Loading...
HomeMy WebLinkAboutCP RESULTS 2012To: Sessions SPECIAL INSPECTION REPORT Site_ Mesa Marin Chevron Food Mart Date: March 7, 2012 Address: 11101 Highway 178 Bakersfield, CA The following results for the above location represent the conclusions of the Special Inspection, which are to be presented to the regulatory agency. Tank No_ 1 -North Capacity 10,000 gallons Dimensions 7'111" x 27' Product Fuel GCR Title 23 -2663 PASS FAIL (b) Tank has been cleaned so that no residue remains on the tank walls X (c) (A) Determine that tank has been vacuum tested at a X vacuum of 5.3 inches of Hg for not less than one minute. (B) Witness ultrasound test - average of 75% or X greater of original thickness. Visually checked the internal lining for discontinuity, X compression, tension cracking and corrosion. Test for thickness and hardness of the lining in X accordance with nationally recognized industry codes. Test the lining using an electrical resistance Holiday X Detector in accordance with nationally recognized industry codes, Holidays located, repaired and re- tested (d) Tank is suitable for continued use for a minimum of five (5) years X (e) Tank is suitable for continued use for a minimum of five (5) years ONLY if it is relined, or other improvements are made. (f) The tank lining is no longer suitable for continued use and shall be closed in accordance with Article 7. Coating Inspector Thomas M. Allen, III Professional Engineer Robert Paul P.E. STAMP Address 2243 Aspen Mirror Way Suite 204 Laughlin, NV 89029 Signature: Registered Professional Engineer No. Corrosion 111 Expiration Date: 3/31/2014 a.: L 0 ° '� To: Sessions SPECIAL INSPECTION REPORT Site: Mesa Marin Chevron Food Mart Date: March 7,2012 Address* 11101 Highway 178 Bakersfield, CA The following results for the above location represent the conclusions of the Special Inspection which are to be presented to the regulatory agency. Tank No. 2-Northwest Capacity 10,000 gallons Dimensions 7'11" x 27' Product Fuel CCR Title 23-2663 PASS FAIL (b) Tank has been cleaned so that no residue remains on the tank walls X (c) (A) Determine that tank has been vacuum tested at a X vacuum of 5.3 inches of Hg for not less than one minute. (13) Witness ultrasound test -average of 75% or X greater of original thickness. Visually checked the internal lining for discontinuity, X compression, tension cracking and corrosion. Test for thickness and hardness of the lining in X accordance with nationally recognized industry codes. Test the lining using an electrical resistance Holiday X Detector in accordance with nationally recognized industry codes, Holidays located, repaired and re-tested (d) Tank is suitable for continued use for a minimum of five (5) years X (e) Tank is suitable for continued use for a minimum of five (5) years ONLY if it is relined, or other improvements are made. (f) The tank lining is no longer suitable for continued use and shall be closed in accordance with Article 7. Coating Inspector Thomas M. Allen, III Professional Engineer Robert Paul P.E. STAMP Address 2243 Aspen Mirror Way S ite 204 Laughlin, NV 89029 Signature: Registered Professional Engineer No. Corrosion 111 Expiration Date: 3/31/2014 T p, No. 111 1; ba To: Sessions SPECIAL INSPECTION REPORT Site: Mesa Marin Chevron Food Mart Date: March 7,2012 Address: 11101 Highway 178 Bakersfield, CA The following results for the above location represent the conclusions of the Special Inspection which are to be presented to the regulatory agency. Tank No. 3- Southeast Capacity 10,000 gallons Dimensions 7'11" x 27' Product Fuel CCR Title 23 -2663 PASS FAIL (b) Tank has been cleaned so that no residue remains on the tank walls X (c) (A) Determine that tank has been vacuum tested at a X vacuum of 5.3 inches of Hg for not less than one minute. (B) Witness ultrasound test - average of 75% or X greater of original thickness. Visually checked the internal lining for discontinuity, X compression, tension cracking and corrosion. Test for thickness and hardness of the lining in X accordance with nationally recognized industry codes. Test the lining using an electrical resistance Holiday X Detector in accordance with nationally recognized industry codes, Holidays located, repaired and re- tested (d) Tank is suitable for continued use for a minimum of five (5) years X (e) Tank is suitable for continued use for a minimum of five (5) years ONLY if it is relined, or other improvements are made. (f) The tank lining is no longer suitable for continued use and shall be closed in accordance with Article 7. Coating Inspector Thomas M. Allen, III Professional Engineer Robert Paul P.E. STAMP Address 2243 Aspen Mirror Way Suite 204 Laughlin, NV 89029 Signature: Registered Professional Engineer No. Corrosion 111 Expiration Date: 3/31/2014 `' i« t No. vas RRO To: Sessions SPECIAL INSPECTION REPORT Site: Mesa Marin Chevron Food Mart Date: March 7,2012 Address: 11101 Highway 178 Bakersfield, CA The following results for the above location represent the conclusions of the Special Inspection which are to be presented to the regulatory agency. Tank No. 4 -South Capacity 10, 000 gallons Dimensions 7'11" x 27' Product Fuel CCR Title 23 -2663 PASS FAIL (b) Tank has been cleaned so that no residue remains on the tank walls X (c) (A) Determine that tank has been vacuum tested at a X vacuum of 5.3 inches of Hg for not less than one minute. (B) Witness ultrasound test - average of 75% or X greater of original thickness. Visually checked the internal lining for discontinuity, X compression, tension cracking and corrosion. Test for thickness and hardness of the lining in X accordance with nationally recognized industry codes. Test the lining using an electrical resistance Holiday X Detector in accordance with nationally recognized industry codes, Holidays located, repaired and re- tested (d) Tank is suitable for continued use for a minimum of five (5) years X (e) Tank is suitable for continued use for a minimum of five (5) years ONLY if it is relined, or other improvements are made. (f) The tank lining is no longer suitable for continued use and shall be closed in accordance with Article 7. Coating Inspector Thomas M. Allen, III Professional Engineer Robert Paul F.E. STAMP Address 2243 Aspen Mirror Way Suite 204 Laughlin, NV 89029 Signature:, �. Registered Professional Engineer No. Corrosion 111 Expiration Date: 3131/2014 rrl�� VY i lip 0 - )__