HomeMy WebLinkAbout2015 INSPECTION REPORTBAKERSFIELD FIRE DEPARTMENT
Prevention Services Division
Underground Storage Tank- Program 2101 H Street
DW Inspection Repo iT Bakersfield, CA 93301
Permission to Inspect:'D Phone: 661-326-3979
Fax: 661-852-2171
Business Name: Stockdale Chevron-15-021-16490
Date:03/26/2015
Address Name: 13004 stockdale hwy.-KHENG CHAD
Inspector Name: Shane Gardner #8248557
Inspection Type: Routine
Report :Final
NVO = No Violation Observed OUT = out of Compliance NA = Not Applicable UD = Undetermined
Cos = Corrected On Site RPT = Repeat Violation
Violation
Program Requirement
o
SOC
Comments
No
z
0
z
File Review
Facility Tank
Information
-
2030021
Facility has a valid Permit
Tank 1-12000-REG-DW
to Operate from the
CUPA - 23 CCR 16 2712(1);
Z
❑
E]
❑
None
Tank 2-12000-MID-DW
Tank 3-20000-PRM-DW
HSC 6.7 25284
Tank 4-20000-DSL-DW
2010010
UST Operating Permit
Application for Facility
information and Tank
❑
❑
None
information
submitted/maintained - 23
CCR 16 2711; HSC 6.7
25286(a) —
2010001
Current BOE number
submitted to the CUPA
❑
❑
❑
❑
❑
None
and/or CERS - HSC 6.7
25286(c)
All D/O Certs in Cers have expired
2030011
UST compliance
statement and/or
Designated Operator
None
current certification
submitted - 23 CCR 16
2715(a), 2715(b)
2030046
A complete and accurate
response plan has been
submitted, approved and
El
❑
None
maintained - 23 CCR 16
2632, 2634(e), 2641(h),
2712(i)
2030041
A complete and accurate
plot plan has been
submitted, approved and
Z
❑
1:1
None
maintained - 23 CCR 16
2632(d),(1)(C), 2711(aj(8
2010006
Owner/Operator has not
made false statements or
Z
El
El
❑
❑
❑
None
representation on any
required document - HSC
6.725299
2010003
Owner/Operator has a
rFR-
DO and/or informed the
CUPA of any change (s)
Z
❑
E - In
❑ 1
None
within 30 days - 23 CCR
16 2715(a)
Violation
Program Requirement
4-
0
0
4) =
SOC
Comments
No
>
Q
a
0
0.
42 (u
O)o
0
z
Testing
2030002
Owner/Operator has
tested and certified leak
❑
❑
❑
El
❑
❑
None
detection equipment
annually - 23 CCR 16 2638
2030048
Secondary containment
testing conducted every
36 months in accordance
❑
❑
❑
❑
❑
❑
None
with requirements - 23
CCR 16 2637
2030055
Spill buckets have been
tested annually as
❑
❑
❑
❑
❑
❑
None
required - HSC 6.7 25284.2
2010009
Secondary containment
test results submitted to
the CUPA within 30 days
❑
❑
❑
❑
❑
❑
None
after the test - 23 CCR 16
2637(e)
2030064
CUPA was poperly
notified within the
prescribed number of
❑
❑
❑
❑
None
hours prior to testing - 23
CCR 16 26370, 2638(e),
2643Lg), 2644.1(a)(4)
Install/Repair
2060009
Permits obtained to
install, replace, repair, or
❑
❑
❑
E:]
❑
❑
None
modify part of the UST
system - 23 CCR 16 2712
UST System Observation
General Monitoring
2030003
Leak detection system
maintains continuous
RD
monitoring that activates
❑
❑
❑
❑
❑
❑
None
[:j
an audible and visual
Yes
alarm - 23 CCR 16 2632,
2634, 2636, 2666
2030016
The annular space of the
tank, piping and sumps
RD
are continuously
monitored and activates
❑
❑
❑
None
❑
the alarm - 23 CCR 16
Yes
2631(8), 2632(c) (2) (A) &(B),
2633(c), 2636(o
2030017
Product piping outside the
UDC is fail-safe and shuts
down the pump or
❑
❑
❑
❑
None
restricts flow - 23 CCR 16
2636(0(5)
2030018
Turbine sump monitor
RD
activates an audible and
visual alarm or stops the
❑
❑
1:1
❑
❑
❑
None
❑
flow of at the dispenser -
Yes
23 CCR 16 2636(0 (1)
Underground Storage Tank Program - DW Inspection Report v 2.0
Violation
Program Requirement
o
SOC
Comments
No
o
d
o
Co
a
L
z
O
z
v
oc
of
2030019
Monitoring system in the
UDCs activates an
audible and visual alarm
❑
❑
❑
❑
None
or stops the flow at the
UDC -23 CCR 16
2636 (0(1)
2030043
Leak detection equipment
RD
properly programmed or
properly operated - 23
❑
❑
❑
❑
❑
❑
None
❑
CCR 16 2632, 2634, 2636,
Yes
2666
2060005
System constructed with
a monitoring system
capable of detecting entry
❑
❑
❑
❑
❑
❑
None
into secondary
containment - HSC 6.7
25291(b
2060014
Correct leak detection
equipment installed for
RD
the type of system
❑
❑
❑
❑
[]
❑
None
❑
present - 23 CCR 16 2638;
Yes
HSC 6.7 25290.1, 25290.2,
25291
2060015
Sensor located in the
RD
proper position /location -
❑
❑
❑
None
❑
23 CCR 16 2630(d), 2641(a)
Yes
2030062
Facility is in compliance
RD
with not tampering with or
disabling leak detection
❑
❑
❑
❑
❑
❑
None
❑
devices or alarms - HSC
Yes
6.7 25299(a)(9)
2060022
System constructed with
a monitoring system
capable of detecting entry
❑
❑
❑
❑
❑
[j
None
into secondary
containment - HSC 6.7
25290.2(d)
2030034
Tag /sticker on affixed
monitoring equipment
being certified, repaired,
El
❑
❑
❑
❑
❑
None
or replaced - 23 CCR 16
2638(
VPH Monitoring VPH
2030065
Interstitial monitoring of
RD
the annular spaces of the
UST is properly
❑
❑
❑
❑
❑
❑
None
❑
maintained - HSC 6.7
Yes
25290.1(e
2060023
System constructed with
a monitoring system
capable of detecting entry
into secondary
❑
❑
❑
❑
❑
❑
None
containment - HSC 6.7
25290.1(d)
Underground Storage Tank Program - DW Inspection Report v 2.0
Violation
Program Requirement
SOC
Comments
No
D
CO
0
Z
0
Z
M
0
Ce
>
Line Leak Detector
2060012
Line leak detector
installed on pressurized
RD
piping system - HSC 6.7
None
❑
25290.1(h), 25290.2(g),
Yes
25291(1), 25292(e),
2636(f) (2)
2030026
Line leak detectors detect
a 3 gph leak and/or
RD
audible and visual alarm
None
[:1
function properly - 23
Yes
CCR 16 2636(0(6),
2666(c)
2030027
Turbine shuts down when
RD
a leak is detected or
when line leak detector is
❑
❑
❑
❑
None
❑
disconnected - 23 CCR 16
Yes
2666 c
2030025
Pressurized piping able to
detect a 3.0 gph leak
RD
within an hour, and
None
❑
restricts the flow or
Yes
alarms - 23 CCR 16
2636(0(2)
Secondary Containment
2060010
UST storing a hazardous
RD
substance has secondary
❑
❑
E:]
None
❑
containment - HSC 6.7
Yes
25292
Underground Storage Tank Program - DW Inspection Report v 2.0
Violation
Program Requirement
o
SOC
Comments
No
OO
¢
o
O
n~.
�o
z
O
z
M
V
Gj
2030008
UDC, sumps, and /or
other secondary
containment in good
❑
❑
❑
❑
❑
❑
None
condition and /or are free
of debris /liquid - HSC 6.7
25290.1, 25290.2, 25291
2030040
Secondarily contained
RD
piping maintained to allow
❑
❑
❑
❑
❑
❑
None
❑
liquid to drain into sump -
Yes
23 CCR 16 2630(d), 2641 a
2060006
Secondary containment
piping slopes back to the
❑
❑
❑
❑
❑
❑
None
collection sump - 23 CCR
16 263(c)
2030047
Secondary containment
maintained tight and has
been confirmed by testing
❑
❑
❑
❑
❑
F-1
None
- 23 CCR 16 2662; HSC 6.7
25290. 1 (c) (2), 25290.2(c) (2),
25291 (a), 2n92(e)
2030060
Entry fittings in secondary
containment for UST
system maintained
❑
❑
❑
❑
❑
❑
None
tight/sealed - 23 CCR 16
2630, 2635(d), 2636(c),
2666
2060020
Spill bucket is installed
RP
and has a functional drain
valve or other means to
❑
❑
❑
❑
❑
❑
None
❑
remove liquid - 23 CCR 16
Yes
2635(b), 2665
2030054
Spill bucket maintained in
RP
good condition and free of
❑
❑
❑
❑
E]
❑
None
❑
debris and /or liquid - 23
Yes
CCR 16 2635(b), 2715(c)(2)
2060019
Spill bucket to has a
minimum capacity of five
❑
❑
❑
❑
❑
❑
None
gallons - 23 CCR 16
2635(b), 2665
Overfill
2030035
UST system is operated
RP
to prevent unauthorized
release, including spills
❑
❑
❑
❑
❑
❑
None
❑
and overfills - HSC 6.7
Yes
25292.1 a
2030036
Overfill prevention system
RP
has not been overridden
and meets overfill
❑
❑
❑
❑
❑
❑
None
F]
requirements - 23 CCR 16
Yes
2635 b 2 , 2665
Underground Storage Tank Program - DW Inspection Report v 2.0
Violation
Program Requirement
4-
0 0
4)
SOC
Comments
No
0
0
0.
=
42 w
z
0
z
M
(.)
w
o>
On Site
Records
Certifications
2030023
Required designated
operators or contractors
maintain a proper and
None
current ICC certification -
23 CCR 16 2715
2030024
Service technician,
installer, and/ or
employee maintain a
None
proper license - 23 CCR
162715
2030031
Employee or contractor
obtained and maintained
proper manufacturer
None
certification - 23 CCR 16
2715
2010007
Submit/maintain current
Certificate of Financial
Responsibility /mechanism
of financial assurance -
El
❑
On
❑
❑
None
23 CCR 16 2711; 23 CCR
18 2808.1, 2809-2809.2,
HSC 6.7 25292.2; HSC
6.75 25299.30-25299.34
Designated Operator
2010004
Copies of DO inspections
for last 12 months and list
of trained employees
None
maintained - 23 CCR 16
2715
2030013
Designated operator
properly conducted the
monthly inspection and
None
the reports are complete -
23 CCR 16 2715
2030010
DO notified operator of
any condition observed
during the monthly
None
inspection that may
require action - 23 CCR 16
2715(d)
2030012
DO employee training
performed, current for at
least one employee on
El
None
site, and a log kept - 23
CCR 16 2715(c)(6), 2715(1)
Underground Storage Tank Program - DW Inspection Report v 2.0
Violation
Program Requirement
=
SOC
Comments
No
O
=
Q
o
O
a
42o
Z
o
z
M
c;>
Logs
2030001
Leak detection alarm
logs, maintenance and
RD
records of appropriate
❑
❑
❑
❑
❑
❑
None
❑
follow -up actions
Yes
maintained - 23 CCR 16
2632, 2634, 2712(b)
Maintenance /Tests
2010008
Monitoring, maintenance,
repairs, linings, and
RD
upgrade records
❑
❑
❑
❑
❑
❑
None
❑
maintained for the proper
Yes
time period - 23 CCR 16
2712(b)
Documentation
2030033
Failure to maintain on site
an approved monitoring
®
❑
❑
❑
❑
❑
None
plan - 23 CCR 16 2632,
2634, 2711, 2712(1)
2030037
Written agreement
between the tank owner
and tank operator to
monitor the tank system
®
❑
❑
❑
❑
❑
None
is maintained - 23 CCR 16
2620(b); HSC 6.7
25284 a (3)
2030061
Suspected or actual
RD
unauthorized release
reported in appropriate
❑
❑
❑
❑
❑
❑
None
❑
time frame - HSC 6.7
Yes
29294, 29295
General Operating Requirements
Permit Condition /Approval
2030039
Compliance with all
operating permit
❑
❑
❑
❑
❑
❑
None
conditions - 23 CCR 16
2712, HSC 6.7 25299
2030059
UST system maintained
in accordance with
exclusion /exemption
❑
❑
❑
❑
❑
F1
None
status - HSC 6.7 25281.6,
25283.5
2030014
Owner /Operator received
approval and has
implemented a training
❑
❑
❑
❑
❑
❑
None
program at an unstaffed
facility - 23 CCR 16
2715( 0(2)
Facility exhibited that the
2030015
method used to monitor
the tank meets the
monitoring methods in
❑
❑
❑
❑
❑
❑
None
2643(f) - 23 CCR 16 2643
Underground Storage Tank Program - DW Inspection Report v /_.v
Violation Program Requirement
.2 SOC Commen0 ts
No
a 0 0
a.
4)
z 0 rz :D 0 W
Red Tag
2030045 Red Tag information is
legible and has not been None
tampered with - 23 CCR
16 2717.1 (g)
2030044 Facility did not allow for
deposit of petroleum into
a UST that has a red tag ❑ ❑ ❑ ❑ None
affixed to the fill - 23 CCR
162717.1(0
Install/Repair
2060024 UST system is made of or
lined with materials that E] F] ❑ None
are compatible with the
substance stored - 23
CCR 16 2631.1
2060021 Striker plate installed and None
positioned correctly - 23
CCR 16 2631(c), 2662(d)
❑ There were no violations noted for this inspection.
❑This report shall serve as a "NOTICE TO COMPLY" for Minor Violations, and a "NOTICE OF VIOLATION" for
Major violations. You are, hereby, ordered to correct the above noted violations within 30 days, or according to
correction summaries provided. Formal enforcement and/or penalty assessment may be initiated for any
violations noted, and for those not corrected in a timely manner. (NOTE: If this is a preliminary report, a final report
will follow.)
Inspectors Signature: Date:
Inspector: Enter # of Violations: RD: RP:
Check one box for facility Significant Operational Status (SOC) to be reported to SWRCB and US EPA:
❑ SOC with both Release Detection and Release Detection (Facility has no Release Prevention and no Release
Prevention Violations)
❑ Not in SOC (Facility has both Release Prevention and Release Detection Violations)
❑SOC with Release Detection only (Facility has no Release Detection violations but one or more Release Prevention
violations)
❑ SOC with Release Prevention only (Facility has no Release Prevention violations but one or more Release Detection
violations)
Underground Storage Tank Program - DW Inspection Report v 2.0