SPECIAL INSPECTION REPORT
Site_ Mesa Marin Chevron Food Mart Date: March 7, 2012
Address: 11101 Highway 178 Bakersfield, CA
The following results for the above location represent the conclusions of the Special Inspection, which are
to be presented to the regulatory agency.
Tank No_ 1 -North
Capacity 10,000 gallons
Dimensions 7'111" x 27'
Product Fuel
GCR Title 23 -2663
PASS FAIL
(b) Tank has been cleaned so that no residue remains on the tank walls
X
(c) (A) Determine that tank has been vacuum tested at a
X
vacuum of 5.3 inches of Hg for not less than one minute.
(B) Witness ultrasound test - average of 75% or
X
greater of original thickness.
Visually checked the internal lining for discontinuity,
X
compression, tension cracking and corrosion.
Test for thickness and hardness of the lining in
X
accordance with nationally recognized industry codes.
Test the lining using an electrical resistance Holiday
X
Detector in accordance with nationally recognized
industry codes, Holidays located, repaired and re- tested
(d) Tank is suitable for continued use for a minimum of five (5) years
X
(e) Tank is suitable for continued use for a minimum of five (5) years
ONLY if it is relined, or other improvements are made.
(f) The tank lining is no longer suitable for continued use and shall be
closed in accordance with Article 7.
Coating Inspector Thomas M. Allen, III
Professional Engineer Robert Paul P.E. STAMP
Address 2243 Aspen Mirror Way Suite 204 Laughlin, NV 89029
Signature:
Registered Professional Engineer No. Corrosion 111
Expiration Date: 3/31/2014
a.:
L
0 ° '�
To: Sessions
SPECIAL INSPECTION REPORT
Site: Mesa Marin Chevron Food Mart Date: March 7,2012
Address* 11101 Highway 178 Bakersfield, CA
The following results for the above location represent the conclusions of the Special Inspection which are
to be presented to the regulatory agency.
Tank No. 2-Northwest
Capacity 10,000 gallons
Dimensions 7'11" x 27'
Product Fuel
CCR Title 23-2663
PASS FAIL
(b)
Tank has been cleaned so that no residue remains on the tank walls
X
(c)
(A) Determine that tank has been vacuum tested at a
X
vacuum of 5.3 inches of Hg for not less than one minute.
(13) Witness ultrasound test -average of 75% or
X
greater of original thickness.
Visually checked the internal lining for discontinuity,
X
compression, tension cracking and corrosion.
Test for thickness and hardness of the lining in
X
accordance with nationally recognized industry codes.
Test the lining using an electrical resistance Holiday
X
Detector in accordance with nationally recognized
industry codes, Holidays located, repaired and re-tested
(d)
Tank is suitable for continued use for a minimum of five (5) years
X
(e)
Tank is suitable for continued use for a minimum of five (5) years
ONLY if it is relined, or other improvements are made.
(f)
The tank lining is no longer suitable for continued use and shall be
closed in accordance with Article 7.
Coating Inspector Thomas M. Allen, III
Professional Engineer Robert Paul P.E. STAMP
Address 2243 Aspen Mirror Way S ite 204 Laughlin, NV 89029
Signature:
Registered Professional Engineer No. Corrosion 111
Expiration Date: 3/31/2014
T p,
No. 111
1; ba
To: Sessions
SPECIAL INSPECTION REPORT
Site: Mesa Marin Chevron Food Mart Date: March 7,2012
Address: 11101 Highway 178 Bakersfield, CA
The following results for the above location represent the conclusions of the Special Inspection which are
to be presented to the regulatory agency.
Tank No. 3- Southeast
Capacity 10,000 gallons
Dimensions 7'11" x 27'
Product Fuel
CCR Title 23 -2663
PASS FAIL
(b) Tank has been cleaned so that no residue remains on the tank walls
X
(c) (A) Determine that tank has been vacuum tested at a
X
vacuum of 5.3 inches of Hg for not less than one minute.
(B) Witness ultrasound test - average of 75% or
X
greater of original thickness.
Visually checked the internal lining for discontinuity,
X
compression, tension cracking and corrosion.
Test for thickness and hardness of the lining in
X
accordance with nationally recognized industry codes.
Test the lining using an electrical resistance Holiday
X
Detector in accordance with nationally recognized
industry codes, Holidays located, repaired and re- tested
(d) Tank is suitable for continued use for a minimum of five (5) years
X
(e) Tank is suitable for continued use for a minimum of five (5) years
ONLY if it is relined, or other improvements are made.
(f) The tank lining is no longer suitable for continued use and shall be
closed in accordance with Article 7.
Coating Inspector Thomas M. Allen, III
Professional Engineer Robert Paul P.E.
STAMP
Address 2243 Aspen Mirror Way Suite 204 Laughlin, NV 89029
Signature:
Registered Professional Engineer No. Corrosion 111
Expiration Date: 3/31/2014
`' i«
t No. vas
RRO
To: Sessions
SPECIAL INSPECTION REPORT
Site: Mesa Marin Chevron Food Mart Date: March 7,2012
Address: 11101 Highway 178 Bakersfield, CA
The following results for the above location represent the conclusions of the Special Inspection which are
to be presented to the regulatory agency.
Tank No. 4 -South
Capacity 10, 000 gallons
Dimensions 7'11" x 27'
Product Fuel
CCR Title 23 -2663
PASS FAIL
(b) Tank has been cleaned so that no residue remains on the tank walls
X
(c) (A) Determine that tank has been vacuum tested at a
X
vacuum of 5.3 inches of Hg for not less than one minute.
(B) Witness ultrasound test - average of 75% or
X
greater of original thickness.
Visually checked the internal lining for discontinuity,
X
compression, tension cracking and corrosion.
Test for thickness and hardness of the lining in
X
accordance with nationally recognized industry codes.
Test the lining using an electrical resistance Holiday
X
Detector in accordance with nationally recognized
industry codes, Holidays located, repaired and re- tested
(d) Tank is suitable for continued use for a minimum of five (5) years
X
(e) Tank is suitable for continued use for a minimum of five (5) years
ONLY if it is relined, or other improvements are made.
(f) The tank lining is no longer suitable for continued use and shall be
closed in accordance with Article 7.
Coating Inspector Thomas M. Allen, III
Professional Engineer Robert Paul F.E. STAMP
Address 2243 Aspen Mirror Way Suite 204 Laughlin, NV 89029
Signature:, �.
Registered Professional Engineer No. Corrosion 111
Expiration Date: 3131/2014