HomeMy WebLinkAboutSB989 2011SWRCB, January 2002 Page 1 of 8 Secondary Containment 'Testing Report Form Thisform is intendedfor use by contractorsperforming periodic testing of USTsecondary containment systems. Use the appropriate pages ofthis form to report resultsfor all components tested. The completedform, written testprocedures, and printouts from tests (ifapplicable), should beprovided to thefacility owner /operatorfor submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: Metro Station I Date of Testing: 5/13/2011 Facility Address: 4600 Stine Road, Bakersfield CA 93309 Facility Contact: Baseem "Sam" Abed Phone: (661) 496 -0838 Date Local Agency Was Notified of Testing: 5/11/2011 Name of Local Agency Inspector (rfpresent during testing): Ernie 2. TESTING CONTRACTOR INFORMATION Company Name: Confidence UST Services Pass Technician Conducting Test: Wayne T. Girard ICC# 8092943 STS/Franklin Fueling #3877033703 Credentials: x CSLB Licensed Contractor SWRCB Licensed Tank Tester License Type: C -61 / D40 Pass License Number:804904 Manufacturer Manufacturer Training Component(s) Franklin Fueling TS -STS 1/22/2013 X 3. SUMMARY OF TEST RESULTS Component Pass Fail Not Tested Repairs Made Component Pass Fail Not Tested Repairs Made 91 SB Fill X UDC #2 X 91 SB Vapor X UDC #3 X 87 #1 SB Fill X I UDC #4 X 1 87 #1 SB Vapor X UDC #5 X 87 #2 SB Fill X 91 Annular X 87 #2 SB Vapor X 87 #1 Annular X DSL SB Fill X 87 #2 Annular X 91 STP X DSL Annular X 87 #1 STP X 91 Secondary X 87 #2 STP X 87 #1 Secondary X DSL STP X 87 #2 Secondary X UDC #1 X I I DSL Secondary X I Ifhydrostatic testing was performed, describe what was done with the water after completion oftests: Water was put back into test trailer and waste drum. CERTIFICATION OF ECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING To the best ofmy knowledge, thefa stated In thls do ment accurate and infull compliance with legal requirements Technician's Signature: %/`— DAW 5/13/2011 SWRCB, January 2002 4. TANK ANNULAR TESTING Page 2 of 8 Test Method Developed By: Tank Manufacturer x Industry Standard Professional Engineer Other (Spec) Test Method Used: Pressure x Vacuum Hydrostatic Other (Spec) Test Equipment Used: Calibrated Gauges Equipment Resolution:0.1" Hg Tank # 1 / 91 Tank # 2 / 87 #1 Tank # 3 / 87 #2 Tank # 4 / DSL Is Tank Exempt From Testing?' Yes x No Yes x No Yes x No Yes x No Tank Capacity: 12k 12k 12k 12k Tank Material: Fiberglass Fiberglass Fiberglass Fiberglass Tank Manufacturer: unknown unknown unknown unknown Product Stored: 91 gasoline 87 gasoline 87 gasoline Diesel Wait time between applying pressure /vacuum/water and starting test: 5 min. 5 min. 5 min. 5 min. Test Start Time: 11:15am 11:15am 9:50am 10:10am Initial Reading (Rj): 5.0" Hg 5.0" Hg 5.0" Hg 5.0" Hg Test End Time: 12:15pm 12:15pm 10:50am 11: 1Oarn Final Reading (RF): 5.0" Hg 5.0" Hg 5.0" Hg 5.0" Hg Test Duration: I hour 1 hour 1 hour 1 hour Change in Reading (RF -Rj): 0.0" Hg 0.0" Hg 0.0" Hg 0.0" Hg Pass/Fail Threshold or Criteria: No change No change No change No change Test Result: X Pass Fail X Pass Fail X Pass Fail X Pass Fail Was sensor removed for testing? X Yes No NA X Yes No NA X Yes No NA X Yes No NA Was sensor properly replaced and verified functional after testing? X Yes No NA X Yes No NA X Yes No NA X Yes No NA Comments — (include information on repairs made prior to testing, and recommendedfollow -upforfailed tests) Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary containment, such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment testing. {California Code ofRegulations. Title 23, Section 2637(a)(6)1 SWRCB, January 2002 5. SECONDARY PIPE TESTING Page 3 of 8 Test Method Developed By: Piping Manufacturer x Industry Standard Professional Engineer Other (Spec) Test Method Used: x Pressure Vacuum Hydrostatic Other (Specify) Test Equipment Used: Calibrated Gauges Equipment Resolution:0.Ipsi Piping Run # 1 / 91 Piping Run # 2 / 87 #1 Piping Run # 3 / 87# 21 Piping Run # 4 / DSL Piping Material: Fiberglass Fiberglass Fiberglass Fiberglass Piping Manufacturer: unknown unknown unknown unknown Piping Diameter: 4" 4" 4" 4" Length of Piping Run: 90' 80' 70' 60' Product Stored: 91 gasoline 87 gasoline 87 gasoline Diesel Method and location of piping-run isolation: Test boot Test boot Test boot Test boot Wait time between applying pressure /vacuum/water and starting test: 5 min. 5 min. 5 min. 5 min. Test Start Time: 11:05am 11:05am 9:50am 10:10am Initial Reading (Rj): 5.0 psi 5.0 psi 5.0 psi 5.0 psi Test End Time: 12:05pm 12:05pm 10:50am 11:10am Final Reading (RF): 5.0 psi 5.0 psi 5.0 psi 5.0 psi Test Duration: I hour 1 hour 1 hour 1 hour Change in Reading (RF -Rj): 0.0 psi 0.0 psi 0.0 psi 0.0 psi Pass/Fail Threshold or Criteria: No change No change No change No change Test Result: X Pass Fail X Pass Fail X Pass Fail X Pass Fail CoMua IMtS — (include information on repairs made prior to testing, and recommendedfollow -upforfailed tests) SWRCB, January 2002 6. PIPING SUMP TESTING Page 4 of 8 Test Method Developed By: Sump Manufacturer x Industry Standard Professional Engineer Other (Spec) Test Method Used: Pressure Vacuum x Hydrostatic Other (Spec) Test Equipment Used: TS -STS Equipment Resolution: .000 1" Sump # 1 / 91 Sump # 2 / 87 #1 Sump # 3 / 87 #2 Sump # 4 / DSL Sump Diameter: 34" 34" 34" 40" Sump Depth: 60" 60" 60" 60" Sump Material: Fiberglass Fiberglass Fiberglass Fiberglass Height from Tank Top to Top of Highest Piping Penetration: 16" 16" 16" 18" Height from Tank Top to Lowest Electrical Penetration: 20" 20" 20" 24" Condition ofsump prior to testing: Clean Clean Clean Clean Portion of Sump Tested' Penetrations Penetrations Penetrations Penetrations Does turbine shut down when sump sensor detects liquid (both product and water)?* Yes No X NA Yes No X NA Yes No X NA Yes No X NA Turbine shutdown response time Is system programmed for fail -safe shutdown?* Yes No X NA Yes No X NA Yes No XNA Yes No X NA Was fail -safe verified to be operational?* Yes No X NA Yes No XNA Yes No XNA Yes No X NA Wait time between applying pressure /vacuum/water and starting test: 15 min. 15 min. 15 min. 15 min. Test Start Time: Initial Reading (RI): Test End Time: Final Reading (RF): See INOON Test Duration: Change in Reading (RF -RI): Pass/Fail Threshold or Criteria: Test Result: X Pass Fail Pass X Fail Pass X Fail Pass X Fail Was sensor removed for testing? X Yes No NA X Yes No NA X Yes No NA X Yes No NA Was sensor properly replaced and verified functional after testing? X Yes No NA X Yes No NA X Yes No NA X Yes No NA Gommenb — (include information on repairs made prior to testing, and recommendedfollow -upforfailed tests) Ifthe entire depth of the sump is not tested, specify how much was tested. Ifthe answer to pay ofthe questions indicated with an asterisk (') is "NO" or "NA ", the entire sump must be tested. (See SWRCB LG -160) j' . 3:: Tt4tR 9^ ITOSLl51N /M1d/Y44 1tas?dh V,'M1MWFwaIXrG'!MA. SWRCB, January 2002 7. UNDER- DISPENSER CONTAINMENT (UDC) TESTING Page 5 of 8 Test Method Developed By: UDC Manufacturer x Industry Standard Other (Spec) Professional Engineer Test Method Used: Pressure Other (Spec) Vacuum x Hydrostatic Test Equipment Used: IN -CON STS Equipment Resolution: 0001 UDC # 1 UDC # 2 UDC # 3 UDC # 4 UDC Manufacturer: Bravo Bravo Bravo Bravo UDC Material: FRP FRP FRP FRP UDC Depth: 36" 36" 36" 36" Height from UDC Bottom to Top of Highest Piping Penetration: 20" 20" 20" 20" Height from UDC Bottom to Lowest Electrical Penetration: N/A N/A N/A N/A Condition of UDC prior to testing: Clean Clean Clean Clean Portion of UDC Tested Pipe Penetrations Pipe Penetrations Pipe Penetrations Pipe Penetrations Does turbine shut down when UDC sensor detects liquid (both product and water)?* Yes No X NA Yes No X NA Yes No X NA Yes No XNA Turbine shutdown response time Is system programmed for fail- safe shutdown ?* Yes No X NA Yes No X NA Yes No X NA Yes No X NA Was fail -safe verified to be operational ?* Yes No X NA Yes No X NA Yes No X NA Yes No X NA Wait time between applying pressure /vacuum/water and starting test 5 min. 5 min. 5 min. 5 min. Test Start Tune: Initial Reading Ri): Test End Time: Final Reading (RF): Sim Mr-CIN Test Duration: I jChangeinReading (RF -Ri): Pass/Fail Threshold or Criteria: Test Result: X Pass Fail X Pass Fail X Pass Fail X Pass Fail Was sensor removed for testing? X Yes No NA X Yes No NA X Yes No NA X Yes No NA Was sensor properly replaced and verified functional after testing? X Yes No NA X Yes No NA X Yes No NA X Yes No NA Comments — (include information on repairs made prior to testing, and recommendedfollow -up forfailed tests) Ifthe entire depth ofthe UDC is not tested, specify how much was tested. If the answer to any of the questions indicated with an asterisk ( *) is "NO" or "NA ", the entire UDC must be tested. (See SWRCB LG -160) I71WOOMI egg Wmzwq, nv-mr, evma IY4Z SWRCB, January 2002 7. UNDER- DISPENSER CONTAINMENT (UDC) Test Method Developed By: 0 UDC Manufacturer x Industry Standard 0 Professional Engineer Other (Specify) Test Method Used: 0 Pressure 0 Vacuum x Hydrostatic 0 Other (Spec) Test Equipment Used: IN -CON STS Equipment Resolution: .0001 UDC # 5 UDC # UDC # UDC # UDC Manufacturer: Bravo UDC Material: FRP UDC Depth: 36" Height from UDC Bottom to Top of Highest Pi2ing Penetration: 2011 Height from UDC Bottom to Lowest Electrical Penetration: N/A Condition of UDC prior to testing: Clean Portion of UDC Tested Pipe Penetrations Does turbine shut down when UDC sensor detects liquid (both product and water)?* 0 Yes No X NA Yes No 0 NA 0 Yes No 0 NA 0 Yes No NA Turbine shutdown response time Is system programmed for fail- safe shutdown ?* 0 Yes No X NA Yes No NA Yes No NA Yes No NA Was fail -safe verified to be operational ?* Yes No X NA Yes No NA 0 Yes No NA Yes 0 No NA Wait time between applying pressure /vacuum/water and starting test 5 min. Test Start Time: Initial Reading (R,): Test End Time: See INIC01 Final Reading (RF): Test Duration: Change in Reading (RF -Ri): Pass/Fail Threshold or Criteria: Test Result: X Pass Fail Pass Fail Pass Fail Pass Fail Was sensor removed for testing? X Yes No 0 NA 0 Yes 0 No NA 0 Yes 0 No NA 0 Yes 0 No NA Was sensor properly replaced and verified functional after testin ? X Yes No 0 NA 0 Yes 0 No NA 0 Yes No NA Yes 0 No 0 NA COII9MIAS — (include information on repairs made prior to testing, and recommendedfollow -upforfailed tests) 1 If the entire depth ofthe UDC is not tested, specify how much was tested. If the answer to My ofthe questions indicated with an asterisk ( °) is "NO" or "NA ", the entire UDC must be tested. (See SWRCB LG -160) y itY +i'!K ik81nN04flt 1 CiL:7i81:d'Q'7 1437AC44R75F. N nacssrr.nn:rncvrarrnr;A :•o- ma:a c^lnx nwsc, :a? SWRCB, January 2002 9. SPILL/OVERFILL CONTAINMENT BOXES Page 7 of 8 Facility is Not Equipped With Spill/Overfill Containment Boxes Spill/Overfill Containment Boxes are Present, but were Not Tested Test Method Developed By: Spill Bucket Manufacturer x Industry Standard Professional Engineer Other (Spec) Test Method Used: Pressure Vacuum x Hydrostatic Other (Spec) Test Equipment Used: TS -STS Equipment Resolution: .0001" Spill Box # 1 / 91F Spill Boa # 2 / 91V Spill Box # 3 / 871F Spill Box # 4 / 871V Bucket Diameter: 12" 12" 12" 12" Bucket Depth: 15" 15" 15" 1Y, Wait time between applying pressure /vacuum/water and starting test: 5 min. 5 min. 5 min. 5 min. Test Start Time: Initial Reading (Rj: Test End Time: Final Reading (RF): Test Duration: Change in Reading (RF -Rj): Pass/Fail Threshold or Criteria: 002" 002" 002" 002" Test Result: Pass X Fail X Pass Fail Pass X Fail X Pass Fail COMMIMts — (include information on repairs madeprior to testing, and recommendedfollow -upforfailed tests) alt SWRCB, January 2002 9. SPILL/OVERFILL CONTAINMENT BOXES Page 8 of8 Facility is Not Equipped With Spill/Overfill Containment Boxes Spill/Overfill Containment Boxes are Present, but were Not Tested Test Method Developed By: Spill Bucket Manufacturer x Industry Standard Professional Engineer Other (Spec) Test Method Used: Pressure Vacuum x Hydrostatic Other (Spec) Test Equipment Used: TS -STS Equipment Resolution: .0001" Spill Box # 5 / 872F Spill Boa # 6 / 872V Spill Box # 7 / DSL F Spill Box # Bucket Diameter: 12" 12" 12" Bucket Depth: 15" 15" 15" Wait time between applying pressure /vacuum/water and starting test: 5 min. 5 min. 5 min. Test Start Time: Initial Reading (R,): Test End Time: Final Reading (RF): Test Duration: Change in Reading (RF -R,): Pass/Fail Threshold or Criteria: 002" 002" 002" Test Result: Pass X Fail X Pass Fail Pass X Fail Pass Fail Comments — (include information on repairs made prior to testing, andrecommendedfollow -upforfailed tests) KzftVj&-n:ftr . M e " Lj MEIE.0 SIA11UI1 MEIFD; ATIOII MEok(1 SIA1110i at$ alINE POAU 4600 STiNr ROAT) 4600 STINE ROAD 5AXERtgiEt5 CA A3'.0c.! BAKERSFIELD CA A330,i F,O,:R I;i.J! CA "'13U:1 GBi WK 661- Q96 -Or3v 061 - 496 -0av JUVOICE 26341 IINDICE 2V4 i 111VOICk 26341 45/13/2011 1t1:5G AM 45;'13 /1011 11:36 n+° Uj /'1 ;, /2611 i2:lij i'H Wrr, 9i 5i1F' 3'2 *W S 3 ` USL SIP ILY as eiiE :I ;1' , /+11 l:rr' .L' 11:c J A" TF. 1ATc1E J T':» A" TES", SWG 01131all t o; STARTE& 0511312JII CS7 STARIEG 05(73/2011 b£1:1k LEVEL -.6530 11: BEUIN LEVEL 6.76f:2 III 6U.IN IEVEL 1.?Nl :it E16 l I IIf 10:54 AM E10 i IMF 11:36 AM Off) TIRE 12:10 PII EI1U [LATE 05/13/2011 EIID DA1t 05/13/20H EI:D WE 05/117/2011 NO LEti, 3.5103 R! I EvEL 4.7673 1N fj LEVEL 1.6744 111 1,EP4 TR'1FSKLu 4, iu?2 111 EAY THRESHOLD 0.002 111 LZAY THRESHOLD 0.0412 IN IN REST : FAILED IEST kcISLILi PASSED TEST RESik I FAILED 11 SBV 372 5 bG 12 SIP IM. S11AR10 10:30 AIT IN biARIED I1:e'J AM IFSI iAk1tD 1`:5j AM iE5T STWED 051 15/20 1 1 FES1 STARTED L15; 13/2011 TEST STARTED 35/I3/2011 aE, IN LEVEL 5. i4jf III EGPN LFVEI. 2. 2301 ;N 60;IN LEVEL 1.65517 111 TJV TIME 101:54 AM Elio TIME 11:36 AM ENUITIME 12:10 PM 111) DATE 05/1312011 ErtD DATE 05113 /2011 Eix1 DATE 05113/•1011 Eli LEVft 5.7441 111 110 LEVEL 2.1925 In END LEVEL 1.4931 N1 LEA,. 14RESkCi_D ti'. 0G2 Its CAD 11,110;; ::I LEAK "MRE5HOLL 0.002 Ut 1EaT RESULT PASSED IFST RESL T FAILED TES? RESULT FAILED 871 SY USE. SNF 51 S +++ii'cIi lU: zi: AM b( 5i „EiEU 1 is j t;tM1 TFzJ S7ARiET. 0j/ 1312011 I /;11' LEVE. 3.9419 Ic: Efi ir. L VEI ?. V028 Ito E1lG T I IF 10:54 AM LIID TIME 11:36 AM EQ (WE 05/ 1'/2'.111 E16 Wt U5/ 131N I I Elio LEilf1 ?.:a.' t III E1IU LEVE' G. X844 IN LEAY 11'1 MOLD 0.002 I1; LEAP T1f'ESkTU ). 742 IN IFST RESULT FAILED ES1 RESULT FAILED 871 SBV TEy: SIAk;EU 10:0 e. TtS1 SihRTED 05/13/2011 ELGIN LEVEL 5. 2026 IN' EIIU i IME 10:54 AM END HATE 05/13/2011 EIID LEVEL 5.2013 !N LEAK THRESH10 0.402 Ila IEST RESULT PASSEU MEip.6 SiAi toll 460U SANE ROAD 811*P riEt:, CA 5,1303 l't61- {198 -OP3v A IWOICF 26341 15/13/2,011 1:10 Ptl 510r LEAN. TEST R'LPUlT 91 SIP Ea STARItu 12:55 PM T T STAitfEU 05/13/2011 rETillt LEVEi 3.2752 IN ENO TIME 1:1L1 PM EtiD UAIE 05/13/2011 1110 LEVEL 3.274,1 IN Ek THRESH80 0.002 IN TEST RESULT PASSED I71 STP iLST Sf6klEb ;2:55 F11 TEST STARTED 05/13/2011 t1E;3fII LE +Et. 2.fr: ilI END TIME 1:10 Ph END DATE 05/13/2011 FND LEVEL 2.63'28 IN EA:: KEvl1T.;_G 0.002 IN TESL RESULT FAILED L l ;ANIF1: 12:55 PM TEST STARTED 05/1.312011 OEGIII LEVEL 3. do"m IN EEIIG TIME 1:10 PM END DATE 05/1300 11 END LEVEL 3,2110 IN Uk 1HRESHOLD 0.002 111 rEsi RESULT PASSED METRO SIATIDI tk.IRO SIAl iGN 4600 STINE ROAD 450G Slat ROAD bA+tEFS; iEi.(1 54x0, FIELD i-A 2330 "1 661 - 496 -OE3E 651- U 6 -4 3z IWICE 26841 INVDICE 2fir4T 5113 /'1011 1: 52 fl9 051 131 PO) 1 2:43, M fi ;iMF Lt.Ak TLST nff't1n1 x'1Mt' ; i=A.Y. lESi u''uY! UDC 2 UDC 4 iE51 SIPRirli 1:06 PI1 r S,Hj !iii 7 ti; TEST STARIEU 05/13/2011 LI; ;;Hf :i!U a:lojnill 2FGfII LEVEL 3.2255 IN rGill LEVEL 5.2449 III END 11ME 1:51 PM rND 1111E 2:43 PM RU DATE 05/13/2011 ENU DATE 05/13/201; Tun LEVEL 3. 2246 IN i t ;.. ' t !i L 5.2051 a: LEAI'. THRESHOLD 0.002 It: C s. c +ArtiH LtJ 0. Ci02 1N TESI RESOLI' PASSED i_; RE1;1u f PASSED UDC 3 UDC 5 iLS. S1APibb 1:36 pm TB: `;!MrFri 2'Jt fM TESL STARTED 05/13/2011 TEST E.!*IEG 05/13/201' 5GIN LEVEL 1.2369 IN gF;;iN LEVEL 2.+522 lH END TIME 1:51 PM Etf) TIME 2:43 PM ENO WE 05/13/2011 ErtG DATE 05/13/2'J11 END LEVEL 1.2361 It: END I.t.UFT 2,1150= IN I.Ex. THRESHOLD G.002 IN LEW WE:.-iC: 0.05 it' TEST RESOLi PASSED TEST REST;;_,, PASSED