Loading...
HomeMy WebLinkAboutSPECIAL INSPECTON REPORT 2-25-2013To: Sermons SPEC�INSPECTION REPORT Site. Floaft Liquors Address: 2023 Baker Street Bakersfield* CA 93305 Date: February 25, 2013 The following resutts for the above location represent the conclusions of the Special lnspaction, which are to be presented to the regulatory agency. Tank No. 3 Capacity 12,000 gallons Dimensions 8' x 33, Product Fuel CCR Tiflis 23 -2863 (b) Tank has Won cleaned so that no residue remains on the tank walls (c) (A) Determine that tank Etas been vacuum tested at a vacuum of 5.3 inches of Hg for not less than one minute. (B) Witness ultrasound test - averages of 76% or greater of original thickness. Misuaily•checked the internal lining for discontinuity, compression, tension cracking and corrosion. Test fvr thickness and hardness of the lining in accordance with nationally recognized industry Modes. Test the Uning using an electrical resistance Holiday Detwkw in accordance with nationally recognized industry codes, Holidays located, repaired and re- tested (d) Tank is suitable for continued use for a minimum of five (5) years (e) Tank is suitable for continued use for a minimum of five (5) years OtL if it is relined, or other Improvements are made. tfj The tank lining is no longer suitable far continued use and shall be closed in accordance with Article 7. Coating inspector Thomas M. Allen, Ill Professional Engineer Robert Paul P.E. Address 2243 Aspen Mirror Way Suite 2014 Laughlin, NV 88029 % Signature: Registered ProtlewWrial Engineer No. Corrosion 111 Expiration pate: 3/31/2014 P,_ASS F.IL x x x X x x x STAMP To: Scions SI!ECIAL INSPECTION REPO . Site: Fiesta Uquom Address: 2023 walker Street Bakersfield, CA 93305 Date: February 25, 2013 The following results for the above location represent the conclusions of the Special Inspection, which are ba be presented to the regulatory agency - Tank No. 2 capacity 12,000 gallons Dimensions W x 33' Product Fuel CCR Tale 23 -2883 (b) Tank has been cleaned so that no residue remains on the tank walls (c) (A) Determine that tank has been vacuum, tested at a vacuum of 5.3 inches of Hg for not Less than one minute. (B) Witness ultrasound test - average of 75°x6 or greater of original thickness. Visually checked the internal lining fear discontinuity, compression, tension cracking and corrosion. Test for thickness and hardness of the lining in accordance with nationally recognized industry codes. Test the lining using an electrical resistance Holiday Deftctor in accordance with na*mWly recognized Industry codes, Holidays Imted, repaired and re- tested (d) Tank is suitable fir continued use for a minimum of five (5) years (e) Tank is suitable for continued use for a minimum of five (5) years Ci1VLY if it is refined, or other improvements are made. (f) The tank lining is no longer suitable for continued use and shall be closed in aoaordanc* with Article 7. Coating Inspector Thomas M. Allen, III professional Enginew Robert Paul P.E. Address 2243 Aspen Mirror Way Suite 204 Laughlin, NV 89029 Signature: Registered professional Engineer No. Corrosion 111 Expiration Date: 3131/2014 EM FAIL X x X x x x X UAW To.- Sessions SPECIAL INSPECT ON ..,.P..T Site: iF "te Uquors Address: 2023 Baker Street Bakersfield, CA 93305 Date: February 25, 2013 The following results for the above location represent the conclusions of the Special Inspection, which are to be presented to the regulatory agency, Tank No. 1 Capacity 12,000 gallons Dimensions 8' x 33' Product Fuel CCR Title 23-M3 (b) Tank has been cleaned so that no residue remains on the tank wails (c) (A) determine that tank has been vacuum tested at a VOW= of 5.3 inches of Hg far not less than one minute. (8) 'Witness ultrasound test -average of 75% or greater of original thickness. Visually checked the internal lining for discontinuity, compression, tension cracking and corrosion. Test for thickness and hardness of the lining in accordance with nationally recognized industry codes. Test the lining using an electrical resistance Holiday Detector in accordance with nationally recognized industry codes, Holidays, located, repaired and re- tested (d) Tank is suitable for continued use for a minimum of five (5) years (e) Tank is suitable for continued use for a minimum of five (5) years ONLY if it is relined, or other improvements are made. (f) The tank Ding is no longer suitable for continued use and shall be closed in accordance with Article 7. Coating Inspector Thomas M. Allen, III Professional Engineer Robert Paul P.E. Address 2243 Aspen Mirror Way Suite 204 Laughlin, NV 89029 Signature: Registered Protessbrtal Engineer No. C,orrosian 111 Expiration Elate: 3/31/2014 PASS fft X X X X X X R STAMP 1— —Z..6~4%en^ /C— A�i—Afnrtmn fin 911ifa tl')-nitAl lKnUMAftifOrl Form Approved. OMB No. 2050-0039 Fwu F-44— It— Vw.... UNIFORM HAMIRMUS 1 1. Generator ID Number 2. Page I of 1 3. Emergency Response Phone 4. Manifest Tracking Number 10109 9447 JJK WASTE MANIFEST 03 66i-55-5-0626 S. Generator's Name and Mailing Address Generator's site Address (if different Than mailing address) 2023 15aker I'St 2012.3 bak—e+ Stxeet CA 93307 C'AL 93-407 Generators Phone: ig-A It '''s . -4 fi 6. Transporter 1 Company Name U.S. EPA ID Number CSZ. '(0-ro..�e-z; Se.-&7;Lc-:e5 XhIL—DBA: CALCOG268462 7. Transporter 2 Company Name U.S. EPA ID Number Nregg A ress U.S. EPA ID Number r"3nmPtoz,,t' CA 90222 FadritYs Phone. 0 — 5 3'` ' — 7": `a C16iT080013352 ga. 9b. U.S. DOT Description (including Proper Shipping Name, Hazard Class, ID Number, 10. Cont ainers 11. Total 12. Unit 13. Waste Codes No. ' Type HM and PaddrigGroup (dany)) Quantity WtjVbI- pOIS 2! 3, PG11 (DBOVD018) Du G 0 4o Z 2. Uj 3. 4. jV dkdditons L, ' n $ ,M.Nester MR-; 7—' Ci 0 MEA SAFETT PRECAUT-76ONS 5. GENERATORWOFFEROWSCERTIFICATION: I hereby dedwe that the contents of this consignment are My and accurately described above by the proper shipping name, and are classified, packaged, marked and labeledloacarded, and are in all respects in proper condition for transport according to applicable international and national governmental regulations. If export shipment and I am the Primary Exporter, I certify that the contents of this consignment conform to the terms of the attached EPAAckriowledgment of Consent 0")> �e I certify that the waste mirfirnization statement Identified in 40 CFR 262.27(a) (If I am a large quantity generator) or (b) Of I am a small quantity ge • 166 1 rOfferpes P' MWQyped Name signature Month Day year watoes, C6L 1 -1 ... j 16. Intemational SNpments ❑ import to U.S. 0 &Ood from U.S. 'PM c'feW/-e Z— 1 Transporter signature (for exports only): W KIWI 17. Trartsporter Acknowiedgment of Receipt of VoWials Transporter I Printeciffyped N Signatsu MO* Day Year CL cc* Z — ' Transporter 2 Printed(Typed Name Signature Month Day Year GC Discrepancy 18a. Discrepancy Indication Spam F-1 Quantity Floe F-1 Residue F-1 Partial R*aw ❑ Full Rejection r Reference Number: >- 18b. Afternate Facility (or Generator} U.S. EPA ID Number w- Witys Phone: UO -1 & Signature of Atimite Faaly or Generator) Month My Year 19. 5= waste Report Management Method Codes (i.e., codes for hazardous waste treatment, disposal, and recycling system) 1. 4. n. Designated Facility Owner or Operator: Certification of receipt of hazardous materials covered by the manifest except as noted in Item 18a PrintedlTyped Name signature Month Day Year EPA Form 8700-22 (Rev. 3-05) Mv'Ous eumOrr- are ODSOele- DESIGNATED FACILITY TO OESTINATION STATE (IF HF-UU1KftV)