HomeMy WebLinkAbout7991 WHITE LANE (3)k FIREArMrJanuary4, 2007
Mr. Julio Sical
Whitewater Car Wash
7991 White Lane
Ronald J. Fraze Bakersfield, CA 93309
Fire Chief
Gary Hutton NOTICE OF VIOLATION
Senior Deputy Chief AND SCHDULE FOR COMPLIANCE
Administration
Re: Failure to Perform Statistical Inventory Reconciliation (SIR) 326 -3650
Manual Tank Gauging at Whitewater Car Wash. 5201 Stockdale Hwy
Deputy Chief Dean Clason
Operations/Training Dear Mr. Sisal:
326 -3652
During your annual fuel monitor certification performed by Redwine Testing
Deputy Chief Kirk Blair Services on Wednesday, January 3, 2007, the following violations were noted:
Fire Safety/Prevention Services 1. No in -tank probes. Currently, your Gilbarco fuel326 -3653
monitor device is not doing Automatic Tank Gauging
ATG). Point -in -fact, you have no probes in any of
PREVENTION SERVICES
your tanks to do ATG. Code allows for Statistical
Inventory Reconciliation (SIR) under the followingRalphHuey, Director conditions:
900 Truxtun, Suite 210
Bakersfield, CA 93301 a. SIR shall be conducted at least once per
VOICE (661) 326 -3979 month in accordance with Section 2646.1
FAX (661) 852 -2171 (Title 23 California Code of Regulations,
Division 3, Chapter 16 Underground Tank
Regulations) and shall be capable of
detecting a release of 0.2 gallons per hour.
In addition, a tank integrity test shall be
conducted once every two years in
accordance with Section 2643.1. SIR
analyzes inventory, delivery, and dispensing
data collected over a period of time to
determine whether or not a tank system is
leaking.
b. Each operating day, the product level is
measured using a gauge stick or other tank
level monitor. You also keep complete
records of all withdrawals from the UST and
all deliveries to the UST. After data have
been collected for the period of time
required by the SIR vendor, you provide the
data to the SIR vendor.
l
Mr. Julio Sical, Whitewater Car Wash, 7991 White Lane, Bakersfield, CA 93309
January 4, 2007
Page 2
C. The SIR vendor uses sophisticated computer software to
conduct a statistical analysis of the data to determine whether
or not your UST system may be leaking. The SIR vendor
provides you with a test report of the analysis.
To be allowable as monthly monitoring, a SIR method must
be able to detect a leak of at least as small as 0.2 gallons per
hour and meet the federal regulatory requirements regarding
probabilities of detection and a false alarm data must be
submitted at least monthly.
e. The vendor, as is mentioned, is a third party firm that
specializes in sophisticated computer software to conduct
SIR. It is not the responsibility of your fuel supplier.
2. All three direct bury spill buckets failed. They must be repaired/
replaced immediately.
3. You have a secondary vent line in the 91 turbine sump that is cracked. The crack
runs at least 12 inches and appears to go through the penetration fitting outside of
the turbine sump. This also must be replaced immediately.
4. When the turbine sumps were opened, two of them (#87 and #91) had free
standing water in them approximately six inches. Both sensor probes were totally
submerged and were not in alarm which indicates that the sensors are not
functioning. Since no alarm was indicated at the panel, these also must be
replaced immediately.
5. You have three exit signs where the bulbs are burned out and must be replaced.
Please have this corrected within 30 days (February 3, 2007).
It is the recommendation of this office that you install an ATG system in lieu of SIR reporting. Your
Gilbarco system is capable of adding an ATG system to its software. This would avoid SIR
requirement.
It is also recommended that your Designated Operator (who should have noticed that much water
in your turbine sumps as it appears that water has been accumulating for some time) should have
caught this with a minor visual inspection.
Also, it is recommended that your documentation (log book) for your Designated Operator be kept
next to your Gilbarco monitor device. This will insure that when an Inspector asks for it, it can be
readily available. Your book was apparently lost (could not be found during my inspection).
However, Redwine Testing Services (I was told) brought out a replacement copy.
Mr. Julio Sical, Whitewater Car Wash, 7991 White Lane, Bakersfield, CA 93309
January 4, 2007
Page 3
Lastly, documentation, all contractors who perform fuel monitoring certifications are required by law
to affix a tag/sticker for every component that is tested and certified. During my inspection, no
stickers were affixed to any of your UST components. In the future, please look to see that any
repair work or certifications that are done have a tag or sticker affixed.
Items 1 through 4 need immediate attention. Failure to comply may result in revocation of your
Permit to Operate. Item 5 must be corrected within 30 days, February 3, 2007.
Should you have any questions, please feel free to call me at 661 — 326 -3190.
Sincerely,
i
Steve Underwood,
Fire Prevention Officer
SU /db
cc: Redwine Testing Services, Inc.
belshi're
environmental services, inc.
25971 Towne Centre Drive, Foothill Ranch, CA 92610
Designated Operator Alternate List
Name's
M _ _
Jhustin Abeleda
3 ICCCert
8036229 -UC
t Expirations Phane
9/26/2011 (949) 460 -5200
10/19/2011 (949) 460 -5200
12/8/2011 (949) 460 -5200
9/8/2012 (949) 460 -5200
10/4/2012 (949) 460 -5200
2/15/2013 (949) 460 -5200
Jeffrey Badders 5252456 -UC
Adam Burton
Oliver Cruz
8049062 -UC `
5244318 -UC
Andy DeGregorio
Ricky Diaz
8019630 -UC
8102023 -UC
Jesse Diaz 8035355 -UC 9/4/2011 949) 460 -5200
949) 460 -5200JackieDougherty — 5234433 -UC 7/14/2012
Justin Downs
Glenda Esteban
8021990 -UC 121712012 — 949) 460 -5200
8018547 -UC 9/8/2012_~ 949) 460 -5200
Cheron Flores 8019649 -UC 949) 460 - 5200_1
Grasiela Gama 8022001 -UC
10/8/2012
12/14/2012 949) 460 -5200
Angelo Georgetti
Kris Gondrez _ —
Noah Henning
Brian Hernandez _ _ ,
Kevin Hom
8027546 -UC
8115255 -UC
8013041 -UC
5308636 -UC
8054461 -UC
3122/2013
5/26/2013
5/26/2012
2/15/2013
1/22/2012
2/11/2012
949) 460 -5200
949) 460 -5200
949) 460 -5200
949) 460,5200 1
949) 460 -5200
949)46 . 0-5200SantiLuangpraseut8057544_UC
Jack Nestler 8079218 -UC 8/31/2012 (949) 460 -5200
Cory Nicholson 8020120 -UC 10/8/2012 (949) 460 -5200
8105942 -UC 3/18/2013 (949) 460 -5200ChukwuemekaOdunze
Clarinda Olson 5244506 -UC 2!2/2013
5/15/2012
949) 460 -5200
949) 460 -5200
949) 460 -5200 i
949) 460 -5200
Cristina Pena —
Spencer Platler
6010939 -UC
8014664 -UC 6116/2012
7/1412012DouglasShearer5240897 -UC
Roman Shekhter 8035361 -UC 9/9/2011 949) 460 -5200
949) 460 -5200GregVierra5317332 -UC 7/22/2011