HomeMy WebLinkAbout1.8-7161 Ph 21 2 NOTES: 04-30-07 REFER TO ELECTRIC &GAS SERVICE REQUIREMENTS (GREEN BOOK) OR SEPARATE PG &E STANDARD DRAWINGS. CONTACT YOUR PG &E REPRESENTATIVE FOR COPIES, OR ACCESS www.pge.com /greenbook CONDUIT, TRENCHING, AND BACKFILL: 1) ALL DIMENSIONS AND LOCATIONS ARE ESTIMATED, APPROXIMATE AND MAY BE SUPERSEDED BY A JOINT TRENCH DRAWING. REFER TO THE JOINT TRENCH COMPOSITE DRAWING FOR EXACT TRENCH E LOCATION 2) MAINTAIN- MAXIMUM PRACTICABLE HORIZONTAL CLEARANCE BETWEE PG &E FACILITIES AND "WET" UTILITIES (WATER, SEWER, STORM DRAIN ETC.). THE MIN. ALLOWABLE SEPARATION BETWEEN PG &E FACILITIES AND ANY PARALLEL "WET" UTILITY IS 3 /FT. WITH A PRESENCE OF 1 /FT. OF UNDISTURBED EARTH OR THE INSTALLATION OF A SUITABLE BARRIER. THIS MEASUREMENT IS BETWEEN. THE OUTER EDGE OF THE PG &E FACILITY AND THE OUTER EDGE OF THE PARALLEL "WET" FACILITY. IF 3 /FT. CANNOT BE MAINTAINED, A FORMAL VARIANCE MU T BE OBTAINED FROM PG&E WORK WITH THE PG &E INSPECTOR (REFERENCE PG &E UO STANDARD S5453). 3) BOX, PAD, AND CONDUIT SIZES AND LOCATIONS SHALL CONFORM TO THE PG &E ELECTRIC CONSTRUCTION DRAWING. 4) PROVIDE LONG CONDUIT SWEEPS WHERE INDICATED. RECOMMENDED SWEEP RADIUS (10' OF RADIUS PER INCH OF CONDUIT DIAMETER) EXAMPLE: 4" CONDUIT = 40' RADIUS 5) DO NOT EXCEED 300 DEGREES OF BENDS IN CONDUIT RUNS. SECONDARY CONDUIT RUNS LESS THAN 200' IN LENGTH ALLOW 315 DEGREES (INCLUDING FEED LOCATION.). 6) MANUFACTURED BENDS OR APPLICATION OF HEAT SHALL NOT BE D USED TO OBTAIN LONG CONDUIT SWEEPS. 7) ALL CONDUITS SHALL BE PROVEN AND A POLYESTER PULLING TAPE INSTALLED. 8) MANUFACTURED BENDS ARE NOT TO BE CUT, SHORTENED, OR ALTERED IN ANY WAY. 9) IDENTIFY ENDS OF BURIED CONDUIT WITH AN ELECTRONIC MARKER AND A VERTICAL CONDUIT SCRAP .INSTALLED FROM RIGID CAP TO GROUND LEVEL. 10) CONDUITS ENTERING PRIMARY BOXES SHALL BE AT A RIGHT ANGLE TO THE WINDOW OR WALL. 11) STUB CONDUITS AT RISER POLES IN QUADRANTS AS SHOWN. AT IDENTIFIED POLE LOCATIONS, THE TRENCHING AGENT IS TO EXCAVATE'. TO TRENCH DEPTH AND INSTALL A 30" DIAMETER CARDBOARD TUBE. THE RISER CONDUIT BEND IS TO BE PLACED OUTSIDE AND ADJACENT TO THE TUBE AT THE POLE QUADRANT INDICATED. BACKFILL AROUND AND INSIDE TUBE WITH CLEAN NATIVE -FILL. 12) LS2 STREET LIGHT CONDUIT GOING TO PG &E BOXES OR PEDESTALS NOT DESIGNATED AS P.O.S. (INCLUDING TRANSFORMERS) WILL NOT BE ACCEPTED OR CONNECTED. C 13) ONLY ONE LS2 STREET LIGHT (P.O.S.) CONNECTION PER BOX OR PEDESTAL. LAND RIGHTS AND EASMENTS: 14) APPLICANT TO PROVIDE ADEQUATE P.U.E'S AND /OR ROW'S FOR PG &E FACILITIES. ANY ADDITIONAL REQUIRED RIGHTS OF WAY ARE TO BE SURVEYED AND DOCUMENTED BY PG &E AT THE APPLICANT'S EXPENSE. SAFETY AND WORKMANSHIP: 15) NOTIFY USA (811) 48 HOURS PRIOR TO DIGGING FOR UNDERGROUND LOCATING. 16) 48 HOUR NOTICE REQUIRED FOR UNDERGROUND INSPECTION. 17) MATERIALS AND WORKMANSHIP SHALL BE FIRST QUALITY IN EVERY RESPECT, PLUMB AND TRUE, AND ACCORDING TO THE SPECIFIC REQUIREMENTS OF THE DRAWINGS AND THE ABOVE APPLICABLE NOTES AND SPECIFICATIONS, 18) THE APPLICANT IS TO VERIFY ALL PROPOSED INSTALLATIONS, CONDITIONS &SPECIFICATIONS PRIOR TO COMMENCING WITH ANY PORTION OF WORK. ANY DISCREPANCIES, DELETIONS OR INCONSISTENCIES ARE TO BE REPORTED TO THE PG &E REPRESENTATIVE IMMEDIATELY. THE APPLICANT SHALL COMPLY WITH B ALL APPLICABLE SPECIFICATIONS. ANY VARIATIONS FROM PLANS OR SPECIFICATIONS RELIEVES PG &E OF ALL RESPONSIBILITY FOR THE SUBSTRUCTURE OR DESIGN. A FOR QUESTIONS REGARDING THIS JOB: EST: MELISSA VARGAS (559) 347 -502 ADE: LINDA PRIAULX (559) 347 -5040 SUP: KEN HENDRICKS OFFICE: (559) 347 -5023 CELL: (559) 970-02813 REP: LES INGLE OFFICE: (661) 398 -5975 CELL: (661) 342 -7948 ��l El 5 !01 w V cx� TYPICAL INTERIOR STREET PATTERN SCALE: 1`5) 7 10i 9 I 10 (AVG.) SQUARE FEET: - _CONFLICTS — --.- MAIN SIZE: 200A MAX AC TONNAGE: 5 TYPICAL SERVICE SETBACK LENGTH: W C) C;d f— X X CIRCLED LOT NUMBERS INDICATE THE FOLLOWING. CIR W _ cn STORM DRAIN CONFLICT WITH ELECTRIC SERVICE AT LOT LINE: NONE r a E­4 WATER SERVICE CONFLICT WITH ELECTRIC SERVICE AT LOT LINE: a N w 15 00 © O L) WATER SERVICE CONFLICT WITH ELECTRIC EQUIPMENT AT LOT LINE: C. �- 0 NONE o L.) 0 En �..` 0 :z C) (n a- The conflicts noted below have been communicated to the Applicant or their Agent on _._. 9/2111 3 (date). The Applicant �-- is responsible to make modifications to the proposed facilities - z Q noted in conflict to establish the required proper clearance from ,) ' facilities as stipulated in PG&Es standards. PG&E 's proposed fa ' p E­4 .�, U 0 � , � � � v WORK AGENT RESPONSIBILITIES--- U-, ry � D Vz PG&E TO INSTALL ELEC. DISTRIBUTION FACIL ITIES x v ,� W APPLICANT TO INSTALL DIST. CONDUIT & SUBSTRUCTURES �, W PG&E TO INSTALL ELEC SERVICE FACILITIES C z APPLICANT TO INSTALL SERVICE CONDUITS & SUBSTRUCTURES -cC o L Q Q CD LO LO w W ©o Q �- n w a N W Q N p Q VJJ 0 t9 C-3 ., Rot W Z C/) -Z =E J Y ­J ­72 • • 4b w cn w Q m . Q C Y u z 0 0 0 z z 0 o o � W (AVG.) SQUARE FEET: 2800 MAIN SIZE: 200A MAX AC TONNAGE: 5 TYPICAL SERVICE SETBACK LENGTH: 25' 39' VICINITY SKETCH Primary Voltage:21 KV Plat Map: 3026126 Circu it: TEVI S 2104 v FARKERH DR Voltage Class: 1 Insulation Dist.: B o STILLBR{OK DR ° Corrosion Dist.: NON Estimator: MELISSA VARGAS JOB SITE PHONE: 559 -- 347 --5027 LINCOLNSHIRE DR PAGER: WHITE LN THESE DRAWINGS ARE BASED ON DEVELOPER PLANS DATED: 04 /22/09 PROJECT CONDITIONS STAMP Type(s) of Work: nX New Business E]PG&E Maintenance & Construction.. - Project Conditions: nXNONE APPARENT (if project design changes, contact ADE) or ❑ CONDITIONS APPLY: ❑ PERMITS ❑ TAILBOARD ❑ OTHER (Provide additional information on line below) eY: MELISSA VARGAS, MCMQ, 10/203 SIGNATURE, NAME, [CORPORATE ID], DATE Underground' Service Alert TWO WORKING DAYS BEFORE YOU DIG 0 0 z� E—+ z W Q C;d w E­4 oT w z L) Z