HomeMy WebLinkAbout2011 FMC RESULTSMONITORING SYSTEM CERTIFICATION For Use By All Jurisdictions Within the State of California Authority Cited: Chapter 6 7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code ofRegulations This form must be used to document testing and servicing ofmonitoring equipment. A separate certification or report must be prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner /operator. The owner /operator must submit a copy of this form to the local agency regulating UST systems within 30 days of this date. A. General Information Facility Name: #347 Fastrip #26 Bldg. No.: _ Site Address: 2698 Oswell Street City: Bakersfield Zip: 93306 Facility Contact Person: Omero Garcia Make /Model of Monitoring System: Gilbarco EMC B. Inventory of Equipment Tested /Certified Check the appropriate bona to Indicate specific equipment Inspected /serviced: Contact Phone No.: 661 - 393 -7000 Date of Testing/Servicing: 8/11/2011 Tank ID: 12000 gal. Regular 1 Tank ID: 12000 gal. Regular 2 N In -Tank Gauging Probe. Model :847390 -107 U 847390 -107GaugingProbe. Model: 847390 -7 x] Annular Space or Vault Probe. Model: 794390-420x] L] Annular Space or Vault Sensor. Model: 794390 -420 x] Piping Sump / Trench Sensor(s). Model: 794380-208 x] Piping Sump / Trench Sensor(s). Model: 794380 -208 Fill Sump Sensor(s) Model: Fill Sump Sensor(s). Model: J Mechanical Line Leak Detector. i odel:FX1V Mechanical Line Leak Detector. Model: N/A Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model: Tank Overfill / High Level Sensor. Mode 1:847390 -107 U Tank Overfill / High Leval Sensor. Model: 847390 -107 Other (specify equip. type and model in Sec. E on Pg. 2) Other (specify equip. type and model in Sec. E on Pg. 2) Tank ID: 12000 gal. Super Tank ID: 12000 gal. Diesel x] in -Tank Gauging Probe. Model:847390 -107 Lx] In -Tank Gauging Probe. Model: 847390 -107 L] Annular Space or Vault Sensor. Model :794390 420 xx] Annular Space or Vault Sensor. Model: 794390 -420 X] Piping Sump / Trench Sensor(s). Model:794380 -208 U Piping Sump / Trench Sensor(s). Model: 794380 -208 Fill Sump Sensors(s). Model: Fill Sump Sensor(s). Model: x_1 Mechanical Line Leak Decector. Model.FX1V Mechanical Line Leak Detector. Model: FX1DV Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model: x] Tank Overfill / High Level Sensor. Model: 847390-107 Lx] Tank Overfill / High Level Sensor. Model: 847390 -107 Other (specify equip. type and model in Sec. E on Pg. 2) Other (specify equip. typs and model in Sec. E on Pg. 2) Dispenser ID: 1 & 2 Dispenser ID: 3&4 Fx] Dispenser Containment Sensor(s). Model: 794380 - 208 X] Dispenser Containment Sensor(s). Model: 794380 -208 X] Shear Valve(s). X] Shear Valve(s). Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s) Dispenser ID: 5 & 6 Dispenser ID: 7 & 8 rx] Dispenser Containment Sensor(s). Model: 794380 - 208 x] Dispenser Containment Sensor(s). Model: 794380 -208 Lx] Shear Valve(s). L] Shear Valve(s). Dispenser Containment Float(s) and Chains(s). Dispenser Containment Float(s) and Chain(s). Dispenser ID: North Transition Sump Dispenser ID: South Transition Sump FXj Dispenser Containment Sensor(s). Model: 794380 -208 LX] Dispenser Containment Sensor(s). Model: 794380 -208 Shear Valve(s). Shear Valve(s). Dispenser Containment Float(s) and Chain(s) Dispenser Containment Float(s) and Chain(s). If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility. C. Certification - I certify that the equipment identified in this document was inspected /services in accordance with the manufacturers' guidlines. Attached to this Certification is information (e.g. manufacturers' checklist) necessary to varify that this information is correct and a plot plan showing the layout of monitoring equipment. For equipment capable of generating such reports, 1 have attached a copy of the report; (check all that apply) x S et -up Alarm hlo grt Technician Name (print): Bryan A Self Signature: Certification No: 837501 License No: 804904 Testing Company Name: Confidence UST Services, Inc. Phone No: 800- 339 -9930 Site Address: 2698 Oswell Street, Bakersfield, CA 93306 Date of Testing/Servicing: 8/11/2011 D. Results of Testing /Servicing Software Version Installed: 327.04 Complete the following checklist: x] Yes No* Is the audible alarm operational? Fxj Yes No* Is the Visual alarm operational? x I Yes No* Were all sensors visually inspected. Ix I Yes No* Were all sensors installed at the lowest point of secondary containment and positioned so that other equipment will not interfere with their proper operation? TT–Y—es No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) x N/A operational? X Yes No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary N/A containment monitoring system detects a leak, fails to operate, or is electrically disconnected? Ifyes: which sensors initate positive shut -down? U Sump /Trench Sensors U Dispenser Containment Sensors Did you confirm positive shut -down due to leaks and sensor failure /disconnected? Yes; L] No; Ix] Yes No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no L-1 N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visual and audible at the tank fill point(s) and operating properly? If so, at what percent of tank capasity does the alarm trigger? L9p % Yes* No Was any monitoring equipment replaced? if Yes, identify specific sensors, probes, or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E, below. Yes* U No Was liquid found inside any secondary containment systems designed as dry systems? Product; Water. If yes, describe causes in Section E, below. TX Was monitoring system set-up reviewed to ensure proper settings? In Section E below, discribe how and when these deficiencies were or will be corrected. E. Comments' Replaced the Diesel PLLD. F. In -Tank Guaging / SIR Equipment: Check this box if tank guaging is used only for inventory control. Check this box if tank guaging or SIR equipment is installed. This section must be completed if in -tank guaging equipment is used to perform leak detection monitoring. Complete the following checklist: U Yes No* Has all input wiring been inspected for proper enter and termination, including testing for ground faults? F_1x3 Yes No* Were all tank guaging probes visually inspected for damage and residue buildup? x Yes 7 No* Was accuracy of system product level readings tested? xj Yes No* Was accuracy of system water level readings tested? x Yes No* Were all probes reinstalled properly? U Yes 1 No* I Were all items on the equipment manufacturer's maintenance checklist completed? In the Section H, below, describe how and when these deficiencies were or will be corrected. G. Line Leak Detectors (LLD): Check this box if LLD's are not installed. Complete the following checklist: Lx] Yes No* For equip. start -up or annual equipment certification, was a leak simulated to varify LLD performance? Check all that apply) Simulated leak rate: Lx]3 g.p.h.: 0.1 g.p.h.; 00.2 g.p.h.; x7 Yes No* Were all LLD's confirmed operational and accurate within regulatory requirments? x Yes No* Was the testing apparatus properly calibrated? xj Yes No * For mac anica LLD's, does the LLD restrict product flow if it detects a leak? N/A Yes No* For electronic LLD's, does the turbine automatically shut off if the LLD detects a leak? Lx] N/A Yes No* For electronic LLD's, does the turbine automatically shut off if any portion of the monitoring system is x] N/A disabled or disconnected? Yes No* For electronic LLD's, does the turbine automatically shut off if any portion of the monitoring system U N/A malfunction or fails a test? Yes No* For electronic LLD's, have all accessible wiring connections been visually inspected? X] N/A x Yes D No Were all items on the equipment manufacturer's maintenance checklist completed? In the section H, below, describe how and when these deficiencies were or will be corrected. H. Comments: Replaced the Diesel PLLD. HA22 I DE112 I TY 111 SAIJI-Eri 2r. 9L 02110.1. ST I3AI,ERSI- I an m301,:- G61 - I AUG I 1. 201 1 8:29 AN su'ritfs: SY21'Em IJNITZ 01,11,1 20iARll 1 ED I M U.S. RS-232 S'EC:URITY f:EPOP'l, S?YST9l I-iiI'jGuA'3'E ODE : EllSABLED ENGLISH I SD 6811:;;' Ill.'; I-ItiPI-I SYSTEM DATE,'TIME FORMHT 201,11-1 BOARD 2 (RS-2232; MON I'D VY","! Hll:f,tl:SS "I"I BAUD RATE 9F.00 PAR I TY N;,/I4E I NVENTi•Ye',' r,,Is, F.,,r FA2'1*R IF, 346 STOP 13 1 1 STOP 2698 QS&IELL '.iT DATA LE141"TH: 0 DATA BAKERSFIELD 93'1'Ur- f%2-232 SECURITY T I ; 1.11,11 1 1 CODE : DISABLED VOLUI*'IE d 76913 GALS 431171 TINE 1 6: I)Q AM 41,11 BOARD 3 < RS-232) 90% ULI-ml--L- 31 10 GALS SHIFT TP-IE 2 DISABLED BAUD RATE 9600 Ti VOLIRIE - 7576 ALS SHIFT TIME 2 D ISABLED PAP I TV NONE HEIGHT - 50.7 1 1 NCHES SHIFT TjI-IE 4 D &iBLED e.,TOP BIT I STOP WATER VOL - 0 GALS DmTli LENGTH: 8 DATA WATER = 0. 00 1 Nt' HES TANK PER TST NEEDED WRN RG-2'32 SE,;URI*Pv' TEMP . 81.1 DEG F D I,":q-irjI.ED C:ODE : DISiABLED TANK ANN TST i,iii:EriED wRoi 111 &-;BLED T 2: 0 1 M-EL AUTO TRANSMIT SETTINGS; VOLUME . 084 GALS L I PIP RE-ENABLE ULLIAGE . 8916 GALS PAS2. L 1 NE TEST AUTO LEAK ALARM LIMIT 90% ULLml.;F= 7716 i';ALS DISABLED Tf'; VOI.IJI-IE - s0-1 f3 GALS LINE PER 'rST 1,10'XiED WRN AUTO HIGH WATER LIMIT IIE 1131 IT = l. 1;*; 1 NCHES DISABLED D I SABLED WATER VOL - 15, ALE L I 14E ANN TST NEFIiEb WRN AUTO OVERFILL LIHIT WATER = 0. B I I KIES DISABLED DISABLED TEI'JP - 85.5 DEG IF AUTO LOW PPODU,T PR I PIT TC* VOLUMES b I SHBLED ENABLED AUTO THEFT LIMIT T D I SABLED VOLUT•IE s 33:35 GALS TEMP GOPIPEN:34:iT I ON AUTO DEI,, I VFR%l STi-iPff ULLA' E = 1,1665 GALS VALUE (DEC F ?: 60. 0 1) 1 SABLED 90% ULLH--;E- 7465 GALS STICE HEIGHT orFsIET ALITO DELIVERY END TC Voi-Ifilt = 32-74 GALS D I SABLED D I PABLED HEIGHT = 30. e9 1 N'--'HE2 ULLHGE: 90'. ALITO FXTERNAL iiovr ON WATER VOL = 0 GALS DISABLED WATER - 0.00 1 NCHES H-PPPTOCOL L" TA FORMAT AUTO EXTERNAL I NPUT OFF TEMP = 96. 1 DEC; P I IE I C;HT D ISABLED DAYLIGHT SmV111*3 TIME AUTO SENSOR FUEL rd-ARM EN BLED DISABLED T 4: UNL 2 START Dpi F AUTO SENSOR WATER i•iLiiRfl VOLUME 75+68 MAR WEEK 2 SUN DISABLED ULLAGE 40,12 GALS START TIME AUTO SENSOR OUT ril,r•iPM 9M. Lll.Lml*;E- 2842 CALS 2:00 AM D I SABLED TC VOLUME = 7842 GALS END DATE RE I OHT - 60.44 1 NCHES NOV WEEE I SUN WATER VOL = 31 GALS END TIME WATER . 1.01 1 1,1031ES 2:00 AM TEMP . 80.7 DEC, F RE-DIRECT LOCAL PRINTOUT EIZ EI,IPO PROT(A'OL PREFIX IRS-23'2, END OF NESS*kc E S DISABLED sysTEH c,',Ei:'IJRJTI ' ' CODE 1 000000 P'lf-',INTENmIlC'E HISTORY ISIABLE1*1 sOFI'I,jp,RE REVISIONc LEVEL VEPS I ON 330.01 TANK 1-:HI;R'r SECURITYSOFTWmRElt34000- 11-11) -D 111 ritifiLED CREATED - 10.07.23.1-1.25 S-11000LEO 3;313160-00.1-a r:UsToll 1AI'MRI-12 SYSTEN F&iTUPEIG: DISABI-Ell PER I SID K' TEST2 I f L:Kl "I il: NOT I D I ;it P(X:vk ISO 21 6o HA22 I DE112 I TY 111 SAIJI-Eri 1 hJ-'rANI: E'fI IP T 2: D I E-,EI_ T *413: I NIP1OrAU, "T COVE THEPI'lr;L COEFF :.000•J50 PP3 '!' THEPHHL : =OEFF :.000701? T I : UWL ) T , I : UL I I TANl: rs 1 iNETER TA14K PP•OI• I LE 96.00 1 PT THhN}: D f r fhF1'L'F 96, 4iu THERMAL CuS FF :. 000700 FULL VOL MOO TANK PROF I LE FULL. VOL 1 FT 12000TANKGIWIETER96.00 TANI, PPOF I LE I PT FULL VOL 12000 F'LOmT 4.0 IN. FLOAT SIZE: 4.11 IN. FL0mT r:I' °E: 4.0 IN. WriM WARN I N;; : H1+::H w/WER LIMIT: 2.0 3.0 HIkcHR WATER ILIMIT: 3.0 WATER WAPN l hh: 2.0 KAX OR L 319EL VOL: 120071 MAX L,riEl. VOL: 1 2000H101WHTERLIM1'r : 0.0 C >VERF 1 LL L l h91 T r F IOVERF ! LI.. [. i J•1 l T 901. MAXOR Lii8EL VOL: 12000 H I CH F'RDuCT 10600 95:: H I :H F RODU "r 10600 95 0OVER'F I Ll. L 1111 T 90 %6 I i -IOl1 1 1 41, HIGH PI ODLU,T 101800 9.FiiV DEL I VERY L I M I T 15' . 1800 C EI. I VEr'f LIMIT 15 %: 11400 16dd DELIVERY LIMIT 15% LOW fROnWT 1 fJOu LOW P T 18001fll0LEAKALHRILIMIT: 9! LEAK ALARM L t P! 99 LOW PPODUCIT 1800 SUrjl'!EPJ 1.02S LIMIT : TANK T I LT 99 0 00 L?CEIV I.Oyti L I M I T : 94 LEAK HLmRM LIMIT: 95 I TriNl: TILT PRODS OFFSET 0.00 0.00SUDDErfLINIT: 99 TANK Ti LT 0.00 PPOBE OFF! :L; r 0.00 81 PHON rt;, l I F 0I.DEL, rHt4F :r; S I PHO14 MmN I FOLDED TAIV1:sI'll : M,urfl, TO : NONE fiHV 1 F1LGt;C fHFFB LINE 1,44N I FOLUID T;il Ttl: NONE Jl:r5 LINE MAN I FOLDED TANK'S NONE TP: NONE LINE MHIV I FOI_bED TAPIV TG : NONE LFril, 1-11 N E'ER 100 (C': LEH1; 11114 PEP I OW : I% 1 .' tPERiObIC` TEST T': PE PEP1ODit' 'fIS'f T ".'PL 0 LEHK 1,91N PhRI Or) IC: 1",, rHN1.HRt ETmIVI,r iFJI?U FEp 1 oI 4I %` '1 k5l' WIPE PER I Ori I t TEST FW 1 L PERIODIC Tk 'r !~r I I_ 1'HNL',HRCr MLAF.11 D I S;i8LE1 ral_AR19 ti I E'H(3LEU PEb: I Ol.+ I •.' TEL'r Fri I L GP.CY32 TMT Fri I L GRO5:3 TE.'T Fri I LHLARI11C11:ShBLED HLHRl*l f 1 I F FSLE- Lj HLAP.MI 1:11 SHBLED CROSS TE-A' Fi4IL PER TfS'r vVEP,A+ ?INr::: OFF PER TEfiT AVM4 114( ;: OFFHLriRMII) I SABLED TANI: TrST NOT I P,' : OFF frit'!li T'I f r NOT 11' "; : OFFIER '1'F,:T riVERriG I N1:: OFF TNK T "f S l I Wlq fjREHf::0F1' TNK T`1 r SIPHON DF!1?HJ' 01=FTrim: 1'E' ""1' tti T 1 F^,': OFF DEL I VEP,' Dii -I. 1 I MIN DEI. I VCR',` BELAY I MINT14KT.Sr $1PHOhl BREAK:01=F PUMF' 1'HRESHtiLD : 10.00: PUMP THRESIiOLD 10.00% DELIVEP"' l"EL.HY I M114 PUMP THkESHOLD : 10.00% T 4: UPIL 2 PPOC,(Jr'T CODE THERMAL --'OEFF 01:07Ci0 I Ti4NY DIHMETER 9C, , ocl TANK PROFILE I PT ' 1FULLVOLI 000 FLOAT SIZE: 4.0 IN. WATER WARN I 1,1C. 2. C: HIGH WATER LINIT: 3.( PIK%' OR LABEL VOL: 12,001) Alii RFILL LIMIT 901. 10G00 11 W PRODUCT 95% I I 40LI DELIVERY LfmIT 1800 LOW PPO[.oUr:T I Aclo LEAK mlA-Pll LIMIT: 91:0 iP-N LO:;'12 LIMIT: 99 TANK T I LT 0. DO FIPOBE OFFSET 0.00 SIPHON MANIFOLDED TANKS Ta '. NONE LINE MmNIFOLDED Tit: NONE LEAK MIN PEPIONC: PEP1001C TEPT TYPE STANDARD PERIODIC TEST FmIL MLAR11 DISAM-ED ROSS TEST FAIL I,LAPM N $AL.LET, PEP TEST mVEPhl3I14,1: OFF Tuii, NOTIFY: OFF TIC TST SIPI-KIN BREi-iY.:OFF GEL I VER, DELAY PUMP THR-E.".14GLE' I Cl. 00% LEAK TEST METHOD I'F-ST ON DHTF : FiLL TANKJUL. 23. START TIME : 111SACILEE, TEST RATE :0-'20 -,i4L.,HRDURoTioiq ; 2 HOURS TST EARLY STOP :bISHBj-P-Lj LEA)! TEST REPORT FOPI-IFiT rJORIIAL L101.110 SENSOR SETUP PUMP 'SEPISOR L I 'UHL I STP TR I -STATE (2 1 NC;LE FLOAT) ci!TEGORl/ : STP SUMP L 2: UlqL I Mll TRI-STATE iS1103LE FLOAT) C:ATEC;OR', : A14NULHR 13•A,::E L 3: risi. STr• TRI-STIATE (SIN(iLE FLC44-1-) t-','ATEC,,OR"l : STP SL0,IP L 4:DSL AM,) TPI -STATE (S,111431-F. FLO 4*1') 4"ATECORIA, : ANNULAP SPIA(:c L 6:PNL Hl,114 TPI-STATE FLOAT) AI*•r;ORY : ANNULAR SPH,-.:E L 7:UNL 2 STP TRI-ISTATE (S1N(;LE FLOAT) STP SlYlp L 8:UNL '--' ANN TRI-S:TATE (Sll.li';LE FLOAT 4TEr;OR7 : ANNULAR SPACE L 9: D 1:;1:' 1 -'w TRI-STmTE {SINC;LE FLN);:iT> CATEGORY : DISPENSER PAN LIQj:DISP 3-4 TRI -STATE FI-Ot-ir) C'ATE,';ORY : rjISPF.M-.*,CR PHN Ll I :Llk]:, 5-6 TRI-S,rAi,E 42INt',I-E FLOAT? 04TEc;w,l : DISPENSER PAN Li2:D15P 7-8 TR I -SITATE (1.1. 1 NXl:.* FLOAT) C:ATEGOPY : DISPENSER PAN•S LI'2:TRAWS S-3-111P I'K) TPI-STATE (SII,)i'!-LE FLOAT) CATECORY : PIPING SUMP 2kii1p 130 TP I • STSI-E FL.GHT> 04TCCOR", : PIPING ..;Ul,lp L 19: PI%IL PTf/ TRI-STATE FLOF Ti Ci-%TE13ORl,' : STP SlJI•lP 2 1 :11141. 1 TAN)" 0: DISPENSE VIODE: STANDARD S 2: PAIL TAIIJI' it; 3 D I SPEPISE MODE: STANDARD OUTPUT l,"ELAY SETUP R I: UPIL I TYPE: PUMP CONTROL OUTPUT TANK 9: 1 i- iiDyin SENSOR ALMS L I : FUEL ALARl"I L 7: FUEL ALAFq,l L 9: FUEL ALARM 1.10: FUEL_ ALARM L I :FUEI. ALARM L 12: FIJEL ALARM L I;SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 9:SENSOR OUT ALMR11 L I Cl: SENSOR OUT ALARM 1.11 :SENSOR OUT HLAPPI 1-12:SENSOR OUT ALARM L I :SHORT ALARM L ?:SHORT ALARM L 9:SHORT Ai-Arm I-Ifi:SHORT ALARI L I :SHORT L 12 : 9 14OPT oLARM ISD SITE AL(-,,RNS I C;ROE;,,, PRES I'M I L 1S DE,,'RD PRES FAIL ISE, VAPOR LEAK FAIL ISD VP PRES FU I,'jiD VP STATUS FAIL ISD HOSE ALARMS ALL :(-',RO.SS COLLECT F,*-i]L ALL :FjE(3RCi COLEE.C-'r FAH. ALL:FLOW COLLECT FAIL R 2:PNL TYPE; PUMP i::OiITROL OU'IFUT I'ANI: A '. 3 LIQUID SENSOR ALMS L 9:FUEL ALARM LIO:FUEL ALARM L I 1 : FUEL ALAR11 L12 :FUEL ALARM LIS:FUEL ALARM L 9:5ENSOR OUT ALARM LIO:SENSOR OUT ALARM LI1:SENSOR OUT ALARM Ll_:SENSOR OUT ALARM L15:SENSOR OUT ALARM L 9:SHORT ALARM LIO:SHORT ALARM 1 -1 1 : SHORT ALARM L 1 2 : SHOPT ALARM L15:S1-10RT AARII I_ 15: RHtP.T ALARM 1$;I' y 1'I C. ALARMS I SI, PREP FAIL IS* DEGPL, PREP, FAIL 1 SD VAPOR LEAK FAIL I PD VP PPES FA I I_ I SL, 'III•= :Ti4TUw FAIL ISO HOSE ALARMS A1.L : CROSS COLLECT FH 1 L ALL : LIEGRD COLLECT FAIL ALL : FLOW C'OLLEVT FA 1 I_ R 3: DSL TYPE: STANDARD NORMALLY CLOSE[, TANK P: NONE L I GU 1 D SENSOR ALMS L 3 : FUEL ALARil L 9:FUEL ALARM LiI:FUEL ALARM L 12 : FIJEL HLARPI L 13 : FIJEL ALARM L14:FUEL ALARM L 3:5ENSOR OUT ALARM 1_ ':SENSOR OUT (ALARM LI0:SENSOR OUT ALARM 1 -11 :SENSOR OUT ALARM 1..12:SENSOR OUT ALARM 1- 13:SENSOR OUT ALARM L 14 : SENSOR. OUT ALARM L 3 :SHORT ALARM L 9:8HORT ALARM I:IO:SHORT ALARM LII:SHORT ALARM L12:SHORT ALARM L13:SHORT ALARM L14:SHORT mi.ARM R S,:OVERFILL ALARM T,'PE : STANDARD NORMALLY OPEN TNNK It: NONE IN -TANK ALARMS A1.1- : «VERF 1 LL ALARPI ALI- :H1C:H PRODUCT r LIiRM AL..L:MAX PRODUCT ALARl,i SKARTSENSOR SETUP s 1:PS 3 -4 C:ATEC ;Ok`, VAPOR PRESSURE s 2 : FI'I 1 -2 C:ATECORY AIR FLOW METER 5 3:17M 3 -clCATEGORYAIR• FLOW Ihl~7'ER s 4:Fi'I 5 -6 CATE13ORY AIR FLOW METER CATEGORYRY AIR FLOW MEJ'ER EVP.ISD SETUP EVR TYPE: V)i;UUM ASS18T VHC:UUm ASS I S'F TYPE HEALY VAC. NOZZLE A•L RANGE MAX: 1.15 MIN: 0.95 VAPOR PROCESSOR T'-,PE NONE ANALYSIS TIMES TIME: 10:00 AM DELAY [III MUTES: 1 ACCEPT HI"-%H ORVR : DISABLED I SD HOSE 'FABLE ID SERIAL IVUM LABEL.. ID FP FL HL AA RR 01 01 01 02 01 - 02 02 02 02 02 01 02 03 03 03 02 02 02 04 04 04 02 02 02 05 05 05 02 03 02 06. 06 06 02 03 02 07 07 07 02 04 02 08 08 OB 02 04 02 I SL, A.I RFLOW PIETER MAP ID SERIAL IVUM LABEL.. 1 8424 FM 1 -2 2 7358 FM 3 -4 3 8425 FM 5 -6 4 8313 Fh'I 7 -8 1 SD FUEL ( %RADE HOSE I V& 1 2 3 4 FP MHH MHH MHH MHH AA 01 -201 301 901 5 -U -1 02 202 302 902 5 U 1 03 203 303 903 U U 04 204 304 904 U U 2 05 205 305 905 5 U 3 06 206 306 906 5 U 3 07 207 307 907 U U 4 Be 208 308 908 U u 4 LABEL 'TABLE 1: UNASSIGNED -- -- - 2: BLEND3 3: REGULAR 4: MID GRADE 5: PREMIUM 6: GOLD BRONZE 8: SILVER y: BLEN92 10: BLEND4 PMC SETUP P11C VERSION: 01 .03 VAPQP. PROC:ESSOP TIPS: NONE PROCESSOR CONTROL LEVEL: NONE kiLAPM H PEPoR*r iAL.ARM - T I : UNL I LOW PRODUCT HLARM APR 5. 2011 4:13 P11 SUbI:iEIq 1.02,8 mLi4Rm MAY 51 :11711 1 10: 35 Pill APP 20, 2011 1:14 AM APR 20. :2011 12:32 AM DEL I VERY NEEDED APR 5. 2011 4:13 PVI n a r. n ENT, - .. A ft s ALARM HISTORY kEPORT I ;ADARM T 2: D I E.9F-L LOW PPOD1,111' MLAP111 JUL 26. 2011 6:59 PM JUL 21. 2011 3:24 PM IlliR .l. 2011 2:20 AM DEL NEEDED JUL 26. 2011 6:59 pm JUL 21- 2011 2:24 PI'l IIMR •1. 2011 3:213 AM A rz x m 4 END - r. --k A - HEARTH HISTOP", PORT IN-TfiNli' ALARM T 3: PNL LOW PRC)LjLD-T tiLARM JUL 1. '011 4:56 PM PP06E OUT FEB 1. 2011 13:41 Pi"I DELIVERY NEEDED JUL 1. 2011 1:56 PH w, x w- ElIff, , '- p- rt -,. ALARM HISTOPY REPORT I N-TANK eiLmR11 T 4 : UIIL 2 LOW PRODUCI' i4l-MRM mPR 5. 2011 6:05 Pill PROBE OUT FEB I. 2, 0 1 1 0 HM JAN 30. 201 1 4:23 Al JmN 30. 2011 2:14 HM DEL I VERI ' ' NEEDED HPR S. 2011 6:0.1 PM r P,. , s- Ellf, , z )-, -t A ALAPM Hl'-zXORY PEpi.,,Ffr 1. 1 : LIPIL I STP STP SUMP, FUEL ALJ•MI JUL 10. 2011 7:17 Pill AI A - END A A A X P; LARIII HI TORY REPORT SEWSOR ALAW L 2: UPIL I ANN mNHULmP SPr -a:E k , t END - 1--• -, It h ALARM HISTORY REPORI SEI oP ADARN L STP SUI'IP FUEL ALARVI JUL 12. 2011 3:58 PM FUEL FiLiirtl JUN b. 21II 1 4:07 Htl FUEL AIJQ1 MAY 27. 2011 4: 2? mtl r P; a . ENE- " A 11 1 K ALrifll HISTUPY REPORT Al-iiRll Hl 'TORY PEPOPT i-il.AFM HISTORY REPORT SENSOR ALl4RM ------ SEm',OR ALiAPM ----- SENSOR mLiAR11 1.11:b1sp 7-8 L 4:bSI. WIN L 8: UNL 2 ANN DISPEIC.ER PAN ANNULAR SPA (E ANNULAR S))A('E t * . x END r. A r•O,ARTI HISTORY PEPORIT 1. &:PNL. ANN NNUIjW. SN-v. t -: - - - END A 4 . -. n oiLHkl'-1 His,rowl, ki:pokT 2CN,. OR ALHRN L *:, STP 811*P SUMP FUEL ALARM JUL 7. 2011 rll FUEL HL;iRtl rhAy :17. 2011 121:1b PM K - j. - rNrj - - :t . h% e,, Er4o - A r t • tLaakM His-rOm, Fn.Powr S.EN$0K, 04LARM L 9: 11 1.3P 1 -'? DISPENSSER PAN r h . -- , END < r. e IALmPl-1 HISTOR" REPOPT ENSOR ALARM LIO:rflS,p 5-4 DISPENSER VAN r s- * END r. n m i r iLoPll Hlb*']'OPY REPORT SENSOR HLAPM L I I : Ei I S'P 11-6 PAN r A - END a ^ , -. In ml-iiRM HISTORY REPORT SENSOR riLAF'I'l 1,13:TRANS SUMP NO PIPING SUl'iP j ^ ^ x END A , - f- P. W.fiPm HISTORY REPORT SENSok ALiAPt•i L14:TRANS SUMP SO P I P I NG , l:;LlMP ft r- Nrl P m ); . HLARI•I W I STOK / REPORT L15:PNL STP STP SUMP. FUEL_ ALHRrj JUN 6- 2011 6:29 Hhl FUEL kjiF9l t-iPK 7. ::011 9:37 P19 FUEL ALmktl KKR 2.1. '13 t I 4: 5a PN m r A . . END - - - - SENSOR ALARM - - - -- L 7: UNL. 2 STP STP SUMP FUEL ALARM HUG I1. 4U11 9:10 AM SEllC*R ALARM -- - -- L 1:UNL I SIP STP SUMP FUEL ALARM AUG 11 . 2711 9:11 AI9 SENSOR -- --- L 3 : LPL k*,TP STP SUMP FLIEL ALARM AW 11, 2011 9:12 µN9 FASTRIP 346 2698 OSWELL ST BAXERSFIELG 9330b 661- 872 -6721 AUG 11. ='01 1 9:15 ;;n SY,fFII STATUS Rrf -OFT i : G Gkt;iC;:; I"PES WARN - - INVENTOR'! REPORT T I: LINL VOLUME - 9185 GALS ULLAr.E - 2815 GALS 90%. ULLHC -E- 1615 GALS Tf; VOLUME - 896E GALS HE I GI IT - 60.67 1 NCHES WATER VOL - 33 GALS WATEF - 1.33 INCHES TEMP - 90,8 DEC, F T 2 : fi I E.SE1_ VOLUME a 087 GALS ULLHC-E = 5013 C;ALS 901; ULlj-v::E- 3813 C:ALS To" VOLUME - 6832 GALS H£I(:HT - 54.22 1 NCHES WATER VOL a 20 1,ALS WATER - 0.95 INCHES TEMP a 931.3 DEG F i T 3:PN1. VOLUME - 4803 f:;ALS ENSOR ALAI ?I.1 - - --- ULLAGE e 7197 GALS LI5:PPJL STP 90% ULLAGE- 5997 GALS STP SUMP TC VOLUME - 4701 GALS FUEL HLHRt1 HEIGHT - 40.45 1NCHES AUG 11. '?Ull 9:12 AM WATER VOL - 54 GALS WATER - 1.86 1NGHES TEMP - 9U.1 PEG F T 4:UNL 2 VOLUME - 7612 GAL. ULLAC;E = 4388 t ;AI.S 90:: I.II..LH1;E- 3188 GALS TC VOLUME - 7455 ALS HEIGHT - 58.21 I NCHES 1- 12:1;11 SP '7 8 WATER VOL - 15 GALS 1'11 SPENSER TAN I WATER - C1.79 1 NC:HES FUEL. ALARI TEMP - 89.5 DEC F HUG 1 1. 201 1 9: 12 rim r* x END i P1SPEN -ER VAN FUEL AI..HRN AUG I I. 201* 1 9:14 All SENSOR HLHP.M - - -- L13:TRAN63 SUMP NO P I P I Ni' SUMP FUEL ALARM AUG 1 1 . 2011 9: 15 #-rl 8Etr;c)R fkbiRll - -- -• - L. I a :TRANS 51.Ih1F :=10 r rP rr11- c ImIP -.. FUEL ALARM AUG 11. 2011 9:14 All SEN:;Ok HLARI1 L 9*1 SP 1 DISPENSER PAN FUEL ALARM AUG 11, 2011 9:16 Afl LII:DISP 5 -6 1? I SPENSER PAN FUEL. ALARM HOC: I1 . 2011 9:17 AN F`H4,TkIN 346 2698 0SWEI.I. ST BAKER2F I ELD 93306 661 -.63'72 -87'21 HUG 1I. 2U11 9 :.19 HM SY,s'mm STSCLIS REPORT ISO GRv s P }:Cis IJAKIN T 4 :INA. '- 11 I C:H C•RODUi: T HLHRM HUr.; I 1 , 201 1 9: 19 AM 1 N •T: -SPIT: HI.IiRhl - _--.._ T 4: UNI. 2 PROBE OUT HI,IG 1 1. ='u I I 9:19 AM ITV -TAN }t - T I:UNL 1 l t001 PR0DUc:T HL+ +I1 1iAUG1I . 2011 9:21 HI'1 A I N -TANI: - T I :IINL I PROBE OUT AUG II. 2011 9:21 AM IN -TANI{ ALARM - -- -- C HI GFI PFODUCT AUiRll ALA: 1I. 2011 9:.22 HM 0 I N -TANY 14LARM - - - -- T 2:DIESEL PROrtE ouT HUB: 11. 2011 9:23 AM n 2690 O:SWELI_ ST BAI.ERSF I EL.0 9330.6 661- 67 ^_ -87 ^! AUG 1I. 2011 9:,24 AM SYSTEI -i STATLI: REPORT T _ : H k,H PRODUCT HI.AR19 T :PROBE out T 4:1,ROLE OUT' 1 sn S.:RO 'S PRE* Wt+RN IN-TANY ALARM - - - -- T 3:PNL OVERFILL ALARM , AUG I I . 21711 , 9 :25 HM T 3:PNL PROBE OUT ALIC: i I . 201 1 9:;25 AN T : U I E-SEl. INVENTORY INCRENSE 1 NCREHSE START AUG 11. 2011 9:'22 AM VOLUh1E • 69137 HEIGHT 54.c2 1NCHE: WATER. Q .'5 INCHES TEMP '`93.9 DEC F 1 NC.REHSE END AUC 11. _'011 9:25 HMt VOLUME + FI1 sq6 GALS HEIGHT - 8G.d9 INCHES WATER '1.28 INCHES TEMP 3 :6 LiEG F GRii55 I NCREH: 'sE- -1359 TG NET 1 NCREASE- 4294 1N -TANK AU1PM -- - -- f3:PNL I NVAL I G FUEL L.EVEi. ALK; 1 1 , 2011 9:26 Am T I : UPIL I I I'IVENTON-.Y 1 Dll,"REASE AUC: 1]. 2011 9:,22 AM VOLUME - 3160 CHLS HEIC:HT - 29.70 INCHES WATER a 0.0*0 INCHES TEMP - 92.2 DEC F 1 PICREHSE END AUG II. 2011 9:26 Hh1 VOLUME . 76c-, GALS HE IGHT - 156.52 1 W+ HES WA'T'ER • 0.00 INCHES TEMP a 88.1 DEC, F GROSS I NORFASEd 4502 TC NET I N':REA.SE- 4422 IN-THNK ALHF11I - - - -- T 3: PNI. LOW PRODUCT ALARM AUG 11. 2011 9:26 HM SENSOR ALARM - - - -- I..IO:UISP 3 -4IN-Ti4NK Q-mPt-1 FASTPIP 346 T 9'PNL DISPENSER PAK, 2698 Olot.-JELL STSENSOROUTALARMBAKERSFIELD93306DELIVERYNEEDEDAUGII - 2111 1 9:35 AM 1- 872 -8721 * AUC 11. '-:,Oil 9 :,->6 (All E.6 HUG 11. 2011 9:35 AM FASTRIP 346 2698 0SWELL ST BAKERSF I ELI) 93306 661-872-8721 AtiCr 11 - 2011 9:26 HM SYSTEN ST6TUS, PF-*r-(*.,.R,r T 4:PROBE OUT ISO GROSS PRES WARN T 3: PIC I NVENTOPY I WC REASE I NCPEHF;E 2TmRT - ^ AUG I I . 201 1 "a:':'4 AM VOLUME HEIGHT WATER TEMP I NCREk Alic; 11 VOLUME HEIGHT WATER TEMP GROSS TC, IqET 4814 01 1-s 0 INCHES 1 .81 1 NCHES 91 .2 DEG F END 20) 1 9:27 Al -1 11377 GAL" 86.42 INCHES 2.19 1 lqi,HEI.-, 90.8 DEC, F I Nl::PEf4,-3E- 6563 1 N,:RLASE= 6422 L 9:DISP 1-2 D 1.spF1'lSER pAIq SEI,ISOP OUT ALARII AUG 11. 2011 9:35 a-i SENSOR 14LARII ----- LKI:TPANS SUMP NO P I P 11,11.3 2Ul'1p SENSOR OUT ml,mRM Ali(. 11, 20111 9:35 All SENSOR ALARM DISFI 5-E, DISPEN-SER PA14 SENSOR ou'r Ai,ARM ALIC; I I - 2011 '-.1: 35 AM I SENSOP ALmRI•I 1-12:DISP 7 -8 DISPENISER PmN SEN20R OUT ALtAR111 AUi3 11, 2011 9: 35 141 SENSOR iALfARI•l ---- 1.14:TPAN'' SUMP SO PIPING Sulip SENSOR OUT ALARM AUG 11. 2011 9'35 f#1 SENSOR ALARM L I:UIIIL I 8TP S-I*p SUMP 7 ENE'OR OUT RLABII AUG 11 . 2011 9:35 ml,I SYSTEM STATUS REPORT L I :SENSOR OUT ALARM L 9: SENSOR OUT ALAPI-I L 10 : SENw:',OR OUT ALARM LI I :SENSOR OUT HLAFTl L I 2":SENSOR OUT i-%LiARM L13:2ENSOR OUT ALARM L14:SENSOR OUT ALARI"i L 15: SENSOR OUT ALARM ISD {;ROSS PRF-S WARN SENSOR ALARM ----- L15:PNL STP SENSOR OUT ALARM AU(; I I 1 2'011 9:35 AM SEN'SOR ALARM L 2:UNL I ANN ANNULAR SPACE SENSOP OUT ALARM AUG 11 - 2011 9:35 AM FHSTR1P 346 2696 OSUELL ST BHF:ERSF I ELU 93''306 661- 8'72 -8721 HUG 1.1. 2011 9:35 AM SYSTEM STATUS REPORT L 1:_:EN:3ON'. OUT Au+ ;Rri _ - L 2: SENSOR 01 IT A1.ORM L 9:5EhIS,OR OUT (ALARM L10:SENSOR OUT ALARM LII :SENSOR OUT ALARM L12:SENSOR OUT ALARM LI3:SENSOR OUT ALARM L 14 : SENSOk OUT iil.P RM L 15: SEICOR OUT ALARM 15D CROSS PRES WHRN FFISTR I P 341; 2696 Oc:J.,lD.L. ST BAKERSFIELD 93306 661 -872-0721 HUG I I . 2011 9:35 HIM SYSTEN STATUS REPORT M L I:SENSUROUT HLARM L 2: SENSX.)R OUT ALARM L 3:SEN5oR OUT ALHRH L 4 : SENS sR OUT ALARM L 6: SENSOR OUT ALARM L 9 :SEIAS:OR OUT ALARM L 10: SEId.S0P OUT ALARM LII:SENSOR OUT ALARM L12:SENSOR OUT ALARM L 13: SENSOR OUT ALARM L14:SENSOR OUT AL1;RM L15:SENSOR OUT ALHRFI I SD GROFF , PRES WARN I FASrRIP 346 2698 OSWEILL. ST RAKERSFIELD 93306 661 - 872-8721 AUG 1 1 . Nil 9:35 of °1 1': STHTIJS REPORT L J :SEPe30R Olrr ALARM L. :,:sm,1.S!}P ('JI:'r !'i1J1r:1M L 3 : SEIVS0F OUT r;LARM L CSENSJR' OUT ALARI11 L 8: S'EJSOR ,^)UT HLHRM L 7: SENSOR OUT ALARM L d : SENSOR OUT HLARf °1 L 9:SENSOR OUT HLrkP1 L.10:SENSOR OUT HLARM L I :?EPJSiR OUT ALARM L 12 : P21112OR ClUT MLARM T 4:UNL 2 VOLUME = 7927 GA1.8 ULLAGE - 4073 C:ALS 90% ULLAGE 2873 GALS TL' VOLLR-IE - 7612 GALS HEIGHT - 60.24 INCHES WATER VOL - 20 GALS WATER 0.96 INCHES TEMP 80.7 DEG F 4 A x F END n 4 A r R FAsTR I P 346 2698 O13LJEI -L ST BAKERSFIELD 93306 661 - 872 - 8721 AUG 1). 21011 9:50 All SENSOR ALARM - --- L a U :L ANN ANNULAR SPACE FUEL ALtiRhI ySTEM STA'I'D REPORT ALIG 1 1 . 201 1 9: 4 ! All L 2 : FUEL ALARM - - - - L 4: FUEI. ALARM L 8:FUEL ALARM I FSD GROSS PRE$ WARN SENSOR ALARM - -__- 1 NVEN7'OPV REPORT L 6: Pill- ANN ANNULAR SPACEFUELALARM Tl' i : UNL l AUG II. 2011 9:4; tihl VOLUME a 7662 GAL S, ULLAGE 4338 GALS 90% ULLAGE- 3138 C:ALS TC VOLUME - 7547 GALS HEIGHT - 58.53 11-rHES WATER VOL - 0 GxAL.S WATER - 0.00 1lNrHES TEMP = 61.2 DEC F SENSOR ALARM -.. - - - T 2 : 0 l ESEL 1_ ?: UIIL I ANN VOLUME o 304u NrINI.II..;iP SF•ACE ULLAGE 89x0 C:AL9 FUEL ALARM 90% Ul- -il:E= 7760 GALS AUG 11. 2011 9:4'1 TC VOLUME - GALSAM X3004 HEIGHT 28.88 1NCHES WATER VOL - 0 GALS WATER. = 0.00 1 NCHE.S TEMP = 85.6 ClEG F T 3:PNL VOLUME _ :3331 GALS ULLAGE = 8669 GALS SEri,-sop ALARM - - - -- 90% ULLAGE- 7469 GAL L 8 UNt- 2 AlUN TC: VOL 11E - 3269 GAI -S ANNULAR 5F('E HEIGHT =:10.86 1NGHE5 FUEL ALARM WATER VOL - 0 GALS AUG 11. 2011 9:50 PM WATER. = 0.00 INCHES TEMP - 86.1 DEG F T 4:UNL 2 VOLUME = 7927 GA1.8 ULLAGE - 4073 C:ALS 90% ULLAGE 2873 GALS TL' VOLLR-IE - 7612 GALS HEIGHT - 60.24 INCHES WATER VOL - 20 GALS WATER 0.96 INCHES TEMP 80.7 DEG F 4 A x F END n 4 A r R SWRCB, January 2006 Spill Bucket Testing Report Form Thisform is intendedfor use by contractors performing annual testing of UST spill containment structures. The completedform and printoutsfrom tests (ifapplicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: #347 Fastrip 926 1 Date of Testing: 8/11/2011 Facility Address: 2698 Oswell Street, Bakersfield, CA 93306 Facility Contact: Omero Garcia I Phone: 661- 393 -7000 Date Local Agency Was Notified of Testing : 7/13/2011 Name of Local Agency Inspector (rfpresent during testing): Ernie Medina 2. TESTING CONTRACTOR INFORMATION Company Name: Confidence UST Services, Inc. Technician Conducting Test: Bryan A Self Credentials: X CSLB Contractor X ICC Service Tech. X SWRCB Tank Tester Other (Specie) License Number(s): CSLB #804904 ICC #8022804 -UT TT #1 1 -1756 3. SPILL BUCKET TESTING INFORMATION Test Method Used: x Hydrostatic Vacuum Other Test Equipment Used: Lake Test Equipment Resolution: 0.0625" Identify Spill Bucket (By Tank Number, Stored Product, etc. 1 Regular 1 2 Regular 2 3 Super 4 Diesel Bucket Installation Type: Direct Bury x Contained in Sump Direct Bury x Contained in Sump Direct Bury x Contained in Sump Direct Bury x Contained in Sum Bucket Diameter: 12.00" 12.00" 12.00" 12.00" Bucket Depth: 14.00" 13.75" 14.00" 14.00" Wait time between applying vacuum /water and start of test: 5 min. 5 min. 5 min. 5 min. Test Start Time (Tj): 9:00am 9:00am 9:00am 9:00am Initial Reading (Ri): 10.00" 10.75" 10.75" 10.25" Test End Time (TF): 10:00am 10:00am 10:00am 10:00am Final Reading (RF): 10.00" 10.75" 10.75" 10.25" Test Duration (TF — Tj): 1 hour 1 hour 1 hour I hour Change in Reading (RF- Ri): 0.00" 0.00" 0.00" 0.00" Pass /Fail Threshold or Criteria: 0.0625" 0.0625" 0.0625" 0.0625" Test Result: X Pass Fail X Pass Fail X Pass Fail X Pass Fail Comments — (include information on repairs made prior to testing, and recommendedfollow -upforfailed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements. Technician's Signature. Date: 8/11/2011 State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements may be more stringent. Overfill Alarm Sensor Key 1) 208 Senser 2) 420 annular senser 3) ATG Probe 4) FX1 V PLLD 5) FX1 DV PLLD IN Mil 0 0 1 Super 0003 4 1 O 03Diesel2 5 04 3 0 0 2Regular0 1 3 Regular (00)0Slave