BAKERSFIELD FIRE DEPARTMENT
OFFICE OF ENVIRONMENTAL SERVICES
INSPECTOR - S 04JUi C "6 91;Ua
1501 TRUXTUN AVE.
BAKERSFIELD, CA. 93301
Test Date: 05/18/2011
Order Number: 3183615
Dear Regulator,
Enclosed are the results of recent testing performed at the following facility:
CHEVRON # 355920
JITB # 7723
10 UNION AVENUE
BAKERSFIELD, CA. 93307
Testing performed:
Impact Valve
Leak detector tests
Monitor Certification
Secondary Containment -Spill Container
Sincerely,
Dawn Kohlmeyer
Manager, Field Reporting
PURPOSE: COMPLIANCE
TEST DATE: 05/18/11
CLIENT: CHEVRON PRODUCTS COMPANY
145 S. STATE COLLEGE BLVD
SUITE 400
BREA, CA 92821
TINA SCOLARO
714)671 -3356
TANKNOLOGY CERTIFICATE OF TESTING
8501 N MOPAC EXPRESSWAY, SUITE 400 AUSTIN, TEXAS 78759
TELEPHONE (512) 451 -6334 FAX (512) 459 -1459
TEST RESULT SUMMARY REPORT
WORK ORDER NUMBER: 3183615
CUSTOMER PO: 15071518
SITE: CHEVRON # 355920
JITB # 7723
10 UNION AVENUE
BAKERSFIELD, CA 93307
MINTA
661)861 -0543
Prnr1ur_t Pina Tinhtnacc Tact Racultc
TEST TYPE: TLD -1
LINE
ID
LINE
PRODUCT
LINE
MATERIAL
DELIVERY
TYPE
TEST RESULT
A B C D
FINAL LEAK RATE (gph)
A B C D
IMPACT
VALVE
FUNCTION
1 UNLEADED DW FIBERG PRESSURE
SERIAL #
ID
Y
2 PREMIUM DW FIBERG PRESSURE
MODEL # SERIAL #
Y
3 DIESEL DW FIBERG PRESSURE
P
Y
Fvictinn I Ina I aalr Ilatarrtnr Tact
LINE
EXISTING LEAK DETECTOR #1 EXISTING LEAK DETECTOR #2
MANUFACTURER MODEL # SERIAL # RESULT MANUFACTURER MODEL # SERIAL #
ID MANUFACTURER MODEL # SERIAL # RESULT MANUFACTURER MODEL # SERIAL # RESULT
1 VAPORLESS LD2000 07121111 P
2 VAPORLESS LD2000 unreadable P
3 RED JACKET FX1 -DV 6138 P
Now Ronlacamanf I Ina I a:%k natactnr Tact
LINE
ID
REP ACED LE ECTOR #1 REP CED LEAK DET CTOR #2
MANUFACTURER MODEL # SERIAL # RESULT MANUFACTURER MODEL # SERIAL # RESULT
ror owner aetanea report InrotTnatlon, visit www.tanKnology.com ana select un -Lme xeports-WKAY, or contact your local 1 anKnoiogy onice.
Tester Name:AXEL MEDINA Technician Certification Number:
Printed 06/01/2011 07:20 MTUTTLE
INDIVIDUAL TANK INFORMATION AND TEST RESULTS
r 743nknolkogy
TEST DATE:05 /18/11 8501 N MOPAC EXPRESSWAY, SUITE 400 WORK ORDER NUMBERS 183615
CLIENT:CHEVRON PRODUCTS AUSTIN, TEXAS 78759 (512) 451 -6334 SITE:CHEVRON # 355920
Printed 06/01/2011 07:20
TANK INFORMATION
Tank ID: 1 Tank manifolded: No Bottom to top fill in inches:
Product: UNLEADED Vent manifolded: YES Bottom to grade in inches:
Capacity in gallons: 19,703 Vapor recovery manifolded: YES Fill pipe length in inches:
Diameter in inches: 117.00 Overfill protection: YES Fill pipe diameter in inches:
Length in inches: 225 Overspill protection: YES Stage I vapor recovery: DUAL
Material: Dw FIBERG Installed: ATG Stage II vapor recovery: ASSIST
CP installed on:
COMMENTS
TANK TEST RESULTS Test Method:vaCUTect LEAK DETECTOR TEST RESULTS Test method: LDT -5000
Start (in) End (in)
Dipped Water Level: New /passed Failed /replaced New /passed Failed /replaced
Dipped Product Level: L.D. #1 L.D. #1 L.D. #2 L.D. #2
Probe Water Level: Make: vAPoRLEss
Ingress Detected: Water Bubble Ullage Model: LD2000
Test time: S /N: 07121111
Open time in sec: 8.50
Inclinometer reading: Holding psi: 34
VacuTect Test Type: NOT
Resiliency cc: 395 NOT
VacuTect Probe Entry Point: TESTED
Test leak rate ml /m: 189.0 TESTED
Pressure Set Point: Metering psi: 20
Tank water level in inches: Calib. leak in gph: 3.00
Water table depth in inches: Results: PASS
Determined by (method):
Result:
COMMENTS
COMMENTS
LINE TEST RESULTS Test type: TLD -1
LINE A B C D
Material: Dw FIBERG
Diameter (in):
Length (ft):
Test psi:
Bleedback cc:
Test time (min): NOT NOT NOT NOT
Start time: TESTED TESTED TESTED TESTED
End time:
Final gph:
Result:
Pump type: PRESSURE
Pump make: FE PETRO
COMMENTS Impact Valves Operational: YES
Printed 06/01/2011 07:20
INDIVIDUAL
TEST DATE: 05/18/11
CLIENT:CHEVRON PRODUCTS
TANK INFORMATION AND
Sir Tanknobgy
8501 N MOPAC EXPRESSWAY, SUITE 400
AUSTIN, TEXAS 78759 (512) 451 -6334
TEST RESULTS
WORK ORDER NUMBER3183615
SITE:CHEVRON # 355920
Printed 06/01/2011 07:20
TANK INFORMATION
Tank ID: 2 Tank manifolded: NO Bottom to top fill in inches:
Product: PREMIUM Vent manifolded: YES Bottom to grade in inches:
Capacity in gallons: 10,369 Vapor recovery manifolded: YES Fill pipe length in inches:
Diameter in inches: 117.00 Overfill protection: YES Fill pipe diameter in inches:
Length in inches: 225 Overspill protection: YES Stage I vapor recovery: DUAL
Material: Dw FIBERG Installed: ATG Stage II vapor recovery: ASSIST
CP installed on:
COMMENTS
TANK TEST RESULTS Tesf Method:vacuTect LEAK DETECTOR TEST RESULTS Test method: LDT- 5000 -:
Start (in) End (in)
Dipped Water Level: New /passed Failed /replaced New /passed Failed /replaced
Dipped Product Level: L.D. #1 L.D. #1 L.D. #2 L.D. #2
Probe Water Level: Make: VAPORLESS
Ingress Detected: Water Bubble Ullage Model: LD2000
Test time: S /N: unreadable
Open time in sec: 3.88
Inclinometer reading: Holding psi: 32
VacuTect Test Type: NOT
Resiliency cc: 225 NOT
VacuTect Probe Entry Point: TESTED
Test leak rate ml /m: 189.0 TESTED
Pressure Set Point: Metering psi: 23
Tank water level in inches: Calib. leak in gph: 3.00
Water table depth in inches: Results: PASS
Determined by (method):
Result:
COMMENTS
COMMENTS
LINE TEST RESULTS Test type: TLD -1
LINE A B C D
Material: Dw FIBERG
Diameter (in):
Length (ft):
Test psi:
Bleedback cc:
Test time (min): NOT NOT NOT NOT
Start time: TESTED TESTED TESTED TESTED
End time:
Final gph:
Result:
Pump type: PRESSURE
Pump make: FE PETRO
COMMENTS Impact Valves Operational: YES
Printed 06/01/2011 07:20
INDIVIDUAL TANK INFORMATION AND TEST RESULTS
i Tank nak)gy
TEST DATE: 05/18/11 8501 N MOPAC EXPRESSWAY, SUITE 400 WORK ORDER NUMBER3183615
CLIENT:CHEVRON PRODUCTS AUSTIN, TEXAS 78759 (512) 451 -6334 SITE:CHEVRON # 355920
Printed 06/01/2011 07:20
TANK INFORMATION.
Tank ID: 3 Tank manifolded: Bottom to top fill in inches:
Product: DIESEL Vent manifolded: Bottom to grade in inches:
Capacity in gallons: 7,029 Vapor recovery manifolded: Fill pipe length in inches:
Diameter in inches: 118.00 Overfill protection: YES Fill pipe diameter in inches:
Length in inches: 150 Overspill protection: YES Stage I vapor recovery: NONE
Material: Dw FIBERG Installed: ATG Stage II vapor recovery: NONE
CP installed on:
COMMENTS
TANK TEST RESULTS Test Method:vaCUTect LEAK DETECTOR TEST RESULTS Test method: LDT -5000
Start (in) End (in)
Dipped Water Level: New /passed Failed /replaced New /passed Failed /replaced
L.D. #1 L.D. #1 L.D. #2 L.D. #2
Dipped Product Level:
Probe Water Level: Make: RED JACKET
Ingress Detected: Water Bubble Ullage Model: Fx1 -DV
Test time: S /N: 6139
Open time in sec: 1.85
Inclinometer reading: Holding psi: 14
VacuTect Test Type: NOT
Resiliency cc: So NOT
VacuTect Probe Entry Point: TESTED
Test leak rate ml /m: 189. o TESTED
Pressure Set Point: Metering psi: 12
Tank water level in inches: Calib. leak in gph: 3.00
Water table depth in inches: Results: PASS
Determined by (method):
Result: COMMENTS
COMMENTS
LINE TEST RESULTS Test type: TLD -1
LINE A B C D
Material: Dw FIBERG
Diameter (in):
Length (ft):
Test psi:
Bleedback cc:
Test time (min): NOT NOT NOT NOT
Start time: TESTED TESTED TESTED TESTED
End time:
Final gph:
Result:
Pump type: PRESSURE
Pump make: FE PETRO
COMMENTS Impact Valves Operational: YES
Printed 06/01/2011 07:20
MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State of California
Authority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3 Title 23, California Code of Regulations
This form must be used to document testing and servicing of monitoring equipment. If more than one monitoring system control panel is installed at the facility, a separate
certification or report must be prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank
system owner /operator. The owner /operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date.
A. General Information
Facility Name: CHEVRON # 355920
Site Address: JITB # 7723
10 UNION AVENUE
Facility Contact Person: MINTA
Make /Model of Monitoring System:TLS -350
B. Inventory of Equipment Tested /Certified
Check the appropriate boxes to Indicate specific equipment inspected /serviced
City: BAKERSFIELD
Contact Phone No: 861 -0543
Date of Testing /Service: 05/18/2011
Work Order Number: 3183615
CA Zip: 93307
Tank ID: 1- UNLEADED Tank ID: 2- PREMIUM
In -Tank Gauging Probe. Model: MAG In -Tank Gauging Probe. Model: MAG
X Annular Space or Vault Sensor. Model: VR-409 Annular Space or Vault Sensor. Model: VR-409
X Piping Sump/Trench Sensor(s). Model: VR -208 Piping Sump/Trench Sensogs). Model: VR -208
X Fill Sump Sensor(s). Model: VR -208 Fill Sump Sensor(s). Model: VR -208
X Mechanical Line Leak Detector. Model: LD -2000 X Mechanical Line Leak Detector. Model: LD -2000
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
X Tank Overfill/High -Level Sensor. Model: OVERFILL ALARM Tank Overfill /High -Level Sensor. Model: OVERFILL ALARM
Other (specify equipment type and model in Section E on page 2). Other (specify equipment type and model in Section E on page 2).
Tank ID: Tank ID:
In -Tank Gauging Probe. Model: MAG In -Tank Gauging Probe. Model:
X Annular Space or Vault Sensor. Model: VR -409 7 Annular Space or Vault Sensor. Model:
X Piping Sump/Trench Sensor(s). Model: VR -208 Piping Sump/Trench Sensogs). Model:
X Fill Sump Sensor(s). Model: VR -208 7 Fill Sump Sensogs). Model:
X Mechanical Line Leak Detector. Model: FX1 DV 7 Mechanical Line Leak Detector. Model:
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
Tank OverfiIUHigh -Level Sensor. Model: OVERFILL ALARM Tank Overfill/High -Level Sensor. Model:
Other (specify equipment type and model in Section E on page 2). Other (specify equipment type and model In Section E on page 2).
Dispenser : 1 -2 Dispenser ID: 3-4
Dispenser Containment Sensor(s) Model: VR -208 X Dispenser Containment Sensors) Model: VR -208
XD Shear Valve(s). X Shear Valve(s)
ElDispenser Containment Float(s) and Chain(s). 7 Dispenser Containment Floats) and Chain(s).
Dispenser ID: 5 -6 Dispenser ID: 7 -8
RI Dispenser Containment Sensor(s) Model: VR -208 X Dispenser Containment Sensogs). Model: VR -208
xO Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). 71 Dispenser Containment Float(s) and Chain(s).
Dispenser ID: 9 -10 DispenserlD: 11 -12
RI Dispenser Containment Sensor(s) Model: VR -208 X Dispenser Containment Sensor(s). Model: VR -208
Shear Valve(s). X Shear Valve(s).
Dispenser Containment Floats) and Chain(s). Dispenser Containment Roat(s) and Chain(s).
If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification
I certify that the equipment identified in this document was inspected /serviced in accordance with the manufacturers' guidelines.
Attached to this certification is Information (e.g manufacturers' checklists) necessary to verify that this information is correct.
and a Site Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also attached
a copy of the (Check all that apply): X System set -up XO Alarm history report
Technician Name (print): AXEL MEDINA Signature: a
Certification No.: b -36644 License. No.: 743160 (Class 'A' General Enginering Contractor License)
Testing Company Name:Tanknology Phone No.: (800) 800 -4633
Site Address: 11000 N. MoPac Expressway, suite 500, Austin, TX 78759 Date of Testing/Servicing: 05/18/2011
Monitoring System Certification Page 1 of 3 Based on CA form dated 03/08
Site Address JITB # 7723
10 UNION AVENUE
D. Results of Testing /Servicing
Software Version Installed: 328.03
Complete the following checklist:
Monitoring System Certification
Date of Testing/Service: 05/18/2011
X Yes No Is the audible alarm operational?
X Yes No Is the visual alarm operational?
Q Yes No Were all sensors visually inspected, functionally tested, and confirmed operational?
Q Yes No ' Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not
interfere with their proper operation?
Yes No • x N/A If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) operational?
Q Yes No • N/A
For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate positive
shut -down? (check all that apply) X Sump/Trench Sensors; X Dispenser Containment Sensors.
Did you confirm positive shut -down due to leaks and sensor failure /disconnection? X Yes No
X Yes No N/A For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e.: no mechanicaloverfillpreventionvalveisinstalled), is the overfill warning alarm visible and audible at the tank fill points(s) and operating
properly? If so, at what percent of tank capacity does the alarm trigger? 2 ^/o
Yes' X No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the
manufacturer name and model for all replacement parts in Section E, below.
X Yes' No Was liquid found inside any secondary containment systems designed as dry systems? (check all that apply) Product;
X Water. If yes, describe causes in Section E, below.
X Yes No' Was monitoring system set -up reviewed to ensure proper settings? Attach set -up reports, if applicable.
X Yes No' Is all monitoring equipment operational per manufacturers' specifications?
In Section E below, describe how and when these deficiences were or will be corrected.
E. Comments:
gallon o water was removed from unleaded fi sump and diesel i sump.
Page 2 of 3 Based on CA form dated 03/08
Monitoring System Certification
Site Address: JITB # 7723
10 UNION AVENUE
F. In -Tank Gauging / SIR Equipment
Check this box if no tank gauging or SIR equipment is installed.
Date of Testing /Service: 05/18/2011
Check this box if tank gauging is used only for inventory control.
Check this box if no tank gauging or SIR equipment is installed.
This section must be completed if in -tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
X Yes No • Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
Q Yes No • Were all tank gauging probes visually inspected for damage and residue buildup?
0 Yes No' Was accuracy of system product level readings tested?
El Yes No • Was accuracy of system water level readings tested?
ElYes No • Were all probes reinstalled properly?
X Yes LID No' Were all items on the equipment manufacturers' maintenance checklist completed?
In the Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD) : Check this box if LLDs are not installed.
Complete the following checklist:
X Yes No N/A
For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance?
Check all that apply) Simulated leak rate: Q 3 g.p.h 0.1 g.p.h 0.2 g.p.h
X Yes No • Were all LLDs confirmed operational and accurate within regulatory requirements?
FX_j Yes E] No Was the testing apparatus properly calibrated?
X Yes No' N/A For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
Yes No' X N/A For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak?
Yes No • Q N/A For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected?
Yes No • M WA For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a test?
Yes No • X N/A For electronic LLDs, have all accessible wiring connections been visually inspected?
LJ Yes No • Were all items on the equipment manufacturers' maintenance checklist completed?
In the Section H, below, describe how and when these deficiencies were or will be corrected.
H. Comments:
Page 3 of 3 Based on CA form dated 03/08
SWRCB, January 2002 Page 1.
Secondary Containment Testing Report Form
Thisform is intendedfor use by contractors performing periodic testing of UST secondary containment systems. Use the
appropriate pages ofthisform to report resultsfor all components tested. The completedform, written testprocedures, and
printoutsfrom tests (ifapplicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: CHEVRON # 355920 Date of Testing: 05/18/2011
Facility Address: JITB # 7723 10 UNION AVENUE, BAKERSFIELD, CA, 93307
Facility Contact: MINTA Phone: (6 61) 861-0543
Date Local Agency Was Notified of Testing:
Name of Local Agency Inspector (if present during testing):
2. TESTING CONTRACTOR INFORMATION
Company Name: TANKNOLOGY , INC.
Pass Fail
Not
Tested
Technician Conducting Test: AXEL MEDINA
Component Pass Fail
Credentials: a CSLB Licensed Contractor
E
SWRCB Licensed Tank Tester
0
License Type: A- UT I License Number: 743160- 8 014 6 82
Manufacturer
Manufacturer Training
Component(s) Date Training Expires
0 0 0
Spill Box 2 PRE FILL X 0
3. SUMMARY OF TEST RESULTS
Component Pass Fail
Not
Tested
Repairs
Made Component Pass Fail
Not
Tested
Repair
Made
Spill Box 1 UNL FILL E 0 0 0 0 0 0
Spill Box 2 PRE FILL X 0 0 0 0 0 0
Spill Box 3 DIE FILL a 0 0 0 0
0 0 0 0 0 0
I I 0 0 0
D I 0 I 0 0 Ell 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 El-
El 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0
0 0 I 0 0 0 0 0 0
Ifhydrostatic testing was performed, describe what was done with the water after completion of tests:
WATER WAS LEFT IN ON SITE 55 GALLON DRUM.
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
To the best ofmy knowledge, thefacts stated in this document are accurate and infull compliance with legal requirements
Technician's Signature: , Date: 05/18/2011
SWRCB, January 2006
9. Spill Bucket Testing Report Form
This form is intendedfor use by contractors performing annual testing of UST spill containment structures. The completedform and
printouts from tests (ifapplicable), should beprovided to thefacility owner /operatorfor submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: CHEVRON # 355920 Date ofTesting: 05/18/2011
Facility Address: JITB # 7723 10 UNION AVENUE, BAKERSFIELD, CA, 93307
Facility Contact: MINTA Phone: (661) 861 -0543
Date Local Agency Was Notified ofTesting:
Name of Local Agency Inspector (if present during testing):
2. TESTING CONTRACTOR INFORMATION
Company Name: TANKNOLOGY , INC.
Technician Conducting Test: AXEL MEDINA
Credentials 1: X CSLB Contractor X ICC Service Tech. SWRCB Tank Tester Other (Spec) A- UT
License Number: 743160- 8 014 6 82
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: Hydrostatic Vacuum Other
Test Equipment Used: MEASURING TAPE Equipment Resolution: VISUAL
Identify Spill Bucket(By Tank
Number, Stored Product, etc)
1 1 UNL FILL Z 2 PRE FILL 3 3 DIE FILL 4
Bucket Installation Type: Direct Bury
Eil Contained in Sump
Direct Bury
Contained in Sump
Direct Bury
EKI Contained in Sump
E] Direct Bury
Contained in Sump
Bucket Diameter: 11" 11" 11"
Bucket Depth: 1411 1411 1411
Wait time between applying
vacuum/water and starting test:
0 0 0
Test Start Time (TI ): 0930 0930 0930
Initial Reading (RI ): 1111 10.5 " 1111
Test End Time (TF ): 1030 1030 1030
Final Reading (R F ): 1111 10.511 111t
Test Duration: 1 HOUR 1 HOUR 1 HOUR
Change in Reading (R F - RI ): 0 0 0
Pass/Fail Threshold or
Criteria:
0 0 0
Test Result: 0 Pass Fail El Pass Fail X Pass Fail Pass Fail
Comments - (include information on repairs madeprior to testing, and recommendedfollow -up forfailed tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements.
Technician's Signature: , Date: 05/18/2011
v
I
State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
Work Order: 3183615
ESO) & (ESV) Tcsting Form - Version 1- 6125!!007
Emergency Shutt Off (ESO) &
Dispenser Emergency Shutoff Valve (ESV)
ANNUAL TEST RECORD LOCATIONS AND TEST DATA
Emergency Shut Off (ESO) 'Testing Results
On s" in accordance with "ESO Vendor fetter (3- 21- 05).doc ", from Valero's Retail
Compliance Department, as a part of annual compliance testing, this representative tested the
Emergency Shut Off ESO switches indicated on this sketch. Findings listed below:
Dis eraser Emergency Shutoff Valve S Testing Results
On -/ in accordance with NFPA 30A this representative tested the automatic - closing feature
of the Dispenser Emergency Shutoff VALVE(S) (ESV) located in the supply lines at the base of each
individual island type dispenser indicated on the diagram below. Each device ( #) in all,
would automatically close. Findings listed below:
Site Map Of Locution and Placement of Devi= Tested.: v/r
jlTB
C -STORE
9 #5
L13101 #6 d : Lt1 #2 r L9
11 dsl ` #7 #3dsl
12•:,; , L14 #8 < L12 dsl #4 ; L10 <
ds! -- -- — z
F)ri L3 UL L2 `STPi ( I ; L1
i L8 U L6 L5
Vj1 (STP! V iST i L4
ESO I )SCJ SUS ' i
Si sture Of Representative:
Testing
company:_ Date:
Location Name: n 3 S l Store #:
N
Stag: ID #:
Date Called
S.k fardAddress: city: state: C
Emergency Shut Off (ESO) fNo, Provide
Operational? N Maintenance Log # Date Called
Disp, Emergency Shut Off IfNo, Provide
Valve (ESV} Operational? Maintenance Log # Date Called
Tanknology Inc. 11000 N. MoPac Expressway, Suite 500, Austin, Texas 78759
Emergency Stop Switch Test
WO# / Date 3183615 05/18/2011
Site ID 355920
Street address JITI3 # 7723 10 UNION AVENUE
City, ST BAKERSFIELD, CA
Total Time Testing E -Stop 10 min
Location of E -Stop
Shut Down
Turbine (Y /N) Dispenser (Y /N) Comments /Repairs
Outside Wall Yes Yes pass
Inside Wall
Other
Did ESO function correctly (remove 220 from both sides of the relay)? YES NO
Test Result (PASS / FAIL) PASS
If the test FAILS call the Elite Customer Solutions Center Immediately.
Date / Time / Name at Help Desk notified
If the test FAILS teach the site personnel alternative emergency shut down procedure
e.g. Circuit breakers, pump controller)
Date / Time / Name at employee trained
If system does not turn back on when the E -Stop Is reactivated, the site personell are to contact the BP Help Desk. The
Help desk will talk them through resetting the E -Stop and I or issue a 4 hour contractor response.
Technician Signature / Date
Rev: March 2007
0 05/18/2011
top T nl W10gy
8501 N MOPAC EXPRESSWAY, SUITE 400
AUSTIN, TEXAS 78759
512) 451 -6334
FAX (512) 459 -1459
TEST DATE:05 /18/11 WORK ORDER NUMBER3183615
CLIENT:CHEVRON PRODUCTS COMPANY SITE:CHEVRON # 355920
COMMENTS
Witness Annual Monitor Certification Inspection Testing with Inspector Ernie Medina Bakersfield
Fire Department confirmed on 5/3/11. Site contacted on 5/10 and confirmed testing with "MINTA ".
Technician checked in and out with 2ndSite and WO # 110518 -050 was given. Found & removed (1)
gallon of water from the unleaded fill and the Diesel fill sump. Replaced (1) Phil -tite SWF -100B
fill adaptor, (1) Syphon jet assembly, (1) Overfill light bulb
PARTS REPLACED
QUANTITY DESCRIPTION
1 SWIVEL FILL ADAPTER
1 SIPHON JET ASSEMBLIES
1 Overfill alarm light bulb
HELIUM PINPOINT TEST RESULTS (IF APPLICABLE)
ITEMS TESTED
HELIUM PINPOINT LEAK TEST RESULTS
Printed 06/01/2011 07:20 MTUTTLE
SITE DIAGRAM
i Tan
8501 N MOPAC EXPRESSWAY, SUITE 400
AUSTIN, TEXAS 78759
512) 451 -6334
FAX (512) 459 -1459
TEST DATE: 05/18/11 WORK ORDER NUMBER3183615
CLIENT:CHEVRON PRODUCTS COMPANY SITE: CHEVRON # 355920
9
10 L13
5 #
6 L11 #2
9L91
IT #11 dsl #7 #3 dsl 8
12 L14 #8 JL12 dsl #4 <5 L10 m
dsl z
@ OLIL L2 STP OI L1
cn
O
L8 L7 L6 L5 CAS
F V STP STP I L4
ESO DSL SU
Printed 06/01/2011 07:20 MTUTTLE
ATG Information Work Order# 3183615
110100
MAY 18, 2011 12:41 PM
CHEVRON 2000
10 UNION AVE.
BAKERSFIELD
Station 355920
SYSTEM STATUS REPORT
ALL FUNCTIONS NORMAL
150301
MAY 18, 2011 12:41 PM
1:CHEVRON 2000
150302
MAY 18, 2011 12:41 PM
2:10 UNION AVE.
150303
MAY 18, 2011 12:41 PM
3:13AKERSFIELD
150304
MAY 18, 2011 12:41 PM
4:Station 355920
151700
MAY 18, 2011 12:41 PM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50F00
MAY 18, 2011 12:41 PM
MON DD YYYY HH:MM:SS xM
160100
MAY 18, 2011 12:41 PM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 UNLEADED ON
2 PREMIUM ON
3 DIESEL ON
4 OFF
160200
MAY 18, 2011 12:41 PM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 UNLEADED
2 PREMIUM
3 DIESEL
4
160300
MAY 18, 2011 12:41 PM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 UNLEADED
2 PREMIUM 2
3 DIESEL 3
3183615
ATG Information Work Order# 3183615
160400
MAY 18, 2011 12:41 PM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 19703
2 PREMIUM 10369
3 DIESEL 7029
4 0
160700
MAY 18, 2011 12:41 PM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 UNLEADED 117.75
2 PREMIUM 117.75
3 DIESEL 118.00
4 0.00
160900
MAY 18, 2011 12:41 PM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 UNLEADED 0.000700
2 PREMIUM 0.000700
3 DIESEL 0.000450
4 0.000000
161200
MAY 18, 2011 12:41 PM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 UNLEADED NONE NONE
2 PREMIUM NONE NONE
3 DIESEL NONE NONE
4 NONE NONE
162100
MAY 18, 2011 12:41 PM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 500
2 PREMIUM 500
3 DIESEL 500
4 0
162200
MAY 18, 2011 12:41 PM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 18718
2 PREMIUM 9850
3 DIESEL 6677
4 0
162300
MAY 18, 2011 12:41 PM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 17732
2 PREMIUM 9332
3 DIESEL 6326
4 0
162400
MAY 18, 2011 12:41 PM
TANK HIGH WATER LEVEL LIMIT
3183615
ATG Information Work Order# 3183615
TANK PRODUCT LABEL INCHES
1 UNLEADED 2.0
2 PREMIUM 2.0
3 DIESEL 2.0
162800
MAY 18, 2011 12:41 PM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 19703
2 PREMIUM 10369
3 DIESEL 7029
4 0
162900
MAY 18, 2011 12:41 PM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 2955
2 PREMIUM 1555
3 DIESEL 1054
4 0
170300
MAY 18, 2011 12:41 PM
LIQUID TYPE
SENSOR LOCATION TYPE
1 UNLEADED ANNULAR TRI -STATE (SINGLE FLOAT)
2 UNLEADED STP SUMP TRI -STATE (SINGLE FLOAT)
3 UNLEADED FILL TRI -STATE (SINGLE FLOAT)
4 SPLIT TANK ANNULAR TRI -STATE (SINGLE FLOAT)
5 PREMIUM STP SUMP TRI -STATE (SINGLE FLOAT)
6 PREMIUM FILL TRI -STATE (SINGLE FLOAT)
7 DIESEL STP SUMP TRI -STATE (SINGLE FLOAT)
8 DIESEL FILL TRI -STATE (SINGLE FLOAT)
9 DISP. 1 -2 TRI -STATE (SINGLE FLOAT)
10 DISP. 3-4 TRI -STATE (SINGLE FLOAT)
11 DISP. 5.6 TRI -STATE (SINGLE FLOAT)
12 DISP. 7-8 TRI -STATE (SINGLE FLOAT)
13 DISP. 9 -10 TRI -STATE (SINGLE FLOAT)
14 DISP. 11 -12 TRI -STATE (SINGLE FLOAT)
15 TRI -STATE (SINGLE FLOAT)
16 TRI -STATE (SINGLE FLOAT)
190200
MAY 18, 2011 12:41 PM
SOFTWARE REVISION LEVEL
VERSION 328.03
SOFTWARE# 346328 -100•D
CREATED - 08.06.06.17,21
S- MODULE# 330160 -004 -a
SYSTEM FEATURES:
PERIODIC IN -TANK TESTS
ANNUAL IN -TANK TESTS
ISO
3183615
120600
MAY 18, 2011 12:41 PM
CHEVRON 2000
10 UNION AVE.
BAKERSFIELD
Station 355920
TANKALARM HISTORY
TANK UNLEADED
HIGH WATER ALARM MAY 18, 2011 10:22 AM
OVERFILL ALARM MAY 18, 2011 10:14 AM
MAY 28, 2010 10:04AM
LOW PRODUCTALARM MAY 18, 2011 10:13 AM
HIGH PRODUCT ALARM MAY 18, 2011 10:15 AM
MAY 28, 2010 10:04 AM
INVALID FUEL LEVEL MAY 18, 2011 10:13 AM
3183615
ATG information Work Order# 3183615
PROBE OUT MAY 18, 2011 10:27 AM
MAY 18, 2011 10:12 AM
MAY28, 2010 10:53 AM
HIGH WATER WARNING MAY 18, 2011 10:22 AM
DELIVERY NEEDED MAY 18, 2011 10:13 AM
MAY 15, 2011 2:50 PM
MAY 11, 2011 9:02 AM
MAX PRODUCT ALARM MAY 18, 2011 10:18 AM
MAY 28, 2010 10:04 AM
LOW TEMP WARNING MAY 18, 2011 10:28 AM
TANK 2 PREMIUM
HIGH WATER ALARM MAY 18, 2011 10:40 AM
OVERFILL ALARM MAY 18, 2011 10:30 AM
MAY 28, 2010 10:01 AM
LOW PRODUCT ALARM MAY 18, 2011 10:29 AM
JUL 27, 2010 4:11 PM
HIGH PRODUCT ALARM MAY 18, 2011 10:30 AM
MAY 28, 2010 10:01 AM
INVALID FUEL LEVEL MAY 18, 2011 10:29 AM
PROBE OUT MAY 18, 2011 10:46 AM
MAY 18, 2011 10:28 AM
JUL 27, 2010 4:11 PM
HIGH WATER WARNING MAY 18, 2011 10:40 AM
MAY 28, 2010 10:08 AM
DELIVERY NEEDED MAY 18, 2011 10:29 AM
MAY 18, 2011 10:28 AM
MAY 17, 2011 12:59 PM
MAX PRODUCT ALARM MAY 18, 2011 10:30 AM
MAY 28, 2010 10:01 AM
LOW TEMP WARNING MAY 18, 2011 10:47 AM
MAY 28, 2010 10:53 AM
TANK 3 DIESEL
HIGH WATER ALARM MAY 18, 2011 11:18 AM
OVERFILL ALARM MAY 18, 2011 11:12 AM
LOW PRODUCT ALARM MAY 18, 2011 11:10 AM
HIGH PRODUCT ALARM MAY 18, 2011 11:12 AM
INVALID FUEL LEVEL MAY 18, 2011 11:11 AM
PROBE OUT MAY 18, 2011 11:28 AM
MAY 18, 2011 11:10 AM
HIGH WATER WARNING MAY 18, 2011 11:18 AM
DELIVERY NEEDED MAY 18, 2011 11:09 AM
MAY 5, 2011 1:30 PM
APR 28, 2011 3:19 PM
MAX PRODUCT ALARM MAY 18, 2011 11:13 AM
LOW TEMP WARNING MAY 18, 2011 11:28 AM
130200
MAY 18, 2011 12:42 PM
CHEVRON 2000
10 UNION AVE.
BAKERSFIELD
Station 355920
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UNLEADED ANNULAR
MAY 18, 2011 9:44 AM SENSOR OUT ALARM
MAY 18, 2011 9:33AM FUEL ALARM
MAY 18, 2011 9:33AM FUEL ALARM
2 UNLEADED STP SUMP
MAY 18, 2011 9:44AM SENSOR OUT ALARM
MAY 18, 2011 9:31 AM FUEL ALARM
MAY 28, 2010 9:56AM SENSOR OUT ALARM
3 UNLEADED FILL
MAY 18, 2011 9:44 AM SENSOR OUT ALARM
MAY 18, 2011 9:31 AM FUEL ALARM
MAY 18, 2011 9:30AM FUEL ALARM
4 SPLIT TANKANNULAR
MAY 18, 2011 9:44AM SENSOR OUT ALARM
MAY 18, 2011 9:27 AM FUEL ALARM
MAY 18, 2011 9:27 AM FUEL ALARM
5 PREMIUMSTP SUMP
MAY 18, 2011 9:44 AM SENSOR OUT ALARM
MAY 18, 2011 9:25 AM FUEL ALARM
MAY 28, 2010 9:56 AM SENSOR OUT ALARM
6 PREMIUM FILL
3183615
ATG information
Work Order# 3183615
MAY 18, 2011 9:44 AM SENSOR OUT ALARM
MAY 18, 2011 9:28 AM FUELALARM
MAR 20, 2011 6:56 PM FUEL ALARM
7 DIESEL STP SUMP
MAY 18, 2011 9:44 AM SENSOR OUTALARM
MAY 18, 2011 9:29 AM FUEL ALARM
MAY28, 2010 9:56 AM SENSOR OUTALARM
8 DIESEL FILL
MAY 18, 2011 9:44 AM SENSOR OUTALARM
MAY 18, 2011 9:29 AM FUEL ALARM
MAR 23, 2011 6:01 PM FUEL ALARM
9 DISP.1 -2
MAY 18, 2011 9:44 AM SENSOR OUTALARM
MAY 18, 2011 9:35 AM FUEL ALARM
MAY 28, 2010 9:56 AM SENSOR OUT ALARM
10 DISP.3 -4
MAY 18, 2011 9:44 AM SENSOR OUT ALARM
MAY 18, 2011 9:34 AM FUEL ALARM
MAY 28, 2010 9:56 AM SENSOR OUT ALARM
11 DISP.5 -6
MAY 18, 2011 9:44 AM SENSOR OUT ALARM
MAY 18, 2011 9:37 AM FUEL ALARM
MAY 28, 2010 9:56 AM SENSOR OUT ALARM
12 DISP.7 -8
MAY 18, 2011 9:44 AM SENSOR OUT ALARM
MAY 18, 2011 9:37 AM FUEL ALARM
MAY 28, 2010 9:56 AM SENSOR OUT ALARM
13 DISP.9 -10
MAY 18, 2011 9:44 AM SENSOR OUT ALARM
MAY 18, 2011 9:40 AM FUEL ALARM
MAY 28, 2010 9:56 AM SENSOR OUT ALARM
14 DISP.11 -12
MAY 18, 2011 9:44 AM SENSOR OUT ALARM
MAY 18, 2011 9:41 AM FUEL ALARM
MAY 28, 2010 9:56 AM SENSOR OUT ALARM
3183615