HomeMy WebLinkAboutINSPECTION REPORT 20131-j6c-V -/r
-/%e7 /�Uo/av/ct�
UNIFIED PROGRAM INSPECTION CHECKLIST
Underground Storage Tank Program
Facility Name:
Fairfax e i Mart.
[
Address:
6700 Auburn St. Bakersfield, CA. 93306
I
Contact:
vo Cola is
Phone:
1( 661) 7 -773
Tank ID
Size
Contents
Construction
Tank Monitoring:
DW: Continuous Interstitial Monitoring
❑ Dry ❑ Brine /H drostatic Vacuum /Pressure.
SW: SIR and Line Test every 2 years.
SW: ATG 0.1 annual.
SW: ATG 0.2 monthly.
SW: Continuous In -Tank Leak Detection (CITLD).
SW: Tank Gauging.
SW: Vadose /GW Monitoring.
Other Description:
Piping Monitoring:
DW Suction: Continuous Interstitial at UDC and Tank Sump.
DW Pressurized: Interstitial at UDC and Turbine Sump and 3.0 gph LLD,
❑ Annual Line Test or uto- shutdown and Failsafe.
DW VPH Monitoring: Includes lines, sumps, fill pipe, vapor lines, etc.
SW Conventional Suction: Triennial 0.1 gph line test., and daily
monitoring.
SW Pressurized: Line 0.1 gph annual or 0.2 gph monthly line test and
LLD with Auto - Shutdown.
SW or DW Safe Suction.
SW: Vadose Zone or GW Monitoring.
DW or SW: Gravity Flow Pipe.
Other Description:
BAKERSFIELD FIRE DEPARTMENT
Prevention Services Division
2101 H Street
Bakersfield, CA 93301
Phone: 661 -326 -3979
Fax: 661 -852 -2171
References to the Health and Safety Code, the California Code of Regulations and the Code of Federal Regulations throughout this Appendix are
intended to be useful but are not necessarily exhaustive of all legal references that might apply or be relevant to a specific compliance determination.
Laws and regulations are subject to change, so the references contained herein may not be up to date. It is the responsibility of the owner and operator
to know and comply with all applicable legal requirements.
UNDERGROUND STORAGE TANK COMPLIANCE INSPECTION REPORT
Facility Name: Date:
Bakersfield Fire Department — Prevention Services Division, 2101 H Street, Bakersfield, CA 93301 (661) 326 -3979
M
PA
If in compliance, check the box. Check NA if not applicable.
If a violation, determine if Minor, Class 11, or Class 1, or To
Violations
Be Determined (TBD) if uncertain and will be determined
later.
... .Y�':, .....
-::x
,...., ... x• t -' "P8 '.. ,.. ...... ,;... .F.. .. ...
�., .k,. ': Y'+.a ,z'r,
.. . i+-
�.. �, , a .. M : S` � #. ,v, . `yw _, 4.. ,..s. x . >•..w i .. £
.v...q. �y
.. m
^ T1,
�I�yj(';� �_... K -
µ�r�'
�
.,.,
f.t !
_ r ,.
,�"�.. `f
µ• :x r !. A., 8 r
nL
. ,
Y�,
F .. . >. sr ..
,. .y, ,
..:. .,.. , ..\ T1 .G.v_.:., Y... .; a• ..x.,.. ..... r..
r �
� . , � .. A" :5�3 to ..., ny '�. iC ?✓. N' � ;. r .: ,.,. ... .. t... .. , .;, r. ...
,..n.
:. .. :, n. a. S£`, .. �• .. �.. # . fir"* .. , L, t'� .r .: .w .. .�_. ,_ .., ..< ., ..
^i pry .. ,, ..... i<N n,.. . Y, ;...2. F.. L-k , ... :y;;: ♦ ,...., ,,..,. ._:._,.... ..T
.'F.
..r,;
,.. . ....
R
K .,.
,.
�.;W
r ,..
..:1.,
nr,
,.r, ..
..s.
w � ,. 1
.E'. .H �'Y .W.
,... ,._x ".xt'" . ,3 , F ,c.
3...,`F'.
:.. ,n r
z�
�s �:..,
'' .,r..M
.> a�
.r. v..... r.. s,.' ...� ..t .. ,. 2 ... ,... 'r� k. .. ... ..... . .. .. .,. ,......
� S.. J .,... .. .. s. ,_, n e'' N f'.. ..,. ,..: ..e r , x:: ., v..
yr!-.< S .,,.. 4 .. r .. - ..t. s �,-, ..... : ,. ?�k'4 .. a•...� "v's... :} f ..
..t, �..,. } ,a,_, �:. it a. ,2.v.,.v yam,,., :"r,3,.i.""[�,. ,�. "°,�'"Me#�,,.awL',✓3': ;C.,:. ., .�,..' f ,Y'... �`n r.
..�t;..
:,,. ..;..
..'
,,
..x ..fi
,..
:z � ::l t
...,,
..,:... - ,v.:.,
�.,.�
�. s .,
rk - *. -^t
,s, 'x...{t i$
._.R.,
�
,tr�4
�' ,5`•.:'
:.,f,±x' $ t.::.. 3k; t ;�,;'.4,i: ..:rR...
is.. .'f +::. X .n t �aay�.� >r�,,�;,
.. ,.. ,tom
'f. ,. � ., .,,, , , �... `� ,. v Mont >, •- u .: ,r. ;: l.:
� .. .... ,. ... :.t. ••��� - ,,, . ,. n,..:.r �...
^'t
K .w =:
s `, �
a ,., t
7x :,�
��,�' r
� „a s .+ ,.,- 3 _ -a:
.. , k..,
.�Yf'J:a`4''4nf3i?`,
..r✓' n'£ ..,. b,_ .x,. .x_. L.. a , .,.:a. -:.t. a �:s. f. .,.: ^t �., ., vi...., Y _'t.r:, .. , f :. ... ..
a. sLX. itrw', xa,..$>:,. t�y3=` Y3��-» rk,-,.,^, s, ��2it�a ;c...._'�.,:µ "5;i+4JY��:. .m.e.. ....... �t.:::_.. cx<_..+..: w` ».c,.,o..,.✓...<_..:..- ,x.... r3w'a::....,,.,.. .ir_ -�v.a r..La., , -... }_
File Review
♦ .......
_
_
..",
�3: rC.
..?2.
&.<.s..,v.:..i Y..
♦.,.{__,.:t...�
f`:,.a .t� 1
L.SSti«.y..Y..E �+. Se.., r4, 3.,. .s._Jm..n „>a..��Rh.svw,.t.r''.: 4. „3sk...u.u... -s
�(
❑ 1
UST Permit to Operate is current. HSC 25284(a), 25299(x)(1) 25299 (b)(1)
❑
❑ 2
Transfer of permit and /or change of information provided within
,
30 days of ownership /information changes. HSC 25284(b) (c); T23
CCR 2712(d)
❑ 3
UST form information current/correct for facility, including BOE
❑
number. HSC 25286(x)
IS14
Fees are paid up -to -date. HSC 25285(c), 25287
❑
X5
Monitoring Plan approved for current owner with appropriate
❑
content and level of detail. T23 CCR 2632(d), 2634 (d), 2641(h)
❑ 6
Current Emergency Response Plan submitted with appropriate
❑
AJ 5v ml * C
content and level of detail. T23 CCR 2632(d), 2634 (d), 2641(h)
6XVA?•
❑ 7
Plot Plan /Site Map submitted with appropriate content and
El
�”' scx��
�
~�
level of detail. T23 CCR 2632(d), 2634(d), 2641(h), 2711(a)(8)
�
❑ 8
Owner/Operator agreement submitted, if required. HSC 25284(a)(3)
❑
❑ 9
Certification of Compliance and Designated Operator
!
❑
1,.r 7'�:' s i-1-
Certification submitted by current tank owner. T23 CCR 2715
X
I
10
Certificate of Financial Responsibility submitted and is current
for the permit period. HSC 25292.2, 25299.30- 25299.34; T23 CCR 2711; 2808.1;
El
2809 - 2809.2
$611
Monitoring system certification (most recent) conducted within
allowable timeframe (sensors and console). Results submitted
❑
and show all required components with passing results. Hsc
25284.1(a (4)(c); T23 CCR 2638
12
Spill- bucket test results (most recent) conducted within
allowable time frame. Results submitted and indicate a passing
❑
test. HSC 25284.2
913
Leak Detector testing conducted within allowable time frame.
The most recent annual certification submitted and shows
RD
RD
RD
RD
❑
passing results. 40 CFR 280.40(a)(2), 280.43(8)(1) &(2), 280.44(a); HSC 25292(e);
T23 CCR 2638, 2641
%214
Secondary containment testing conducted within allowable
time frame. Most recent testing results submitted and indicate
❑
a passing test. HSC 25284.1(a)(4)(8); T23 CCR 2637(a)
015
Pipe and /or tank integrity testing conducted within allowable
time frame. Most recent testing results submitted and indicate
passing results. 40 CFR 280.33, 280.40, 280.41, 280.44; T23 CCR 2636(0,
2643(b) 3 , (c)(3), (d ) (e
016
Repaired tanks /piping are tightness tested within 30 days of
RD
RD
RD
RD
the repair. 40 CFR 280.33, T23 CCR 2661
017
ELD test conducted within allowable time frame. Most recent
,
test results submitted and passing results achieved. T23 CCR
2644.1
018
The corrosion protection system is checked by a corrosion
specialist within six months of installation /repair and at least
every three years thereafter; results show protection to be
RP
RP
RP
RP
l`
adequate, Impressed current inspected every 60- calendar
days. 40 CFR 280.31, 280.70, T23 CCR 2635(a)(2)
019
Tank Lining recertification is current (within 10 years of lining
and every 5 years thereafter) and compliant. 40 CFR280.21(b)(1)(ii,);
RP
RP
RP
RP`
T23 CCR 2663(h)
f
Bakersfield Fire Department — Prevention Services Division, 2101 H Street, Bakersfield, CA 93301 (661) 326 -3979
M
PA
Pacility Name:
UNDERGROUND STORAGE TANK COMPLIANCE INSPECTION REPORT
Date:
Bakersfield Fire Department — Prevention Services Division, 2101 H Street, Bakersfield, CA 93301 (661) 326 -3979
On-Site Review
This Inspection is being conducted durij
monitoring certification. )(YES L7 NO
The service technician has provided IC(
manufacturers training documentation, i
tester's license or works under a CSLB
�FYES L7 NO
N20
Tank systems meet current constructior
for type of system. HSC 25288
Hazardous substance tanks have secor
CFR 280.42(b); T23 CCR 2631
W2
Electronic monitoring system has audibl
operating condition. r23 CCR 2632, 2634, 2636
3
Monitor console programmed appropria
option used. T23 CCR 2638, 2643, 2643.1
❑24
Tank systems in temporary closure meE
280.70, T23 CCR 2670 & 2671
12f25
Overfill Prevention mechanism present
according to type: ❑FIapper valve ?CAL
❑ball float. ❑ A/V alarm and Ball Float,
280.21(o); T23 CCR 2635(b)(2), 2631(d)(4)
pq46
Spill prevention device is present and fu
condition and drain mechanism operatic
280.20(c)(1)(1), 280.21(d); T23 CCR 2635(b)(1),,2665
Piping and piping penetration boots with
ciood condition. HSC 25288(a), 25292.1
N28
All sumps, spill buckets, and UDC's freE
HSC 25291(e), 25290.1, 25290.2, T23 CCR 2635(b)(1)((
$229
7—
Areas around vents appear to be free fn
releases. HSC 25288(a), 25290.1, 25290,2, 25295.5
F30
i
Release Detection methods are present
standards. See LG-1 13. 40 CFR 280.40(a)(3)
R31
All sensors are correct for the type of sy
40 CFR 280.40(a
)(2), 280.43(g)(I)&(2); HSC 25290.1 e
P2
All sensors are located in the proper po.,
280.40(a)(2), 280.43(8)(1)&(2); HSC 25290.1, 25290.2,
2632(c);2641(a)
�33
All secondary containment, including U1
with a continuous monitoring system the
A/V alarm or stops the flow of product a,
detects a leak. T23 CCR 2636 (0(1)
Tank -Monitoring
❑34
❑ Interstitial monitoring conducted prop
280,43(g)(I)&(2); T23 CCR 2632 (c)(2); 2634(d)(1)
5
WVPH monitoring conducted properly.
...... . ..
O SIR
❑36
SIR and Biennial 0.1 gph tank test perfc
280.41, 280.43; T23 CCR 2643, 2646.1
❑37
Non-passing SIR monitoring report resu
investigated properly. 40 CFR 280.4 1 (a), 280.4
Bakersfield Fire Department — Prevention Services Division, 2101 H Street, Bakersfield, CA 93301 (661) 326 -3979
UNDERGROUND STORAGE TANK COMPLIANCE INSPECTION REPORT
Facility Name: Date:
Bakersfield Fire Department — Prevention Services Division, 2101 H Street, Bakersfield, CA 93301 (661) 326 -3979
O Automatic Tank Gauging (ATG) / Continuous In -Tank Leak
Detection CITLD
038
ATG or CITLD 0.2 gph monthly test performed properly. 40 CFR
RD
RD
RD
RD
280.43; T23 CCR 2643(b)(1), 2643 b 5
;W39
ATG generates a hard copy printout of all data reported
including time and date, tank I.D., fuel depth, water depth,
temperature, liquid volume and duration of test. If installed after
❑
1/1/95 printout includes calculated leak rate and leak threshold.
T23 CCR 2643 b 1
O Manual Tank Gauging (SW tanks </ =1000 gal. ONLY)
040
Weekly manual tank gauging performed properly. 40 CFR 280.43;
RD
RD
RD
RD
T23 CCR 2645
❑41
Tank Integrity test performed, if necessary. 40 CFR 280.43; T23 CCR
RD
RD
RD
RD
2645
O Vadose Zone and /or Groundwater Monitoring
042
Monitoring system is installed and monitored properly. 40 CFR
RD
RD
RD
RD
280.43, T23 CCR 2647 -48
*Tank Exemption
043
Tanks /piping meet tank exemption criteria, and weekly visual
monitoring records are kept up-do-date. HsC 25283.5
Pipe Monitoring
J
..Y
O Continuous Monitoring System
4
DW piping (gravity, suction, pressure) in the turbine sump has
continuous monitoring system that activates an audible and
RD
RD
RD
RD
❑
visual alarm or restricts or stops flow at dispenser. T23 CCR
2636 (1
)4-15
DW piping in the UDC is continuously monitored and method
either shuts down the flow of product to the dispenser or
❑
activates an AN alarm. T23 CCR 26360(1)
O Line Integrity Testing for Pressurized Piping
❑46
An annual 0.1 gph line integrity test is performed properly.
(Either third party or by Enhanced Line Leak Detection) T23 CCR
RD
RD
RD
RD
2636 (0(4)
047
In lieu of the annual tightness test for DW pressurized piping,
the monitoring system for all product piping outside the
dispenser is fail -safe and shuts down the pump when a leak is
RD
RD
RD
RD
detected and the monitoring system shuts down the pump or
flow restriction occurs when a leak is detected in the UDC. T23
CCR 26360(5)
O Line Leak Detectors (LLD)
8
LLD's installed, annually tested, and operational on DW
pressurized piping that detects a 3.0 -gph leak, and restricts or
RD
RD
RD
RD
❑
shuts off flow of product. T23 CCR 26360(2)
O DW Emergency Generator Tank
049
LLD activates AN alarm and monitoring system is checked
RD
RD
RD
RD
daily. T23 CCR 26360(2)
❑50
In lieu of LLD, continuous monitoring system of DW emergency
generator tank activates AN alarm, system is checked daily,
and logs are kept. T23 CCR 2636 0(6)
1.
NIntegrity
1 I Iv
O Line Testing
051
SW pressurized piping: annual 0.1 gph line integrity test or a
monthly 0.2 gph line integrity test is performed properly. 40 CFR
RD
RD
RD
RD
280.41, 280.44; T23 CCR 2643(c)(2),(3)
052
SW conventional suction system: 0.1 gph line integrity test is
RD
RD
RD
RD
performed every three years. 40 CFR 280.40, 280.41; T23 CCR 2643(d)
Bakersfield Fire Department — Prevention Services Division, 2101 H Street, Bakersfield, CA 93301 (661) 326 -3979
UNDERGROUND STORAGE TANK COMPLIANCE INSPECTION REPORT
Facility Name: Date:
053
SW conventional suction system: inspections conducted for
presence of air in the pipeline. Daily monitoring records are
kept. T23 CCR 2643(d)
❑54
SW gravity flow piping: biennial 0.1 gph integrity test or overfill
tank integrity test is conducted within allowable time frames.
T23 CCR 2643(e
O Safe Suction (SS) System
055
Piping meets the SS requirements. 40 CFR 280.41; T23 CCR 2636(a)(3)
RD
RD
RD
RD
A -D
O LLD for Pressurized Piping
❑56
LLD's installed, annually tested and operational on SW
pressurized piping. Pump shuts down when a leak occurs and
RD
RD
RD
RD
when the LLD fails or is disconnected. T23 CCR 2666
057
LLD's installed, annually tested, and operational on SW
emergency generator systems; LLD is connected to an AN
alarm. 40 CFR 280.40(a)(2), 280.43(8)(1), (2), 280.44(a); T23 CCR 2666
Corrosion Protection
058
Metal Tanks and piping components have corrosion protection,
RP
RP
RP
RP
or are isolated from the backfill. 40 CFR 280.20, 280.21
059
Corrosion protection equipment turned on, functioning properly
and provides continuous protection. 40 CFR 280.31(a),(b)(1); T23 CCR
RP
RP
RP
RP
2635
060
Cathodic protection system is tested within 6 months of
installation and then every 3 years. 40 CFR 280.31(x) & (b)(1); T23 CCR
RP
RP
RP
RP
Vr
2635 a 2
061
Impressed current systems checked every 60- calendar days
RP
RP
RP
RP
and records are up-to-date. 40 CFR 280.31(c); T23 CCR 2635(x)(2)
On -site Paperwork
062
Permit and conditions available on -site. Facility is operated
❑
,�� e 0A) :5.
according t0 permit and conditions. HsC 25293; 25299; T23 CCR 2712(1)
X63
Monitoring and response plans are on -site and are the
❑
approved version. T23 CCR 2712(i); 2632;2634; 2641
064
Site plan depicts current site conditions and has all required
❑
elements. T23 CCR 2632(d)
IX
65
All release detection records for monitoring method are
available, up -to -date, and appropriate for leak detection
RD
RD
RD
RD
❑
method. 40 CFR 280.41, 280.45
❑66
All monitoring /testing records /documents are available for the
required timeframe. (3 years, 6 1/2 years, five years, life of tank) T23 CCR
❑
FoEl A1rr7`6,A� ,
2712
S"
7
Equipment maintenance records/logs available. T23 CCR 2712(b)
❑
8
Alarm logs /tapes available and appropriate follow -up actions
❑
occurred. T23 CCR 2712(b); 2632; 2634
` 09
Visual observation logs available, up -to -date, and appropriate
❑
follow-up actions t0 problems occurred. T23 CCR 2712(b); 2642
'0
Designated UST Operator monthly reports available and
❑
com lete. T23 CCR 2715
071
Employee training records available and training appropriate
❑�°'
-� '">�
and u -to -date. T23 CCR 2715
A
mcr
72
Suspected or actual unauthorized releases are recorded
and /or reported within allowed timeframes, including non-
RD
RD
RD
RD
❑
passing test results. Leak and Spill Logs available. 40 CFR 280.50,
T23 CCR, 2650, 2652
X73
Financial Responsibility Certificate and mechanisms (CFO
Letter, etc.) on -site and up -to -date. HsC 25292.2, 25299.30- 25299.34; T23
❑�,%���3
CCR 2711; T23 2808.1; 2809 - 2809.2
Bakersfield Fire Department — Prevention Services Division, 2101 H Street, Bakersfield, CA 93301 (661) 326 -3979
UNDERGROUND STORAGE TANK COMPLIANCE INSPECTION REPORT
Facilitv Name: Date:
On-Site Observation of Periodic Testing
❑74 Spill-bucket testing conducted appropriately and a passing test
achieved.
5 1-15 Secondary Containment testing conducted appropriately and a F1
r)assina test achieved.
SOC AND RED TAG
Item
# � Inspection Comments:
Bakersfield Fire Department — Prevention Services Division, 2101 H Street, Bakersfield, CA 93301 (661) 326 -3979
a. This facility is in compliance with RE
violations in boxes marked RD, but on
b. This facility is in compliance with RE
violations in boxes marked RP, but on
c. This facility is in compliance with B(
Prevention (RP) requirements. (No vii
d. This facility is NOT in compliance w
Prevention (RP) requirements. (One
and RP.)
.......................
P "s _401,M
Am
A Red Tag was issued to this facility b
Red Tag #
Reason for Red Tag (Choose one):
1. Violation that causes or threatens t(
2. Violation that impairs the ability of a
3. Chronic violation or committed by a
Item
# � Inspection Comments:
Bakersfield Fire Department — Prevention Services Division, 2101 H Street, Bakersfield, CA 93301 (661) 326 -3979