HomeMy WebLinkAbout2015 REPORT FMCViolation Program Requirement 4- 0 C 0 .0 SOC Comments No O��. D a 0 0 1- 'M O)o 2 0 z D Testing 2030002 Owner/Operator has tested and certified leak 0 ❑ ❑ ❑ ❑ ❑ None detection equipment annually - 23 CCR 16 2638 2030048 Secondary containment testing conducted every 36 months in accordance None with requirements - 23 CCR 16 2637 2030055 Spill buckets have been tested annually as None required - HSC 6.7 25284.2 2010009 Secondary containment test results submitted to the CUPA within 30 days ❑ ❑ ❑ ❑ ❑ None after the test - 23 CCR 16 2637(e) 2030064 CUPA was poperly notified within the prescribed number of ❑ ❑ ❑ None hours prior to testing - 23 CCR 16 26370, 2638(e), 2643(g), 2644.1(a)(4) Install/Repair 2060009 Permits obtained to install, replace, repair, or ❑ E-1 ❑ None modify part of the UST system - 23 CCR 16 2712 UST System Observation General Monitoring 2030003 Leak detection system maintains continuous RD monitoring that activates 0 ❑ ❑ ❑ 1:1 ❑ None ❑ an audible and visual Yes alarm - 23 CCR 16 2632, 2634, 2636, 2666 2030016 The annular space of the tank, piping and sumps are continuously RD monitored and activates ❑ None ❑ the alarm - 23 CCR 16 Yes 2631(g), 2632(c)(2)(A)&(8), 2633(c), 2636(o 2030017 Product piping outside the UDC is fail-safe and shuts down the pump or None restricts flow - 23 CCR 16 2636(0(5) 2030018 Turbine sump monitor activates an audible and RD visual alarm or stops the ❑ ❑ ❑ ❑ ❑ None ❑ flow of at the dispenser - Yes 23 CCR 16 2636(0(1) 1 f I Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement o SOC Comments No z 0 O 42 W 0)75 z = o> 2030019 Monitoring system in the UDCs activates an audible and visual alarm ® ❑ ❑ ❑ ❑ ❑ None or stops the flow at the UDC -23 CCR 16 2636( (1) 2030043 Leak detection equipment properly programmed or RD properly operated - 23 ® ❑ ❑ ❑ ❑ ❑ None ❑ CCR 16 2632, 2634, 2636, Yes 2666 2060005 System constructed with a monitoring system capable of detecting entry ® ❑ ❑ ❑ ❑ ❑ None into secondary containment - HSC 6.7 25291(b) 2060014 Correct leak detection equipment installed for RD the type of system ® ❑ ❑ ❑ ❑ ❑ None ❑ present - 23 CCR 16 2638, Yes HSC 6.7 25290.1, 25290.2, 25291 2060015 Sensor located in the RD proper position /location - ® ❑ ❑ ❑ ❑ ❑ None ❑ 23 CCR 16 2630(d), 2641(a) Yes 2030062 Facility is in compliance with not tampering with or RD disabling leak detection ® ❑ ❑ ❑ ❑ ❑ None ❑ devices or alarms - HSC Yes 6.7 25299 (a) (9 2060022 System constructed with a monitoring system capable of detecting entry ® ❑ ❑ ❑ ❑ ❑ None into secondary containment - HSC 6.7 25290.2(d) 2030034 Tag /sticker on affixed monitoring equipment being certified, repaired, ® ❑ ❑ ❑ ❑ ❑ None or replaced - 23 CCR 16 2638( VPH Monitoring VPH 2030065 Interstitial monitoring of the annular spaces of the RD UST is properly ❑ ❑ 0 ❑ ❑ ❑ None ❑ maintained - HSC 6.7 Yes 25290.1(e) 2060023 System constructed with a monitoring system capable of detecting entry into secondary ❑ ❑ ® ❑ ❑ ❑ None containment - HSC 6.7 25290.1(d) Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement 4- 0 0.0 SOC Comments No In 0 9L 00 Z 0 Z M 05 13 Line Leak Detector 2060012 Line leak detector installed on pressurized RD piping system - HSC 6.7 ❑ FJ ❑ ❑ ❑ None ❑ 25290. 1 (h), 25290.2(g), Yes 252910, 25292(e), 2636(0(2) 2030026 Line leak detectors detect a 3 gph leak and/or RD audible and visual alarm E ❑ ❑ 1:1 ❑ El ❑ 0 n None ❑ function properly - 23 CCR 16 2636(0(6), Yes 2666(c) 2030027 Turbine shuts down when a leak is detected or RD when line leak detector is ❑ ❑ 2 ❑ ❑ ❑ None ❑ disconnected - 23 CCR 16 Yes 2666(c) 2030025 Pressurized piping able to detect a 3.0 gph leak RD within an hour, and ❑ ❑ ❑ ❑ ❑ None [:1 restricts the flow or Yes alarms - 23 CCR 16 2636(0(2) Secondary Containment 2060010 UST storing a hazardous RD substance has secondary None ❑ containment - HSC 6.7 Yes 25292 Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement W. 0 0.0 SOC Comments No a 0 m 42 �4W (a �o Z 0 Z :3 2030008 UDC, sumps, and/or other secondary containment in good E ❑ ❑ ❑ ❑ ❑ None condition and/or are free of debris/liquid - HSC 6.7 25290.1, 25290.2, 25291 2030040 Secondarily contained RD piping maintained to allow ❑ None ❑ liquid to drain into sump - Yes 23 CCR 16 2630(d), 2641(a 2060006 Secondary containment piping slopes back to the E ❑ None collection sump - 23 CCR 16 263(c) 2030047 Secondary containment maintained tight and has been confirmed by testing Z ❑ None - 23 CCR 16 2662; HSC 6.7 25290.1(c)(2), 25290.2(c)(2), 25291 (a), 25292(e) 2030060 Entry fittings in secondary containment for UST system maintained Z None tight/sealed - 23 CCR 16 2630, 2635(d), 2636(c), 2666 2060020 Spill bucket is installed and has a functional drain RP valve or other means to 1:1 1:1 ❑ ❑ ❑ None ❑ remove liquid - 23 CCR 16 Yes 2635(b), 2665 2030054 Spill bucket maintained in RP good condition and free of Z None ❑ debris and/or liquid - 23 Yes CCR 16 2635(b), 2715(c)(2) 2060019 Spill bucket to has a minimum capacity of five E El ❑ 1:1 F-1 F-1 None gallons - 23 CCR 16 2635(b), 2665 Overfill 2030035 UST system is operated to prevent unauthorized RP release, including spills ❑ ❑ F-1 None ❑ and overfills - HSC 6.7 Yes 25292.1 (a) 2030036 Overfill prevention system has not been overridden RP and meets overfill 2 ❑ ❑ 1:1 ❑ F-1 None F-1 requirements - 23 CCR 16 Yes 2635(b)(2)! 2665 Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement 4- 0 0.0 SOC Comments No z F— M C) (1) 0 a. 0 w 1- cc IM 0 0 z M U w On Site Records Certifications 2030023 Required designated operators or contractors maintain a proper and ❑ FIR ❑ ❑ None current ICC certification - 23 CCR 16 2715 2030024 Service technician, installer, and/ or employee maintain a ❑ ❑ None proper license - 23 CCR 162715 2030031 Employee or contractor obtained and maintained proper manufacturer None certification - 23 CCR 16 2715 2010007 Submit/maintain current Certificate of Financial Responsibility /mechanism of financial assurance - 1:1 1:1 ❑ ❑ None 23 CCR 16 2711; 23 CCR 18 2808.1, 2809-2809.2; HSC 6.7 25292.2; HSC 6.75 25299.30-25299.34 Designated Operator 2010004 Copies of DO inspections for last 12 months and list of trained employees None maintained - 23 CCR 16 2715 2030013 Designated operator properly conducted the monthly inspection and E ❑ ❑ 1:1 ❑ ❑ None the reports are complete - 23 CCR 16 2715 2030010 DO notified operator of any condition observed during the monthly ❑ ❑ ❑ None inspection that may require action - 23 CCR 16 2715(d) 2030012 DO employee training performed, current for at least one employee on None site, and a log kept - 23 CCR 16 2715(c)(6), 2715(o Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement 4- 0 0.0 SOC Comments No qct 0 0 (L 00 Z 0 Z Logs 2030001 Leak detection alarm logs, maintenance and RD records of appropriate Z ❑ ❑ ❑ ❑ ❑ None ❑ follow-up actions Yes maintained - 23 CCR 16 2632, 2634, 2712(b) Maintenance/Tests 2010008 Monitoring, maintenance, repairs, linings, and RD upgrade records 0 ❑ 1:1 ❑ ❑ ❑ None ❑ maintained for the proper Yes time period - 23 CCR 16 2712(b) Documentation 2030033 Failure to maintain on site an approved monitoring ❑ ❑ 1-1 ❑ None plan - 23 CCR 16 2632, 2634, 2711, 2712(1) 2030037 Written agreement between the tank owner and tank operator to monitor the tank system None is maintained - 23 CCR 16 2620(b); HSC 6.7 25284(8)(3) 2030061 Suspected or actual unauthorized release RD reported in appropriate None ❑ time frame - HSC 6.7 Yes 29294,29295 General Operating Requirements Permit Condition/Approval 2030039 Compliance with all operating permit None conditions - 23 CCR 16 2712, HSC 6.7 25299 2030059 UST system maintained in accordance with exclusion/exemption None status - HSC 6.7 25281.6, 25283.5 2030014 Owner/Operator received approval and has implemented a training None program at an unstaffed facility - 23 CCR 16 2715(f)(2) 2030015 Facility exhibited that the method used to monitor the tank meets the monitoring methods in None 2643(f - 23 CCR 16 2643 Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement o SOC Comments No Uj :3 d 0 O a CDo z O z M V W of Red Tag 2030045 Red Tag information is legible and has not been ❑ ❑ ® ❑ ❑ ❑ None tampered with - 23 CCR 16 2717.1(g) 2030044 Facility did not allow for deposit of petroleum into a UST that has a red tag ❑ ❑ ® ❑ ❑ ❑ None affixed to the fi I I - 23 CCR 16 2717.1 Install /Repair 2060024 UST system is made of or lined with materials that are compatible with the ® ❑ ❑ ❑ ❑ ❑ None substance stored - 23 CCR 16 2631.1 2060021 Striker plate installed and positioned correctly - 23 ® ❑ ❑ ❑ ❑ ❑ None CCR 16 2631(c), 2662 d ® There were no violations noted for this inspection. ❑This report shall serve as a "NOTICE TO COMPLY" for Minor Violations, and a "NOTICE OF VIOLATION" for Major violations. You are, hereby, ordered to correct the above noted violations within 30 days, or according to correction summaries provided. Formal enforcement and /or penalty assessment may be initiated for any violations noted, and for those not corrected in a timely manner. (NOTE: If this is a preliminary report, a final report will follow.) Inspectors Signature:f� Date: l s Inspector: Enter # of Violations: RD: RP: Check one box for facility Significant Operational Status (SOC) to be reported to SWRCB and US EPA: HOC with both Release Detection and Release Detection (Facility has no Release Prevention and no Release Prevention Violations) ❑ Not in SOC (Facility has both Release Prevention and Release Detection Violations) ❑SOC with Release Detection only (Facility has no Release Detection violations but one or more Release Prevention violations) ❑ SOC with Release Prevention only (Facility has no Release Prevention violations but one or more Release Detection violations) Underground Storage Tank Program - DVS Inspection Report v 2.0