HomeMy WebLinkAboutUST-MONIT. SYSTEM 9/7/2011MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State ofCalifornia
Authority Cited: Chapter 6 7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code ofRegulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be
prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided
to the tank system owner /operator. The owner /operator must submit a copy of this form to the local agency regulating UST systems
within 30 days of this date.
A. General Information
Facility Name: L Petro Mobil
Site Address: 800 34th St
Facility Contact Person: Peter Cloven
Make /Model of Monitoring System: Veeder -Root TLS 350
B. Inventory of Equipment Tested /Certified
Check the appropriate boxes to indicate specificequipment Inspected /serviced:
Bldg. No.:
City: Bakersfield Zip: 93301
Contact Phone No.: 925 - 673 -5500
Date of Testing/Servicing: 9/7/2011
Tank -ID: 10000 gal. Regular Tank
z]
ID: 10000 gal. Plus
In -Tank Gauging Probe. Model: NoneJIn -Tank Gauging Probe. Model: 847390-107
x] Annular Space or Vault Probe. Model: 794390-409 X] Annular Space or Vault Sensor. Model: 794390 -409
x] Piping Sump / Trench Sensor(s). Model: 794380-208 Piping Sump / Trench Sensor(s). Model: 794380 -208
Fill Sump Sensor(s) Model: Fill Sump Sensor(s). Model:
J Mechanical Line Leak Detector. ModeI :FX1V x] Mechanical Line Leak Detector. Model: FX1V
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
U Tank Overfill / High Level Sensor. Model: OPW -6I -SO U Tank Overfill / High Leval Sensor. Model: OPW -6I -SO
Other (specify equip. type and model in Sec. E on Pg. 2) Other (specify equip. type and model in Sec. E on Pg. 2)
Tank ID: 10000 gal. Super Tank ID:
x] In -Tank Gauging Probe. Mode1:847390 -107 In -Tank Gauging Probe. Model:
x] Annular Space or Vault Sensor. Model:794390 -409 Annular Space or Vault Sensor. Model:
X] Piping Sump /Trench Sensor(s). Model -794380-208 Piping Sump / Trench Sensor(s). Model:
Fill Sump Sensors(s). Model: Fill Sump Sensor(s). Model:
xx Mechanical Line Leak Decector. Model:FX1DV Mechanical Line Leak Detector. Model:
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
Lx] Tank Overfill / High Level Sensor. Model:OPW -6I -SO Tank Overfill / High Level Sensor. Model:
Other (specify equip. type and model in Sec. E on Pg. 2) Other (specify equip. typs and model in Sec. E on Pg. 2)
Dispenser ID: 1 & 2 Dispenser ID: 3&4
Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s). Model:
X] Shear Valve(s). U Shear Valve(s).
FxI Dispenser Containment Float(s) and Chain(s). x] Dispenser Containment Float(s) and Chain(s)
Dispenser ID: 5&6 Dispenser ID: 7 & 8
Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s). Model:
U Shear Valve(s). U Shear Valve(s).
U Dispenser Containment Float(s) and Chains(s). x] Dispenser Containment Float(s) and Chain(s).
Dispenser ID: Dispenser ID:
Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s). Model:
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s) Dispenser Containment Float(s) and Chain(s).
If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification - I certify that the equipment identified in this document was inspected /services in accordance with the
manufacturers' guidlines. Attached to this Certification is information (e.g. manufacturers' checklist) necessary to varify that
this information is correct and a plot plan showing the layout of monitoring equipment. For equipment capable of gene tmg
such reports, 1 have attached a copy of the report; (check all that apply) x S s Set -up Alarm re ort
Technician Name (print): Bryan A Self Signature: `
Certification No: B37501 License No: 804904
Testing Company Name: Confidence UST Services, Inc. Phone NJ: 800 - 339 -9930
Site Address: 800 34th St Bakersfield, CA 93301 Date of Testing/Servicing: 917/2011
D. Results of Testing /Servicing
Software Version Installed: 15.01
Complete the following checklist:
Lx] Yes No* Is the audible alarm operational?
x Yes No* Is the Visual alarm operational?
x I Yes No* Were all sensors visually inspected, functionally tested, and confirmed operational?
Ej Yes No* Were all sensors installed at the lowest point of secondary containment and positioned so that other
equipment will not interfere with their proper operation?
Yes No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) Hx N/A operational?
x Yes No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary
N/A containment monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes:
which sensors initate positive shut -down? Sump /Trench Sensors Dispenser Containment Sensors
Did you confirm positive shut -down due to leaks and sensor failure /disconnected? [X] Yes; No;
UYes No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no
N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visual and audible at
the tank fill point(s) and operating properly? If so, at what percent of tank capasity does the alarm
trigger? E9p %
Yes* I_ I No Was any monitoring equipment replaced? If Yes, identify specific sensors, probes, or other equipment
replaced and list the manufacturer name and model for all replacement parts in Section E, below.
Yes* No Was liquid found inside any secondary containment systems designed as dry systems?
Product; Water. If yes, describe causes in Section E, below.
x I Yes I I I No* Was monitoring system set -up reviewed to ensure proper settings? Attach set -up reports, if applicable.
Lx_1 Yes No* I Is all monitoring equipment operational per manufacturer's specifications?
In Section E below, discribe how and when these deficiencies were or will be corrected.
E. Comments:
F. In -Tank Guaging / SIR Equipment: [X] Check this box if tank guaging is used only for inventory control.
i Check this box if tank guaging or SIR equipment is installed.
This section must be completed if in -tank guaging equipment is used to perform leak detection monitoring.
Complete the following checklist:
Cx] Yes No* Has all input wiring been inspected for proper enter and term ination,including testing for ground faults?
x Yes No* Were all tank guaging probes visually inspected for damage and residue buildup?
x Yes No* Was accuracy of system product level readings tested?
x Yes 7 No* Was accuracy of system water level readings tested?
x Yes No* Were all probes reinstalled properly?
U Yes No* Were all items on the equipment manufacturer's maintenance checklist completed?
In the Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD): Check this box if LLD's are not installed.
Complete the following checklist:
Lx] Yes No* For equip. start-up or annual equipment certification, was a leak simulated to varify LLD performance?
Check all that apply) Simulated leak rate: E3 g.p.h.: 0.1 g.p.h.; 0.2 g.p.h.;
x Yes No* Were all LLD's confirmed operational and accurate within regulatory requirments?
x Yes No Was the testing apparatus proper y calibrated?
L] Yes For mac amca LLD's, does the LLD restrict product ow if it detects a leak?
E7 Yes No* For electronic LLD's, does the turbine automatically shut off if the LLD detects a leak?
xj N/A
Yes No* For electronic LLD's, does the turbine automatically shut off if any portion of the monitoring system is
x] N/A disabled or disconnected?
F-1 Yes No* For electronic LLD's, does the turbine automatically shut off if any portion of the monitoring system
U N/A malfunction or fails a test?
Yes No* For electronic LLD's, have all accessible wiring connections been visually inspected?
Lx] N/A
x Yes No Were all items on the equipment manufacturer's maintenance checklist completed?
In the section H, below, describe how and when these deficiencies were or will be corrected.
H. Comments:
RS -232 END OF MESSAGE
DISABLED
SYSTEM SETUP
09 -07 -11 9:32 AM
L PETRO MOBIL
8OU 34TH
BAKERSFIELD CA 93301
661 - 869 -1974 SYSTEM UNITS
U.S. 1N -TANK SETUP
09-07 -11 9:32 AM SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE /TIME FORMAT T I:SUPER UNLEADED 91
MM -DD -Y HH:MM:SS Al PRODUCT CODE 1
SYSTEM STATUS REPORT THERMAL COEFF :.000070
L PETRO MOBIL TANK DIAMETER 90.85
T 2:PROBE OUT 600 34TH TANK PROFILE 4 PTS
BAKERSFIELD CA 93301 FULL VOL 9741
661-869-1974 68.1 INCH VOL 7917
INVENTORY REPORT 45.4 INCH VOL : 4884
SHIFT TIME l 10:00 PM 22.7 INCH VOL 1885
SHIFT TIME 2 6:00 AM
T I:SUPER UNLEADED 91 SHIFT TIME 3 DISABLED
VOLUME a 1502 GALS SHIFT TIME 4 DISABLED FLOAT SIZE: 4.0 IN. 8496
ULLAE o 8239 GALS
90 ULLACE- 7264 GALS TANK PERIODli:: WARNINGS WATER WARNING 2.0
TC VOLUME o 1499 GALS DISABLED HIGH WATER LIMIT: 3.0
HEIGHT - 19.38 INCHES TANK ANNUAL WARNINGS
WATER VOL a 12 BLS DISABLED MAX OR LABEL VOL: 9741
WATER - 0.80 INCHES LINE PERIODIC: WARNING'S OVERFILL LIMIT 9CM
TEMP a 86.3 DEC F DISABLED 8766
LINE ANNUAL WARNINGS HIGH PRODUCT 95:
DISABLED 9254
T 3:REGULAR UNLEADED 87 DELIVERY] LIMIT 10%
VOLUME = 5885 GALS PRINT TC VOLUMES 974
ULLAGE v 3856 GALS ENABLED
90•a ULLAGE= 2881 GALS LOW PRODUCT 500
TC VOLUME a 5871 GALS TEMP COMPENSATION LEAK ALARM LIMIT: 99
HEIGHT o 52.55 1NCHES VALUE (DEG F ): 60.0 SUDDEN LOSS LIMIT: 50
WATER VOL - 23 GALS STICK HEIGHT OFFSET TANK TILT 1.50
WATER o 1.20 INCHES DISABLED
TEMP e 92.3 DEC.; F DAYLIGHT SAVING TIME MAN IFOLDED TANKS
ENABLED Tit: NONE
START DATE
4 x x x A E14D 9wk x x APR WEEK I SUN
START TIME LEAK MIN PERIODIC: Ox
2:00 AM 0
END DATE
OCT WEEK 6 SUN LEAK MIN ANI4UAL 0%
END TIME 0
2:00 AM
PERIODIC TEST TYPE
SYSTEM SECURITY STANDARD
CODE 000000
ANNUAL TEST FAIL
SOF- TWARE REVISION LEVEL ALARM DISABLED
VERSION 15.01
SOF'TWAREa 346015 -100 -B PERIODIC TEST FAIL
CREATED - 9'7.10.23.08.56 ALARM DISABLED
ti
NO SOFTWARE MODULE GROSS TEST FAIL
SYSTEM FEATURES: ALARM DISABLED
PERIODIC IN -TANK TESTS
ANNUAL IN -TANK TESTS ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
COM11UNICATIONS SETUP
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
PORT SETTINGS:
DELIVERY DELAY : 15 MIN
NONE FOUND
RS-232 SECURITY!
CODE : 000000
RS -232 END OF MESSAGE
DISABLED
T 2:SPECIAL UNLEADED 89
PRODUCT CODE 2
THERMAL COEFF :.000070
TANK DIAMETER 90.85
TANK PROFILE 4 PTS
FULL VOL 9741
68.1 INCH VOL 7917
45.4 INCH VOL 4884
22.7 INCH VOL : 1885
MAX OR LABEL VOL: 9741
OVERFILL LIMIT 90%
HIGH WATER LIMIT: 8766
HIGH PRODUCT 95y
OVERFILL LIMIT
9254
DELIVERY LIMIT 10%
HIGH PRODUCT
974
LOW PRODUCT 500
LEAK ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 50
TANK. TILT 1.70
MANIFOLDED TANKS 99
TO: NONE 50
LEAF: MIN PERIODIC: 0%
0
LEAF; MIN ANNUAL on
0
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY : 15 MIN
T 3:REGULAR UNLEADED 87
PRODUCT CODE 3
THERMAL COEFF :.000070
TANK DIAMETER 90.65
TANK PROFILE 4 PTS
FULL VOL 9741
68.1 INCH VOL 7917
45.4 INCH VOL 4884
22.7 INCH VOL 1885
FLOAT SIZE: 4.0 IN. B496
WATER WARNING 2.0
HIGH WATER LIMIT: 3.0
MAX OR LABEL VOL: 9741
OVERFILL LIMIT 90%
8766
HIGH PRODUCT 95%1
9254
DELIVERY LIMIT 10%:
974
LOW PRODUCT 500
LEAF: ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 50
TANK TILT 1.30
MANIFOLDED TANKS
TN: NONE
LEAK MIN PERIODIC: ox
0
LEAK MIN ANNUAL OX
0
PERIODIC TEST TYPE
STANDARD
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
T14K TST SIPHON BREAK :OFF
DELIVERY DELAY : 15 MIN
LEAK TEST METHOD
TEST ON DATE : ALL TANK
MAR 26. 1999
START TIME : 2:00 AM
TEST RATE :0.20 GAL /HR
DURATION : 2 HOURS
LEAK TEST REPORT FORMAT
NORMAL
LIQUID SENSOR SETUP
L 1:91 ANNLLAR
TRI -STATE tSINGLE FLOAT)
CATEGORY : ANNULAR SPACE
L 2:89 ANNULAR
TRI-STATE (SINGLE FLOAT)
CATEGORY : ANNULAR SPACE
L 3 :87 ANULLAR
TRI-STATE (SINGLE FLOAT)
CATEGORY : ANNULAR SPACE
L 5:91 STP SUMP
TRI -STATE (SINGLE FLOAT)
CATEGORY : STP SUMP
L 6:89 STP SUMP
TRI -STATE (SINGLE FLOAT)
CATEGORY : STP SUMP
L 7:87 STP SUMP
TRI-STATE (SINGLE FLOAT)
CATEGORY : STP SUMP
OUTPUT PELAY SETUP
R 1:UNLEDED
TYPE:
STANDARD
NORMALLY CLOSED
LIQUID SENSOR ALMS
L 3:FUEL ALARM
L 4:FUEL ALARM
L 7:FUEL ALARM
L 3:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
R 2:PLu4
TYPE:
STANDARD
NORMALLY CLOSED
LIQUID SENSOR ALMS
L 2:FUEL ALARM
L 4 :FUEL ALARM
L.6:FUEL ALARM
L 7:FUEL ALARM
L 2:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
R 3:PREMIUM
TYPE:
STANDARD
NORMALLY CLOSED
LIQUID SENSOR ALMS
L 1 : FUEL ALAR14
L 4:FUEL ALARM
L 5:FUEL ALARM
L I:SENSOR OUT ALARM
L 5:SENSOR OU'T ALARM
R 4:SONITROL ALARM
TYPE:
STANDARD
NORMALLY OPEN
LIQUID SENSOR AU49
ALL :FUEL ALARM
ALARM HISTORY REPORT
SYSTEM ALARt1 - -- --
PAPER OUT
07 -18-11 10:00 PM
PRINTER ERROR
07 -18 -11 10:00 PM
BATTERY IS OFF
01 -01 -96 8:00 All
CLOCK, IS INCORRECT
10 -29 -00 1:01 All
k r R k k END x w X k w
ALARM HISTORY REPORT ALARM HISTORY REPORT
114- TANK: ALARM - - - -- IN -TANK ALARM -----
T I:SUPER UNLEADED 91 T 3:REGULAR UNLEADED 87
SETUP DATA WARNING SETUP DATA WARNING
04 -19 -03 9:09 AM 03 -26 -98 8:48 AM
03 -26 -98 8:48 AM
MAX PRODUCT ALARM
OVERFILL ALARM
OVERFILL ALARM 07-10 -10 6:49 AM
02 -12-03 5:24 AM 07 -05 -10 1:11 PM
06 -25 -02 10:17 AM 06-23 -10 10:35 AM
01 -06 -02 12:44 PM
LOW PRODUCT ALARM
LOW PRODUCT ALARM 04 -03 -06 10:38 AM
16 -11-06 10:15 AM 10 -11-05 12:14 PM
10 -11 -05 11:53 AM
HIGH PRODUCT ALARM
HIGH PRODUCT ALARM 07 -10 -10 6:51 AM
06 -25 -02 10:18 AM 04 -25 -10 12:30 PM
01 -06-02 12:46 PM 03 -23 -10 3:26 PM
12 -25 -01 7:01 PM
INVALID FUEL LEVEL
114VALID FUEL LEVEL 06 -26 -11 4:12 AM
09 -01 -11 9:18 AM 10-04 -10 1:25 PM
07 -19 -11 2:06 PM 03 -01 -09 4:13 AM
01 -12 -07 4•:25 PH
PROBE OUT
PROBE. OUT 05 -17 -07 12:03 PM
02 -23 -11 1 :07 PM 10 -11 -06 10:46 AM
02 -23 -11 12:55 PM 10 -11 -05 12:14 PM
10 -II -06 10 :16 AM
LOW TEMP WARNING
10 -II -05 11:55 AM
kxxxx END xrik Pik
xxw)x x END xxxxx
1 c
DELIVERY NEEDED
DELIVERY NEEDED 08 -31-11 9:19 AM
08 -26 -11 5:57 PM 08 -09 -11 1:20 Ptl
08 -04 -11 3:53 PM 07 -17 -11 5:54 PM
07 -12-11 6:27 PM
MAX PRODUCT ALARM LOW TEMP WARNING
12 -25 -01 7:03 PM 05 -17 -07 12:12 PM
08 -05 -01 3:22 All
06-16 -01 7:47 PM
LOW TEMP WARNING
10 -II -05 11:55 AM
kxxxx END xrik Pik
xxw)x x END xxxxx
1 c
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 1:91 ANULLAR
ANNULAR SPACE
SENSOR OUT ALARM
I1 -19-10 3:10 PM
FUEL ALARM
I1-19 -10 2:52 PM
SETUP DATA WARNING
12 -02 -08 2:51 PM
x'xx9 END Am9m E
ALARM HISTORY REPORT
SENSOR ALARM --- --
L 2:89 ANULLAR
ANNULAR SPACE
SENSOR OUT ALARM
08 -30 -11 8:50 PM
SENSOR OUT ALARM
11-19 -10 3:10 PM
FUEL ALARM
II -19 -10 2:50 PM
ALARM HISTORY REPORT
SENSOR ALARM ---
L 3:87 ANULLAR
ANNULAR SPACE
SENSOR OUT ALARM
11 -19 -10 3:10 PM
FUEL ALARM
11 -19 -10 2:58 PM
FUEL ALARM
11-19 -10 2:55 PM
x x x x x END x w x x x
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 4:TRENCH LINER
OTHER SENSORS
SENSOR OUT ALARM
03 -18 -04 9 :29 AM
FUEL ALARM
03 -18 -04 9:28 AM
SENSOR OUT ALARM
03 -18 -04 9:27 AM
ALARM HISTORY REPORT
SENSOR ALARM - - ---
L 5:91 STP SUMP
STP SUMP
SENSOR OUT ALARM
11 -19 -10 3:10 PM
FUEL ALARM
11 -19 -10 2:47 PM
FUEL ALARM
tO —I4 -08 1:19 PM
A ii x x w END x R x x x
ALARM HISTORY REPORT
SENSOR ALARM - - ---
L 6:89 STP SUMP
STP SUMP
SENSOR OUT ALARM
11 -19 -10 3:10 PM
FUEL ALARM
11 -19 -10 2:43 PM
FUEL ALARM
10 -14 -08 1:23 PM
x si x x w END x x X x X •0 x x x x END w x i x x w w W x A w END x X A x A
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 7:87 STP SUMP
STP SUMP
SENSOR OUT ALARM
11-19-10 3:10 PM
FUEL ALARM
11 -19 -10 2:45 PM
FUEL ALARM
10 -14 -08 1:22 PM
r x x X END : W. x x
SENSOR ALARM -- ---
L 6:89 STP SUMP
STP SUMP
FUEL ALARM
09 -07 -11 10:222 AM
SENSOR ALARM - - - --
L 7:87 STP SUMP
STP SUMP
FUEL ALARM
09 -07 -11 10:23 AM
SENSOR ALARM
L 5:91 STP SUMP
STP SUMP
FUEL ALARM
09-07 -11 10:25 MM
SENSOR ALARM - - - --
L 7:87 STP SUMP
STP SUMP
SE14SOR OUT ALARM
09 -07 -11 10:28 AM
I
SENSOR ALARM - -- --
L 1:91 ANULLAR
ANNULAR SPACE
SENSOR OUT ALARM
09 -07 -11 10:28 AM
SENSOR ALARM - -- --
L 2:89 ANULLAR
ANNULAR SPACE
SENSOR OUT ALARM
09 -07 -11 10:28 All
SENSOR ALARM - - - --
SENSOR ALARM - - - -- L 3:87 ANULLARL3 :87 ANULLAR ANNULAR SPACEANNULARSPACEFUELALARMSENOROUTALARM09 -07 -11 10:48 AM09- 07- 11.10:28 AM
SENSOR ALARM - - --- SENSOR ALARM -- - -- L 3:87 ANULLARL5:91 STP SUMP ANNULAR SPACESTPSUMPFUELALARMSENSOROUTALARM09 -07 -11 10:51 AM09-07 -11 10:28 AM
SENSOR ALARM - - -- L PETRO MOBIL
800 34THL6:89 STP SUMP BAKERSFIELD CA 93301STPSUMP661 -869 -1974SENSOROUTALARM
09 -07 -11 10:28 AM 09 -07 -11 11:42 AM
SYSTEM STATUS REPORT
T 2:PROBE OUT
X x x x x END o K x x 0
SENSOR ALARM
L 2:89 ANULLAR
ANNULAR SPACE
FUEL ALARM
09 -07 -11 10:39 AM
INVENTORY REPORTSENSORALARM - - - --
L 3:87 ANULLAR
ANNULAR SPACE T I:SUPER UNLEADED 91FUELALARMVOLUMEa1501GALS
09 -07 -11 10:35 AM ULLAGE a 8240 GALS
90s: ULLAGE- 7265 GALS
TC VOLUME o 1498 GALS
HEIGHT - 19.37 INCHES
WATER VOL - 12 GALS
WATER - 0.80 INCHES
TEMP - 86.5 DEC F
UNLEADED 87
SENSOR ALARM - - - -- •
VOLUMEGULAR
5884 GALS
L 1:91 ANULLAR ULLAGE -, 3857 GALS
ANNULAR SPACE 90% ULLAGE- 2882 GALSFUELTCVOLUME - 5870 GALS
0ALARM
11 10.J7 HM HEIGHT 52.55 INCHES
WATER VOL a 23 GALS
WATER - 1.20 INCHES
TEMP - 92.3 DEG F
X x x x x END o K x x 0
SENSOR ALARM
L 2:89 ANULLAR
ANNULAR SPACE
FUEL ALARM
09 -07 -11 10:39 AM
SWRCB, January 2006
Spill Bucket Testing Report Form
Thisform is intendedfor use by contractors performing annual testing of UST spill containment structures. The completedform and
printoutsfrom tests (fapplicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: L Petro Mobil Date ofTesting: 09/07/2011
Facility Address: 800341h St Bakersfield CA 93301
Facility Contact: Peter Cloven Phone: 925- 673 -5500
Date Local Agency Was Notified of Testing: 8/24/2011
Name ofLocal Agency Inspector (cfpresent during testing): Ernie Madina
2. TESTING CONTRACTOR INFORMATION
Company Name: Confidence UST Services, Inc.
Technician Conducting Test: Bryan A Self
Credentials: x CSLB Contractor X ICC Service Tech. X SWRCB Tank Tester Other (Spec)
License Number(s): CSLB# 804904 ICC# 8022804 -UT Tank Tester 11 -1756
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: x Hydrostatic Vacuum Other
Test Equipment Used: Lake Test Equipment Resolution: 0.0625"
Identify Spill Bucket (By Tank
Number, Stored Product, etc.)
1 Regular Fill 2 Plus Fill 3 Super Fill 4
Bucket Installation Type: X Direct Bury
Contained in Sump
X Direct Bury
Contained in Sump
X Direct Bury
Contained in Sump
Direct Bury
Contained in Sum
Bucket Diameter: 12.00" 12.00" 12.00"
Bucket Depth: 13.00" 13.00" 13.00"
Wait time between applying
vacuum /water and start oftest: 5 Minuets 5 Minuets 5 Minuets
Test Start Time (Ti): 9:00 am 9:00 am 9:00 am
Initial Reading (Ri): 9.75" 9.50" 9.50"
Test End Time (TF): 9:05 am 9:05 am 9.05 am
Final Reading (RF): 8.00" 7.00" 8.25"
Test Duration (TF — Ti): 5 Minuets 5 Minuets 5 Minuets
Change in Reading (RF - Rj): 1.75" 2.50" 1.25"
Pass/Fail Threshold or
Criteria: 0.0625" 0.0625" 0.0625"
Test Result: Pass X Fail Pass X Fail Pass X Fail Pass Fail
Comments — (include information on repairs made prior to testing, and recommendedfollow -upforfailed tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information contained in this report is true, accurate, and infull compliance with legal requirements.
Techr Date: 09/07/2011
State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
SWRCB, January 2006
Spill Bucket Testing Report Form
Thisform is intendedfor use by contractors performing annual testing ofUSTspill containment structures. The completedform and
printoutsfrom tests (fapplicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: L Petro Mobil Date of Testing: 09/07/2011
Facility Address: 800 34`h St Bakersfield CA 93301
Facility Contact: Peter Cloven Phone: 925- 673 -5500
Date Local Agency Was Notified of Testing: 8/24/2011
Name of Local Agency Inspector (fpresent during testing): Ernie Madina
2. TESTING CONTRACTOR INFORMATION
Company Name: Confidence UST Services, Inc.
Technician Conducting Test: Bryan A Self
Credentials: 9 CSLB Contractor X ICC Service Tech. X SWRCB Tank Tester Other (Spec)
License Number(s): CSLB# 804904 ICC# 8022804 -UT Tank Tester 11 -1756
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: x Hydrostatic Vacuum Other
Test Equipment Used: Lake Test Equipment Resolution: 0.0625"
Identify Spill Bucket (By Tank
Number, Stored Product, etc.)
I Regular Vapor 2 Plus Vapor 3 Super Vapor 4
Bucket Installation Type: X Direct Bury
Contained in Sump
X Direct Bury
Contained in Sump
X Direct Bury
Contained in Sump
Direct Bury
Contained in Sum
Bucket Diameter: 12.00" 12.00" 12.00"
Bucket Depth: 13.00" 13.00" 13.00"
Wait time between applying
vacuum /water and start of test: 5 Minuets 5 Minuets 5 Minuets
Test Start Time (Ti): 9:00 am 9:00 am 9:00 am
Initial Reading (Ri): 9.50" 10.00" 9.50"
Test End Time (TF): 10:00 am 9:10 am 10.00 am
Final Reading (RF): 9.50" 7.00" 9.50"
Test Duration (TF — Ti): 1 Hour 10 Minuets 1 Hour
Change in Reading (RF - Ri): 0.00" 3.00" 0.00"
Pass/Fail Threshold or
Criteria: 0.0625" 0.0625" 0.0625"
Test Result: X Pass Fail Pass X Fail X Pass Fail Pass Fail
Comments — (include information on repairs made prior to testing, and recommendedfollow -up forjailed tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information contained in this report is true, accurate, and infull compliance with legal requirements
Technician's Signature: ZS— \ Date: 09/07/2011
State laws and regulations do not currenfy require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
CONFIDENCE UST SERVICES, INC.
417 Montclair Street, Bakersfield, CA 93309 800 - 339.9930 or 661 -631 -3870
FINAL TEST RESULTS:
ALERT 1000 / ALERT 1050 / TEI LT -3
CUSTOMER ADDRESS: WORK ORDER:27866 SITE ADDRESS:
Pinnacle Environmental Mobil
P.O. Box 904 TEST DATE: 9/7/2011 800 34th Street
Clayton, CA 904 Bakersfield, CA 93301
SITE CONTACT:Peter Cloven PHONE NUMBER:925- 673 -5500
TECHNICIAN:Kristopher Karns PHONE NUMBER:661- 340 -8602 LICENSE:09 -1743
WATER IN BACKFILL: 0 . 0 0 " DATE 6 TIME OF LAST FUEL DELIVERY:+ 24 Hours
TANK INFORMATION:
WETTED)
PRODUCT TYPE:
TOTAL GALLONS:
PRODUCT LEVEL:
PERCENT FULL:
TEST METHOD:
WATER IN TANK:
TANK MATERIAL:
P.S.I.@ BOTTOM:
TEST DURATION:
FINAL LEAK RATE:
TEST RESULT:
TANK INFORMATION
ULLAGE)U /F ONLY
ULLAGE GALLONS:
START PRESSURE:
END PRESSURE:
TEST RESULT:
PRODUCT LINES:
LINE TYPE:
START TINE:
END TINE:
TEST PRESSURE:
FINAL LEAK RATE:
TEST RESULT:
MECHANICAL
LEAK DETECTORS:
MODEL:
SERIAL NUMBER:
CHECK VALVE PSI:
BLEED OFF ml:
LEAK RATE TESTED:
TEST RESULT:
TANK 1 TANK 2 TANK 3 TANK 4
Regular Plus Super
10000 10000 10000
ALERT 105OX ALERT 1050X ALERT 1050X ALERT 1050X
TEI LT -3 TEI LT -3 TEI LT -3 TEI LT -3
Pressure Pressure Pressure
10:30 A.M. 10:30 A.M. 10:45 A.M.
10:45 A.M. 10:45 A.M. 11:00 A.M.
55 PSI 55 PSI 55 PSI
0.004 0.002 0.002
Pass Pass Pass
Red Jacket FXT Red Jacket FXT Red Jacket FXT Red Jacket FXT
Fxly Fxly Fxly
15 PSI 16 PSI 15 PSI
33 ML 25 ML 22 ML
3 GPH @ 10 PSI 3 GPH @ 10 PSI 3 GPH @ 10 PSI
Pass Pass Pass
A) These systems and methods meet or exceed the criteria in USEPA 40CFR parts 280, NFPA 329 -87 and all
applicable state codes.
B) Any failure listed above may require further action, check with all regulatory agencies.
Technicians signature: Date: ManufactureranCderotrification No:
yLKristopher Karns q / / Alert:2008011 TEI: LT -098
0
Plus
C
76
OT0
Regular
C
76
0
VJ0
Super
07
6
I'
Sensor Key
1) VeederRoot TLS 350
2) Floats & Chains
3) Veeder Root 409 Senser
4) Emergency Shut Off
5) ATG Probe
6) FX1 V LLD
7) VeederRoot 208 Senser