Loading...
HomeMy WebLinkAboutFMC Results 9-14-14MONITORING SYSTEM CERTIFICATION For Use By All Jurisdictions Within the State of CaliforniaAuthority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner/operator. The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date. A.General Information Facility Name:Bldg. No.: Site Address:City:Zip: Facility Contact Person: Contact Phone No.: Make/Model of Monitoring System:Date of Testing/Servicing: B.Inventory of Equipment Tested/Certified Check the appropriate boxes to indicate specific equipment inspected/serviced: Tank ID:Tank ID: In-Tank Gauging Probe.Model:In-Tank Gauging Probe.Model: Annular Space or Vault Sensor.Model:Annular Space or Vault Sensor.Model: Piping Sump / Trench Sensor(s).Model:Piping Sump / Trench Sensor(s).Model: Fill Sump Sensor(s).Model:Fill Sump Sensor(s).Model: Mechanical Line Leak Detector.Model:Mechanical Line Leak Detector.Model: Electronic Line Leak Detector.Model:Electronic LineLeak Detector.Model: Tank Overfill / High-Level Sensor.Model:Tank Overfill / High-Level Sensor.Model: Other (specify equipment type and model in Section E on Page 2).Other (specify equipment type and model in Section E on Page 2). Tank ID:Tank ID: In-Tank Gauging Probe.Model:In-Tank Gauging Probe.Model: Annular Space or Vault Sensor.Model:Annular Space or Vault Sensor.Model: Piping Sump / TrenchSensor(s).Model:Piping Sump / Trench Sensor(s).Model: Fill Sump Sensor(s).Model:Fill Sump Sensor(s).Model: Mechanical Line Leak Detector.Model:Mechanical Line Leak Detector.Model: Electronic Line Leak Detector.Model:Electronic Line Leak Detector.Model: Tank Overfill / High-Level Sensor.Model:Tank Overfill / High-Level Sensor.Model: Other (specify equipment type and model in Section E on Page 2).Other (specify equipment type and model in Section E on Page 2). Dispenser ID:Dispenser ID: Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model: Shear Valve(s).Shear Valve(s). Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s). Dispenser ID:Dispenser ID: Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model: Shear Valve(s).Shear Valve(s). Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s). Dispenser ID:Dispenser ID: Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model: Shear Valve(s).Shear Valve(s). Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s). *If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility. C.Certification -I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers’ guidelines. Attached to this Certification is information (e.g. manufacturers' checklists)necessary to verify that this information is correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also attached a copy of the report;(check all that apply):System set-up Alarm history report Technician Name (print):Signature: Certification No.:License. No.:804904 Testing Company Name:Confidence UST Services, Inc.Phone No.:(800)339-9930 Site Address:Date of Testing/Servicing: Page 1 of 3 Chevron 2525WhiteLaneBakersfield93304 BassemAzzi (805)217-0610 Veeder-RootTLS-350 09/14/2014 12.000gal.Regular 847390-107 Ronan Ronan 794380-208 794380-208 PLLD OPW61-SO 12,000gal.Super 847390-107 PLLD OPW61-SO 12,000gal.Diesel 847390-107 Ronan 794380-208 OPW61-SO PLLD 1-2 3-4 5-6 7-8 AustinSterling B45438 2525WhiteLane Bakersfield,CA93304 09/14/2014 Monitoring System Certification D.Results of Testing/Servicing Software Version Installed: Complete the following checklist: Yes No*Isthe audible alarm operational? Yes No*Is the visual alarm operational? Yes No*Were all sensors visually inspected, functionally tested, and confirmed operational? Yes No*Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not interfere with their proper operation? Yes No* N/A If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem) operational? Yes No* N/A For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate positive shut-down? (Check all that apply) Sump/Trench Sensors; Dispenser Containment Sensors. Did you confirm positive shut-down due to leaks and sensor failure/disconnection? Yes; No. Yes No* N/A For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank fill point(s) and operating properly? If so, at what percent oftank capacity does the alarm trigger? % Yes*NoWas any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E, below. Yes*NoWas liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) Product; Water. If yes, describe causes in Section E, below. Yes No*Was monitoring system set-up reviewed to ensure proper settings? Attach set up reports, if applicable Yes No*Is all monitoring equipment operational per manufacturer’s specifications? * In Section E below, describe how and when these deficiencies were or will be corrected. E.Comments: Page 2 of 3 329.01 Monitoring System Certification F.In-Tank Gauging / SIR Equipment: Check this box if tank gauging is used only for inventory control. Check this box if no tank gauging or SIR equipment is installed. This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring. Complete the following checklist: Yes No*Has all input wiring been inspected for proper entry and termination, including testing for ground faults? Yes No*Were all tank gauging probes visually inspected for damage and residue buildup? Yes No*Was accuracy of system product level readings tested? Yes No*Was accuracy of system water level readings tested? Yes No*Were all probes reinstalled properly? Yes No*Were all items on the equipment manufacturer’s maintenance checklist completed? * In the Section H, below, describe how and when these deficiencies were or will be corrected. G.Line Leak Detectors (LLD):Check this box if LLDs are not installed. Complete the following checklist: Yes No* N/A For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance? (Check all that apply)Simulated leak rate: 3 g.p.h.; 0.1 g.p.h ; 0.2 g.p.h. Yes No*Were all LLDs confirmed operational and accurate within regulatory requirements? Yes No*Was the testing apparatus properly calibrated? Yes No* N/A For mechanical LLDs, does the LLD restrict product flow if it detects a leak? Yes No* N/A For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak? Yes No* N/A For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? Yes No* N/A For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a test? Yes No* N/A For electronic LLDs, have all accessible wiring connections been visually inspected? Yes No*Were all items on the equipment manufacturer’s maintenance checklist completed? * In the Section H, below, describe how and when these deficiencies were or will be corrected. H.Comments: Page 3 of 3 Leak Detector Test Results Sheet Customer Address: Work Order: Site Address: Test Date: Site Contact: Phone: Technician: Phone: 800-339-9930 ICC No.: Product Type LLD Type Model Serial No. Check Valve Holding Pressure Bleed Off ML. Leak Rate Tested: Pass/Fail 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi Technician Name: Technician No.: Signature: Date: ProactiveProp.,Inc.dbaWhiteLnChvn 15000OliveViewDr.,UnitG Sylmar,CA91342 35165 09/14/2014 8339953-UT Regular Electronic PLLD AustinSterling (805)217-0610BassemAzzi Bakersfield,CA93304 2525WhiteLane Chevron 11 psi85 ml Pass PLLDElectronicPremium 11 psi110 ml Pass PLLDElectronicDiesel 13 psi 125 ml Pass AustinSterling 8339953-UT 09/14/2014 White lane chevron system setup Responses Received: 200 WHITE LANE CHEVRON 2525 WHITE LANE BAKERSFIELD CA 93304 661-832-9781 SEP 14, 2015 11:34 AM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 DIESEL 1515 20.33 0.0 95.0 10507 2 SUPREME 2785 31.27 0.8 91.9 9237 3 REGULAR 8698 75.39 0.8 94.4 3324 I90500 SEP 14, 2015 11:34 AM SOFTWARE REVISION LEVEL VERSION 329.01 SOFTWARE# 346329-100-B CREATED - 09.01.29.15.44 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD I50500 SEP 14, 2015 11:34 AM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM I50201 SEP 14, 2015 11:34 AM SHIFT TIME 1 : 5:00 AM I50202 SEP 14, 2015 11:34 AM SHIFT TIME 2 : DISABLED I50203 SEP 14, 2015 11:34 AM SHIFT TIME 3 : DISABLED I50204 SEP 14, 2015 11:34 AM SHIFT TIME 4 : DISABLED I54600 SEP 14, 2015 11:34 AM TANK PER TST NEEDED WRN: DISABLED I54900 SEP 14, 2015 11:34 AM TANK ANN TST NEEDED WRN: DISABLED I55300 SEP 14, 2015 11:34 AM LINE RE-ENABLE METHOD PASS LINE TEST I55600 SEP 14, 2015 11:34 AM LINE PER TST NEEDED WRN: DISABLED I55900 SEP 14, 2015 11:34 AM LINE ANN TST NEEDED WRN: DISABLED I50D00 SEP 14, 2015 11:34 AM PRINT TC VOLUMES ENABLED I50E00 SEP 14, 2015 11:34 AM TEMP COMPENSATION VALUE (DEG F ): 60.0 I60B00 SEP 14, 2015 11:34 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 SEP 14, 2015 11:34 AM H-PROTOCOL DATA FORMAT HEIGHT I51A01 SEP 14, 2015 11:34 AM DAYLIGHT SAVING TIME ENABLED ON I51B00 SEP 14, 2015 11:34 AM DAYLIGHT SAVING TIME START DATE MAR WEEK 2 SUN 2:00 AM END DATE NOV WEEK 1 SUN 2:00 AM I51600 SEP 14, 2015 11:34 AM RE-DIRECT LOCAL PRINTOUT DISABLED I50400 SEP 14, 2015 11:34 AM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED I21900 SEP 14, 2015 11:34 AM TANK CHART SECURITY DISABLED I5BD00 SEP 14, 2015 11:34 AM CUSTOM ALARM LABELS DISABLED I56000 SEP 14, 2015 11:34 AM MASS/DENSITY DISABLED I88101 SEP 14, 2015 11:34 AM PORT SETTINGS: COMM BOARD : 1 (RS-232) BAUD RATE : 9600 PARITY : EVEN STOP BIT : 1 STOP DATA LENGTH: 7 DATA RS-232 SECURITY CODE : DISABLED I88102 SEP 14, 2015 11:34 AM I88103 SEP 14, 2015 11:34 AM PORT SETTINGS: COMM BOARD : 3 (EDIM ) RS-232 SECURITY CODE : DISABLED I88104 SEP 14, 2015 11:34 AM I88105 SEP 14, 2015 11:34 AM PORT SETTINGS: COMM BOARD : 5 (RS-485) BAUD RATE : 2400 PARITY : NONE STOP BIT : 2 STOP DATA LENGTH: 7 DATA RS-232 SECURITY CODE : DISABLED I88106 SEP 14, 2015 11:34 AM PORT SETTINGS: COMM BOARD : 6 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I52000 SEP 14, 2015 11:34 AM RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 ON DATE AUG 27, 2010 DISABLED 2 ON DATE AUG 27, 2010 DISABLED 3 ON DATE AUG 27, 2010 DISABLED 4 ON DATE AUG 27, 2010 DISABLED 5 ON DATE AUG 27, 2010 DISABLED 6 ON DATE AUG 27, 2010 DISABLED 7 ON DATE AUG 27, 2010 DISABLED 8 ON DATE AUG 27, 2010 DISABLED I60100 SEP 14, 2015 11:34 AM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 DIESEL ON 2 SUPREME ON 3 REGULAR ON 4 OFF I60200 SEP 14, 2015 11:34 AM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 DIESEL 2 SUPREME 3 REGULAR 4 I60300 SEP 14, 2015 11:34 AM TANK PRODUCT CODE TANK PRODUCT LABEL 1 DIESEL 1 2 SUPREME 2 3 REGULAR 3 4 4 I60900 SEP 14, 2015 11:34 AM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 DIESEL 0.000450 2 SUPREME 0.000700 3 REGULAR 0.000700 4 0.000000 I60700 SEP 14, 2015 11:34 AM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 DIESEL 111.00 2 SUPREME 111.00 3 REGULAR 111.00 4 0.00 I60A00 SEP 14, 2015 11:34 AM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 DIESEL 4 PTS 12022 2 SUPREME 4 PTS 12022 3 REGULAR 4 PTS 12022 4 1 PT 0 I60400 SEP 14, 2015 11:34 AM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 DIESEL 12022 2 SUPREME 12022 3 REGULAR 12022 4 0 I60500 SEP 14, 2015 11:34 AM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 DIESEL 12022 9677 6011 2357 2 SUPREME 12022 9677 6011 2357 3 REGULAR 12022 9677 6011 2357 4 0 0 0 0 I60600 SEP 14, 2015 11:34 AM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 DIESEL 12022 0 0 0 0 9677 0 0 0 0 6011 0 0 0 0 2357 0 0 0 0 2 SUPREME 12022 0 0 0 0 9677 0 0 0 0 6011 0 0 0 0 2357 0 0 0 0 3 REGULAR 12022 0 0 0 0 9677 0 0 0 0 6011 0 0 0 0 2357 0 0 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 SEP 14, 2015 11:34 AM TANK PRODUCT LABEL METER DATA 1 DIESEL NO 2 SUPREME NO 3 REGULAR NO 4 NO I62F00 SEP 14, 2015 11:34 AM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 DIESEL 4.0 INCHES 2 SUPREME 4.0 INCHES 3 REGULAR 4.0 INCHES I62700 SEP 14, 2015 11:34 AM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 DIESEL 2.0 2 SUPREME 2.0 3 REGULAR 2.0 9999FF1B I62400 SEP 14, 2015 11:34 AM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 DIESEL 3.0 2 SUPREME 3.0 3 REGULAR 3.0 I62800 SEP 14, 2015 11:34 AM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 DIESEL 12022 2 SUPREME 12022 3 REGULAR 12022 4 0 I62300 SEP 14, 2015 11:34 AM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 DIESEL 10819 2 SUPREME 10819 3 REGULAR 10819 4 0 I62200 SEP 14, 2015 11:34 AM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 DIESEL 11421 2 SUPREME 11421 3 REGULAR 11421 4 0 I62900 SEP 14, 2015 11:34 AM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 DIESEL 1442 2 SUPREME 1442 3 REGULAR 1442 4 0 I62100 SEP 14, 2015 11:34 AM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 DIESEL 500 2 SUPREME 500 3 REGULAR 500 4 0 I62600 SEP 14, 2015 11:34 AM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 DIESEL 32 2 SUPREME 32 3 REGULAR 32 4 99 I62500 SEP 14, 2015 11:34 AM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 DIESEL 25 2 SUPREME 25 3 REGULAR 25 4 99 I60800 SEP 14, 2015 11:34 AM TANK TILT TANK PRODUCT LABEL INCHES 1 DIESEL 3.70 2 SUPREME 2.00 3 REGULAR 2.00 4 0.00 I60B00 SEP 14, 2015 11:34 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 SEP 14, 2015 11:34 AM TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 DIESEL 0.00 2 SUPREME 0.00 3 REGULAR 0.00 4 0.00 I61200 SEP 14, 2015 11:34 AM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 DIESEL NONE NONE 2 SUPREME NONE NONE 3 REGULAR NONE NONE 4 NONE NONE I63600 SEP 14, 2015 11:34 AM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 DIESEL 0 2 SUPREME 0 3 REGULAR 0 4 0 I62A00 SEP 14, 2015 11:34 AM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 DIESEL 0 2 SUPREME 0 3 REGULAR 0 4 0 I62C00 SEP 14, 2015 11:34 AM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 DIESEL STANDARD 2 SUPREME STANDARD 3 REGULAR STANDARD 4 STANDARD I62D00 SEP 14, 2015 11:34 AM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 DIESEL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 SUPREME GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 REGULAR GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 SEP 14, 2015 11:34 AM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 DIESEL OFF OFF 2 SUPREME OFF OFF 3 REGULAR OFF OFF 4 OFF OFF I63000 SEP 14, 2015 11:34 AM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 DIESEL OFF 2 SUPREME OFF 3 REGULAR OFF 4 OFF I63200 SEP 14, 2015 11:34 AM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 DIESEL OFF 2 SUPREME OFF 3 REGULAR OFF 4 OFF I61000 SEP 14, 2015 11:34 AM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 DIESEL 1 2 SUPREME 3 3 REGULAR 3 4 1 I63A00 SEP 14, 2015 11:34 AM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 DIESEL 10.00% 2 SUPREME 10.00% 3 REGULAR 10.00% 4 10.00% I61100 SEP 14, 2015 11:34 AM LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : ALL TANK JAN 29, 2009 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED I61300 SEP 14, 2015 11:35 AM CSLD PROBABLITY OF DETECTION I61400 SEP 14, 2015 11:35 AM CSLD CLIMATE FACTOR I61600 SEP 14, 2015 11:35 AM TANK PRODUCT LABEL CAL UPDATE 1 DIESEL IMMEDIATE 2 SUPREME IMMEDIATE 3 REGULAR IMMEDIATE 4 IMMEDIATE I61A00 SEP 14, 2015 11:35 AM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 DIESEL DISABLED 2 SUPREME DISABLED 3 REGULAR DISABLED 4 DISABLED I61B00 SEP 14, 2015 11:35 AM IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 SEP 14, 2015 11:35 AM CSLD REPORT ONLY I62B00 SEP 14, 2015 11:35 AM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 DIESEL ??? 0, 0 2 SUPREME ??? 0, 0 3 REGULAR ??? 0, 0 4 ??? 0, 0 I63300 SEP 14, 2015 11:35 AM LEAK TEST REPORT FORMAT: NORMAL I63400 SEP 14, 2015 11:35 AM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 DIESEL 0 2 SUPREME 0 3 REGULAR 0 4 0 I63500 SEP 14, 2015 11:35 AM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 DIESEL 1 2 SUPREME 1 3 REGULAR 1 4 1 I63900 SEP 14, 2015 11:35 AM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 DIESEL END FACTOR: NONE 2 SUPREME END FACTOR: NONE 3 REGULAR END FACTOR: NONE 4 END FACTOR: NONE I78000 SEP 14, 2015 11:35 AM PRESSURE LINE LEAK SETUP Q 1:DIESEL TYP:2.0/3.0IN FIBERGLASS 2.0IN DIA LEN: 250 FEET 3.0IN DIA LEN: 0 FEET SHUTDOWN RATE: 3.0 GPH LOW PRESSURE SHUTOFF:NO LOW PRESSURE : 0 PSI T 1:DIESEL DISPENSE MODE: STANDARD SENSOR: HIGH PRESSURE PRESSURE OFFSET: 0.0PSI Q 2:SUPREME TYP:2.0/3.0IN FIBERGLASS 2.0IN DIA LEN: 180 FEET 3.0IN DIA LEN: 0 FEET SHUTDOWN RATE: 3.0 GPH LOW PRESSURE SHUTOFF:NO LOW PRESSURE : 0 PSI T 2:SUPREME DISPENSE MODE: STANDARD SENSOR: HIGH PRESSURE PRESSURE OFFSET: 0.0PSI Q 3:REGULAR TYP:2.0/3.0IN FIBERGLASS 2.0IN DIA LEN: 180 FEET 3.0IN DIA LEN: 0 FEET SHUTDOWN RATE: 3.0 GPH LOW PRESSURE SHUTOFF:NO LOW PRESSURE : 0 PSI T 3:REGULAR DISPENSE MODE: STANDARD SENSOR: HIGH PRESSURE PRESSURE OFFSET: 0.0PSI I77700 SEP 14, 2015 11:35 AM I77800 SEP 14, 2015 11:35 AM I78C00 SEP 14, 2015 11:35 AM I78300 SEP 14, 2015 11:35 AM I78F00 SEP 14, 2015 11:35 AM PRESSURE LINE LEAK DISPENSE THRESHOLD LINE LOW PRESSURE Q 1:DIESEL 0 PSI Q 2:SUPREME 0 PSI Q 3:REGULAR 0 PSI I78700 SEP 14, 2015 11:35 AM PRESSURE LLD SETUP REPORT Q 1:DIESEL IN-TANK ALARMS T 1:HIGH WATER ALARM T 1:LOW PRODUCT ALARM LIQUID SENSOR ALMS L 1:FUEL ALARM L 2:FUEL ALARM L 1:SENSOR OUT ALARM L 2:SENSOR OUT ALARM L 1:SHORT ALARM L 2:SHORT ALARM L 2:HIGH LIQUID ALARM Q 2:SUPREME IN-TANK ALARMS T 2:HIGH WATER ALARM T 2:LOW PRODUCT ALARM LIQUID SENSOR ALMS L 3:FUEL ALARM L 4:FUEL ALARM L 3:SENSOR OUT ALARM L 4:SENSOR OUT ALARM L 3:SHORT ALARM L 4:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL Q 3:REGULAR IN-TANK ALARMS T 3:HIGH WATER ALARM T 3:LOW PRODUCT ALARM LIQUID SENSOR ALMS L 5:FUEL ALARM L 6:FUEL ALARM L 5:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L 5:SHORT ALARM L 6:SHORT ALARM L 6:HIGH LIQUID ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL I70200 SEP 14, 2015 11:35 AM LIQUID LABEL DEVICE LABEL 1 DIESEL ANN 2 DIESEL STP 3 SUPREME ANN 4 SUPREME STP 5 REGULAR ANN 6 REGULAR STP 7 8 I70300 SEP 14, 2015 11:35 AM LIQUID TYPE SENSOR LOCATION TYPE 1 DIESEL ANN NORMALLY CLOSED 2 DIESEL STP TRI-STATE (SINGLE FLOAT) 3 SUPREME ANN NORMALLY CLOSED 4 SUPREME STP TRI-STATE (SINGLE FLOAT) 5 REGULAR ANN NORMALLY CLOSED 6 REGULAR STP TRI-STATE (SINGLE FLOAT) 7 TRI-STATE (SINGLE FLOAT) 8 TRI-STATE (SINGLE FLOAT) I70400 SEP 14, 2015 11:35 AM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 DIESEL ANN ANNULAR SPACE 2 DIESEL STP STP SUMP 3 SUPREME ANN ANNULAR SPACE 4 SUPREME STP STP SUMP 5 REGULAR ANN ANNULAR SPACE 6 REGULAR STP OTHER SENSORS 7 OTHER SENSORS 8 OTHER SENSORS I74200 SEP 14, 2015 11:35 AM I74300 SEP 14, 2015 11:35 AM I74400 SEP 14, 2015 11:35 AM I74700 SEP 14, 2015 11:35 AM I74800 SEP 14, 2015 11:35 AM I74900 SEP 14, 2015 11:35 AM I7BC00 SEP 14, 2015 11:35 AM I80200 SEP 14, 2015 11:35 AM I80300 SEP 14, 2015 11:35 AM I80400 SEP 14, 2015 11:35 AM I80700 SEP 14, 2015 11:35 AM I80900 SEP 14, 2015 11:35 AM I80B00 SEP 14, 2015 11:35 AM I80A00 SEP 14, 2015 11:35 AM I80C00 SEP 14, 2015 11:35 AM I80800 SEP 14, 2015 11:35 AM I79000 SEP 14, 2015 11:35 AM EDIM:1 VR:349633-002-C TD:98.09.21.11.16 I79100 SEP 14, 2015 11:35 AM I72300 SEP 14, 2015 11:35 AM WHITE LANE CHEVRON 2525 WHITE LANE BAKERSFIELD CA 93304 661-832-9781 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 PRESS SENSOR VAPOR PRESSURE 02 CANISTER VAPOR VALVE 03 UNKNOWN 04 FM 1-2 AIR FLOW METER 05 FM 3-4 AIR FLOW METER 06 FM 5-6 AIR FLOW METER 07 FM 7-8 AIR FLOW METER 08 ATMP PRESSURE ATM P SENSOR 09 UNKNOWN 10 UNKNOWN 11 UNKNOWN 12 UNKNOWN 13 UNKNOWN 14 UNKNOWN 15 UNKNOWN 16 UNKNOWN 17 UNKNOWN 18 UNKNOWN 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN 22 UNKNOWN 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN I72A00 SEP 14, 2015 11:35 AM VACUUM SENSOR VOLUME DEVICE LABEL VOLUME IV4E00 SEP 14, 2015 11:35 AM WHITE LANE CHEVRON 2525 WHITE LANE BAKERSFIELD CA 93304 661-832-9781 EVR/ISD SETUP TYPE: BALANCE IV4F00 SEP 14, 2015 11:35 AM WHITE LANE CHEVRON 2525 WHITE LANE BAKERSFIELD CA 93304 661-832-9781 NOZZLE A/L RANGE A/L RATIO: 1.00 - 1.20 IV4000 SEP 14, 2015 11:35 AM WHITE LANE CHEVRON 2525 WHITE LANE BAKERSFIELD CA 93304 661-832-9781 VAPOR PROCESSOR TYPE VEEDER-ROOT POLISHER IV4700 SEP 14, 2015 11:35 AM WHITE LANE CHEVRON 2525 WHITE LANE BAKERSFIELD CA 93304 661-832-9781 ASSESSMENT TIME START TIME: 10:00 AM TIME DELAY MINUTES: 1 IV5200 SEP 14, 2015 11:35 AM WHITE LANE CHEVRON 2525 WHITE LANE BAKERSFIELD CA 93304 661-832-9781 ACCEPT HIGH ORVR: NO IV4A00 SEP 14, 2015 11:35 AM WHITE LANE CHEVRON 2525 WHITE LANE BAKERSFIELD CA 93304 661-832-9781 ISD HOSE TABLE HOSE FP FP AFM HOSE ID ID LABEL ID LABEL 01 00 01 01 BLEND3 02 01 02 01 BLEND3 03 02 03 02 BLEND3 04 03 04 02 BLEND3 05 04 05 03 BLEND3 06 05 06 03 BLEND3 07 06 07 04 BLEND3 08 07 08 04 BLEND3 IV4B00 SEP 14, 2015 11:35 AM WHITE LANE CHEVRON 2525 WHITE LANE BAKERSFIELD CA 93304 661-832-9781 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 00 01 04/01 05/01 09/01 xx/xx 01 01 04/02 05/02 09/02 xx/xx 02 02 04/03 05/03 09/03 xx/xx 03 02 04/04 05/04 09/04 xx/xx 04 03 04/05 05/05 09/05 xx/xx 05 03 04/06 05/06 09/06 xx/xx 06 04 04/07 05/07 09/07 xx/xx 07 04 04/08 05/08 09/08 xx/xx IV4900 SEP 14, 2015 11:35 AM WHITE LANE CHEVRON 2525 WHITE LANE BAKERSFIELD CA 93304 661-832-9781 LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 IV1000 SEP 14, 2015 11:35 AM ISD VERSION: 01.02 White lane chevron alarm history before Responses Received: I10200 SEP 14, 2015 9:05 AM WHITE LANE CHEVRON 2525 WHITE LANE BAKERSFIELD CA 93304 661-832-9781 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 UNUSED 9217486 9616237 2 UNUSED 9173110 9483269 3 INTERSTITIAL BD 202003 202759 4 UNUSED 9178500 9484534 5 4 PROBE / G.T. 163228 163808 6 PLLD SENSOR BD 3959 4008 7 7SMARTSENSOR BD 506196 508321 8 UNUSED 9176410 9489618 9 UNUSED 9170611 9473296 10 PLLD POWER BD 99844 100055 11 UNUSED 9176728 9481411 12 UNUSED 9174418 9476765 13 UNUSED 9170765 9473819 14 UNUSED 9172987 9476394 15 UNUSED 9172899 9472903 16 UNUSED 9174242 9482066 COMM 1 RS232 SERIAL BD 14992 15065 COMM 2 REMOTE DISPLAY 27458 27600 COMM 3 ELEC DISP INT. 100698 101147 COMM 4 UNUSED 9174264 9488807 COMM 5 RS485 SERIAL BD 68140 68501 COMM 6 RS232 SERIAL BD 14903 14977 I90200 SEP 14, 2015 9:05 AM SOFTWARE REVISION LEVEL VERSION 329.01 SOFTWARE# 346329-100-B CREATED - 09.01.29.15.44 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD I11100 SEP 14, 2015 9:05 AM WHITE LANE CHEVRON 2525 WHITE LANE BAKERSFIELD CA 93304 661-832-9781 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME E 1 OTHER COMMUNICATION ALARM CLEAR 9-14-15 12:20AM E 1 OTHER COMMUNICATION ALARM ALARM 9-14-15 12:09AM E 1 OTHER COMMUNICATION ALARM CLEAR 9-13-15 2:42PM E 1 OTHER COMMUNICATION ALARM ALARM 9-13-15 2:34PM Q 3 OTHER REGULAR PLLD SHUTDOWN ALARM CLEAR 9-10-15 11:33AM Q 2 OTHER SUPREME PLLD SHUTDOWN ALARM CLEAR 9-10-15 11:33AM h 3 OTHER FP3: BLEND3 FLOW COLLECT FAIL CLEAR 9-10-15 11:33AM h 3 OTHER FP3: BLEND3 FLOW COLLECT FAIL ALARM 9-10-15 10:03AM Q 3 OTHER REGULAR PLLD SHUTDOWN ALARM ALARM 9-10-15 10:03AM Q 2 OTHER SUPREME PLLD SHUTDOWN ALARM ALARM 9-10-15 10:03AM E 1 OTHER COMMUNICATION ALARM CLEAR 9-08-15 12:17AM E 1 OTHER COMMUNICATION ALARM ALARM 9-08-15 12:07AM E 1 OTHER COMMUNICATION ALARM CLEAR 9-06-15 12:29AM E 1 OTHER COMMUNICATION ALARM ALARM 9-06-15 12:18AM E 1 OTHER COMMUNICATION ALARM CLEAR 9-05-15 6:22AM E 1 OTHER COMMUNICATION ALARM ALARM 9-05-15 6:12AM E 1 OTHER COMMUNICATION ALARM CLEAR 8-31-15 11:44AM E 1 OTHER COMMUNICATION ALARM ALARM 8-31-15 11:37AM E 1 OTHER COMMUNICATION ALARM CLEAR 8-31-15 11:25AM E 1 OTHER COMMUNICATION ALARM ALARM 8-31-15 11:16AM E 1 OTHER COMMUNICATION ALARM CLEAR 8-28-15 1:56PM E 1 OTHER COMMUNICATION ALARM ALARM 8-28-15 1:45PM E 1 OTHER COMMUNICATION ALARM CLEAR 8-28-15 12:47PM E 1 OTHER COMMUNICATION ALARM ALARM 8-28-15 12:37PM E 1 OTHER COMMUNICATION ALARM CLEAR 8-24-15 12:23AM E 1 OTHER COMMUNICATION ALARM ALARM 8-24-15 12:12AM E 1 OTHER COMMUNICATION ALARM CLEAR 8-16-15 12:25AM E 1 OTHER COMMUNICATION ALARM ALARM 8-16-15 12:17AM E 1 OTHER COMMUNICATION ALARM CLEAR 8-10-15 12:23AM E 1 OTHER COMMUNICATION ALARM ALARM 8-10-15 12:12AM E 1 OTHER COMMUNICATION ALARM CLEAR 8-08-15 12:16AM E 1 OTHER COMMUNICATION ALARM ALARM 8-08-15 12:05AM E 1 OTHER COMMUNICATION ALARM CLEAR 8-01-15 12:06AM E 1 OTHER COMMUNICATION ALARM ALARM 7-31-15 11:54PM Q 3 OTHER REGULAR PLLD SHUTDOWN ALARM CLEAR 7-27-15 9:24AM L 6 OTHER REGULAR STP FUEL ALARM CLEAR 7-27-15 9:24AM Q 3 OTHER REGULAR GROSS LINE FAIL CLEAR 7-27-15 9:24AM L 6 OTHER REGULAR STP FUEL ALARM ALARM 7-27-15 9:24AM Q 3 OTHER REGULAR PLLD SHUTDOWN ALARM ALARM 7-27-15 9:22AM Q 3 OTHER REGULAR GROSS LINE FAIL ALARM 7-27-15 9:22AM Q 3 OTHER REGULAR PLLD SHUTDOWN ALARM CLEAR 7-26-15 12:49PM Q 3 OTHER REGULAR GROSS LINE FAIL CLEAR 7-26-15 12:49PM Q 3 OTHER REGULAR PLLD SHUTDOWN ALARM ALARM 7-26-15 12:40PM Q 3 OTHER REGULAR GROSS LINE FAIL ALARM 7-26-15 12:40PM Q 2 OTHER SUPREME PLLD SHUTDOWN ALARM CLEAR 7-15-15 1:22PM Q 2 OTHER SUPREME GROSS LINE FAIL CLEAR 7-15-15 1:22PM Q 2 OTHER SUPREME PLLD SHUTDOWN ALARM ALARM 7-15-15 11:45AM Q 2 OTHER SUPREME GROSS LINE FAIL ALARM 7-15-15 11:45AM E 1 OTHER COMMUNICATION ALARM CLEAR 7-13-15 12:11AM E 1 OTHER COMMUNICATION ALARM ALARM 7-13-15 12:00AM I11200 SEP 14, 2015 9:05 AM WHITE LANE CHEVRON 2525 WHITE LANE BAKERSFIELD CA 93304 661-832-9781 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME h 3 OTHER FP3: BLEND3 FLOW COLLECT WARN CLEAR 9-10-15 10:00AM h 3 OTHER FP3: BLEND3 FLOW COLLECT WARN ALARM 9-09-15 10:02AM T 2 TANK SUPREME DELIVERY NEEDED CLEAR 9-07-15 7:16PM T 2 TANK SUPREME DELIVERY NEEDED ALARM 9-07-15 1:49PM T 1 TANK DIESEL DELIVERY NEEDED CLEAR 8-22-15 4:12AM T 1 TANK DIESEL DELIVERY NEEDED ALARM 8-20-15 8:35AM SYSTEM PRINTER ERROR CLEAR 8-17-15 2:44PM SYSTEM PAPER OUT CLEAR 8-17-15 2:44PM SYSTEM PRINTER ERROR ALARM 8-17-15 2:44PM SYSTEM PAPER OUT ALARM 8-17-15 2:44PM T 1 TANK DIESEL DELIVERY NEEDED CLEAR 8-15-15 3:59AM T 1 TANK DIESEL DELIVERY NEEDED ALARM 8-12-15 9:19AM OTHER ISD VAPOR LEAK WARN CLEAR 8-10-15 4:21PM T 1 TANK DIESEL DELIVERY NEEDED CLEAR 8-06-15 9:07PM T 1 TANK DIESEL INVALID FUEL LEVEL CLEAR 8-06-15 9:05PM T 1 TANK DIESEL INVALID FUEL LEVEL ALARM 8-06-15 8:09AM OTHER ISD VAPOR LEAK WARN ALARM 8-04-15 10:02AM T 1 TANK DIESEL DELIVERY NEEDED ALARM 8-03-15 8:51AM T 1 TANK DIESEL DELIVERY NEEDED CLEAR 7-22-15 11:45PM T 1 TANK DIESEL DELIVERY NEEDED ALARM 7-21-15 8:18AM T 1 TANK DIESEL DELIVERY NEEDED CLEAR 7-17-15 12:01AM T 1 TANK DIESEL DELIVERY NEEDED ALARM 7-14-15 9:45PM OTHER ISD SENSOR OUT WARN CLEAR 7-12-15 10:02AM OTHER ISD SENSOR OUT WARN ALARM 7-11-15 10:02AM h 2 OTHER FP2: BLEND3 FLOW COLLECT WARN CLEAR 7-11-15 10:00AM SYSTEM PRINTER ERROR CLEAR 7-10-15 12:13PM SYSTEM PAPER OUT CLEAR 7-10-15 12:13PM SYSTEM PAPER OUT ALARM 7-10-15 12:12PM SYSTEM PRINTER ERROR ALARM 7-10-15 12:12PM SYSTEM PRINTER ERROR CLEAR 7-10-15 12:12PM SYSTEM PAPER OUT CLEAR 7-10-15 12:12PM SYSTEM PRINTER ERROR ALARM 7-10-15 10:02AM SYSTEM PAPER OUT ALARM 7-10-15 10:02AM h 2 OTHER FP2: BLEND3 FLOW COLLECT WARN ALARM 7-10-15 10:02AM T 1 TANK DIESEL DELIVERY NEEDED CLEAR 6-27-15 5:29AM T 1 TANK DIESEL DELIVERY NEEDED ALARM 6-25-15 8:05AM T 1 TANK DIESEL DELIVERY NEEDED CLEAR 6-19-15 8:15PM T 1 TANK DIESEL DELIVERY NEEDED ALARM 6-19-15 6:07AM h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN CLEAR 6-15-15 10:00AM h 2 OTHER FP2: BLEND3 FLOW COLLECT WARN CLEAR 6-15-15 10:00AM h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN ALARM 6-14-15 10:01AM h 2 OTHER FP2: BLEND3 FLOW COLLECT WARN ALARM 6-14-15 10:01AM T 1 TANK DIESEL DELIVERY NEEDED CLEAR 6-13-15 9:39AM T 1 TANK DIESEL DELIVERY NEEDED ALARM 6-11-15 5:47AM T 1 TANK DIESEL DELIVERY NEEDED CLEAR 6-04-15 11:49PM T 1 TANK DIESEL DELIVERY NEEDED ALARM 6-03-15 10:55AM T 2 TANK SUPREME DELIVERY NEEDED CLEAR 6-01-15 5:02AM T 2 TANK SUPREME DELIVERY NEEDED ALARM 5-31-15 3:22PM OTHER ISD SENSOR OUT WARN CLEAR 5-29-15 9:14PM SYSTEM PRINTER ERROR CLEAR 5-29-15 11:31AM I20600 SEP 14, 2015 9:05 AM WHITE LANE CHEVRON 2525 WHITE LANE BAKERSFIELD CA 93304 661-832-9781 TANK ALARM HISTORY TANK 1 DIESEL SUDDEN LOSS ALARM OCT 16, 2014 9:07 AM INVALID FUEL LEVEL AUG 6, 2015 8:09 AM JAN 16, 2015 5:36 PM OCT 16, 2014 9:31 AM PROBE OUT OCT 16, 2014 9:30 AM OCT 16, 2014 9:08 AM DELIVERY NEEDED AUG 20, 2015 8:35 AM AUG 12, 2015 9:19 AM AUG 3, 2015 8:51 AM TANK 2 SUPREME HIGH WATER ALARM OCT 16, 2014 9:33 AM SUDDEN LOSS ALARM OCT 16, 2014 9:09 AM HIGH PRODUCT ALARM OCT 16, 2014 9:30 AM INVALID FUEL LEVEL OCT 16, 2014 10:39 AM OCT 16, 2014 9:30 AM PROBE OUT OCT 16, 2014 10:38 AM OCT 16, 2014 9:41 AM OCT 16, 2014 9:38 AM HIGH WATER WARNING OCT 16, 2014 9:33 AM DELIVERY NEEDED SEP 7, 2015 1:49 PM MAY 31, 2015 3:22 PM APR 18, 2015 8:23 AM MAX PRODUCT ALARM OCT 16, 2014 9:30 AM LOW TEMP WARNING OCT 16, 2014 9:39 AM OCT 16, 2014 9:30 AM TANK 3 REGULAR OVERFILL ALARM APR 15, 2015 2:28 AM JAN 9, 2015 6:14 AM NOV 23, 2014 10:12 AM SUDDEN LOSS ALARM OCT 16, 2014 9:12 AM HIGH PRODUCT ALARM OCT 16, 2014 9:25 AM PROBE OUT OCT 16, 2014 9:28 AM OCT 16, 2014 9:12 AM MAX PRODUCT ALARM OCT 16, 2014 9:25 AM I38200 SEP 14, 2015 9:05 AM WHITE LANE CHEVRON 2525 WHITE LANE BAKERSFIELD CA 93304 661-832-9781 PRESSURE LINE LEAK ALARM HISTORY REPORT Q 1:DIESEL OCT 16, 2014 10:44 AM PLLD SHUTDOWN ALARM OCT 16, 2014 10:37 AM PLLD SHUTDOWN ALARM OCT 16, 2014 10:37 AM GROSS LINE FAIL OCT 16, 2014 9:47 AM PLLD SHUTDOWN ALARM OCT 16, 2014 9:46 AM PLLD SHUTDOWN ALARM OCT 17, 2013 10:09 AM PLLD SHUTDOWN ALARM OCT 17, 2013 10:09 AM GROSS LINE FAIL OCT 17, 2013 9:37 AM PLLD SHUTDOWN ALARM OCT 17, 2013 9:30 AM PLLD SHUTDOWN ALARM OCT 17, 2013 9:29 AM PLLD SHUTDOWN ALARM Q 2:SUPREME SEP 10, 2015 10:03 AM PLLD SHUTDOWN ALARM JUL 15, 2015 11:45 AM PLLD SHUTDOWN ALARM JUL 15, 2015 11:45 AM GROSS LINE FAIL OCT 16, 2014 10:44 AM PLLD SHUTDOWN ALARM OCT 16, 2014 10:26 AM PLLD SHUTDOWN ALARM OCT 16, 2014 10:26 AM GROSS LINE FAIL OCT 16, 2014 9:47 AM PLLD SHUTDOWN ALARM OCT 16, 2014 9:44 AM PLLD SHUTDOWN ALARM OCT 16, 2014 9:33 AM PLLD SHUTDOWN ALARM JAN 4, 2014 7:44 AM PLLD SHUTDOWN ALARM Q 3:REGULAR SEP 10, 2015 10:03 AM PLLD SHUTDOWN ALARM JUL 27, 2015 9:22 AM PLLD SHUTDOWN ALARM JUL 27, 2015 9:22 AM GROSS LINE FAIL JUL 26, 2015 12:40 PM PLLD SHUTDOWN ALARM JUL 26, 2015 12:40 PM GROSS LINE FAIL MAR 3, 2015 5:59 PM PLLD SHUTDOWN ALARM NOV 24, 2014 9:32 PM PLLD SHUTDOWN ALARM NOV 24, 2014 9:32 PM GROSS LINE FAIL OCT 16, 2014 10:44 AM PLLD SHUTDOWN ALARM OCT 16, 2014 10:24 AM PLLD SHUTDOWN ALARM I30200 SEP 14, 2015 9:05 AM WHITE LANE CHEVRON 2525 WHITE LANE BAKERSFIELD CA 93304 661-832-9781 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 DIESEL ANN OCT 16, 2014 10:44 AM FUEL ALARM OCT 16, 2014 9:47 AM FUEL ALARM OCT 17, 2013 9:37 AM FUEL ALARM 2 DIESEL STP OCT 16, 2014 10:44 AM SENSOR OUT ALARM OCT 16, 2014 9:46 AM FUEL ALARM OCT 17, 2013 9:37 AM SENSOR OUT ALARM 3 SUPREME ANN OCT 16, 2014 10:44 AM FUEL ALARM OCT 16, 2014 9:47 AM FUEL ALARM OCT 17, 2013 9:37 AM FUEL ALARM 4 SUPREME STP OCT 16, 2014 10:44 AM SENSOR OUT ALARM OCT 16, 2014 9:44 AM FUEL ALARM OCT 17, 2013 9:37 AM SENSOR OUT ALARM 5 REGULAR ANN OCT 16, 2014 10:44 AM FUEL ALARM OCT 16, 2014 9:47 AM FUEL ALARM OCT 17, 2013 9:36 AM FUEL ALARM 6 REGULAR STP JUL 27, 2015 9:24 AM FUEL ALARM MAR 3, 2015 5:59 PM FUEL ALARM OCT 16, 2014 10:44 AM SENSOR OUT ALARM I31600 SEP 14, 2015 9:05 AM WHITE LANE CHEVRON 2525 WHITE LANE BAKERSFIELD CA 93304 661-832-9781 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 PRESS SENSOR 2 CANISTER JUL 11, 2015 7:47 AM SENSOR FAULT ALARM FEB 28, 2014 2:18 PM SENSOR FAULT ALARM FEB 28, 2014 2:08 PM SENSOR FAULT ALARM 4 FM 1-2 5 FM 3-4 6 FM 5-6 7 FM 7-8 8 ATMP PRESSURE I40200 SEP 14, 2015 9:05 AM I40300 SEP 14, 2015 9:05 AM I34200 SEP 14, 2015 9:05 AM I34700 SEP 14, 2015 9:05 AM IV0100 SEP 14, 2015 9:05 AM WHITE LANE CHEVRON 2525 WHITE LANE BAKERSFIELD CA 93304 661-832-9781 ISD ALARM STATUS REPORT EVR TYPE: BALANCE ISD TYPE: 01.02 VAPOR PROCESSOR TYPE: VEEDER-ROOT POLISHER OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% STAGE I TRANSFERS: 0 of 0 NOTEST EVR/ISD PASS TIME :100% VAPOR PROCESSOR :PASS WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 15-09-09 10:02:59 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3 0.56 15-08-10 10:03:42 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 40.63 15-08-09 10:03:38 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 39.28 15-08-08 10:03:43 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 36.86 15-08-07 10:02:31 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 34.70 15-08-06 10:02:59 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 36.13 15-08-05 10:02:06 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 29.88 15-08-04 10:02:16 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 14.86 15-07-11 10:02:36 SENSOR OUT SELFTEST PMC SENSOR FAULT 15-07-10 10:02:45 FLOW PERFORMANCE HOSE BLOCKAGE FP 2 BLEND3 0.56 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 15-09-10 10:03:06 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3 SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 15-09-13 14:42:00 TIME CHANGE DETECTED AT: 15-09-13 14:44:10 15-09-10 11:33:04 COLLECTION TEST HH03 GRADE TEST MANUALLY CLEARED 15-09-10 10:03:06 FLOW PERFORMANCE BLK DISABLED FP 03 BLEND3 15-08-10 16:21:08 CONTAINMENT VAPOR LEAKAGE TEST MANUALLY CLEARED 15-05-29 21:14:22 SENSOR OUT TEST MANUALLY CLEARED 15-05-22 10:02:31 READINESS ISD:PP EVR:PPP ISD & EVR READY 15-05-21 14:56:20 READINESS ISD:PP EVR:NNN EVR READINESS PENDING 15-05-21 14:56:20 ISD STARTUP 15-05-21 14:30:54 ISD SHUTDOWN 15-04-26 10:01:54 READINESS ISD:PP EVR:PPP ISD & EVR READY White lane chevron alarm history after Responses Received: I10200 SEP 14, 2015 11:31 AM WHITE LANE CHEVRON 2525 WHITE LANE BAKERSFIELD CA 93304 661-832-9781 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 UNUSED 9217486 9167974 2 UNUSED 9173110 9131227 3 INTERSTITIAL BD 202003 201944 4 UNUSED 9178500 9130452 5 4 PROBE / G.T. 163228 162877 6 PLLD SENSOR BD 3959 3971 7 7SMARTSENSOR BD 506196 505806 8 UNUSED 9176410 9129169 9 UNUSED 9170611 9122598 10 PLLD POWER BD 99844 99977 11 UNUSED 9176728 9127933 12 UNUSED 9174418 9116864 13 UNUSED 9170765 9119012 14 UNUSED 9172987 9120650 15 UNUSED 9172899 9116864 16 UNUSED 9174242 9116532 COMM 1 RS232 SERIAL BD 14992 15043 COMM 2 REMOTE DISPLAY 27458 27475 COMM 3 ELEC DISP INT. 100698 100723 COMM 4 UNUSED 9174264 9127512 COMM 5 RS485 SERIAL BD 68140 68187 COMM 6 RS232 SERIAL BD 14903 14954 I90200 SEP 14, 2015 11:31 AM SOFTWARE REVISION LEVEL VERSION 329.01 SOFTWARE# 346329-100-B CREATED - 09.01.29.15.44 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD I11100 SEP 14, 2015 11:31 AM WHITE LANE CHEVRON 2525 WHITE LANE BAKERSFIELD CA 93304 661-832-9781 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME Q 3 OTHER REGULAR PLLD SHUTDOWN ALARM CLEAR 9-14-15 11:31AM Q 3 OTHER REGULAR GROSS LINE FAIL CLEAR 9-14-15 11:31AM Q 2 OTHER SUPREME PLLD SHUTDOWN ALARM CLEAR 9-14-15 11:30AM Q 2 OTHER SUPREME GROSS LINE FAIL CLEAR 9-14-15 11:30AM Q 1 OTHER DIESEL PLLD SHUTDOWN ALARM CLEAR 9-14-15 11:27AM Q 1 OTHER DIESEL GROSS LINE FAIL CLEAR 9-14-15 11:27AM Q 1 OTHER DIESEL PLLD SHUTDOWN ALARM ALARM 9-14-15 11:10AM Q 1 OTHER DIESEL GROSS LINE FAIL ALARM 9-14-15 11:10AM Q 2 OTHER SUPREME PLLD SHUTDOWN ALARM ALARM 9-14-15 10:48AM Q 2 OTHER SUPREME GROSS LINE FAIL ALARM 9-14-15 10:48AM Q 3 OTHER REGULAR PLLD SHUTDOWN ALARM ALARM 9-14-15 10:39AM Q 3 OTHER REGULAR GROSS LINE FAIL ALARM 9-14-15 10:39AM Q 3 OTHER REGULAR PLLD SHUTDOWN ALARM CLEAR 9-14-15 10:01AM L 6 OTHER REGULAR STP SENSOR OUT ALARM CLEAR 9-14-15 10:01AM L 5 ANNULAR REGULAR ANN FUEL ALARM CLEAR 9-14-15 10:01AM Q 2 OTHER SUPREME PLLD SHUTDOWN ALARM CLEAR 9-14-15 10:01AM L 4 STP SUMP SUPREME STP SENSOR OUT ALARM CLEAR 9-14-15 10:01AM L 3 ANNULAR SUPREME ANN FUEL ALARM CLEAR 9-14-15 10:01AM Q 1 OTHER DIESEL PLLD SHUTDOWN ALARM CLEAR 9-14-15 10:01AM L 2 STP SUMP DIESEL STP SENSOR OUT ALARM CLEAR 9-14-15 10:01AM L 1 ANNULAR DIESEL ANN FUEL ALARM CLEAR 9-14-15 10:01AM L 3 ANNULAR SUPREME ANN FUEL ALARM ALARM 9-14-15 10:00AM L 6 OTHER REGULAR STP SENSOR OUT ALARM ALARM 9-14-15 10:00AM L 4 STP SUMP SUPREME STP SENSOR OUT ALARM ALARM 9-14-15 10:00AM Q 2 OTHER SUPREME PLLD SHUTDOWN ALARM ALARM 9-14-15 10:00AM L 2 STP SUMP DIESEL STP SENSOR OUT ALARM ALARM 9-14-15 10:00AM L 5 ANNULAR REGULAR ANN FUEL ALARM ALARM 9-14-15 10:00AM Q 3 OTHER REGULAR PLLD SHUTDOWN ALARM ALARM 9-14-15 10:00AM L 1 ANNULAR DIESEL ANN FUEL ALARM ALARM 9-14-15 9:59AM Q 1 OTHER DIESEL PLLD SHUTDOWN ALARM ALARM 9-14-15 9:59AM Q 2 OTHER SUPREME PLLD SHUTDOWN ALARM CLEAR 9-14-15 9:48AM L 3 ANNULAR SUPREME ANN FUEL ALARM CLEAR 9-14-15 9:48AM Q 1 OTHER DIESEL PLLD SHUTDOWN ALARM CLEAR 9-14-15 9:47AM L 1 ANNULAR DIESEL ANN FUEL ALARM CLEAR 9-14-15 9:47AM Q 3 OTHER REGULAR PLLD SHUTDOWN ALARM CLEAR 9-14-15 9:47AM L 5 ANNULAR REGULAR ANN FUEL ALARM CLEAR 9-14-15 9:47AM L 1 ANNULAR DIESEL ANN FUEL ALARM ALARM 9-14-15 9:43AM Q 1 OTHER DIESEL PLLD SHUTDOWN ALARM ALARM 9-14-15 9:43AM L 5 ANNULAR REGULAR ANN FUEL ALARM ALARM 9-14-15 9:43AM Q 3 OTHER REGULAR PLLD SHUTDOWN ALARM ALARM 9-14-15 9:43AM L 3 ANNULAR SUPREME ANN FUEL ALARM ALARM 9-14-15 9:43AM Q 2 OTHER SUPREME PLLD SHUTDOWN ALARM ALARM 9-14-15 9:43AM Q 3 OTHER REGULAR PLLD SHUTDOWN ALARM CLEAR 9-14-15 9:43AM L 5 ANNULAR REGULAR ANN FUEL ALARM CLEAR 9-14-15 9:43AM L 5 ANNULAR REGULAR ANN FUEL ALARM ALARM 9-14-15 9:43AM Q 3 OTHER REGULAR PLLD SHUTDOWN ALARM ALARM 9-14-15 9:43AM Q 3 OTHER REGULAR PLLD SHUTDOWN ALARM CLEAR 9-14-15 9:41AM L 6 OTHER REGULAR STP FUEL ALARM CLEAR 9-14-15 9:41AM L 6 OTHER REGULAR STP FUEL ALARM ALARM 9-14-15 9:41AM Q 3 OTHER REGULAR PLLD SHUTDOWN ALARM ALARM 9-14-15 9:41AM I11200 SEP 14, 2015 11:31 AM WHITE LANE CHEVRON 2525 WHITE LANE BAKERSFIELD CA 93304 661-832-9781 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME h 3 OTHER FP3: BLEND3 FLOW COLLECT WARN CLEAR 9-10-15 10:00AM h 3 OTHER FP3: BLEND3 FLOW COLLECT WARN ALARM 9-09-15 10:02AM T 2 TANK SUPREME DELIVERY NEEDED CLEAR 9-07-15 7:16PM T 2 TANK SUPREME DELIVERY NEEDED ALARM 9-07-15 1:49PM T 1 TANK DIESEL DELIVERY NEEDED CLEAR 8-22-15 4:12AM T 1 TANK DIESEL DELIVERY NEEDED ALARM 8-20-15 8:35AM SYSTEM PRINTER ERROR CLEAR 8-17-15 2:44PM SYSTEM PAPER OUT CLEAR 8-17-15 2:44PM SYSTEM PRINTER ERROR ALARM 8-17-15 2:44PM SYSTEM PAPER OUT ALARM 8-17-15 2:44PM T 1 TANK DIESEL DELIVERY NEEDED CLEAR 8-15-15 3:59AM T 1 TANK DIESEL DELIVERY NEEDED ALARM 8-12-15 9:19AM OTHER ISD VAPOR LEAK WARN CLEAR 8-10-15 4:21PM T 1 TANK DIESEL DELIVERY NEEDED CLEAR 8-06-15 9:07PM T 1 TANK DIESEL INVALID FUEL LEVEL CLEAR 8-06-15 9:05PM T 1 TANK DIESEL INVALID FUEL LEVEL ALARM 8-06-15 8:09AM OTHER ISD VAPOR LEAK WARN ALARM 8-04-15 10:02AM T 1 TANK DIESEL DELIVERY NEEDED ALARM 8-03-15 8:51AM T 1 TANK DIESEL DELIVERY NEEDED CLEAR 7-22-15 11:45PM T 1 TANK DIESEL DELIVERY NEEDED ALARM 7-21-15 8:18AM T 1 TANK DIESEL DELIVERY NEEDED CLEAR 7-17-15 12:01AM T 1 TANK DIESEL DELIVERY NEEDED ALARM 7-14-15 9:45PM OTHER ISD SENSOR OUT WARN CLEAR 7-12-15 10:02AM OTHER ISD SENSOR OUT WARN ALARM 7-11-15 10:02AM h 2 OTHER FP2: BLEND3 FLOW COLLECT WARN CLEAR 7-11-15 10:00AM SYSTEM PRINTER ERROR CLEAR 7-10-15 12:13PM SYSTEM PAPER OUT CLEAR 7-10-15 12:13PM SYSTEM PAPER OUT ALARM 7-10-15 12:12PM SYSTEM PRINTER ERROR ALARM 7-10-15 12:12PM SYSTEM PRINTER ERROR CLEAR 7-10-15 12:12PM SYSTEM PAPER OUT CLEAR 7-10-15 12:12PM SYSTEM PRINTER ERROR ALARM 7-10-15 10:02AM SYSTEM PAPER OUT ALARM 7-10-15 10:02AM h 2 OTHER FP2: BLEND3 FLOW COLLECT WARN ALARM 7-10-15 10:02AM T 1 TANK DIESEL DELIVERY NEEDED CLEAR 6-27-15 5:29AM T 1 TANK DIESEL DELIVERY NEEDED ALARM 6-25-15 8:05AM T 1 TANK DIESEL DELIVERY NEEDED CLEAR 6-19-15 8:15PM T 1 TANK DIESEL DELIVERY NEEDED ALARM 6-19-15 6:07AM h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN CLEAR 6-15-15 10:00AM h 2 OTHER FP2: BLEND3 FLOW COLLECT WARN CLEAR 6-15-15 10:00AM h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN ALARM 6-14-15 10:01AM h 2 OTHER FP2: BLEND3 FLOW COLLECT WARN ALARM 6-14-15 10:01AM T 1 TANK DIESEL DELIVERY NEEDED CLEAR 6-13-15 9:39AM T 1 TANK DIESEL DELIVERY NEEDED ALARM 6-11-15 5:47AM T 1 TANK DIESEL DELIVERY NEEDED CLEAR 6-04-15 11:49PM T 1 TANK DIESEL DELIVERY NEEDED ALARM 6-03-15 10:55AM T 2 TANK SUPREME DELIVERY NEEDED CLEAR 6-01-15 5:02AM T 2 TANK SUPREME DELIVERY NEEDED ALARM 5-31-15 3:22PM OTHER ISD SENSOR OUT WARN CLEAR 5-29-15 9:14PM SYSTEM PRINTER ERROR CLEAR 5-29-15 11:31AM I20600 SEP 14, 2015 11:32 AM WHITE LANE CHEVRON 2525 WHITE LANE BAKERSFIELD CA 93304 661-832-9781 TANK ALARM HISTORY TANK 1 DIESEL SUDDEN LOSS ALARM OCT 16, 2014 9:07 AM INVALID FUEL LEVEL AUG 6, 2015 8:09 AM JAN 16, 2015 5:36 PM OCT 16, 2014 9:31 AM PROBE OUT OCT 16, 2014 9:30 AM OCT 16, 2014 9:08 AM DELIVERY NEEDED AUG 20, 2015 8:35 AM AUG 12, 2015 9:19 AM AUG 3, 2015 8:51 AM TANK 2 SUPREME HIGH WATER ALARM OCT 16, 2014 9:33 AM SUDDEN LOSS ALARM OCT 16, 2014 9:09 AM HIGH PRODUCT ALARM OCT 16, 2014 9:30 AM INVALID FUEL LEVEL OCT 16, 2014 10:39 AM OCT 16, 2014 9:30 AM PROBE OUT OCT 16, 2014 10:38 AM OCT 16, 2014 9:41 AM OCT 16, 2014 9:38 AM HIGH WATER WARNING OCT 16, 2014 9:33 AM DELIVERY NEEDED SEP 7, 2015 1:49 PM MAY 31, 2015 3:22 PM APR 18, 2015 8:23 AM MAX PRODUCT ALARM OCT 16, 2014 9:30 AM LOW TEMP WARNING OCT 16, 2014 9:39 AM OCT 16, 2014 9:30 AM TANK 3 REGULAR OVERFILL ALARM APR 15, 2015 2:28 AM JAN 9, 2015 6:14 AM NOV 23, 2014 10:12 AM SUDDEN LOSS ALARM OCT 16, 2014 9:12 AM HIGH PRODUCT ALARM OCT 16, 2014 9:25 AM PROBE OUT OCT 16, 2014 9:28 AM OCT 16, 2014 9:12 AM MAX PRODUCT ALARM OCT 16, 2014 9:25 AM I38200 SEP 14, 2015 11:32 AM WHITE LANE CHEVRON 2525 WHITE LANE BAKERSFIELD CA 93304 661-832-9781 PRESSURE LINE LEAK ALARM HISTORY REPORT Q 1:DIESEL SEP 14, 2015 11:10 AM PLLD SHUTDOWN ALARM SEP 14, 2015 11:10 AM GROSS LINE FAIL SEP 14, 2015 9:59 AM PLLD SHUTDOWN ALARM SEP 14, 2015 9:43 AM PLLD SHUTDOWN ALARM SEP 14, 2015 9:39 AM PLLD SHUTDOWN ALARM OCT 16, 2014 10:44 AM PLLD SHUTDOWN ALARM OCT 16, 2014 10:37 AM PLLD SHUTDOWN ALARM OCT 16, 2014 10:37 AM GROSS LINE FAIL OCT 16, 2014 9:47 AM PLLD SHUTDOWN ALARM OCT 16, 2014 9:46 AM PLLD SHUTDOWN ALARM Q 2:SUPREME SEP 14, 2015 10:48 AM PLLD SHUTDOWN ALARM SEP 14, 2015 10:48 AM GROSS LINE FAIL SEP 14, 2015 10:00 AM PLLD SHUTDOWN ALARM SEP 14, 2015 9:43 AM PLLD SHUTDOWN ALARM SEP 14, 2015 9:40 AM PLLD SHUTDOWN ALARM SEP 10, 2015 10:03 AM PLLD SHUTDOWN ALARM JUL 15, 2015 11:45 AM PLLD SHUTDOWN ALARM JUL 15, 2015 11:45 AM GROSS LINE FAIL OCT 16, 2014 10:44 AM PLLD SHUTDOWN ALARM OCT 16, 2014 10:26 AM PLLD SHUTDOWN ALARM Q 3:REGULAR SEP 14, 2015 10:39 AM PLLD SHUTDOWN ALARM SEP 14, 2015 10:39 AM GROSS LINE FAIL SEP 14, 2015 10:00 AM PLLD SHUTDOWN ALARM SEP 14, 2015 9:43 AM PLLD SHUTDOWN ALARM SEP 14, 2015 9:43 AM PLLD SHUTDOWN ALARM SEP 14, 2015 9:41 AM PLLD SHUTDOWN ALARM SEP 10, 2015 10:03 AM PLLD SHUTDOWN ALARM JUL 27, 2015 9:22 AM PLLD SHUTDOWN ALARM JUL 27, 2015 9:22 AM GROSS LINE FAIL JUL 26, 2015 12:40 PM PLLD SHUTDOWN ALARM I30200 SEP 14, 2015 11:32 AM WHITE LANE CHEVRON 2525 WHITE LANE BAKERSFIELD CA 93304 661-832-9781 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 DIESEL ANN SEP 14, 2015 9:59 AM FUEL ALARM SEP 14, 2015 9:43 AM FUEL ALARM OCT 16, 2014 10:44 AM FUEL ALARM 2 DIESEL STP SEP 14, 2015 10:00 AM SENSOR OUT ALARM SEP 14, 2015 9:39 AM FUEL ALARM OCT 16, 2014 10:44 AM SENSOR OUT ALARM 3 SUPREME ANN SEP 14, 2015 10:00 AM FUEL ALARM SEP 14, 2015 9:43 AM FUEL ALARM OCT 16, 2014 10:44 AM FUEL ALARM 4 SUPREME STP SEP 14, 2015 10:00 AM SENSOR OUT ALARM SEP 14, 2015 9:40 AM FUEL ALARM OCT 16, 2014 10:44 AM SENSOR OUT ALARM 5 REGULAR ANN SEP 14, 2015 10:00 AM FUEL ALARM SEP 14, 2015 9:43 AM FUEL ALARM SEP 14, 2015 9:43 AM FUEL ALARM 6 REGULAR STP SEP 14, 2015 10:00 AM SENSOR OUT ALARM SEP 14, 2015 9:41 AM FUEL ALARM JUL 27, 2015 9:24 AM FUEL ALARM I31600 SEP 14, 2015 11:32 AM WHITE LANE CHEVRON 2525 WHITE LANE BAKERSFIELD CA 93304 661-832-9781 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 PRESS SENSOR 2 CANISTER JUL 11, 2015 7:47 AM SENSOR FAULT ALARM FEB 28, 2014 2:18 PM SENSOR FAULT ALARM FEB 28, 2014 2:08 PM SENSOR FAULT ALARM 4 FM 1-2 5 FM 3-4 6 FM 5-6 7 FM 7-8 8 ATMP PRESSURE I40200 SEP 14, 2015 11:32 AM I40300 SEP 14, 2015 11:32 AM I34200 SEP 14, 2015 11:32 AM I34700 SEP 14, 2015 11:32 AM IV0100 SEP 14, 2015 11:32 AM WHITE LANE CHEVRON 2525 WHITE LANE BAKERSFIELD CA 93304 661-832-9781 ISD ALARM STATUS REPORT EVR TYPE: BALANCE ISD TYPE: 01.02 VAPOR PROCESSOR TYPE: VEEDER-ROOT POLISHER OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% STAGE I TRANSFERS: 0 of 0 NOTEST EVR/ISD PASS TIME :100% VAPOR PROCESSOR :PASS WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 15-09-09 10:02:59 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3 0.56 15-08-10 10:03:42 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 40.63 15-08-09 10:03:38 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 39.28 15-08-08 10:03:43 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 36.86 15-08-07 10:02:31 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 34.70 15-08-06 10:02:59 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 36.13 15-08-05 10:02:06 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 29.88 15-08-04 10:02:16 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 14.86 15-07-11 10:02:36 SENSOR OUT SELFTEST PMC SENSOR FAULT 15-07-10 10:02:45 FLOW PERFORMANCE HOSE BLOCKAGE FP 2 BLEND3 0.56 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 15-09-10 10:03:06 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3 SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 15-09-14 10:08:21 READINESS ISD:PP EVR:NNN EVR READINESS PENDING 15-09-14 10:08:21 ISD STARTUP 15-09-14 10:06:56 ISD SHUTDOWN 15-09-13 14:42:00 TIME CHANGE DETECTED AT: 15-09-13 14:44:10 15-09-10 11:33:04 COLLECTION TEST HH03 GRADE TEST MANUALLY CLEARED 15-09-10 10:03:06 FLOW PERFORMANCE BLK DISABLED FP 03 BLEND3 15-08-10 16:21:08 CONTAINMENT VAPOR LEAKAGE TEST MANUALLY CLEARED 15-05-29 21:14:22 SENSOR OUT TEST MANUALLY CLEARED 15-05-22 10:02:31 READINESS ISD:PP EVR:PPP ISD & EVR READY 15-05-21 14:56:20 READINESS ISD:PP EVR:NNN EVR READINESS PENDING SWRCB, January 2006 Spill Bucket Testing Report Form This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printouts from tests (if applicable), should be provided to the facility owner/operator forsubmittal to the local regulatory agency. 1.FACILITY INFORMATION Facility Name:Date of Testing: Facility Address: Facility Contact:Phone: Date Local Agency Was Notified of Testing : Name of Local Agency Inspector (if present during testing): 2.TESTING CONTRACTOR INFORMATION Company Name:Confidence UST Services, Inc. Technician Conducting Test: Credentials1:CSLB Contractor ICC Service Tech. SWRCB Tank Tester Other (Specify) License Number(s):CSLB#804904 ICC# 3.SPILL BUCKET TESTING INFORMATION Test Method Used:Hydrostatic Vacuum Other Test Equipment Used:Lake TestEquipment Resolution:0.0625” Identify Spill Bucket (By Tank Number, Stored Product, etc.) 1234 Bucket Installation Type: Direct Bury Contained in Sump Direct Bury Contained in Sump Direct Bury Contained in Sump Direct Bury Contained in Sump Bucket Diameter: Bucket Depth: Wait time between applying vacuum/water and start of test: Test Start Time (TI): Initial Reading (RI): Test End Time (TF): Final Reading (RF): Test Duration (TF – TI): Change in Reading (RF -RI): Pass/Fail Threshold or Criteria: Test Result: Pass Fail Pass Fail Pass Fail Pass Fail Comments –(include information on repairs made prior to testing, and recommended follow-up for failed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements. Technician’s Signature:________________________________________________ Date:_________ 1 State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements may be more stringent. Chevron 09/14/2014 2525WhiteLane Bakersfield,CA93304 BassemAzzi(805)217-0610 9/1/15 Kris Karns AustinSterling 8339953-UT Regular 12.00" 13.00" 5min. 9:30 am 7.25" 10:30 am 7.25" 1hour 0.00" 0.0625" Super 12.00" 13.50" 5min. 9:30 am 7.50" 10:30 am 7.50" 1hour 0.00" 0.0625"0.0625" Diesel 12.00" 10.50" 5min. 9:30 am 5.00 10:30 am 5.00" 1hour 0.00" 09/14/2014