HomeMy WebLinkAboutSPECIAL INSPECTION REPORT 8-8-2008Sfte: Wholesale Fuels �2A 5 IWO The following results for the above location represent the conclusions of the Special Inspection, which are to be presented to the regulatory agency, Tank No. 2 Capacity 10,000 gallons Dimensions ' 7'1 T' x 2i Product Fuel CCR Title 23-2663 PASS FAIL (b) Tank has been cleaned so that no residue remains on the tank walls X (c) (A) Determine that tank has been vacuum tested at a X vacuum of 5.3 inches of Hg for not less than one minute. (8) Witness ultrasound test -average of 75% or X greater of original thickness. Visually checked the internal lining for discontinuity, X compression, tension cracking and corrosion. Test for thickness and hardness of the lining in X accordance with nationally recognized industry codes. Test the lining using an electrical resistance Holiday X Detector in accordance with nationally recognized industry codes, Holidays located, repaired and re-tested (d) Tank is suitable for continued use for a minimum of five (5) years X (e) Tank is suitable for continued use for a minimum of five (5) years GAIL Y if it is relined, or other improvements are made. (f) The tank lining is no longer suitable for continued use and shall be closed in accordance with Article 7. This Special Inspection covers only the corrosion control aspects of the tank internals. The corrosion control aspects of the tank externals would be the subject of a separate report. Coating Inspector Dan Lawhorn Professional Engineer Robert Paul P. E. Address 2243 Aspen Mirror Way Suite 204 Laughlin, NV 89029 Signature: Registered Professional Engineer No. Corrosion 111 Expiration Date: 3/31/2010 T (40.111 nr 1111117 Site.- Wholesale Fuels 0* The follom(ing results for the above location represent the conclusions of the Special Inspection, which are to be presented to the regulatory agency. Tank No. 3 Capacity 20,000 gallons Dimensions 10'4' x 33' Product Fuel CS R Title 23-2663 PASS FAIL (b) Tank has been cleaned so that no residue remains on the tank walls x (c) (A) Determine that tank has been vacuum tested at a x vacuum of 5.3 inches of Hg for not less than one minute. (6) Witness ultrasound test -average of 75% or x greater of original thickness. Visually checked the internal lining for discontinuity, x compression, tension cracking and corrosion. Test for thickness and hardness of the lining in x accordance with nationally recognized industry codes. Test the lining using an electrical resistance Holiday x Detector in accordance with nationally recognized industry codes, Holidays located, repaired and re-tested (d) Tank is suitable for continued use for a minimum of five (5) years x (e) Tank is suitable for continued use fora minimum of five (5) years ONLY if it is relined, or other improvements afe made. (f) The tank lining is no longer suitable for continued use and shall be closed in accordance with Article 7. This Special Inspection covers only the corrosion control aspects of the tank internals. The corrosion control aspects of the tank externals would be the subject of a separate report. Coating Inspector Dan Lawhorn Professional Engineer Robert Paul P.E. STAMP Address 2243 Aspen Mirror Way Suite 204 Laughlin, NV 89029 Signature: Registered Professional Engineer No. Corrosion I11 tf ESS11 Expiration Date: 313112010 RT p CD No. III OS' _e OF NV c Site: Wholesale Fuels Address: 2200 E. Brundage Ln, Bakersfield, CA The following results for the above location represent the conclusions of the Special Inspection, Which are to be presented to the regulatory agency. Tank No. 2 Capacity 10,000 gallons Dimensions 111"' x Zi Product Fuel CCR Title 23-2663 PASS FAIL (b) Tank has been cleaned so that no residue remains on the tank wails X (c) (A) Determine that tank has been vacuum tested at a X vacuum of 5.3 inches of Hg for not less than one minute. (13) Witness ultrasound test -average of 75% or X greater of original thickness. Visually checked the internal lining for discontinuity, X compression, tension cracking and corrosion. Test for thickness and hardness of the lining in X accordance with nationally recognized industry codes. Test the lining using an electrical resistance Holiday X Detector in accordance with nationally recognized industry codes, Holidays located, repaired and re-tested (d) Tank is suitable for continued use for a minimum of five (5) years X (e) Tank is suitable for continued use for a minimum of five (5) years ONLY if it is relined, or other improvements are made. (f) The tank lining is no longer suitable for continued use and shall be closed in accordance with Article 7. This Special Inspection covers only the corrosion control aspects of the tank internals. The corrosion control aspects of the tank externals would be the subject of a separate report. Coating Inspector Dan Lawhorn Professional Engineer Robert Paul P.E. Address 2243 Aspen Mirror Way Suite 204 Laughlin, NV 89029 Signature. Registered Professional Engineer No. Corrosion I11 Expiration Date: 3/3112010 ?,T CjAjJ 0r= G N Site: Wholesale Fuels • 111111111 'T 1112MM ITINO The following results for the above location represent the conclusions of the Special Inspection, which are to be presented to the regulatory agency. Tank No. 3 Capacity 20,000 gallons Dimensions 10'4' x 3& Product Fuel CCR Title 23-2663 PASS FAIL (b) Tank has been cleaned so that no residue remains on the tank walls X (c) (A) Determine that tank has been vacuum tested at a X vacuum of 5.3 inches of Hg for not less than one minute. (B) Witness ultrasound test -,average of 750 or X greater of original thickness. Visually checked the internal lining for discontinuity, X compression, tension cracking and corrosion. Test for thickness and hardness of the lining in X accordance with nationally recognized industry codes, Test the lining using an electrical resistance Holiday X Detector in accordance with nationally recognized industry codes, Holidays located, repaired and re-tested (d) Tank is suitable for continued use for a minimum of five (5) years X (e) Tank is suitable for continued use for a minimum of five (5) years ONLY if it is relined, or other improvements are made. (f) The tank lining is no longer suitable for continued use and shall be closed in accordance with Article 7. This Special Inspection covers only the corrosion control aspects of the tank internals. The corrosion control aspects of the tank externals would be the subject of a separate report. Coating Inspector Dan Lawhorn Professional Engineer Robert Paul P.E. STAMP Address 2243 Aspen Mirror Way Suite 204 Laughlin, NV 89029 Signature: Registered Professional Engineer No. Corrosion 171 ISS/ Expiration Date: 3/31/2010 No. ill in Site: Wholesale Fuels Date. August 8, 2008 The following results for the above location represent the conclusions of the Special Inspection, which are to be presented to the regulatory agency. 1 4 I ank No. Capacity 20,000 gallons Dimensions 10'4" x 33' Product Fuel CCR Title 23-2663 PASS FAIL (b) Tank has been cleaned so that no residue remains on the tank walls X (c) (A) Determine that tank has been vacuum tested at a X vacuum of 5.3 inches of Hg for not less than one minute. (B) Witness ultrasound test -average of 75% or X greater of original thickness. Visually checked the internal lining for discontinuity, X compression, tension cracking and corrosion. Test for thickness and hardness of the lining in X accordance with nationally recognized industry codes. Test the lining using an electrical resistance Holiday X Detector in accordance with nationally recognized industry codes, Holidays located, repaired and re-tested (d) Tank is suitable for continued use for a minimum of five (5) years X (e) Tank is suitable for continued use for a minimum of five (5) years ONLY if it is relined, or other improvements are made. (f) The tank lining is no longer suitable for continued use and shall be closed in accordance with Article 7. This Special Inspection covers only the corrosion control aspects of the tank internals. The corrosion control aspects of the. tank externals would be the subject of a separate report. Coating Inspector Dan Lawhorn Professional Engineer Robert Paul P.E. STAMP Address 2243 Aspen Mirror Way Suite 204 Laughlin, NV 89029 Signature. Registered Professional Engineer No. Corrosion 111 Date". 3/3112010 O�Essl P1.1 Expiration �W CID f Of SPECIAL INSPECTION REPORT Site: Wholesale Fuels Date, August 8, 2008 Address: 2200 E. Brundage'Ln. Bakersfield, CA The following results for the above location represent the conclusions of the Special Inspection, which are to be presented to the regulatory agency. Tank No. 5 Capacity 20,000 gallons Dimensions I OW x 33' Product Fuel C R Title 23-2663 PASS FAIL (b) Tank has been cleaned so that no residue remains on the tank walls X (c) (A) Determine that tank has been vacuum tested at a X vacuum of 5.3 inches of Hg for not less than one minute. (13) Witness ultrasound test -average of 75% or X greater of original thickness. Visually checked the internal lining for discontinuity, X compression, tension cracking and corrosion. Test for thickness and hardness of the lining in X accordance with nationally recognized industry codes. Test the lining using an efectrical resistance Holiday X Detector in accordance with nationally recognized industry codes, Holidays located, repaired and re-tested (d) Tank is suitable for continued use for a minimum of five (5) years X (e) Tank is suitable for continued use for a minimum of five (5) years ONLY if it is refined, or-other improvements af-e made. J) The tank lining is no longer suitable for continued use and shall be closed in accordance with Article 7. This Special Inspection covers only the corrosion control aspects of the tank internals. The corrosion control aspects of the tank externals would be the subject of a separate report. Coating Inspector Dan Lawhorn Professional Engineer Robert Paul P. E. Address 2243 As en Mirror Way Suite 204 Laughlin, NV 89029 Signature. Registered Professional Engineer No. Corrosion 11 I Expiration Date: 3/31/2010 T 0 6�1 W& Site. Wholesale Fuels Address: 2200 E. Brundage Ln. Bakersfield, CA I The following results for the above location represent the conclusions of the Special Inspection, which are to be presented to the regulatory agency. Tank No. 6 Capacity 20,000 gallons Dimensions 10'4"' x 33' Product Fuel CCR Title 23-2663 PASS FAIL (b) Tank has been cleaned so that no residue remains on the tank walls X (c) (A) Determine that tank has been vacuum tested at a X vacuum of 5.3 inches of Hg for not less than one minute. (13) Witness ultrasound test -average of 75% or X greater of original thickness. Visually checked the internal lining f ©r discontinuity, X compression, tension cracking and corrosion. Test for thickness and hardness of the lining in X accordance with nationally recognized industry codes. Test the lining using an electrical resistance Holiday X Detector in accordance m(ith nationally recognized industry codes, Holidays located, repaired and re-tested (d) Tank is suitable for continued use for a minimum of five (5) years X (e) Tank is suitable for continued use for a minimum of five (5) years -ONLY if it is relined, or other impfovements are made. (f) The tank lining is no longer suitable for continued use and shall be closed in accordance with Article 7. This Special Inspection covers only the corrosion control aspects of the tank internals. The corrosion control aspects of the tank externals would be the subject of a separate report. Coating Inspector Dan Lawhorn Professional Engineer Robert Paul P.E. STAMP Address 2243 Aspen Mirror Way Suite 204 Laughlin, NV 89029 Signature: .44 Registered Professional Engineer No. Corrosion I I I Expiration Date: 313112010