MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State of California
Authority Cited. Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations
This form must be used to document testing and servicing of monitoring equipment. A s_parate certification or Mort must be prepared for each j
monitoring stem control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner /operator.
The owner /operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date.
A. General Information
Facility Name: LUCKY 7 FOOD STORE
Site Address: 2501 WHITE LN. City: BAKERSFIELD
Facility Contact Person: ' MANJIT SINGH
Make/Model of Monitoring System: TLS -350 INSP. - ERNIE MADINA
B. Inventory of Equipment Tested/Certified
Bldg. No.:
Zip: 93304
Contact Phone No.: ( )
Date of Testing/Servicing: 2/26/2015
% -nccji twit S rV s-It
Tank ID: MID GRADE 89
.Tank ID: REG87
• In -Tank Gauging Probe.
Model: MAG
® In -Tank Gauging Probe.
Model: LIAG
• Annular Space or Vault Sensor.
® Piping Sump / Trench Sensor(s).
❑ Fill Sump Sensor(s).
® Mechanical Line Leak Detector.
Model: 409
Model: 208
Model:
Model: FX1 V
Annular Space or Vault Sensor.
® Piping Sump / Trench Sensor(s).
❑ Fill Sump Sensor(s).
® Mechanical Line Leak Detector.
Model: 409
Model: 208
Model:
Model: FE -PETRO
El Electronic Line Leak Detector.
Model:
❑ Electronic Line Leak Detector_
Model:
❑ Tank Overfill / High -Level Sensor. Model:
❑ Other (specify equipment type and model in Section E, on Page 2).
❑ Tank Overfill / High -Level Sensor. Model:
❑ Other (specify equipment type and model in Section E on Page 2).
Tank ID: PREM91
Tank ID:
• in -Tank Gauging Probe.
Model: MAG
❑ In-Tank Gauging Probe.
Model:
• Annular Space or Vault Sensor. Model: 409
® Piping Sump / Trench Sensor(s). Model: 208
❑ Fill Sump Sensor(s). Model:
® Mechanical Line Leak Detector. Model: FX1V
❑ Electronic Line Leak Detector. Model:
❑ Tank Overfill / High -Level Sensor. Model:
❑ Other (specify equipment type and model in Section E on Page 2).
❑ Annular Space or Vault Sensor. Model:
❑ Piping Sump / Trench Sensor(s). Model:
❑ Fill Sump Sensor(s). Model:
❑ Mechanical Line Leak Detector. Model:
❑ Electronic Line Leak Detector. Model:
❑ Tank Overfill / High -Level Sensor. Model:
❑ Other (specify equipment type and model in Section E on Page 2).
Dispenser ID: 112
® Dispenser Containment Sensor(s). Model: 406
19 Shear Valve(s).
❑ Dispenser Containment Float(s) and Chain(s).
Dispenser ID: 314
® Dispenser Containment Sensor(s). Model: 406
® Shear Valve(s).
❑ Dispenser Containment Float(s) and Chain(s).
Dispenser ID:
❑ Dispenser Containment Sensor(s). Model:
❑ Shear Valve(s).
❑ Dispenser Containment FIoat(s) and Chain(s).
Dispenser ID:
❑ Dispenser Containment Sensor(s). Model:
❑ Shear Valve(s).
❑ Dispenser Containment Float(s) and Chain(s).
Dispenser ID:
❑ Dispenser Containment Sensor(s). Model:
❑ Shear Valve(s).
❑ Dispenser Containment Float(s) and Chain(s).
Dispenser ID:
❑ Dispenser Containment Sensor(s). Model:
❑ Shear Valve(s).
❑ Dispenser Containment Float(s) and Chain(s).
*If the facility contains more tanu or dispensers, copy uus corm. j- uciuue uummautul tvx vv jLy Lau z. MA.& 41Jk,V13JV1 µv s ......__ J.
C. Certification - I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers'
guidelines. Attached to this Certification is information (e.g. manufacturers' checklists) necessary to verify that this information is
correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also
attached a copy of the report; (check all that apply): ® System set -up ® Alarm history report
Technician Name (print): RICHARD MASON Signature:
Certification No.: 5297857 -UT 1 B36880 License. No.: C611 D40 A 809850
Testing Company Name: RICH ENVIRONMENTAL Phone No.: (661) 392 -8687
Testing Company Address: 5643 BROOKS CT. BAKERSFIELD, CA 93308 Date of Testing/Servicing: 2126115
Page 1 of 5
UN-036 —1/4 www.unidocsorg Rev. 01/17/08
Monitoring System Certification
I A Results of Testing/Servicing
Software Version Installed: 323.03
f mmnititp the fnllnwino rhp►rklict!
® Yes
❑ No*
Is the audible alarm operational?
® Yes
❑ No*
Is the visual alarm operational?
® Yes
❑ No*
Were all sensors visually inspected, functionally tested, and confirmed operational?
® Yes
❑ No*
Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will
not interfere with their proper operation?
' ❑ Yes
❑ No*
If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem)
® N/A
operational?
® Yes
❑ No*
For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
❑ N/A
monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate
positive shut-down? (Check all that apply) ® Sump /Trench Sensors; ❑ Dispenser Containment Sensors.
Did you confirm positive shut -down due to leaks and sensor failure /disconnection? ® Yes; ❑ No.
❑ Yes
❑ No*
For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no
® NIA
mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank
fill point(s) and operating properly? If so, at what percent of tank capacity does the alarm trigger? %
❑ Yes*
® No
Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced
and list the manufacturer name and model for all replacement parts in Section E, below.
❑ Yes*
10 No
Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply)
❑ Product; ❑ Water. If yes, describe causes in Section E, below.
Yes
❑ No*
Was monitoring system setup reviewed to ensure proper settings? Attach set up reports, if applicable
® Yes
❑ No*
Is all monitoring equipment operational per manufacturer's specifications?
* In Section E below, describe how and when these deficiencies were or will be corrected.
E. Comments:
Page 2 of 5
UN -036 — 2/4 www.unidocs.org Rev. 01 /17/08
Monitoring System Certification
F. In -Tank Gauging / SIR Equipment:
{0Zt0'J
ED Check this box if tank gauging is used only for inventory control.
❑ Check this box if no tank gauging or SIR equipment is installed.
This section must be completed if in -tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
❑ Yes
❑ No*
Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
❑ Yes
❑ No*
Were all tank gauging probes visually inspected for damage and residue buildup?
® Yes
❑ No*
Was accuracy of system product level readings tested?
❑ Yes
❑ No*
Was accuracy of system water level readings tested?
❑ Yes
❑ No*
Were all probes reinstalled properly?
Q Yes
❑ No*
Were all items on the equipment manufacturer's maintenance checklist completed?
* In Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD):
❑ Check this box if LLDs are not installed.
VR/.ii AVW
® Yes
W- fVYV..
❑ No*
a..
For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance.
N/A
(Check all that apply) Simulated leak rate: ® 3 g.p.h.; [10. 1 g.p.h ; ❑ 0.2 g.p.h.
® Yes
❑ No*
Were all LLDs confirmed operational and accurate within regulatory requirements?
® Yes
❑ No*
Was the testing apparatus properly calibrated?
® Yes
❑ No*
For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
❑ N/A
❑ Yes
❑ No*
For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak?
® N/A
❑ Yes
❑ No*
For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled
® N/A
or disconnected?
❑ Yes
❑ No*
For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions
® N/A
or fails a test?
❑ Yes
❑ No*
For electronic LLDs, have all accessible wiring connections been visually inspected?
® N/A
® Yes
❑ No*
Were all items on the equipment manufacturer's maintenance checklist completed?
* In Section H, below, describe how and when these deficiencies were or will be corrected.
H. Comments:
UN -036 — 3/4
Page 3 of 5
www.unidoes.org
Rev. 01/17/08
"7LD6
"o 0
Let wd m �di 6 B s
c id :it..,! ta tdr-lbaw pag -W Y, it A�
i 0.1
Y
VC 4 .0
km 01 'U.I.g
IA
Alt%shi
glebe
spa, spl'
Y, ar
lt. -.,;.
Im. Pan., In. AJ by.
t" ,
MO
INSW M. V. an
"
Wo b MA sl used
tic- W6� 1
RICA ENVIRfINMENTAL
3305 BRITTAN ST. BAKERSFIELD, CA. 93308
OFFICE (661)326 -8402 FAX (661)326 -8934
PRODUCT LINE LEAK DETECTOR TEST
WORK SHEET
W /0 #:
FACILITY NAMIE: LUCKY 7 FOOD STORE
FACILITY ADDRESS: 2501 WHITE LANE, BAKERSFIELD
PRODUCT LINE TYPE: PRESSURE
)oDwl�l
PRODUCT
LEAK DETECTOR TYPE
TEST
TRIP
PASS
BELOW
P.S.I.
OR
SERIAL NUMBER
3 G.P.H.
FAIL
UNL87
L/D TYPE: FXIV
YES
11
PASS
SERIAL # 6251
NM89
L/D TYPE: FE -PETRO
YES
10
PASS
SERIAL # UNREADABLE
PREM91
L/D TYPE: FX1V
YES
10
PASS
SERIAL # 9 787__
L/D TYPE:
PASS
YES
SERIAL #
FAIL
I CERTIFY THE ABOVE TESTS WERE CONDUCTED ON THIS DATE ACCORDING TO RED
JACKET PUMPS FIELD TEST APPARATUS TESTING PROCEDURE AND LIMITATIONS.
THE MECHANICAL LEAK DETECTOR TEST PASS / FAIL IS DETERMINED BY USING A
LOW FLOW THRESHOLD TRIP RATE OF 3 GALLONS PER HOUR OR LESS AT 10 P.S.I. I
ACKNOWLEDGE THAT ALL DATA COLLECTED IS TRUE AND CORRECT TO THE BEST
OF MY KNOWLEDGE.
TECHNICIAN: RICHARD MASON
SIGNATURE: `� DATE: 2/26/15
scan'
SWRCB, January 2006
Spill Bucket Testing Report Form
This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and
printouts from tests (f applicable), should be provided to the facility owner /operator for submittal to the local regulatory agency.
I T A rTT .T'i'V TNW0RMAT10N
Facility Name: LUCKY 7 FOOD STORE
Date of Testing: 2/26/15
Facility Address: 2501 WHITE LN. BAKERSFIELD .
Facility Contact. MANJIT SINGH
Phone:
Date Local Agency Was Notified of Testing: 1/13/15 i
Name of Local Agency Inspector (af present during testing): _ _ _ . ......... .
It WUQrrnvr rn vrru A PTnV INTnuMATION
Company Name: RICH ENVIRONMENTAL
Technician Conducting Test: RICHARD MASON
Credentials': ❑ CSLB Contractor X ICC Service Tech. ❑ SWRCB Tank Tester ❑ Other (Spec)
License Number(s): 5297857 -UT
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: X Hydrostatic
❑ Vacuum ❑ Other
Test Equipment Used: VISUAL
Equipment Resolution: 0
2 PREM91 FILL
3 NM89 FILL
4
Identify Spill Bucket (By Tank
LNumber, Stored Product, etc.
1 REG87 FILL
Bucket Installation Type:
X Direct Bury
❑ Contained in Sump
X Direct Bury
❑ Contained in Sump
X Direct Bury
❑ Contained in §ump
El Direct Bury
❑ Contained in Sum
Bucket Diameter:
12"
12"
12"
Bucket Depth:
14"
14"
14'
Wait time between applying
vacuum/water and start of test:
30MIN
30NIIN
30MIN
Test Start Time (T):
9:30
9:30
9:30
Initial Reading (R):
IT,
ITI
12"
Test End Time (TF):
10:30
10:30
10:30
Final Reading (RF):
12"
12"
1T'
Test Duration (TF — Tz):
60MIN
60MiN
60NEN
Change in Reading (RF - R):
0
0
0
Pass/Fail Threshold or 0 0 0
Criteria:
Comments — (include information on repairs made prior to testing, and recommended follow -up for failed tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements.
Technician's Signature: Date: 2/26/15
' State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
LEAK MIN PERIODIC:
o
LEAK MIN ANNUAL 0/0
0
PERIODIC TEST TYPE
STANDARD
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY 15 MIN
PUMP THRESHOLD 10-00%
LEAK TEST METHOD
-TEST ON'DATE ALL TANK
JAW 1.- 1996
.-START TIME ' DISABLED
TEST RATE 0.20 GAL/HR
DURATION, 2 HOURS
TST EARLY STOP:DISABLED
LEAK ,TEST REPORT NO FORMAT
RMAL
LIQUID SENSOR•SETUP
- - - - - - - - - - - - -
L 1:87 STP
TRI-STATE (SINGLE FLOAT)
CATEGORY : STP SUMP
L 2:89-STP
TRI-STATE (SINGLE FLOAT)
CATEGORY : STP-SUMP
L 3:91 -STP.
TRI-STATE (SINGLE FLOAT)
CATEGORY : STP SUMP
L 4:87-ANNULAR I
TRI-STATE (SINGLE FLOAT)
CATEGORY .: ANNULAR SPACE
L,5:91-ANNULAR
TRI-STATE (SINGLE FLOAT)
CATEGORY : ANNULAR SPACE
L 6:89-ANNULAR
TRI-STATE (SINGLE FLOAT)'
CATEGORY : ANNULAR SPACE
MUSIC
OUTPUT RELAY SETUP
- - - - - - - - - - - -
R 1:07 SHUTOFF*
TYPE:
STANDARD
NORMALLY CLOSED
LIQUID SENSOR ALMS
ALL:FUEL ALARM
ALL:SENSOR OUT ALARM
ALL:SHORT ALARM
R 2:91 SHUTOFF
TYPE:
STANDARD
NORMALLY CLOSED
LIQUID SENSOR ALMS
ALL:FUEL ALARM
ALL:SENSOR OUT ALARM
ALL:SHORT ALARM
R 3:89 SHUTOFF
TYPE:
. STANDARD
NORMALLY CLOSED
LIQUID SENSOR ALMS
ALL:FUEL ALARM
ALL:SENSOR OUT ALARM
ALL:SHORT ALARM
RECONCILIATION SETUP
- - - - - - - - - - - -
AUTOMATIC DAILY CLOSING
TIME: 2:00 AM
PERIODIC RECONCILIATION
MODE: MONTHLY
TEMP COMPENSATION
STANDARD
BUS SLOT FUEL METER.TANK
- - - - - - -- - - - - -
TANK MAP EMPTY
COMMUNICATIONS SETUP
PORT SETTINGS:
.:NONE FOUND
RS-232 END OF MESSAGE
DISABLED
I N7TANK SET UP
T I:UNLEADED 87
PRODUCT CODE,
THERMAL COEFF :.000070
TANK DIAMETER 96-00
TANK PROFILE I PT
FULL VOL 10080
FLOAT. SIZE: 4.0
IN.
WATER WARN I NG
2.0
3.0
H16H -W LIMIT
OR '. LABEL VOL: 10000
OV8RF I'LL LIMIT
/o
9000
Hl-GH' PRODUCT
9500
DELIVERY LIMIT
10%
1000
Low PRODUCT
500
99
LEAK' ALA p M LIMIT'
SUDDEN LOSS LIMIT:
99
TANK -TILT.
4.00
—1.00
p.ROBE OFFSET
SIPHON MANIFOLDED TANKS
'NONE
LINE MANIFOLDED TANKS
T4 NONE
LEAK MIN PERIODIC:
0/0 0
LEAK MIN ANNUAL
0
PERIODIC TEST TYPE
STANDARD
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST.FAIL i
ALARM DISABLED
GROSS TEST FAIL
.. ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK.:OFF
DELIVERY DELAY : 15 MIN
PUMP THRESHOLD : 10-00%
T 2:SUPER 91
PRODUCT CODE 2
THERMAL COEFF :.000070
TANK DIAMETER 96.00
TANK PROFILE 1 PT
FULL VOL 10000:
FLOAT SIZE: 4.0 IN.
WATER WARNING 2.0
HIGH WATER LIMIT: '3.0
MAX OR LABEL VOL: 10000
OVERFILL LIMIT 90%
• 9000
HIGH PRODUCT 95%
• 9500
DELIVERY LIMIT 10y
1000
LOW PRODUCT 500
LEAK ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 99
TANK TILT 3.10
PROBE OFFSET 0.00
SIPHON MANIFOLDED TANKS
TO: NONE
LINE MANIFOLDED TANKS
TO: NONE
LEAK MIN PERIODIC: 014
0
LEAK MIN ANNUAL 00/0
0
toollot)
PERIODIC TEST TYPE
STANDARI
ANNUAL TEST FAIL
ALARM DISABLEI
PERIODIC TEST FAIL
ALARM DISABLE
GROSS TEST FAIL
ALARM DISABLE]
ANN TEST AVERAGING: OF)
PER TEST AVERAGING: OF)
TANK TEST NOTIFY, OF]
TNK TST SIPHON BREAK:OFl
DELIVERY DELAY : 15 Mll
PUMP THRESHOLD : 10-00. I
T 3:SPECIAL 89
PRODUCT CODE
THERMAL COEFF :.0000'e
TANK DIAMETER
TANK PROFILE
FULL VOL 1001
FLOAT SIZE: 4.0 It
WATER WARNING 2
HIGH WATER LIMIT: 3
MAX OR LABEL VOL: 1001
OVERFILL LIMIT 91
901
HIGH PRODUCT 91
95
DELIVERY LIMIT I
10
LOW PRODUCT 5
LEAK ALARM LIMIT:
SUDDEN LOSS LIMIT:
TANK TILT 4.
PROBE OFFSET 0.
SIPHON MANIFOLDED TANK
TO: NONE
LINE MANIFOLDED TANKS
TO: NONE
•- •-�' �.e^•_'!1!F!-'^RG+A!;L„+ti..w.
ALARM HISTORY REPi�RT
.-. s:- r s.+, s'- +' ` E,'." y- ..'+'s"",...,'""�w.•�r".•r"+k
ALARM HISTORY REPORT .
r��r�'
__ - -_ SENSOR ALARM - - - -- E
----- SENSOR ALARM ------
L 1:87 STP
L 4:87— ANNULAR
- _ _........_... _ _ ........... ....... __ ......__
STP SUMP
ANNULAR SPACE
SENSOR OUT ALARM
SENSOR OUT ALARM
FEB 26, 2015 10:44 AM
FEB 26, 2015 10:44 AM
FUEL ALARM
FUEL ALARM
FEB 26, 2015 10:31 AM
FEB 26. 2015 10:33 AM
SENSOR OUT-ALARM
SENSOR OUT ALARM
SYSTEM SETUP
JAN 15. 2014 1:40 PM
MAR 2, 2014 9:01 PM
— — — — — — — — — — — —
FEB 26x 2015 9:15 AM
t
t
SYSTEM UNITS
'
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH : MM : SS xM
END �e
ae.�e END€
LUCKY 7
25011 WHITE Lid
BAKERSFIELD CA 93304
661- 397 -3722
SHIFT TIME 1 : DISABLED
} SHIFT TIME 2 : DISABLED
6 SHIFT TIME 3;: DISABLED
�
t
E SHIFT TIME 4 : DISABLED
i
TANK PER TST NEEDED WRN
!
ALARM HISTORY! REPORT
ALARM HISTORY REPORT
DISABLED
TANK ANN TST NEEDED WRN
- -- -- SENSOR ALARM - - -T—
- - -;— SENSOR'ALARM - -_ --
DISABLED
L 2 :89 —STP
L.5.91— ANNULAR
•..STP.SUMP
ANNULAR SPACE
LINE RE— ENABLE METHOD
•
SENSOR OUT ALARM
.SENSOR OUT ALARM r..
PASS LINE TEST
.
FEB 26, 2015 10:44 AM
FEB 26r 2015 10:44 AM
LINE PER TST NEEDED WRN
FUEL ALARM
FUEL ALARM
DISABLED
• FEB 26, 2G15.10:28 AM
FEB 26. 2015 10:34 AM
LINE ANN TST NEEDED WRN
,
DISABLED
. ...- �:.�_.,,.�,;�...::_.u::.
SETUP DtTi WRNI
SE:NS€�R�t�UT• ��ARM "
JAN 15, 2014 1:40 FM
z
PRINT TO VOLUMES
JUN 9, 2014 ' ,9:17 AM
ENABLED
E
` TEMP COMPENSATION
i
VALUE (DEG F 60.0
STICK HEIGHT OFFSET
DISABLED
DAYLIGHT SAKI I NG TIME
DISABLED
END �€ �€
END
SYSTEM SECURITY
CODE : 000000
- ,
CUSTOM ALARM LABELS
'
DISABLED
SOFTWARE REVISION LEVEL
VERSION 323.03
SOFTWARE# 346323 -100 =D
CREATED — 03.08.06.08.10
ALARM HISTORY REPORT
ALARM HISTORY REPORT
NO SOFTWARE MODULE
SYSTEM FEATURES:
_ S
-- — '— Etd�OR ALARM - - - --
- - - -- SENSOR ALARM - - - --
PERIODIC IN —TANK TESTS
L 3:91 —STP'
L 6:89— ANNULAR
ANNUAL IN —TANK TESTS
STP SUMP
ANNULAR SPADE
SENSOR OUT ALARM
SENSOR -OUT ALARM
.FEB 26r - 2015.10:44 AM
FEB 26, 2016 10:44 AM
FUEL ALARM -
FUEL ALARM
FEET 26. 2015 10:30 AM
FEB 26� 2015 10:35 AM
SENSOR OUT ALARM
SENSOR OUT ALARM
,TAN 15, 2014 1:40 PM i
FEB '. 2014 8:31 PM
(407P3
MONITOR CERT. FAILURE REPORT
SITE NAME: LUCKY 7 FOOD STORE DATE : 2/26/15
ADDRESS: 2501 WHITE LANE TECHNICIAN : RICHARD MASON
THE FOLLOWING COMPONENTS WERE REPLACED/REPAIRED TO COMPLETE
TESTING.
REPAIRS: NONE
LABOR: NONE
PARTS INSTALLED: NONE
NAME: TITLE:
SIGNATURE:
THE ABOVE NAMED PERSON TAKES FULL RESPONSIBILITY OF NOTIFYING
THE APPROPRIATE PARTY TO HAVE CORRECTIVE ACTION TAKEN TO REPAIR
THE ABOVE LISTED PROBLEMS AND NOTIFYING RICH ENVIRONMANTAL FOR
ANY NEEDED RETESTING. THIS ALSO RELEASES RICH ENVIRONMENTAL OF
ANY FINES OR PENALTIES OCCURING FROM NON - COMPLIANCE.
A COPY OF THIS DOCUMENT HAS BEEN LEFT ON -SITE FOR YOUR
CONVIENENCE.