HomeMy WebLinkAboutFMC Results 2015 (South)MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State of CaliforniaAuthority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each
monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner/operator.
The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date.
A.General Information
Facility Name:Bldg. No.:
Site Address:City:Zip:
Facility Contact Person: Contact Phone No.:
Make/Model of Monitoring System:Date of Testing/Servicing:
B.Inventory of Equipment Tested/Certified
Check the appropriate boxes to indicate specific equipment inspected/serviced:
Tank ID:Tank ID:
In-Tank Gauging Probe.Model:In-Tank Gauging Probe.Model:
Annular Space or Vault Sensor.Model:Annular Space or Vault Sensor.Model:
Piping Sump / Trench Sensor(s).Model:Piping Sump / Trench Sensor(s).Model:
Fill Sump Sensor(s).Model:Fill Sump Sensor(s).Model:
Mechanical Line Leak Detector.Model:Mechanical Line Leak Detector.Model:
Electronic Line Leak Detector.Model:Electronic LineLeak Detector.Model:
Tank Overfill / High-Level Sensor.Model:Tank Overfill / High-Level Sensor.Model:
Other (specify equipment type and model in Section E on Page 2).Other (specify equipment type and model in Section E on Page 2).
Tank ID:Tank ID:
In-Tank Gauging Probe.Model:In-Tank Gauging Probe.Model:
Annular Space or Vault Sensor.Model:Annular Space or Vault Sensor.Model:
Piping Sump / TrenchSensor(s).Model:Piping Sump / Trench Sensor(s).Model:
Fill Sump Sensor(s).Model:Fill Sump Sensor(s).Model:
Mechanical Line Leak Detector.Model:Mechanical Line Leak Detector.Model:
Electronic Line Leak Detector.Model:Electronic Line Leak Detector.Model:
Tank Overfill / High-Level Sensor.Model:Tank Overfill / High-Level Sensor.Model:
Other (specify equipment type and model in Section E on Page 2).Other (specify equipment type and model in Section E on Page 2).
Dispenser ID:Dispenser ID:
Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model:
Shear Valve(s).Shear Valve(s).
Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s).
Dispenser ID:Dispenser ID:
Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model:
Shear Valve(s).Shear Valve(s).
Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s).
Dispenser ID:Dispenser ID:
Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model:
Shear Valve(s).Shear Valve(s).
Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s).
*If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C.Certification -I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers’
guidelines. Attached to this Certification is information (e.g. manufacturers' checklists)necessary to verify that this information is
correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also
attached a copy of the report;(check all that apply):System set-up Alarm history report
Technician Name (print):Signature:
Certification No.:License. No.:804904
Testing Company Name:Confidence UST Services, Inc.Phone No.:(800)339-9930
Site Address:Date of Testing/Servicing:
Page 1 of 3
Sully'sDowntown(South)
2317LStreetBakersfield93301
FrankSullivan (661)327-5008
Veeder-RootTLS-350 11/10/2015
12,000gal.Regular
847390-107
794390-420 794390-420
794380-208 794380-208
FX1V
847390-107
8,000gal.Plus
847390-107
FX1V
847390-107
10,000gal.Super
847390-107
794390-420
794380-208
847390-107
FX1V
794380-208
1-2
794380-208 794380-208
794380-208
794380-208
3-4
5-6 7-8
9-10
794380-208
11-12
DustinReese
B43426
2317LStreet Bakersfield,CA93301 11/10/2015
Monitoring System Certification
D.Results of Testing/Servicing
Software Version Installed:
Complete the following checklist:
Yes No*Isthe audible alarm operational?
Yes No*Is the visual alarm operational?
Yes No*Were all sensors visually inspected, functionally tested, and confirmed operational?
Yes No*Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will
not interfere with their proper operation?
Yes No*
N/A
If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem)
operational?
Yes No*
N/A
For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate
positive shut-down? (Check all that apply) Sump/Trench Sensors; Dispenser Containment Sensors.
Did you confirm positive shut-down due to leaks and sensor failure/disconnection? Yes; No.
Yes No*
N/A
For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no
mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank
fill point(s) and operating properly? If so, at what percent oftank capacity does the alarm trigger? %
Yes*NoWas any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced
and list the manufacturer name and model for all replacement parts in Section E, below.
Yes*NoWas liquid found inside any secondary containment systems designed as dry systems? (Check all that apply)
Product; Water. If yes, describe causes in Section E, below.
Yes No*Was monitoring system set-up reviewed to ensure proper settings? Attach set up reports, if applicable
Yes No*Is all monitoring equipment operational per manufacturer’s specifications?
* In Section E below, describe how and when these deficiencies were or will be corrected.
E.Comments:
Page 2 of 3
329.00
90
Monitoring System Certification
F.In-Tank Gauging / SIR Equipment: Check this box if tank gauging is used only for inventory control.
Check this box if no tank gauging or SIR equipment is installed.
This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
Yes No*Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
Yes No*Were all tank gauging probes visually inspected for damage and residue buildup?
Yes No*Was accuracy of system product level readings tested?
Yes No*Was accuracy of system water level readings tested?
Yes No*Were all probes reinstalled properly?
Yes No*Were all items on the equipment manufacturer’s maintenance checklist completed?
* In the Section H, below, describe how and when these deficiencies were or will be corrected.
G.Line Leak Detectors (LLD):Check this box if LLDs are not installed.
Complete the following checklist:
Yes No*
N/A
For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance?
(Check all that apply)Simulated leak rate: 3 g.p.h.; 0.1 g.p.h ; 0.2 g.p.h.
Yes No*Were all LLDs confirmed operational and accurate within regulatory requirements?
Yes No*Was the testing apparatus properly calibrated?
Yes No*
N/A
For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
Yes No*
N/A
For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak?
Yes No*
N/A
For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled
or disconnected?
Yes No*
N/A
For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions
or fails a test?
Yes No*
N/A
For electronic LLDs, have all accessible wiring connections been visually inspected?
Yes No*Were all items on the equipment manufacturer’s maintenance checklist completed?
* In the Section H, below, describe how and when these deficiencies were or will be corrected.
H.Comments:
Page 3 of 3
Leak Detector Test Results Sheet
Customer Address: Work Order: Site Address:
Test Date:
Site Contact: Phone:
Technician: Phone: 800-339-9930 ICC No.:
Product Type LLD Type Model Serial No. Check
Valve
Holding
Pressure
Bleed
Off ML.
Leak
Rate
Tested:
Pass/Fail
3 gph @
10 psi
3 gph @
10 psi
3 gph @
10 psi
3 gph @
10 psi
3 gph @
10 psi
3 gph @
10 psi
3 gph @
10 psi
3 gph @
10 psi
Technician Name: Technician No.:
Signature: Date:
SullivanPetroleum,LLC
1000TruxtunAvenue
Bakersfield,CA93301
35411
11/10/2015
8216722-UT
Regular Mechanical FX1V
DustinReese
(661)327-5008FrankSullivan
Bakersfield,CA93301
2317LStreet
Sully'sDowntown(South)
14psi110ml Pass
FX1VMechanicalPlus 14psi120ml Pass
FX1VMechanicalPremium 12psi89ml Pass
DustinReese 8216722-UT
11/10/2015
Downtown Chev South, 2317 L St
System Setup: Responses Received:
200 DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 NOV 10, 2015 9:15 AM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 SUPREME 4276 66.52 0.0 74.9 3828 2 PLUS 3867 38.58 0.0 81.2 6278 3 UNLEADED 7685 77.70 0.0 74.7 4356 I90500 NOV 10, 2015 9:15 AM SOFTWARE REVISION LEVEL VERSION 329.00 SOFTWARE# 346329-100-A CREATED - 08.10.09.17.08 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD I50500 NOV 10, 2015 9:15 AM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM I50201 NOV 10, 2015 9:15 AM SHIFT TIME 1 : 6:00 AM I50202 NOV 10, 2015 9:15 AM SHIFT TIME 2 : DISABLED
I50203 NOV 10, 2015 9:15 AM SHIFT TIME 3 : DISABLED I50204 NOV 10, 2015 9:15 AM SHIFT TIME 4 : DISABLED I54600 NOV 10, 2015 9:15 AM TANK PER TST NEEDED WRN: DISABLED I54900 NOV 10, 2015 9:15 AM TANK ANN TST NEEDED WRN: DISABLED I55300 NOV 10, 2015 9:15 AM LINE RE-ENABLE METHOD PASS LINE TEST I55600 NOV 10, 2015 9:15 AM LINE PER TST NEEDED WRN: DISABLED I55900
NOV 10, 2015 9:15 AM LINE ANN TST NEEDED WRN: DISABLED I50D00 NOV 10, 2015 9:15 AM PRINT TC VOLUMES ENABLED I50E00 NOV 10, 2015 9:15 AM TEMP COMPENSATION
VALUE (DEG F ): 60.0 I60B00 NOV 10, 2015 9:15 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 NOV 10, 2015 9:15 AM H-PROTOCOL DATA FORMAT HEIGHT I51A01 NOV 10, 2015 9:15 AM DAYLIGHT SAVING TIME ENABLED OFF I51B00 NOV 10, 2015 9:15 AM DAYLIGHT SAVING TIME START DATE MAR WEEK 2 SUN 2:00 AM END DATE NOV WEEK 1 SUN 2:00 AM I51600 NOV 10, 2015 9:15 AM RE-DIRECT LOCAL PRINTOUT DISABLED
I50400 NOV 10, 2015 9:15 AM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 231782 ENABLED 2 231782 ENABLED 3 000000 DISABLED 4 000000 DISABLED 5 231782 ENABLED 6 000000 DISABLED
I21900 NOV 10, 2015 9:15 AM TANK CHART SECURITY DISABLED I5BD00 NOV 10, 2015 9:15 AM CUSTOM ALARM LABELS DISABLED I56000 NOV 10, 2015 9:15 AM MASS/DENSITY DISABLED I88101 NOV 10, 2015 9:15 AM PORT SETTINGS: COMM BOARD : 1 (EDIM ) RS-232 SECURITY CODE : 231782 I88102 NOV 10, 2015 9:15 AM PORT SETTINGS: COMM BOARD : 2 (RS-232) BAUD RATE : 9600 PARITY : ODD
STOP BIT : 1 STOP DATA LENGTH: 7 DATA RS-232 SECURITY CODE : 231782 I88103 NOV 10, 2015 9:15 AM I88104 NOV 10, 2015 9:15 AM I88105
NOV 10, 2015 9:15 AM PORT SETTINGS: COMM BOARD : 5 (S-SAT ) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : 231782 DTR NORMAL STATE: HIGH I88106 NOV 10, 2015 9:15 AM I52000 NOV 10, 2015 9:15 AM RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 ON DATE NOV 25, 2014 DISABLED 2 ON DATE NOV 25, 2014 DISABLED 3 ON DATE NOV 25, 2014 DISABLED 4 ON DATE NOV 25, 2014 DISABLED 5 ON DATE NOV 25, 2014 DISABLED 6 ON DATE NOV 25, 2014 DISABLED 7 ON DATE NOV 25, 2014 DISABLED 8 VEEDER ROOT (FMS) ON DATE JUL 9, 2015 2:15 PM I60100 NOV 10, 2015 9:15 AM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 SUPREME ON 2 PLUS ON 3 UNLEADED ON 4 OFF
I60200 NOV 10, 2015 9:15 AM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 SUPREME 2 PLUS 3 UNLEADED 4 I60300 NOV 10, 2015 9:15 AM
TANK PRODUCT CODE TANK PRODUCT LABEL 1 SUPREME 1 2 PLUS 2 3 UNLEADED 3 4 4 I60900 NOV 10, 2015 9:15 AM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 SUPREME 0.000700 2 PLUS 0.000700 3 UNLEADED 0.000700 4 0.000000 I60700 NOV 10, 2015 9:15 AM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 SUPREME 127.50 2 PLUS 95.00 3 UNLEADED 127.50 4 0.00 I60A00 NOV 10, 2015 9:15 AM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 SUPREME 1 PT 8104 2 PLUS 1 PT 10145 3 UNLEADED 1 PT 12041 4 50 PTS 0 I60400 NOV 10, 2015 9:15 AM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 SUPREME 8104 2 PLUS 10145 3 UNLEADED 12041 4 0 I60500 NOV 10, 2015 9:15 AM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 SUPREME 8104 0 0 0 2 PLUS 10145 0 0 0
3 UNLEADED 12041 0 0 0 4 0 0 0 0 I60600 NOV 10, 2015 9:15 AM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 SUPREME 8104 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 PLUS 10145 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 UNLEADED 12041 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 NOV 10, 2015 9:15 AM TANK PRODUCT LABEL METER DATA 1 SUPREME NO 2 PLUS NO 3 UNLEADED NO 4 NO
I62F00 NOV 10, 2015 9:15 AM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 SUPREME 4.0 INCHES 2 PLUS 4.0 INCHES 3 UNLEADED 4.0 INCHES I62700 NOV 10, 2015 9:15 AM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES
1 SUPREME 2.0 2 PLUS 2.0 3 UNLEADED 2.0 9999FF1B I62400 NOV 10, 2015 9:15 AM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 SUPREME 3.0 2 PLUS 3.0 3 UNLEADED 3.0 I62800 NOV 10, 2015 9:15 AM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 SUPREME 8104 2 PLUS 10145 3 UNLEADED 12041 4 0 I62300 NOV 10, 2015 9:15 AM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 SUPREME 7293 2 PLUS 9130 3 UNLEADED 10837 4 0 I62200 NOV 10, 2015 9:15 AM TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS 1 SUPREME 7698 2 PLUS 9637 3 UNLEADED 11439 4 0 I62900 NOV 10, 2015 9:15 AM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 SUPREME 810 2 PLUS 1014 3 UNLEADED 1204 4 0
I62100 NOV 10, 2015 9:15 AM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 SUPREME 800 2 PLUS 1000 3 UNLEADED 1200 4 0 I62600 NOV 10, 2015 9:15 AM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 SUPREME 99 2 PLUS 99 3 UNLEADED 99 4 99 I62500 NOV 10, 2015 9:15 AM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 SUPREME 99 2 PLUS 99 3 UNLEADED 99 4 99 I60800 NOV 10, 2015 9:15 AM TANK TILT TANK PRODUCT LABEL INCHES 1 SUPREME 2.86
2 PLUS 0.73 3 UNLEADED 1.10 4 0.00 I60B00 NOV 10, 2015 9:15 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 NOV 10, 2015 9:15 AM TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES
1 SUPREME 0.00 2 PLUS 0.00 3 UNLEADED 0.00 4 0.00 I61200 NOV 10, 2015 9:15 AM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 SUPREME NONE NONE 2 PLUS NONE NONE 3 UNLEADED NONE NONE 4 NONE NONE I63600 NOV 10, 2015 9:15 AM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 SUPREME 810 2 PLUS 1014 3 UNLEADED 1204 4 0 I62A00 NOV 10, 2015 9:15 AM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 SUPREME 810 2 PLUS 1014 3 UNLEADED 1204 4 0 I62C00 NOV 10, 2015 9:15 AM
TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 SUPREME STANDARD 2 PLUS STANDARD 3 UNLEADED STANDARD 4 STANDARD I62D00 NOV 10, 2015 9:15 AM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 SUPREME GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED 2 PLUS GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 UNLEADED GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 NOV 10, 2015 9:15 AM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 SUPREME OFF OFF 2 PLUS OFF OFF 3 UNLEADED OFF OFF 4 OFF OFF I63000 NOV 10, 2015 9:15 AM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 SUPREME OFF 2 PLUS OFF 3 UNLEADED OFF 4 OFF I63200 NOV 10, 2015 9:15 AM
TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 SUPREME OFF 2 PLUS OFF 3 UNLEADED OFF 4 OFF I61000 NOV 10, 2015 9:15 AM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 SUPREME 1
2 PLUS 1 3 UNLEADED 1 4 1 I63A00 NOV 10, 2015 9:15 AM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 SUPREME 10.00% 2 PLUS 10.00% 3 UNLEADED 10.00% 4 10.00% I61100 NOV 10, 2015 9:15 AM LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : ALL TANK JAN 2, 2016 START TIME : 2:00 AM TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED I61300 NOV 10, 2015 9:15 AM CSLD PROBABLITY OF DETECTION I61400 NOV 10, 2015 9:15 AM CSLD CLIMATE FACTOR
I61600 NOV 10, 2015 9:15 AM TANK PRODUCT LABEL CAL UPDATE 1 SUPREME IMMEDIATE 2 PLUS IMMEDIATE 3 UNLEADED IMMEDIATE 4 IMMEDIATE I61A00 NOV 10, 2015 9:15 AM IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP: 1 SUPREME DISABLED 2 PLUS DISABLED 3 UNLEADED DISABLED 4 DISABLED I61B00 NOV 10, 2015 9:15 AM IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 NOV 10, 2015 9:15 AM CSLD REPORT ONLY I62B00 NOV 10, 2015 9:15 AM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 SUPREME ??? 0, 0 2 PLUS ??? 0, 0 3 UNLEADED ??? 0, 0 4 ??? 0, 0 I63300 NOV 10, 2015 9:15 AM LEAK TEST REPORT FORMAT: NORMAL I63400 NOV 10, 2015 9:15 AM
RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 SUPREME 0 2 PLUS 0 3 UNLEADED 0 4 0 I63500 NOV 10, 2015 9:15 AM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 SUPREME 1 2 PLUS 1
3 UNLEADED 1 4 1 I63900 NOV 10, 2015 9:15 AM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 SUPREME END FACTOR: NONE 2 PLUS END FACTOR: NONE 3 UNLEADED END FACTOR: NONE 4 END FACTOR: NONE I78000 NOV 10, 2015 9:15 AM I77700 NOV 10, 2015 9:15 AM I77800 NOV 10, 2015 9:15 AM I78C00
NOV 10, 2015 9:15 AM I78300 NOV 10, 2015 9:15 AM I78F00 NOV 10, 2015 9:15 AM I78700 NOV 10, 2015 9:15 AM
I70200 NOV 10, 2015 9:15 AM LIQUID LABEL DEVICE LABEL 1 89 STP 2 87 91 ANN 3 87 STP 4 91 STP 5 89 ANN 6 DISP 1-2 7 DISP 3-4 8 DISP 5-6 9 DISP 7-8 10 DISP 9-10 11 DISP 11-12 12 13 14 15 16 I70300 NOV 10, 2015 9:15 AM LIQUID TYPE SENSOR LOCATION TYPE 1 89 STP TRI-STATE (SINGLE FLOAT) 2 87 91 ANN TRI-STATE (SINGLE FLOAT) 3 87 STP TRI-STATE (SINGLE FLOAT) 4 91 STP TRI-STATE (SINGLE FLOAT) 5 89 ANN TRI-STATE (SINGLE FLOAT) 6 DISP 1-2 TRI-STATE (SINGLE FLOAT) 7 DISP 3-4 TRI-STATE (SINGLE FLOAT) 8 DISP 5-6 TRI-STATE (SINGLE FLOAT) 9 DISP 7-8 TRI-STATE (SINGLE FLOAT) 10 DISP 9-10 TRI-STATE (SINGLE FLOAT) 11 DISP 11-12 TRI-STATE (SINGLE FLOAT) 12 TRI-STATE (SINGLE FLOAT) 13 TRI-STATE (SINGLE FLOAT)
14 TRI-STATE (SINGLE FLOAT) 15 TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT) I70400 NOV 10, 2015 9:15 AM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 89 STP STP SUMP 2 87 91 ANN ANNULAR SPACE 3 87 STP STP SUMP 4 91 STP STP SUMP 5 89 ANN ANNULAR SPACE 6 DISP 1-2 DISPENSER PAN
7 DISP 3-4 DISPENSER PAN 8 DISP 5-6 DISPENSER PAN 9 DISP 7-8 DISPENSER PAN 10 DISP 9-10 DISPENSER PAN 11 DISP 11-12 DISPENSER PAN 12 OTHER SENSORS 13 OTHER SENSORS 14 OTHER SENSORS 15 OTHER SENSORS 16 OTHER SENSORS I74200 NOV 10, 2015 9:15 AM I74300 NOV 10, 2015 9:15 AM I74400 NOV 10, 2015 9:15 AM I74700 NOV 10, 2015 9:15 AM I74800 NOV 10, 2015 9:15 AM I74900 NOV 10, 2015 9:15 AM I7BC00 NOV 10, 2015 9:15 AM
I80200 NOV 10, 2015 9:15 AM I80300 NOV 10, 2015 9:15 AM I80400 NOV 10, 2015 9:15 AM
I80700 NOV 10, 2015 9:15 AM RELAY LABEL DEVICE LABEL 1 UNLEADED 2 PLUS 3 SUPREME 4 OVERFILL ALARM I80900 NOV 10, 2015 9:15 AM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 UNLEADED NORMALLY CLOSED 2 PLUS NORMALLY CLOSED 3 SUPREME NORMALLY CLOSED 4 OVERFILL ALARM NORMALLY OPEN I80B00 NOV 10, 2015 9:15 AM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 UNLEADED 3 2 PLUS 2 3 SUPREME 1 4 OVERFILL ALARM NONE I80A00 NOV 10, 2015 9:16 AM RELAY TYPE RELAY DESIGNATION TYPE
1 UNLEADED STANDARD 2 PLUS STANDARD 3 SUPREME STANDARD 4 OVERFILL ALARM STANDARD I80C00 NOV 10, 2015 9:16 AM I80800 NOV 10, 2015 9:16 AM RELAY SETUP REPORT R 1:UNLEADED
TYPE: STANDARD NORMALLY CLOSED TANK #: 3 LIQUID SENSOR ALMS L 3:FUEL ALARM L 6:FUEL ALARM L 7:FUEL ALARM L 8:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L 3:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 8:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L 3:SHORT ALARM L 6:SHORT ALARM L 7:SHORT ALARM L 8:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS h 1:GROSS COLLECT FAIL h 2:GROSS COLLECT FAIL h 3:GROSS COLLECT FAIL h 4:GROSS COLLECT FAIL h 5:GROSS COLLECT FAIL h 6:GROSS COLLECT FAIL h 7:GROSS COLLECT FAIL
h 8:GROSS COLLECT FAIL h 9:GROSS COLLECT FAIL h10:GROSS COLLECT FAIL h11:GROSS COLLECT FAIL h12:GROSS COLLECT FAIL h 1:DEGRD COLLECT FAIL h 2:DEGRD COLLECT FAIL h 3:DEGRD COLLECT FAIL h 4:DEGRD COLLECT FAIL h 5:DEGRD COLLECT FAIL h 6:DEGRD COLLECT FAIL h 7:DEGRD COLLECT FAIL h 8:DEGRD COLLECT FAIL h 9:DEGRD COLLECT FAIL h10:DEGRD COLLECT FAIL h11:DEGRD COLLECT FAIL h12:DEGRD COLLECT FAIL
R 2:PLUS TYPE: STANDARD NORMALLY CLOSED TANK #: 2 LIQUID SENSOR ALMS L 1:FUEL ALARM L 5:FUEL ALARM L 6:FUEL ALARM L 7:FUEL ALARM L 8:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L 1:SENSOR OUT ALARM L 5:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 8:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L 1:SHORT ALARM L 5:SHORT ALARM L 6:SHORT ALARM L 7:SHORT ALARM L 8:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS h 1:GROSS COLLECT FAIL h 2:GROSS COLLECT FAIL
h 3:GROSS COLLECT FAIL h 4:GROSS COLLECT FAIL h 5:GROSS COLLECT FAIL h 6:GROSS COLLECT FAIL h 7:GROSS COLLECT FAIL h 8:GROSS COLLECT FAIL h 9:GROSS COLLECT FAIL h10:GROSS COLLECT FAIL h11:GROSS COLLECT FAIL h12:GROSS COLLECT FAIL h 1:DEGRD COLLECT FAIL h 2:DEGRD COLLECT FAIL h 3:DEGRD COLLECT FAIL h 4:DEGRD COLLECT FAIL h 5:DEGRD COLLECT FAIL h 6:DEGRD COLLECT FAIL h 7:DEGRD COLLECT FAIL h 8:DEGRD COLLECT FAIL
h 9:DEGRD COLLECT FAIL h10:DEGRD COLLECT FAIL h11:DEGRD COLLECT FAIL h12:DEGRD COLLECT FAIL R 3:SUPREME TYPE: STANDARD NORMALLY CLOSED TANK #: 1 LIQUID SENSOR ALMS L 4:FUEL ALARM L 6:FUEL ALARM L 7:FUEL ALARM L 8:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L 4:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 8:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L 4:SHORT ALARM L 6:SHORT ALARM L 7:SHORT ALARM L 8:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS
h 1:GROSS COLLECT FAIL h 2:GROSS COLLECT FAIL h 3:GROSS COLLECT FAIL h 4:GROSS COLLECT FAIL h 5:GROSS COLLECT FAIL h 6:GROSS COLLECT FAIL h 7:GROSS COLLECT FAIL h 8:GROSS COLLECT FAIL h 9:GROSS COLLECT FAIL h10:GROSS COLLECT FAIL h11:GROSS COLLECT FAIL h12:GROSS COLLECT FAIL h 1:DEGRD COLLECT FAIL h 2:DEGRD COLLECT FAIL h 3:DEGRD COLLECT FAIL h 4:DEGRD COLLECT FAIL h 5:DEGRD COLLECT FAIL h 6:DEGRD COLLECT FAIL
h 7:DEGRD COLLECT FAIL h 8:DEGRD COLLECT FAIL h 9:DEGRD COLLECT FAIL h10:DEGRD COLLECT FAIL h11:DEGRD COLLECT FAIL h12:DEGRD COLLECT FAIL R 4:OVERFILL ALARM TYPE: STANDARD NORMALLY OPEN TANK #: NONE IN-TANK ALARMS ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM ALL:MAX PRODUCT ALARM I79000 NOV 10, 2015 9:16 AM EDIM:1 VR:349634-003-C TD:06.05.11.11.15 I79100 NOV 10, 2015 9:16 AM I72300 NOV 10, 2015 9:16 AM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301
SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 FM 1-2 AIR FLOW METER 02 FM 3-4 AIR FLOW METER 03 FM 5-6 AIR FLOW METER 04 FM 7-8 AIR FLOW METER 05 FM 9-10 AIR FLOW METER 06 FM 11-12 AIR FLOW METER 07 UNKNOWN 08 PS 1-2 VAPOR PRESSURE 09 UNKNOWN 10 UNKNOWN 11 UNKNOWN 12 UNKNOWN 13 UNKNOWN 14 UNKNOWN
15 UNKNOWN 16 UNKNOWN 17 UNKNOWN 18 UNKNOWN 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN 22 UNKNOWN 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN I72A00 NOV 10, 2015 9:16 AM VACUUM SENSOR VOLUME DEVICE LABEL VOLUME IV4E00 NOV 10, 2015 9:16 AM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301
EVR/ISD SETUP TYPE: VACUUM ASSIST VACUUM ASSIST TYPE: HEALY VAC IV4F00 NOV 10, 2015 9:16 AM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15
IV4000 NOV 10, 2015 9:16 AM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 VAPOR PROCESSOR TYPE NONE IV4700 NOV 10, 2015 9:16 AM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 ASSESSMENT TIME START TIME: 10:00 AM TIME DELAY MINUTES: 1 IV5200 NOV 10, 2015 9:16 AM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 ACCEPT HIGH ORVR: NO IV4A00 NOV 10, 2015 9:16 AM DOWNTOWN CHEV SOUTH 2317 L STREET
BAKERSFIELD CA 93301 ISD HOSE TABLE HOSE FP FP AFM HOSE ID ID LABEL ID LABEL 01 17 01 01 BLEND3 02 18 02 01 BLEND3 03 19 03 02 BLEND3 04 20 04 02 BLEND3 05 21 05 03 BLEND3 06 22 06 03 BLEND3 07 23 07 04 BLEND3 08 24 08 04 BLEND3 09 25 09 05 BLEND3 10 26 10 05 BLEND3 11 27 11 06 BLEND3
12 28 12 06 BLEND3 IV4B00 NOV 10, 2015 9:16 AM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 17 01 01/01 02/01 00/01 xx/xx 18 01 02/02 01/02 00/02 xx/xx 19 02 02/03 01/03 00/03 xx/xx 20 02 02/04 01/04 00/04 xx/xx 21 03 02/05 01/05 00/05 xx/xx 22 03 02/06 01/06 00/06 xx/xx 23 04 02/07 01/07 00/07 xx/xx 24 04 02/08 01/08 00/08 xx/xx 25 05 02/09 01/09 00/09 xx/xx 26 05 02/10 01/10 00/10 xx/xx 27 06 02/11 01/11 00/11 xx/xx 28 06 02/12 01/12 00/12 xx/xx IV4900 NOV 10, 2015 9:16 AM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM
06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 IV1000 NOV 10, 2015 9:16 AM ISD VERSION: 01.02
Downtown Chev South
Alarm Hist Before: Responses Received:
I10200 NOV 10, 2015 9:20 AM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 8SMARTSENSOR BD 39614 39575 2 4 PROBE / G.T. 162032 162196 3 INTERSTITIAL BD 200676 201031 4 INTERSTITIAL BD 200288 200458 5 UNUSED 8582861 9022190 6 UNUSED 8576936 9010814 7 UNUSED 8572884 9009959 8 UNUSED 8575912 9012480 9 RELAY BOARD 14962 14970 10 UNUSED 8576912 9015299 11 UNUSED 8569441 9008702 12 UNUSED 8582293 9013392 13 UNUSED 8581073 9013568 14 UNUSED 8577958 9009929 15 UNUSED 8571597 9005260 16 UNUSED 8575279 9012099 COMM 1 ELEC DISP INT. 100734 100823 COMM 2 RS232 SERIAL BD 14962 14970 COMM 3 UNUSED 8581117 9015431 COMM 4 UNUSED 8589133 9011069 COMM 5 SERIAL SAT BD 485401 485349 COMM 6 UNUSED 8584820 9009469 I90200 NOV 10, 2015 9:20 AM SOFTWARE REVISION LEVEL VERSION 329.00 SOFTWARE# 346329-100-A CREATED - 08.10.09.17.08 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD I11100 NOV 10, 2015 9:20 AM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301
PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME E 1 OTHER COMMUNICATION ALARM CLEAR 10-11-15 6:04PM E 1 OTHER COMMUNICATION ALARM ALARM 10-11-15 3:23PM E 1 OTHER COMMUNICATION ALARM CLEAR 10-11-15 3:17PM E 1 OTHER COMMUNICATION ALARM ALARM 10-11-15 11:45AM T 3 TANK UNLEADED OVERFILL ALARM CLEAR 8-24-15 2:40AM T 3 TANK UNLEADED OVERFILL ALARM ALARM 8-24-15 2:36AM T 3 TANK UNLEADED OVERFILL ALARM CLEAR 8-17-15 2:42AM T 3 TANK UNLEADED OVERFILL ALARM ALARM 8-17-15 2:38AM L 2 ANNULAR 87 91 ANN SENSOR OUT ALARM CLEAR 7-17-15 10:48AM L 2 ANNULAR 87 91 ANN SENSOR OUT ALARM ALARM 7-17-15 10:45AM h 5 OTHER FP5: BLEND3 GROSS COLLECT FAIL CLEAR 7-14-15 8:51AM h 5 OTHER FP5: BLEND3 GROSS COLLECT FAIL ALARM 7-13-15 10:03AM h 5 OTHER FP5: BLEND3 GROSS COLLECT FAIL CLEAR 7-13-15 10:03AM h 5 OTHER FP5: BLEND3 GROSS COLLECT FAIL ALARM 7-12-15 10:03AM T 3 TANK UNLEADED OVERFILL ALARM CLEAR 7-10-15 4:30AM T 3 TANK UNLEADED OVERFILL ALARM ALARM 7-10-15 4:26AM L 2 ANNULAR 87 91 ANN FUEL ALARM CLEAR 7-09-15 2:42PM L 2 ANNULAR 87 91 ANN FUEL ALARM ALARM 7-09-15 2:30PM T 1 TANK SUPREME PROBE OUT CLEAR 7-09-15 1:31PM T 1 TANK SUPREME PROBE OUT ALARM 7-09-15 1:30PM T 3 TANK UNLEADED PROBE OUT CLEAR 7-09-15 1:22PM T 3 TANK UNLEADED PROBE OUT ALARM 7-09-15 1:22PM L 2 ANNULAR 87 91 ANN FUEL ALARM CLEAR 7-09-15 1:22PM f 2 OTHER FM 3-4 CHK VAPOR FLOW MTR CLEAR 7-09-15 10:00AM L 2 ANNULAR 87 91 ANN FUEL ALARM ALARM 7-09-15 9:39AM T 3 TANK UNLEADED PROBE OUT CLEAR 7-09-15 8:30AM T 3 TANK UNLEADED PROBE OUT ALARM 7-09-15 8:29AM L 2 ANNULAR 87 91 ANN FUEL ALARM CLEAR 7-09-15 8:26AM T 3 TANK UNLEADED PROBE OUT CLEAR 7-09-15 8:25AM T 3 TANK UNLEADED PROBE OUT ALARM 7-09-15 8:25AM L 2 ANNULAR 87 91 ANN FUEL ALARM ALARM 7-08-15 4:17PM f 2 OTHER FM 3-4 CHK VAPOR FLOW MTR ALARM 7-08-15 10:03AM T 3 TANK UNLEADED OVERFILL ALARM CLEAR 7-02-15 2:05AM T 3 TANK UNLEADED OVERFILL ALARM ALARM 7-02-15 2:01AM f 2 OTHER FM 3-4 CHK VAPOR FLOW MTR CLEAR 7-01-15 7:44AM f 2 OTHER FM 3-4 CHK VAPOR FLOW MTR ALARM 6-30-15 10:03AM T 3 TANK UNLEADED OVERFILL ALARM CLEAR 6-26-15 2:38AM T 3 TANK UNLEADED OVERFILL ALARM ALARM 6-26-15 2:35AM L 7 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 6-24-15 9:27AM L 7 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 6-24-15 9:27AM L 7 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 6-24-15 9:27AM L 7 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 6-24-15 9:27AM
L 7 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 6-24-15 9:27AM L 7 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 6-24-15 9:23AM L 7 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 6-24-15 9:22AM L 7 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 6-24-15 9:22AM L 3 STP SUMP 87 STP FUEL ALARM CLEAR 6-18-15 2:58PM L 3 STP SUMP 87 STP FUEL ALARM ALARM 6-18-15 2:19PM T 3 TANK UNLEADED OVERFILL ALARM CLEAR 6-07-15 4:48AM T 3 TANK UNLEADED OVERFILL ALARM ALARM 6-07-15 4:44AM I11200 NOV 10, 2015 9:20 AM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301
NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN CLEAR 11-09-15 4:21PM h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN CLEAR 11-09-15 10:00AM SYSTEM PRINTER ERROR CLEAR 11-08-15 4:12AM SYSTEM PRINTER ERROR ALARM 11-08-15 4:12AM SYSTEM PRINTER ERROR CLEAR 11-08-15 4:12AM SYSTEM PAPER OUT CLEAR 11-08-15 4:12AM SYSTEM PAPER OUT ALARM 11-08-15 4:11AM SYSTEM PRINTER ERROR ALARM 11-08-15 4:11AM SYSTEM PRINTER ERROR CLEAR 11-08-15 3:15AM SYSTEM PRINTER ERROR ALARM 11-08-15 3:15AM SYSTEM PRINTER ERROR CLEAR 11-08-15 3:14AM SYSTEM PRINTER ERROR ALARM 11-08-15 3:14AM SYSTEM PRINTER ERROR CLEAR 11-08-15 3:14AM SYSTEM PRINTER ERROR ALARM 11-08-15 3:14AM SYSTEM PRINTER ERROR CLEAR 11-08-15 3:13AM SYSTEM PAPER OUT CLEAR 11-08-15 3:13AM SYSTEM PAPER OUT ALARM 11-08-15 3:13AM SYSTEM PAPER OUT CLEAR 11-08-15 3:13AM SYSTEM PRINTER ERROR ALARM 11-08-15 3:13AM SYSTEM PAPER OUT ALARM 11-08-15 3:13AM SYSTEM PRINTER ERROR CLEAR 11-08-15 3:13AM SYSTEM PAPER OUT CLEAR 11-08-15 3:13AM SYSTEM PRINTER ERROR ALARM 11-08-15 3:13AM SYSTEM PAPER OUT ALARM 11-08-15 3:13AM SYSTEM PRINTER ERROR CLEAR 11-08-15 3:13AM SYSTEM PAPER OUT CLEAR 11-08-15 3:13AM SYSTEM PRINTER ERROR ALARM 11-08-15 3:13AM SYSTEM PAPER OUT ALARM 11-08-15 3:13AM SYSTEM PRINTER ERROR CLEAR 11-08-15 3:13AM SYSTEM PAPER OUT CLEAR 11-08-15 3:13AM SYSTEM PRINTER ERROR ALARM 11-08-15 3:13AM SYSTEM PAPER OUT ALARM 11-08-15 3:13AM SYSTEM PRINTER ERROR CLEAR 11-07-15 11:39PM SYSTEM PRINTER ERROR ALARM 11-07-15 11:39PM SYSTEM PRINTER ERROR CLEAR 11-07-15 11:38PM SYSTEM PAPER OUT CLEAR 11-07-15 11:38PM SYSTEM PRINTER ERROR ALARM 11-07-15 11:37PM SYSTEM PAPER OUT ALARM 11-07-15 11:37PM h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN ALARM 11-05-15 10:01AM h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN ALARM 11-04-15 10:01AM h12 OTHER FP12: BLEND3 DEGRD COLLECT WARN CLEAR 11-03-15 6:14PM h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN CLEAR 11-03-15 6:13PM
OTHER ISD GROSS PRES WARN CLEAR 11-03-15 5:35PM OTHER ISD GROSS PRES WARN ALARM 11-03-15 10:01AM h12 OTHER FP12: BLEND3 DEGRD COLLECT WARN ALARM 11-03-15 10:01AM h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN ALARM 11-03-15 10:01AM h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN CLEAR 10-29-15 10:00AM h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN ALARM 10-28-15 10:03AM h12 OTHER FP12: BLEND3 DEGRD COLLECT WARN CLEAR 10-23-15 11:38AM h12 OTHER FP12: BLEND3 DEGRD COLLECT WARN ALARM 10-23-15 10:03AM I20600 NOV 10, 2015 9:20 AM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301
TANK ALARM HISTORY TANK 1 SUPREME PROBE OUT JUL 9, 2015 1:30 PM TANK 2 PLUS TANK 3 UNLEADED OVERFILL ALARM AUG 24, 2015 2:36 AM AUG 17, 2015 2:38 AM JUL 10, 2015 4:26 AM PROBE OUT JUL 9, 2015 1:22 PM JUL 9, 2015 8:29 AM JUL 9, 2015 8:25 AM I38200 NOV 10, 2015 9:20 AM I30200 NOV 10, 2015 9:20 AM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 89 STP MAY 22, 2015 12:03 PM FUEL ALARM MAY 22, 2015 11:04 AM FUEL ALARM MAY 22, 2015 10:06 AM FUEL ALARM 2 87 91 ANN JUL 17, 2015 10:45 AM SENSOR OUT ALARM
JUL 9, 2015 2:42 PM SETUP DATA WARNING JUL 9, 2015 2:30 PM FUEL ALARM 3 87 STP JUN 18, 2015 2:19 PM FUEL ALARM MAY 22, 2015 9:39 AM FUEL ALARM 4 91 STP MAY 22, 2015 12:08 PM FUEL ALARM MAY 22, 2015 12:05 PM FUEL ALARM MAY 22, 2015 12:04 PM FUEL ALARM 5 89 ANN MAY 22, 2015 12:04 PM FUEL ALARM MAY 22, 2015 9:48 AM FUEL ALARM 6 DISP 1-2 MAY 22, 2015 10:07 AM FUEL ALARM 7 DISP 3-4 JUN 24, 2015 9:27 AM SENSOR OUT ALARM JUN 24, 2015 9:27 AM SENSOR OUT ALARM JUN 24, 2015 9:23 AM SENSOR OUT ALARM
8 DISP 5-6 MAY 22, 2015 5:03 PM FUEL ALARM MAY 22, 2015 10:07 AM FUEL ALARM 9 DISP 7-8 MAY 22, 2015 9:34 AM FUEL ALARM 10 DISP 9-10 MAY 22, 2015 9:37 AM FUEL ALARM 11 DISP 11-12 MAY 22, 2015 9:33 AM FUEL ALARM I31600 NOV 10, 2015 9:20 AM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 FM 1-2 2 FM 3-4 OCT 9, 2008 8:11 AM COMMUNICATION ALARM 3 FM 5-6 OCT 9, 2008 8:11 AM COMMUNICATION ALARM 4 FM 7-8 OCT 9, 2008 8:11 AM COMMUNICATION ALARM 5 FM 9-10 OCT 9, 2008 8:11 AM COMMUNICATION ALARM 6 FM 11-12 OCT 9, 2008 8:11 AM COMMUNICATION ALARM 8 PS 1-2 OCT 9, 2008 8:11 AM COMMUNICATION ALARM I40200 NOV 10, 2015 9:20 AM I40300
NOV 10, 2015 9:20 AM I34200 NOV 10, 2015 9:20 AM I34700 NOV 10, 2015 9:20 AM IV0100 NOV 10, 2015 9:20 AM DOWNTOWN CHEV SOUTH
2317 L STREET BAKERSFIELD CA 93301 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.02 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :WARN EVR VAPOR COLLECTION :WARN EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% STAGE I TRANSFERS: 0 of 0 NOTEST EVR/ISD PASS TIME : 0% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 15-11-09 10:01:31 A/L RATIO DEGRADATION FP 3 BLEND3 0.77 15-11-08 10:01:43 A/L RATIO DEGRADATION FP 6 BLEND3 0.80 15-11-08 10:01:43 A/L RATIO DEGRADATION FP 3 BLEND3 0.76 15-11-07 10:02:21 A/L RATIO DEGRADATION FP 6 BLEND3 0.79 15-11-07 10:02:21 A/L RATIO DEGRADATION FP 3 BLEND3 0.74 15-11-06 10:02:21 A/L RATIO DEGRADATION FP 6 BLEND3 0.77 15-11-06 10:02:21 A/L RATIO DEGRADATION FP 3 BLEND3 0.76 15-11-05 10:01:26 A/L RATIO DEGRADATION FP 6 BLEND3 0.79 15-11-05 10:01:26 A/L RATIO DEGRADATION FP 3 BLEND3 0.78 15-11-04 10:01:09 A/L RATIO DEGRADATION FP 3 BLEND3 0.80 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 15-07-13 10:03:17 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD 15-07-12 10:03:57 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD 15-05-31 10:09:16 A/L RATIO GROSS BLOCKAGE FP 9 BLEND3 0.29 15-05-22 00:00:09 SENSOR OUT SELFTEST E 1 15-05-22 00:00:09 SETUP SELFTEST MISSING TANK(S) 15-05-22 00:00:09 SETUP SELFTEST MISSING HOSE(S) 15-05-21 00:00:09 SENSOR OUT SELFTEST s 8 15-05-21 00:00:09 SENSOR OUT SELFTEST s 1 15-05-21 00:00:09 SENSOR OUT SELFTEST E 1 15-05-21 00:00:09 SETUP SELFTEST MISSING TANK(S) SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME 15-11-09 16:21:18 COLLECTION TEST HH03 GRADE TEST MANUALLY CLEARED 15-11-03 18:14:03 COLLECTION TEST HH12 GRADE TEST MANUALLY CLEARED 15-11-03 18:13:56 COLLECTION TEST HH10 GRADE TEST MANUALLY CLEARED 15-11-03 17:35:53 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 15-11-01 01:00:00 TIME CHANGE DETECTED AT: 15-11-01 02:00:13 15-10-23 11:38:39 COLLECTION TEST HH12 GRADE TEST MANUALLY CLEARED 15-10-12 10:01:09 READINESS ISD:PP EVR:PP ISD & EVR READY 15-10-11 15:17:46 READINESS ISD:PP EVR:NN EVR READINESS PENDING 15-10-11 15:17:46 ISD STARTUP 15-10-11 15:17:39 ISD SHUTDOWN
Downtown chevron south
Alarm history after: Responses Received:
I10200 NOV 10, 2015 11:37 AM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 8SMARTSENSOR BD 39614 39741 2 4 PROBE / G.T. 162032 162564 3 INTERSTITIAL BD 200676 201413 4 INTERSTITIAL BD 200288 200874 5 UNUSED 8582861 9353974 6 UNUSED 8576936 9353630 7 UNUSED 8572884 9333372 8 UNUSED 8575912 9347322 9 RELAY BOARD 14962 14992 10 UNUSED 8576912 9342596 11 UNUSED 8569441 9347354 12 UNUSED 8582293 9333813 13 UNUSED 8581073 9347419 14 UNUSED 8577958 9336892 15 UNUSED 8571597 9340207 16 UNUSED 8575279 9347225 COMM 1 ELEC DISP INT. 100734 100995 COMM 2 RS232 SERIAL BD 14962 14992 COMM 3 UNUSED 8581117 9333060 COMM 4 UNUSED 8589133 9348882 COMM 5 SERIAL SAT BD 485401 485978 COMM 6 UNUSED 8584820 9354070 I90200 NOV 10, 2015 11:37 AM SOFTWARE REVISION LEVEL VERSION 329.00 SOFTWARE# 346329-100-A CREATED - 08.10.09.17.08 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD I11100 NOV 10, 2015 11:37 AM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301
PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L10 DISP PAN DISP 9-10 FUEL ALARM CLEAR 11-10-15 11:04AM L10 DISP PAN DISP 9-10 FUEL ALARM ALARM 11-10-15 11:03AM L 4 STP SUMP 91 STP SENSOR OUT ALARM CLEAR 11-10-15 10:33AM L 8 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 11-10-15 10:33AM L 7 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 11-10-15 10:33AM L 6 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 11-10-15 10:33AM L 3 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 11-10-15 10:33AM L 2 ANNULAR 87 91 ANN SENSOR OUT ALARM CLEAR 11-10-15 10:33AM L 5 ANNULAR 89 ANN SENSOR OUT ALARM CLEAR 11-10-15 10:33AM L 1 STP SUMP 89 STP SENSOR OUT ALARM CLEAR 11-10-15 10:33AM L10 DISP PAN DISP 9-10 SENSOR OUT ALARM CLEAR 11-10-15 10:33AM L11 DISP PAN DISP 11-12 SENSOR OUT ALARM CLEAR 11-10-15 10:33AM L 9 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 11-10-15 10:33AM L 4 STP SUMP 91 STP SENSOR OUT ALARM ALARM 11-10-15 10:32AM L 3 STP SUMP 87 STP SENSOR OUT ALARM ALARM 11-10-15 10:32AM L 8 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 11-10-15 10:32AM L 7 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 11-10-15 10:32AM L 2 ANNULAR 87 91 ANN SENSOR OUT ALARM ALARM 11-10-15 10:32AM L 6 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 11-10-15 10:32AM L 1 STP SUMP 89 STP SENSOR OUT ALARM ALARM 11-10-15 10:32AM L 5 ANNULAR 89 ANN SENSOR OUT ALARM ALARM 11-10-15 10:32AM L11 DISP PAN DISP 11-12 SENSOR OUT ALARM ALARM 11-10-15 10:32AM L10 DISP PAN DISP 9-10 SENSOR OUT ALARM ALARM 11-10-15 10:32AM L 9 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 11-10-15 10:32AM T 2 TANK PLUS PROBE OUT CLEAR 11-10-15 10:24AM T 2 TANK PLUS OVERFILL ALARM CLEAR 11-10-15 10:24AM T 2 TANK PLUS PROBE OUT ALARM 11-10-15 10:24AM T 2 TANK PLUS OVERFILL ALARM ALARM 11-10-15 10:23AM T 1 TANK SUPREME PROBE OUT CLEAR 11-10-15 10:21AM T 1 TANK SUPREME OVERFILL ALARM CLEAR 11-10-15 10:20AM T 1 TANK SUPREME PROBE OUT ALARM 11-10-15 10:20AM T 1 TANK SUPREME OVERFILL ALARM ALARM 11-10-15 10:20AM T 3 TANK UNLEADED PROBE OUT CLEAR 11-10-15 10:19AM T 3 TANK UNLEADED OVERFILL ALARM CLEAR 11-10-15 10:18AM T 3 TANK UNLEADED PROBE OUT ALARM 11-10-15 10:18AM T 3 TANK UNLEADED OVERFILL ALARM ALARM 11-10-15 10:18AM L 2 ANNULAR 87 91 ANN FUEL ALARM CLEAR 11-10-15 10:17AM L 2 ANNULAR 87 91 ANN FUEL ALARM ALARM 11-10-15 10:16AM L 5 ANNULAR 89 ANN FUEL ALARM CLEAR 11-10-15 10:16AM L 5 ANNULAR 89 ANN FUEL ALARM ALARM 11-10-15 10:15AM L10 DISP PAN DISP 9-10 FUEL ALARM CLEAR 11-10-15 10:15AM L10 DISP PAN DISP 9-10 FUEL ALARM ALARM 11-10-15 10:13AM
L11 DISP PAN DISP 11-12 FUEL ALARM CLEAR 11-10-15 10:09AM L11 DISP PAN DISP 11-12 FUEL ALARM ALARM 11-10-15 10:08AM L 9 DISP PAN DISP 7-8 FUEL ALARM CLEAR 11-10-15 10:07AM L 9 DISP PAN DISP 7-8 FUEL ALARM ALARM 11-10-15 10:07AM L 8 DISP PAN DISP 5-6 FUEL ALARM CLEAR 11-10-15 10:06AM L 8 DISP PAN DISP 5-6 FUEL ALARM ALARM 11-10-15 10:05AM L 7 DISP PAN DISP 3-4 FUEL ALARM CLEAR 11-10-15 10:04AM L 7 DISP PAN DISP 3-4 FUEL ALARM ALARM 11-10-15 10:04AM I11200 NOV 10, 2015 11:37 AM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301
NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME T 1 TANK SUPREME LOW TEMP WARNING CLEAR 11-10-15 10:22AM T 1 TANK SUPREME LOW TEMP WARNING ALARM 11-10-15 10:21AM T 3 TANK UNLEADED LOW TEMP WARNING CLEAR 11-10-15 10:20AM T 3 TANK UNLEADED LOW TEMP WARNING ALARM 11-10-15 10:19AM OTHER ISD GROSS PRES WARN ALARM 11-10-15 10:01AM h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN CLEAR 11-09-15 4:21PM h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN CLEAR 11-09-15 10:00AM SYSTEM PRINTER ERROR CLEAR 11-08-15 4:12AM SYSTEM PRINTER ERROR ALARM 11-08-15 4:12AM SYSTEM PRINTER ERROR CLEAR 11-08-15 4:12AM SYSTEM PAPER OUT CLEAR 11-08-15 4:12AM SYSTEM PAPER OUT ALARM 11-08-15 4:11AM SYSTEM PRINTER ERROR ALARM 11-08-15 4:11AM SYSTEM PRINTER ERROR CLEAR 11-08-15 3:15AM SYSTEM PRINTER ERROR ALARM 11-08-15 3:15AM SYSTEM PRINTER ERROR CLEAR 11-08-15 3:14AM SYSTEM PRINTER ERROR ALARM 11-08-15 3:14AM SYSTEM PRINTER ERROR CLEAR 11-08-15 3:14AM SYSTEM PRINTER ERROR ALARM 11-08-15 3:14AM SYSTEM PRINTER ERROR CLEAR 11-08-15 3:13AM SYSTEM PAPER OUT CLEAR 11-08-15 3:13AM SYSTEM PAPER OUT ALARM 11-08-15 3:13AM SYSTEM PAPER OUT CLEAR 11-08-15 3:13AM SYSTEM PRINTER ERROR ALARM 11-08-15 3:13AM SYSTEM PAPER OUT ALARM 11-08-15 3:13AM SYSTEM PRINTER ERROR CLEAR 11-08-15 3:13AM SYSTEM PAPER OUT CLEAR 11-08-15 3:13AM SYSTEM PRINTER ERROR ALARM 11-08-15 3:13AM SYSTEM PAPER OUT ALARM 11-08-15 3:13AM SYSTEM PRINTER ERROR CLEAR 11-08-15 3:13AM SYSTEM PAPER OUT CLEAR 11-08-15 3:13AM SYSTEM PRINTER ERROR ALARM 11-08-15 3:13AM SYSTEM PAPER OUT ALARM 11-08-15 3:13AM SYSTEM PRINTER ERROR CLEAR 11-08-15 3:13AM SYSTEM PAPER OUT CLEAR 11-08-15 3:13AM SYSTEM PRINTER ERROR ALARM 11-08-15 3:13AM SYSTEM PAPER OUT ALARM 11-08-15 3:13AM SYSTEM PRINTER ERROR CLEAR 11-07-15 11:39PM SYSTEM PRINTER ERROR ALARM 11-07-15 11:39PM SYSTEM PRINTER ERROR CLEAR 11-07-15 11:38PM SYSTEM PAPER OUT CLEAR 11-07-15 11:38PM SYSTEM PRINTER ERROR ALARM 11-07-15 11:37PM
SYSTEM PAPER OUT ALARM 11-07-15 11:37PM h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN ALARM 11-05-15 10:01AM h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN ALARM 11-04-15 10:01AM h12 OTHER FP12: BLEND3 DEGRD COLLECT WARN CLEAR 11-03-15 6:14PM h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN CLEAR 11-03-15 6:13PM OTHER ISD GROSS PRES WARN CLEAR 11-03-15 5:35PM OTHER ISD GROSS PRES WARN ALARM 11-03-15 10:01AM h12 OTHER FP12: BLEND3 DEGRD COLLECT WARN ALARM 11-03-15 10:01AM I20600 NOV 10, 2015 11:37 AM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301
TANK ALARM HISTORY TANK 1 SUPREME OVERFILL ALARM NOV 10, 2015 10:20 AM PROBE OUT NOV 10, 2015 10:20 AM NOV 10, 2015 9:27 AM JUL 9, 2015 1:30 PM LOW TEMP WARNING NOV 10, 2015 10:21 AM TANK 2 PLUS OVERFILL ALARM NOV 10, 2015 10:23 AM PROBE OUT NOV 10, 2015 10:24 AM NOV 10, 2015 9:26 AM TANK 3 UNLEADED OVERFILL ALARM NOV 10, 2015 10:18 AM AUG 24, 2015 2:36 AM AUG 17, 2015 2:38 AM PROBE OUT NOV 10, 2015 10:18 AM NOV 10, 2015 9:27 AM JUL 9, 2015 1:22 PM LOW TEMP WARNING NOV 10, 2015 10:19 AM I38200 NOV 10, 2015 11:37 AM I30200 NOV 10, 2015 11:37 AM DOWNTOWN CHEV SOUTH
2317 L STREET BAKERSFIELD CA 93301 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 89 STP NOV 10, 2015 10:32 AM SENSOR OUT ALARM NOV 10, 2015 9:58 AM FUEL ALARM NOV 10, 2015 9:55 AM FUEL ALARM 2 87 91 ANN NOV 10, 2015 10:32 AM SENSOR OUT ALARM NOV 10, 2015 10:16 AM FUEL ALARM JUL 17, 2015 10:45 AM SENSOR OUT ALARM 3 87 STP NOV 10, 2015 10:32 AM SENSOR OUT ALARM NOV 10, 2015 9:44 AM FUEL ALARM
JUN 18, 2015 2:19 PM FUEL ALARM 4 91 STP NOV 10, 2015 10:32 AM SENSOR OUT ALARM NOV 10, 2015 9:40 AM FUEL ALARM NOV 10, 2015 9:39 AM FUEL ALARM 5 89 ANN NOV 10, 2015 10:32 AM SENSOR OUT ALARM NOV 10, 2015 10:15 AM FUEL ALARM MAY 22, 2015 12:04 PM FUEL ALARM 6 DISP 1-2 NOV 10, 2015 10:32 AM SENSOR OUT ALARM NOV 10, 2015 10:01 AM FUEL ALARM MAY 22, 2015 10:07 AM FUEL ALARM 7 DISP 3-4 NOV 10, 2015 10:32 AM SENSOR OUT ALARM NOV 10, 2015 10:04 AM FUEL ALARM JUN 24, 2015 9:27 AM SENSOR OUT ALARM 8 DISP 5-6 NOV 10, 2015 10:32 AM SENSOR OUT ALARM NOV 10, 2015 10:05 AM FUEL ALARM MAY 22, 2015 5:03 PM FUEL ALARM 9 DISP 7-8 NOV 10, 2015 10:32 AM SENSOR OUT ALARM NOV 10, 2015 10:07 AM FUEL ALARM MAY 22, 2015 9:34 AM FUEL ALARM 10 DISP 9-10 NOV 10, 2015 11:03 AM FUEL ALARM NOV 10, 2015 10:32 AM SENSOR OUT ALARM NOV 10, 2015 10:13 AM FUEL ALARM 11 DISP 11-12 NOV 10, 2015 10:32 AM SENSOR OUT ALARM NOV 10, 2015 10:08 AM FUEL ALARM MAY 22, 2015 9:33 AM FUEL ALARM I31600 NOV 10, 2015 11:37 AM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION 1 FM 1-2 2 FM 3-4 OCT 9, 2008 8:11 AM COMMUNICATION ALARM 3 FM 5-6 OCT 9, 2008 8:11 AM COMMUNICATION ALARM 4 FM 7-8 OCT 9, 2008 8:11 AM COMMUNICATION ALARM 5 FM 9-10 OCT 9, 2008 8:11 AM COMMUNICATION ALARM 6 FM 11-12 OCT 9, 2008 8:11 AM COMMUNICATION ALARM 8 PS 1-2 OCT 9, 2008 8:11 AM COMMUNICATION ALARM
I40200 NOV 10, 2015 11:37 AM I40300 NOV 10, 2015 11:37 AM I34200 NOV 10, 2015 11:37 AM I34700 NOV 10, 2015 11:37 AM IV0100 NOV 10, 2015 11:37 AM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.02 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :WARN EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :WARN ISD MONITOR UP-TIME :100% STAGE I TRANSFERS: 0 of 0 NOTEST EVR/ISD PASS TIME : 0% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 15-11-10 10:01:19 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.71 15-11-09 10:01:31 A/L RATIO DEGRADATION FP 3 BLEND3 0.77 15-11-08 10:01:43 A/L RATIO DEGRADATION FP 6 BLEND3 0.80 15-11-08 10:01:43 A/L RATIO DEGRADATION FP 3 BLEND3 0.76
15-11-07 10:02:21 A/L RATIO DEGRADATION FP 6 BLEND3 0.79 15-11-07 10:02:21 A/L RATIO DEGRADATION FP 3 BLEND3 0.74 15-11-06 10:02:21 A/L RATIO DEGRADATION FP 6 BLEND3 0.77 15-11-06 10:02:21 A/L RATIO DEGRADATION FP 3 BLEND3 0.76 15-11-05 10:01:26 A/L RATIO DEGRADATION FP 6 BLEND3 0.79 15-11-05 10:01:26 A/L RATIO DEGRADATION FP 3 BLEND3 0.78 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 15-07-13 10:03:17 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD 15-07-12 10:03:57 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD 15-05-31 10:09:16 A/L RATIO GROSS BLOCKAGE FP 9 BLEND3 0.29 15-05-22 00:00:09 SENSOR OUT SELFTEST E 1 15-05-22 00:00:09 SETUP SELFTEST MISSING TANK(S) 15-05-22 00:00:09 SETUP SELFTEST MISSING HOSE(S) 15-05-21 00:00:09 SENSOR OUT SELFTEST s 8
15-05-21 00:00:09 SENSOR OUT SELFTEST s 1 15-05-21 00:00:09 SENSOR OUT SELFTEST E 1 15-05-21 00:00:09 SETUP SELFTEST MISSING TANK(S) SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 15-11-10 10:32:20 READINESS ISD:PP EVR:NN EVR READINESS PENDING 15-11-10 10:32:20 ISD STARTUP 15-11-10 10:30:12 ISD SHUTDOWN 15-11-09 16:21:18 COLLECTION TEST HH03 GRADE TEST MANUALLY CLEARED 15-11-03 18:14:03 COLLECTION TEST HH12 GRADE TEST MANUALLY CLEARED 15-11-03 18:13:56 COLLECTION TEST HH10 GRADE TEST MANUALLY CLEARED 15-11-03 17:35:53 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 15-11-01 01:00:00 TIME CHANGE DETECTED AT: 15-11-01 02:00:13 15-10-23 11:38:39 COLLECTION TEST HH12 GRADE TEST MANUALLY CLEARED 15-10-12 10:01:09 READINESS ISD:PP EVR:PP ISD & EVR READY
SWRCB, January 2006
Spill Bucket Testing Report Form
This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and
printouts from tests (if applicable), should be provided to the facility owner/operator forsubmittal to the local regulatory agency.
1.FACILITY INFORMATION
Facility Name:Date of Testing:
Facility Address:
Facility Contact:Phone:
Date Local Agency Was Notified of Testing :
Name of Local Agency Inspector (if present during testing):
2.TESTING CONTRACTOR INFORMATION
Company Name:Confidence UST Services, Inc.
Technician Conducting Test:
Credentials1:CSLB Contractor ICC Service Tech. SWRCB Tank Tester Other (Specify)
License Number(s):CSLB#804904 ICC#
3.SPILL BUCKET TESTING INFORMATION
Test Method Used:Hydrostatic Vacuum Other
Test Equipment Used:Lake TestEquipment Resolution:0.0625”
Identify Spill Bucket (By Tank
Number, Stored Product, etc.)
1234
Bucket Installation Type: Direct Bury
Contained in Sump
Direct Bury
Contained in Sump
Direct Bury
Contained in Sump
Direct Bury
Contained in Sump
Bucket Diameter:
Bucket Depth:
Wait time between applying
vacuum/water and start of test:
Test Start Time (TI):
Initial Reading (RI):
Test End Time (TF):
Final Reading (RF):
Test Duration (TF – TI):
Change in Reading (RF -RI):
Pass/Fail Threshold or
Criteria:
Test Result: Pass Fail Pass Fail Pass Fail Pass Fail
Comments –(include information on repairs made prior to testing, and recommended follow-up for failed tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements.
Technician’s Signature:________________________________________________ Date:_________
1 State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
Sully'sDowntown(South)11/10/2015
2317LStreet Bakersfield,CA93301
FrankSullivan(661)327-5008
11/3/2015
Kris karns
DustinReese
8216722-UT
Regular
12.00"
12.00"
5min.
9:10 am
10.25"
10:10 am
10.25"
1hour
0.00"
0.0625"
Plus
12.00"
12.00"
5min.
9:10 am
10.25"
10:10 am
10.25"
1hour
0.00"
0.0625"0.0625"
Super
12.00"
12.00"
5min.
9:10 am
10.75"
10:10 am
10.75"
1hour
0.00"
"
11/10/2015