HomeMy WebLinkAbout2013 FMC RESULTS'TAIT
!--:7 141560!8222 �iv, yi, i -.o ryi
December 19, 2013
VIA FED EX 7721 5773 8378
Bakersfield Fire Department
2101 H Street
Bakersfield CA 93301
Re: Product Line Testing
Monitoring System Certification
Spill Bucket Testing
Pacific Bell Telephone Co. dba AT&T California
1918 I'M" STREET, BAKERSFIELD, CA
GEOPAR: SA004
To Whom It May Concern:
Enclosed are the results for the following tests completed on December 2, 2014:
■ Product Line Testing Report Form
■ Monitoring System Certification Report Form
■ Spill Bucket Testing Report Form
Please do not hesitate to call me if you have any questions.
Very Truly Yours,
�aalrlos E. Cardenas
Program Manager
CA ::ic MO98 AZ 095984 11: NV hc;; 0049666 1 TX CU000041
DATA CHART FOR USE WITH PETRO TITS LINE TESTER
Job Number: ATTPL14 Date of Test: 12/02/2014
LOCATION: 1918 M STREET BAKERSFIELD CA.
OWNER:
OPERATOR:
REASON FOR TEST:
TEST REQUESTED BY:
Street No. city State Telephone No.
Pacific Bell Telephone Company dba AT&T California
Name Address Representative Position Telephone No.
Grant Armstrong Environmental Site Manager 661-327-6903
Name Dealer, Mgr. Or Other Address (if different than location) Telephone No.
Annual Compliance
Shane Gardner Bakersfield Fire Dept.
Name Position
SPECIAL IMIKULAIUNZ:
TECHNICIAN: Patrick Banbury
,-4
Name
IS A TANK TEST TO BE MADE WITH THIS LINE TEST?
MAKE AND TYPE OF PUMP OR DISPENSERS
WEATHER Overcast
COVER OVER LINES Concrete I Black Top
Order No.
Signature
❑ Yes [D No
FE- PETRO TURBINE
Billing Address
90-1413
License Number
TEMPERATURE IN TANKS OF Oc
APPROX. BURIAL DEPTH 24"
Concrete, Black Top, Etc.
PRESSURE VOLUME
EACH LINE TIME PSI READING TEST RESULTS
AS TESTED MILITARY) BEFORE AFTER BEFORE AFTER NET CHANGE CONCLUSIONS
DIESEL
1045
START
80
+.0000 G.P.H.
Line Tight E YES ❑ NO
Bleed Back 0 OK
❑ NOT OK
SA0040001
1115
STABILIZATION
80
60
1145
START TEST
60
60
1200
60
60
.0570
.0570
+.0000
1215
60
60
.0570
.0570
+.0000
1216
BLEED BACK
60
0
.0570
.0910
+.0340
BLEED BACK
START TEST
BLEED BACK
BLEED BACK
START TEST
BLEED BACK
COMMENTS: Local CUPA on site Shane Gardner. 1.5" Western Fiberglass Flex Line.
G.P.H.
Line Tight F-1 YES ❑ NO
Bleed Back r-1 OK
F-1 NOT OK
G.P.H.
Line Tight F-1 YES F-1 NO
Bleed Back F-1 OK
❑ NOT OK
Appendix VI
(Copies of Monitoring System Certification form and UST Monitoring Plot Plan available at http: / /w•ww.waterboards.ca.gov .)
MONITORING SYSTEM CERTIFICATION
For Use By,411 Jurisdictions Within the State of California
Authority Cited. Chapter 6.7, Health andSafety Code; Chapter 16, Division 3, Title 23, California Code ofRegulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each
monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner /operator
owner /operator must submit a copy ofthis form to the local agency regulating UST systems within 30 days of test date.
A. General Information
Facility Name: Pacific Bell Telephone Co. dba AT &T California Building No.: SA004
Site Address: 1918 M STREET City: Bakersfield Zip: 93301
The
Facility Contact Person: Grant Armstrong Contact Phone No.: (661) 327 -6903
Make/Model of Monitoring System: Veeder Root TLS -350 Plus Date of Testing/Servicing: 12/2/2014
B. Inventory of Equipment Tested /Certified
Check the appropriate boxes to indicate specific equipment inspected /serviced:
Tank ID: SA004U001�� _�_,.w,_,_._,.,•...,.,. -..� ,...�� .w.,.w..�...�.....M,...�... Tank ID.
In -Tank Gauging Probe. Model: 846390 - 109/729482 In -Tank Gauging Probe. Model:
794390-420/N/A
kk Annular Space or Vault Sensor. Model: F Annular Space or Vault Sensor. Model:
')v 794380- 208/729482 Piping Sum / Trench Sensors . Model:
Piping Sump/ Sensor(s). Model: p g p ()
Fill Sump Sensor(s). Model: 794380- 208/797241 Fill Sump Sensor(s). Model:
} F Mechanical Line Leak Detector. Model: Mechanical Line Leak Detector. Model:
j F Electronic Line Leak Detector. Model: F Electronic Line Leak Detector. Model:
'. Tank Overfill / High -Level Sensor. Model: 790091 -001 r Tank Overfill / High -Level Sensor. Model: €
Other (specify equipment type and model in Section on Page 2). F Other (specify equipment type and model in Section on Page 2).
:°aXSU.azo:.•n;,x �xx::rx„- .a.:x- ;.,-: s::: �tts�x: �a» ax��uaraaax :✓••�"x:•a. >: >kz: ^,:::nm�: x:a;.•:x;;.�;xmra �z. ra�v;. vzacuwc�ww» ax> e, 7:.: ::r.„,;,:ws:r;.a- x;^,:wxcrrxs� wcx;c �' '�,s�e. ° Y. h.";'" 5¢% �;. a" a', ?X�"���`Fc�&zika�`"F✓4t,,xgmr,„ �' .. ... .... ..
Tank ID: Tank ID.
In -Tank Gauging Probe. Model: In -Tank Gauging Probe. Model:
Annular Space or Vault Sensor. Model: Annular Space or Vault Sensor. Model:
Piping Sump/ Trench Sensor(s). Model: Piping Sump/ Trench Sensor(s). Model:
Fill Sump Sensor(s). Model: r Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector. Model: F Mechanical Line Leak Detector. Model:
F Electronic Line Leak Detector. Model: F Electronic Line Leak Detector. Model:
F Tank Overfill / High -Level Sensor. Model: Tank Overfill / High -Level Sensor. Model:
j Other (specify equipment type and model in Section E on Page 2). Other (specify equipment type and model in Section on Page 2).
Dispenser ID:� Dispenser ID:
Dispenser Containment Sensor(s). Model: r Dispenser Containment Sensor(s). Model:
Shear Valve(s). Shear Valve(s).
k
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
� Dispenser ID' Dispenser ID:
Dispenser Containment Sensor(s). Model: _� Dispenser Containment Sensor(s). Model:
i
Valve(s).
Shear Valve(s). �� Shear e( s )• {
� k
j Dispenser Containment Float(s) and Chain(s). F Dispenser Containment Float(s) and Chain(s).
*If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification - I certify that the equipment identified in this document was inspected /serviced in accordance with the manufacturers'
guidelines. Attached to this Certification is information (e.g. manufacturers' checklists) necessary to verify that this information is correct and
a Plot Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also attached a copy of
the report; (check all that apply) : System set -up Alarm history report
Technician Name (print): Pat Banbury
Signature:
Certification No.: A20465 License. No.: 588098
Testing Company Name: TAIT ENVIRONMENTAL SERVICES Phone No.: 714560 -8222
Testing Company Address: 2131 soUTHDUPON U;UV y Ar1A1MM,CA92806 Date of Testing/Servicing: 12/2/2014
D. Results of Testing /Servicing
Software Version Installed: 123.01
Complete the following checklist:
,�..,�.�...�.,. ..�.. � ..... _.,... �.w MM,_wM � � p..__ __ww,.__._ w_ w.. ------
Yes No* Its the audible alarm operational?
�ys��'..,, GF' �K�. i3.. s``.'. r` z.'."` w3,' a'' w`'=.'"' n' a'':". r� "`m.�"a'S��'x�a'x"a�4``�"�i:'�. `..Y�"Y'�.'.�`?a' �xs'.v t. � .?`ks.�uu'"`i'$s�.c�%'���«.�`3' `•6,v�
Yes N o *. ,= Is the visual alarm operational?
v `-' ; Were all sensors visually inspected, functionally tested, an conrme operational?
€�. � Yes s� No * W i f i ll d d fi d ,,
f.- M�..��- ��,,_._,,...,.. � �.r��____ m��_:�.�.. �..�N..�_...�.���.�mmw..� _�- �w.��..�:;�w:� w�mm���µ :�.�:�,.�:,�,�•,.....�..� . ���. �,. �. ���� ..�.�.�m,.:m�,:m.�..�r��w��mm.m �.�.��
€ fF Yes F No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment
will not interfere with theirs
proper operation?
��u` x`. z` k? 8:;,' sswa�s.`.' s.<; e.: 3s' fii°•' QP's A.'.8.`.`�s..E.k�.'P<'%,P,m..�' .`,.�,":?az<s:�..;c."aY.'z;:>& .-; sCw^.'.''"? 3,' a`: a...` r, d?.., k2': t. c: o. aiz"" s' iaa'`."., aa' 7s3" 3: i.`. y2:: a�n ;�us't::;`x�.'za>5'"�Snat''r,. yr4"..0 >srr.: - .:$STr.<. .","Ii.h^.:'E3 �q
* Yes No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem)
t
N/A ` =operational.
s �y ... ... .... .. ..y, :,_b. 'T' ak.'S ]S# ... , .. , .; ..� ,. .,+.wd.: `'Er. .mu <. ¢'Y •tJ.• y;. ,>� ,:Yw -y ..+,., �y,y ...SY ` �.`�$�. '�``^.:' '(a.. ,Z..wt� =ir:�.�r:(��R:. ..`=?.3kkk'::;'.�p1
'�.;..�5'.R3".�..eLk".i ..aw.='c.�.�b'zx,.?c`"x: �.. �%,,.: 3% a... �.. P£ O..>??> ��e"'.. K�%. v.°,< �3. �` �C���:, ffi` ��e,'.. �.' �a° �2" a` a�`'" r35,<> �. r�: a.<.".., 9...,... .:rsk�..n�.�iO'C.°..�ea"�.�.'�. ". ��s��y a�. �.`.»$ �.' �s�e�,> s.` y',". �'° �"°. A. �v. �. ix�..,.. ��ias: 5�' c' �° ios3�i�:" F:.. �: M"` 3' .':�.<"t3':.v�'�.�v.«S,�'�..n. ,,,". �' i.;.+\`%," ro�. �' �.><.+a�.��v°:.T.. >�.w.s:•.,.�m X59..., >,., „X.&.s$
Yes No * For pressurized piping systems, does the turbine automatically shut down if the piping secondary
N/A ;containment monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which
sensors initiate positive shut -down? (Check all that apply)'
' F Sump /Trench Sensors; r Dispenser Containment Sensors. Did you confirm positive shut-down
due to leaks and sensor failure /disconnection? F
F Yes; F N o.
Yes No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no
mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the
a; N/A = =tank fill point (s) and operating properly? If so , at what percent of tank capacity ndoes the alarm tri gg er?
J;
€�. %
w Yes v No any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment
�i
f replaced and list the manufacturer name and model for all replacement parts in Section E, below.
EYes *) ' No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that
apply) r Product; F Water. If yes, describe causes in Section E, below.
Yes No* Was monitoring system set -up reviewed to ensure proper settings? Attach set up reports, if applicable
Yes No* $GIs all monitoring equipment operational per manufacturer's specifications ?'
* In SectionE below, describe how and when these deficiencies were or will be corrected
E. Comments:
Other lens ors from page one:
L4 Piping transition sump sensor 794380 -208/ N/A certified
L5 Day tank containment sensor 794380- 208 - 930304 certified.
L6 Generator room floor sensor 7943 80- 208/930141 certified.
A mechanical drop tube overfill prevention valve is installed as primary overfill.
F. In -Tank Gauging / SIR Equipment:
Check this box if tank gauging is used only for inventory control.
Check this box if no tank gauging or SIR equipment is installed
This section must be completed if in -tank gauging equipment is used to perform leak detection monitoring.
*In the Section H, below, describe how andwhen these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD): Check this box if LLDs are not installed.
Complete the following checklist:
Yes . ° No* For equipment start -up or annual equipment certification, was a leak simulated to verify LLD performance ?(Check
N/A : all that apply) Simulated 1 eak rate: F 3 g. p.h.; 0.1 g. p. h ; 0.2 g.p.h.
....�..............�.. ...... ......
Yes f No* Were all LLDs confirmed operational and accurate within regulatory requirements?
Yes a F No* Was the testing apparatus properly calibrated?
fYes F No* For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
r
� I
l N/A i
Yes No* For electronic LLDs, does the turbine automatically shut off ifthe LLD detects a leak? k
N/A
i Yes No* For electronic LLDs, does the turbine automatically shut off ifany portion of the monitoring system is disabled or
disconnected?
s
#I F Yes F No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or
N/A
fails a test?
y ..... ..:...».».�a..n..... w.�w '...........:....w.v..w..rr . r.....+..........+ .............ua.uw . r....a..n.....vv......w..... .....,......,. ...,.. u....... w.... x.. www+.......................... .... ... w.... x... n. ... wrw».. r .rM...w.r.rmmmnrw..mw.......... .V..v....w.vnwmmmv.......... tS
Yes i No* For electronic LLDs, have all accessible wiring connections been visually inspected?
>a ! N/A
� Yes � �' No* Were all items on the equipment manufacturer's maintenance checklist completed?
* In the Section H, below, describe how and when these deficiencies were or will be corrected.
H. Comments:
Pressurized double wall supply line. The supply line passed a precision line rest.
Site Address • 1918 M STREET, Bakersfield, 93301
atat
UST Monitoring Site Plan
Monitoring Plan Site Flap
Business Name: Pacific Bell Telephone Co. dba AT &T Cal. (SA004)
Business Address: 1980 M St Bakersfield
Fluor Sensor 11-5)
794380 -208
N
S
Drawing NOT to Scale
Transition Sump
wl Sensor (L4)
794380 -208
Vent Riser --� ;` IL71 1NMAt -4ZU
Fill ' Sump vrl Sensor
Vent Line I j - 1-2. 79438t 2i8, Spill
Bucket & ATG
Fuel Lines - I
I SAD04€1009
I i 20K UST Diesel
Piping Sump W1
Sensor (1-3)
794380 -208
Date map was drawn: 12/2/2014
Instructions
If you already have a diagram that shows all required information, you may include it, rather than this page, with your Monitoring System
Certification. On your site plan, show the general layout of tanks and piping. Clearly identify locations of the following equipment, if
installed: monitoring system control panels; sensors monitoring tank annular spaces, sumps, dispenser pans, spill containers, or other
secondary containment areas; mechanical or electronic line leak detectors; and in -tank liquid level probes (if used for leak detection). In the
space provided, note the date this Site Plan was prepared
Spill Bucket Testing Report Form
This form is intendedfor use by contractors performing annual testing of UST spill containment structures. The completed form and
printouts from tests (if applicable), should be provided to the facility owner /operatorfor submittal to the local regulatory agency.
FAC'TT.TTV INFORMATION Facility M- SA004
Facility Name: Pacific Bell Telephone Co. dba AT &T California
Date of Testing: 12 /2/2014
Facility Address: 1918 M STREET, Bakersfield, CA 93301
Facility Contact: Grant Armstrong
Phone: 661- 327 -6903
Date Local Agency Was Notified of Testing. 2014 -10 -23
Name of Local Agency Inspector (ifpresent during testing): Shane Gardner
T1P4ZTTNC;' CnNTRAC'TnP TNFnPMATION
Company Name: TAIT Environmental Services, Inc.
Technician Conducting Test: Pat Banbury
Credential I : CSLB Contractor ICC Service Tech. r SWRCB Tank Tester Other (Specify)
License number(s): A B ASB C -10 HAZ License Number 588098 : 5254955
GATT T RTTi -k'l 'r TTi'QTTNC:' TNFnPI%4ATInN
Test Method Used: Hydrostatic Vacuum Other
Test Equipment Used: Tape Measure
Equipment Resolution: 1/ 16th inch
Identify Spill Bucket (By Tank
Number, Stored Product, etc.
1 SA004UO01
Bucket Installation Type:
Direct Bury
Contained in Sump
On top of AST
Direct Bury
Contained in Sump
On top of AST
Direct Bury
F Contained in Sump
r7 On top of AST
Direct Bury
Contained in Sump
r7 On top of AST
Bucket Diameter:
11"
Bucket Depth:
16.5"
Wait time between applying
vacuum /water and start of test:
5 min
Test Start Time (TI):
9:55 am
Initial Reading (RI):
15.5"
Test End Time (TO:
10:55 am
Final Reading (RF):
15.5"
Test Duration (TF — TI):
One H our
Change in Reading (RF -RI):
0.00"
Pass/Fail Threshold or
Criteria:
0.00"
Test Result:
Pass Fail
r Pass 17 Fail
Pass Fail
Pass Fail
Comments — (include information on repairs made prior to testing, and recommendedfollow -zip for Jailed tests)
Transport test water to Tait shop.
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements.
Technician's Signature: Date: 12/2/2014
I 5 0,3 01
DEC 9, 2014 9:04 AM
# 1:BKFDCAI2 SA004 S -S
L
I50302
DEC 9, 2014 9:04 AM
# 2:1918 M ST.
L
I50303
DEC 9, 2014 9:04 AM
# 3:BAKERSFIELD,CA 93301
L
I50304
DEC 9, 2014 9:04 AM
# 4:661- 631 -2540
L
I51700
DEC 9, 2014 9:04 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE /TIME FORMAT
MON DD YYYY HH:MM:SS xM
L
I50F00
DEC 9, 2014 9:04 AM
MON DD YYYY HH:MM:SS xM
L
I10200
DEC 9, 2014 9:05 AM
BKFDCA12 SA004 S -S.
1918 M ST.
BAKERSFIELD,CA 93301
661- 631 -2540
SYSTEM CONFIGURATION
SLOT
BOARD TYPE
POWER ON RESET
CURRENT
1
4 PROBE / G.T.
163858
162909
2
INTERSTITIAL BD
201571
200974
3
UNUSED
9807749
9740626
4
UNUSED
9779270
9731856
5
UNUSED
9773701
9733099
6
UNUSED
9777894
9736328
7
UNUSED
9762690
9729456
8
UNUSED
9771838
9745252
9
COMBO I/O BOARD
9933
9969
10
COMBO I/O BOARD
9955
9969
11
UNUSED
9777370
9740536
12
UNUSED
9766698
9732681
13
UNUSED
9769260
9735321
14
UNUSED
9767566
9728231
15
UNUSED
9766910
9741321
16
UNUSED
9765364
9730129
COMM 1 FAXMODEM BOARD
40262
40298
COMM 2 UNUSED
9774427
9739772
COMM 3 UNUSED
9760324
9728973
COMM 4 UNUSED
9766571
9740448
COMM 5 UNUSED
9764941
9726900
COMM 6 UNUSED
9764496
9736783
L
I60100
DEC 9, 2014 9:05 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 DIESEL TK #SA004U001 ON
2 OFF
3 OFF
4 OFF
L
I60200
DEC 9, 2014 9:05 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 DIESEL TK #SA004U001
2
3
4
L
I60300
DEC 9, 2014 9:05 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 DIESEL TK #SA004U001 1
2 2
3 3
4 4
L
260400
DEC 9, 2014 9:05 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 DIESEL TK #SA004U001 20149
2 0
3 0
4 0
L
I60700
DEC 9, 2014 9:06 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 DIESEL TK #SA004U001 114.00
2 0.00
3 0.00
4 0.00
L
I60900
DEC 91 2014 9:06 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 DIESEL TK#SA004U001 0.000450
2 0.000000
3 0.000000
4 0.000000
L
I61200
DEC 9, 2014 9:06 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS
1 DIESEL TK #SA004U001 NONE
2 NONE
3 NONE
4 NONE
L
162100
DEC 9, 2014 9:06 AM
LINE MANIFOLDED TANKS
NONE
NONE
NONE
NONE
TANK LOW 'PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK #SA004U001 12000
2 0
3 0
4 0
L
262200
DEC 9, 2014 9:06 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK #SA004U001 19141
2 0
3 0
4 0
L
I62300
DEC 9, 2014 9:06 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK #SA004U001 18134
2 0
3 0
4 0
L
262400
DEC 9, 2014 9:06 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 DIESEL TK #SA004U001 2.0
L
I62800
DEC 9, 2014 9:06 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK #SA004U001 20149
2 0
3 0
4 0
L
I62900
DEC 9, 2014 9:06 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK #SA004U001 12000
2 0
3 0
4 0
L
270300
DEC 9,
2014 9:06 AM
LIQUID
TYPE
SENSOR
LOCATION
TYPE
1
ANNULAR SPACE
TRI -STATE
(SINGLE
FLOAT)
2
FILL SUMP
TRI -STATE
(SINGLE
FLOAT)
3
PIPING SUMP
TRI -STATE
(SINGLE
FLOAT)
4
TRANSITION SUMP
TRI -STATE
(SINGLE
FLOAT)
S
DAY TANK CONTAINMENT
TRI -STATE
(SINGLE
FLOAT)
6
GEN ROOM FLOOR
TRI -STATE
(SINGLE
FLOAT)
7
TRI -STATE
(SINGLE
FLOAT)
8
TRI -STATE
(SINGLE
FLOAT)
L
290200
DEC 9, 2014 9:07 AM
SOFTWARE REVISION LEVEL
•VERSION 123.01
SOFTWARE## 346123 -100 -B
CREATED - 02.06.21.13.00
S- MODULE# 330160 -002 -A
SYSTEM FEATURES:
PERIODIC IN -TANK TESTS
ANNUAL IN -TANK TESTS
CSLD
I11100
DEC
9, 2014
9:08 AM
BKFDCAI2 SA004 S -S
1918 M ST.
BAKERSFIELD,CA 93301
661
-631 -2540
PRIORITY ALARM HISTORY
ID
CATEGORY
DESCRIPTION
ALARM TYPE
STATE
DATE
TIME
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
CLEAR
12 -05 -14
7:54PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
ALARM
12 -05 -14
7:54PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
CLEAR
12 -05 -14
7:52PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
ALARM
12 -05 -14
7 :52PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
CLEAR
12 -05 -14
7:51PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
ALARM
12 -05 -14
7:50PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
CLEAR
12 -05 -14
7:50PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
ALARM
12 -05 -14
7:49PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
CLEAR
12 -05 -14
7 :49PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
ALARM
12 -05 -14
7:43PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
CLEAR
12 -05 -14
7:43PM
13
INPUT
GEN
RUN
EXTERN INPUT
ALARM
ALARM
12 -05 -14
7:43PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
CLEAR
12 -05 -14
7:40PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
ALARM
12 -05 -14
7:40PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
CLEAR
12 -05 -14
7:40PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
ALARM
12 -05 -14
7:40PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
CLEAR
12 -05 -14
7:36PM
13
INPUT
GEN
RUN
EXTERN INPUT
ALARM
ALARM
12 -05 -14
7:32PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
CLEAR
12 -05 -14
7:27PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
ALARM
12 -05 -14
7:20PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
CLEAR
12 -05 -14
7:19PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
ALARM
12 -05 -14
7:19PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
CLEAR
12 -05 -14
7:18PM
I 2
INPUT
PUMP RUN
EXTERN INPUT
ALARM
CLEAR
12 -05 -14
7:17PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
ALARM
12 -05 -14
7:09PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
CLEAR
12 -05 -14
7:09PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
ALARM
12 -05 -14
7:08PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
CLEAR
12 -05 -14
7:08PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
ALARM
12 -05 -14
7:08PM
I 2
INPUT
PUMP RUN
EXTERN INPUT
ALARM
ALARM
12 -05 -14
7:07PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
CLEAR
12 -05 -14
7:05PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
ALARM
12 -05 -14
7:05PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
CLEAR
12 -05 -14
7:04PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
ALARM
12 -05 -14
7:04PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
CLEAR
12 -05 -14
6:49PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
ALARM
12 -05 -14
6:45PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
CLEAR
12 -05 -14
6:39PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
ALARM
12 -05 -14
6:26PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
CLEAR
12 -05 -14
5:53PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
ALARM
12 -05 -14
5:52PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
CLEAR
12 -05 -14
5:42PM
13
INPUT
GEN
RUN
EXTERN INPUT
ALARM
ALARM
12 -05 -14
5:42PM
13
INPUT
GEN
RUN
EXTERN INPUT
ALARM
CLEAR
12 -05 -14
5:41PM
13
INPUT
GEN
RUN
EXTERN INPUT
ALARM
ALARM
12 -05 -14
5:40PM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
CLEAR
12 -03 -14
4:46AM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
ALARM
12 -03 -14
4:32AM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
CLEAR
12 -03 -14
4:27AM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
ALARM
12 -03 -14
3:11AM
13
INPUT
GEN
RUN
EXTERN INPUT
ALARM
CLEAR
12 -03 -14
2:55AM
I 3
INPUT
GEN
RUN
EXTERN INPUT
ALARM
ALARM
12 -03 -14
2:50AM
I11200
DEC 9, 2014 9:09 AM
BKFDCAI2 SA004 S -S
1918 M ST.
BAKERSFIELD,CA 93301
661 -631 -2540
NON - PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 1
TANK
DIESEL
TK##SA004U001
LOW
TEMP
WARNING
CLEAR
12 -02 -14
10:51AM
T 1
TANK
DIESEL
TK #SA004U001
LOW
TEMP
WARNING
ALARM
12 -02 -14
10:48AM
T 1
TANK
DIESEL
TK #SA004U001
HIGH WATER WARNING
CLEAR
12 -02 -14
10:48AM
T 1
TANK
DIESEL
TK #SA004U001
HIGH WATER WARNING
ALARM
12 -02 -14
10:37AM
T 1
TANK
DIESEL
TK #SA004U001
HIGH PRODUCT ALARM
CLEAR
12 -02 -14
10:31AM
T 1
TANK
DIESEL
TK #SA004U001
HIGH PRODUCT ALARM
ALARM
12 -02 -14
10:29AM
T 1
TANK
DIESEL
TK #SA004U001
DELIVERY
NEEDED
CLEAR
12 -12 -13
10:20AM
T 1
TANK
DIESEL
TK #SA004U001
DELIVERY
NEEDED
ALARM
12 -12 -13
10:19AM
T 1
TANK
DIESEL
TK #SA004U001
HIGH WATER WARNING
CLEAR
12 -12 -13
9:58AM
T 1
TANK
DIESEL
TK #SA004U001
HIGH WATER WARNING
ALARM
12 -12 -13
9:54AM
T 1
TANK
DIESEL
TK #SA004U001
HIGH PRODUCT ALARM
CLEAR
12 -12 -13
9:47AM
T 1
TANK
DIESEL
TK #SA004U001
HIGH PRODUCT ALARM
ALARM
12 -12 -13
9:47AM
T 1
TANK
DIESEL
TK #SA004U001
INVALID FUEL LEVEL
CLEAR
12 -12 -13
9:45AM
T 1
TANK
DIESEL
TK #SA004U001
INVALID FUEL LEVEL
ALARM
12 -12 -13
9:45AM
T 1
TANK
DIESEL
TK #SA004U001
HIGH WATER WARNING
CLEAR
4 -11 -13
12:14PM
T 1
TANK
DIESEL
TK #SA004U001
LOW
TEMP
WARNING
CLEAR
4 -11 -13
12:14PM
T 1
TANK
DIESEL
TK #SA004U001
LOW
TEMP
WARNING
ALARM
4 -11 -13
12:13PM
T 1
TANK
DIESEL
TK #SA004U001
HIGH PRODUCT ALARM
CLEAR
4 -11 -13
12:06PM
T 1
TANK
DIESEL
TK #SA004U001
HIGH PRODUCT ALARM
ALARM
4 -11 -13
12:06PM
T 1
TANK
DIESEL
TK #SA004U001
LOW
TEMP
WARNING
CLEAR
2 -01 -13
3:58PM
T 1
TANK
DIESEL
TK #SA004U001
LOW
TEMP
WARNING
ALARM
2 -01 -13
3:54PM
T 1
TANK
DIESEL
TK #SA004U001
LOW
TEMP
WARNING
CLEAR
2 -01 -13
3:49PM
T 1
TANK
DIESEL
TK##SA004U001
LOW
TEMP
WARNING
ALARM
2 -01 -13
3:41PM
T 1
TANK
DIESEL
TK #SA004U001
LOW
TEMP
WARNING
CLEAR
2 -01 -13
7:33AM
T 1
TANK
DIESEL
TK #SA004U001
LOW
TEMP
WARNING
ALARM
2 -01 -13
7:24AM
T 1
TANK
DIESEL
TK #SA004U001
LOW
TEMP
WARNING
CLEAR
2 -01 -13
7 :17AM
T 1
TANK
DIESEL
TK#SA004U001
LOW
TEMP
WARNING
ALARM
2 -01 -13
6:55AM
T 1
TANK
DIESEL
TK #SA004U001
LOW
TEMP
WARNING
CLEAR
2 -01 -13
6:44AM
T 1
TANK
DIESEL
TK #SA004U001
LOW
TEMP
WARNING
ALARM
2 -01 -13
6:02AM
T 1
TANK
DIESEL
TK #SA004U001
LOW
TEMP
WARNING
CLEAR
2 -01 -13
5:57AM
T 1
TANK
DIESEL
TK #SA004U001
LOW
TEMP
WARNING
ALARM
2 -01 -13
5:12AM
T 1
TANK
DIESEL
TK #SA004U001
LOW
TEMP
WARNING
CLEAR
2 -01 -13
4:29AM
T 1
TANK
DIESEL
TK #SA004U001
LOW
TEMP
WARNING
ALARM
2 -01 -13
4:06AM
T 1
TANK
DIESEL
TK #SA004U001
LOW
TEMP
WARNING
CLEAR
2 -01 -13
1:41AM
T 1
TANK
DIESEL
TK #SA004U001
LOW
TEMP
WARNING
ALARM
2 -01 -13
1:38AM
T 1
TANK
DIESEL
TK #SA004U001
LOW
TEMP
WARNING
CLEAR
2 -01 -13
12:55AM
T 1
TANK
DIESEL
TK #SA004U001
LOW
TEMP
WARNING
ALARM
2 -01 -13
12 :44AM
T 1
TANK
DIESEL
TK #SA004U001
LOW
TEMP
WARNING
CLEAR
2 -01 -13
12:38AM
T 1
TANK
DIESEL
TK #SA004U001
LOW
TEMP
WARNING
ALARM
2 -01 -13
12:27AM
T 1
TANK
DIESEL
TK #SA004U001
LOW
TEMP
WARNING
CLEAR
2 -01 -13
12:21AM
T 1
TANK
DIESEL
TK #SA004U001
LOW
TEMP
WARNING
ALARM
2 -01 -13
12:14AM
T 1
TANK
DIESEL
TK #SA004U001
LOW
TEMP
WARNING
CLEAR
2 -01 -13
12:05AM
T 1
TANK
DIESEL
TK #SA004U001
LOW
TEMP
WARNING
ALARM
1 -31 -13
11:22PM
T 1
TANK
DIESEL
TK #SA004U001
LOW
TEMP
WARNING
CLEAR
1 -31 -13
11:OOPM
T 1
TANK
DIESEL
TK #SA004U001
LOW
TEMP
WARNING
ALARM
1 -31 -13
10:41PM
T 1
TANK
DIESEL
TK #SA004U001
LOW
TEMP
WARNING
CLEAR
1 -31 -13
10:35PM
T 1
TANK
DIESEL
TK #SA004U001
LOW
TEMP
WARNING
ALARM
1 -31 -13
10:12PM
T 1
TANK
DIESEL
TK #SA004U001
HIGH WATER WARNING
ALARM
1 -31 -13
10:08PM
T 1
TANK
DIESEL
TK#SA004U001
LOW
TEMP
WARNING
CLEAR
1 -31 -13
10:08PM
T 1
TANK
DIESEL
TK #SA004U001
LOW
TEMP
WARNING
ALARM
1 -31 -13
9:41PM
I20600
DEC 9, 2014 9:11 AM
BKFDCA12 SA004 S -S
1918 M ST.
BAKERSFIELD,CA 93301
661 -631 -2540
TANK ALARM HISTORY
TANK 1 DIESEL TK #SA004U001
HIGH WATER ALARM
DEC
2,
2014
10:37 AM
DEC
12,
2013
9:54 AM
JAN
31,
2013
10:08 PM
OVERFILL ALARM
DEC
2,
2014
10:30 AM
DEC
12,
2013
9:46 AM
APR
11,
2013
12:06 PM
LOW PRODUCT ALARM
DEC
12,
2013
10:19 AM
JAN
30,
2013
3:27 PM
JAN
30,
2013
2:43 PM
HIGH PRODUCT ALARM
DEC
2,
2014
10:29 AM
DEC
12,
2013
9:47 AM
APR
11,
2013
12:06 PM
INVALID FUEL LEVEL
DEC
12,
2013
9:45 AM
AUG
29,
2012
3:13 AM
AUG
29,
2012
3:13 AM
PROBE OUT
DEC
2,
2014
10:46 AM
DEC
2,
2014
10:26 AM
DEC 12, 2013 9:57 AM
HIGH WATER WARNING
DEC 2,
2014
10:37 AM
DEC 12,
2013
9:54 AM
2014
JAN 31,
2013
10:08 PM
DELIVERY NEEDED
DEC 12,
2013
10:19 AM
9:08 AM
JAN 30,
2013
3:27 PM
DEC
JAN 30,
2013
2:43 PM
MAX PRODUCT ALARM
JAN 30,
2013
3:27 PM
MAY 31,
2012
11:06 AM
LOW TEMP WARNING
DEC 2,
2014
10:48 AM
FUEL
APR 11,
2013
12:13 PM
12,
FEB 1,
2013
3:54 PM
130200
DEC 9, 2014 9:12 AM
BKFDCA12 SA004 S-S
1918 M ST.
BAKERSFIELD,CA 93301
661-631-2540
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1
ANNULAR
SPACE
DEC
2,
2014
9:58 AM
FUEL
ALARM
DEC
12,
2013
9:08 AM
FUEL
ALARM
DEC
20,
2012
9:49 AM
FUEL
ALARM
2
FILL SUMP
DEC
2,
2014
10:04 AM
FUEL
ALARM
DEC
12,
2013
9:14 AM
FUEL
ALARM
DEC
20,
2012
9:57 AM
FUEL
ALARM
3
PIPING SUMP
DEC
2,
2014
10:07 AM
FUEL
ALARM
DEC
12,
2013
9:20 AM
FUEL
ALARM
DEC
20,
2012
10:00 AM
FUEL
ALARM
4
TRANSITION SUMP
DEC
2,
2014
10:11 AM
FUEL
ALARM
DEC
12,
2013
9:28 AM
FUEL
ALARM
DEC
20,
2012
10:04 AM
FUEL
ALARM
5
DAY
TANK CONTAINMENT
DEC
2,
2014
10:14 AM
FUEL
ALARM
DEC
12,
2013
9:34 AM
FUEL
ALARM
DEC
20,
2012
10:14 AM
FUEL
ALARM
6
GEN
ROOM FLOOR
DEC
2,
2014
10:17 AM
FUEL
ALARM
DEC
12,
2013
9:31 AM
FUEL
ALARM
DEC
20,
2012
10:10 AM
FUEL
ALARM