HomeMy WebLinkAboutFMC 2015MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State of CaliforniaAuthority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each
monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner/operator.
The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date.
A.General Information
Facility Name:Bldg. No.:
Site Address:City:Zip:
Facility Contact Person: Contact Phone No.:
Make/Model of Monitoring System:Date of Testing/Servicing:
B.Inventory of Equipment Tested/Certified
Check the appropriate boxes to indicate specific equipment inspected/serviced:
Tank ID:Tank ID:
In-Tank Gauging Probe.Model:In-Tank Gauging Probe.Model:
Annular Space or Vault Sensor.Model:Annular Space or Vault Sensor.Model:
Piping Sump / Trench Sensor(s).Model:Piping Sump / Trench Sensor(s).Model:
Fill Sump Sensor(s).Model:Fill Sump Sensor(s).Model:
Mechanical Line Leak Detector.Model:Mechanical Line Leak Detector.Model:
Electronic Line Leak Detector.Model:Electronic LineLeak Detector.Model:
Tank Overfill / High-Level Sensor.Model:Tank Overfill / High-Level Sensor.Model:
Other (specify equipment type and model in Section E on Page 2).Other (specify equipment type and model in Section E on Page 2).
Tank ID:Tank ID:
In-Tank Gauging Probe.Model:In-Tank Gauging Probe.Model:
Annular Space or Vault Sensor.Model:Annular Space or Vault Sensor.Model:
Piping Sump / TrenchSensor(s).Model:Piping Sump / Trench Sensor(s).Model:
Fill Sump Sensor(s).Model:Fill Sump Sensor(s).Model:
Mechanical Line Leak Detector.Model:Mechanical Line Leak Detector.Model:
Electronic Line Leak Detector.Model:Electronic Line Leak Detector.Model:
Tank Overfill / High-Level Sensor.Model:Tank Overfill / High-Level Sensor.Model:
Other (specify equipment type and model in Section E on Page 2).Other (specify equipment type and model in Section E on Page 2).
Dispenser ID:Dispenser ID:
Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model:
Shear Valve(s).Shear Valve(s).
Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s).
Dispenser ID:Dispenser ID:
Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model:
Shear Valve(s).Shear Valve(s).
Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s).
Dispenser ID:Dispenser ID:
Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model:
Shear Valve(s).Shear Valve(s).
Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s).
*If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C.Certification -I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers’
guidelines. Attached to this Certification is information (e.g. manufacturers' checklists)necessary to verify that this information is
correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also
attached a copy of the report;(check all that apply):System set-up Alarm history report
Technician Name (print):Signature:
Certification No.:License. No.:804904
Testing Company Name:Confidence UST Services, Inc.Phone No.:(800)339-9930
Site Address:Date of Testing/Servicing:
Page 1 of 3
#7773Fastrip#31
3501Mt.VernonAvenueBakersfield93306
OmeroGarcia (661)393-7000
Veeder-RootTLS-350 08/04/2015
12,000gal.Regular
847390-107
794390-420
794380-208
794380-208
FX1V
847390-107
12,000gal.Super
847390-107
794390-420
794380-208
794380-208
FX1V
847390-107
12,000gal.Diesel
847390-107
794390-420
794380-208
794380-208
FX1DV
847390-107
1-2
794380-208
3-4
794380-208
5-6
794380-208 794380-208
7-8
TransitionSump
794380-208
DustinReese
B43426
3501Mt.VernonAvenue Bakersfield,CA93306 08/04/2015
794380-208
794380-208
794380-208
Monitoring System Certification
D.Results of Testing/Servicing
Software Version Installed:
Complete the following checklist:
Yes No*Isthe audible alarm operational?
Yes No*Is the visual alarm operational?
Yes No*Were all sensors visually inspected, functionally tested, and confirmed operational?
Yes No*Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will
not interfere with their proper operation?
Yes No*
N/A
If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem)
operational?
Yes No*
N/A
For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate
positive shut-down? (Check all that apply) Sump/Trench Sensors; Dispenser Containment Sensors.
Did you confirm positive shut-down due to leaks and sensor failure/disconnection? Yes; No.
Yes No*
N/A
For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no
mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank
fill point(s) and operating properly? If so, at what percent oftank capacity does the alarm trigger? %
Yes*NoWas any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced
and list the manufacturer name and model for all replacement parts in Section E, below.
Yes*NoWas liquid found inside any secondary containment systems designed as dry systems? (Check all that apply)
Product; Water. If yes, describe causes in Section E, below.
Yes No*Was monitoring system set-up reviewed to ensure proper settings? Attach set up reports, if applicable
Yes No*Is all monitoring equipment operational per manufacturer’s specifications?
* In Section E below, describe how and when these deficiencies were or will be corrected.
E.Comments:
Page 2 of 3
331.01
90
Monitoring System Certification
F.In-Tank Gauging / SIR Equipment: Check this box if tank gauging is used only for inventory control.
Check this box if no tank gauging or SIR equipment is installed.
This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
Yes No*Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
Yes No*Were all tank gauging probes visually inspected for damage and residue buildup?
Yes No*Was accuracy of system product level readings tested?
Yes No*Was accuracy of system water level readings tested?
Yes No*Were all probes reinstalled properly?
Yes No*Were all items on the equipment manufacturer’s maintenance checklist completed?
* In the Section H, below, describe how and when these deficiencies were or will be corrected.
G.Line Leak Detectors (LLD):Check this box if LLDs are not installed.
Complete the following checklist:
Yes No*
N/A
For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance?
(Check all that apply)Simulated leak rate: 3 g.p.h.; 0.1 g.p.h ; 0.2 g.p.h.
Yes No*Were all LLDs confirmed operational and accurate within regulatory requirements?
Yes No*Was the testing apparatus properly calibrated?
Yes No*
N/A
For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
Yes No*
N/A
For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak?
Yes No*
N/A
For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled
or disconnected?
Yes No*
N/A
For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions
or fails a test?
Yes No*
N/A
For electronic LLDs, have all accessible wiring connections been visually inspected?
Yes No*Were all items on the equipment manufacturer’s maintenance checklist completed?
* In the Section H, below, describe how and when these deficiencies were or will be corrected.
H.Comments:
Page 3 of 3
Leak Detector Test Results Sheet
Customer Address: Work Order: Site Address:
Test Date:
Site Contact: Phone:
Technician: Phone: 800-339-9930 ICC No.:
Product Type LLD Type Model Serial No. Check
Valve
Holding
Pressure
Bleed
Off ML.
Leak
Rate
Tested:
Pass/Fail
3 gph @
10 psi
3 gph @
10 psi
3 gph @
10 psi
3 gph @
10 psi
3 gph @
10 psi
3 gph @
10 psi
3 gph @
10 psi
3 gph @
10 psi
Technician Name: Technician No.:
Signature: Date:
JamiesonHill
P.O.Box82515
Bakersfield,CA93380-2515
34919A
08/04/2015
8216722-UT
Regular Mechanical FX1V
DustinReese
(661)393-7000OmeroGarcia
Bakersfield,CA93306
3501Mt.VernonAvenue
#7773Fastrip#31
40411-2525 18psi 110ml Pass
FX1VMechanicalPremium 10613-4710 15psi 189ml Pass
FX1DVMechanicalDiesel 20707-5762 12psi98ml Pass
DustinReese 8216722-UT
08/04/2015
3501 MT Vernon, Fastrip 773
System Setup:
Responses Received:
200
FASTRIP 773
3501 MT VERNON
BAKERSFIELD CA
AUG 4, 2015 9:08 AM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 UNLEADED 8723 75.39 0.8 92.2 3339
2 DIESEL 2824 31.56 0.0 88.6 9238
3 PREMIUM 4772 46.36 0.0 90.3 7290
I90500
AUG 4, 2015 9:08 AM
SOFTWARE REVISION LEVEL
VERSION 331.01
SOFTWARE# 346331-100-B
CREATED-11.03.22.16.28
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I50500
AUG 4, 2015 9:08 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50201
AUG 4, 2015 9:08 AM
SHIFT TIME 1 : DISABLED
I50202
AUG 4, 2015 9:08 AM
SHIFT TIME 2 : DISABLED
I50203
AUG 4, 2015 9:08 AM
SHIFT TIME 3 : DISABLED
I50204
AUG 4, 2015 9:08 AM
SHIFT TIME 4 : DISABLED
I54600
AUG 4, 2015 9:08 AM
TANK PER TST NEEDED WRN: DISABLED
I54900
AUG 4, 2015 9:08 AM
TANK ANN TST NEEDED WRN: DISABLED
I55300
AUG 4, 2015 9:08 AM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
AUG 4, 2015 9:08 AM
LINE PER TST NEEDED WRN: DISABLED
I55900
AUG 4, 2015 9:08 AM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
AUG 4, 2015 9:08 AM
PRINT TC VOLUMES
ENABLED
I50E00
AUG 4, 2015 9:08 AM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
AUG 4, 2015 9:08 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
AUG 4, 2015 9:08 AM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
AUG 4, 2015 9:08 AM
DAYLIGHT SAVING TIME
DISABLED
I51B00
AUG 4, 2015 9:08 AM
I51600
AUG4, 2015 9:08 AM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
AUG 4, 2015 9:08 AM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
AUG 4, 2015 9:08 AM
TANK CHART SECURITY
DISABLED
I5BD00
AUG 4, 2015 9:08 AM
CUSTOM ALARM LABELS
DISABLED
I56000
AUG 4, 2015 9:08 AM
MASS/DENSITY
DISABLED
I88101
AUG 4, 2015 9:08 AM
PORT SETTINGS:
COMM BOARD : 1 (EDIM )
RS-232 SECURITY
CODE : DISABLED
I88102
AUG 4, 2015 9:08 AM
PORT SETTINGS:
COMM BOARD : 2 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88103
AUG 4, 2015 9:08 AM
PORT SETTINGS:
COMM BOARD : 3 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88104
AUG 4, 2015 9:08 AM
I88105
AUG 4, 2015 9:08 AM
I88106
AUG 4, 2015 9:08 AM
I52000
AUG 4, 2015 9:08 AM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 ON DATE ??? 4, 2015 DISABLED
2ON DATE ??? 4, 2015 DISABLED
3 ON DATE ??? 4, 2015 DISABLED
4 ON DATE ??? 4, 2015 DISABLED
5 ON DATE ??? 4, 2015 DISABLED
6ON DATE ??? 4, 2015 DISABLED
7 ON DATE ??? 4, 2015 DISABLED
8 ON DATE ??? 4, 2015 DISABLED
I60100
AUG 4, 2015 9:08 AM
TANK CONFIGURATION
DEVICE LABELCONFIGURED
1 UNLEADED ON
2 DIESEL ON
3 PREMIUM ON
4 OFF
I60200
AUG 4, 2015 9:08 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1UNLEADED
2 DIESEL
3 PREMIUM
4
I60300
AUG 4, 2015 9:08 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 UNLEADED 1
2 DIESEL 2
3 PREMIUM 3
4 4
I60900
AUG 4, 2015 9:08 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 UNLEADED 0.000700
2 DIESEL0.000450
3 PREMIUM 0.000700
4 0.000000
I60700
AUG 4, 2015 9:08 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 UNLEADED 111.00
2 DIESEL 111.00
3 PREMIUM 111.00
4 0.00
I60A00
AUG 4, 2015 9:08 AM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED
1 PT 12062 2 DIESEL 1 PT 12062 3 PREMIUM
1 PT 12062 4 1 PT 0
I60400
AUG 4, 2015 9:08 AM
TANK FULL VOLUME
TANK PRODUCT LABELGALLONS
1 UNLEADED 12062
2 DIESEL 12062
3 PREMIUM 12062
4 0
I60500
AUG 4, 2015 9:08 AM
TANK 4 POINT VOLUMES
TANK PRODUCT LABELGALLONS
1 UNLEADED 12062 0 0 0
2 DIESEL 12062 0 0 0
3 PREMIUM 12062 0 0 0
40 0 0 0
I60600
AUG 4, 2015 9:08 AM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12062 0 0 0
0 00 0
0 0 0 0
0 0 0 0
0 0 0 0
2 DIESEL 120620 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
3 PREMIUM 12062 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
4 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
I61500
AUG 4, 2015 9:08 AM
TANK PRODUCT LABEL METER DATA
1 UNLEADED NO
2 DIESEL NO
3 PREMIUM NO
4 NO
I62F00
AUG 4, 2015 9:08 AM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABELFLOAT SIZE:
1 UNLEADED 4.0 IN.
2 DIESEL 4.0 IN.
3 PREMIUM 4.0 IN.
I62700
AUG 4, 2015 9:08 AM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABELINCHES
1 UNLEADED 2.0
2 DIESEL 2.0
3 PREMIUM 2.0
I64200
AUG 4, 2015 9:08 AM
WATER ALARM FILTER
TANK PRODUCT LABEL
1 UNLEADED LOW
2 DIESELLOW
3 PREMIUM LOW
I62400
AUG 4, 2015 9:08 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 3.0
2 DIESEL 3.0
3 PREMIUM 3.0
I62800
AUG 4, 2015 9:08 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12062
2 DIESEL 12062
3 PREMIUM 12062
4 0
I62300
AUG 4, 2015 9:08 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 10855
2 DIESEL 10855
3 PREMIUM 10855
4 0
I62200
AUG 4, 2015 9:08 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 11459
2 DIESEL 11459
3 PREMIUM 11459
4 0
I62900
AUG 4, 2015 9:08 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1809
2 DIESEL1809
3 PREMIUM 1809
4 0
I62100
AUG 4, 2015 9:08 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 500
2 DIESEL 500
3 PREMIUM 500
4 0
I62600
AUG 4, 2015 9:08 AM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 99
2 DIESEL 99
3 PREMIUM 99
4 99
I62500
AUG 4, 2015 9:08 AM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 99
2 DIESEL 99
3 PREMIUM 99
4 99
I60800
AUG 4, 2015 9:08 AM
TANK TILT
TANK PRODUCT LABEL INCHES
1 UNLEADED 0.00
2 DIESEL 0.00
3 PREMIUM 0.00
4 0.00
I60B00
AUG 4, 2015 9:08 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
AUG 4, 2015 9:08 AM
TANK STICK HEIGHT OFFSET
TANK PRODUCTLABEL INCHES
1 UNLEADED 0.00
2 DIESEL 0.00
3 PREMIUM 0.00
4 0.00
I61200
AUG 4, 2015 9:08 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 UNLEADED NONE NONE
2 DIESEL NONE NONE
3 PREMIUMNONE NONE
4 NONE NONE
I63600
AUG 4, 2015 9:08 AM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 120
2 DIESEL 120
3 PREMIUM 120
4 0
I62A00
AUG 4, 2015 9:08 AM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 120
2 DIESEL 120
3 PREMIUM 120
4 0
I62C00
AUG 4, 2015 9:08 AM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABELPERIODIC TEST TYPE
1 UNLEADED STANDARD
2 DIESEL STANDARD
3 PREMIUM STANDARD
4 STANDARD
I62D00
AUG 4, 2015 9:08 AM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 UNLEADED GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
2 DIESELGROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
3 PREMIUM GROSS TEST FAIL ALARMDISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
4 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
AUG 4, 2015 9:08 AM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 UNLEADED OFF OFF
2 DIESEL OFF OFF
3 PREMIUM OFF OFF
4 OFF OFF
I63000
AUG 4, 2015 9:08 AM
IN-TANK LEAK TEST NOTIFY
TANKPRODUCT LABEL TANK TEST NOTIFY:
1 UNLEADED OFF
2 DIESEL OFF
3 PREMIUM OFF
4 OFF
I63200
AUG 4, 2015 9:08 AM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 UNLEADED OFF
2 DIESEL OFF
3 PREMIUM OFF
4 OFF
I61000
AUG 4, 2015 9:08 AM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 UNLEADED 1
2 DIESEL 1
3 PREMIUM 1
4 1
I63A00
AUG 4, 2015 9:08 AM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 UNLEADED 10.00%
2 DIESEL 10.00%
3 PREMIUM 10.00%
4 10.00%
I61100
AUG 4, 2015 9:08 AM
LEAK TEST METHOD
------------
TEST ON DATE : ALL TANK
MAR 22, 2011
START TIME : DISABLED
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
I61300
AUG 4, 2015 9:08 AM
CSLD PROBABLITY OF DETECTION
I61400
AUG 4, 2015 9:08 AM
CSLD CLIMATE FACTOR
I61600
AUG 4, 2015 9:08 AM
TANK PRODUCT LABEL CAL UPDATE
1 UNLEADED IMMEDIATE
2 DIESEL IMMEDIATE
3 PREMIUM IMMEDIATE
4IMMEDIATE
I61A00
AUG 4, 2015 9:08 AM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 UNLEADED DISABLED
2 DIESEL DISABLED
3 PREMIUM DISABLED
4 DISABLED
I61B00
AUG 4, 2015 9:08 AM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
I61C00
AUG 4, 2015 9:08 AM
CSLD REPORT ONLY
I62B00
AUG 4, 2015 9:08 AM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 UNLEADED ??? 0, 0
2 DIESEL ??? 0, 0
3 PREMIUM ??? 0, 0
4 ??? 0, 0
I63300
AUG 4, 2015 9:08 AM
LEAK TEST REPORT FORMAT: NORMAL
I63400
AUG 4, 2015 9:08 AM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 0
2 DIESEL 0
3 PREMIUM 0
4 0
I63500
AUG 4, 2015 9:08 AM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1
2 DIESEL 1
3 PREMIUM 1
4 1
I63900
AUG 4, 2015 9:08 AM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1 UNLEADED
END FACTOR: NONE
2 DIESEL
END FACTOR: NONE
3 PREMIUM
END FACTOR: NONE
4
END FACTOR: NONE
I78000
AUG 4, 2015 9:08 AM
I77700
AUG 4, 2015 9:08 AM
I77800
AUG 4, 2015 9:08 AM
I78C00
AUG 4, 2015 9:08 AM
I78300
AUG 4, 2015 9:08 AM
I78F00
AUG 4, 2015 9:08 AM
I78700
AUG 4, 2015 9:09 AM
I70200
AUG 4, 2015 9:09 AM
LIQUID LABEL
DEVICE LABEL
1 UNL ANN
2 DSL ANN
3 PNL ANM
4 UNL STP
5 DSL STP
6 PNL STP
7
8
9 DISP 1-2
10 DISP 3-4
11 DISP 5-6
12 DISP 7-8
13 TRANS SUNP
14
15
16
I70300
AUG 4, 2015 9:09 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 UNL ANN TRI-STATE (SINGLE FLOAT)
2 DSL ANN TRI-STATE (SINGLE FLOAT)
3 PNL ANM TRI-STATE (SINGLE FLOAT)
4 UNL STP TRI-STATE (SINGLE FLOAT)
5 DSL STP TRI-STATE (SINGLE FLOAT)
6 PNL STP TRI-STATE (SINGLE FLOAT)
7 TRI-STATE (SINGLE FLOAT)
8 TRI-STATE (SINGLE FLOAT)
9 DISP 1-2 TRI-STATE (SINGLE FLOAT)
10 DISP 3-4 TRI-STATE (SINGLE FLOAT)
11 DISP 5-6 TRI-STATE (SINGLE FLOAT)
12 DISP 7-8 TRI-STATE (SINGLE FLOAT)
13 TRANS SUNP TRI-STATE (SINGLE FLOAT)
14 TRI-STATE (SINGLE FLOAT)
15 TRI-STATE (SINGLE FLOAT)
16 TRI-STATE (SINGLE FLOAT)
I70400
AUG 4, 2015 9:09 AM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 UNL ANNANNULAR SPACE
2 DSL ANN ANNULAR SPACE
3 PNL ANM ANNULAR SPACE
4 UNL STP STP SUMP
5 DSL STP STP SUMP
6 PNL STP STP SUMP
7OTHER SENSORS
8 OTHER SENSORS
9 DISP 1-2 DISPENSER PAN
10 DISP 3-4 DISPENSER PAN
11 DISP 5-6 DISPENSER PAN
12 DISP 7-8 DISPENSER PAN
13 TRANS SUNP PIPING SUMP
14 OTHER SENSORS
15 OTHER SENSORS
16 OTHER SENSORS
I74200
AUG 4, 2015 9:09 AM
I74300
AUG 4, 2015 9:09 AM
I74400
AUG4, 2015 9:09 AM
I74700
AUG 4, 2015 9:09 AM
I74800
AUG 4, 2015 9:09 AM
I74900
AUG 4, 2015 9:09 AM
I7BC00
AUG 4, 2015 9:09 AM
I80200
AUG 4, 2015 9:09 AM
I80300
AUG 4, 2015 9:09 AM
I80400
AUG 4, 2015 9:09 AM
I80700
AUG4, 2015 9:09 AM
RELAY LABEL
DEVICE LABEL
1 UNL
2 PNL
3 DSL
4 OVERFILL ALARM
I80900
AUG 4, 2015 9:09 AM
RELAY ORIENTATION
RELAY DESIGNATIONORIENTATION
1 UNL NORMALLY OPEN
2 PNL NORMALLY OPEN
3 DSL NORMALLY CLOSED
4 OVERFILL ALARM NORMALLY OPEN
I80B00
AUG 4, 2015 9:09 AM
RELAY TANK ASSIGNMENT
RELAYDESIGNATION TANK
1 UNL 1
2 PNL 3
3 DSL 2
4 OVERFILL ALARM NONE
I80A00
AUG 4, 2015 9:09 AM
RELAY TYPE
RELAY DESIGNATION TYPE
1 UNL PUMP CONTROL OUTPUT
2 PNL PUMP CONTROL OUTPUT
3 DSL STANDARD
4 OVERFILL ALARM STANDARD
I80C00
AUG 4, 2015 9:09 AM
I80800
AUG 4, 2015 9:09 AM
RELAY SETUP REPORT
R 1:UNL
TYPE:
PUMP CONTROL OUTPUT
TANK #: 1
LIQUID SENSOR ALMS
L 4:FUEL ALARM
L 9:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L13:FUEL ALARM
L 4:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L 4:SHORT ALARM
L 9:SHORT ALARM
L10:SHORT ALARM
L11:SHORT ALARM
L12:SHORT ALARM
L13:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 2:PNL
TYPE:
PUMP CONTROL OUTPUT
TANK #: 3
LIQUID SENSOR ALMS
L 6:FUEL ALARM
L 9:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L13:FUEL ALARM
L 6:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L 6:SHORT ALARM
L 9:SHORT ALARM
L10:SHORT ALARM
L11:SHORT ALARM
L12:SHORT ALARM
L13:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 3:DSL
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: 2
LIQUID SENSOR ALMS
L 5:FUEL ALARM
L10:FUEL ALARM
L12:FUEL ALARM
L13:FUEL ALARM
L 5:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L 5:SHORT ALARM
L10:SHORT ALARM
L12:SHORT ALARM
L13:SHORT ALARM
R 4:OVERFILL ALARM
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
IN-TANK ALARMS
ALL:OVERFILL ALARM
ALL:HIGH PRODUCT ALARM
ALL:MAX PRODUCT ALARM
I79000
AUG4, 2015 9:09 AM
EDIM:1 VR:349634-003-C TD:06.05.11.11.15
I79100
AUG 4, 2015 9:09 AM
I72300
AUG 4, 2015 9:09 AM
FASTRIP 773
3501 MT VERNON
BAKERSFIELD CA
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01PS 1-2 VAPOR PRESSURE
02 FM 1-2 AIR FLOW METER
03 FM 3-4 AIR FLOW METER
04 FM 5-6 AIR FLOW METER
05 FM 7-8 AIR FLOW METER
06UNKNOWN
07 UNKNOWN
08 UNKNOWN
09 UNKNOWN
10 UNKNOWN
11 UNKNOWN
12 UNKNOWN
13UNKNOWN
14 UNKNOWN
15 UNKNOWN
16 UNKNOWN
17 UNKNOWN
18 UNKNOWN
19UNKNOWN
20 UNKNOWN
21 UNKNOWN
22 UNKNOWN
23 UNKNOWN
24 UNKNOWN
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38UNKNOWN
39 UNKNOWN
40 UNKNOWN
I72A00
AUG 4, 2015 9:09 AM
VACUUM SENSOR VOLUME
DEVICE LABEL VOLUME
IV4E00
AUG 4, 2015 9:09 AM
FASTRIP 773
3501 MT VERNON
BAKERSFIELD CA
EVR/ISD SETUP
TYPE: VACUUM ASSIST
VACUUM ASSIST TYPE: HEALY VAC
IV4F00
AUG 4, 2015 9:09 AM
FASTRIP 773
3501 MT VERNON
BAKERSFIELD CA
NOZZLE A/L RANGE
A/L RATIO: 0.95 -1.15
IV4000
AUG 4, 2015 9:09 AM
FASTRIP 773
3501 MT VERNON
BAKERSFIELD CA
VAPOR PROCESSOR TYPE
NONE
IV4700
AUG 4, 2015 9:09 AM
FASTRIP 773
3501 MT VERNON
BAKERSFIELD CA
ASSESSMENT TIME
START TIME: 10:00 AM
TIME DELAY MINUTES: 1
IV5200
AUG 4, 2015 9:09 AM
FASTRIP 773
3501 MT VERNON
BAKERSFIELD CA
ACCEPT HIGH ORVR: NO
IV4A00
AUG 4, 2015 9:09 AM
FASTRIP 773
3501 MT VERNON
BAKERSFIELD CA
ISD HOSE TABLE
HOSE FP FP AFM HOSE
ID ID LABEL ID LABEL
01 01 01 01 BLEND3
02 02 02 01 BLEND3
03 03 03 02 BLEND3
04 04 04 02 BLEND3
05 05 05 03 BLEND3
06 06 06 03 BLEND3
07 07 07 04 BLEND3
08 08 08 04 BLEND3
IV4B00
AUG 4, 2015 9:09 AM
FASTRIP 773
3501 MT VERNON
BAKERSFIELD CA
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H4
01 01 02/01 03/01 09/01 xx/xx
02 01 02/02 03/02 09/02 xx/xx
03 02 02/03 03/03 09/03 xx/xx
04 02 02/04 03/04 09/04 xx/xx
05 03 02/0503/05 09/05 xx/xx
06 03 02/06 03/06 09/06 xx/xx
07 04 02/07 03/07 09/07 xx/xx
08 04 02/08 03/08 09/08 xx/xx
IV4900
AUG 4, 2015 9:09 AM
FASTRIP 773
3501 MT VERNON
BAKERSFIELD CA
LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4
IV1000
AUG 4, 2015 9:09 AM
ISD VERSION: 01.04
Fastrip 773 Mt Vernon
Alarm Hist Before:
Responses Received:
I10200
AUG 4, 2015 9:12 AM
FASTRIP 773
3501 MT VERNON
BAKERSFIELD CA
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 7SMARTSENSOR BD 511865 507928
2 INTERSTITIAL BD 202542 201791
3 4 PROBE / G.T. 162119 161837
4 INTERSTITIAL BD 201727 201334
5UNUSED 9875362 9607131
6 UNUSED 9851759 9599414
7 UNUSED 9841100 9597967
8 UNUSED 9837166 9597265
9 STP SENSE BOARD 33186 33191
10 RELAY BOARD 15057 15080
11 UNUSED 9842904 9603899
12 UNUSED 9835121 9595459
13 UNUSED 9831462 9601970
14 UNUSED 9830933 9595613
15 UNUSED 9823108 9594451
16 UNUSED 9829030 9597586
COMM 1 ELEC DISP INT. 101235 101307
COMM 2 RS232 SERIAL BD 14929 14926
COMM 3 RS232 SERIAL BD 14972 14992
COMM 4 UNUSED 9844194 9602672
COMM 5 UNUSED 9827613 9598463
COMM 6 UNUSED 9827507 9591053
I90200
AUG 4, 2015 9:12 AM
SOFTWARE REVISION LEVEL
VERSION 331.01
SOFTWARE# 346331-100-B
CREATED-11.03.22.16.28
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
AUG 4, 2015 9:12 AM
FASTRIP 773
3501 MT VERNON
BAKERSFIELD CA
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATEDATE TIME
L 1 ANNULAR UNL ANN FUEL ALARM CLEAR 7-28-15 2:33PM
L 1 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 7-28-15 2:31PM
L 1 ANNULAR UNL ANN FUEL ALARM ALARM 7-28-15 2:31PM
L 1ANNULAR UNL ANN SENSOR OUT ALARM ALARM 7-28-15 2:30PM
L 1 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 7-28-15 2:29PM
L 1 ANNULAR UNL ANN SENSOR OUT ALARM ALARM 7-28-15 2:24PM
L 1 ANNULAR UNL ANN FUEL ALARM CLEAR 7-28-15 2:24PM
L 3 ANNULAR PNL ANM FUEL ALARM CLEAR 7-28-15 2:19PM
L 3 ANNULAR PNL ANM FUEL ALARM ALARM 7-28-15 2:17PM
L 3 ANNULAR PNL ANMFUEL ALARM CLEAR 7-28-15 2:14PM
L 3 ANNULAR PNL ANM FUEL ALARM ALARM 7-28-15 2:14PM
L 3 ANNULAR PNL ANM FUEL ALARM CLEAR 7-28-15 2:14PM
L 1 ANNULAR UNL ANN FUEL ALARMALARM 7-28-15 2:04PM
E 1 OTHER COMMUNICATION ALARM CLEAR 7-28-15 1:58PM
L 3 ANNULAR PNL ANM FUEL ALARM ALARM 7-28-15 1:57PM
E 1 OTHER COMMUNICATION ALARM ALARM 7-28-15 12:48PM
L13 PIPE TRANS SUNP FUEL ALARM CLEAR 7-28-15 12:42PM
L13 PIPE TRANS SUNP FUEL ALARM ALARM 7-28-15 12:42PM
E 1 OTHER COMMUNICATION ALARM CLEAR 7-28-15 12:12PM
E 1OTHER COMMUNICATION ALARM ALARM 7-28-15 12:06PM
L 3 ANNULAR PNL ANM FUEL ALARM CLEAR 7-28-15 11:48AM
T 1 TANK UNLEADED PROBE OUT CLEAR 7-28-15 11:29AM
T 1 TANK UNLEADED OVERFILL ALARM CLEAR 7-28-15 11:28AM
T 1 TANK UNLEADED PROBE OUT ALARM 7-28-15 11:28AM
T 1 TANK UNLEADED OVERFILL ALARM ALARM 7-28-15 11:28AM
T 2 TANK DIESELPROBE OUT CLEAR 7-28-15 11:27AM
T 2 TANK DIESEL OVERFILL ALARM CLEAR 7-28-15 11:26AM
T 2 TANK DIESEL PROBE OUT ALARM 7-28-15 11:26AM
L 3 ANNULAR PNL ANM FUEL ALARMALARM 7-28-15 11:26AM
T 2 TANK DIESEL OVERFILL ALARM ALARM 7-28-15 11:26AM
T 3 TANK PREMIUM PROBE OUT CLEAR 7-28-15 11:25AM
T 3 TANK PREMIUM OVERFILL ALARM CLEAR 7-28-15 11:24AM
T 3 TANK PREMIUM PROBE OUT ALARM 7-28-15 11:24AM
T 3 TANK PREMIUM OVERFILL ALARM ALARM 7-28-15 11:23AM
L 2 ANNULAR DSL ANN FUEL ALARM CLEAR 7-28-15 11:20AM
L 2ANNULAR DSL ANN FUEL ALARM ALARM 7-28-15 11:18AM
L 6 STP SUMP PNL STP SENSOR OUT ALARM CLEAR 7-28-15 11:14AM
L 5 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 7-28-15 11:14AM
L 4 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 7-28-15 11:14AM
L 2 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 7-28-15 11:14AM
L 3 ANNULAR PNL ANM FUEL ALARM CLEAR 7-28-15 11:14AM
L 1 ANNULAR UNL ANNFUEL ALARM CLEAR 7-28-15 11:14AM
L12 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 7-28-15 11:14AM
L11 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 7-28-15 11:14AM
L10 DISP PAN DISP 3-4 SENSOR OUT ALARMCLEAR 7-28-15 11:14AM
L 9 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 7-28-15 11:14AM
L13 PIPE TRANS SUNP SENSOR OUT ALARM CLEAR 7-28-15 11:14AM
L 2 ANNULAR DSL ANN SENSOR OUT ALARM ALARM7-28-15 11:13AM
L 4 STP SUMP UNL STP SENSOR OUT ALARM ALARM 7-28-15 11:13AM
L 1 ANNULAR UNL ANN FUEL ALARM ALARM 7-28-15 11:13AM
I11200
AUG 4, 2015 9:12 AM
FASTRIP 773
3501 MT VERNON
BAKERSFIELDCA
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 8-03-15 9:58PM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 8-03-15 5:25PM
T 1 TANK UNLEADED LOW TEMP WARNING CLEAR 7-28-15 11:30AM
T 1 TANK UNLEADED LOW TEMP WARNING ALARM 7-28-15 11:29AM
T 1 TANK UNLEADED HIGH PRODUCT ALARM CLEAR 7-28-15 11:29AM
T1 TANK UNLEADED HIGH PRODUCT ALARM ALARM 7-28-15 11:28AM
T 3 TANK PREMIUM HIGH PRODUCT ALARM CLEAR 7-28-15 11:25AM
T 3 TANK PREMIUM HIGH PRODUCT ALARM ALARM 7-28-15 11:22AM
T 2 TANK DIESEL DELIVERY NEEDED CLEAR 7-28-15 10:20AM
T 2 TANK DIESEL DELIVERY NEEDED ALARM 7-28-15 10:19AM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 7-25-15 11:52AM
h 4 OTHER FP4: BLEND3DEGRD COLLECT WARN CLEAR 7-25-15 10:00AM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 7-25-15 9:15AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 7-24-15 10:02AM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 7-24-15 12:33AM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 7-23-15 8:27PM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 7-22-15 4:45AM
T 2 TANK DIESEL DELIVERY NEEDED CLEAR 7-22-15 4:39AM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 7-21-15 11:40PM
T 2 TANK DIESEL DELIVERY NEEDED ALARM 7-21-15 5:54PM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 7-19-15 6:50PM
T1 TANK UNLEADED DELIVERY NEEDED ALARM 7-19-15 1:26PM
OTHER ISD GROSS PRES WARN CLEAR 7-15-15 10:00AM
OTHER ISD GROSS PRES WARN ALARM 7-14-15 10:02AM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 7-13-15 7:58PM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 7-13-15 5:13PM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 7-11-15 4:29PM
T 1 TANK UNLEADEDDELIVERY NEEDED ALARM 7-11-15 12:24PM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 7-09-15 1:03AM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 7-08-15 9:51PM
OTHER ISD GROSS PRESWARN CLEAR 7-07-15 3:14PM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 7-07-15 10:26AM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 7-07-15 10:17AM
OTHER ISD GROSS PRES WARN ALARM 7-07-15 10:02AM
T 2 TANK DIESEL DELIVERY NEEDED CLEAR 7-03-15 4:07AM
T 2 TANK DIESEL DELIVERY NEEDED ALARM 7-02-15 9:22AM
T 2 TANK DIESEL DELIVERY NEEDED CLEAR 7-01-15 9:50AM
T2 TANK DIESEL DELIVERY NEEDED ALARM 6-29-15 7:35AM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 6-25-15 5:36PM
T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 6-25-15 5:34PM
T 1 TANKUNLEADED INVALID FUEL LEVEL ALARM 6-25-15 4:30PM
h 5 OTHER FP5: BLEND3 DEGRD COLLECT WARN CLEAR 6-25-15 12:02PM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 6-25-15 10:58AM
h 5 OTHER FP5: BLEND3DEGRD COLLECT WARN ALARM 6-25-15 10:02AM
SYSTEM PRINTER ERROR CLEAR 6-21-15 1:30PM
SYSTEM PRINTER ERROR ALARM 6-21-15 1:29PM
SYSTEM PRINTER ERROR CLEAR 6-21-15 1:29PM
SYSTEM PRINTER ERROR ALARM 6-21-15 1:29PM
SYSTEM PAPER OUT CLEAR 6-21-15 1:29PM
SYSTEM PAPER OUT ALARM 6-21-15 1:27PM
I20600
AUG 4, 2015 9:12 AM
FASTRIP 773
3501 MT VERNON
BAKERSFIELD CA
TANK ALARM HISTORY
TANK 1 UNLEADED
OVERFILL ALARM JUL 28, 2015 11:28 AM
JUN 29, 2015 1:09 PM
APR 7, 2015 10:27 AM
LOW PRODUCT ALARM JUN 25, 2015 4:22 PM
JUN 15, 2015 5:59 PM
AUG 4, 2014 9:19 AM
SUDDEN LOSS ALARM JUL 28, 2015 10:20 AM
AUG 4, 2014 10:42 AM
AUG 4, 2014 9:18 AM
HIGH PRODUCT ALARM JUL 28, 2015 11:28 AM
AUG 4, 2014 10:41 AM
JUL 21, 2014 12:33 PM
INVALID FUEL LEVEL JUN 25, 2015 4:30 PM
AUG 4, 2014 9:19 AM
JUL 31, 2013 1:27 PM
PROBE OUT JUL 28, 2015 11:28 AM
JUL 28, 2015 10:21 AM
AUG 4, 2014 10:42 AM
DELIVERY NEEDED AUG 3, 2015 5:25 PM
JUL 25, 2015 9:15 AM
JUL 23, 2015 8:27 PM
LOW TEMP WARNING JUL 28, 2015 11:29 AM
AUG 6, 2013 1:48 PM
AUG 6, 2013 1:03 PM
TANK 2 DIESEL
OVERFILL ALARM JUL 28, 2015 11:26 AM
AUG 4, 2014 10:40 AM
JUL 21, 2014 12:36 PM
HIGH PRODUCT ALARM JUL 21, 2014 12:35 PM
AUG 6, 2013 1:47 PM
JUL 31, 2013 2:32 PM
INVALID FUEL LEVEL JUL 21, 2014 12:36 PM
PROBE OUT JUL 28, 2015 11:26 AM
JUL 28, 2015 10:19 AM
AUG 4, 2014 10:40 AM
DELIVERY NEEDED JUL 28, 2015 10:19 AM
JUL 21, 2015 5:54 PM
JUL 2, 2015 9:22 AM
MAX PRODUCT ALARM AUG 6, 2013 1:47 PM
LOW TEMP WARNING AUG 4, 2014 9:16 AM
AUG 6, 2013 1:49 PM
JUL 31, 2013 2:34 PM
TANK 3 PREMIUM
OVERFILL ALARM JUL 28, 2015 11:23 AM
AUG 4, 2014 10:38 AM
AUG 6, 2013 2:18 PM
SUDDEN LOSS ALARM JUL 28, 2015 10:18 AM
AUG 15, 2014 8:38 AM
AUG 4, 2014 9:17 AM
HIGH PRODUCT ALARM JUL 28, 2015 11:22 AM
JUL 21, 2014 12:37 PM
AUG 6, 2013 2:18 PM
INVALID FUEL LEVEL AUG 4, 2014 10:39 AM
AUG 6, 2013 1:01 PM
PROBE OUT JUL 28, 2015 11:24 AM
JUL 28, 2015 10:18 AM
AUG 4, 2014 10:38 AM
HIGH WATER WARNING AUG 7, 2012 2:20 PM
DELIVERY NEEDED NOV 8, 2014 12:01 PM
AUG4, 2014 9:17 AM
APR 18, 2014 12:19 PM
MAX PRODUCT ALARM AUG 11, 2011 1:19 PM
LOW TEMP WARNING AUG 4, 2014 9:18 AM
JUL 21, 2014 12:38 PM
JUL 21, 2014 12:33 PM
I38200
AUG 4, 2015 9:12 AM
I30200
AUG 4, 2015 9:12 AM
FASTRIP 773
3501 MT VERNON
BAKERSFIELD CA
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UNL ANN
JUL 28, 2015 2:31 PM FUEL ALARM
JUL 28, 2015 2:30 PM SENSOR OUT ALARM
JUL 28, 2015 2:24 PM SENSOR OUT ALARM
2 DSL ANN
JUL 28, 2015 11:18 AM FUEL ALARM
JUL 28, 2015 11:13 AM SENSOR OUT ALARM
JUL 28, 2015 10:52 AM FUEL ALARM
3 PNL ANM
JUL 28, 2015 2:17 PM FUEL ALARM
JUL 28, 2015 2:14 PM FUEL ALARM
JUL 28, 2015 1:57 PM FUEL ALARM
4 UNL STP
JUL 28, 2015 11:13 AM SENSOR OUT ALARM
JUL 28, 2015 10:51 AM FUEL ALARM
JUL 28, 2015 10:42 AM FUEL ALARM
5 DSL STP
JUL 28, 2015 11:13 AM SENSOR OUT ALARM
JUL 28, 2015 10:29 AM FUEL ALARM
AUG 4, 2014 10:19 AM FUEL ALARM
6 PNL STP
JUL 28, 2015 11:13 AM SENSOR OUT ALARM
JUL 28, 2015 10:27 AMFUEL ALARM
FEB 7, 2015 6:38 PM SENSOR OUT ALARM
9 DISP 1-2
JUL 28, 2015 11:13 AM SENSOR OUT ALARM
JUL 28, 2015 11:09 AM FUEL ALARM
AUG 4, 2014 10:30 AM FUEL ALARM
10 DISP 3-4
JUL 28, 2015 11:13 AM SENSOR OUT ALARM
JUL 28, 2015 11:11 AM FUEL ALARM
AUG 4, 2014 10:34 AM FUEL ALARM
11 DISP 5-6
JUL 28, 2015 11:13 AM SENSOR OUT ALARM
JUL 28, 2015 11:08 AM FUEL ALARM
AUG 4, 2014 10:31 AM FUEL ALARM
12 DISP 7-8
JUL 28, 2015 11:13 AM SENSOR OUT ALARM
JUL 28, 2015 11:10 AM FUEL ALARM
AUG 4, 2014 10:33 AM FUEL ALARM
13 TRANS SUNP
JUL 28, 2015 12:42 PM FUEL ALARM
JUL 28, 2015 11:13 AM SENSOR OUT ALARM
AUG 4, 2014 10:28 AM FUELALARM
I31600
AUG 4, 2015 9:12 AM
FASTRIP 773
3501 MT VERNON
BAKERSFIELD CA
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 PS 1-2
2 FM 1-2
3 FM 3-4
4 FM 5-6
JUN 3, 2011 11:01 AM COMMUNICATION ALARM
5 FM 7-8
JUN 3, 2011 11:01 AM COMMUNICATION ALARM
I40200
AUG 4, 2015 9:12 AM
I40300
AUG 4, 2015 9:12 AM
I34200
AUG 4, 2015 9:12 AM
I34700
AUG 4, 2015 9:12 AM
IV0100
AUG 4, 2015 9:12 AM
FASTRIP 773
3501 MT VERNON
BAKERSFIELD CA
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.04
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
15-07-24 10:02:39 A/L RATIO DEGRADATION FP 4 BLEND3 0.79
15-07-14 10:02:28 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.35
15-07-07 10:02:41 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95%1.31
15-06-25 10:02:33 A/L RATIO DEGRADATION FP 5 BLEND3 BLKD
15-03-23 10:01:09 A/L RATIO DEGRADATION FP 5 BLEND3 0.80
15-03-22 10:01:09 A/L RATIO DEGRADATION FP 5 BLEND3 0.79
15-01-23 10:01:09 A/L RATIO GROSSBLOCKAGE FP 5 BLEND3 BLKD
14-12-23 10:01:09 A/L RATIO DEGRADATION FP 6 BLEND3 0.80
14-12-09 10:01:09 A/L RATIO DEGRADATION FP 8 BLEND3 0.80
14-08-15 10:01:09 A/L RATIO DEGRADATION FP 5 BLEND3 BLKD
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
13-08-12 10:01:28 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
13-08-11 10:03:38 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
13-01-20 10:01:52 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
13-01-20 10:01:52 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
15-07-29 10:02:38 READINESS ISD:PP EVR:PP ISD & EVR READY
15-07-28 11:17:57 READINESS ISD:PP EVR:NN EVR READINESS PENDING
15-07-28 11:17:57 ISD STARTUP
15-07-28 11:16:52 ISD SHUTDOWN
15-07-07 15:14:18 CONTAINMENT GROSS & DEGRD TEST MANUALLYCLEARED
15-06-27 10:02:22 READINESS ISD:PP EVR:PP ISD & EVR READY
15-06-27 09:18:55 READINESS ISD:PP EVR:NN EVR READINESS PENDING
15-06-27 09:18:55 ISD STARTUP
15-06-27 09:18:27 ISD SHUTDOWN
15-06-2512:02:39 COLLECTION TEST HH05 GRADE TEST MANUALLY CLEARED
Fastrip 773
Alarm Hist After:
Responses Received:
I10200
AUG 4, 2015 12:17 PM
FASTRIP 773
3501 MT VERNON
BAKERSFIELD CA
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 7SMARTSENSOR BD 511865 507453
2 INTERSTITIAL BD 202542 201800
3 4 PROBE / G.T. 162119 161661
4 INTERSTITIAL BD 201727 201187
5UNUSED 9875362 9626048
6 UNUSED 9851759 9608376
7 UNUSED 9841100 9614260
8 UNUSED 9837166 9613170
9 STP SENSE BOARD 33186 33161
10 RELAY BOARD 15057 15050
11 UNUSED 9842904 9608962
12 UNUSED 9835121 9611708
13 UNUSED 9831462 9607851
14 UNUSED 9830933 9606151
15 UNUSED 9823108 9608788
16 UNUSED 9829030 9604234
COMM 1 ELEC DISP INT. 101235 101171
COMM 2 RS232 SERIAL BD 14929 14919
COMM 3 RS232 SERIAL BD 14972 14985
COMM 4 UNUSED 9844194 9616894
COMM 5 UNUSED 9827613 9609071
COMM 6 UNUSED 9827507 9603537
I90200
AUG 4, 2015 12:18 PM
SOFTWARE REVISION LEVEL
VERSION 331.01
SOFTWARE# 346331-100-B
CREATED-11.03.22.16.28
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
AUG 4, 2015 12:18 PM
FASTRIP 773
3501 MT VERNON
BAKERSFIELD CA
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATEDATE TIME
E 1 OTHER COMMUNICATION ALARM CLEAR 8-04-15 10:33AM
E 1 OTHER COMMUNICATION ALARM ALARM 8-04-15 10:26AM
T 3 TANK PREMIUM PROBE OUT CLEAR 8-04-15 10:18AM
T 3TANK PREMIUM PROBE OUT ALARM 8-04-15 10:17AM
T 2 TANK DIESEL PROBE OUT CLEAR 8-04-15 10:16AM
T 2 TANK DIESEL PROBE OUT ALARM 8-04-15 10:15AM
T 1 TANK UNLEADED PROBE OUT CLEAR 8-04-15 10:14AM
T 1 TANK UNLEADED PROBE OUT ALARM 8-04-15 10:13AM
L 3 ANNULAR PNL ANM FUEL ALARM CLEAR 8-04-15 10:08AM
L 2 ANNULAR DSL ANNFUEL ALARM CLEAR 8-04-15 10:07AM
L 1 ANNULAR UNL ANN FUEL ALARM CLEAR 8-04-15 10:07AM
L 2 ANNULAR DSL ANN FUEL ALARM ALARM 8-04-15 10:05AM
L 9 DISP PAN DISP 1-2 FUEL ALARMCLEAR 8-04-15 10:03AM
L 9 DISP PAN DISP 1-2 FUEL ALARM ALARM 8-04-15 10:03AM
L10 DISP PAN DISP 3-4 FUEL ALARM CLEAR 8-04-15 10:02AM
L10 DISP PAN DISP 3-4 FUEL ALARM ALARM 8-04-15 10:01AM
L12 DISP PAN DISP 7-8 FUEL ALARM CLEAR 8-04-15 10:00AM
L12 DISP PAN DISP 7-8 FUEL ALARM ALARM 8-04-15 10:00AM
L11 DISP PAN DISP 5-6 FUEL ALARM CLEAR 8-04-15 9:59AM
L11DISP PAN DISP 5-6 FUEL ALARM ALARM 8-04-15 9:58AM
L13 PIPE TRANS SUNP FUEL ALARM CLEAR 8-04-15 9:56AM
L13 PIPE TRANS SUNP FUEL ALARM ALARM 8-04-15 9:55AM
L 3 ANNULAR PNL ANM FUEL ALARM ALARM 8-04-15 9:55AM
L 1 ANNULAR UNL ANN FUEL ALARM ALARM 8-04-15 9:54AM
L 4 STP SUMP UNL STP FUEL ALARM CLEAR 8-04-15 9:53AM
L 4 STP SUMP UNL STPFUEL ALARM ALARM 8-04-15 9:53AM
L 5 STP SUMP DSL STP FUEL ALARM CLEAR 8-04-15 9:52AM
L 5 STP SUMP DSL STP FUEL ALARM ALARM 8-04-15 9:52AM
L 6 STP SUMP PNL STP FUEL ALARMCLEAR 8-04-15 9:51AM
L 6 STP SUMP PNL STP FUEL ALARM ALARM 8-04-15 9:51AM
T 1 TANK UNLEADED SUDDEN LOSS ALARM CLEAR 8-04-15 9:51AM
T 1 TANK UNLEADED PROBE OUT CLEAR 8-04-15 9:47AM
T 1 TANK UNLEADED PROBE OUT ALARM 8-04-15 9:47AM
T 1 TANK UNLEADED SUDDEN LOSS ALARM ALARM 8-04-15 9:46AM
T 2 TANK DIESEL PROBE OUT CLEAR 8-04-15 9:45AM
T 2TANK DIESEL PROBE OUT ALARM 8-04-15 9:44AM
T 3 TANK PREMIUM PROBE OUT CLEAR 8-04-15 9:44AM
T 3 TANK PREMIUM PROBE OUT ALARM 8-04-15 9:44AM
L10 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 8-04-15 9:42AM
L12 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 8-04-15 9:41AM
L11 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 8-04-15 9:41AM
L 9 DISP PAN DISP 1-2SENSOR OUT ALARM CLEAR 8-04-15 9:41AM
L13 PIPE TRANS SUNP SENSOR OUT ALARM CLEAR 8-04-15 9:41AM
L 6 STP SUMP PNL STP SENSOR OUT ALARM CLEAR 8-04-15 9:41AM
L 5 STP SUMP DSL STP SENSOR OUT ALARMCLEAR 8-04-15 9:41AM
L 4 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 8-04-15 9:41AM
L 3 ANNULAR PNL ANM SENSOR OUT ALARM CLEAR 8-04-15 9:41AM
L 2 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR8-04-15 9:41AM
L 1 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 8-04-15 9:41AM
L 4 STP SUMP UNL STP SENSOR OUT ALARM ALARM 8-04-15 9:41AM
I11200
AUG 4, 2015 12:18 PM
FASTRIP 773
3501 MT VERNON
BAKERSFIELDCA
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 3 TANK PREMIUM LOW TEMP WARNING CLEAR 8-04-15 10:18AM
T 3 TANK PREMIUM LOW TEMP WARNING ALARM 8-04-15 10:18AM
T 3 TANK PREMIUM HIGH PRODUCT ALARM CLEAR 8-04-15 10:16AM
T 3 TANK PREMIUM HIGH PRODUCT ALARM ALARM 8-04-15 10:16AM
T 2 TANK DIESEL LOW TEMP WARNING CLEAR 8-04-15 10:16AM
T2 TANK DIESEL LOW TEMP WARNING ALARM 8-04-15 10:16AM
T 2 TANK DIESEL HIGH PRODUCT ALARM CLEAR 8-04-15 10:15AM
T 2 TANK DIESEL HIGH PRODUCT ALARM ALARM 8-04-15 10:15AM
T 1 TANK UNLEADED HIGH PRODUCT ALARM CLEAR 8-04-15 10:13AM
T 1 TANK UNLEADED HIGH PRODUCT ALARM ALARM 8-04-15 10:13AM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 8-03-15 9:58PM
T 1 TANK UNLEADEDDELIVERY NEEDED ALARM 8-03-15 5:25PM
T 1 TANK UNLEADED LOW TEMP WARNING CLEAR 7-28-15 11:30AM
T 1 TANK UNLEADED LOW TEMP WARNING ALARM 7-28-15 11:29AM
T 1 TANK UNLEADED HIGH PRODUCT ALARM CLEAR 7-28-15 11:29AM
T 1 TANK UNLEADED HIGH PRODUCT ALARM ALARM 7-28-15 11:28AM
T 3 TANK PREMIUM HIGH PRODUCT ALARM CLEAR 7-28-15 11:25AM
T 3 TANK PREMIUM HIGH PRODUCT ALARM ALARM 7-28-15 11:22AM
T 2 TANK DIESEL DELIVERY NEEDED CLEAR 7-28-15 10:20AM
T 2 TANK DIESEL DELIVERY NEEDED ALARM 7-28-15 10:19AM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 7-25-15 11:52AM
h4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 7-25-15 10:00AM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 7-25-15 9:15AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 7-24-15 10:02AM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 7-24-15 12:33AM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 7-23-15 8:27PM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 7-22-15 4:45AM
T 2 TANK DIESELDELIVERY NEEDED CLEAR 7-22-15 4:39AM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 7-21-15 11:40PM
T 2 TANK DIESEL DELIVERY NEEDED ALARM 7-21-15 5:54PM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 7-19-15 6:50PM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 7-19-15 1:26PM
OTHER ISD GROSS PRES WARN CLEAR 7-15-15 10:00AM
OTHER ISD GROSS PRES WARN ALARM 7-14-15 10:02AM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 7-13-15 7:58PM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 7-13-15 5:13PM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 7-11-15 4:29PM
T1 TANK UNLEADED DELIVERY NEEDED ALARM 7-11-15 12:24PM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 7-09-15 1:03AM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 7-08-15 9:51PM
OTHER ISD GROSS PRES WARN CLEAR 7-07-15 3:14PM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 7-07-15 10:26AM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 7-07-15 10:17AM
OTHERISD GROSS PRES WARN ALARM 7-07-15 10:02AM
T 2 TANK DIESEL DELIVERY NEEDED CLEAR 7-03-15 4:07AM
T 2 TANK DIESEL DELIVERY NEEDED ALARM 7-02-15 9:22AM
T 2 TANK DIESELDELIVERY NEEDED CLEAR 7-01-15 9:50AM
T 2 TANK DIESEL DELIVERY NEEDED ALARM 6-29-15 7:35AM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 6-25-15 5:36PM
T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 6-25-15 5:34PM
I20600
AUG 4, 2015 12:18 PM
FASTRIP 773
3501 MT VERNON
BAKERSFIELD CA
TANK ALARM HISTORY
TANK 1 UNLEADED
OVERFILL ALARM JUL 28, 2015 11:28 AM
JUN 29, 2015 1:09 PM
APR 7, 2015 10:27 AM
LOW PRODUCT ALARM JUN 25, 2015 4:22 PM
JUN 15, 2015 5:59 PM
AUG 4, 2014 9:19 AM
SUDDEN LOSS ALARM AUG 4, 2015 9:46 AM
JUL 28, 2015 10:20 AM
AUG 4, 2014 10:42 AM
HIGH PRODUCT ALARM AUG 4, 2015 10:13 AM
JUL 28, 2015 11:28 AM
AUG 4, 2014 10:41 AM
INVALID FUEL LEVEL JUN 25, 2015 4:30 PM
AUG 4, 2014 9:19 AM
JUL 31, 2013 1:27 PM
PROBE OUT AUG4, 2015 10:13 AM
AUG 4, 2015 9:47 AM
JUL 28, 2015 11:28 AM
DELIVERY NEEDED AUG 3, 2015 5:25 PM
JUL 25, 2015 9:15 AM
JUL 23, 2015 8:27 PM
LOW TEMP WARNING JUL 28, 2015 11:29 AM
AUG 6, 2013 1:48 PM
AUG 6, 2013 1:03 PM
TANK 2 DIESEL
OVERFILL ALARM JUL 28, 2015 11:26 AM
AUG 4, 2014 10:40 AM
JUL 21, 2014 12:36 PM
HIGH PRODUCT ALARM AUG 4, 2015 10:15 AM
JUL 21, 2014 12:35 PM
AUG 6, 2013 1:47 PM
INVALID FUEL LEVEL JUL 21, 2014 12:36 PM
PROBE OUT AUG 4, 2015 10:15 AM
AUG 4, 2015 9:44 AM
JUL 28, 2015 11:26 AM
DELIVERY NEEDED JUL 28, 2015 10:19 AM
JUL 21, 2015 5:54 PM
JUL 2, 2015 9:22 AM
MAX PRODUCT ALARM AUG 6, 2013 1:47 PM
LOW TEMP WARNING AUG 4, 2015 10:16 AM
AUG 4, 2014 9:16 AM
AUG 6, 2013 1:49 PM
TANK 3 PREMIUM
OVERFILL ALARM JUL 28, 2015 11:23 AM
AUG 4, 2014 10:38 AM
AUG 6, 2013 2:18 PM
SUDDEN LOSS ALARM JUL 28, 2015 10:18 AM
AUG 15, 2014 8:38 AM
AUG 4, 2014 9:17 AM
HIGH PRODUCT ALARM AUG 4, 2015 10:16 AM
JUL 28, 2015 11:22 AM
JUL 21, 2014 12:37 PM
INVALID FUEL LEVEL AUG 4, 2014 10:39 AM
AUG 6, 2013 1:01 PM
PROBE OUT AUG 4, 2015 10:17 AM
AUG 4, 2015 9:44 AM
JUL 28, 2015 11:24 AM
HIGH WATER WARNING AUG 7, 2012 2:20 PM
DELIVERY NEEDED NOV 8, 2014 12:01 PM
AUG4, 2014 9:17 AM
APR 18, 2014 12:19 PM
MAX PRODUCT ALARM AUG 11, 2011 1:19 PM
LOW TEMP WARNING AUG 4, 2015 10:18 AM
AUG 4, 2014 9:18 AM
JUL 21, 2014 12:38 PM
I38200
AUG 4, 2015 12:18 PM
I30200
AUG 4, 2015 12:18 PM
FASTRIP 773
3501 MT VERNON
BAKERSFIELD CA
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UNL ANN
AUG 4, 2015 9:54 AM FUEL ALARM
AUG 4, 2015 9:41 AM SENSOR OUT ALARM
JUL 28, 2015 2:31 PM FUEL ALARM
2 DSL ANN
AUG 4, 2015 10:05 AM FUEL ALARM
AUG 4, 2015 9:41 AM SENSOR OUT ALARM
JUL 28, 2015 11:18 AM FUEL ALARM
3 PNL ANM
AUG 4, 2015 9:55 AM FUEL ALARM
AUG 4, 2015 9:41 AM SENSOR OUT ALARM
JUL 28, 2015 2:17 PM FUEL ALARM
4 UNL STP
AUG 4, 2015 9:53 AM FUEL ALARM
AUG 4, 2015 9:41 AM SENSOR OUT ALARM
JUL 28, 2015 11:13 AM SENSOR OUT ALARM
5 DSL STP
AUG 4, 2015 9:52 AM FUEL ALARM
AUG 4, 2015 9:41 AM SENSOR OUT ALARM
JUL 28, 2015 11:13 AM SENSOR OUT ALARM
6 PNL STP
AUG 4, 2015 9:51 AM FUEL ALARM
AUG 4, 2015 9:41 AM SENSOR OUT ALARM
JUL 28, 2015 11:13 AM SENSOR OUT ALARM
9 DISP 1-2
AUG 4, 2015 10:03 AM FUEL ALARM
AUG 4, 2015 9:41 AM SENSOR OUT ALARM
JUL 28, 2015 11:13 AMSENSOR OUT ALARM
10 DISP 3-4
AUG 4, 2015 10:01 AM FUEL ALARM
AUG 4, 2015 9:41 AM SENSOR OUT ALARM
JUL 28, 2015 11:13 AM SENSOR OUT ALARM
11 DISP 5-6
AUG 4, 2015 9:58 AM FUEL ALARM
AUG 4, 2015 9:41 AM SENSOR OUT ALARM
JUL 28, 2015 11:13 AM SENSOR OUT ALARM
12 DISP 7-8
AUG 4, 2015 10:00 AM FUEL ALARM
AUG 4, 2015 9:41 AM SENSOR OUT ALARM
JUL 28, 2015 11:13 AM SENSOR OUT ALARM
13 TRANS SUNP
AUG 4, 2015 9:55 AM FUEL ALARM
AUG 4, 2015 9:41 AM SENSOR OUT ALARM
JUL 28, 2015 12:42 PM FUEL ALARM
I31600
AUG 4, 2015 12:18 PM
FASTRIP 773
3501 MT VERNON
BAKERSFIELD CA
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 PS 1-2
2 FM 1-2
3 FM 3-4
4 FM 5-6
JUN 3, 2011 11:01 AM COMMUNICATION ALARM
5 FM 7-8
JUN 3, 2011 11:01 AM COMMUNICATION ALARM
I40200
AUG 4, 2015 12:18 PM
I40300
AUG 4, 2015 12:18 PM
I34200
AUG 4, 2015 12:18 PM
I34700
AUG 4, 2015 12:18 PM
IV0100
AUG 4, 2015 12:18 PM
FASTRIP 773
3501 MT VERNON
BAKERSFIELD CA
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.04
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME : 99%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
15-07-24 10:02:39 A/L RATIO DEGRADATION FP 4 BLEND3 0.79
15-07-14 10:02:28 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.35
15-07-07 10:02:41 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95%1.31
15-06-25 10:02:33 A/L RATIO DEGRADATION FP 5 BLEND3 BLKD
15-03-23 10:01:09 A/L RATIO DEGRADATION FP 5 BLEND3 0.80
15-03-22 10:01:09 A/L RATIO DEGRADATION FP 5 BLEND3 0.79
15-01-23 10:01:09 A/L RATIO GROSSBLOCKAGE FP 5 BLEND3 BLKD
14-12-23 10:01:09 A/L RATIO DEGRADATION FP 6 BLEND3 0.80
14-12-09 10:01:09 A/L RATIO DEGRADATION FP 8 BLEND3 0.80
14-08-15 10:01:09 A/L RATIO DEGRADATION FP 5 BLEND3 BLKD
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
13-08-12 10:01:28 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
13-08-11 10:03:38 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
13-01-20 10:01:52 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
13-01-20 10:01:52 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
15-08-04 10:03:05 READINESS ISD:PP EVR:PP ISD & EVR READY
15-08-04 09:40:50 READINESS ISD:PP EVR:NN EVR READINESS PENDING
15-08-04 09:40:50 ISD STARTUP
15-08-04 09:39:23 ISD SHUTDOWN
15-07-29 10:02:38 READINESS ISD:PP EVR:PP ISD & EVR READY
15-07-28 11:17:57 READINESS ISD:PP EVR:NN EVR READINESS PENDING
15-07-28 11:17:57 ISD STARTUP
15-07-28 11:16:52 ISD SHUTDOWN
15-07-07 15:14:18 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
15-06-2710:02:22 READINESS ISD:PP EVR:PP ISD & EVR READY
SWRCB, January 2006
Spill Bucket Testing Report Form
This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and
printouts from tests (if applicable), should be provided to the facility owner/operator forsubmittal to the local regulatory agency.
1.FACILITY INFORMATION
Facility Name:Date of Testing:
Facility Address:
Facility Contact:Phone:
Date Local Agency Was Notified of Testing :
Name of Local Agency Inspector (if present during testing):
2.TESTING CONTRACTOR INFORMATION
Company Name:Confidence UST Services, Inc.
Technician Conducting Test:
Credentials1:CSLB Contractor ICC Service Tech. SWRCB Tank Tester Other (Specify)
License Number(s):CSLB#804904 ICC#
3.SPILL BUCKET TESTING INFORMATION
Test Method Used:Hydrostatic Vacuum Other
Test Equipment Used:Lake TestEquipment Resolution:0.0625”
Identify Spill Bucket (By Tank
Number, Stored Product, etc.)
1234
Bucket Installation Type: Direct Bury
Contained in Sump
Direct Bury
Contained in Sump
Direct Bury
Contained in Sump
Direct Bury
Contained in Sump
Bucket Diameter:
Bucket Depth:
Wait time between applying
vacuum/water and start of test:
Test Start Time (TI):
Initial Reading (RI):
Test End Time (TF):
Final Reading (RF):
Test Duration (TF – TI):
Change in Reading (RF -RI):
Pass/Fail Threshold or
Criteria:
Test Result: Pass Fail Pass Fail Pass Fail Pass Fail
Comments –(include information on repairs made prior to testing, and recommended follow-up for failed tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements.
Technician’s Signature:________________________________________________ Date:_________
1 State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
#7773Fastrip#31 08/04/2015
3501Mt.VernonAvenue Bakersfield,CA93306
OmeroGarcia(661)393-7000
07/14/2015
Shane Gardner
DustinReese
8216722-UT
Regular
12.00"
14.00"
5min.
9:30 am
12.00"
10:30 am
12.00"
1hour
0.00"
0.0625"
Super
12.00"
13.50"
5min.
9:30 am
11.50"
10:30 am
11.50"
1hour
0.00"
0.0625 0.0625
Diesel
12.00"
13.50"
5min.
9:30 am
9.50"
10:30 am
9.50"
1hour
0.00"
08/04/2015