Shane Gardner / Kris Karns
BAKERSFIELD FIRE DEPARTMENT
2101 H Street
Bakersfield, CA 93301
SB989 POST REPAIR SECONDARY COMPLIANCE TEST
SUBJECT: SB 989 POST REPAIR COMPLIANCE TESTING AT COSTCO FUELING STATION —
3800 ROSEDALE HWY, BAKERSFIELD, CA 93308 — FACILITY NO. 688
Below please find the post repair secondary containment testing results for the above - referenced site. These results are
being sent to you per the requirement of SB 989. Repairs were made pursuant to Bakersfield City Fire Permit #15-
10000205. Post Repair testing performed by Wayne Perry, Inc., in the presence of Inspector Karns, on 4/24/2015 with
components passing. Please see attached report for further details.
CONTRACTOR:
License No:
Technician:
Sincerely,
Wayne Perry, Inc.
JW ary young
Mary Young
Program Coordinator
Wayne Perry, Inc.
300345
Leonard Alan Evans — ICC #8221154
Attachments — Testing Results
Cc: Dennis Bock — Costco Wholesale
Costco Site #688
8281 Commonwealth Avenue Buena Park, California 90621 Phone (714) 826 -0352 Fax (714) 523 -9735
Page 1 of 3
Secondary Containment Testing Report Form
This form is intended for use by contractors performing periodic testing of UST secondary containment systems. Use the
appropriate pages of this form to report results for all components tested. The completed form, written test procedures, and
printouts from tests (if applicable), should be provided to the facility owner /operator for submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: COSTCO #688
1 Date of Testing: 4/24/2015
Facility Address: 3800 ROSEDALE HWY, BAKERSFIELD, CA 93308
Facility Contact:
I Phone:
Date Local Agency Was Notified of Testing: 4/22/2015
Name of Local Agency Inspector (ifpresent during testing): Kris Karns
2. TESTING CONTRACTOR INFORMATION
Company Name: Wayne Perry, Incorporated
Technician Conducting Test: Leonard Alan Evans — ICC #8221154
Credentials: X CSLB Licensed Contractor SWRCB Licensed Tank Tester
License Type: A, HAZ, C21, C10, B , C61, D40 License Number: 300345
Manufacturer Training
Manufacturer Component(s) Date Training Expires
Furnished on request
3. SUMMARY OF TEST RESULTS
rr•r ®
® ®
®�� i
i rir•r
• Sump M
MAN,
o
oaoo o
oor�c�
0000 c
c■�c•�oo
0000 0
0000
0000 0
0000
000r■�■ o
oc•�c•�o
oor■�o 0
0000
r•�000 o
or�oo
0000 c
c•�c■�oo
0000 c
c�000
If hydrostatic testing was performed, describe what was done with the water after completion of tests:
No drums were left on site
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
To the best of my knowledge, the facts stated in this document are accurate and in full compliance with legal requirements
Technician's Signature:
A411 Date:_ 4/24/2015
Page 2 of 3
Test Method Developed By: ❑ Piping Manufacturer ® Industry Standard ❑ Professional Engineer
Other (Sped)
Test Method Used: ® Pressure ❑ Vacuum ❑ Hydrostatic
❑ Other (Specify)
Test Equipment Used: See attached testing procedures
Equipment Resolution:
i. rwM'v ......n
V ^4�-F v2t � S`
rc�
..... ,. �W.
a"% ✓..�.,eka�.a,fi..N.+m..,�.v. � ..r.J� C 3:. +rd,rnrti:.�
Piping Run # 87
Piping Run #
Piping Run #
Piping Run #
Syphon
Piping Material:
Fiberglass
Piping Manufacturer:
Smith
Piping Diameter:
2 99/3"
Length of Piping Run:
Approx 20'
Product Stored:
Regular
Method and location of
Test Boots in Sump
piping-run isolation:
Wait time between applying
30 minutes
30 minutes
30 minutes
30 minutes
pressure /vacuum/water and
starting test:
Test Start Time:
8:45am
Initial Reading (RI):
5 psi
Test End Time:
9:45am
Final Reading (RF):
5 psi
Test Duration:
1 hour
1 hour
1 hour
1 hour
Change in Reading (RF -RI):
0
Pass/Fail Threshold or
0.00
0.00
0.00
0.00
Criteria:
Test- Result:
® Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
❑Pass ❑Fail
Comments — (include information on repairs made prior to testing, and recommended follow -up for failed tests)
Repairs made pursuant to Bakersfield Fire Permit 15- 10000205 — Inspector Kris Karns present during inspection
Page 3 of 3
2. PIPING SUMP TESTING
Test Method Developed By: F-1 Sump Manufacturer Z Industry Standard F-1 Professional Engineer
❑ Other (Specify)
Test Method Used: F-1 Pressure ❑ Vacuum Hydrostatic
❑ Other (Specify)
Test Equipment Used: See attached testing procedures
Equipment Resolution:
Yti .1R 4 4 ,
Sump # 87 Aux
Sump# 87 Aux
Sump# 91
Sump# 91
Sump Diameter:
48"
4899
48"
4899
Sump Depth:
6299
62"
62"
62"
Sump Material & Manufacturer:
Fiberglass
Fiberglass
Fiberglass
Fiberglass
Height from Tank Top to Top of
2691)
2691
2699
2699
Piping Penetration:
-Highest
Height from Tank Top to Lowest
2491
2499
2299
2299
Electrical Penetration:
Condition of sump prior to testing:
Fair
Fair
Fair
Fair
Portion of Sump Tested'
Above highest
Above highest
Above highest
Above highest
penetration
penetration
penetration
penetration
Does turbine shut down when
sump sensor detects liquid (both
[:1 Yes ❑ No Z NA
❑Yes [:1 No Z NA
❑Yes ❑ No Z NA
❑ Yes ❑ No Z NA
product and water)?*
Turbine shutdown response time
Is system programmed for fail-safe
F] Yes El No Z NA
❑Yes ❑ No Z NA
❑Yes [I No Z NA
El Yes ❑ No Z NA
shutdown ?*
Was fail-safe verified to be
❑ Yes [:1 No Z NA
❑Yes ❑ No Z NA
❑Yes ❑ No Z NA
❑ Yes ❑ No Z NA
operational?*
Wait time between applying
pressure/vacuum/water and starting
30 minutes
30 minutes
30 minutes
30 minutes
test:
Test Start Time:
9:21am,
9:38am
9:12am
9:28am
Initial Reading (RI):
5.1048
5.1046
4.0364
4.0360
Test End Time:
9:36am
9:53am.
9:27am
9:434am
Final Reading (RF):
5.1045
5.1039
4.0360
4.0359
Test Duration:
15 min
15 min
15 min
15 min
Change in Reading (RF-R,):
0.00038
0.00067
0.00040
0.00013
Pass/Fail Threshold or Criteria:
0.002
0.002
0.002
0.002
Test Result:
0 Pass ❑ Fail
Z Pass ❑ Fail
Z Pass ❑ Fail
0 Pass ❑ Fail
Was sensor removed for testing?
0 Yes ❑ No ❑ NA
ZYes 1:1 No 1:1 NA
ZYes 1:1 No 1:1 NA
Z Yes ❑ No ❑ NA
Was sensor properly replaced and
Z Yes ❑ No ❑ NA
ZYes, ❑ No ❑ NA
ZYes ❑ No ❑ NA
Z Yes ❑ No ❑ NA
verified functional after testing?
I
-Comments — (include information on repairs made prior to testing, and recommended follow -up for failed tests)
Repairs made pursuant to Bakersfield Fire Permit 15-10000205 — Inspector Kris Karns present during inspection
1 If the entire depth of the sump is not tested, specify how much was tested. If the answer to any of the questions indicated with an
asterisk (*) is "NO" or "NA", the entire sump must be tested. (See SWRCB LG-160)