HomeMy WebLinkAboutINSP COVERLETTER 7/21/201125-78 INSPECTION, TESTING, AND MAINTENANCE OF WATER -BASED FIRE PROTECTION SYSTEMS
Inspection, Testing,,an& aintenance Cover Sheet
NFPA 25 as: amend' d?by,_; CR, Title 19
Property Information:
Name: .. %/`` %/tGt' Occupancy /Use: of CA
op
Address: L // .. ;CE L, D Construction. Type: v
City: No. Stories:
ZIP: 73, v Year Constructed:
Contact: F
Telephone:
ontractor Information: Number of System Risers
Jorgensen Company
Copy sent to:
2345 S. Fruitvale Ave., #1
Owner Date
Bakersfield gfire AHJ Date
CA 93308
Contractor Date
661 - 327 -4352
NOTES:
262995 1) For.specific Inspection, -testing, and
maintenance requirements and information,
see NFPA-25,2002 Edition as amended:by
Job # S California Code of Regulations, Title.191,, §001
to §906.
2) Inspection Items may be performed by. the
Performed by:
Print)
Owner in accordance with California Code of
Regulations Title 19 §904.1(a)
Forms included with this report NFPA 25
Chapter Number of Forms N/A FAIL' PASS
rAutomatic Sprinkler System 5
Standpipe and Hose Systems g
Private Water Supply System 7
Fire Pump g
Water Storage Tank g
Water Spray System 10
Foam Water Sprinkler System 11
See "Deficiencies and Comments ", section at end of each respective form.
State Fire Marshal AES 1 March 21, 2006
wil1fc1 25 -79
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25, Chapter Sas amended by CCR, Title 19
Page 1 of 4
Date of Inspection, Testing, Maintenance: System Riser ID:
Initial Static Pressure: 60 (psi)
Property Information:
M = Maintenance
Name: /% G —' %s Type of System:
Wet Pipe
of CA4./.
0
MI = Per Manufacturer's Instructions
Address: 32% /V . gC?Z- ,2 0 Dry Pipe a
Description
0 Preaction
Fail N/A
O Deluge r, ARE MP+
City: /eG /;:7
Daily Preaction /Deluge Valves — Enclosure
Main Drain Test Results: Abbreviation Key:
I =Inspection
Initial Static Pressure: 60 (psi) T = Test
M = Maintenance
Residual Pressure: SS (psi) A -O = After Operation
MI = Per Manufacturer's Instructions
Restored Static Pressure: S` (psi)
Item Activity Frequency Description NFPA 25
Reference Fail N/A Pass
1.1 1 Daily Preaction /Deluge Valves — Enclosure 12.4.3.1Weeklytemrature X
1.2 1 Daily Dry Pipe Valves — Enclosure 12,4.4.1.1Weeklytemperature k-
1.3 1 Quarterly Gauges (Dry, Preaction, Deluge 5.2.4.2
Systems) 5.2.4.3
1.4 I Quarterly Control Valves 12.3.2.1
1.5 1 Quarterly Alarm Devices 5.2.6
1.6 1 Quarterly Gauges (Wet Pipe Systems) 5.2.4.1 X
1.7 1 Quarterly Hydraulic nameplate 5.2.7
1.8 1 Quarterly Pipe and Fittings 5.2.2
1.9 1 Quarterly Sprinklers 5.2.1 k
1.10 1 Quarterly Spare Sprinklers 5.2.1.3 Nc
1.11 1 Quarterly Fire Department Connections 12.7.1
1.12 1 Quarterly Alarm Valves — Exterior Inspection 12.4.1.1
1.13 1 Quarter) Quarterly
Preaction /Deluge Valves — Exterior 12.4.3.1.6
Inspection
1.14 1 Quarterly Pressure Reducing Valves 12.5.1.1
1.15 1 Quarterly Dry Pipe Valves — Exterior Inspection 12.4.4.1.4
1.16 1 Quarterly Backflow Preventers 12.6.1 X
1.17 1 Annually Buildings 5.2.5 k
State Fire Marshal AES 2 March.21, 2006
25 -80 INSPECTION, TESTING, AND MAINTENANCE OF WATER -BASED FIRE PROTECTION SYSTEMS
Inspection, Testing, and Maintenance Fire Sprinkler System Page 2 of 4
NFPA 25, Chapter 5 as amended by CCR Title 19
Date of Inspection, Testing, Maintenance: —Z/ "/l System Riser ID:
Property Information:
Name: G / /—G dE
Type of System: OF CAI.
Wet Pipe
Z
Address: 13 Dry Pipe " a
Preaction
Deluged
ARE MP
City: tG. /i
Item Activity Frequency Description NFPA 25
Reference Fail N/A Pass
1.18 1 Annually Hangers 5.2.3
1.19 1 Annually Seismic Braces 5.2.3
1.20 1 5 Years Hangers (Accessible concealed spaces) 5.2.3.3
1.21 1 5 Years Seismic Braces (Accessible concealed 5.2.3.3
1.22 1 5 Years Pipe a Fittings (Accessible concealed 5.2.2.3spaces)
1.23 1 5 Years Sprinklers (Accessible concealed spaces) 5.2.1.1.4
1.24 1 5 Years Alarm Valves — Interior Inspection 12.4.1.2
1.25 1 5 Years Alarm Valves - Strainers, filters, orifices 12.4.1.2
1.26 1 5 Years Check Valves — Interior Inspection 12.4.2.1
1.27 1 5 Years PreaclorvDeluge Valves — ,Interior 12.4.3.1.7Inspection
1.28 1 5 Years PreactioNDeluge Valves - Strainers, 12,4.3.1.8filtersorifices
1.29 1 5 Years Dry Pipe Valves — Interior Inspection 12.4.4.1.5
1.30 1 5 Years Dry Pipe Valves - Strain* filters, orifices 12.4.4.1.6
2.1 T Annually Alarm Devices (90 Sec) 5.3.3
12.2.7
12.2.6
2.2 T Annually Main Drain Test'(Enterdatp on Page 1) 12.2.6.1
12.3.3.4
2.3 T Annually Antifreeze Test 5.3.4 X
2.4 T Annually Control Valve - Position 12.3.3.1
2.5 T Annually Control Valve — Operation 12.3.3.1
2.6 T Annually Supervisory 12.3.3.5
2.7 T Annually Preaction Valve— Priming Water 12.4.3.2.1
2.8 T Annually Preaction Valve — Low Air Pressure Alarm 12.4.3.2.10 k
2.9 T Annually Preaction Valve — Full Flow Trip Test 12.4.3.2.2
State Fire Marshal AES 2 March 21, 2006
25 -81
Inspection, Testing, and Maintenance Fire Sprinkler System Page 3 of 4
NFPA 25 Chapter 5 as.amended by CCR Title 19
Date of Inspection, Testing, Maintenance: System Riser ID:
Property Information:
Name: 1—/-,L76-7 //U1't e of of c,aL,
o9TypesW
tstem
Pipe
Address: .72 -7 /t/ % i 1
D Pipe ` 2DryPiPipa
n
Deluges P
SAE Mp
City:
Item Activity Frequency Description NFPA 25
Reference Fail N/A Pass
2.10 T Annually Dry Pipe Valve — Priming Water 12.4.4.2.1
2.11 T Annuallyy ry Pipe Valve — Low Air Pressure 12.4.4.2.6Alarm k
2.12 T Annually DD Valve — Quick - Opening 12.4.4.2.4
2.13 T Annually Dry Pipe Valve — Trip Test 12.4.4.2.2
2.14 T Annually Backflow Preventer Assemblies 12.6.2 x
2.15 T 3 Years Dry Pipe Valve — Full Flow Trip Test 12.4.4.2.2.2
2.16 T 5 Years Gauges 5.3.2
2.17 T 5 Years Pressure Reducing Valve 12.5.1.2
2.18 T 5 Years Fire Department Connection Backflush 12.7.4
2.19 T 5 Years Sprinklers — Extra High Temperature 5.3.1.1.1.3 k
2.20 T 5 Years Sprinklers — Corrosive environment or 5.3.1.1.2
corrosive water
2.21 T 10 Years Sprinklers - Dry 5.3.1.1.1.5
2.22 T 20 Years Sprinklers - Fast Response 5.3.1.1.1.2
2.23 T 50 Years Sprinklers 5.3.1.1.1
2.24 T 75 Years Sprinklers 75 years in service 5.3.1.1.1.4
2.25 T Sprinklers manufactured prior to 1920 5.3.1.1.1.1Replace
3.1 M Annually Control Valves 12.3.4
3.2 M Annually Preaction/Deluge Valves 12.4.3.3.2
3.3 M Annually Dry Pipe Valves/Quick- Opening 12.4.4.3.2 kDevices
3.4 M Annually Dry Pipe Valve — Low Point Drains 12.4.4.3.3
3.5 M 5 Years Obstruction Investigation Chapter 13
State Fire Marshal AES 2 March 21, 2006