HomeMy WebLinkAboutFMC 2012MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State ofCalifornia
Authority Cited: Chapter 6 7, Health and Safety Code; Chapter 16, Dtvision 3, Title 23, California Code ofRegulations
This form must be used to document testing and servicing of monitoring equipment. A separate "certification or report must be prepared for each
monitoring system control panel by the technician who performs the work. A copy ofthis form must be provided to the tank system owner /operator.
The owner /operator must submit a copy ofthis form to the local agency regulating UST systems within 30 days of test date.
A. General Information
Facility Name: JOHNNYS ARCO Bldg. No.:
Site Address: 3333 UNION AVE. City: BAKERSFIELD Zip: 93308
Facility Contact Person: JOHNNY
Make/Model of Monitoring System: TLS -350 ERNIE MADINA
B. Inventory of Equipment 'Tested /Certified
Check the annronrinte boxes to indicate snecific equioment insneeted/serviced:
Contact Phone No.: (661) 703 -8083
Date of Testing/Servicing: 1/9/2012
Tank ID: UNL87 Tank ID: UNL87 SYPHON
In -Tank Gauging Probe. Model: MAGEIn -Tank Gauging Probe. Model: MAG
Annular Space or Vault Sensor. Model: 409 E Annular Space or Vault Sensor, Model: 409
Piping Sump / Trench Sensor(s). Model: 323 Piping Sump / Trench Sensor(s). Model: 323
Fill Sump Sensor(s). Model: 323 E Fill Sump Sensor(s). Model: 323
Mechanical Line Leak Detector. Model: Mechanical Line Leak Detector. Model:
Electronic Line Leak Detector. Model: PLLD Electronic Line Leak Detector. Model:
Tank Overfill / High -Level Sensor. Model: FLAPPER Tank Overfill / High -Level Sensor. Model: FLAPPER
Other (specify equipment type and model in Section E on Page 2). Other (specify equipment type and model in Section E on Page 2).
Tank ID: PLUS91 Tank ID: PREM91
E In -Tank Gauging Probe. Model: MAG E In -Tank Gauging Probe. Model: MAG
E Annular Space or Vault Sensor. Model: 409 Annular Space or Vault Sensor. Model: 409
E Piping Sump / Trench Sensor(s). Model: 323 Piping Sump / Trench Sensor(s). Model: 323
E Fill Sump Sensor(s). Model: 323 E Fill Sump Sensor(s). Model: 323
Mechanical Line Leak Detector. Model: Mechanical Line Leak Detector. Model:
Electronic Line Leak Detector. Model: PLLD Electronic Line Leak Detector, Model: PLLD
E Tank Overfill / High -Level Sensor. Model: FLAPPER E Tank Overfill / High -Level Sensor. Model: FLAPPER
Other (specify equipment type and model in Section E on Page 2). Other (specify equipment type and model in Section E on Page 2).
Dispenser ID: 1/2 Dispenser ID: 314
Dispenser Containment Sensor(s). Model: 323 Dispenser Containment Sensor(s). Model: 323
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
Dispenser TD: 516 Dispenser ID: 718
E Dispenser Containment Sensor(s). Model: 323 E Dispenser Containment Sensor(s). Model: 323
E Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
Dispenser ID: Dispenser ID:
Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s). Model:
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification - I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers'
guidelines. Attached to this Certification is information (e.g. manufacturers' checklists) necessary o verify that this information is
correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable enerating such reports, I have also
attached a copy of the report; (check all that apply): ® System set -up ® Alarm h' ry report
Technician Name (print): RICH PHILLIPS Signature:
Certification No.: A29084/1035169-UT License. No.: C611 D40 809850
Testing Company Name: RICH ENVIRONMENTAL Phone No.: (661) 392 -8687
Testing Company Address: 5643 BROOKS CT., BAKERSFIELD, CA 93308 Date of Testing/Servicing: 1/9/2012
Page 1 of 5
UN -036 —1 /4 www.unidocs org Rev. 01/17/08
Monitoring System Certification
D. Results of Testing/Servicing
Software Version Installed: 329.00
Yes No* Is the audible alarm operational?
Yes No* Is the visual alarm operational?
Yes No* Were all sensors visually inspected, functionally tested, and confirmed operational?
Yes No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will
not interfere with their proper operation?
Yes No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem)
N/A operational?
Yes No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
N/A monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate
positive shut -down? (Check all that apply) ® Sump/Trench Sensors; ® Dispenser Containment Sensors.
Did you confirm positive shut -down due to leaks and sensor failure /disconnection? ® Yes; No.
Yes No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no
N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank
fill point(s) and operating properly? Ifso, at what percent of tank capacity does the alarm trigger? %
E Yes* No Was any monitoring equipment replaced? Ifyes, identify specific sensors, probes, or other equipment replaced
and list the manufacturer name and model for all replacement parts in Section E, below.
Yes* No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply)
Product; Water. Ifyes, describe causes in Section E, below.
Yes No* Was monitoring system set -up reviewed to ensure proper settings? Attach set up reports, if applicable
Yes No* Is all monitoring equipment operational per manufacturer's specifications?
In Section E below, describe how and when these deficiencies were or will be corrected.
E. Comments: SENSOR IN 87 SYPHON FILL SUMP AND 91 FILL SUMP NOT WORKING. CUSTOMER WILL
ORDER SENSOR TO BE REPLACED.
1/16/12 RICHARD MASON REPLACED SENSOR - RETESTED AND PASSED.
Page 2 of 5
UN-036 — 2/4 www.unidocs.org Rev. 01/17/08
Monitoring System Certification
I
F. In -Tank Gauging / SIR Equipment: Check this box iftank gauging is used only for inventory control.
Check this box ifno tank gauging or SIR equipment is installed.
This section must be completed if in -tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
Yes No* Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
Yes No* Were all tank gauging probes visually inspected for damage and residue buildup?
Yes No* Was accuracy of system product level readings tested?
Yes No* Was accuracy of system water level readings tested?
Yes No* Were all probes reinstalled properly?
Yes No* Were all items on the equipment manufacturer's maintenance checklist completed?
In Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD):
Complete the following checklist:
Check this box if LLDs are not installed.
Yes No* For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance?
N/A Check all that apply) Simulated leak rate: ® 3 g.p.h.; 0.1 g.p.h ; 0.2 g.p.h.
Yes No* Were all LLDs confirmed operational and accurate within regulatory requirements?
Yes No* Was the testing apparatus properly calibrated?
Yes No* For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
N/A
Yes No* For electronic LLDs, does the turbine automatically shut offifthe LLD detects a leak?
N/A
Yes No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled
N/A or disconnected?
Yes No* For electronic LLDs, does the turbine automatically shut off if any portion ofthe monitoring system malfunctions
N/A or fails a test?
Yes No* For electronic LLDs, have all accessible wiring connections been visually inspected?
N/A
Yes No* I Were all items on the equipment manufacturer's maintenance checklist completed?
In Section H, below, describe how and when these deficiencies were or will be corrected.
H. Comments:
UN -036 - 3/4
Page 3 of 5
www.unidocs.org Rev. 01/17/08
Monitoring System Certification
r
UST Monitoring Site Plan
site Address: 3333 UNION AVE. BAKERSFIELD, CA. 93305
3ys ..................... ...............................
cY
est1
fl
4
A - - to
t .
PCLO
P
T . . . . . . . . . . . . . . .... - . . . .
0tO Sump
v
T..
08:..4k.. . a . . . . . . .
2.. .........................
3
3 . 3 £ .......... .............
g.............
sr+HN iicD(6car^r* ao{ t7ki3 . . .
I............... .
F ...........................
I .... ...............................
I ......... I ..............
I.............. .
Date map was drawn:Q"QQ
Instructions
If you already have a diagram that shows all required information, you may include it, rather than this page, with your Monitoring
System Certification. On your site plan, show the general layout of tanks and piping. Clearly identify locations of the following
equipment, if installed: monitoring system control panels; sensors monitoring tank annular spaces, sumps, dispenser pans, spill
containers, or other secondary containment areas; mechanical or electronic line leak detectors; and in -tank liquid level probes (if used
for leak detection). In the space provided, note the date this Site Plan was prepared.
Page 5 of 5
UN -036 — 4/4 www.unidoe8.org Rev. 01/17/08
utlbwl
SWRCB, January 2006
Spill Bucket Testing Report Form
Thisform is intendedfor use by contractors performing annual testing ofUST spill containment structures. The completedform and
printoutsfrom tests (fapplicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: JOHNNY'S ARCO Date ofTesting: 1/9/12
Facility Address: 3333 UNION AVE., BAKERSFIELD
Facility Contact: JOHNNY I Phone: (661) 703 -8088
Date Local Agency Was Notified ofTesting : 11/30/11
Name of Local Agency Inspector (fpresent during testing):
2. TESTING CONTRACTOR INFORMATION
Company Name: RICH ENVIRONMENTAL
Technician Conducting Test: RICH PHILLIPS
Credentials: CSLB Contractor X ICC Service Tech. SWRCB Tank Tester Other (Spec)
License Number(s): 1035169 -UT
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: X Hydrostatic Vacuum Other
Test Equipment Used: VISUAL I Equipment Resolution: 0
Identify Spill Bucket (By Tank
Number, StoredProduct, etc.
1 UNL87 2 UNL87 SYPHON 3 PLUS89 4 PREM91
Bucket Installation Type: Direct Bury
X Contained in Sump
Direct Bury
X Contained in Sump
Direct Bury
X Contained in Sump
Direct Bury
X Contained in Sum
Bucket Diameter: 12" 12" 12" 12"
Bucket Depth: 16" 16" 16" 16"
Wait time between applying
vacuum /water and start oftest: l OMIN l OMIN l OMIN IOMIN
Test Start Time (Ti): 1:30 1:30 1:30 1:30
Initial Reading (Rj): 14" 14" 14" 14"
Test End Time (TF): 2:30 2:30 2:30 2:30
Final Reading (RF): 14" 14" 14" 14"
Test Duration (TF —Tj): l -HOUR 1 -HOUR 1 -HOUR 1 -HOUR
Change in Reading (RF - Rj): 0 0 0 0
Pass/Fail Threshold or
Criteria: 000 0.00 0.00 0.00
Test Result: X Pass Fail X Pass Fail X Pass Fail X Pass Fail
Comments — (include information on repairs made prior to testing, and recommendedfollow -upforfailed tests)
CERTIFICATION OF TECH CIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
1 hereby certify that all the informatlon twined in this report is true, accurate, and in full compliance with legal requirements.
Technician's Signature: Date: 1/9/12
State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
RICH ENVIRONMENTAL
3305 BRITTAN ST. BAKERSFIELD, CA. 93308
OFFICE (661)326 -8402 FAX (661)326 -8934
PRODUCT LINE LEAK DETECTOR TEST
WORK SHEET
W /p #:
FACILITY NAME: JOHNNY'S ARCO
FACILITY ADDRESS: 3333 UNION AVE. BAKERSFIELD
PRODUCT LINE TYPE: PRESSURE
I 1 eti
t
PRODUCT LEAK DETECTOR TYPE TEST TRIP PASS
BELOW P.S.I. OR
SERIAL NUMBER 3 G.P.H. FAIL
UNL87 L/D TYPE: ELECTRONIC
YES p PASS
SERIAL # VEEDER -ROOT
PLUS89 L/D TYPE: ELECTRONIC
YES p PASS
SERIAL # VEEDER -ROOT
PREM91 L/D TYPE: ELECTRONIC
YES p PASS
SERIAL # VEEDER -ROOT
L/D TYPE • PASS
YES
SERIAL # FAIL
I CERTIFY THE ABOVE TESTS WERE CONDUCTED ON THIS DATE ACCORDING TO RED
JACKET PUMPS FIELD TEST APPARATUS TESTING PROCEDURE AND LIMITATIONS.
THE MECHANICAL LEAK DETECTOR TEST PASS / FAIL IS DETERMINED BY USING A
LOW FLOW THRESHOLD TRIP RATE OF 3 GALLONS PER HOUR OR LESS AT 10 P.S.I. I
ACKNOWLEDGE THAT ALL DATA COLLECTED IS TRUE AND CORRECT TO THE BEST
OF MY KNOWLEDGE.
TECHNICIAN: RICH P IPS
SIGNATURE: DATE: I /9/12
ARCO am,,Pm 82765
3333 Union Ave H- PROTOCOL DATA FORMAT
Bakersfield HEIGHT
PRECISION TEST DURATIONCA93305HOURS: 12
JAN 9, 2012 12:29 PM DAYLIGHT SAVING TIMEENABLED
SYSTEM DATE /TIME FORMAT
START DATE
MON DD YYYY HH:MM:SS xM
MAR WEEK 3 SUN
SYSTEM STATUS REPORT START TIME
2:05 AM
ALL FUNCTIONS NORMAL END DATE
NOV WEEK 1 SUN
Bakersfield
END TIME
CA 93305
2:00 AM
SHIFT TIME 1 10:00 PM
RE- DIRECT LOCAL PRINTOUT
r
DISABLED
SHIFT TIME 3 DISABLED
EURO PROTOCOL PREFIX
SHIFT TIME 4 DISABLED
S
SOFTWARE REVISION LEVEL
VERSION 329.02
SOFTWARE# 346329 -100 -C
CREATED - 09.07.01.16.29
S- MODULE# 330160 -D04 -a
SYSTEM FEATURES:
PERIODIC IN -TANK TESTS
ANNUAL IN -TANK TESTS
ISD
SYSTEM SECURITYCODE : 000000
MAINTENANCE HISTORYDISABLED
TANK CHART SECURITYDISABLED
CUSTOM ALARMS
DISABLED
SERVICE'NOTICEDISABLED
SYSTEM SETUP
JAN 9, 2012 12:29 PM - 3166 COUNTRY
CODE:
SYSTEM UNITS P
I SiDENSITY
ABLERU.S.
SYSTE
SLANGUAGE
ENGL
SYSTEM DATE /TIME FORMAT
MON DD YYYY HH:MM:SS xM
ARCO am,lPm .82765
3333 Union Ave.
Bakersfield
CA 93305
SHIFT TIME 1 10:00 PM
SHIFT TIME 2 DISABLED COM11UNICATIONS SETUPSHIFTTIME3DISABLED
SHIFT TIME 4 DISABLED
TANK PER TST NEEDED WRN PORT SETTINGS: DISABLED -'
TANK ANN TST NEEDED WRN COMM BOARD 1 (S -SAT ) DISABLED BAUD RATE 9600
LINE RE- ENABLE METHOD PARITY NONE
STOP BIT : 1 STOPPASSLINETESTDATALENGTH: 8 DATA
LI.NE PER TST NEEDED WRN RS -232 SECURITY
CODE : DISABLEDDISABLED.
LINE ANN TST NEEDED WRN DTR NORMAL STATE: HIGH
DISABLED COMM BOARD : 2 (EDIM )
PRINT TC VOLUMES I RS -232 SECURITY
CODE : DISABLEDENABLED
TEMP COMPENSATION COMM BOARD 3 (RS -232) BAUD RATE 4200VALUE (DEG F ): 60.0 PARITY ODDSTICKHEIGHTOFFSET
DISABLED STOP BIT 1 STOP
ULLAGE: 91r4 DATA LENGTH: 7 DATA
RS -232 SECURITY
CODE : DISABLED
AUTO TRANSMIT SETTINGS:
AUTO LEAK ALARM LIMIT
Iv
DISABLED
AUTO HIGH WATER LIMIT
DISABLED
AUTO OVERFILL LIMIT
DISABLED
AUTO LOW PRODUCT
DISABLED
AUTO_ THEFT LIMIT
DISABLED
AUTO DELIVERY START
DISABLED
AUTO DELIVERY END
DISABLED
AUTO EXTERNAL INPUT ON
DISABLED
AUTO EXTERNAL INPUT OFF
DISABLED
AUTO SENSOR FUEL ALARM
DISABLED
AUTO SENSOR WATER ALARM
DISABLED
AUTO SENSOR OUT ALARM
DISABLED
RECEIVER SETUP:
NONE
AUTO DIAL TIME SETUP:
NONE
RS -232 END OF MESSAGE
DISABLED
AUTO DIAL ALARM SETUP
J —TANK SETUP
1:UL MID ORA
0.8
1.0
2ODUCT CODE 2
iERMAL COFFF 000700
Nl; DIAMETER 117.58
MIX PROFILE 4 PTS
10369FULLVOL
88.2 INCH VOL 8509
88.2 INCH VOL
1555
29.4 INCH VOL 19495
OAT SIZE: 2.0 IN.
kTF.R WARM NG '. :
GH WATER LIMIT:
0.8
1.0
X OR LABEL VOL: 10369
IERFILL LIMIT
000700
TANK DIAMETER
9332
GH PRODUCT 95%
9850
LIVERY LIMIT
10369
88.2 INCH VOL
1555
W PRODUCT 4 ,J0
AK ALARM LIMIT: 99
JDDEN LOSS LIMIT: 0.00aNKTILT
OBE OFFSET 0.00
PHON MANIFOLDED TANKS
t: .NONE
NE MANIFOLDED TANKSisNONE
AK MIN PERIODIC: O
AK ill N ANNUAL O
iR I OD I C TEST TYPESTAIVDARD
4NUAL TEST
ALAR
L
MDISABLED
RIQDIC TpLA DISABLED
ZOSS TEST FAILALARM DISABLED
4N TEST AVERAGING: OFF
R TEST AVERAGING: OFF
INK TEST NOTIFY: OFF
JK TST SIPHON BREAK :OFF
LIVERY DELAY 1 MIN
JMP THRESHOI —D : 10.00%
T 2:UNLEADED R
PRODUCT CODE 1
THERMAL COEFF :..000700
TANK DIAMETER 117.58
TANK, PROFILE 4 PTS
FULL VOL 10369
88.2 INCH VOL 8509
58.8 INCH VOL 5299
29.4 INCH VOL 1945
FLOAT SIZE: 2.0 IN.
WATER WARNING : 0.8
HIGH WATER LIMIT: 1.0
MAX OR LABEL VOL: 10369
OVERFILL LIMIT 90310
9332
HIGH PRODUCT 95%
9850
DELIVERY LIMIT 15%
1555
LOW PRODUCT 400
LEAK ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 99
TANK TILT 0.00
PROBE OFFSET 0.00
SIPHON MANIFOLDED TANKS
T #: NONE
LINE MANIFOLDED TANKS
T #: NONE
LEAK MIN PERIODIC: Dye
0
LEAK MIN ANNUAL 0%
0
PERIODIC TEST TYPE
STANDARD
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY 1 MIN
PUMP THRESHOLD : 10.00%
tool
ea
T 3:UNLEADED R
PRODUCT CODE 1
THERMAL COEFF 000700
TANK DIAMETER 117.58
TANK PROFILE 4 PTS
FULL VOL 10369
88.2 INCH VOL 8509
58.8 INCH VOL 5299
29.4 INCH VOL 1945
FLOAT SIZE: 2.0 IN.
WATER WARNING 1.0
HIGH WATER LIMIT: 2.0
MAX OR LABEL VOL: 10369
OVERFILL LIMIT
99
HIGH PRODUCT
985%
DELIVERY LIMIT
185
LOW PRODUCT 400
LEAK ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 99
TANK TILT 0.00
PROBE OFFSET 0.00
SIPHON MANIFOLDED TANKS
T #: NONE
LINE MANIFOLDED TANKS
T #: NONE
LEAK MIN PERIODIC: O%
LEAK MIN ANNUAL 00
PERIODIC TEST TYPE
STANDARD
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST
DISABLED
GRASS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY 1 MIN
PUMP THRESHOLD 10.00%
T 4 :UL PREMIUM
PRODUCT CODE
THERMAL COEFF 000700TANKDIAMETER
TANK PROFILE 117.58
FULL 10359
4 PTS
88.2 INCH VOjL 850458.8 INCH VOL
29.4 INCH VOL 5249
1945
FLOAT SIZE: 2.0 IN.
WATER WARNING 1.0HIGHWATERLIMIT: 2.0
MAX OR LABEL VOL: 10369OVERFILLLIMIT90%
HIGH PRODUCT 4332
950
DELIVERY LIMIT 4850
15%
1555
LOW PRODUCT 400
SUDDEN
ALARM 99TANKTILT0.00PROBFOFFSET0.Q0
SIPHON MANIFOLDED TANKSTo: NONE
LINE MANIFOLDED TANKST#: NONE
LEAK MIN PERIODIC: 00
0
LEAK MIN ANNUAL : 04
0
PERIODIC TEST TYPE
STANDARD
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFFPERTESTAVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY . I MINPUMPTHRESHOLD : 10.00%
LEAK TEST METHOD
TEST ON DATE : ALL TANKOCT9, 2008STARTTIME : DISABLEDTESTRATE :0.20 GALsHRDURATION : 2 HOURS
TST EARLY STOP :DISABLED
LEAK TEST REPORT FORMAT
NORMAL
PRESSURE LINE -LEAK SETUP
0 1 :89
TYP:2.0i3.0IN FIBERGLASS
2.0IN DIA LEN: 200 FEET
3.OIN DIA LEN: 0 FEET
SHUTDOWN RATE: 3.0 GPH
LOW PRESSURE SHUTOFF:YES
LOW PRESSURE : 5 PSI
T 1:UL MID GRA
DISPENSE MODE:
STANDARD
SENSOR: NON- VENTED
PRESSURE OFFSET: O.OPSI
MECHANICAL BLENDER: NO
0 2 :87
TYP :2.0i3.0IN FIBERGLASS
2.0IN DIA LEN: 150 FEET
3.,0IN DIA LEN: 150 FEET
SHUTDOWN RATE: 3.0 GPM
LOW PRESSURE SHUTOFF:YES
LOW PRESSURE : 5 PSI
T 2:UNLEADED R
DISPENSE MODE:
STANDARD
SENSOR: NON- VENTED
PRESSURE OFFSET: O.OPSI
MECHANICAL BLENDER: NO
9 3 :91
TYP:2.0i3.01N FIBERGLASS
2.0IN DIA LEN: 150 FEET
3.0IN DIA LEN: 150 FEET
SHUTDOWN RATE: 3.0 GPH
LOW PRESSURE SHUTOFF:YES
LOW PRESSURE : 5 PSI
T 4:UL PREMIUM
DISPENSE MODE:
STANDARD
SENSOR: NON- VENTED
PRESSURE OFFSET: O.OPSI
MECHANICAL 'BLENDER: NO
LINE LEAK LOCKOUT SETUP
LOCKOUT SCHEDULE
DAILY
START TIME: DISABLED
STOP TIME : DISABLED
LIQUID SENSOR SETUP
L 1:DIS 1 -2
TRI -STATE (SINGLE FLOAT)
CATEGORY : DISPENSER PAN
L 2:DIS 3 -4
TRI -STATE (SINGLE FLOAT)
CATEGORY : DISPENSER PAN
L 3:DIS 5 -6
TRI -STATE (SINGLE FLOAT)
CATEGORY : DISPENSER PAN
L 4:DIS 7 -6
TRI -STATE (SINGLE FLOAT)
CATEGORY : DISPENSER PAN
L 5:89 FILL
TRI -STATE (SINGLE FLOAT)
CATEGORY : PIPING SUMP
L 6:89 STP
TRI -STATE (SINGLE FLOAT)
CATEGORY : STP SUMP
L 7:89 ANNULAR
TRI - SPATE (SINGLE FLOAT)
CATEGORY : ANNULAR SPACE
L 8:87 MAIN FILL
TRI -STATE (SINGLE FLOAT)
CATEGORY : PIPING SUMP
L 9:87 MAIN STP
TRI -STATE (SINGLE FLOAT)
CATEGORY : STP SUMP
L10:87 MAIN ANNULAR
TRI -STATE (SINGLE FLOAT)
CATEGORY : ANNULAR SPACE
L11:87 SLAVE FILL
TRI -STATE (SINGLE FLOAT)
CATEGORY : PIPING SUMP
L12:87 SLAVE SUMP
TRI -STATE (SINGLE FLOAT)
CATEGORY : PIPING SUMP
Llb:87,SLAVE ANNULAR PLLD LINE DISABLE SETUP
TRI- STATE .(SINGLE FLOAT) Q 3:91
CATEGORY : ANNULAR SPACE Q 1:89 LIQUID SENSOR ALMS
L 1:FUEL ALARMLIQUIDSENSORALMSL2:FUEL ALARM
L14:91 FILL L I :FUEL ALARM L 3 :FUEL ALARM
TRI -STATE (SINGLE FLOAT) L 2 :FUEL ALARM
L 3:FUEL ALARM L 4:FUEL ALARM
CATEGORY : PIPING SUMP L 4:FUEL ALARM L15 -FUEL ALARM
I.15--SENSOR OUT ALARML6:FUEL ALARM L 1:S}iORT ALARM
L15:91 STP L 1:SENSOR OUT ALARM L 2 :SHORT ALARM
STATE (SINGLE FLOAT) 2:SENSOR OUT ALARM L 3:SHORT ALARMACTEEGORYSTPSUMPCATEGORYL3:SENSOR OUT ALARM L 4:SHORT ALARML4:SENSOR OUT ALARM L15:SHORT ALARML6:SENSOR OUT ALARM
L16:91 ANNUIrAR L 1:SHORT ALARM PRESSURE LINE LEAK
TRI -STATE (aINGLE FLOAT) L 2:SHORT ALARM Q 31PLLD OPEN ALARM
CATEGORY ANNULAR SPACE L 3:SHORT ALARM
L 4:SHORT ALARM ISD SITE ALARMSL6:SHORT ALARM ISD GROSS PRES FAILISDDEGRDPRESFAILISDSITEALARMSISDVAPORLEAKFAILISDGROSSPRESFAILISDVPPRESFAILISDDEGRDPRESFAIL
ISD VAPOR LEAK FAIL ISD HOSE ALARMSISDVPPRESFAILALL:GROSS COLLECT FAILISDVPSTATUSFAILALL :DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAILISDHOSEALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
OUTPUT RELAY SETUP ALL:FLOW COLLECT FAIL
Q2:87
R 1:OVERFILL ALARM
TYPE' LIQUID SENSOR ALMS
STANDARD L i:FUEL ALARM
NORMALLY OPEN L 2:FUEL ALARM
L 3:FUEL ALARM
TANK #: NONE L 4:FUEL ALARM AIARTSENSOR SETUPL9:FUELALARM
L12:FUEL ALARM
IN -TANK ALARMS L 1:SENSOR OUT ALARM s 1:AFM 1 -2ALL:OVERFILL ALARM L 2:SENSOR OUT ALARM CATEGORY AIR FLOW METER
ALL:HIGH PRODUCT ALARM L 3:SENSOR OUT ALARM
ALL:MAX PRODUCT ALARM L 4:SENSOR OUT ALARM s 2:AFM 3 -4L9:SENSOR OUT ALARM CATEGORY AIR FLOW METERL12:SENSOR OUT ALARM
L 1:SHORT ALARM s 3:AFM 5 -6L2:SHORT ALARM CATEGORY AIR FLOW METERL3:SHORT ALARM
L 4:SHORT ALARM s 4:AFM 7 -8L9:SHORT ALARM CATEGORY AIR FLOW METERL12:SHORT ALARM
ISD SITE ALARMS CATEGORY- 2VAPOR PRESSURE
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL s 6:CANASTERISDVAPORLEAKFAILCATEGORYVAPOR VALVEISDVPPRESFAIL
ISD HOSE ALARMS s B:ATM PRESSURE
CATEGORY ATM P SENSORALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
EVR/ I SD SETUP
EVR TYPE: BALANCE
13ALANCE NOZZLE TYPE
VST
VAPOR PROCESSOR TYPE
VEEDER-ROOT POLISHER
ANALYSIS TIMES
TIME: 9:45 AM
DELAY MINUTES:
ACCEPT HIGH ORVR:
ENABLED
ISD HOSE TABLE
ID FP FL HL AA RR
01 01 01 02 04 UU
02 02 02 02 04 UU
03 03 03 02 01 UU
04 04 04 02 01 UU
05 05 05 02 02 UU
06 06 06 02 02 UU
07 07 07 02 03 UU
08 08 08 02 03 UU
ISD AIRFLOW METER MAP
ID SERIAL NUM LABEL
1 31692 AFM 3 -4
2 31784 AFM 5 -6
3 31509 AFM 7 -8
4 31346 AFM 1 -2
ISD FUEL GRADE HOSE MAP
1 2 3 4
FP MHH MHH MHH MHH AA
01 101 301 201 U U 4
02 102 202 302 U U 4
03 103 203 303 U U 1
04 104 304 204 U U 1
05 105 305 205 U U 2
06 106 206 306 U U 2
07 107 307 207 U U 3
08 108 308 208 U U 3
LABEL TABLE
1: UNASSIGNED
2: BLENDS
3: REGULAR
4: MID GRADE
5: PREMIUM
6: GOLD
7: BRONZE
8: SILVER
9: BLEND2
10: BLEND4
PMC SETUP
PMC VERSION: 01.02
VAPOR PROCESSOR TYPE
VEEDER -ROOT POLISHER
ALARM HISTORY REPORT
SENSOR ALARM -- - --
L I:DIS 1 -2
DISPENSER PAN
SENSOR OUT ALARM
JAN 9, 2012 1:54 PM
FUEL ALARM
JAN 9. 2012 1:54 PM
SENSOR OUT ALARM
JAN 9. 2012 1:49 PM
ALARM HISTORY REPORT
SENSOR ALARM -----
L 2:DIS 3 -4
DISPENSER PAN
FUEL ALARM 2 ;05 PMJAN9, 2012
SENSOR OUT ALARM
JAN 9, 2012 1:55 PM
FUEL ALARM
JAN 9, 2012 1:54 PM
ALARM HISTORY REPORT
SENSOR ALARM - - - -- L 3:DIS 5 -6
DISPENSER PAN
SENSOR OUT ALARM
JAN 9. 2012 1:57-PM
SENSOR OUT ALARMJAN9, 2012 1:49 PM
SETUP DATA WARNINGJUL1. 2009 8:58 AM
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 4:DIS 7 -8
DISPENSER PAN-,
SENSOR OUT ALARM
JAN 9, 2012 1:56 PM
FUEL ALARM
JAN 9, 2012 1:56 PM
SENSOR OUT ALARM
JAN 9, 2012 1:56 PM
ALARM HISTORY REPORT
SENSOR ALARM --
L 5:89 FILL
PIPING SUMP
SENSOR OUT ALARM
JAN 9. 2012 1 :49 P111
FUEL ALARM
JAN 9, 2012 1:20 PM
SETUP DATA WARNING
JUL 1. 2009 8:58 AM
ALARM HISTORY REPORT L-
1
L 6:89SSpOR ALARM,---- - STP SUMPSENSORNSOJANOUT ALARM9, 2012 1:49 PM
JAN ALARM9, 2012 1;19 pM
SETUP DATA WARNINGJUL1, 2009 8 :58 AM
ALARM HISTORY REPORT
SENSOR ALARM - - - --
ANNULARASPAER
SENSOR OUT ALARM
JAN 9, 2012 1:49 PM
FUEL ALARM
JAN 9, 2012 1:20 PM
SETUP DATA 61ARNING
JUL 1, 2009 8:58 AM
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 8 :87 MAIN FILL
PIPING SUMP
SENSOR OUT ALARM
JAN 9, 2012 1:49 PM
FUEL ALARM
JAN 9, 2012 1:29 PM
FUEL ALARM
JAN 6, 2012 11:38 AM
ALARM HISTORY REPORT
L 9:- SENSOR ALARM -_ STP SUMPAIN STP - --
SENSOR OUT ALARMJAN9, 2012 1 :49 pM
SENSOR OUT ALARplJAN9, 2012 1:25 PM
JAN ALARM9, 201'2 1:25 PM
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L10 :87 MAIN ANNULAR
ANNULAR SPACE
SENSOR OUT ALARM 49 PM
JAN 9,
FUEL ALARM PM
JAN 9• 2012
FUEL ALARM2012 1;31'PMJAN9•
x
ALARM HISTORY REPORT
1.11 87SENSOR ALARM - - - --
PIPING SUMP
SENSOR OUT ALARMJAN9, 2012 1:49 PM
SENSOR OUT ALARMJAN9, 2012 12:45 PM
SETUP DATA WARNINGJUL1, 2009 8 :58 AM
ALARM HISTORY REPORT
L12:87SSLAAVE SUMPPM -
PIPING SUMP
SENSOR OUT ALARMJAN9, 2012 1:49 PM
SENSOR OUT ALARMJAN9, 2012 1:26 PM
FUEL ALARM
JAN 9. 2012 1:26 PM
ALARM HISTORY REPORT
SENSOR ALARM ------
L 13:87 SLAVE ANNULAR
ANNUI -AR SPACE
SENSOR OUT ALARM
JAN 9, 2012 1:49 PM
FUEL ALARM
JAN 9, 2012 1:34 PNI
SETUP DATA WARNING
JUL 1. 2009 8:58 AM
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L14:91 FILL
PIPING SUMP
SENSO9,02012LARM49 PM
JAN
JAN 09,02012112.49 PM
JULUP DATA WARNING AM
1, 2009
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L15:91 STP
STP SU141P
SENSOR OUT ALARM
JAN 9, 2012 1:49 PM
SENSOR OUT ALARM
JAN 9. 201' 1 :42 PM
FUEL ALARM "
JAN 9: 2012. 1:42 PM
ALARM HISTORY REPORT
SENSOR ALARM
1.16:91 ANNULAR
ANNULAR SPACE
SENSOR OUT ALARM
JAN 9, 2012 1:49 PM
FUEL ALARM
JAN 9, 2012 1:36 PM
SETUP DATA WARNING
JUL 1, 2009 8:58 AM
Lf6w . 1 /11/
MONITOR CERT. FAILURE REPORT
SITE NAME: ,7-6 ALL,- Ane-a DATE: Z-
ADDRESS: 3333 vA-4oN AUL"' TECHNICIAN: RICHIE PHILLIPS
CITY: e A SIGNATURE:
REPAIRS: r? jc;a, rim)° °n- sz_ L A? g Fi G
r - , i•L a eff— .dam,y_
PARTS INSTALLED:
NONE
THE ABOVE NAMED PERSON TAKES FULL RESPONSIBILITY OF NOTIFYING
THE APPROPRIATE PARTY TO HAVE CORRECTIVE ACTION TAKEN TO REPAIR
THE ABOVE LISTED PROBLEMS AND NOTIFYING RICH ENVIRONMANTAL FOR
ANY NEEDED RETESTING. THIS ALSO RELEASES RICH ENVIRONMENTAL OF
ANY FINES OR PENALTIES OCCURING FROM NON - COMPLIANCE.
A COPY OF THIS DOCUMENT HAS BEEN LEFT ON -SITE FOR YOUR
CONVIENENCE.
a