATI : UI4L 661- 397 -8606
VOLUME = 7116 GALS
ULLAGE - 4946 GALS SHIFT TIME I : DISABLED
90% ULLAGE- 3739 GALS SHIFT TIME DISABLED
TC VOLUME - 6999 GALS SHIFT TIME 3 DISABLED
HEIGHT - 63.65 INCHES SHIFT TIME 4 DISABLED
WATER VOL - 0 GALS
WATER s 0.00 INCHES TANK. PER TST NEEDED WRNTEMP = 83.3 DEG F DISABLED
TANK ANN TST NEEDED 1JR14
DISABLED
T ':DIESEL
VOLUME a 625 GALS LINE RE- ENABLE METHODULLAGE . 9437 GALS PASS LINE TEST
90% ULLAGE= 6230 GALS
Tt_ VOLUME - 2592 GALS LINE PER TST NEEDED IJRNHEIGHT - 30. CIS INCHES DISABLEDWATERVOL = 0 GALS LI14E ANN TST NEEDED WRNWATER . 0.00 1NCHEE, DISABLED
TEMP = 87.5 DEG F
PR114T TC VOLUI "IES
ENABLED
T 3:PNL
VOLUME _ 1AiI2 CcALS TEMP COMPENSAT1U14ULLAGE . 8260 GALS VALUE (DEG F >: 60.0
90% ULLAGE- 7053 GALS STICK HEIGHT OFFSETTl' VOLUME - 3721 GALS DISABLEDHEIGHT - 39.33 INCHES ULLAGE: 90%
WATER VOL - 12 GALS
WATER = 0.82 IN,HE.S H- PROTOCOL DATA FORMATTEMPo90.5 DEC; F HEIGHT
DA`1LIGHT SAVING TIME
ENABLEDT4:UHL 2 SIPHON START DATE
VOLUME - 7219 GALS MAR WEEK 2 SUN
ULLAGE . 4843 GALS START TIME90% ULLAC:E- 3636 GALS AM
TG VOLUME - 7105 GALS ENDENV DATE
HEIGHT - 6.4.41 114CHES WEE}. I SUN
WATER VOL - 13 GALS END TIMEEND
WATER . 0.86 1 Ph:HES 2:00 AIMTEMP . 82.6 DEG F
P, . < . . END * w . :t x
RE—DIRECT LOCAL PRINTOUT
DISABLED
EURO PROTOCOL PREFIX,
s
SYSTEM SECURITY
CODE : 000000
MAINTENANCE HISTORY
DISABLED
TANK CHART SECURITY
DISABLED
CUSTOM ALARMS
DISABLED
SERVICE NOTICE
11 1SABLED
ISO 3166 COUNTRY
CODE:
MASS DENSITY
DISABLED
COMMUN 1 C'HT I ONS SETUP
FORT SETT 1 N 3S
COMYI BOAF:D l t R5 -232 )
BAUD RATE 9600
PAP. IT,., NONE
STOP BIT I STOP
DATA LENGTH: 8 DATA
PS -23' SECURITY
CODE : DISABLED
OMM 130Apr, tRS-.3
BAUCl RH1T_ . ...
PAR I T`; 1I-HE
STOP 1311 1 3TC,P
DATA LEN6`I H: 8 DATA
RS -232 SECURIl'
CODE : DISABLED
COMM BOARD : 3 1 ED I r•! )
RS -232 SECURITY
ODE : DISABLED
AUTO TRA14SM 1 T SECT I PIGS :
AUTO LEAK ALARM LIMIT
DISABLED
AUTO HIGH WATER LIMIT
DISABLED
AUTO OVERFILL LIMIT
DISABLED
AUTO LOW PRODUCT
DISABLED
AUTO THEFT' LIMIT
DISABLED
AUTO DELIVERY START
DISABLED
AUTO DELIVERY END
111 SABLED
AUTO E,TEPNAL INPUT 01-1
DISABLED
AUTO EXTERNAL. 1 NPt.fi OFF
DISABLED
AUTO SENSOR FUEL ALARM
DISABLED
AUTO SEW OR WATER HL.ARri
DISABLED
AUTO SENSOR OUT ALHRIh
DISABLED
IN -TANK SETUP
T I:UNL
PRODUCT CODE t
THERMAL COEFF :.000700
TANK DIAMETER 111.50
TANK PROFILE 1 PT
FULL VOL 12062
FLOAT SIZE: 4.0 IN.
WATER WARN IPha 2.0
HIGH WATER LIMIT: 3.0
MAX OR LABEL VOL: 1 '.:062
OVERFILL LIMIT 90%
10855
HIGH PRODUCT 95 =:
11459
DELIVERY LIMIT 15%
1809
LOW PRODUCT 500
LEAK ALARM LIMIT: 99
SUDDEN LOS'S LIMIT: 99
TANK TILT 4.50
PRONE OFFSET 0.00
SIPHON NmNIFOLDED TANKS
TO: NONE
LINE MAN I FOLDE[l TANKS
TP: NONE
LEAK MIN PERIODIC: l0y
1220
PERIODIC TFST TYPE
STANDARD
PERIODIC TEST FAIL
ALARM DISABLED
0RO,3S TEST FAIL
ALARM DISABLED
PER TEST AVERAGING: OFF
THINK TEST INOT I FY : OFF
TOW TST SIPHON E-1:EH)c :OFF
DELIVERY DELAY I MIN
PUMP THRESHOLD 10.001:
RS-232 END DF MESSAC +E
DISABLED y
T 2:DIESEL
PRODUCT CODE 2
THERMAL COEFF 000450
TANK DIAMETER 111.50
TANK PROFILE I PT
FULL VOL 12062
FLOAT SIZE: 4.0 IN.
WATER WARNING 0.0
HIGH WATER LIMIT: 3.0
MA:'{ OR LABEL VOL: t2062
OVERFILL LIMIT 90%
10855
H 1 C:H PRODUCT 95
11459
DELIVERY LIMIT 15%
1809
LOW PRODUCT 500
LEAK ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 99
TANK TILT 2.50
PROBE OFFSET 0.00
SIPHON MANIFOLDED TANKS
TO: NONE
LINE MANIFOLDED TANKS
TO: NONE
LEAK MIN PERIODIC: I %.
120
PERIODIC TEST TYPE
STANDARD
PER 1 OD I C` TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
PER TES'T AVERAUING: OFF
TAN): TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY 1 MIN
PUMP THRESHOLD 10.00%:
T 3:PNL
PRODUCT CODE 3
THERMAL COEFF :.000700
TANK: DIAMETER 111.50
TANK PROFILE I PT
FULL VOL 12062
FLOAT ::I?E: 4.0 IN.
WATER WARNING, 2.0
HIGH WATER LIMIT: 3.0
MAX. OR LABEL VOL: 12062
OVERFILL LIMIT 90%
10855
HIGH PRODUCT 95%
11459
DELIVERY LIMIT 15%
1809
LOW PRODUCT 500
LEAK ALAR11 L 1 M 1 "[ : 99
SUDDEN L02S LIMIT: 99
TANY, TILT 4.30
PROBE OFFSET 0.00
S I PHON MAN I FOLDED TA14KS
TA: NONE
LINE MANIFOLDED TANKS
TO: NONE
LEAF: M 114 PER I OD I is I'•
120
PERIODIC TENT fYPE
STANCwRD
PER 1 Ori I TEST FA 1 L
ALARM DISABLED
TEST FAI L
FILmRll D 113;iHLLD
PER TEST AVERAGING: OFF
TANK. TEST NOTIFY: OFF
TNK TST sipHoii BREAK:OFF
DELA `.1CR'f DELAY I M I N
PUrlP THRESHOLD : 10.00%4
T 4:UNL 2 SIPHON
PRODUCT CODE 4
THERMAL COEFF :,000700
TANK DIAMETER 111.50
TANK, PROFILE 1 PT
FULL VOL 1206:
FLOAT SIZE: 4.0 IN.
WATER WARNING' 2.0
HIGH WATER 1_11°11T: 3.0
MAX OR LABEL VOL: 12062
OVERFILL LIMIT 9Us
0855HIGHPRODUCT95%
11459
DELIVERY LIMIT J5%
1809
LOW PP.ODUC'T 500
LEAI; ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 99
TANK TILT 4.4q
PROBE OFFSET 0.00
S I F'HvN MAN I FOLDED TA141:S
TO: NONE
LINE MANIFOLDED TANKS
TO: NONE
LEAK MIN PERIODIC: I =:
120
LEAK MIN ANNUAL I
I:u
PERIODIC TEST TYPE
STAND.ikD
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK T 6* r SIPHON BREA):: OFF
DELIVERY DELAY I MIN
PUMP THRESHOLD 10.00%
LEAK TEST METHOD
TEST UN DATE : TANK: I
MAR 19. 2009
START TIME : DISABLED
TEST RATE :0.20 GAL•HR
DURATION . _ HOURS
TS'r EARLY .MjI, :DISABLED
TEST ON LaiTE : TANK
MAR 19. ='009
START TIME : D l S+;BLET,
TEST RATE :0.20 GhL 11R
DURAT I ON : 2 IiOUR:,
TST EARLY :--jT0 :1,1 Si4BLED
TEST ON DATE : TANK 3
MAR 19, 2009
START TIME DISABLED
TEST RATE : 1J . 20 GAL: HR
DURATION 2 HOURS
TST EARL`! STOF:DISADLED
TES'[ ON DATE : TANK 4
MAR 19, 2009
START TIME : DISABLED
TEST RATE :0. 2_0 GAL-HR
DURATION : 2 HOURS
TST EARLY STOP :DISABLED
LEAK TEST REPORT FORMAT
NORMAL
L 1 OUi D SE14SOR SETUP
L I:UNL 1 STP
TRI -STATE (SINGLE FLOAT)
CFITE(sORY : STP SUMP
L 2:UNL1 ANN
TRI-STATE (SINGLE FLOAT)
CATEGORY : ANNULAR SPACE
L 3:DIESEL STP
TRI -STATE (SINGLE FLOAT)
CATEGORY : STP SUMP
L 4:DIESEL ANN
TRI -STATE (SINGLE FLOAT)
CATEGORY : ANNULAR. SPACE
L 5:PNL STP
TRI-STATE (SINGLE FLOAT)
CATEGORY : STP SUMP
L 6:PNL ANN
TRI -STATE (SINGLE FLOAT)
CATEGORY : ANNULAR SPACE
L 7:UNL2 SIPON STP
TRI -STATE (SINGLE FLOAT)
CATEGORY : STP SUMP
L 8:UNL2 ANN R 5:OVERFILL ALARM
TRI -STATE (SINGLE FLOAT) OUTPUT RELAY SETUP TYPE:
CATEGORY : ANI4ULAR SPACE - - _ - - - _ _ - - - _ STANDARD
NORMALLY OPEN
L 9:D1SP 1 -2
TRI -STATE (SINGLE FLOAT)
CATEGORY : DISPENSER PAN
LIO:DISP 3 -4
TRI -STATE cSINGLE FLOAT)
CATEGORY : DISPENSER PAN
LII:DISP 5 -6
TRI -STATE (SINGLE FLOAT)
CATEGORY : DISPENSER. PAN
L1 "':LISP 7 -8
TRI -STATE (SINGLE FLOAT)
CATEGORY : DISPENSER FAN
L13:TRAN NO.
TRI -STATE (SINGLE FLOAT)
CATEGORY : P I P I I*3 SUMP
L 14 : TRAN SO.
TRI -STATE (SINGLE FLOAT)
CATEGORY : PIPING SU1P
PUMP SENSOR ::ETuF'
I:UNL
TAl`IK a: I
DISPENSE MODE:
STANDARD
S 2:PNL
TANK 0: 3
DISPENSE MODE:
STANDARD
R I:UNL l
TYPE:
PUMP CGNTROL OUTPUT
TANK. 0: 1
LIOU1D SENSOR ALMS
L i:FUEL ALARM
L 7:FUEL ALARM
L 9:FUEL ALARM
LIO:FUEL ALARM
LII:FUEL ALARM
L12:FUEL ALARM
L 1:SENSOR. OUT ALARM
L 7:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
LIO:SENSOR OUT ALAR11
LII :SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L 1:SHORT ALARM
L 7 :SHORT ALARM
L 9:SHORT ALARM
LIO:SHORT ALARM
LII:SHORT ALARM
L12:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL :FLOW COLLECT FAIL
R ":DIESEL
TYPE:
STANDARD
NORMALLY CLOSED
TANK a: _
LIQUID SENSOR ALMS
L 3:FUEL ALARM
L 9:FUEL ALARM
LII *FUEL ALARM
L13:FUEL ALARM
L14:FUEL ALARM
L 3 :SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L11 :SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L14:SENSOR OUT ALARM
L 3:SHORT ALARM
L 4:SHORT ALARM
L 9:SHORT ALARM
LII:SHORT ALARM
L13:SHORT ALARM
L14:SHORT ALARM
R 3: P14L
TYPE:
PUM1P C014TROL OUTPUT
TA14R 0: 3
LIQUID SENSOR ALP }S
L 5:FUEL ALARM
L 9 : FL'FL ALARM
L10:FUEL ALARM
LII:FUEL ALARM
L12:FUEL ALARM
L 5:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
LII:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
ISD HOSE ALARMS
ALL : CROSS COLLECT Fiat L
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
TANK 0: NONE
IN -TANK ALARMS
ALL:OVERFILL ALARM
ALL : H I H PRODUCT ALARM
ALL:MAX PRODUCT ALARM
91ARTSENSOR SETUP
s I:V.P.SENSOR DISP 3 -4
Cr TEGORY VAPOR PRESSURE
s 2:F.M.DISP 1 -2
CATEGORY AIR, FLOW METER
s 3:F.M.DISP 3 -4
CATEGORY AIR FLOW PIETER
s 4:F.M.DISP 5 -6
CATEGORY AIR FLOW METER
s 5:F.M.DISP 7 -8
ATEGORY AIR FLOW METER
EVR /ISD SETUP ALARM HISTORY REPORT ALARM HISTORY REWORT
ID
SENSOR ALARM - - - -- SENSOR ALARM - - - --
EVR TYPE. VACUUM ASSIST L I:UNL 1 STP
L 2:UNL1 ANN
L 4'-DIESEL ANN
VACUUM ASSIST TYPE STP SUMP
ANNULAR SPACE
ANNULAR SPACE
HEALY VAC' FUEL ALARM
MAR II, 2011 5:29 HM FUEL ALARM
3 8453 F.M.DISP 5 SEP 30. 2010 2:24 PM
SEP 30. 2010 2:24 PM
NOZZLE AiL RAN6E
8451 F.M.DISP 7
ALARM HISTORY REPORT
SEP 30. 2010 1:16 PM
MAX: 1.15 MIN: 0.95 FUEL ALARM
MAR 8. 20, 10:54 All SENSOR OUT ALARM
1SD MAY !. 2010 6:16 PM
MAY 1. 2010 6:40 F11
VAPOR PROCESSOR TYPE
I 2 3 4
MHH MHH P-- MHH SENSOR OUT ALARMSENSOR
NONE I+RM
DEC AEC18. 5:30 P+1 SENSOR OUT ALARM
01 201 301 901 5 U 1
FUEL ALARM
SEP 30. 2010 1:17 PM
MAY 1. 2010 6:37 PM
ANALYSIS TIMES
202 302 902 5 U 1
MAY 1. 2010 6:40 PM
TIME: 10:00 AM
203 303 903 U U
JAN 9. 2009 8:0_ HM
DELAY MINUTES: I
204 304 904 U U
ACCEPT HIGH ORVR:
DISABLED
1SD HOSE TABLE ; xIDFPFLHLAARR ;r R A x x END x x t x
01 01 01 02 01 UU
02 02 02 02 01 UU
03 03 03 02 02 UU
04 04 04 02 02 UU
05 05 05 02 03 UU
06 06 06 02 03 UU
07 07 07 02 04 UU
08 08 08 02 04 UU
ISD AIRFLOW METER. MAP ALARM HISTOR`! REPORT ALARM HISTORY REPORT
ID ABELSERIALNUMLABEL SENSOR ALARM - -- --
L 2:UNL1 ANN SE14SOR ALARM - - - --
1 8452 F.M.DISP I ANNULAR SPACE L 5:PNL STP
2 8300 F.M.DISP 3 FUEL ALARM STP SUMP
3 8453 F.M.DISP 5 SEP 30. 2010 2:24 PM FUEL ALARM
4 8451 F.M.DISP 7
ALARM HISTORY REPORT
SEP 30. 2010 1:16 PM
SENSOR OLIT ALARM SETUP DATA WARN l (JG
1SD FUEL GRADE NOSE MAP MAY !. 2010 6:16 PM JAN 29, 2009 8:02 AM
FP
I 2 3 4
MHH MHH P-- MHH SENSOR OUT ALARMSENSOR
SEP 30. 2010 2:e4 PM
MAY 1, 2010 5:46 Phl
STP SUMP
01 201 301 901 5 U 1
FUEL ALARM
SEP 30. 2010 1:17 PM SENSOR OUT ALARM
02 202 302 902 5 U 1
MAY 1. 2010 6:40 PM
03 203 303 903 U U
JAN 9. 2009 8:0_ HM
04 204 304 904 U U
05 205 305 905 5 U 3
VAPOR r ROC'ESSOR TYPE
06 206 306 906 5 U 3
NONE
07 207 307 907 U U 4
08 908 208 306 U U 4 END R
LABEL TABLE END >: x a•
1: UNASSIGNED
2: BLEND3
3: RE,: ULAR
4: 111 D GRADE
5: PREMIUM
6: GOLD
7: BP.ON-E
8: SILVER ALARM HISTORY REPORT
9: BLEND2
10: BLEND4 ALARM HISTORY REPORT SEI6OR ALARM -----
L 6:PNL ANN
SENSOR ALARM - - - -- ANNULAR SPACE
FUEL ALARML3:DIESEL STP SEP 30. 2010 2:e4 PMSTPSUMP
FUEL ALARM
SEP 30. 2010 1:17 PM SENSOR OUT ALARM
MAY 1. 2010 6:40 PM
SETUP DATA WARN 1 N13 SENSOR OUT ALARMJAN 9. 2009 8:0_ HM MAY 1, 2010 6:36 PM
PMC SETUP
Ph1C= VERS 1 r(: 01 .0
VAPOR r ROC'ESSOR TYPE
NONE
PROCESSOR CONTROL LEVEL:
NONE
x r. x v ri END x ri x t t EN I i, f j( 4 n
ALARM HISTORY REPORT ALARM HISTORY REPORT
ENSOR ALARM - - - -- SENSOR ALARM - - - --
L 7:UNL2 S1PON STP L10:DISP 3 -4STPSUMPDISPENSERPANSENSOROUTALARMSENSOROUTALARM
JUL 28. 2011 6:24 AM SEP 30, 2010 2:21 PM
SENSOR OUT ALARM FUEL ALAR11
JUL 28, 2011 4:24 AM SEP 30, 2010 2:19 PM
SENSOR OUT ALARM SETUP DATA WARNINGJUL26, 2011 1:00 P11 JAN 29. 2009 8:02 All
x x E14D ,k x, r r w x x x END t x w x x
ALARM HISTORY REPORT ALARM HISTORY REPORT
SENSOR ALARM - - - -- SENSOR ALARt•I - - - -- L 8 : UNL2 ANN L11:C11SP 5 -6
ANNULAR SPACE DISPENSER PANFUELALARMSENSOROUTALARMSEP30. 2010 2:25 PI °1 SEP 30. 2010 2 :21 P(,1
SENSOR OUT ALARM FUEL ALARMMAY1. 2010 6:39 Pll SEP 30. 2010 2:17 Phi
SENSOR. OUT ALARM SETUP DATA WARNINGMAY1. 2010 6:39 Pll JAN 29. 2009 8:02 All
i x x+ END x* - x r # p x x x END x t -. x x
r
ALARM HISTORY REPORT ALARM HISTORY REPORT
SENSOR ALARM - - - -- SENSOR ALARM - - - -- L 9:DISP 1 -2 L12:D1SP 7 -8DISPENSER. PAN DISPENSER PANSENSOROUTALARMFUELALARMSEP30. 2010 2:21 PM MAR 8, 2011 7:49 AM
FUEL ALARM SENSOR OUT ALARMSEP30. 2010 2:18 PH SEP 30. 2010 2:21 Pi•I
SETUP DATA WARNING FUEL ALARMJAN29. 2009 6:02 AM SEP 30, 2010 2:16 PH
A A x;-i A END r% A* F k i x x x END : A A x x
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L13:TRAN NO.
PIPING SUMP
SENSOR OUT ALARM
SEP 30. 2010 2:21 PM
FUEL ALARM
SEP 30. 2010 2:19 PM
SETUP DATA WARNING
JAN 29, 2009 8 :02 AM
ri x t x r END w x x x
ALARM HISTORY REPORT
SENSOR ALARM - -- --
L14 TRAN SO.
PIPING SUMP
SENSOR OUT ALARM
SEP 30. 2010 2:21 PM
FUEL ALARM
SEP 30. 2010^ -:20 PM
SETUP DATM (WARNING
JAN 29. 2009 8:02 All
r r x x x END * ri j R x
riki:H 1 VE UT I L I T`.
SAvE SETUP DHTH
START TIME:
SEP 13, 2011 12:13:53 PI-1
ARCHIVE UTILI'f1'
SAVE SETUP DATA:
END TIME:
SEP 13, 2011 1?:Ic:G1 PM
BYTES : 16384
aENSOR HI -ARM -----
L 5 : PNL STP
STP SUMP
FUEL ALARM
SEP 13. 2011 12 :46 PM
IN -TANK ALAW - - - --
T 2:DIESEL
DELIVER`: NEEDED
SEP 13. 2011 12:47 PH
IN -TANK ALAF11 - - - --
T 3 : P, I ESEL
PROBE OUT
SEP 13, 2011 12:47 PNI
1 N- Ti;i'IK HLARVI - - - --
T 3:PNL
DELIVERV NEEDED
SEP 13, 2011 12:48 F1^!
IN-TANK HLHF' I - - --
T 3:PNL
PROBE OUT
SEP 13, 2011 12:48 Prl
IN -TANK ALARM - - - --
T I : UI4L
PROBE OUT
SEP 13. 2011 12:48 PM
1 N -T::NK ALAPI'1 -- - --
T I : UNL.
L01,1 TEMP WAkN I NG
SEP 13, 2011 12:49 PNI
IN-TANK ALARM - - - --
T 4:UNL 2 SIPHON
PROBE OUT
SEP 13, 2011 12:49 Phi
FASTRIP 562
MINE- CHESTER
BAKERSF I ELD CA
661- 397 -8606
SEP 13. 2011 12:44 F11
SYSTEM STATUS REPORT
T 4:PROBE OUT
1SD CROSS PRES WARN
I NVEI-ITOP.Y REPORT
T I : UNL
VOLUME 5407 GALS
ULLAGE ° 6655 GALS
90%t ULLAGE- 5448 GALS
TC VOLUME ° 5318 GALS
HEIGHT ° 51.21 1NCHESyWATERVOL - 18 GALS
WATER b 1.03 INCHES
TEMP ° 03.3 DEG F
T :DIESEL
VOLUME a 6578 GALS
ULLAGE 5484 GALS
90% ULLAGE- 4277 GALS
TC VOLUME a 6484 GALS
HEIGHT - 59.73 INCHES
WATER VOL ° 0 GALS
WATER = 0.00 INCHES
TEMP ° 91.5 DEC; F
T 3:PNL
VOLUt-IE - 7692 GALS
ULLAGE 4370 GALS
90Y. ULL"3E° 3163 GALS
Tr VOLUME - 7519 GALS
HEIGHT - 67.91 INCHES
WATER VOL e 0 GALS
WATER ° 0.00 INCHES
TEMP - 92.1 DEG F
x A END A A A X X
SENSOR ALARM
L13 ;TRAN 140.
P 1 P 1 NG SLPIP
SENSOR. OUT ALARM
SEP 13, 2011 1:03 PIN
SENSOR ALARM - - - --
L I : UPIL I STP
STP SUMP
SENSOR OUT ALARM
SEP 13. 2011 1:03 PI1
2ENSOR ALARM - - - --
L 9 :1,ISP 1 -2
D I SPENSER F-AN
SENSOR OUT ALARM
SEP 13, 2011 1:03 PM
SENSOR ml-wRv
LII:DISP 5 -6
DISPENSER PAN
SENSOR OUT ALARM
SEP 13. 2011 1:04 PM
SENSOR ALARM
LI2:DISP 7-8
DISPENSER PAN
SENSOR OUT ALARM
SEP 13, 2011 1:04 Phi
SENSOR ALAR11 - - - --
L14:TRAN SO.
PIPING SUMP
SENSOR. OUT ALARM
SEP 13, 2011 1:04 PM
SENSOR ALARM
L 5:PNL STP
STP SUMP
SENSOR OUT ALARM
SEP 13. 2011 1:u4 PM
SENSOR ALARM - - - -- FAS'TRIP 562 --- -- SE1lISOR i+L:;R1`1 - - - --
L 2: IJNL I HNN M I NG- CHESTER L 10: 1111 SP 3 -4
ANNULAR SPACE DISPENSER PHN
SENSOR OUT ALARM 661 -3 97 -860
CA FUEL ALARM
SEP 13, 2011 1:04 PM 661- 347 -8606 SEP 13. 2011 1:10 Phl
SENSOR ALARM - - - --
L10:DISP 3 -4
DISPENSER PAN
SENSOR OUT HLARM
SEP 13. 2011 1:04 PM
SENSOR ALARM - - - --
L 3:0IESEL STP
STP SUMP
SENSOR OUT ALARM
SEP 13. 2011 1:04 PM
SENSOR HLARM - ----
L 4:DIESEL HNN
ANNULAR SF,Al E
SENSOR OUT ALARh1
SEP 13. 2011 1:U4 PM
SENSOR ALARM - - - --
L 6:PNL ANN
ANNULAR SPACE
SENSOR OUT ALARM
SEP 13. 2011 1:04 PM
SENSOR ALARM - - - --
L 7:UNL2 SIPUH STP
STP SUMP
SENSOR OUT ALARM
SEP 13. 2011 1:04 PM
SENSOR ALAR11 - - - --
L 8: UNI_2 ANN
ANNULAR SPACE
SENSOR OUT ALARM
SEP 13. 2011 1:04 PM
SEP 13, 2011 1 :04 PM
SYSTEM STATUS REPORT
ISD GROSS PRES WARN
SENSOR ALARM - - - --
L 5:PNL STP
STP SUMP
FUEL ALARM
SEP 13. 2011 1:06 PM
SENSOR ft!.ARM - - - --
I. 3:DIESEL .. ;TP
STP SUMP
FUEL ALARM
SEP 13. 2011 1:06 PM
SENSOR F;LHkM - - - --
L I:UNL I STP
STP Sl.lMP
FUEL ALARM
SEP 13. 2011 1:07 PM
SENOR i:+LkRll - - - --
l. 7:UNL2 SIPOH STP
STP SKIP
FUEL ALARM
SEP 13. 2n11 1:08 PM
SENSOR ALARM - - - --
L 9:DISP 1-2
DISPENSER PAN
FUEL ALARM
8EP 13, 2011 1:09 PM
E
SENSOR ALHRPI -
LII:DISP 5 -6
DISPENSER PAN
FUEL ALARM
SEP 13. 2011 1 : I I F'11
SENSOR ALHR1'l - - --
L12:D1SP 7 -8
DISPENSER PAN
FUEL ALARM
SEP 13. 2011 1 : I I PM
SENSOR ALARM - - - --
L 13 : TRAIII NO.
PIPING SUMP
FUEL ALARM
SEP 13. 2011 1:12 Pill
SEI 60R ALARM - - ---
L14:TRHN SO.
P I P I Nc, SUMP
FUEL ALARM
SEP 13, 2011 1:12 Pill
SENSOR ALARM
L 6 : PIVL ANN
ANNULAR SPACE
FUEL ALARM
SEP 13, 2011 1:13 PM
SENSOR ALARM
L 4:DIESEL ANN
ANNULAR SPACE
FUEL ALARM
SEP 13. 2011 1:14 PM
SENSOR ALARM T 3:PNL
L ^:UNLI ANN INVENTORY INCREASE T 2:DIESEL
ANNIJLHR SPACE INVENTORY INCREASE
FUEL ALARM
SEP 13. 2011 1 : 14 PI•!
INCREASE START
SEP 13. ='01 1 1 : I B Phi INCREASE STHkT
SEP 13. 2IS1 :10 PH
VOLUME e 7692 GALS
HEIGHT - 67.90 INCHES VOLUME 6579 GHLS
WATER . 0.00 1 [KHES HEIGHT - 59.73 1 Ni •HES
TEMP - 101.6 DEG F WATER a 0.00 INCHES
TEMP - 103.3 DEG F
INCREASE END
SEP 13. 20lI 1:22 PM INCREASE END
SENSOR HLr:RM SEP 13. 2011 1:26 PH
L 8:UNL2 HNN VOLUME - 10819 GALS
ANNULAR SPr1C'E HEIGHT 93.09 INCHES VOLUME - 1 01867 GHLS
FUEL ALARM WATER = 0.00 11V` HEIGHT - 94.1t INCHES
SEP I.J. 2011 1:14 PM TEMP - 101.5 DEG FF WATER - 0.00 1 Nt,HES
TEMP - 103.2 DEG F
GROSS INCREASE- 3127
TC NET INCREASE= 3037 GROSS INCREASE= 4208
TC NET INCREASE- 4205
1N -TANK NLARM
T 3: PNL
OVERFILL HLAR11
SEP 13. 2011 1:19 F111
SIESEL
IN -TANY HLARh1
T D - -- -- IN -TANK ALARM
OVERFILL ALARM T l:UNL
SEP 13. 2011 1:24 P11 LOW TEMP WARNING
SEP 13. 2011 t:27 PM
IN -TANK ALARM
T 3:PNL
PROBE OUT
SEP 13, 2011 1:20 PM
IN -TANK ALARM - - - --
T DIESEL IN -TANK ALARM
PROBE OUT T 4:UNL 2 SIPHON
SEP 13. 2li1 1 1 :' 4 PM OVERFILL ALARM
SEP 13, 2011 1.27 PM
IN -TANK ALARM
T 3:PNL
INVALID FUEL LEVEL
SEP 13, 2011 1:20 PM
IN-TANK HL -;Pt1 - - - --
T I:UNL IN -TANK ALARM
OVERFILL T 4: UNL 2 SIPHON
SEP 13. 3011 1:26 PM PROBE OUT
SEP 13, 2011 1:28 PM
FHSTRIP 562
M I NG - -CHESTER
BAICERSF I ELD CA
661-397-0606
SEP 13, 21311 1:21 P4.1
IN-TANK ALARM - - - --
T :UNL
S"STEIM STATUS REPORT F'ROBE OUT
ISD GROSS PRES WARD!- - -
SEP 13. 2011 1:?PM6P
SWRCB, January 2006
Spill Bucket Testing Report Form
This form is intendedfor use by contractors performing annual testing of UST spill containment .structures. The completedform and
printouts from tests (ifapplicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: 4562 Fastrip #6 Date of Testing: 9/13/2011
Facility Address: 1640 South Chester Avenue, Bakersfield, CA 93304
Facility Contact: Omero Garcia I Phone: 661- 393 -7000
Date Local Agency Was Notified of Testing: 8/29/2011
Name of Local Agency Inspector (fpresent during testing): Ernie Medina
2. TESTING CONTRACTOR INFORMATION
Company Name: Confidence UST Services, Inc.
Technician Conducting Test: Bradley Seykora
Credentials: 0 CSLB Contractor x ICC Service Tech. SWRCB Tank Tester Other (Specify)
License Number(s): CSLB #804904 ICC #8111231
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: El Hydrostatic Vacuum Other
Test Equipment Used: Lake Test Equipment Resolution: 0.0625"
Identify Spill Bucket (lay Tank
Number, Stored Product, etc.)
1 Regular 1 2 Regular 2 3 Super 4 Diesel
Bucket Installation Type: I-1 Direct Bury
x Contained in Sump
17 Direct Bury
Z Contained in Sump
Direct Bury
x Contained in Sump
Direct Bury
x Contained in Sum
Bucket Diameter: 12.00" 12.00" 12.00" 12.00"
Bucket Depth: 1 13.25" 13.00" 13.00" 12.75"
Wait time between applying
vacuum /water and start of test: 5 min. 5 min. 5 min. 5 min.
Test Start Time (Ti): 1:00 P.M. 1:00 P.M. 1:00 P.M. 1:00 P.M.
Initial Reading (Ri): 8.75" 8.50" 8.75" 9.00"
Test End Time (TF): 2:00 P.M. 2:00 P.M. 1:15 P.M. 2:00 P.M.
Final Reading (RF): 8.75" 8.50" 7.75" 9.00"
Test Duration (TI. — Ti): I hour 1 hour 15 min. 1 hour
Change in Reading (RF - Ri): 0.00" 0.00" 1.00" 0.00"
Pass /Fail Threshold or
Criteria: 0.0625" 0.0625" 0.0625" 0.0625"
Test Result: x Pass Fail N Pass Fail Pass x Fail El Pass Fail
Comments — (include information on repairs made prior to testing, and recommendedfollow -upforfailed tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements.
Technician's Signature:/f Date: 9/13/2011
State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
562 Fastrip #6
1640 South Chester Ave.
Bakersfield, CA 93304
TLS -350
ESO
Overfill
Alarm
L1 - 87 STP, Veeder -Root 208 sensor
L2 - 87 Annular, Veeder -Root 420 sensor
L3 - Deisel STP, Veeder -Root 208 sensor
L4 - Deisel Annular, Veeder -Root 420 sensor
L5 - 91 STP, Veeder -Root 208 sensor
L6 - 91 Annular, Veeder -Root 420 sensor
L7 - 87 siphon STP, Veeder -Root 208 sensor
L8 - 87 siphon Annular, Veeder -Root 420 sensor
L9 - Disp. 1 -2, Veeder -Root 208 sensor
L10 - Disp. 3 -4, Veeder -Root 208 sensor
L11 - Disp. 5 -6, Veeder -Root 208 sensor
L12 - Disp. 7 -8, Veeder -Root 208 sensor
L13 - Trans. North, Veeder -Root 208 sensor
L14 - Trans. South, Veeder -Root 208 sensor
1 - Mag Probe
2 - FX -1 V
3 - FX -1 DV
2 6
1 5
L9 L11
Transition Transition
Sump Sump
L13 L14
804
3 7
L10 L12
STP
L5, 1, 2 Super
12,000 gal. DE) L6
STP
L3, 1, 3 Deisel
12,000 gal. OO L4
STP
L1, 1, 2 Regular
12,000 gal. 0O L2
STP
L7, 1, 2 Regular siphon
12,000 gal. 0O L8