BAKERSFIELD FIRE DEPARTMENT
OFFICE OF ENVIRONMENTAL SERVICES
INSPECTOR CRAIG PERKINS
1501 TRUXTUN AVE.
BAKERSFIELD, CA 93301
Test Date: 5/11/2012
Order Number: 3403432
I
Date Printed and Mailed: 5/30/2012
Dear Regulator,
Enclosed are the results of recent testing performed at the following facility:
7- ELEVEN #32376, MKT 2368
9600 BRIMHALL RD.
BAKERSFIELD, CA 93312
Testing performed: .
ATG
IMPACT VALVE
LEAK DETECTOR
SPILL BUCKET TEST
Sincerely,
Dawn Kohlmeyer i
Manager, Field Reporting
i
Appendix VI
Copies of Monitoring System Certification forth and UST Monitoring Plot Plan available at http://www.swrtb. ca. gov.)
MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State of California
Authority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of
Regulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each monitoring
system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner /operator. The
owner /operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date.
A. General Information
Facility Name: 7- ELEVEN #32376, MKT 2368 + Bldg. No.:
Site Address: 9600 BRIMHALL RD. City: BAKERSFIELD Zip: 93312
Facility Contact Person: MANAGER
Make /Model of Monitoring System: Veeder Root TLS 350
B. Inventory of Equipment Tested /Certified
rhn Lr hha anmmn'iafa 1 nvna fn InAirnto cndlfie anidmmnnf ine +nA 1a m,1. A.
Contact Phone No.: 588 -4059
Date of Testing /Servicing: 5/11/2012
Tank ID: T2 RUL - RUL Tank ID:
r In -Tank Gauging Probe. Model: MAG PROBE r In -Tank Gauging Probe. Model:
r' Annular Space or Vault Sensor. Model: VR -420 r Annular Space or Vault Sensor. Model:
r. Piping Sump / Trench Sensor(s), Model: VR -352 r; Piping Sump / Trench Sensor(s). Model:
r' Fill Sump Sensor(s). Model: r Fill Sump Sensor(s). Model:
P Mechanical Line Leak Detector. Model: Vaporless LD -2000 Mechanical Line Leak Detector. Model:
r Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
r Tank Overfill /High Level Sensor. Model: ATG /FLAPPER Tank Overfill / High -Level Sensor. Model:
Other(specify equipment a and model in Section E on Page 2). i Other (specify equipment a and model in Section E on Page 2).
Tank ID: T3 PUL - PUL Tank ID:
r. In -Tank Gauging Probe. Model: MAG PROBE j In -Tank Gauging Probe. Model:
r Annular Space or Vault Sensor. Model: VR -420 r Annular Space or Vault Sensor. Model:
r Piping Sump / Trench Sensor(s). Model: VR -352 r Piping Sump / Trench Sensor(s), Model:
r Fill Sump Sensor(s). Model: rE Fill Sump Sensor(s). Model:
W. Mechanical Line Leak Detector. Model: Vaporless LD -2000 r Mechanical Line Leak Detector. Model: i
r' Electronic Line Leak Detector. Model: r Electronic Line Leak Detector. Model:
J Tank Overfill /High -Level Sensor. Model: ATG /FLAPPER rj Tank Overfill / High -Level Sensor. Model:
Other(specify equipment type and model in Section E on Pa e 2). I Other(specify equipment a and model In Section E on Page 2).
Dispenser 1/2 Dispenser 7/8ID: ID:
r Dispenser Containment Sensor(s). Model: VR -352 r Dispenser Containment Sensor(s). Model: VR -352 i
r Shear Valve(s), r Shear Valve(s). i
r Dispenser Containment Float(s) and Chain(s). r Dispenser Containment Float(s) and Chain(s).
Dispenser 3/4 Dispenser 9/10ID: ID:
r. Dispenser Containment Sensor(s). Model: VR -352 Dispenser Containment Sensor(s). Model: VR 352 ;
r Shear Valve(s). Fi Shear Valve(s).
r: Dispenser Containment Float(s) and Chain(s). r Dispenser Containment Float(s) and Chain(s).
Dispenser 5/6 Dispenser 11/12ID: ID:
r Dispenser Containment Sensor(s). Model: VR -352 jJ, Dispenser Containment Sensor(s). Model: VR -352
r Shear Valve(s), r Shear Valve(s).
r Dispenser Containment Float(s) and Chain(s). r Dispenser Containment Float(s) and Chain(s).
it the racniry contains more tanks or dispensers, copy this Corm. Include information for every tank and dispenser at the facility.
C. Certification - I certify that the equipment identified in this document was inspected /serviced in accordance with the manufacturers' guidelines, Attached to
this Certification is Information (e.g. manufacturers' checklists) necessary to verify that this information is correct and a Plot Plan showing the layout of
monitoring equipment. For any equipment capable of generating such reports, I have also attached a copy of the report; (check all that apply):. Ml System set-
up r Alarm history report
Technician Name (print): Edwin Pineda Signature:
Certification No.: B37453 License. No.: 743160 Class'A' r
Testing Company Name: Tanknology Phone No.: (800) 800 -4633
Testing Company Address: 11000 N. MoPac Expressway Suite 500 Date of Testing /Servicing: 5/11/2012
Monitoring System Certification Paae i of 3 12/07
D. Results of Testing /Servicing
Software Version Installed: 329.02
Complete the following checklist:
C Yes r No* Is the audible alarm operational?
F. Yes M No* Is the visual alarm operational?
C Yes r, No* Were all sensors visually Inspected, functionally tested, and confirmed operational?
is Yes 0 No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not Interfere wit
their proper operation?
C Yes No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) operational?
IT-, N/A
r Yes I^ No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment monitoring
N/A system detects a leak, falls to operate, or is electrically disconnected? If yes: which sensors Initiate positive shut -down? (Check
all that apply) WJppy) Sump/Trench Sensors; PO' Dispenser Containment Sensors.
Did you confirm positive shut -down due to leaks and sensor failure /disconnection? t: Yes; r No
G Yes C No* For tank systems that utilize the monitoring system as the primary tank overfiil warning device (i.e. no mechanical overfill
C prevention valve is installed), is the overfill warning alarm visible and audible at the tank fill point(s) and operating properly? IfN/A so at what percent of tank capacity does the alarm trigger? 90%
I: Yes* r No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the
manufacturer name and model for all replacement parts In Section E below.
r Yes* r? No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply)
rs Product Water. If es describe causes in Section E below.
r Yes No* Was monitoring system set -up reviewed to ensure proper settings? Attach set up reports, if applicable
Yes rQ No* Is all monitoring equipment operational per manufacturer's specifications? •
In section t below, describe now and when these dericiencies were or will be corrected.
Monitoring System Certification Page 2 of 3 I 12/07
F. In -Tank Gauging / SIR Equipment: Fi Check this box if tank gauging is used only for inventory control.
r' Check this box If no tank gauging or SIR equipment Is installed.
This section must be completed If In -tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
f: Yes r No* Has all Input wiring been Inspected for proper entry and termination, including testing for ground faults?
is Yes No* Were all tank gauging probes visually Inspected for damage and residue buildup?
f? Yes No* Was accuracy of system product level readings tested?
M Yes No* Was accuracy of system water level readings tested?
Yes ir No* lWere all probes reinstalled properly?
Yes r No* Were all Items on the equipment manufacturer ?s maintenance checklist completed?
In the Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD): r Check this box if LLDs are not installed.
Complete the following checklist:
M Yes r No* For equipment start-up or annual equipment certification was a leak simulated to verify LLD performance? (Check all that
r N/A apply) Simulated leak rate: W, 3 g.p.h.; r 0.1 g.p.h; L_.; 0.2 g.p.h. j
r Yes r No* Were all LLDs confirmed operational and accurate within regulatory requirements? I
f: Yes r No* Was the testing apparatus properly calibrated?
C: Yes r No* For mechanical LLDs, does the LLD restrict product Flow if it detects a leak?
r` N/A
r Yes r No* For electronic LLDs, does the turbine automatically shut off If the LLD detects a leak?
N/A
f" Yes` No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected?
M N/A
r Yes r No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a test?
P, N/A
t^ Yes r No* For electronic LLDs, have all accessible wiring connections been visually inspected?
r N/A
C Yes No* Were all Items on the equipment manufacturer's maintenance checklist completed? !
In the sectlon M, below, describe how and when these deficiencies were or will be corrected.
rayc J V J iL/ V
f
SWRCB, January 2002 Page 1 of 1
Secondary Containment Testing Report Form
Thisform is intended for use by contractors performing periodic testing of UST secondary containment systems Use the appropriate
pages of this form to report results for all components tested. The completedform, written test procedures, and printoutsfrom tests
if applicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: 7- ELEVEN #32376, MKT 2368 jDate of Testing: 5/11/2012
Facility Address: 9600 BRIMHALL RD. , BAKERSFIELD, CA 93312
Facility Contact: MANAGER Phone: 5884059
Date Local Agency Was Notified of Testing: 4/20/2012
Name of Local Agency Inspector (if present during testing): None Present
2. TESTING CONTRACTOR INFORMATION
Company Name: TANKNOLOGY INC.
Pass
Technician Conducting Test: Edwin Pineda
Not
Tested
Credentials: r CSLB Licensed Contractor r SWRCB Licensed Tank Tester
License Type: A License Number: 743160
Manufacturer
Manufacturer Training
Component(s) Date Training Expires
OPW Phase 1 EVR 8/2/2012
3. SUMMARY OF TEST RESULTS
Component Pass Fail Not
Tested
Repair
Made
Component Pass Fail -, i Not
Tested
Repairs
Made
Spill Box T2 RUL rul fill X
Spill Box T3 PUL put fill X
I
I ,
If hydrostatic testing was performed, describe what was done with the water after completion of tests:
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I. .
To the best ofmy knowledge, thefa lctsstatedinthisdocumentareaccurateandinfullcompliancewithlega requirements
Technician's Signature: Qj I) A 1.. . Date: 5/11/20121
WO: 3403432
i
i
Page 1 of 1
SPILL /OVERFILL CONTAINMENT BOXES
Facility is Not Equipped With Fill Riser Containment Sumps r_?
Fill Riser Containment Sumps are Present, but were Not Tested r
Test Method Developed By: r Spill Bucket Manufacturer!: Industry Standard r Professional .Engineer
r Other (Specify):
Test Method Used By: Pressure r Vacuum rr Hydrostatic
r Other (Specify):
Test Equipment Used: LAKE TEST Equipment Resolution: 0.062 in.
cam-; ,k e4" >T •i 4,. Z ,4.t;. a
rTank T2FRUL RULE': 3Tank T3 -'PUL PUL' t` rl xrSIII Box # 'SP
r S III f3oz #
A r'Flll Direct sr s
Bucket Diameter: 12.00 12.00
Bucket Depth: 12.00 14.00
Wait time between applying
pressure /vacuum /water and 0 min 0 min min min
starting test
Test Start Time: 09:00:00 09:00:00
Initial Reading p,l: 11.50 13.00
Test End Time: 10:00:00 10:00:00
Final Reading oar. 11.50 13.00
Test Duration: 1 hr 1 hr
Change in Reading y : 0.00 0.00
Pass /Fall Threshold or Criteria: 0.00 0.00
Test Result4# Passe Afil#- }YPass , r
y} 3
dA
l R JJhh 4.
I"
Comments ? (include information on repairs made prior to testing, and recommended follow -up for failed tests)
W0: 3403432
i
i 'i
Tanknolo Site DiagramgY(This site diagram is for reference only and is not drawn to scale)
Work Order: 3403432 Date: 5/11/2012
Site ID / Name: 3237617- ELEVEN #32376, MKT 2368
Address: 9600 BRIMHALL RD,
City: BAKERSFIELD State: CA Zip: 93312
VENTS OO
CAS ;
H2O
12 410
EA
m
ICE ,.
5 REG PREM
10K 10K
v
r
00 -
7 #5 N.
Z4STPSTP
A 11 l3
l#4 #2 `
S
31
W.O.# SC1- 3403432
I10100
MAY 11, 2012 12:55 PM
235431 7 -11 32376
9600 BRIMHALL
BAKERSFIELD,CA 93312
B0687875505001
SYSTEM STATUS REPORT
T 3:DELIVERY NEEDED
150301
MAY 11, 2012 12:55 PM
1:235431 7 -11 32376
I50302
MAY 11, 2012 12:55 PM
2:9600 BRIMHALL
I50303
MAY 11, 2012 12:55 PM
3:BAKERSFIELD,CA 93312
I50304
MAY 11, 2012 12:55 PM
4:B0687875505001
I51700
MAY 11, 2012 12:55 PM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE /TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50F00
MAY 11, 2012 12:56 PM
MON DD YYYY HH:MM:SS xM
I60100
MAY 11, 2012 12:56 PM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 OFF
2 RUL ON
3 PUL ON
4 OFF
f
i
i
160200
MAY 11, 2012 12:56 PM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1
2 RUL
3 PUL
4
I60300
MAY 11, 2012 12:56 PM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1
2 RUL
3 PUL
4
160400
MAY 11, 2012 12:56 PM
TANK FULL VOLUME
TANK PRODUCT LABEL
1
2 RUL
3 PUL
4
I60700
MAY 11, 2012 12:56 PM
TANK DIAMETER .
TANK PRODUCT LABEL
1
2 RUL
3 PUL
4
160900
MAY 11, 2012 12:56 PM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1
2 RUL
3 PUL
4
I61200
MAY 11, 2012 12:56 PM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL
1
2 RUL
3 PUL
4
I62100
1
2
3
4
GALLONS i
0 j
10028
10028
0
i
INCHES
0.00
96.00
96.00
0.00
i
i
0.000000
0.000700
0.000700
0.000000
SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
NONE NONE
NONE NONE
NONE NONE
NONE NONE
MAY 11, 2012 12:56 PM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 0
2 RUL 900
3 PUL 769
4 0
162200
MAY 11, 2012 12:56 PM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 0
2 RUL 9526
3 PUL 9526
4 0
162300
MAY 11, 2012 12:56 PM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 0
2 RUL 9025
3 PUL 9025
4 0
162400
MAY 11, 2012 12:56 PM
2 RUL 1.5
3 PUL 1.5
I62800
MAY 11, 2012 12:56 PM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 0
2 RUL 10028
3 PUL 10028
4 0
162900
MAY 11, 2012 12:56 PM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 0
2 RUL 1504
3 PUL 1504
4 0
170300
MAY 11, 2012 12:56 PM
LIQUID TYPE
SENSOR LOCATION TYPE
1 RUL STP SUMP DUAL FLT. HIGH VAPOR
2 RUL ANNULAR TRI -STATE (SINGLE FLOAT)
3 PUL STP SUMP DUAL FLT. HIGH VAPOR
4 PUL ANNULAR TRI -STATE SINGLE FLOAT)
5
235431 7 -11 32376
TRI -STATE SINGLE FLOAT)
6 TRI -STATE SINGLE FLOAT)
7 DISP 1 -2 DUAL FLT. HIGH VAPOR
8 DISP 3 -4 DUAL FLT. DISCRIMINATING
9 DISP 5 -6 DUAL FLT. DISCRIMINATING
10 DISP 7 -8 DUAL FLT. DISCRIMINATING
11 DISP 9 -10 DUAL FLT. DISCRIMINATING
12 DISP 11 -12 DUAL FLT. DISCRIMINATING
13
2012 10:41
TRI -STATE SINGLE FLOAT)
14
11, 2012
TRI -STATE SINGLE FLOAT)
15
APR 17,
TRI -STATE SINGLE FLOAT)
16
APR
TRI -STATE SINGLE FLOAT)
I90200
MAY 11, 2012 12:56 PM
SOFTWARE REVISION LEVEL
VERSION 329.02
SOFTWARE# 346329 -100 -C
CREATED - 09.07.01.16.29
S- MODULE# 330160 -106 -a
SYSTEM FEATURES:
PERIODIC IN -TANK TESTS
ANNUAL IN -TANK TESTS
CSLD
BIR
ISD
120600
MAY 11, 2012 12:56 PM
235431 7 -11 32376
9600 BRIMHALL
BAKERSFIELD,CA 93312
B0687875505001
TANK ALARM HISTORY
TANK 2 RUL
HIGH WATER ALARM MAY 11, 2012 10:41 AM
OVERFILL ALARM MAY 11, 2012 10:32 AM
APR 17, 2012 12:42 AM
APR 10, 2012 5:29 AM
LOW PRODUCT ALARM MAY 11, 2012 10:31 AM
APR 25, 2012 8:22 PM
MAR 29, 2012 9:14 PM
HIGH PRODUCT ALARM MAY 11, 2012 10:34 AM
MAY 11, 2012 10:32 AM
APR 17, 2012 12:44 AM
INVALID FUEL LEVEL MAY 11, 2012 10:49 AM
MAY 11, 2012 10:31 AM
PROBE OUT MAY 11, 2012 11:20 AM
MAY 11, 2012 10:48 AM
MAY 11, 2012 10:30 AM
HIGH WATER WARNING MAY 11, 2012 10:41 AM
DELIVERY NEEDED MAY 11, 2012 10:31 AM
APR 28, 2012 4:40 PM
APR 25, 2012 5:23 PM
MAX PRODUCT ALARM MAY 11, 2012 10:35 AM
TANK 3 PUL
HIGH WATER ALARM MAY 11, 2012 11:27 AM
OVERFILL ALARM MAY 11, 2012 10:32 AM
LOW PRODUCT ALARM MAY 11, 2012 10:29 AM
i
r
i -
i
HIGH PRODUCT ALARM MAY 11, 2012 10:34 AM
MAY 11, 2012 10:31 AM
INVALID FUEL LEVEL MAY 11, 2012 11:32 AM
AM
MAY 11, 2012 10:30 AM
PROBE OUT MAY 11, 2012 11:31 AM
MAY 11, 2012 11:21 AM
9:21
MAY 11, 2012 11:00 AM
HIGH WATER WARNING MAY 11, 2012 11:27 AM
DELIVERY NEEDED MAY 11, 2012 11:32 AM
PUL
MAY 10, 2012 5:22 PM
APR 20, 2012 7 :19 PM
MAX PRODUCT ALARM MAY 11, 2012 10:35 AM
130200
MAY 11, 2012 12:57 PM
235431 7 -11 32376
9600 BRIMHALL
BAKERSFIELD,CA 93312
B0687875505001
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 RUL STP SUMP
MAY 11, 2012 9:21 AM SENSOR OUT ALARM
MAY 11, 2012 9:07 AM FUEL ALARM
MAY 11, 2012 9:07 AM FUEL ALARM
2 RUL ANNULAR
MAY 11, 2012 9:21 AM SENSOR OUT ALARM
MAY 11, 2012 9:09 AM FUEL ALARM
JUL 1, 2009 8:02 AM SETUP DATA WARNING
3 PUL STP SUMP
MAY 11, 2012 9:21 AM SENSOR OUT ALARM
MAY 11, 2012 9:11 AM LIQUID WARNING
MAY 11, 2012 9:11 AM LIQUID WARNING
4 PUL ANNULAR
MAY 11, 2012 9:21 AM SENSOR OUT ALARM
MAY 11, 2012 9:12 AM FUEL ALARM
JUL 1, 2009 8:02 AM SETUP DATA WARNING
7 DISP 1 -2
MAY 11, 2012 9:21 AM SENSOR OUT ALARM
MAY 11, 2012 9:16 AM LIQUID WARNING
MAY 11, 2012 9:16 AM LIQUID WARNING
8 DISP 3 -4
4'
MAY 11, 2012 9:21 AM SENSOR OUT ALARM
MAY 11, 2012 9:17 AM LIQUID WARNING
MAY 11, 2012 9:17 AM LIQUID WARNING
9 DISP 5 -6
MAY 11, 2012 9:21 AM SENSOR OUT ALARM
MAY 11, 2012 9:15 AM LIQUID WARNING
MAY 11, 2012 9:15 AM LIQUID WARNING ;.
10 DISP 7 -8
MAY 11, 2012 9 :21 AM SENSOR OUT ALARM
MAY 11, 2012 9:15 AM LIQUID WARNING
MAY 11, 2012 9:14 AM LIQUID WARNING
11 DISP 9 -10
MAY 11, 2012 9:21 AM SENSOR
i
OUT ALARM
MAY 11, 2012 9:13 AM LIQUID WARNING
MAY 11, 2012 9:13 AM LIQUID WARNING
12 DISP 11 -12
MAY 11, 2012 9:21 AM SENSOR OUT ALARM
i
I
MAY 11, 2012 9:14 AM LIQUID WARNING
MAY 11, 2012 9:14 AM LIQUID WARNING
110100
MAY 11, 2012 12:57 PM
235431 7 -11 32376
9600 BRIMHALL
EAKERSFIELD,CA 93312
80687875505001
SYSTEM STATUS REPORT
T 3:DELIVERY NEEDED